Split / VRF indoor unit BACnet interface · BACnet points list
Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet points list
Updated 4 November 2026
The DKN Plus Interface is a Wi-Fi controller that wires to a single Daikin indoor unit (P1P2 or S21 connection) and also acts as a BACnet MS/TP slave on its RS-485 port. It exposes 12 objects: on/off, setpoint, room and return temperature, mode, fan speed, louvers and error status. The manual carries Airzone branding and its PICS names the vendor as ALTRA S.L.; the BACnet address is set from the DKN Cloud NA app.
This page lists 12 BACnet objects for the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.
- Manufacturer
- Daikin
- Model
- DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)
- Equipment
- Split / VRF indoor unit BACnet interface
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 12 (6 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application 4.01 (BI 2 and BO 0 need 4.03 or later)
- Also known as
- AZAI6WSPDKC, DKN Plus, DKN Cloud NA, DKN Wi-Fi controller, Daikin DKN Plus BACnet
Reference only, provided as-is: verify against Daikin’s current documentation and the live device before use. Not official Daikin information. Terms of use.
BMS integration notes: Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)
Give the interface its MS/TP address from the DKN Cloud NA app, then write On/Off (BV 0), Modes (MV 0), Setpoint (AV 0) and Speeds (MV 1). Read Localtemp and the IU communication and error objects for status. Ignore any object whose Out_Of_Service is TRUE.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | On/Off | Indoor unit on/off (1 = on) | Write |
| MV 0 | Modes | Operating mode; codes differ in the manual | Write |
| AV 0 | Setpoint | Indoor unit setpoint | Write |
| MV 1 | Speeds | Fan speed: 0 auto, 1-3 speed | Write |
| AV 1 | Localtemp | Room temperature | Write |
| BI 0 | IU communication | 0 = no communication with indoor unit | Read |
| BI 1 | IU error | Indoor unit error active | Read |
| CSV 1 | Errors | Indoor unit error code | Read |
Sensors & values from the BMS
On a P1P2 connection the BMS can write the room temperature to Localtemp (AV 1); on S21 it is read only and equals the return temperature.
Network setup
- The MS/TP slave address is entered in the DKN Cloud NA app (Configure Units > Communication protocol > BACnet).
- RS-485 port: 300 to 115200 bps, 8 data bits, even parity, 1 stop bit.
Watch out for
- Mode codes in the object list and the detailed description do not match; verify by reading MV 0 while changing mode at the unit.
- Objects not supported by the connected unit stay Out_Of_Service; their values are invalid.
Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | On/Off | Indoor unit on/off | Write | 0 = Off, 1 = On | |
| BImin | 0 | IU communication | Indoor unit communication status | Read | 0 = No communication, 1 = IU ready | |
| BImin | 1 | IU error | Indoor unit error flag | Read | 0 = No error, 1 = IU with error | |
| BI | 2 | Digital Input | Digital input state (firmware 4.03+) | Read | 0 = Inactive, 1 = Active | |
| BO | 0 | Auxiliary Heat | Auxiliary heat state (firmware 4.03+) | Read | 0 = Inactive, 1 = Active | |
| AVmin | 0 | Setpoint | Indoor unit setpoint | Write | ||
| AVmin | 1 | Localtemp | Room temperature; writable only on a P1P2 connection | Write | ||
| AI | 0 | Return temperature | Indoor unit return air sensor | Read | ||
| MVmin | 0 | Modes | Operating mode | Write | 1 = Auto, 2 = Cooling, 3 = Heating, 4 = Fan, 5 = Dry | |
| MVmin | 1 | Speeds | Indoor unit fan speed | Write | 0 = Automatic, 1 = Speed 1, 2 = Speed 2, 3 = Speed 3 | |
| MV | 2 | Louvers | Louver position | Write | 1-9 = Position, 10 = Swing | |
| CSVmin | 1 | Errors | Indoor unit error code | Read |
No points match these filters.
Object ID lookup: Daikin DKN Plus Interface point IDs by name
Integration notes
- Object availability depends on the connected unit; an object whose Out_Of_Service is TRUE is not present on that system and its value is not valid.
