 "manufacturer": "Daikin",
 "manufacturer_slug": "daikin",
 "model": "intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects",
 "model_slug": "itm-bacnet-server-gateway-indoor",
 "aliases": [
  "DCM014A51",
  "iTM BACnet",
  "intelligent Touch Manager",
  "DCM601A71",
  "DCM601B71",
  "iTM BACnet Server Gateway"
 ],
 "equipment_type": "VRV BACnet gateway (iTM option)",
 "applies_to": "VRV and ductless indoor unit groups managed by a Daikin intelligent Touch Manager with the DCM014A51 BACnet server option.",
 "summary": "The DCM014A51 software option turns a Daikin intelligent Touch Manager into a BACnet IP server. The iTM acts as a BACnet virtual router: each indoor unit becomes its own virtual BACnet device carrying the same 37-object list, and a separate system control device holds schedule, auto-changeover, timed-override and forced-off objects. Objects can be enabled or disabled per unit during commissioning, so a site may expose fewer points than listed.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "notes": [
  "Each indoor unit is a separate virtual BACnet device behind the iTM's virtual router; instances 1-37 repeat on every indoor unit device.",
  "The last four points (BO 1, BO 2, MV 3, BO 4) live on the iTM system control device, not on indoor unit devices.",
  "Temperature units follow the iTM regional setting (Celsius or Fahrenheit).",
  "Commands that the indoor unit rejects are reverted by the iTM after about 10 minutes.",
  "Only the remote-controller group's designated unit (#0) should receive commands in a multi-unit group.",
  "Freeze Protection (BI 37) is only available on certain indoor unit models."
 ],
 "source": {
  "title": "intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide",
  "doc_number": "DG_DCM014A51_02-19",
  "revision_date": "2019-02",
  "url": "https://daikincomfort.com/docs/default-source/itm-bacnet-server-gateway-option/eg-itm_bacnetgatewayguide_v2-0.pdf"
 },
 "integration": {
  "summary": "Enable the DCM014A51 option on the iTM, assign each indoor unit a unique device ID and a BACnet network number for the virtual network, then use Occupancy Mode and the setpoint objects per indoor unit device. System-wide schedule, auto-changeover and forced-off objects sit on the separate system control device.",
  "minimum_points": [
   {
    "ref": "MO 1",
    "name": "Occupancy Mode",
    "why": "Occ/Unocc/Standby; sends on/off to the indoor unit"
   },
   {
    "ref": "MV 4",
    "name": "Operation Mode",
    "why": "Cool/Heat/Fan/Dry"
   },
   {
    "ref": "AV 6",
    "name": "Occ Cooling Setpoint",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "AV 7",
    "name": "Occ Heating Setpoint",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "MV 16",
    "name": "Fan Speed",
    "why": "Low / medium / high / auto"
   },
   {
    "ref": "BI 2",
    "name": "Unit On_Off Status",
    "why": "Actual on/off status"
   },
   {
    "ref": "AI 5",
    "name": "Room Temperature",
    "why": "Indoor unit room temperature, °F/°C"
   },
   {
    "ref": "BI 3",
    "name": "Alarm Status",
    "why": "Alarm; error code in the Description property"
   },
   {
    "ref": "BI 26",
    "name": "Communication Status",
    "why": "Communication alarm for the unit"
   }
  ],
  "enable": "Writing Occupancy Mode (MO 1) is the start/stop: Occ sends On, Unocc sends Off, Standby sends On with energy saving (setpoint offset by 3.6 F / 2 C). The iTM sends the command even if the unit is already in that state, and Occupancy Mode is set to 1 (Unocc) at iTM start-up. The 'Enable iTM Schedule Operation' object on the system control device turns the iTM's own schedule on or off.",
  "heartbeat": "No BMS heartbeat is described. If a written value is not accepted by the indoor unit, the iTM reverts the BACnet present value to the previous value after a 10-minute timer.",
  "remote_sensors": null,
  "setup": [
   "Recommended device IDs: 530000 for the system control device and 53PGGG for indoor units (P = port 1-8, GGG = DIII-Net group address, e.g. 531100).",
   "Virtual BACnet network number must be unique; default is 100.",
   "A virtual device's MAC address is the hex form of its device instance.",
   "Can be configured as a BACnet foreign device with a BBMD IP address and port when the BMS is on another subnet."
  ],
  "gotchas": [
   "In a multi-unit remote-controller group, only command the designated unit (#0); other units decide whether to follow.",
   "Commands from cool to heat (or back) are refused unless the unit is the changeover master.",
   "Objects can be disabled per unit during commissioning, so some points may be missing on site.",
   "Setpoint values are rounded to the object's significant digits; temperature units follow the iTM locale."
