- Home
- BACnet points lists
- ABB
- M4M 20 / M4M 30 network analyzer (BACnet IP)
Power meter / network analyzer · BACnet points list
ABB M4M 20 / M4M 30 network analyzer (BACnet IP) BACnet points list
Updated 6 November 2026
The M4M 20 and M4M 30 BACnet network analyzers serve BACnet IP with a fixed object list. Readings are Analog Values: voltages, currents, energies by tariff, power, power quality (THD, unbalance, frequency, power factor), phase angles, average/min/max values and, on the M4M 30, individual harmonics 2-40. A few Integer Values and one Multi-state Value hold CT/VT ratios, wiring scheme and active tariff.
This page lists 492 BACnet objects for the ABB M4M 20 / M4M 30 network analyzer (BACnet IP) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.
- Manufacturer
- ABB
- Model
- M4M 20 / M4M 30 network analyzer (BACnet IP)
- Equipment
- Power meter / network analyzer
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 492 (8 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- M4M 20 BACnet, M4M 30 BACnet, M4M 30SBA, M4M network analyzer, 2CSG445052D0201
Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.
BMS integration notes: ABB M4M 20 / M4M 30 network analyzer (BACnet IP)
Give the meter a unique device instance and IP settings, then read energy (AV 100), total power (AV 220), voltages, currents, frequency and power factor. Set the CT/VT ratios (IV 3400-3403) and wiring scheme (MV 3501) at commissioning, not from the BMS in normal operation.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 100 | Active energy import total | Imported active energy, total | Read |
| AV 220 | Active power total | Total active power | Read |
| AV 201 | Voltage L1 | Voltage L1-N | Read |
| AV 204 | Voltage L1-L2 | Voltage L1-L2 | Read |
| AV 211 | Current L1 | Current L1 | Read |
| AV 341 | Frequency | Frequency | Read |
| AV 346 | Power factor total | Total power factor | Read |
Network setup
- Device object identifier and object name are writable (example shows device 228).
- Foreign device registration: enable BBMD mode and set the BBMD IP address, UDP port and TTL in the meter.
- Device profile B-ASC; DeviceCommunicationControl is supported for a finite time only, no password.
Watch out for
- No segmentation: requests whose reply exceeds 480 octets are rejected; split them.
- IV 3301 Active tariff is only writable when the tariff source is set to communication (M4M 30).
ABB M4M 20 / M4M 30 network analyzer (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 201 | Voltage L1 | Read | |||
| AV | 202 | Voltage L2 | Read | |||
| AV | 203 | Voltage L3 | Read | |||
| AVmin | 204 | Voltage L1-L2 | Read | |||
| AV | 205 | Voltage L2-L3 | Read | |||
| AV | 206 | Voltage L1-L3 | Read | |||
| AV | 210 | Current 3 Phase | Read | |||
| AVmin | 211 | Current L1 | Read | |||
| AV | 212 | Current L2 | Read | |||
| AV | 213 | Current L3 | Read | |||
| AV | 214 | Current Neutral | Read | |||
| AVmin | 100 | Active energy import total | Read | |||
| AV | 101 | Active energy import tariff 1 | Read | |||
| AV | 102 | Active energy import tariff 2 | Read | |||
| AV | 103 | Active energy import tariff 3 | Read | |||
| AV | 104 | Active energy import tariff 4 | Read | |||
| AV | 105 | Active energy import tariff 5 | Read | |||
| AV | 106 | Active energy import tariff 6 | Read | |||
| AV | 107 | Active energy export total | Read | |||
| AV | 114 | Active energy net total | Read | |||
| AV | 130 | Reactive energy import total | Read | |||
| AV | 137 | Reactive energy export total | Read | |||
| AV | 144 | Reactive energy net total | Read | |||
| AV | 160 | Apparent energy import total | Read | |||
| AV | 167 | Apparent energy export total | Read | |||
| AV | 174 | Apparent energy net total | Read | |||
| AVmin | 220 | Active power total | Read | |||
| AV | 221 | Active power L1 | Read | |||
| AV | 222 | Active power L2 | Read | |||
| AV | 223 | Active power L3 | Read | |||
| AV | 230 | Reactive power total | Read | |||
| AV | 231 | Reactive power L1 | Read | |||
| AV | 232 | Reactive power L2 | Read | |||
| AV | 233 | Reactive power L3 | Read | |||
| AV | 240 | Apparent power total | Read | |||
| AV | 241 | Apparent power L1 | Read | |||
| AV | 242 | Apparent power L2 | Read | |||
| AV | 243 | Apparent power L3 | Read | |||
| AV | 301 | THD voltage L1 | Read | |||
| AV | 302 | THD voltage L2 | Read | |||
| AV | 303 | THD voltage L3 | Read | |||
| AV | 311 | THD voltage L1-L2 | Read | |||
| AV | 312 | THD voltage L2-L3 | Read | |||
| AV | 313 | THD voltage L1-L3 | Read | |||
| AV | 321 | THD current L1 | Read | |||
| AV | 322 | THD current L2 | Read | |||
| AV | 323 | THD current L3 | Read | |||
| AV | 324 | THD current neutral | Read | |||
| AV | 331 | Unbalance line voltage | Read | |||
| AV | 332 | Unbalance phase voltage | Read | |||
| AV | 333 | Unbalace current | Read | |||
| AVmin | 341 | Frequency | Read | |||
| AVmin | 346 | Power factor total | Read | |||
| AV | 347 | Power factor L1 | Read | |||
| AV | 348 | Power factor L2 | Read | |||
| AV | 349 | Power factor L3 | Read | |||
| AV | 400 | Phase angle power total | Read | |||
| AV | 401 | Phase angle power L1 | Read | |||
| AV | 402 | Phase angle power L2 | Read | |||
| AV | 403 | Phase angle power L3 | Read | |||
| AV | 404 | Phase angle current L1 | Read | |||
| AV | 405 | Phase angle current L2 | Read | |||
| AV | 406 | Phase angle current L3 | Read | |||
| AV | 407 | Phase angle voltage L1 | Read | |||
| AV | 408 | Phase angle voltage L2 | Read | |||
| AV | 409 | Phase angle voltage L3 | Read | |||
| AV | 501 | AVERAGE_VOLTAGE_L1 | Read | |||
| AV | 502 | AVERAGE_VOLTAGE_L2 | Read | |||
| AV | 503 | AVERAGE_VOLTAGE_L3 | Read | |||
| AV | 504 | AVERAGE_VOLTAGE_L1_L2 | Read | |||
| AV | 505 | AVERAGE_VOLTAGE_L2_L3 | Read | |||
| AV | 506 | AVERAGE_VOLTAGE_L1_L3 | Read | |||
| AV | 511 | AVERAGE_CURRENT_L1 | Read | |||
| AV | 512 | AVERAGE_CURRENT_L2 | Read | |||
| AV | 513 | AVERAGE_CURRENT_L3 | Read | |||
| AV | 514 | AVERAGE_CURRENT_NEUTRAL | Read | |||
| AV | 520 | AVERAGE_ACTIVE_POWER_TOTAL | Read | |||
| AV | 521 | AVERAGE_ACTIVE_POWER_L1 | Read | |||
| AV | 522 | AVERAGE_ACTIVE_POWER_L2 | Read | |||
