Easy BACnet
  1. Home
  2. BACnet points lists
  3. Daikin
  4. Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)

Rooftop unit controller (light commercial packaged units and heat pumps) · BACnet points list

Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The iLINQ DDC controller on Daikin light commercial packaged units talks BACnet MS/TP (port J25 BMS2) or BACnet IP (Ethernet) without extra hardware. Its object list covers space, supply and outdoor conditions, refrigerant pressures, setpoints, blower and economizer settings, network sensor inputs, relay status, individual alarm flags and multistate schedule, mode and configuration objects.

This page lists 215 BACnet objects for the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) — 76 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)
Equipment
Rooftop unit controller (light commercial packaged units and heat pumps)
Equipment type
Heat pumps
BACnet objects
215 (76 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
15000
Also known as
iLINQ, Daikin iLINQ, BDG-ILINQA, iLINQ DDC controller
Source document
Daikin iLINQ BACnet Design Guide · BDG-ILINQA
Download CSV 215 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin’s current documentation and the live device before use. Not official Daikin information. Terms of use.

BMS integration notes: Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)

Integration in brief

Pick MS/TP or IP in the communication settings, set the instance ID (and MAC/baud for MS/TP) and set Update to Yes. Command occupancy by writing ScheduleSource (MV 0) and write OccCoolSP / OccHeatSP; read space and supply air temperature, HVAC mode, blower status and AlarmDO.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 0ScheduleSource3 = Force Occupied, 4 = Force Unoccupied from the BASWrite
AV 17OccCoolSPOccupied cooling setpoint, °FWrite
AV 18OccHeatSPOccupied heating setpoint, °FWrite
MV 2HVACMode_BacMsvCurrent HVAC modeRead
BV 6BlowerStage1Blower stage 1 relay on/offRead
AI 0SpaceTempSpace temperature, °FRead
AI 1SupplyAirTempSupply air temperature, °FRead
BV 20AlarmDOAny alarm activeRead

Enable & remote start

To schedule from the BAS, write 3 (Force Occupied) or 4 (Force Unoccupied) to ScheduleSource (MV 0); the onboard schedule and optimal start/stop are then ignored. If PushButtonOvrDuration (AV 79) is above 0, the space sensor button or the Remote Start Stop input can still give a temporary override.

Sensors & values from the BMS

Space temperature, space humidity, outdoor temperature, outdoor humidity and space CO2 can come from the BAS through AV 12-16 once each source is set to Network at the LCD or web interface (the source objects MV 9-13 are read-only over BACnet).

