- FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
Variable frequency drive (BACnet/IP adapter module) · BACnet points list
ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) BACnet points list
Updated 4 November 2026
FBIP-21 is ABB's two-port Ethernet adapter that puts ACH480 and ACH580 HVAC drives on BACnet IP. On first boot it builds its object list from the drive, so not every object exists on every drive. The list resembles the drive's embedded MS/TP list (run/stop, references, I/O, PID loops, faults) and adds warning/fault enumerations, loop objects and hourly/daily energy values.
This page lists 119 BACnet objects for the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.
- Manufacturer
- ABB
- Model
- FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
- Equipment
- Variable frequency drive (BACnet/IP adapter module)
- Equipment type
- VFDs & pumps
- BACnet objects
- 119 (40 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 0
- Also known as
- FBIP-21, FBIP21, ACH580 BACnet/IP, ACH480 BACnet/IP, ACH580 E-Clipse BACnet IP, 3AXD50000028468
Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.
BMS integration notes: ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
Enable the adapter with 50.01 FBA A enable, set IP settings (51.04-51.13, DHCP by default), the device object ID (51.14/51.15) and comm-loss settings, then save with 96.07 and apply with 51.27. Point 20.01 Ext1 commands at Fieldbus A and 28.11 (or 22.11) at FB A ref1, then command BV 10 and AV 16.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10 | RUN-STOP-Command | Start/stop from the BMS | Command |
| AV 16 | Input-Reference-1 | Speed reference in % | Command |
| BV 14 | Fault-Reset-Command | Reset a tripped drive | Write |
| BV 0 | RUN-STOP-Monitor | Running status | Read |
| BV 4 | HAND-AUTO-Monitor | Shows if the panel has the drive in Hand | Read |
| AV 1 | Output-Freq | Output frequency in Hz | Read |
| AV 4 | Output-Current | Motor amps | Read |
| AV 6 | Output-Power | Drive power in kW | Read |
| BV 2 | OK-FAULT-Monitor | Any active drive fault | Read |
| MV 1 | Active-Fault-1 | Which fault is active | Read |
Enable & remote start
Set 20.01 Ext1 commands = Fieldbus A so BV 10 starts and stops the drive, and 28.11 Ext1 frequency ref1 = FB A ref1 (or the speed reference equivalent) for AV 16. BV 18 Control-Override-Command takes control from the normal source, but panel HAND mode still has priority.
Heartbeat & communication loss
51.20 Timeout time (default 300 = 30.0 s, 0 = off) and 51.21 Timeout mode (default Any packet; Control RW = only control/reference writes reset it) detect a lost master. 50.02 FBA A comm loss func sets the drive reaction and 50.03 FBA A comm loss t out the delay.
Sensors & values from the BMS
For the process PID, write AV 42 LOOP-Setpoint and AV 43 LOOP-Feedback from the BMS (with the drive PID sources set accordingly). AO 0/AO 1 and BO 0-5 drive outputs when the drive is configured for BACnet control.
Network setup
- 50.01 FBA A enable = Enable; 51.01 shows FBA type 47808 = BACnet.
- 51.04 IP configuration default DHCP; static IP via 51.05-51.13.
- Device object ID = 51.14 (0-9999) + 10000 x 51.15; default 0, so set it (valid 1-4194303).
- 51.18 BACnet/IP UDP port, default 47808.
- Save with 96.07 Parameter save manually and validate with 51.27 FBA A par refresh.
Watch out for
- Panel HAND mode beats BACnet control override (BV 18).
- BV 39 Parameter-Save-Command writes permanent memory; do not write it cyclically.
- Mailbox (AV 25/AV 26) addresses parameters as group x 1000 + index, e.g. 47001 for 47.01.
ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | AI1-Monitor | Analog input 1 level | % | Read | |
| AI | 1 | AI2-Monitor | Analog input 2 level | % | Read | |
| AO | 0 | AO1-command | Analog output 1 command (drive set for BACnet control) | % | Command | |
| AO | 1 | AO2-command | Analog output 2 command (drive set for BACnet control) | % | Command | |
| AV | 0 | Output-RPM | Motor speed | rpm | Read | |
| AVmin | 1 | Output-Freq | Output frequency | Hz | Read | |
| AV | 2 | DC-Voltage | DC bus voltage | V | Read | |
| AV | 3 | Output-Voltage | AC output voltage | V | Read | |
| AVmin | 4 | Output-Current | Drive output current | A | Read | |
| AV | 5 | Output-Torque | Motor torque, % of nominal | % | Read | |
| AVmin | 6 | Output-Power | Output power | kW | Read | |
| AV | 7 | Operating-Temp-Range | Heatsink temperature (unit printed as %) | % | Read | |
| AV | 8 | Kilowatt-Hour-Meter-R | Resettable energy counter | kWh | Read | |
| AV | 9 | Kilowatt-Hour-Meter-NR | Non-resettable energy counter | kWh | Read | |
| AV | 10 | Process-PID-Feedback | Process PID feedback | % | Read | |
| AV | 11 | Process-PID-Deviation | Process PID deviation | % | Read | |
| AV | 12 | External-PID-Feedback | External PID feedback | % | Read | |
| AV | 13 | External-PID-Deviation | External PID deviation | % | Read | |
| AV | 14 | Running-Hours | Resettable run time (write 0 to reset) | h | Read | |
| AV | 15 | Motor-Temp-Degrees-C | Motor temperature | °C | Read | |
| AVmin | 16 | Input-Reference-1 | Speed reference 1, -150..150 | % | Command | |
| AV | 17 | Input-Reference-2 | Speed reference 2, -150..150 | % | Command | |
| AV | 18 | Active-Fault | Active fault code | Read | ||
| AV | 19 | Previous-Fault-1 | Previous fault 1 | Read | ||
| AV | 20 | Previous-Fault-2 | Previous fault 2 | Read | ||
| AV | 21 | AO1-Monitor | Analog output 1 level | % | Read | |
| AV | 22 | AO2-Monitor | Analog output 2 level | % | Read | |
| AV | 23 | Accel-1-Seconds | Acceleration time 1 | s | Write | |
| AV | 24 | Decel-1-Seconds | Deceleration time 1 | s | Write | |
| AV | 25 | Mbox-Param | Parameter number for mailbox read/write (e.g. 47001 for 47.01) | Write | ||
| AV | 26 | Mbox-Data | Mailbox parameter value | Write | ||
| AV | 29 | Min-Speed | Minimum speed | Hz | Write | |
| AV | 30 | Max-Speed | Maximum speed | Hz | Write | |
| AV | 31 | Output-Speed | Actual motor speed, % | % | Read | |
| AV | 32 | Output-Current-Range | Actual motor current, % | % | Read | |
| AV | 33 | Max-Current | Maximum motor current | A | Write | |
| AV | 34 | DC-Ripple | DC bus ripple voltage | V | Read | |
| AV | 40 | LOOP-Feedback-Monitor | Loop controller feedback | % | Read | |
| AV | 41 | LOOP-Setpoint-Monitor | Loop setpoint monitor | % | Read | |
| AV | 42 | LOOP-Setpoint | Loop setpoint | % | Command | |
| AV | 43 | LOOP-Feedback | Loop feedback written by the BMS | % | Write | |
| AV | 44 | LOOP-Output | Loop output | % | Read | |
| AV | 45 | LOOP-Gain | Loop gain | Write | ||
| AV | 46 | LOOP-Integration-Time | Loop integration time | s | Write | |
| AV | 49 | LOOP-Deviation-Monitor | Loop controller deviation (access not printed) | % | Read | |
| AV | 53 | LOOP-1-Gain | Loop 1 gain | Write | ||
| AV | 54 | LOOP-1-Integration-Time | Loop 1 integration time | s | Write | |
| AV | 55 | LOOP-2-Feedback-Monitor | External loop feedback | % | Read | |
| AV | 56 | LOOP-2-Setpoint-Monitor | External loop setpoint | % | Read | |
| AV | 59 | LOOP-2-Output | External loop output | % | Read | |
| AV | 60 | LOOP-2-Gain | External loop gain | Write | ||
