 "manufacturer": "Daikin",
 "manufacturer_slug": "daikin",
 "model": "DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit",
 "model_slug": "dzk-bacnet-hub4-zoning-kit",
 "short_model": "DZK BACnet HUB4",
 "aliases": [
  "DZK-BACNET-HUB4",
  "DZK-4",
  "Daikin Zoning Kit BACnet",
  "DZK BACnet Interface"
 ],
 "equipment_type": "Zoning system / zone thermostat BACnet interface",
 "applies_to": "Daikin Zoning Kit (DZK) systems on a Daikin indoor unit (the manual's layouts show VRV), with objects for up to six zones, through the DZK BACnet interface board.",
 "summary": "The DZK BACnet Interface plugs onto the DZK main control board and exposes the zoning system on BACnet IP (Ethernet or Wi-Fi) or BACnet MS/TP. The object list is fixed for six zones: per-zone on/off, heat and cool setpoints, room temperature, humidity, demands and damper step, plus the system mode, user mode and indoor unit status. One interface is needed per DZK system.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 1000,
 "access_inferred": false,
 "notes": [
  "Objects for zones that do not exist report Out_Of_Service TRUE; only use values where Out_Of_Service is FALSE.",
  "Z1 local ventilation is printed 'Z1 Local Ventilation'; zones 2-6 use 'Local ventilation'.",
  "Temperature ranges are printed in both °F and °C; the unit follows the system setting.",
  "IU errors (MI 1): convert the value to hex 0xXY, row = X-1, column = Y, then look up the Daikin malfunction code table in the manual.",
  "The DZK error states are printed as display codes 1-3 mapping to errors 9, 10 and 11; the detailed text also lists 0 for normal operation.",
  "Values are refreshed every second; COV subscriptions are supported."
 ],
 "source": {
  "title": "DZK-4 Integration manual (DZK BACnet Interface)",
  "doc_number": null,
  "revision_date": "Rev. 1",
  "url": "https://daikincomfort.com/docs/default-source/dzk-zoning-kit/um-dzk-bacnet-hub4.pdf"
 },
 "integration": {
  "summary": "Set BACnet IP or MS/TP and the device ID in the configuration app, then use DZK operation mode (MO 0) and user mode (MO 1) for the system, and Zx ON/OFF plus the zone heat and cool setpoints per zone. Read zone temperatures, IU status, IU speed and the error objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MO 1",
    "name": "DZK user mode",
    "why": "1 stop, 2 comfort, 3 unoccupied, 5 eco, 6 vacation"
   },
   {
    "ref": "MO 0",
    "name": "DZK operation mode",
    "why": "1 auto, 2 cool, 3 heat, 4 dry, 5 emergency heat"
   },
   {
    "ref": "BV 3",
    "name": "Z1 ON/OFF",
    "why": "Zone 1 on/off (repeat for zones 2-6)"
   },
   {
    "ref": "AV 1",
    "name": "Z1 Heat Set point",
    "why": "Zone 1 heating setpoint"
   },
   {
    "ref": "AV 2",
    "name": "Z1 Cool Set point",
    "why": "Zone 1 cooling setpoint"
   },
   {
    "ref": "BI 0",
    "name": "IU Status ON/OFF",
    "why": "Indoor unit running"
   },
   {
    "ref": "AI 0",
    "name": "Z1 Room Temperature",
    "why": "Zone 1 room temperature"
   },
   {
    "ref": "MI 0",
    "name": "IU speed",
    "why": "Indoor unit fan step: low, medium, high"
   },
   {
    "ref": "MI 1",
    "name": "IU errors",
    "why": "Indoor unit error; hex value = Daikin code"
   },
   {
    "ref": "MI 2",
    "name": "DZK error",
    "why": "Zoning system error (bus, interface, P1P2)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP defaults: device ID 1000, UDP port 47808, DHCP (static default 192.168.0.100).",
   "BACnet MS/TP: MAC 0-127, device ID 0-4194302 and baud rate are set in the app; select the MS/TP integration port.",
   "One DZK BACnet interface per DZK control board."