- The object list gives Modes (MV 0) as 1 Auto, 2 Cooling, 3 Heating, 4 Fan, 5 Dry, but the detailed description lists 0 Stop, 2 Cooling, 3 Heating, 4 Dry, 6 Ventilation. Check on site.
- The object list marks Speeds (MV 1) R/W, while the detailed description calls fan speed read only.
- Localtemp (AV 1) is writable only on a P1P2 connection; on S21 it equals the return temperature.
- Temperature units are not stated in the object list.
- The PICS in the same document names the product 'DZK Plus Interface' and the vendor ALTRA S.L.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)
How many BACnet points does the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) have?
This list has 12 BACnet objects: 1 analog input, 2 analog values, 3 binary inputs, 1 binary output, 1 binary value, 3 multi-state values, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet points are writable?
6 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet documentation?
The source is DKN Plus Interface AZAI6WSPDKC Integration manual (BACnet) (AZAI6WSPDKC), revision 2021-02 (PICS date), published free by Daikin at https://daikincomfort.com/docs/default-source/dkn-plus-interface/om-om_bacnet_azai6wspdkc_10202.pdf.
What are the minimum BACnet points to integrate the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?
Start with BV 0 On/Off (Indoor unit on/off (1 = on)); MV 0 Modes (Operating mode; codes differ in the manual); AV 0 Setpoint (Indoor unit setpoint); MV 1 Speeds (Fan speed: 0 auto, 1-3 speed); AV 1 Localtemp (Room temperature); BI 0 IU communication (0 = no communication with indoor unit); BI 1 IU error (Indoor unit error active); CSV 1 Errors (Indoor unit error code).
Can the BMS supply sensor values to the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?
On a P1P2 connection the BMS can write the room temperature to Localtemp (AV 1); on S21 it is read only and equals the return temperature.
How do I check these points on the real DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin BACnet points lists
- Networked room thermostat
Daikin AppStat BACnet Thermostat (DAPPS)
Daikin light commercial rooftop units and heat pumps controlled by the BACnet AppStat thermostat.
Also known as: DAPPS, AppStat, BACnet AppStat, Daikin BACnet thermostat, 250803, DG-DAPPS - Rooftop unit controller (light commercial packaged units and heat pumps)
Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)
Daikin light commercial packaged rooftop units (AC with electric or gas heat, or heat pump) fitted with the iLINQ DDC controller.
Also known as: iLINQ, Daikin iLINQ, BDG-ILINQA, iLINQ DDC controller - VRV BACnet gateway
Daikin DMS502B71 Interface for use in BACnet
Daikin VRV and ductless indoor units and ERV (VAM) units on up to four DIII-Net lines (256 groups).
Also known as: DMS502B71, DAM411B51, D-BACS, Daikin VRV BACnet interface, BACnet Interface, EDUS72-749 - Zoning system / zone thermostat BACnet interface
Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
Daikin Zoning Kit (DZK) systems on a Daikin indoor unit (the manual's layouts show VRV), with objects for up to six zones, through the DZK BACnet interface board.
Also known as: DZK-BACNET-HUB4, DZK-4, Daikin Zoning Kit BACnet, DZK BACnet Interface - VRV BACnet gateway (iTM option)
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects
VRV and ductless indoor unit groups managed by a Daikin intelligent Touch Manager with the DCM014A51 BACnet server option.
Also known as: DCM014A51, iTM BACnet, intelligent Touch Manager, DCM601A71, DCM601B71, iTM BACnet Server Gateway - VRV BACnet gateway (iTM option)
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects
VRV outdoor units (main, sub-1 and sub-2 modules) monitored through an iTM with the DCM014A51 BACnet server option.
Also known as: DCM014A51, iTM BACnet outdoor unit, intelligent Touch Manager, DCM601A71, DCM601B71
Source: DKN Plus Interface AZAI6WSPDKC Integration manual (BACnet) · AZAI6WSPDKC · rev. 2021-02 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.