| AV | 61 | LOOP-2-Integration-Time | External loop integration time | s | Write | |
| AV | 64 | LOOP-2-Deviation-Monitor | External loop deviation | % | Read | |
| AV | 130 | Kilowatt-Hour-This-Hour | Energy this hour | kWh | Read | |
| AV | 131 | Kilowatt-Hour-Last-Hour | Energy last hour | kWh | Read | |
| AV | 132 | Kilowatt-Hour-This Day | Energy today | kWh | Read | |
| AV | 133 | Kilowatt-Hour-Last-Day | Energy yesterday | kWh | Read | |
| BI | 0 | RO1-Monitor | Relay output 1 status | Read | ON/OFF | |
| BI | 1 | RO2-Monitor | Relay output 2 status | Read | ON/OFF | |
| BI | 2 | RO3-Monitor | Relay output 3 status | Read | ON/OFF | |
| BI | 3 | RO4-Monitor | Relay output 4 status | Read | ON/OFF | |
| BI | 4 | RO5-Monitor | Relay output 5 status | Read | ON/OFF | |
| BI | 5 | DO1-Monitor | Digital output 1 status | Read | ON/OFF | |
| BI | 6 | DI1-Monitor | Digital input 1 status | Read | ON/OFF | |
| BI | 7 | DI2-Monitor | Digital input 2 status | Read | ON/OFF | |
| BI | 8 | DI3-Monitor | Digital input 3 status | Read | ON/OFF | |
| BI | 9 | DI4-Monitor | Digital input 4 status | Read | ON/OFF | |
| BI | 10 | DI5-Monitor | Digital input 5 status | Read | ON/OFF | |
| BI | 11 | DI6-Monitor | Digital input 6 status | Read | ON/OFF | |
| BO | 0 | RO1-Command | Relay 1 output command | Command | ON/OFF | |
| BO | 1 | RO2-Command | Relay 2 output command | Command | ON/OFF | |
| BO | 2 | RO3-Command | Relay 3 output command | Command | ON/OFF | |
| BO | 3 | RO4-Command | Relay 4 output command | Command | ON/OFF | |
| BO | 4 | RO5-Command | Relay 5 output command | Command | ON/OFF | |
| BO | 5 | DO1-Command | Digital output 1 command | Command | ON/OFF | |
| BVmin | 0 | RUN-STOP-Monitor | Drive run status | Read | RUN/STOP | |
| BV | 1 | Direction-Monitor | Rotation direction | Read | REVERSE/FORWARD | |
| BVmin | 2 | OK-FAULT-Monitor | Drive fault status | Read | FAULT/OK | |
| BV | 3 | EXT1-EXT2-Monitor | Active control source | Read | EXT2/EXT1 | |
| BVmin | 4 | HAND-AUTO-Monitor | Hand or Auto mode | Read | HAND/AUTO | |
| BV | 5 | Warning-Monitor | Warning status | Read | WARNING/OK | |
| BV | 7 | Ready-Monitor | Ready status | Read | READY/NOT-READY | |
| BV | 8 | At-Setpoint-Monitor | At setpoint | Read | YES/NO | |
| BV | 9 | Enabled-Monitor | Run enabled status | Read | ENABLE/DISABLE | |
| BVmin | 10 | RUN-STOP-Command | Start/stop command | Command | RUN/STOP | |
| BV | 11 | Direction-Command | Direction command | Command | REVERSE/FORWARD | |
| BV | 12 | Run-Permissive-Command | Run permissive command | Command | ENABLE/DISABLE | |
| BV | 13 | EXT1-EXT2-Command | Select EXT1 or EXT2 | Command | EXT2/EXT1 | |
| BVmin | 14 | Fault-Reset-Command | Fault reset | Write | RESET/NO | |
| BV | 17 | Lock-Parameters | Parameter lock status | Read | LOCK/UNLOCK | |
| BV | 18 | Control-Override-Command | BACnet control override | Command | ON/OFF | |
| BV | 19 | Control-Override-Monitor | Control override active | Read | ON/OFF | |
| BV | 20 | Start-Interlock-1-Command | Start interlock 1 | Command | ENABLE/DISABLE | |
| BV | 21 | Start-Interlock-2-Command | Start interlock 2 | Command | ENABLE/DISABLE | |
| BV | 24 | Started-Monitor | Start status | Read | STARTED/NOT-STARTED | |
| BV | 25 | Safe-Torque-Off-Monitor | Safe Torque Off status | Read | Active/OK | |
| BV | 26 | Underload-Monitor | Underload status | Read | UNDERLOAD/OK | |
| BV | 27 | Overload-Monitor | Overload status | Read | OVERLOAD/OK | |
| BV | 28 | Motor-Heating-Command | Motor heating command | Write | ON/OFF | |
| BV | 29 | Motor-Heating-Monitor | Motor heating status | Read | ON/OFF | |