  ],
  "gotchas": [
   "In VRV heat pump systems the operating mode of a DZK on a slave indoor unit can be limited by the master indoor unit's mode.",
   "The DZK address and group address (AV 13, 14) are learned at indoor unit start-up; if the DZK powers up after the indoor unit they may need a refresh from the controller.",
   "IU Set Point (AV 0) is calculated by the zoning system and is read only; change the zone setpoints instead."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "IU Status ON/OFF",
   "description": "Indoor unit on/off status",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DZK system input alarm",
   "description": "System alarm input",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "DZK Global Fan",
   "description": "Global ventilation status",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "DZK Aux Heat1",
   "description": "Auxiliary heat stage 1 status",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "DZK Aux Heat2",
   "description": "Auxiliary heat stage 2 status",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Z1 ON/OFF",
   "description": "Zone 1 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Z1 Local Ventilation",
   "description": "Zone 1 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Z1 Vacation override",
   "description": "Zone 1 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Z1 Unoccupied override",
   "description": "Zone 1 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Z2 ON/OFF",
   "description": "Zone 2 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Z2 Local ventilation",
   "description": "Zone 2 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Z2 Vacation override",
   "description": "Zone 2 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Z2 Unoccupied override",
   "description": "Zone 2 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Z3 ON/OFF",
   "description": "Zone 3 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Z3 Local ventilation",
   "description": "Zone 3 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Z3 Vacation override",
   "description": "Zone 3 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Z3 Unoccupied override",
   "description": "Zone 3 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Z4 ON/OFF",
   "description": "Zone 4 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Z4 Local ventilation",
   "description": "Zone 4 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Z4 Vacation override",
   "description": "Zone 4 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Z4 Unoccupied override",
   "description": "Zone 4 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Z5 ON/OFF",
   "description": "Zone 5 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Z5 Local ventilation",
   "description": "Zone 5 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Z5 Vacation override",
   "description": "Zone 5 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Z5 Unoccupied override",
   "description": "Zone 5 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Z6 ON/OFF",
   "description": "Zone 6 on/off",
   "units": "",
   "access": "W",
   "states": "0 = Off, 1 = On"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Z6 Local ventilation",
   "description": "Zone 6 local ventilation enable",
   "units": "",
   "access": "W",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Z6 Vacation override",
   "description": "Zone 6 vacation override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Disable, 1 = Enable"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Z6 Unoccupied override",
   "description": "Zone 6 unoccupied override timer active",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "DZK/BACnet Interface communication error",
   "description": "Interface lost contact with DZK control board",
   "units": "",
   "access": "R",
   "states": "0 = Deactivated, 1 = Activated"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "Z1 Room Temperature",
   "description": "Zone 1 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Z2 Room Temperature",
   "description": "Zone 2 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Z3 Room Temperature",
   "description": "Zone 3 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Z4 Room Temperature",
   "description": "Zone 4 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Z5 Room Temperature",
   "description": "Zone 5 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Z6 Room Temperature",
   "description": "Zone 6 room temperature, 50-95 °F (10-35 °C)",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "IU Set Point",
   "description": "Setpoint the zoning system sends to the indoor unit, 64-86 °F",
   "units": "°F/°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Z1 Heat Set point",
   "description": "Zone 1 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Z1 Cool Set point",
   "description": "Zone 1 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Z2 Heat Set point",
   "description": "Zone 2 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Z2 Cool Set point",
   "description": "Zone 2 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Z3 Heat Set point",
   "description": "Zone 3 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Z3 Cool Set point",
   "description": "Zone 3 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Z4 Heat Set point",
   "description": "Zone 4 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Z4 Cool Set point",
   "description": "Zone 4 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Z5 Heat Set point",
   "description": "Zone 5 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Z5 Cool Set point",
   "description": "Zone 5 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Z6 Heat Set point",
   "description": "Zone 6 heating setpoint, 59-86 °F (15-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Z6 Cool Set point",
   "description": "Zone 6 cooling setpoint, 64-86 °F (18-30 °C)",
   "units": "°F/°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "DZK address (DK AirNet address)",
   "description": "Indoor unit DIII AirNet address, 0-255",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "DZK group address (DK group address)",
   "description": "Indoor unit group address, 0-255",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Z1 cooling demand (%)",
   "description": "Zone 1 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Z1 heating demand (%)",
   "description": "Zone 1 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Z1 aux heating demand (%)",
   "description": "Zone 1 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Z2 cooling demand (%)",
   "description": "Zone 2 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Z2 heating demand (%)",
   "description": "Zone 2 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Z2 aux heating demand (%)",
   "description": "Zone 2 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Z3 cooling demand (%)",
   "description": "Zone 3 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Z3 heating demand (%)",
   "description": "Zone 3 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Z3 aux heating demand (%)",
   "description": "Zone 3 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Z4 cooling demand (%)",
   "description": "Zone 4 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Z4 heating demand (%)",
   "description": "Zone 4 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Z4 aux heating demand (%)",
   "description": "Zone 4 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Z5 cooling demand (%)",
   "description": "Zone 5 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Z5 heating demand (%)",
   "description": "Zone 5 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Z5 aux heating demand (%)",
   "description": "Zone 5 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Z6 cooling demand (%)",
   "description": "Zone 6 cooling demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Z6 heating demand (%)",
   "description": "Zone 6 heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Z6 aux heating demand (%)",
   "description": "Zone 6 auxiliary heating demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Z1 humidity",
   "description": "Zone 1 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Z2 humidity",
   "description": "Zone 2 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Z3 humidity",
   "description": "Zone 3 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Z4 humidity",
   "description": "Zone 4 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Z5 humidity",
   "description": "Zone 5 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Z6 humidity",
   "description": "Zone 6 relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "IU speed",
   "description": "Indoor unit fan speed step",
   "units": "",
   "access": "R",
   "states": "1 = Speed Low, 2 = Speed Medium, 3 = Speed High (number of speeds depends on IU model)"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "IU errors",
   "description": "Indoor unit error; value in hex gives the Daikin malfunction code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "DZK error",
   "description": "Zoning system error",
   "units": "",
   "access": "R",
   "states": "1 = Error 9: DZK internal bus fault, 2 = Error 10: BACnet interface board fault, 3 = Error 11: P1P2 communication error"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "DZK operation mode",
   "description": "System operating mode",
   "units": "",
   "access": "W",
   "states": "1 = Auto, 2 = Cold, 3 = Heat, 4 = Dry, 5 = Emergency heat"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "DZK user mode",
   "description": "System user mode",
   "units": "",
   "access": "W",
   "states": "1 = Stop, 2 = Comfort, 3 = Unoccupied, 4 = Night time, 5 = Eco, 6 = Vacation"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Z1 opening step damper",
   "description": "Zone 1 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Z2 opening step damper",
   "description": "Zone 2 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Z3 opening step damper",
   "description": "Zone 3 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Z4 opening step damper",
   "description": "Zone 4 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Z5 opening step damper",
   "description": "Zone 5 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Z6 opening step damper",
   "description": "Zone 6 modulating damper step",
   "units": "",
   "access": "R",
   "states": "1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/daikin/dzk-bacnet-hub4-zoning-kit",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}