  ]
 },
 "points": [
  {
   "type": "MO",
   "instance": 1,
   "name": "Occupancy Mode",
   "description": "Occupancy mode",
   "units": "",
   "access": "C",
   "states": "1=Unocc, 2=Occ, 3=Standby"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Unit On_Off Status",
   "description": "Indoor unit on/off status",
   "units": "",
   "access": "R",
   "states": "Inactive=Off, Active=On"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Alarm Status",
   "description": "Alarm status; error code in Description property",
   "units": "",
   "access": "R",
   "states": "Inactive=Normal, Active=Alarm"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Operation Mode",
   "description": "Operation mode",
   "units": "",
   "access": "C",
   "states": "1=Cool, 2=Heat, 3=Fan, 4=Dry"
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Room Temperature",
   "description": "Room temperature",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Occ Cooling Setpoint",
   "description": "Occupied cooling setpoint",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Occ Heating Setpoint",
   "description": "Occupied heating setpoint",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Unocc Cooling Setpoint",
   "description": "Unoccupied (setback) cooling setpoint",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Unocc Heating Setpoint",
   "description": "Unoccupied (setback) heating setpoint",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Max Cooling Setpoint",
   "description": "Cooling setpoint upper limit",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Min Cooling Setpoint",
   "description": "Cooling setpoint lower limit",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Max Heating Setpoint",
   "description": "Heating setpoint upper limit",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Min Heating Setpoint",
   "description": "Heating setpoint lower limit",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Min Setpoint Differential (Cooling & Heating)",
   "description": "Minimum cool/heat setpoint differential",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Cooling & Heating Setpoint Tracking Mode",
   "description": "Cooling and heating setpoint tracking mode",
   "units": "",
   "access": "C",
   "states": "Inactive=Disable, Active=Enable"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "Fan Speed",
   "description": "Fan speed",
   "units": "",
   "access": "C",
   "states": "1=Low, 2=Reserved, 3=Medium, 4=Reserved, 5=High, 6=Reserved, 7=Reserved, 8=Auto"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "Airflow Direction",
   "description": "Airflow direction (louver position)",
   "units": "",
   "access": "C",
   "states": "1=P0, 2=P1, 3=P2, 4=P3, 5=P4, 6=Reserved, 7=Reserved, 8=P7"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Timed Override Operation",
   "description": "Timed override operation",
   "units": "",
   "access": "C",
   "states": "Inactive=Disable, Active=Enable"
  },
  {
   "type": "MI",
   "instance": 19,
   "name": "Current Unit Operation",
   "description": "Current unit operation",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Override, 4=Setback"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "Remote Controller Prohibit (On_Off)",
   "description": "Remote controller on/off permit/prohibit",
   "units": "",
   "access": "C",
   "states": "1=Permit, 2=Prohibit, 3=Stop Only"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Remote Controller Prohibit (Operation Mode)",
   "description": "Remote controller mode permit/prohibit",
   "units": "",
   "access": "C",
   "states": "Inactive=Permit, Active=Prohibit"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Remote Controller Prohibit (Setpoint)",
   "description": "Remote controller setpoint permit/prohibit",
   "units": "",
   "access": "C",
   "states": "Inactive=Permit, Active=Prohibit"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "Filter Sign Status",
   "description": "Filter sign status",
   "units": "",
   "access": "R",
   "states": "Inactive=Normal, Active=Alarm"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Filter Sign Reset",
   "description": "Filter sign reset",
   "units": "",
   "access": "C",
   "states": "Inactive=Reset, Active=Alarm"
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "Indoor Fan Status",
   "description": "Indoor fan status",
   "units": "",
   "access": "R",
   "states": "Inactive=Off, Active=On"
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "Communication Status",
   "description": "Communication status",
   "units": "",
   "access": "R",
   "states": "Inactive=Normal, Active=Alarm"
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "Thermo-on Status",
   "description": "Thermo-on status",
   "units": "",
   "access": "R",
   "states": "Inactive=Off, Active=On"
  },
  {
   "type": "MI",
   "instance": 28,
   "name": "Compressor Status",
   "description": "Compressor status",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=On, 3=Defrost/Hot Start"
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "Aux Heater Status",
   "description": "Auxiliary heater status",
   "units": "",
   "access": "R",
   "states": "Inactive=Off, Active=On"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Forced Thermo-off",
   "description": "Forced thermo-off",
   "units": "",
   "access": "C",
   "states": "Inactive=Disable, Active=Enable"
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "Indoor Unit Changeover Option",
   "description": "Changeover option available on this unit",
   "units": "",
   "access": "R",
   "states": "Inactive=Not Available, Active=Available"
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Return Air Temperature",
   "description": "Return air temperature",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Discharge Air Temperature",
   "description": "Discharge air temperature",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Liquid Pipe Temperature",
   "description": "Liquid pipe temperature",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Gas Pipe Temperature",
   "description": "Gas pipe temperature",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "EV Position",
   "description": "Electronic expansion valve position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Freeze Protection",
   "description": "Freeze protection (select FXEQ/FXFQ/FXTQ/FXUQ/FXSQ/CXTQ models)",
   "units": "",
   "access": "R",
   "states": "Inactive=Off, Active=On"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Enable iTM Schedule Operation",
   "description": "System control device: enable iTM schedule",
   "units": "",
   "access": "C",
   "states": "Inactive=Disable, Active=Enable"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Enable iTM Auto-Changeover Operation",
   "description": "System control device: enable auto-changeover",
   "units": "",
   "access": "C",
   "states": "Inactive=Disable, Active=Enable"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Timed Override Minutes",
   "description": "System control device: timed override duration",
   "units": "min",
   "access": "C",
   "states": "1=30, 2=60, 3=90, 4=120, 5=150, 6=180"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "System Forced Off",
   "description": "System control device: forced shutdown of all groups",
   "units": "",
   "access": "C",
   "states": "Inactive=Inactive, Active=Active"
  }
 ],
 "short_model": "iTM BACnet Gateway, Indoor Units",
 "page": "https://easybacnet.com/bacnet-points-lists/daikin/itm-bacnet-server-gateway-indoor",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}