| AV | 523 | AVERAGE_ACTIVE_POWER_L3 | Read | |||
| AV | 530 | AVERAGE_REACTIVE_POWER_TOTAL | Read | |||
| AV | 531 | AVERAGE_REACTIVE_POWER_L1 | Read | |||
| AV | 532 | AVERAGE_REACTIVE_POWER_L2 | Read | |||
| AV | 533 | AVERAGE_REACTIVE_POWER_L3 | Read | |||
| AV | 540 | AVERAGE_APPARENT_POWER_TOTAL | Read | |||
| AV | 541 | AVERAGE_APPARENT_POWER_L1 | Read | |||
| AV | 542 | AVERAGE_APPARENT_POWER_L2 | Read | |||
| AV | 543 | AVERAGE_APPARENT_POWER_L3 | Read | |||
| AV | 601 | MIN_VOLTAGE_L1 | Read | |||
| AV | 602 | MIN_VOLTAGE_L2 | Read | |||
| AV | 603 | MIN_VOLTAGE_L3 | Read | |||
| AV | 604 | MIN_VOLTAGE_L1_L2 | Read | |||
| AV | 605 | MIN_VOLTAGE_L2_L3 | Read | |||
| AV | 606 | MIN_VOLTAGE_L1_L3 | Read | |||
| AV | 611 | MIN_CURRENT_L1 | Read | |||
| AV | 612 | MIN_CURRENT_L2 | Read | |||
| AV | 613 | MIN_CURRENT_L3 | Read | |||
| AV | 614 | MIN_CURRENT_NEUTRAL | Read | |||
| AV | 620 | MIN_ACTIVE_POWER_TOTAL | Read | |||
| AV | 621 | MIN_ACTIVE_POWER_L1 | Read | |||
| AV | 622 | MIN_ACTIVE_POWER_L2 | Read | |||
| AV | 623 | MIN_ACTIVE_POWER_L3 | Read | |||
| AV | 630 | MIN_REACTIVE_POWER_TOTAL | Read | |||
| AV | 631 | MIN_REACTIVE_POWER_L1 | Read | |||
| AV | 632 | MIN_REACTIVE_POWER_L2 | Read | |||
| AV | 633 | MIN_REACTIVE_POWER_L3 | Read | |||
| AV | 640 | MIN_APPARENT_POWER_TOTAL | Read | |||
| AV | 641 | MIN_APPARENT_POWER_L1 | Read | |||
| AV | 642 | MIN_APPARENT_POWER_L2 | Read | |||
| AV | 643 | MIN_APPARENT_POWER_L3 | Read | |||
| AV | 701 | MAX_VOLTAGE_L1 | Read | |||
| AV | 702 | MAX_VOLTAGE_L2 | Read | |||
| AV | 703 | MAX_VOLTAGE_L3 | Read | |||
| AV | 704 | MAX_VOLTAGE_L1_L2 | Read | |||
| AV | 705 | MAX_VOLTAGE_L2_L3 | Read | |||
| AV | 706 | MAX_VOLTAGE_L1_L3 | Read | |||
| AV | 711 | MAX_CURRENT_L1 | Read | |||
| AV | 712 | MAX_CURRENT_L2 | Read | |||
| AV | 713 | MAX_CURRENT_L3 | Read | |||
| AV | 714 | MAX_CURRENT_NEUTRAL | Read | |||
| AV | 720 | MAX_ACTIVE_POWER_TOTAL | Read | |||
| AV | 721 | MAX_ACTIVE_POWER_L1 | Read | |||
| AV | 722 | MAX_ACTIVE_POWER_L2 | Read | |||
| AV | 723 | MAX_ACTIVE_POWER_L3 | Read | |||
| AV | 730 | MAX_REACTIVE_POWER_TOTAL | Read | |||
| AV | 731 | MAX_REACTIVE_POWER_L1 | Read | |||
| AV | 732 | MAX_REACTIVE_POWER_L2 | Read | |||
| AV | 733 | MAX_REACTIVE_POWER_L3 | Read | |||
| AV | 740 | MAX_APPARENT_POWER_TOTAL | Read | |||
| AV | 741 | MAX_APPARENT_POWER_L1 | Read | |||
| AV | 742 | MAX_APPARENT_POWER_L2 | Read | |||
| AV | 743 | MAX_APPARENT_POWER_L3 | Read | |||
| AV | 1102 | 2 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1103 | 3 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1104 | 4 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1105 | 5 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1106 | 6 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1107 | 7 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1108 | 8 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1109 | 9 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1110 | 10 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1111 | 11 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1112 | 12 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1113 | 13 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1114 | 14 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1115 | 15 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1116 | 16 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1117 | 17 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1118 | 18 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1119 | 19 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1120 | 20 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1121 | 21 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1122 | 22 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1123 | 23 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1124 | 24 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1125 | 25 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1126 | 26 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1127 | 27 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1128 | 28 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1129 | 29 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1130 | 30 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1131 | 31 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1132 | 32 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1133 | 33 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1134 | 34 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1135 | 35 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1136 | 36 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1137 | 37 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1138 | 38 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1139 | 39 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1140 | 40 Harmonics voltage L1 | M4M 30 only | Read | ||
| AV | 1202 | 2 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1203 | 3 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1204 | 4 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1205 | 5 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1206 | 6 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1207 | 7 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1208 | 8 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1209 | 9 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1210 | 10 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1211 | 11 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1212 | 12 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1213 | 13 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1214 | 14 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1215 | 15 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1216 | 16 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1217 | 17 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1218 | 18 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1219 | 19 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1220 | 20 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1221 | 21 