Easy BACnet
  1. Home
  2. BACnet points lists
  3. ABB
  4. ACH580 E-Clipse and packaged bypass (bypass BACnet objects)

Variable frequency drive bypass controller (HVAC) · BACnet points list

ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) BACnet points list

Updated 6 November 2026

Short answer

The E-Clipse bypass has its own controller with an embedded BACnet MS/TP port. Its objects cover bypass relay and digital I/O status, system run, fault, warning and mode flags, start/stop, override, permissive, interlock and reset commands, and current, voltage, energy and run-time values. With bypass parameter 1625 COMM CTL = SYSTEM, start/stop and interlocks go through these bypass objects instead of the drive's.

This page lists 54 BACnet objects for the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.

Manufacturer
ABB
Model
ACH580 E-Clipse and packaged bypass (bypass BACnet objects)
Equipment
Variable frequency drive bypass controller (HVAC)
Equipment type
VFDs & pumps
BACnet objects
54 (22 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
ACH580 E-Clipse, E-Clipse bypass, ACH580 packaged bypass, ACH580-BxR, 3AXD50000289554
Source document
ACH580 E-Clipse and Packaged Bypass User/Hardware Manual, US · 3AXD50000289554 Rev C
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.

BMS integration notes: ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)

Integration in brief

Set 9802 COMM PROT SEL = BACNET (5). The bypass is its own MS/TP node: give it a unique MAC in 5003 (default 256 keeps it off the network) and a device instance in 5040/5099. Then set 1625 COMM CTL = SYSTEM and 1601 = COMM, command BV10 and read BV0, BV3, BV4 and AV0.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN/STOP CMDSystem run / stop commandCommand
BV 12RUN PERMISSIVE CMDRun permissive commandCommand
BV 14FAULT RESETReset a bypass faultCommand
BV 0SYS RUN ACTSystem runningRead
BV 4SYSTEM MODEMotor on bypass or driveRead
AV 1BYPASS MODEHand / off / auto: 0 off, 1 hand, 2 autoRead
AV 0CURRENTOutput current, ARead
BV 3SYS FLT ACTSystem faultRead
AV 3LAST FLTLast bypass fault codeRead

Enable & remote start

Bypass parameter 1625 COMM CTL = (1) SYSTEM makes the bypass objects the control path; 1601 = COMM is needed for BV10 run/stop and 1701 = COMM for BV11 override. BV20 CTL OVERRIDE CMD puts the bypass in BACnet control override; panel HAND mode still has priority.

Heartbeat & communication loss

Bypass parameters 3004 COMM LOSS (action) and 3005 COMM TIME (timeout) set the reaction to lost communication; fault 3028 EXT COMM LOSS shows when the BMS does not poll within 3005.

