Variable frequency drive (HVAC) · BACnet points list

ABB ACH580 HVAC drive (embedded BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The ACH580 has BACnet MS/TP built into its EFB (RS-485) terminal, enabled with parameter 58.01. Its fixed object list covers relay and digital I/O status, run/stop and direction commands, speed references, energy meters, fault and warning history, two PID loops and ten user-mapped Data-IO values. BACnet IP needs a separate adapter (e.g. FBIP-21), which is not covered by this list.

This page lists 129 BACnet objects for the ABB ACH580 HVAC drive (embedded BACnet MS/TP) — 46 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.

Manufacturer
ABB
Model
ACH580 HVAC drive (embedded BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
129 (46 writable)
Transport
BACnet MS/TP
Firmware
Firmware manual Rev J; device object reports firmware revision 14.01
Default device instance
4194303
Also known as
ACH580, ACH580-01, ACH580-31, ACH580 E-Clipse, ACH580 HVAC control program, 3AXD50000027537
Source document
ACH580 HVAC control program Firmware manual · 3AXD50000027537 Rev J · rev. 2026-02-23
Download CSV 129 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: ABB ACH580 HVAC drive (embedded BACnet MS/TP)

Integration in brief

Set 58.01 Protocol enable = BACnet MSTP, then 58.03 node address, 58.04 baud and 58.40 Device object ID, save with 96.07 and apply with 58.06 Refresh settings. Point 20.01 Ext1 commands at Embedded fieldbus and the Ext1 frequency or speed reference (28.11 or 22.11) at EFB ref1, then command BV10 and AV16. Configure 58.14-58.16 so the drive reacts to a lost BMS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN-STOP-CommandStart/stop from the BMSCommand
AV 16Input-Reference-1Speed reference in %Command
BV 14Fault-Reset-CommandReset a tripped driveWrite
BV 0RUN-STOP-MonitorRunning statusRead
BV 4HAND-AUTO-MonitorShows if the panel has the drive in HandRead
AV 1Output-FreqOutput frequency in HzRead
AV 4Output-CurrentMotor ampsRead
AV 6Output-PowerDrive power in kWRead
BV 2OK-FAULT-MonitorAny active drive faultRead
MV 1Active-Fault-1Which fault is activeRead

Enable & remote start

Set 20.01 Ext1 commands (and 20.07 Ext2) to Embedded fieldbus so BV10 starts and stops the drive; 20.21 Direction = Request lets BV11 set direction. For the reference set 28.11 Ext1 frequency ref1 = EFB ref1 (scalar mode, the default) or 22.11 Ext1 speed ref1 = EFB ref1 (vector) for AV16; ref2/AV17 uses 28.15 or 22.18. 19.11 = EFB MCW bit 11 lets BV13 choose Ext1/Ext2, and 20.40/20.41/20.42 = Embedded fieldbus hand run permissive and start interlocks to BV12, BV20 and BV21. BV18 Control-Override-Command takes control from the normal source, but panel HAND still has priority.

Heartbeat & communication loss

BACnet has no built-in timeout, so the drive uses 58.14 Communication loss action (default No action; also Fault, Last speed, Speed ref safe via 22.41/28.41, Fault always, Warning), 58.15 Communication loss mode (default Cw/Ref1/Ref2, meaning only control word or reference writes reset the timer; or Any message) and 58.16 Communication loss time (0-6000 s, default 30 s). In the default mode the BMS must keep rewriting the command or reference. Loss gives fault 6681 or warning A7CE EFB comm loss; there is a 30 s boot-up delay, and changes need a reboot or 58.06 Refresh settings.

Sensors & values from the BMS

For the process PID set 40.08 Set 1 feedback 1 source = Feedback data storage and 40.16 Set 1 setpoint 1 source = Setpoint data storage, then write AV43 LOOP-Feedback and AV42 LOOP-Setpoint. AO0/AO1 drive the analog outputs when 13.12/13.22 = AO data storage, and BO0-BO5 drive the relays when their source is an RO/DIO control word bit.

