Easy BACnet
  1. Home
  2. BACnet points lists
  3. ABB
  4. ACS800 drive (ProtoNode FPC-N54 profile)

Variable frequency drive via BACnet gateway · BACnet points list

ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode FPC-N54 reads an ACS800 drive over Modbus RTU and serves 50 BACnet objects: references, ramp times and PID tuning as AVs, drive measurements and I/O status as AIs and BIs, and start/stop, alarm reset, EXT1/EXT2 select and relay commands as BVs. Select profile 1 (ACS800) in the gateway's web configurator.

This page lists 50 BACnet objects for the ABB ACS800 drive (ProtoNode FPC-N54 profile) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of ABB’s documentation hosted by Baltimore Aircoil Company, not by ABB itself, so treat it as unofficial.

Manufacturer
ABB
Model
ACS800 drive (ProtoNode FPC-N54 profile)
Equipment
Variable frequency drive via BACnet gateway
Equipment type
VFDs & pumps
BACnet objects
50 (14 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
ACS800 BACnet, FPC-N54 ACS800, ABB ProtoNode
Source document
ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4) (unofficial copy, hosted by Baltimore Aircoil Company)
Download CSV 50 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.

BMS integration notes: ABB ACS800 drive (ProtoNode FPC-N54 profile)

Integration in brief

Set the drive to take start/stop and reference 1 from the fieldbus, then write START/STOP and REFERENCE 1 COMMAND and read speed, current, ready and tripped status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1START/STOPStart/stop commandWrite
AV 1REFERENCE 1 COMMANDSpeed reference 1Write
BV 2ALARM RESETFault resetWrite
BI 2RUN ENABLEDRun enabled statusRead
AI 1MOTOR SPEEDMotor speedRead
AI 3CURRENTMotor currentRead
AI 21POWERDrive powerRead
BI 3TRIPPEDDrive tripped (fault)Read
BI 4ALARMDrive alarmRead

Enable & remote start

For BACnet control set parameter 10.01 EXT1 STRT/STP/DIR = COMM.CW and 11.03 EXT REF1 SELECT = COMM.REF; for monitoring only, skip these.

Network setup

Watch out for

ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

50 of 50 shown
Type
Access
Show
ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet Points List
DescriptionStates
AVmin1REFERENCE 1 COMMANDWrite
AV2REFERENCE 2 COMMANDWrite
AV3REFERNECE 4 COMMANDWrite
AV4REFERENCE 5 COMMANDWrite
AV5ACCEL TIMEWrite
AV6DECEL TIMEWrite
AV7PID GAINWrite
AV8PID I TIMEWrite
AImin1MOTOR SPEEDRead
AI2FREQUENCEYRead
AImin3CURRENTRead
AI4DC BUS VOLTAGERead
AI5MAIN VOLTAGERead
AI6OUTPUT VOLTAGERead
AI7EXTERNAL REF 1Read
AI8EXTERNAL REF 2Read
AI9ACTIVE CONTROL LOCATIONRead
AI10RUNTIMERead
AI11KWNRead
AI12AI 1 STATUSRead
AI13AI 2 STAUTSRead
AI14AI 3 STATUSRead
AI15AO 1 STATUSRead
AI16AO 2 STATUSRead
AI17PID 1 FEEDBACKRead
AI18PID 2 FEEDBACKRead
AI19PID DEVIATIONRead
AI20HEATSINK TEMPERATURERead
AImin21POWERRead
BVmin1START/STOPWrite
BVmin2ALARM RESETWrite
BV3EXT1/EXT2 SELECTWrite
BV4RO1 COMMANDWrite
BV5RO2 COMMANDWrite
BV6RO3 COMMANDWrite
BI1READYRead
BImin2RUN ENABLEDRead
BImin3TRIPPEDRead
BImin4ALARMRead
BI5DRV AT SETPOINTRead
BI6EXT1/EXT2 MODERead
BI7DI 1 STATUSRead
BI8DI 2 STATUSRead
BI9DI 3 STATUSRead
BI10DI 4 STATUSRead
BI11DI 5 STATUSRead
BI12DI 6 STATUSRead
BI13RO1 STATUSRead
BI14RO2 STATUSRead
BI15RO3 STATUSRead
Object ID lookup: ABB ACS800 drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ACS800 drive (ProtoNode FPC-N54 profile) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ABB ACS800 drive (ProtoNode FPC-N54 profile)

How many BACnet points does the ABB ACS800 drive (ProtoNode FPC-N54 profile) have?

This list has 50 BACnet objects: 21 analog inputs, 8 analog values, 15 binary inputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet points are writable?

14 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ABB ACS800 drive (ProtoNode FPC-N54 profile) BACnet documentation?

ABB does not publish it on its own website. This list comes from ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD, revision Document Revision 3.C, February 2020 (Web Configurator Template Revision 4), a copy hosted by Baltimore Aircoil Company at https://baltimoreaircoil.com/download_api_endpoint/1089/gatewaybacnetacs880protonodefpc-n54startupguide_20200709.pdf. Ask ABB or its representative for the current revision.

What are the minimum BACnet points to integrate the ABB ACS800 drive (ProtoNode FPC-N54 profile)?

Start with BV 1 START/STOP (Start/stop command); AV 1 REFERENCE 1 COMMAND (Speed reference 1); BV 2 ALARM RESET (Fault reset); BI 2 RUN ENABLED (Run enabled status); AI 1 MOTOR SPEED (Motor speed); AI 3 CURRENT (Motor current); AI 21 POWER (Drive power); BI 3 TRIPPED (Drive tripped (fault)); BI 4 ALARM (Drive alarm).

How do I enable BMS control of the ABB ACS800 drive (ProtoNode FPC-N54 profile)?

For BACnet control set parameter 10.01 EXT1 STRT/STP/DIR = COMM.CW and 11.03 EXT REF1 SELECT = COMM.REF; for monitoring only, skip these.

How do I check these points on the real ACS800 drive (ProtoNode FPC-N54 profile)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ABB BACnet points lists

Source: ProtoNode FPC-N54 Start-up Guide For Interfacing ABB Products: ACS800, ACS880, ACS880-CTDD · rev. Document Revision 3.C, February 2020 (Web Configurator Template Revision 4). Object names, instances and units are reproduced as published; descriptions are our own.