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1222 | 22 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1223 | 23 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1224 | 24 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1225 | 25 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1226 | 26 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1227 | 27 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1228 | 28 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1229 | 29 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1230 | 30 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1231 | 31 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1232 | 32 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1233 | 33 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1234 | 34 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1235 | 35 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1236 | 36 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1237 | 37 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1238 | 38 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1239 | 39 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1240 | 40 Harmonics voltage L2 | M4M 30 only | Read | ||
| AV | 1302 | 2 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1303 | 3 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1304 | 4 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1305 | 5 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1306 | 6 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1307 | 7 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1308 | 8 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1309 | 9 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1310 | 10 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1311 | 11 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1312 | 12 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1313 | 13 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1314 | 14 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1315 | 15 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1316 | 16 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1317 | 17 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1318 | 18 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1319 | 19 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1320 | 20 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1321 | 21 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1322 | 22 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1323 | 23 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1324 | 24 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1325 | 25 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1326 | 26 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1327 | 27 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1328 | 28 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1329 | 29 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1330 | 30 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1331 | 31 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1332 | 32 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1333 | 33 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1334 | 34 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1335 | 35 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1336 | 36 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1337 | 37 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1338 | 38 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1339 | 39 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1340 | 40 Harmonics voltage L3 | M4M 30 only | Read | ||
| AV | 1402 | 2 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1403 | 3 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1404 | 4 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1405 | 5 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1406 | 6 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1407 | 7 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1408 | 8 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1409 | 9 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1410 | 10 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1411 | 11 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1412 | 12 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1413 | 13 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1414 | 14 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1415 | 15 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1416 | 16 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1417 | 17 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1418 | 18 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1419 | 19 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1420 | 20 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1421 | 21 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1422 | 22 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1423 | 23 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1424 | 24 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1425 | 25 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1426 | 26 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1427 | 27 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1428 | 28 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1429 | 29 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1430 | 30 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1431 | 31 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1432 | 32 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1433 | 33 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1434 | 34 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1435 | 35 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1436 | 36 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1437 | 37 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1438 | 38 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1439 | 39 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1440 | 40 Harmonics voltage L1-L2 | M4M 30 only | Read | ||