Network setup

Watch out for

ABB ACH580 HVAC drive (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

129 of 129 shown
Type
Multi-stateOther
Access
Show
ABB ACH580 HVAC drive (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
BI0RO1-MonitorStatus of relay output 1ReadActive: On, Inactive: Off
BI1RO2-MonitorStatus of relay output 2ReadActive: On, Inactive: Off
BI2RO3-MonitorStatus of relay output 3ReadActive: On, Inactive: Off
BI3RO4-MonitorStatus of relay output 4ReadActive: On, Inactive: Off
BI4RO5-MonitorStatus of relay output 5ReadActive: On, Inactive: Off
BI5DO1-MonitorStatus of digital output 1ReadActive: On, Inactive: Off
BI6DI1-MonitorStatus of digital input 1ReadActive: On, Inactive: Off
BI7DI2-MonitorStatus of digital input 2ReadActive: On, Inactive: Off
BI8DI3-MonitorStatus of digital input 3ReadActive: On, Inactive: Off
BI9DI4-MonitorStatus of digital input 4ReadActive: On, Inactive: Off
BI10DI5-MonitorStatus of digital input 5ReadActive: On, Inactive: Off
BI11DI6-MonitorStatus of digital input 6ReadActive: On, Inactive: Off
BO0RO1-CommandOutput state of relay 1CommandActive: On, Inactive: Off
BO1RO2-CommandOutput state of relay 2CommandActive: On, Inactive: Off
BO2RO3-CommandOutput state of relay 3CommandActive: On, Inactive: Off
BO3RO4-CommandOutput state of relay 4CommandActive: On, Inactive: Off
BO4RO4-CommandOutput state of relay 5CommandActive: On, Inactive: Off
BO5DO1-CommandOutput state of digital output 1CommandActive: On, Inactive: Off
BVmin0RUN-STOP-MonitorDrive’s run statusReadActive: Run, Inactive: Stop
BV1Direction-MonitorRotational direction of the motorReadActive: Reverse, Inactive: Forward
BVmin2OK-FAULT-MonitorActual fault status of driveReadActive: Fault, Inactive: OK
BV3EXT1-EXT2-MonitorActual control sourceReadActive: Ext2, Inactive: Ext1
BVmin4HAND-AUTO-MonitorActual operating modeReadActive: Hand, Inactive: Auto
BV5Warning-MonitorActual warning statusReadActive: Warning, Inactive: OK
BV7Ready-MonitorActual ready statusReadActive: Ready, Inactive: Not-Ready
BV8At-Setpoint-MonitorActual at setpoint statusReadActive: Yes, Inactive: No
BV9Enabled-MonitorActual run enabled statusReadActive: Enable, Inactive: Disable
BVmin10RUN-STOP-CommandCommand to start driveCommandActive: Run, Inactive: Stop
BV11Direction-CommandCommand to rotational directionCommandActive: Reverse, Inactive: Forward
BV12Run-Permissive-CommandCommand to run permissive commandCommandActive: Enable, Inactive: Disable
BV13EXT1-EXT2-CommandSelects external control location EXT1 or EXT2CommandActive: Ext2, Inactive: Ext1
BVmin14Fault-Reset-CommandCommanded to fault resetWriteActive: Reset, Inactive: No
BV17Lock-ParametersActual status of parameter lockReadActive: Lock, Inactive: Unlock
BV18Control-Override-CommandPuts the drive under BACnet control override; panel HAND still winsCommandActive: On, Inactive: Off
BV19Control-Override-MonitorShows whether BACnet control override (BV18) is activeReadActive: On, Inactive: Off
BV20Start-Interlock-1-CommandCommand to start enable 1CommandActive: Enable, Inactive: Disable
BV21Start-Interlock-2-CommandCommand to start enable 2CommandActive: Enable, Inactive: Disable
BV24Started-MonitorActual start statusReadActive: Started, Inactive: Not-Started
BV25Safe-Torque-Off-MonitorActual status of Safe Torque OffReadActive: Active, Inactive: OK
BV26Underload-MonitorOn when load-curve signal is below the underload curveReadActive: Underload, Inactive: OK
BV27Overload-MonitorOn when load-curve signal is above the overload curveReadActive: Overload, Inactive: OK
BV28Motor-Heating-CommandCommand to motor heating modeWriteActive: On, Inactive: Off
BV29Motor-Heating-MonitorActual status of motor heating modeReadActive: On, Inactive: Off
BV30User0-MonitorActual status of “User bit0” in drive status wordReadActive: On, Inactive: Off
BV31User1-MonitorActual status of “User bit1” in drive status wordReadActive: On, Inactive: Off
BV32User2-MonitorActual status of “User bit2” in drive status wordReadActive: On, Inactive: Off
BV33User3-MonitorActual status of “User bit3” in drive status wordReadActive: On, Inactive: Off
BV34User0-CommandCommands “User bit0” in drive status wordCommandActive: On, Inactive: Off
BV35User1-CommandCommands “User bit1” in drive status wordCommandActive: On, Inactive: Off
BV36User2-CommandCommands “User bit2” in drive status wordCommandActive: On, Inactive: Off
BV37User3-CommandCommands “User bit3” in drive status wordCommandActive: On, Inactive: Off
BV39Parameter-Save-CommandSaves drive parameters and persistent BACnet propertiesWriteActive: Save, Inactive: No
BV40PID-Set-SelectSelects process PID set 1 or set 2WriteActive: Set1, Inactive: Set2
AI0AI1-MonitorInput level of analog input 1%Read
AI1AI2-MonitorInput level of analog input 2%Read
AO0AO1-CommandDrives analog output 1 (needs BACnet as AO source)%Command
AO1AO2-CommandDrives analog output 2 (needs BACnet as AO source)%Command
