Variable frequency drive via BACnet gateway · BACnet points list
ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet points list
Updated 7 November 2026Unofficial source
The ProtoNode FPC-N54 reads an ACS800 drive over Modbus RTU and serves 50 BACnet objects: references, ramp times and PID tuning as AVs, drive measurements and I/O status as AIs and BIs, and start/stop, alarm reset, EXT1/EXT2 select and relay commands as BVs. Select profile 1 (ACS800) in the gateway's web configurator.
This page lists 50 BACnet objects for the ABB ACS800 drive (ProtoNode FPC-N54 profile) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of ABB’s documentation hosted by Baltimore Aircoil Company, not by ABB itself, so treat it as unofficial.
- Manufacturer
- ABB
- Model
- ACS800 drive (ProtoNode FPC-N54 profile)
- Equipment
- Variable frequency drive via BACnet gateway
- Equipment type
- VFDs & pumps
- BACnet objects
- 50 (14 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ACS800 BACnet, FPC-N54 ACS800, ABB ProtoNode
- Source document
- ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4) (unofficial copy, hosted by Baltimore Aircoil Company)
Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.
BMS integration notes: ABB ACS800 drive (ProtoNode FPC-N54 profile)
Set the drive to take start/stop and reference 1 from the fieldbus, then write START/STOP and REFERENCE 1 COMMAND and read speed, current, ready and tripped status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | START/STOP | Start/stop command | Write |
| AV 1 | REFERENCE 1 COMMAND | Speed reference 1 | Write |
| BV 2 | ALARM RESET | Fault reset | Write |
| BI 2 | RUN ENABLED | Run enabled status | Read |
| AI 1 | MOTOR SPEED | Motor speed | Read |
| AI 3 | CURRENT | Motor current | Read |
| AI 21 | POWER | Drive power | Read |
| BI 3 | TRIPPED | Drive tripped (fault) | Read |
| BI 4 | ALARM | Drive alarm | Read |
Enable & remote start
For BACnet control set parameter 10.01 EXT1 STRT/STP/DIR = COMM.CW and 11.03 EXT REF1 SELECT = COMM.REF; for monitoring only, skip these.
Network setup
- Drive Modbus via RMBA-01: 98.02 = STD Modbus, 52.01 = 1, 52.02 = 19.2 kbps, 52.03 = NONE1STOPBIT, then power-cycle the drive.
- Choose profile 1 (ACS800) in the ProtoNode web configurator.
- ProtoNode default IP address 192.168.1.24, subnet 255.255.255.0; it serves BACnet IP or BACnet MS/TP.
Watch out for
- Direction control is not available over BACnet.
- Access is not printed for this profile; confirm writes on site.
ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REFERENCE 1 COMMAND | Write | |||
| AV | 2 | REFERENCE 2 COMMAND | Write | |||
| AV | 3 | REFERNECE 4 COMMAND | Write | |||
| AV | 4 | REFERENCE 5 COMMAND | Write | |||
| AV | 5 | ACCEL TIME | Write | |||
| AV | 6 | DECEL TIME | Write | |||
| AV | 7 | PID GAIN | Write | |||
| AV | 8 | PID I TIME | Write | |||
| AImin | 1 | MOTOR SPEED | Read | |||
| AI | 2 | FREQUENCEY | Read | |||
| AImin | 3 | CURRENT | Read | |||
| AI | 4 | DC BUS VOLTAGE | Read | |||
| AI | 5 | MAIN VOLTAGE | Read | |||
| AI | 6 | OUTPUT VOLTAGE | Read | |||
| AI | 7 | EXTERNAL REF 1 | Read | |||
| AI | 8 | EXTERNAL REF 2 | Read | |||
| AI | 9 | ACTIVE CONTROL LOCATION | Read | |||
| AI | 10 | RUNTIME | Read | |||
| AI | 11 | KWN | Read | |||
| AI | 12 | AI 1 STATUS | Read | |||