| AV | 1502 | 2 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1503 | 3 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1504 | 4 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1505 | 5 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1506 | 6 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1507 | 7 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1508 | 8 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1509 | 9 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1510 | 10 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1511 | 11 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1512 | 12 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1513 | 13 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1514 | 14 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1515 | 15 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1516 | 16 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1517 | 17 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1518 | 18 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1519 | 19 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1520 | 20 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1521 | 21 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1522 | 22 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1523 | 23 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1524 | 24 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1525 | 25 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1526 | 26 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1527 | 27 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1528 | 28 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1529 | 29 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1530 | 30 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1531 | 31 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1532 | 32 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1533 | 33 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1534 | 34 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1535 | 35 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1536 | 36 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1537 | 37 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1538 | 38 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1539 | 39 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1540 | 40 Harmonics voltage L2-L3 | M4M 30 only | Read | ||
| AV | 1602 | 2 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1603 | 3 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1604 | 4 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1605 | 5 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1606 | 6 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1607 | 7 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1608 | 8 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1609 | 9 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1610 | 10 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1611 | 11 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1612 | 12 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1613 | 13 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1614 | 14 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1615 | 15 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1616 | 16 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1617 | 17 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1618 | 18 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1619 | 19 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1620 | 20 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1621 | 21 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1622 | 22 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1623 | 23 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1624 | 24 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1625 | 25 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1626 | 26 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1627 | 27 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1628 | 28 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1629 | 29 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1630 | 30 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1631 | 31 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1632 | 32 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1633 | 33 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1634 | 34 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1635 | 35 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1636 | 36 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1637 | 37 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1638 | 38 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1639 | 39 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1640 | 40 Harmonics voltage L1-L3 | M4M 30 only | Read | ||
| AV | 1702 | 2 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1703 | 3 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1704 | 4 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1705 | 5 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1706 | 6 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1707 | 7 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1708 | 8 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1709 | 9 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1710 | 10 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1711 | 11 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1712 | 12 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1713 | 13 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1714 | 14 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1715 | 15 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1716 | 16 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1717 | 17 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1718 | 18 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1719 | 19 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1720 | 20 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1721 | 21 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1722 | 22 