| BV | 30 | User0-Monitor | User bit 0 status | Read | ON/OFF | |
| BV | 31 | User1-Monitor | User bit 1 status | Read | ON/OFF | |
| BV | 32 | User2-Monitor | User bit 2 status | Read | ON/OFF | |
| BV | 33 | User3-Monitor | User bit 3 status | Read | ON/OFF | |
| BV | 34 | User0-Command | User bit 0 command | Command | ON/OFF | |
| BV | 35 | User1-Command | User bit 1 command | Command | ON/OFF | |
| BV | 36 | User2-Command | User bit 2 command | Command | ON/OFF | |
| BV | 37 | User3-Command | User bit 3 command | Command | ON/OFF | |
| BV | 39 | Parameter-Save-Command | Save parameters to permanent memory | Write | SAVE/NO | |
| BV | 40 | PID-Set-Select | Process PID set 1 or set 2 | Write | Set1/Set2 | |
| MV | 0 | HAND-AUTO-Reference | Hand, Auto or override mode | Read | Off, Hand, Auto, Override | |
| MVmin | 1 | Active-Fault-1 | Type of the most recent active fault | Read | None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss, Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active, Other | |
| MV | 2 | Active-Fault-2 | Type of the 2nd most recent active fault | Read | None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss, Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active, Other | |
| MV | 3 | Active-Fault-3 | Type of the 3rd most recent active fault | Read | None, Comm-Error, Overcurrent, Overtemperature, Overspeed, Overvoltage, Undervoltage, Short-Circuit, Ground-Fault, Motor-Overload, Inverter-Overload, Motor-Underload, External-Fault, Operator-Interface-Error, Config-Error, Feedback-Failure, Output-Phase-Loss, Motor-Stall, Power-Unit-Error, Input-Phase-Fault, Internal-Failure, STO-Active, Other | |
| MV | 4 | Active-Warning-1 | Type of the most recent active warning | Read | None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, Run-Permissive, Internal-Warning, Start-Delay, Other | |
| MV | 5 | Active-Warning-2 | Type of the 2nd most recent active warning | Read | None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, Run-Permissive, Internal-Warning, Start-Delay, Other | |
| MV | 6 | Active-Warning-3 | Type of the 3rd most recent active warning | Read | None, Comm-Error, Current-Limit, Overtemperature, Start-Interlock-1, Start-Interlock-2, Start-Interlock-3, Start-Interlock-4, Run-Permissive, Internal-Warning, Start-Delay, Other | |
| LO | 0 | LOOP-Set1 | Loop object for process PID set 1 (AV 42/43/44) | Read | ||
| LO | 1 | LOOP-Set2 | Loop object for process PID set 2 (AV 42/43/44) | Read |
No points match these filters.
Object ID lookup: ABB FBIP-21 BACnet/IP adapter point IDs by name
AI0AI1-MonitorAI1AI2-MonitorAO0AO1-commandAO1AO2-commandAV0Output-RPMAV1Output-FreqAV2DC-VoltageAV3Output-VoltageAV4Output-CurrentAV5Output-TorqueAV6Output-PowerAV7Operating-Temp-RangeAV8Kilowatt-Hour-Meter-RAV9Kilowatt-Hour-Meter-NRAV10Process-PID-FeedbackAV11Process-PID-DeviationAV12External-PID-FeedbackAV13External-PID-DeviationAV14Running-HoursAV15Motor-Temp-Degrees-CAV16Input-Reference-1AV17Input-Reference-2AV18Active-FaultAV19Previous-Fault-1AV20Previous-Fault-2AV21AO1-MonitorAV22AO2-MonitorAV23Accel-1-SecondsAV24Decel-1-SecondsAV25Mbox-ParamAV26Mbox-DataAV29Min-SpeedAV30Max-SpeedAV31Output-SpeedAV32Output-Current-RangeAV33Max-CurrentAV34DC-RippleAV40LOOP-Feedback-MonitorAV41LOOP-Setpoint-MonitorAV42LOOP-SetpointAV43LOOP-FeedbackAV44LOOP-OutputAV45LOOP-GainAV46LOOP-Integration-TimeAV49LOOP-Deviation-MonitorAV53LOOP-1-GainAV54LOOP-1-Integration-TimeAV55LOOP-2-Feedback-MonitorAV56LOOP-2-Setpoint-MonitorAV59LOOP-2-OutputAV60LOOP-2-GainAV61LOOP-2-Integration-TimeAV64LOOP-2-Deviation-MonitorAV130Kilowatt-Hour-This-HourAV131Kilowatt-Hour-Last-HourAV132Kilowatt-Hour-This