Network setup

Watch out for

ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

54 of 54 shown
Type
Analog
Access
Show
ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) BACnet Points List
DescriptionStates
BI0RO 1 ACTStatus of bypass Relay Output 1ReadActive: ON, Inactive: OFF
BI1RO 2 ACTStatus of bypass Relay Output 2ReadActive: ON, Inactive: OFF
BI2RO 3 ACTStatus of bypass Relay Output 3ReadActive: ON, Inactive: OFF
BI3RO 4 ACTStatus of bypass Relay Output 4ReadActive: ON, Inactive: OFF
BI4RO 5 ACTStatus of bypass Relay Output 5ReadActive: ON, Inactive: OFF
BI5DI 1 ACTStatus of bypass Digital Input 1ReadActive: ON, Inactive: OFF
BI6DI 2 ACTStatus of bypass Digital Input 2ReadActive: ON, Inactive: OFF
BI7DI 3 ACTStatus of bypass Digital Input 3ReadActive: ON, Inactive: OFF
BI8DI 4 ACTStatus of bypass Digital Input 4ReadActive: ON, Inactive: OFF
BI9DI 5 ACTStatus of bypass Digital Input 5ReadActive: ON, Inactive: OFF
BI10DI 6 ACTStatus of bypass Digital Input 6ReadActive: ON, Inactive: OFF
BO0RO1 COMMANDBypass relay output 1 command (needs 1401 = COMM)CommandActive: ON, Inactive: OFF
BO1RO2 COMMANDBypass relay output 2 command (needs 1404 = COMM)CommandActive: ON, Inactive: OFF
BO2RO3 COMMANDBypass relay output 3 command (needs 1407 = COMM)CommandActive: ON, Inactive: OFF
BO3RO4 COMMANDBypass relay output 4 command (needs 1410 = COMM, OREL-01 option)CommandActive: ON, Inactive: OFF
BO4RO5 COMMANDBypass relay output 5 command (needs 1413 = COMM, OREL-01 option)CommandActive: ON, Inactive: OFF
BVmin0SYS RUN ACTSystem run status regardless of the control sourceReadActive: RUN, Inactive: STOP
BV1SYST START ACTSystem started status regardless of the control sourceReadActive: START, Inactive: NO START
BV2BYP FLT ACTBypass fault statusReadActive: FAULT, Inactive: OK
BVmin3SYS FLT ACTSystem fault statusReadActive: FAULT, Inactive: OK
BVmin4SYSTEM MODEWhether bypass or drive runs the motorReadActive: BYPASS, Inactive: DRIVE
BV5WARNING ACTBypass warning statusReadActive: WARNING, Inactive: OK
BV6BYP RUN ACTBypass run status regardless of the control sourceReadActive: RUN, Inactive: STOP
BV7READY TO RUNWhether the system is ready to receive a run commandReadActive: READY, Inactive: NO READY
BV8UNDERLOADWhether the system is in an underload conditionReadActive: YES, Inactive: NO
BV9ENABLE ACTSystem enable status (all run and start interlocks)ReadActive: ENABLE, Inactive: DISABLE
BVmin10RUN/STOP CMDSystem start command (needs 1601 = COMM)CommandActive: RUN, Inactive: STOP
BV11OVERRIDE CMDOverride 2 command (needs 1701 = COMM)CommandActive: YES, Inactive: NO
BVmin12RUN PERMISSIVE CMDSystem run permissive commandCommandActive: ENABLE, Inactive: DISABLE
BV13OVERRIDE ACTOverride 1 or 2 active, regardless of control sourceReadActive: YES, Inactive: NO
BVmin14FAULT RESETReset a faulted bypassCommandActive: RESET, Inactive: NO
BV15START INTERLOCK 1System Start Interlock 1CommandActive: ENABLE, Inactive: DISABLE
BV16START INTERLOCK 2System Start Interlock 2CommandActive: ENABLE, Inactive: DISABLE
BV17START INTERLOCK 3System Start Interlock 3CommandActive: ENABLE, Inactive: DISABLE
BV18START INTERLOCK 4System Start Interlock 4CommandActive: ENABLE, Inactive: DISABLE
BV19PAR LOCKWhen switched to locked prevents parameter changes from the panelWriteActive: LOCK, Inactive: UNLOCK
BV20CTL OVERRIDE CMDBACnet control override (panel HAND has priority)CommandActive: ON, Inactive: OFF
BV21MBOX READMailbox read of the parameter in AV13WriteActive: READ, Inactive: RESET
BV22MBOX WRITEMailbox write of AV14 to the parameter in AV13WriteActive: WRITE, Inactive: RESET
AVmin0CURRENTMeasured output currentARead
AVmin1BYPASS MODEHand/Off/Auto status of the bypassRead0=OFF, 1=HAND, 2=AUTO
AV2BYP RUN DLYBypass Run delaysWrite
AVmin3LAST FLTLast fault recorded by the bypassRead
AV4WARNING WORD 1First warning status word of the bypassRead
AV5WARNING WORD 2First warning status word of the bypassRead
AV6INPUT VOLTAverage of line-line input voltageVRead
AV7PCB TEMPDEG C of bypass board°CRead
AV8KW HOURSBypass mode kilowatt hourskWhWrite
AV9RUN TIMEBypass mode run hourshWrite
AV10A-B VOLTPhase A - Phase B voltageVRead
AV11B-C VOLTPhase B - Phase C voltageVRead
AV12C-B VOLTPhase C - Phase A voltageVRead
AV13MBOX PARAMParameter to be read or written to by the mailbox functionWrite
AV14MBOX DATAMailbox value read from, or to write to, the AV13 parameterWrite
Object ID lookup: ABB ACH580 E-Clipse Bypass point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACH580 E-Clipse and packaged bypass (bypass BACnet objects) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)

How many BACnet points does the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) have?

This list has 54 BACnet objects: 15 analog values, 11 binary inputs, 5 binary outputs, 23 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) BACnet points are writable?

22 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) BACnet documentation?

The source is ACH580 E-Clipse and Packaged Bypass User/Hardware Manual, US (3AXD50000289554 Rev C), published free by ABB at https://library.e.abb.com/public/a8d8ce51a16e4deab6469e1d15bd7171/3AXD50000289554_en_C_ACH580%20E-Clipse%20and%20Packaged%20Bypass%20Hardware%20Manual%2C%20US.pdf.

What are the minimum BACnet points to integrate the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)?

Start with BV 10 RUN/STOP CMD (System run / stop command); BV 12 RUN PERMISSIVE CMD (Run permissive command); BV 14 FAULT RESET (Reset a bypass fault); BV 0 SYS RUN ACT (System running); BV 4 SYSTEM MODE (Motor on bypass or drive); AV 1 BYPASS MODE (Hand / off / auto: 0 off, 1 hand, 2 auto); AV 0 CURRENT (Output current, A); BV 3 SYS FLT ACT (System fault); AV 3 LAST FLT (Last bypass fault code).

How do I enable BMS control of the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)?

Bypass parameter 1625 COMM CTL = (1) SYSTEM makes the bypass objects the control path; 1601 = COMM is needed for BV10 run/stop and 1701 = COMM for BV11 override. BV20 CTL OVERRIDE CMD puts the bypass in BACnet control override; panel HAND mode still has priority.

Does the ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects) need a BACnet heartbeat or have a communication timeout?

Bypass parameters 3004 COMM LOSS (action) and 3005 COMM TIME (timeout) set the reaction to lost communication; fault 3028 EXT COMM LOSS shows when the BMS does not poll within 3005.

How do I check these points on the real ACH580 E-Clipse and packaged bypass (bypass BACnet objects)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ABB BACnet points lists

Source: ACH580 E-Clipse and Packaged Bypass User/Hardware Manual, US · 3AXD50000289554 Rev C. Object names, instances and units are reproduced as published; descriptions are our own.