Easy BACnet
  1. Home
  2. BACnet points lists
  3. ABB
  4. ACS880 drive (ProtoNode FPC-N54 profile)

Variable frequency drive via BACnet gateway · BACnet points list

ABB ACS880 drive (ProtoNode FPC-N54 profile) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The FPC-N54 profile 2 serves an ACS880 as 32 BACnet objects: relay and digital-input states, run, fault, warning, ready and local/remote status bits, a commandable run/stop BV, analog input readbacks, and speed, frequency, current, power, energy, temperature and fault-code AVs plus a commandable speed reference.

This page lists 32 BACnet objects for the ABB ACS880 drive (ProtoNode FPC-N54 profile) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of ABB’s documentation hosted by Baltimore Aircoil Company, not by ABB itself, so treat it as unofficial.

Manufacturer
ABB
Model
ACS880 drive (ProtoNode FPC-N54 profile)
Equipment
Variable frequency drive via BACnet gateway
Equipment type
VFDs & pumps
BACnet objects
32 (2 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Standard ACS880 firmware
Also known as
ACS880 BACnet, FPC-N54 ACS880, ABB ProtoNode
Source document
ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4) (unofficial copy, hosted by Baltimore Aircoil Company)
Download CSV 32 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.

BMS integration notes: ABB ACS880 drive (ProtoNode FPC-N54 profile)

Integration in brief

Point the drive's run/stop and reference 1 at the embedded fieldbus, then command BV 10 and AV 16 from the BMS and read run, fault and speed feedback.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10Run-Stop CommandRun/stop command (1 = run)Command
AV 16Input-Reference-1Speed reference, 0-100 %Command
BV 0RUN-STOP MONITORRunning statusRead
BV 4Local-RemoteRemote control active (1 = remote)Read
AV 0Output-RPMMotor speed, RPMRead
AV 4Output-CurrentOutput currentRead
AV 6Output-PowerOutput powerRead
BV 2OK-Fault-MonitorDrive fault (1 = fault)Read
AV 18Active-Fault-CodeActive fault codeRead

Enable & remote start

Set the run/stop source to the embedded fieldbus and the speed reference to EFB ref1 (parameter 28.11 in scalar mode, 22.11 in DTC mode); skip this for monitoring only.

Network setup

Watch out for

ABB ACS880 drive (ProtoNode FPC-N54 profile) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
Access
Show
ABB ACS880 drive (ProtoNode FPC-N54 profile) BACnet Points List
DescriptionStates
BI0RO1-MonitorRelay output stateRead0=Off, 1=On
BI1RO2-MonitorRelay output stateRead0=Off, 1=On
BI2RO3-MonitorRelay output stateRead0=Off, 1=On
BI6DI1-MonitorDigital input stateRead0=Off, 1=On
BI7DI2-MonitorDigital input stateRead0=Off, 1=On
BI8DI3-MonitorDigital input stateRead0=Off, 1=On
BI9DI4-MonitorDigital input stateRead0=Off, 1=On
BI10DI5-MonitorDigital input stateRead0=Off, 1=On
BI11DI6-MonitorDigital input stateRead0=Off, 1=On
BI12DIIL-MonitorDigital input stateRead0=Off, 1=On
BVmin0RUN-STOP MONITORDrive is in the run stateRead0=Not running, 1=Started
BV1Direction-MonitorRotation directionRead0=Forward, 1=Reverse
BVmin2OK-Fault-MonitorDrive fault statusRead0=No fault, 1=Fault
BVmin4Local-RemoteLocal or remote controlRead0=Local, 1=Remote
BV5Warning-MonitorDrive warning activeRead0=No warning, 1=Warning
BV7Ready-MonitorReady to startRead0=Not ready, 1=Ready
BV8At-Setpoint-MonitorRunning at setpointRead0=Not at setpoint, 1=At setpoint
BV9Enabled-MonitorRun enabledRead0=Not enabled, 1=Enabled
BVmin10Run-Stop CommandRun/stop commandCommand0=Stop, 1=Run
AI0AI1-MonitorDrive analog input 1%Read
AI1AI2-MonitorDrive analog input 2%Read
AVmin0Output-RPMMotor speedRPMRead
AV1Output-FrequencyOutput frequency, -500 to 500HzRead
AV2DC-Bus-VoltageDC bus voltageVDCRead
AV3Output-VoltageOutput voltageVACRead
AVmin4Output-CurrentOutput currentARead
AVmin6Output-PowerOutput powerkW or HPRead
AV7Heatsink-TemperatureDrive temperature as % of fault limit%Read
AV9Inverter-kW-hoursEnergykWhRead
AV14Running daysRun daysdaysRead
AVmin16Input-Reference-1Speed reference, 0-100 %%Command
AVmin18Active-Fault-CodeActive fault code (hex)Read
Object ID lookup: ABB ACS880 drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACS880 drive (ProtoNode FPC-N54 profile) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ABB ACS880 drive (ProtoNode FPC-N54 profile)

How many BACnet points does the ABB ACS880 drive (ProtoNode FPC-N54 profile) have?

This list has 32 BACnet objects: 2 analog inputs, 11 analog values, 10 binary inputs, 9 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ABB ACS880 drive (ProtoNode FPC-N54 profile) BACnet points are writable?

2 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ABB ACS880 drive (ProtoNode FPC-N54 profile) BACnet documentation?

ABB does not publish it on its own website. This list comes from ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD, revision Document Revision 3.C, February 2020 (Web Configurator Template Revision 4), a copy hosted by Baltimore Aircoil Company at https://baltimoreaircoil.com/download_api_endpoint/1089/gatewaybacnetacs880protonodefpc-n54startupguide_20200709.pdf. Ask ABB or its representative for the current revision.

What are the minimum BACnet points to integrate the ABB ACS880 drive (ProtoNode FPC-N54 profile)?

Start with BV 10 Run-Stop Command (Run/stop command (1 = run)); AV 16 Input-Reference-1 (Speed reference, 0-100 %); BV 0 RUN-STOP MONITOR (Running status); BV 4 Local-Remote (Remote control active (1 = remote)); AV 0 Output-RPM (Motor speed, RPM); AV 4 Output-Current (Output current); AV 6 Output-Power (Output power); BV 2 OK-Fault-Monitor (Drive fault (1 = fault)); AV 18 Active-Fault-Code (Active fault code).

How do I enable BMS control of the ABB ACS880 drive (ProtoNode FPC-N54 profile)?

Set the run/stop source to the embedded fieldbus and the speed reference to EFB ref1 (parameter 28.11 in scalar mode, 22.11 in DTC mode); skip this for monitoring only.

How do I check these points on the real ACS880 drive (ProtoNode FPC-N54 profile)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ABB BACnet points lists

Source: ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4). Object names, instances and units are reproduced as published; descriptions are our own.