DayAV133Kilowatt-Hour-Last-DayBI0RO1-MonitorBI1RO2-MonitorBI2RO3-MonitorBI3RO4-MonitorBI4RO5-MonitorBI5DO1-MonitorBI6DI1-MonitorBI7DI2-MonitorBI8DI3-MonitorBI9DI4-MonitorBI10DI5-MonitorBI11DI6-MonitorBO0RO1-CommandBO1RO2-CommandBO2RO3-CommandBO3RO4-CommandBO4RO5-CommandBO5DO1-CommandBV0RUN-STOP-MonitorBV1Direction-MonitorBV2OK-FAULT-MonitorBV3EXT1-EXT2-MonitorBV4HAND-AUTO-MonitorBV5Warning-MonitorBV7Ready-MonitorBV8At-Setpoint-MonitorBV9Enabled-MonitorBV10RUN-STOP-CommandBV11Direction-CommandBV12Run-Permissive-CommandBV13EXT1-EXT2-CommandBV14Fault-Reset-CommandBV17Lock-ParametersBV18Control-Override-CommandBV19Control-Override-MonitorBV20Start-Interlock-1-CommandBV21Start-Interlock-2-CommandBV24Started-MonitorBV25Safe-Torque-Off-MonitorBV26Underload-MonitorBV27Overload-MonitorBV28Motor-Heating-CommandBV29Motor-Heating-MonitorBV30User0-MonitorBV31User1-MonitorBV32User2-MonitorBV33User3-MonitorBV34User0-CommandBV35User1-CommandBV36User2-CommandBV37User3-CommandBV39Parameter-Save-CommandBV40PID-Set-SelectMV0HAND-AUTO-ReferenceMV1Active-Fault-1MV2Active-Fault-2MV3Active-Fault-3MV4Active-Warning-1MV5Active-Warning-2MV6Active-Warning-3LO0LOOP-Set1LO1LOOP-Set2
Integration notes
- This is the BACnet IP adapter; the drive's built-in BACnet MS/TP (EFB) object list is a separate entry (ABB ACH580).
- The adapter builds its object list from the connected drive on first boot; some objects may be missing on a given drive.
- AV 7 is the heatsink temperature but its unit is printed as %; kept as printed.
- AV 49 has no access type printed; listed as read-only since it is a monitor value.
- Multistate values (printed MSV) list the fault/warning types; "Output-Phase-Loss Motor-Stall" is split into two states here.
- C = commandable (priority array), per the manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FBIP-21 BACnet/IP adapter (ACH480 / ACH580) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
How many BACnet points does the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) have?
This list has 119 BACnet objects: 2 analog inputs, 2 analog outputs, 53 analog values, 12 binary inputs, 6 binary outputs, 35 binary values, 2 loops, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) BACnet points are writable?
40 of the 119 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) BACnet documentation?
The source is FBIP-21 BACnet/IP adapter module User's manual (3AXD50000028468 Rev D), revision 2023-01-05, published free by ABB at https://library.e.abb.com/public/c663f475913640da82f13c51bee49b96/EN_FBIP-21_UM_D_A4.pdf.
What are the minimum BACnet points to integrate the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)?
Start with BV 10 RUN-STOP-Command (Start/stop from the BMS); AV 16 Input-Reference-1 (Speed reference in %); BV 14 Fault-Reset-Command (Reset a tripped drive); BV 0 RUN-STOP-Monitor (Running status); BV 4 HAND-AUTO-Monitor (Shows if the panel has the drive in Hand); AV 1 Output-Freq (Output frequency in Hz); AV 4 Output-Current (Motor amps); AV 6 Output-Power (Drive power in kW); BV 2 OK-FAULT-Monitor (Any active drive fault); MV 1 Active-Fault-1 (Which fault is active).
How do I enable BMS control of the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)?
Set 20.01 Ext1 commands = Fieldbus A so BV 10 starts and stops the drive, and 28.11 Ext1 frequency ref1 = FB A ref1 (or the speed reference equivalent) for AV 16. BV 18 Control-Override-Command takes control from the normal source, but panel HAND mode still has priority.