Network setup

Watch out for

Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

215 of 215 shown
Type
Multi-state
Access
Show
Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) BACnet Points List
DescriptionStates
AImin0SpaceTempSpace Temperature°FRead
AImin1SupplyAirTempSupply Air Temperature°FRead
AI2SlideAdjustConvCalculated Local Setpoint Adjust Value°FRead
AI3SpaceHumiditySpace Humidity%RHRead
AI4OutdoorAirTempOutdoor Air Temperature°FRead
AI5OutdoorAirHumOutdoor Air Humidity%RHRead
AI6EconomizerFeedbackEconomizer Damper Position Feedback%Read
AI7CO2Space CO2ppmRead
AI8HeadPres1Head Pressure for circuit 1psiRead
AI9HeadPres2Head Pressure for circuit 2psiRead
AI10SuctionPres1Suction Pressure for circuit 1psiRead
AI11SuctionPres2Suction Pressure for circuit 2psiRead
AV0EconDamperPosSetEconomizer Damper Position Command%Read
AV1OutdoorEnthalpyOutdoor EnthalpyBtu/lbRead
AV2SpaceEnthalpySpace EnthalpyBtu/lbRead
AV3ReheatValvePosReheat Valve position Feedback From EVD%Read
AV4BlowerSpeedBlower Speed Command%Read
AV5SCRHeatSCR Heat Command%Read
AV6ActiveCoolingSPActive Space Temperature Cooling Setpoint°FRead
AV7ActiveHeatingSPActive Space Temperature Heating Setpoint°FRead
AV8ActiveSATSPActive Supply Air Temperature setpoint°FRead
AV9ActiveHumiditySPActive Space Humidity Setpoint%RHRead
AV10EffCoolingLoadEffective Cooling Load%Read
AV11EffHeatingLoadEffective Heating Load%Read
AV12SpaceTempNetworkSpace Temperature Network from the BAS°FWrite
AV13SpaceHumidityNetworkSpace Humidity Network from the BAS%RHWrite
AV14OutdoorAirHumNetworkOutdoor Air Humidity Network from the BAS%RHWrite
AV15OutdoorAirTempNetworkOutdoor Air Temperature Network from the BAS°FWrite
AV16CO2NetworkSpace CO2 value from the BASppmWrite
AVmin17OccCoolSPOccupied Space Temperature Cooling Setpoint°FWrite
AVmin18OccHeatSPOccupied Space Temperature Heating Setpoint°FWrite
AV19UnoccCoolOffsetUnoccupied Space Temperature Cooling Offset°FWrite
AV20UnoccHeatOffsetUnoccupied Space Temperature Heating Offset°FWrite
AV21SpaceHumBandSpace Humidity Control Band%RHWrite
AV22SpaceTempAlarmOffsetSpace Temperature Alarm Offset°FWrite
AV23SpaceHumAlarmOffsetSpace Humidity Alarm Offset%RHWrite
AV24SpaceHumSPOccupied Space Humidity Setpoint%RHWrite
AV25AuxHeatSpaceTempOffsetAuxiliary Heat Space Temperature Setpoint Offset°FWrite
AV26LoadShedOffsetTempLoad Shedding Space Temperature Setpoint Offset°FWrite
AV27LoadShedOffsetHumLoad shedding humidity setpoint offset%RHWrite
AV28SpaceHumUnoccOffsetSpace Humidity Unoccupied Setpoint Offset%RHWrite
AV29SlideAdjustOffsetMaximum Local Setpoint Adjust°FWrite
AV30CoolingBandSpace Temperature Cooling Proportional Control Band°FWrite
AV31MechCoolAlarmOffsetMechanical Cooling Failure Alarm Supply Temperature Offset°FWrite
AV32HeatingBandSpace Temperature Heating Proportional Control Band°FWrite
AV33MechHeatAlarmOffsetMechanical Heating Failure Alarm Supply Temperature Offset°FWrite
AV34LowSupplyAirAlarmSPLow Supply Air Temperature Alarm Setpoint°FWrite
AV35HighSupplyAirAlarmSPHigh Supply Air Temperature Alarm Setpoint°FWrite
AV36SupplyAirCoolSPSupply Air Temperature Cooling Cutoff Setpoint°FWrite
AV37SupplyAirHeatSPSupply Air Temperature Heating Cutoff Setpoint°FWrite
AV38DehumMinSATSPMinimum Supply Air Temperature Setpoint during dehumidification°FWrite
AV39DehumMaxSATSPMaximum Supply Air Temperature Setpoint during dehumidification°FWrite
AV40CoolingOALockoutCooling Outdoor Air Temperature Lockout°FWrite
AV41HeatingOALockoutHeating Outdoor Air Temperature Lockout°FWrite