AV0Output-RPMMotor speedrpmRead
AVmin1Output-FreqOutput frequencyHzRead
AV2DC-VoltageDC bus voltageVRead
AV3Output-VoltageAC output voltageVRead
AVmin4Output-CurrentOutput current of driveARead
AV5Output-TorqueMotor torque as % of nominal torque%Read
AVmin6Output-PowerOutput power in kWkWRead
AV7Operating-Temp-RangeHeatsink temperature%Read
AV8Kilowatt-Hour-Meter-RCumulative energy use, resettablekWhWrite
AV9Kilowatt-Hour-Meter-NRCumulative energy use, not resettablekWhRead
AV10Process-PID-FeedbackProcess PID feedback%Read
AV11Process-PID-DeviationProcess PID deviation from setpoint%Read
AV12External-PID-FeedbackExternal PID feedback%Read
AV13External-PID-DeviationExternal PID deviation from setpoint%Read
AV14Running-HoursResettable run time; write 0 to resethRead
AV15Motor-Temp-Degrees-CMotor temperature°CRead
AVmin16Input-Reference-1Speed setpoint 1%Command
AV17Input-Reference-2Speed setpoint 2%Command
AV18Active-FaultDisplays most recent fault currently activeRead
AV19Previous-Fault-1Most recent stored (inactive) faultRead
AV20Previous-Fault-2Second most recent stored (inactive) faultRead
AV21AO1-MonitorOutput level of analog output 1%Read
AV22AO2-MonitorOutput level of analog output 2%Read
AV23Accel-1-SecondsRamp1 acceleration timesWrite
AV24Decel-1-SecondsRamp 1 deceleration timesWrite
AV25Mbox-ParamParameter number used by the mailbox functionWrite
AV26Mbox-DataMailbox data value (write to set, read to view)Write
AV27External-PID-SetpointExternal PID controller setpoint%Command
AV29Min-SpeedMinimum allowed output frequencyHzWrite
AV30Max-SpeedMaximum allowed output frequencyHzWrite
AV31Output-SpeedActual motor speed%Read
AV32Output-Current-RangeActual motor current%Read
AV33Max-CurrentMax motor currentAWrite
AV40LOOP-Feedback-MonitorLoop controller feedback after source selection and filtering%Read
AV41LOOP-Setpoint-MonitorLoop controller setpoint after limiting and ramping%Read
AV42LOOP-SetpointLoop controller setpoint written by BACnet%Command
AV43LOOP-FeedbackLoop controller feedback value written by BACnet%Write
AV44LOOP-OutputLoop controller output%Read
AV45LOOP-GainLoop controller gainWrite
AV46LOOP-Integration-TimeLoop controller integration timesWrite
AV49LOOP-Deviation-MonitorLoop controller deviation%Read
AV53LOOP-1-GainLoop controller gain (set 2)Write
AV54LOOP-1-Integration-TimeLoop controller integration time (set 2)sWrite
AV55LOOP-2-Feedback-MonitorExternal loop controller feedback after filtering%Read
AV56LOOP-2-Setpoint-MonitorExternal loop controller setpoint after limiting and ramping%Read
AV59LOOP-2-OutputExternal loop controller output%Read
AV60LOOP-2-GainExternal loop controller gainWrite
AV61LOOP-2-Integration-TimeExternal loop controller integration timesWrite
AV64LOOP-2-Deviation-MonitorExternal loop controller deviation%Read
AV120Data-IO-1Value of the drive parameter mapped in 58.101Write
AV121Data-IO-2Value of the drive parameter mapped in 58.102Write
AV122Data-IO-3Value of the drive parameter mapped in 58.103Write
AV123Data-IO-4Value of the drive parameter mapped in 58.104Write
AV124Data-IO-5Value of the drive parameter mapped in 58.105Read
AV125Data-IO-6Value of the drive parameter mapped in 58.106Read
AV126Data-IO-7Value of the drive parameter mapped in 58.107Read
AV127Data-IO-8Value of the drive parameter mapped in 58.108Read
AV128Data-IO-9Value of the drive parameter mapped in 58.109Read
AV129Data-IO-10Value of the drive parameter mapped in 58.110Read
AV130Kilowatt-Hour-This-HourCurrent hour energy consumptionkWhRead
AV131Kilowatt-Hour-Last-HourLast hour energy consumptionkWhRead
AV132Kilowatt-Hour-This-DayCurrent day energy consumptionkWhRead
AV133Kilowatt-Hour-Last-DayLast day energy consumptionkWhRead
MV0HAND-AUTO-ReferenceHand, Auto, Off or Override control stateRead1=Off, 2=Hand, 3=Auto, 4=Override
MVmin1Active-Fault-1Most recent active fault, as enumerated typeRead1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other
MV2Active-Fault-2Second most recent active fault, as enumerated typeRead1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other
MV3Active-Fault-3Third most recent active fault, as enumerated typeRead1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other
MV4Active-Warning-1Most recent active warning, as enumerated typeRead1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other
MV5Active-Warning-2Second most recent active warning, as enumerated typeRead1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other
MV6Active-Warning-3Third most recent active warning, as enumerated typeRead1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other
LO0LOOP-Set1Loop object for process PID set 1Read
LO1LOOP-Set2Loop object for process PID set 2Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACH580 HVAC drive (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ABB ACH580 HVAC drive (embedded BACnet MS/TP)