| AI | 13 | AI 2 STAUTS | Read | |||
| AI | 14 | AI 3 STATUS | Read | |||
| AI | 15 | AO 1 STATUS | Read | |||
| AI | 16 | AO 2 STATUS | Read | |||
| AI | 17 | PID 1 FEEDBACK | Read | |||
| AI | 18 | PID 2 FEEDBACK | Read | |||
| AI | 19 | PID DEVIATION | Read | |||
| AI | 20 | HEATSINK TEMPERATURE | Read | |||
| AImin | 21 | POWER | Read | |||
| BVmin | 1 | START/STOP | Write | |||
| BVmin | 2 | ALARM RESET | Write | |||
| BV | 3 | EXT1/EXT2 SELECT | Write | |||
| BV | 4 | RO1 COMMAND | Write | |||
| BV | 5 | RO2 COMMAND | Write | |||
| BV | 6 | RO3 COMMAND | Write | |||
| BI | 1 | READY | Read | |||
| BImin | 2 | RUN ENABLED | Read | |||
| BImin | 3 | TRIPPED | Read | |||
| BImin | 4 | ALARM | Read | |||
| BI | 5 | DRV AT SETPOINT | Read | |||
| BI | 6 | EXT1/EXT2 MODE | Read | |||
| BI | 7 | DI 1 STATUS | Read | |||
| BI | 8 | DI 2 STATUS | Read | |||
| BI | 9 | DI 3 STATUS | Read | |||
| BI | 10 | DI 4 STATUS | Read | |||
| BI | 11 | DI 5 STATUS | Read | |||
| BI | 12 | DI 6 STATUS | Read | |||
| BI | 13 | RO1 STATUS | Read | |||
| BI | 14 | RO2 STATUS | Read | |||
| BI | 15 | RO3 STATUS | Read |
No points match these filters.
Object ID lookup: ABB ACS800 drive point IDs by name
AV1REFERENCE 1 COMMANDAV2REFERENCE 2 COMMANDAV3REFERNECE 4 COMMANDAV4REFERENCE 5 COMMANDAV5ACCEL TIMEAV6DECEL TIMEAV7PID GAINAV8PID I TIMEAI1MOTOR SPEEDAI2FREQUENCEYAI3CURRENTAI4DC BUS VOLTAGEAI5MAIN VOLTAGEAI6OUTPUT VOLTAGEAI7EXTERNAL REF 1AI8EXTERNAL REF 2AI9ACTIVE CONTROL LOCATIONAI10RUNTIMEAI11KWNAI12AI 1 STATUSAI13AI 2 STAUTSAI14AI 3 STATUSAI15AO 1 STATUSAI16AO 2 STATUSAI17PID 1 FEEDBACKAI18PID 2 FEEDBACKAI19PID DEVIATIONAI20HEATSINK TEMPERATUREAI21POWERBV1START/STOPBV2ALARM RESETBV3EXT1/EXT2 SELECTBV4RO1 COMMANDBV5RO2 COMMANDBV6RO3 COMMANDBI1READYBI2RUN ENABLEDBI3TRIPPEDBI4ALARMBI5DRV AT SETPOINTBI6EXT1/EXT2 MODEBI7DI 1 STATUSBI8DI 2 STATUSBI9DI 3 STATUSBI10DI 4 STATUSBI11DI 5 STATUSBI12DI 6 STATUSBI13RO1 STATUSBI14RO2 STATUSBI15RO3 STATUS
Integration notes
- The ACS800 table lists only object IDs and names; access is inferred (AV/BV writable, AI/BI read-only).
- No units, ranges or state texts are printed for this profile.
- Object names keep the guide's spelling (REFERNECE, FREQUENCEY, STAUTS, KWN).
- Direction control is not offered over BACnet; wire it to the drive if needed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACS800 drive (ProtoNode FPC-N54 profile) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ABB ACS800 drive (ProtoNode FPC-N54 profile)
How many BACnet points does the ABB ACS800 drive (ProtoNode FPC-N54 profile) have?
This list has 50 BACnet objects: 21 analog inputs, 8 analog values, 15 binary inputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet points are writable?
14 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet documentation?
ABB does not publish it on its own website. This list comes from ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD, revision Document Revision 3.C, February 2020 (Web Configurator Template Revision 4), a copy hosted by Baltimore Aircoil Company at https://baltimoreaircoil.com/download_api_endpoint/1089/gatewaybacnetacs880protonodefpc-n54startupguide_20200709.pdf. Ask ABB or its representative for the current revision.
What are the minimum BACnet points to integrate the ABB ACS800 drive (ProtoNode FPC-N54 profile)?