AV42HeatPumpOALockoutHeat Pump Outdoor Air Temperature Lockout°FWrite
AV43OAEconFixedDrybulbEconomizer Outdoor Air Drybulb Temperature Enable Setpoint°FWrite
AV44OAEconFixedEnthalpyEconomizer Outdoor Air Enthalpy Enable SetpointBtu/lbWrite
AV45OAEconDiffDrybulbEconomizer Outdoor Air Drybulb Temperature Differential Setpoint°FWrite
AV46OAEconDiffEnthalpyEconomizer Outdoor Air Enthalpy Differential SetpointBtu/lbWrite
AV47CO2SPSpace CO2 SetpointppmWrite
AV48CO2BandSpace CO2 Control BandppmWrite
AV49CO2AlarmOffsetSpace CO2 Alarm OffsetppmWrite
AV50VentFanSpeedBlower Speed for Vent Mode%Write
AV51CoolLowFanSpeedBlower Speed for Cooling Stage 1%Write
AV52CoolHighFanSpeedBlower Speed for Cooling Stage 2%Write
AV53HeatLowFanSpeedBlower Speed for Heating Stage 1%Write
AV54HeatHighFanSpeedBlower Speed for Heating Stage 2%Write
AV55EconMinVentDCVMinimum Economizer position for vent mode when Demand Control Ventilation is active%Write
AV56EconMinCoolLowDCVMinimum Economizer position for Stage 1 Cooling when Demand Control Ventilation is%Write
AV57EconMinCoolHighDCVMinimum Economizer position for Stage 2 Cooling when Demand Control Ventilation is%Write
AV58EconMinHeatLowDCVMinimum Economizer position for Stage 1 Heating when Demand Control Ventilation is%Write
AV59EconMinHeatHighDCVMinimum Economizer position for Stage 2 Heating when Demand Control Ventilation is%Write
AV60EconMinVentMinimum Economizer position for vent mode%Write
AV61EconMinCoolLowMinimum Economizer position for Stage 1 Cooling%Write
AV62EconMinCoolHighMinimum Economizer position for Stage 2 Cooling%Write
AV63EconMinHeatLowMinimum Economizer position for Stage 1 Heating%Write
AV64EconMinHeatHighMinimum Economizer position for Stage 2 Heating%Write
AV65CompMinRunTimeCompressor Minimum Run TimeminWrite
AV66CompMinOffTimeCompressor Minimum Off TimeminWrite
AV67HeatMinRunTimeHeating Minimum Run TimeminWrite
AV68HeatMinOffTimeHeating Minimum Off TimeminWrite
AV69DehumMinRunTimeDehumidification Minimum Run TimeminWrite
AV70SpaceTempAlarmTimeDelaySpace Temperature Alarm Time DelayminWrite
AV71SpaceHumAlarmTimeDelaySpace Humidity Alarm time delayminWrite
AV72MechAlarmTimeDelayMechanical Cooling/Heating Alarm Time DelayminWrite
AV73MaxOptStartTimeMaximum Optimal Start TimeminWrite
AV74MaxOptStopTimeMaximum Optimal Stop TimeminWrite
AV75CO2AlarmTimeDelaySpace CO2 Alarm Time DelayminWrite
AV76DefrostIntervalDefrost Timer IntervalminWrite
AV77LeadLagRunTimeDifferentialLead Lag Runtime DifferentialhWrite
AV78UnitOccupiedStartDelayUnit Occupied Start DelaysWrite
AV79PushButtonOvrDurationPush Button Override Time DurationhWrite
AV80DirtyFilterTimeSetpointFilter Run Time Before AlarmhWrite
AV81SpaceTempCalOffsetSpace Temperature Calibration Offset°FWrite
AV82SpaceHumCalOffsetSpace Humidity Calibration Offset%RHWrite
AV83SupplyTempCalOffsetSupply Temperature Calibration Offset°FWrite
AV84OutdoorTempCalOffsetOutdoor Temperature Calibration Offset°FWrite
AV85OutdoorHumCalOffsetOutdoor Humidity Calibration Offset%RHWrite
AV86CO2CalOffsetSpace CO2 Calibration OffsetppmWrite
AV87UnitRunTImeUnit Calculated Run TimehRead
AV88C1RunTImeCompressor Calculated Run TimehRead
AV89C2RunTimeCompressor Calculated Run TimehRead
AV90C3RunTimeCompressor Calculated Run TimehRead
AV91C4RunTimeCompressor Calculated Run TimehRead
AV92FilterRunTImeFilter Calculated Run TimehRead
AV93SoftwareRev_BacAvBACnet AV Mirror: Software RevisionRead
AV94NoOfCompressors_BacAvBACnet AV Mirror: Number of installed compressorsRead
