Split / VRF indoor unit BACnet interface · BACnet points list

Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The DKN Plus Interface is a Wi-Fi controller that wires to a single Daikin indoor unit (P1P2 or S21 connection) and also acts as a BACnet MS/TP slave on its RS-485 port. It exposes 12 objects: on/off, setpoint, room and return temperature, mode, fan speed, louvers and error status. The manual carries Airzone branding and its PICS names the vendor as ALTRA S.L.; the BACnet address is set from the DKN Cloud NA app.

This page lists 12 BACnet objects for the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)
Equipment
Split / VRF indoor unit BACnet interface
Equipment type
VRF & split air conditioners
BACnet objects
12 (6 writable)
Transport
BACnet MS/TP
Firmware
Application 4.01 (BI 2 and BO 0 need 4.03 or later)
Also known as
AZAI6WSPDKC, DKN Plus, DKN Cloud NA, DKN Wi-Fi controller, Daikin DKN Plus BACnet
Source document
DKN Plus Interface AZAI6WSPDKC Integration manual (BACnet) · AZAI6WSPDKC · rev. 2021-02 (PICS date)
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin’s current documentation and the live device before use. Not official Daikin information. Terms of use.

BMS integration notes: Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)

Integration in brief

Give the interface its MS/TP address from the DKN Cloud NA app, then write On/Off (BV 0), Modes (MV 0), Setpoint (AV 0) and Speeds (MV 1). Read Localtemp and the IU communication and error objects for status. Ignore any object whose Out_Of_Service is TRUE.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0On/OffIndoor unit on/off (1 = on)Write
MV 0ModesOperating mode; codes differ in the manualWrite
AV 0SetpointIndoor unit setpointWrite
MV 1SpeedsFan speed: 0 auto, 1-3 speedWrite
AV 1LocaltempRoom temperatureWrite
BI 0IU communication0 = no communication with indoor unitRead
BI 1IU errorIndoor unit error activeRead
CSV 1ErrorsIndoor unit error codeRead

Sensors & values from the BMS

On a P1P2 connection the BMS can write the room temperature to Localtemp (AV 1); on S21 it is read only and equals the return temperature.

Network setup

Watch out for

Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
Multi-stateOther
Access
Show
Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet Points List
DescriptionStates
BVmin0On/OffIndoor unit on/offWrite0 = Off, 1 = On
BImin0IU communicationIndoor unit communication statusRead0 = No communication, 1 = IU ready
BImin1IU errorIndoor unit error flagRead0 = No error, 1 = IU with error
BI2Digital InputDigital input state (firmware 4.03+)Read0 = Inactive, 1 = Active
BO0Auxiliary HeatAuxiliary heat state (firmware 4.03+)Read0 = Inactive, 1 = Active
AVmin0SetpointIndoor unit setpointWrite
AVmin1LocaltempRoom temperature; writable only on a P1P2 connectionWrite
AI0Return temperatureIndoor unit return air sensorRead
MVmin0ModesOperating modeWrite1 = Auto, 2 = Cooling, 3 = Heating, 4 = Fan, 5 = Dry
MVmin1SpeedsIndoor unit fan speedWrite0 = Automatic, 1 = Speed 1, 2 = Speed 2, 3 = Speed 3
MV2LouversLouver positionWrite1-9 = Position, 10 = Swing
CSVmin1ErrorsIndoor unit error codeRead
Object ID lookup: Daikin DKN Plus Interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)

How many BACnet points does the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) have?

This list has 12 BACnet objects: 1 analog input, 2 analog values, 3 binary inputs, 1 binary output, 1 binary value, 3 multi-state values, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet points are writable?

6 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP) BACnet documentation?

The source is DKN Plus Interface AZAI6WSPDKC Integration manual (BACnet) (AZAI6WSPDKC), revision 2021-02 (PICS date), published free by Daikin at https://daikincomfort.com/docs/default-source/dkn-plus-interface/om-om_bacnet_azai6wspdkc_10202.pdf.

What are the minimum BACnet points to integrate the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?

Start with BV 0 On/Off (Indoor unit on/off (1 = on)); MV 0 Modes (Operating mode; codes differ in the manual); AV 0 Setpoint (Indoor unit setpoint); MV 1 Speeds (Fan speed: 0 auto, 1-3 speed); AV 1 Localtemp (Room temperature); BI 0 IU communication (0 = no communication with indoor unit); BI 1 IU error (Indoor unit error active); CSV 1 Errors (Indoor unit error code).

Can the BMS supply sensor values to the Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?

On a P1P2 connection the BMS can write the room temperature to Localtemp (AV 1); on S21 it is read only and equals the return temperature.

How do I check these points on the real DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: DKN Plus Interface AZAI6WSPDKC Integration manual (BACnet) · AZAI6WSPDKC · rev. 2021-02 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.