How many BACnet points does the ABB ACH580 HVAC drive (embedded BACnet MS/TP) have?

This list has 129 BACnet objects: 2 analog inputs, 2 analog outputs, 63 analog values, 12 binary inputs, 6 binary outputs, 35 binary values, 2 loops, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ABB ACH580 HVAC drive (embedded BACnet MS/TP) BACnet points are writable?

46 of the 129 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ABB ACH580 HVAC drive (embedded BACnet MS/TP) BACnet documentation?

The source is ACH580 HVAC control program Firmware manual (3AXD50000027537 Rev J), revision 2026-02-23, published free by ABB at https://library.e.abb.com/public/c896544ee053430081a08ac378039428/EN_ACH580_FW_J_A5.pdf.

What are the minimum BACnet points to integrate the ABB ACH580 HVAC drive (embedded BACnet MS/TP)?

Start with BV 10 RUN-STOP-Command (Start/stop from the BMS); AV 16 Input-Reference-1 (Speed reference in %); BV 14 Fault-Reset-Command (Reset a tripped drive); BV 0 RUN-STOP-Monitor (Running status); BV 4 HAND-AUTO-Monitor (Shows if the panel has the drive in Hand); AV 1 Output-Freq (Output frequency in Hz); AV 4 Output-Current (Motor amps); AV 6 Output-Power (Drive power in kW); BV 2 OK-FAULT-Monitor (Any active drive fault); MV 1 Active-Fault-1 (Which fault is active).

How do I enable BMS control of the ABB ACH580 HVAC drive (embedded BACnet MS/TP)?

Set 20.01 Ext1 commands (and 20.07 Ext2) to Embedded fieldbus so BV10 starts and stops the drive; 20.21 Direction = Request lets BV11 set direction. For the reference set 28.11 Ext1 frequency ref1 = EFB ref1 (scalar mode, the default) or 22.11 Ext1 speed ref1 = EFB ref1 (vector) for AV16; ref2/AV17 uses 28.15 or 22.18. 19.11 = EFB MCW bit 11 lets BV13 choose Ext1/Ext2, and 20.40/20.41/20.42 = Embedded fieldbus hand run permissive and start interlocks to BV12, BV20 and BV21. BV18 Control-Override-Command takes control from the normal source, but panel HAND still has priority.

Does the ABB ACH580 HVAC drive (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

BACnet has no built-in timeout, so the drive uses 58.14 Communication loss action (default No action; also Fault, Last speed, Speed ref safe via 22.41/28.41, Fault always, Warning), 58.15 Communication loss mode (default Cw/Ref1/Ref2, meaning only control word or reference writes reset the timer; or Any message) and 58.16 Communication loss time (0-6000 s, default 30 s). In the default mode the BMS must keep rewriting the command or reference. Loss gives fault 6681 or warning A7CE EFB comm loss; there is a 30 s boot-up delay, and changes need a reboot or 58.06 Refresh settings.

Can the BMS supply sensor values to the ABB ACH580 HVAC drive (embedded BACnet MS/TP)?

For the process PID set 40.08 Set 1 feedback 1 source = Feedback data storage and 40.16 Set 1 setpoint 1 source = Setpoint data storage, then write AV43 LOOP-Feedback and AV42 LOOP-Setpoint. AO0/AO1 drive the analog outputs when 13.12/13.22 = AO data storage, and BO0-BO5 drive the relays when their source is an RO/DIO control word bit.

How do I check these points on the real ACH580 HVAC drive (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ABB BACnet points lists

Source: ACH580 HVAC control program Firmware manual · 3AXD50000027537 Rev J · rev. 2026-02-23. Object names, instances and units are reproduced as published; descriptions are our own.