AV95NumOfFurnaces_BacAvBACnet AV Mirror: Number of Installed FurnacesRead
AV96NumAuxiliaryStages_BacAvBACnet AV Mirror: Number of Auxiliary Heat StagesRead
AV97NumSuctionPresSensors_BacAvBACnet AV Mirror: Number of Suction Pressure sensors installedRead
AV98NumHeadPresSensors_BacAvBACnet AV Mirror: Number of Head Pressure sensors installedRead
AV99NumCoolingStages_BacAvBACnet AV Mirror: Number of Cooling StagesRead
AV100NumHeatingStages_BacAvBACnet AV Mirror: Number of Heating StagesRead
BI0EmergencyShutdownEmergency Shutdown Input StatusRead
BI1BlowerProvingSwBlower Proving Switch StatusRead
BI2CompPresSw1Compressor 1 Pressure Switch StatusRead
BI3CompPresSw2Compressor 2 Pressure Switch StatusRead
BI4CompPresSw3Compressor 3 Pressure Switch StatusRead
BI5CompPresSw4Compressor 4 Pressure Switch StatusRead
BI6DefrostSwitch1Defrost Switch status for circuit 1Read
BI7DefrostSwitch2Defrost Switch status for circuit 2Read
BI8RemoteStartStopRemote Occupancy Input StatusRead
BI9LoadSheddingLoad Shedding Input StatusRead
BI10DirtyFilterSwDirty Filter Switch StatusRead
BI11IICFeedback1IIC Furnace Board 2 FeedbackRead
BI12IICFeedback2IIC Furnace Board 1 FeedbackRead
BI13Tstat_GG Status for Thermostat modeRead
BI14Tstat_Y1Y1 Status for Thermostat modeRead
BI15Tstat_Y2Y2 Status for Thermostat modeRead
BI16Tstat_W1W1 Status for Thermostat modeRead
BI17Tstat_W2W2 Status for Thermostat modeRead
BI18Tstat_OO Status for Thermostat modeRead
BV0CoolingLockoutCooling LockoutRead
BV1HeatLockoutHeating LockoutRead
BV2HeatPumpHeatLockoutHeat Pump Heating LockoutRead
BV3EconomizerEnableEconomizer Enable StatusRead
BV4DefrostEnabledDefrost EnabledRead
BV5DehumLockoutDehumidification LockoutRead
BVmin6BlowerStage1Blower Stage 1 Relay StatusRead
BV7BlowerStage2Blower Stage 2 Relay StatusRead
BV8HeatStage1Heat Stage 1 Relay StatusRead
BV9HeatStage2Heat Stage 2 Relay StatusRead
BV10RevValve1Reversing Valve 1 Relay StatusRead
BV11RevValve2Reversing Valve 2 Relay StatusRead
BV12ExhaustFanEnaExhaust Fan Relay StatusRead
BV13Compressor1Compressor 1 Relay StatusRead
BV14Compressor2Compressor 2 Relay StatusRead
BV15Compressor3Compressor 3 Relay StatusRead
BV16Compressor4Compressor 4 Relay StatusRead
BV17CondFan1Condenser Fan 1 Relay StatusRead
BV18CondFan2Condenser Fan 2 Relay StatusRead
BV19ReheatPurgeValveReheat purge valve status (False = open, True = closed)Read
BVmin20AlarmDOAlarm Digital OutputRead
BV21SCRHeatInstalledSCR Heater Kit is installedRead
BV22FanCyclingFan CyclingRead
BV23ReheatInstalledModulating Hot Gas Reheat is installedRead
BV24ExhaustFanInstalledExhaust Fan is installedRead
BV25LeadLagEnableLead Lag is enabledRead
BV26AutoDefrostIntervalEnable Auto Defrost Interval CalculationRead
BV27Al_retain.ActiveRetained Variable alarmRead
BV28Al_Err_retain_write.ActiveWrite Retained Variable alarmRead
BV29Al_HighSupplyAirTemp.ActiveHigh Supply Air Temperature alarmRead
BV30Al_Blower.ActiveBlower Alarm alarmRead
BV31Al_EmergencyShutdown.ActiveEmergency Shutdown alarmRead
BV32Al_CompPresSW1.ActiveCompressor Pressure Switch 1 alarmRead
BV33Al_CompPresSW2.ActiveCompressor Pressure Switch 2 alarmRead
BV34Al_CompPresSW3.ActiveCompressor Pressure Switch 3 alarmRead
BV35Al_CompPresSW4.ActiveCompressor Pressure Switch 4 alarmRead
BV36Al_DirtyFilter.ActiveDirty Filter alarmRead
BV37Al_LowSupplyAirTemp.ActiveLow Supply Air Temperature alarmRead
BV38Al_HighSpaceHumidity.ActiveHigh Space Air Humidity alarmRead
BV39Al_MechanicalCooling.ActiveMechanical Cooling Failure alarmRead
BV40Al_MechanicalHeating.ActiveMechanical Heating Failure alarmRead