Does the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580) need a BACnet heartbeat or have a communication timeout?
51.20 Timeout time (default 300 = 30.0 s, 0 = off) and 51.21 Timeout mode (default Any packet; Control RW = only control/reference writes reset it) detect a lost master. 50.02 FBA A comm loss func sets the drive reaction and 50.03 FBA A comm loss t out the delay.
Can the BMS supply sensor values to the ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)?
For the process PID, write AV 42 LOOP-Setpoint and AV 43 LOOP-Feedback from the BMS (with the drive PID sources set accordingly). AO 0/AO 1 and BO 0-5 drive outputs when the drive is configured for BACnet control.
How do I check these points on the real FBIP-21 BACnet/IP adapter (ACH480 / ACH580)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ABB BACnet points lists
- Variable frequency drive (HVAC)
ABB ACH180 HVAC drive (embedded BACnet MS/TP)
ABB ACH180 compact HVAC drives using the built-in EFB (RS-485) port with protocol set to BACnet MS/TP.
Also known as: ACH180, ACH180-01, ACH180 HVAC control program, 3AXD50000955893 - Variable frequency drive (HVAC)
ABB ACH550 HVAC drive (embedded BACnet MS/TP)
ABB ACH550 HVAC drives using the built-in RS-485 port with native BACnet MS/TP.
Also known as: ACH550, ACH550-01, ACH550-UH, ACH550 E-Clipse - Variable frequency drive bypass controller (HVAC)
ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)
ABB ACH580 drives with the E-Clipse bypass or packaged bypass (US); this list covers the bypass controller's own BACnet MS/TP objects.
Also known as: ACH580 E-Clipse, E-Clipse bypass, ACH580 packaged bypass, ACH580-BxR, 3AXD50000289554 - Variable frequency drive (HVAC)
ABB ACH580 HVAC drive (embedded BACnet MS/TP)
ABB ACH580 HVAC drives using the built-in EFB port with protocol set to BACnet MS/TP.
Also known as: ACH580, ACH580-01, ACH580-31, ACH580 E-Clipse, ACH580 HVAC control program, 3AXD50000027537 - Variable frequency drive (HVAC)
ABB ACS355 HVAC with BACnet (+N831)
ABB ACS355 machinery drives with the HVAC with BACnet firmware (option +N831, firmware 6502 or later).
Also known as: ACS355, ACS355 +N831, ACS355 HVAC, ACS355 BACnet, 3AXD50000024172 - Variable frequency drive via BACnet gateway
ABB ACS800 drive (ProtoNode FPC-N54 profile)
ABB ACS800 drives (6-pulse or active front end, standard firmware) fitted with an RMBA-01 Modbus adapter and an FPC-N54 ProtoNode.
Also known as: ACS800 BACnet, FPC-N54 ACS800, ABB ProtoNode - Variable frequency drive via BACnet gateway
ABB ACS880 drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with standard firmware (6-pulse or active front end) wired to an FPC-N54 ProtoNode over embedded Modbus RTU.
Also known as: ACS880 BACnet, FPC-N54 ACS880, ABB ProtoNode - Variable frequency drive via BACnet gateway (cooling tower fan)
ABB ACS880-CTDD cooling tower direct drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with Cooling Tower Direct Drive firmware (+N5350) that run permanent-magnet cooling tower fan motors, through an FPC-N54 ProtoNode.
Also known as: ACS880 CTDD BACnet, ACS880 +N5350, Cooling Tower Direct Drive, FPC-N54 ACS880-CTDD - Power meter / network analyzer
ABB M4M 20 / M4M 30 network analyzer (BACnet IP)
ABB M4M 20 and M4M 30 panel network analyzers in their BACnet versions; harmonics and some settings are on the M4M 30 only.
Also known as: M4M 20 BACnet, M4M 30 BACnet, M4M 30SBA, M4M network analyzer, 2CSG445052D0201 - Motor softstarter
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
ABB PSTX softstarters fitted with the Anybus CompactCom BACnet MS/TP or BACnet IP fieldbus module.
Also known as: PSTX, PSTX softstarter, Anybus CompactCom BACnet, 1SFC132381M0201
Source: FBIP-21 BACnet/IP adapter module User's manual · 3AXD50000028468 Rev D · rev. 2023-01-05. Object names, instances and units are reproduced as published; descriptions are our own.