Start with BV 1 START/STOP (Start/stop command); AV 1 REFERENCE 1 COMMAND (Speed reference 1); BV 2 ALARM RESET (Fault reset); BI 2 RUN ENABLED (Run enabled status); AI 1 MOTOR SPEED (Motor speed); AI 3 CURRENT (Motor current); AI 21 POWER (Drive power); BI 3 TRIPPED (Drive tripped (fault)); BI 4 ALARM (Drive alarm).
How do I enable BMS control of the ABB ACS800 drive (ProtoNode FPC-N54 profile)?
For BACnet control set parameter 10.01 EXT1 STRT/STP/DIR = COMM.CW and 11.03 EXT REF1 SELECT = COMM.REF; for monitoring only, skip these.
How do I check these points on the real ACS800 drive (ProtoNode FPC-N54 profile)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ABB BACnet points lists
- Variable frequency drive (HVAC)
ABB ACH180 HVAC drive (embedded BACnet MS/TP)
ABB ACH180 compact HVAC drives using the built-in EFB (RS-485) port with protocol set to BACnet MS/TP.
Also known as: ACH180, ACH180-01, ACH180 HVAC control program, 3AXD50000955893 - Variable frequency drive (HVAC)
ABB ACH550 HVAC drive (embedded BACnet MS/TP)
ABB ACH550 HVAC drives using the built-in RS-485 port with native BACnet MS/TP.
Also known as: ACH550, ACH550-01, ACH550-UH, ACH550 E-Clipse - Variable frequency drive bypass controller (HVAC)
ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)
ABB ACH580 drives with the E-Clipse bypass or packaged bypass (US); this list covers the bypass controller's own BACnet MS/TP objects.
Also known as: ACH580 E-Clipse, E-Clipse bypass, ACH580 packaged bypass, ACH580-BxR, 3AXD50000289554 - Variable frequency drive (HVAC)
ABB ACH580 HVAC drive (embedded BACnet MS/TP)
ABB ACH580 HVAC drives using the built-in EFB port with protocol set to BACnet MS/TP.
Also known as: ACH580, ACH580-01, ACH580-31, ACH580 E-Clipse, ACH580 HVAC control program, 3AXD50000027537 - Variable frequency drive (HVAC)
ABB ACS355 HVAC with BACnet (+N831)
ABB ACS355 machinery drives with the HVAC with BACnet firmware (option +N831, firmware 6502 or later).
Also known as: ACS355, ACS355 +N831, ACS355 HVAC, ACS355 BACnet, 3AXD50000024172 - Variable frequency drive via BACnet gateway
ABB ACS880 drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with standard firmware (6-pulse or active front end) wired to an FPC-N54 ProtoNode over embedded Modbus RTU.
Also known as: ACS880 BACnet, FPC-N54 ACS880, ABB ProtoNode - Variable frequency drive via BACnet gateway (cooling tower fan)
ABB ACS880-CTDD cooling tower direct drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with Cooling Tower Direct Drive firmware (+N5350) that run permanent-magnet cooling tower fan motors, through an FPC-N54 ProtoNode.
Also known as: ACS880 CTDD BACnet, ACS880 +N5350, Cooling Tower Direct Drive, FPC-N54 ACS880-CTDD - Variable frequency drive (BACnet/IP adapter module)
ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
ABB FBIP-21 BACnet/IP adapter fitted to ACH480 (with BAPO-01) and ACH580 / ACH580 E-Clipse bypass drives (with CMOD-01 or CMOD-02).
Also known as: FBIP-21, FBIP21, ACH580 BACnet/IP, ACH480 BACnet/IP, ACH580 E-Clipse BACnet IP, 3AXD50000028468 - Power meter / network analyzer
ABB M4M 20 / M4M 30 network analyzer (BACnet IP)
ABB M4M 20 and M4M 30 panel network analyzers in their BACnet versions; harmonics and some settings are on the M4M 30 only.
Also known as: M4M 20 BACnet, M4M 30 BACnet, M4M 30SBA, M4M network analyzer, 2CSG445052D0201 - Motor softstarter
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
ABB PSTX softstarters fitted with the Anybus CompactCom BACnet MS/TP or BACnet IP fieldbus module.
Also known as: PSTX, PSTX softstarter, Anybus CompactCom BACnet, 1SFC132381M0201
Source: ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4). Object names, instances and units are reproduced as published; descriptions are our own.