BV41Al_SpaceTemperature.ActiveSpace Temperature Alarm alarmRead
BV42Al_SpaceTempSensorMissing.ActiveSpace Temperature Sensor Missing alarmRead
BV43Al_SupplyAirTempSensorMissing.ActiveSupply Air Temperature Sensor Missing alarmRead
BV44Al_OutdoorAirTempSensorMissing.ActiveOutdoor Air Temperature Sensor Missing alarmRead
BV45Al_OutdoorAirHumSensorMissing.ActiveOutdoor Air Humidity Sensor Missing alarmRead
BV46Al_SpaceHumSensorMissing.ActiveSpace Humidity Sensor Missing alarmRead
BV47Al_HighCO2.ActiveHigh CO2 alarmRead
BV48Al_CO2SensorMissing.ActiveCO2 Sensor Missing alarmRead
BV49Al_EconFeedbackMissing.ActiveEconomizer Feedback Missing alarmRead
BV50Al_EconHighSupplyTemp.ActiveEconomizer High Supply Air Temperature alarmRead
BV51Al_EconDamperOpenAlarm.ActiveEconomizer Not Modulating Open alarmRead
BV52Al_EconDamperClosedAlarm.ActiveEconomizer Not Modulating Closed alarmRead
BV53Al_HeadPres1SensorMissing.ActiveMissing Head Pressure 1 Sensor alarmRead
BV54Al_HeadPres2SensorMissing.ActiveMissing Head Pressure 2 Sensor alarmRead
BV55Al_LowSuctionPres1.ActiveLow Suction Pressure 1 alarmRead
BV56Al_SuctionPres1SensorMissing.ActiveSuction Pressure 1 Sensor Missing alarmRead
BV57Al_LowSuctionPres2.ActiveLow Suction Pressure 2 alarmRead
BV58Al_SuctionPres2SensorMissing.ActiveSuction Pressure 2 Sensor Missing alarmRead
BV59Al_Batt_EVD_1.ActiveEVD Battery discharge alarmRead
BV60Al_EEPROM_EVD_1.ActiveEVD EEPROM Alarm alarmRead
BV61Al_IncompleteClosing_EVD_1.ActiveEVD Incomplete closing alarmRead
BV62Al_EmergencyClosing_EVD_1.ActiveEVD Emergency closing alarmRead
BV63Al_FW_CompatibErr_EVD_1.ActiveEVD Firmware not compatible alarmRead
BV64Al_ConfigErr_EVD_1.ActiveEVD Configuration Error alarmRead
BV65Al_EVD_Offline.ActiveEVD Offline alarmRead
BV66Al_IIC1Alarm.ActiveFurnace Board 1 Feedback Alarm alarmRead
BV67Al_IIC2Alarm.ActiveFurnace Board 2 Feedback Alarm alarmRead
BV68Al_DefrostFailed.ActiveDefrost Cycle Incomplete Alarm alarmRead
MVmin0ScheduleSourceSchedule sourceWrite1=Onboard, 2=Remote Start Stop Only, 3=Force Occupied, 4=Force Unoccupied
MV1ScheduleMode_BacMsvSchedule mode statusRead1=Unoccupied, 2=Occupied, 3=Push Button Override, 4=Holiday Unoccupied, 5=Holiday Occupied, 6=Force Unoccupied, 7=Force Occupied, 8=TSTAT, 9=Optimized Start, 10=Optimized Stop
MVmin2HVACMode_BacMsvHVAC mode statusRead1=Off, 2=Vent, 3=Cooling, 4=Econ Cooling, 5=Heating, 6=Dehumidification, 7=Force
MV3LeadCompressor_BacMsvLead compressor statusRead1=Compressor 1, 2=Compressor 2, 3=Compressors 1&2, 4=Compressors 3&4
MV4UnitConfig_BacMsvUnit configurationRead1=AC/Electric Heat, 2=AC/Gas Heat, 3=Heat Pump
MV5FanType_BacMsvFan type configurationRead1=Single Speed, 2=Two Speed, 3=Variable Speed
MV6EconConfig_BacMsvEconomizer type configurationRead1=None, 2=Installed, 3=Installed With CO2
MV7EconEnableSource_BacMsvEconomizer enable source settingRead1=None, 2=Fixed Drybulb, 3=Differential Drybulb, 4=Fixed Enthalpy, 5=Differential Enthalpy
MV8ControlMode_BacMsvControl mode setting (DDC or thermostat)Read1=DDC, 2=TSTAT
MV9SpaceTempSource_BacMsvSpace temperature sourceRead1=Onboard IO, 2=Network
MV10SpaceHumSource_BacMsvSpace humidity sourceRead1=Onboard IO, 2=Network
MV11OutdoorAirTempSource_BacMsvOutdoor air temperature sourceRead1=Onboard IO, 2=Network
MV12OutdoorAirHumSource_BacMsvOutdoor air humidity sourceRead1=Onboard IO, 2=Network
MV13CO2Source_BacMsvSpace CO2 sourceRead1=Onboard IO, 2=Network
Object ID lookup: Daikin Daikin iLINQ Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)

How many BACnet points does the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) have?

This list has 215 BACnet objects: 12 analog inputs, 101 analog values, 19 binary inputs, 69 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) BACnet points are writable?

76 of the 215 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP) BACnet documentation?

The source is Daikin iLINQ BACnet Design Guide (BDG-ILINQA), published free by Daikin at https://daikincomfort.com/docs/default-source/daikin-ilinq-controller/bdg-ilinq.pdf.

What are the minimum BACnet points to integrate the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)?

Start with MV 0 ScheduleSource (3 = Force Occupied, 4 = Force Unoccupied from the BAS); AV 17 OccCoolSP (Occupied cooling setpoint, °F); AV 18 OccHeatSP (Occupied heating setpoint, °F); MV 2 HVACMode_BacMsv (Current HVAC mode); BV 6 BlowerStage1 (Blower stage 1 relay on/off); AI 0 SpaceTemp (Space temperature, °F); AI 1 SupplyAirTemp (Supply air temperature, °F); BV 20 AlarmDO (Any alarm active).

How do I enable BMS control of the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)?

To schedule from the BAS, write 3 (Force Occupied) or 4 (Force Unoccupied) to ScheduleSource (MV 0); the onboard schedule and optimal start/stop are then ignored. If PushButtonOvrDuration (AV 79) is above 0, the space sensor button or the Remote Start Stop input can still give a temporary override.

Can the BMS supply sensor values to the Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)?

Space temperature, space humidity, outdoor temperature, outdoor humidity and space CO2 can come from the BAS through AV 12-16 once each source is set to Network at the LCD or web interface (the source objects MV 9-13 are read-only over BACnet).

How do I check these points on the real Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: Daikin iLINQ BACnet Design Guide · BDG-ILINQA. Object names, instances and units are reproduced as published; descriptions are our own.