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1723 | 23 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1724 | 24 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1725 | 25 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1726 | 26 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1727 | 27 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1728 | 28 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1729 | 29 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1730 | 30 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1731 | 31 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1732 | 32 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1733 | 33 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1734 | 34 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1735 | 35 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1736 | 36 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1737 | 37 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1738 | 38 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1739 | 39 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1740 | 40 Harmonics current L1 | M4M 30 only | Read | ||
| AV | 1802 | 2 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1803 | 3 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1804 | 4 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1805 | 5 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1806 | 6 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1807 | 7 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1808 | 8 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1809 | 9 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1810 | 10 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1811 | 11 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1812 | 12 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1813 | 13 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1814 | 14 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1815 | 15 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1816 | 16 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1817 | 17 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1818 | 18 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1819 | 19 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1820 | 20 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1821 | 21 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1822 | 22 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1823 | 23 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1824 | 24 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1825 | 25 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1826 | 26 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1827 | 27 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1828 | 28 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1829 | 29 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1830 | 30 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1831 | 31 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1832 | 32 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1833 | 33 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1834 | 34 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1835 | 35 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1836 | 36 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1837 | 37 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1838 | 38 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1839 | 39 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1840 | 40 Harmonics current L2 | M4M 30 only | Read | ||
| AV | 1902 | 2 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1903 | 3 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1904 | 4 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1905 | 5 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1906 | 6 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1907 | 7 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1908 | 8 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1909 | 9 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1910 | 10 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1911 | 11 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1912 | 12 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1913 | 13 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1914 | 14 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1915 | 15 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1916 | 16 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1917 | 17 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1918 | 18 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1919 | 19 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1920 | 20 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1921 | 21 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1922 | 22 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1923 | 23 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1924 | 24 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1925 | 25 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1926 | 26 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1927 | 27 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1928 | 28 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1929 | 29 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1930 | 30 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1931 | 31 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1932 | 32 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1933 | 33 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1934 | 34 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1935 | 35 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1936 | 36 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1937 | 37 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1938 | 38 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1939 | 39 Harmonics current L3 | M4M 30 only | Read | ||
| AV | 1940 | 40 Harmonics current L3 | M4M 30 only | Read | ||
| IV | 3301 | Active tariff | Active tariff; writable when tariff source is communication (M4M 30 only) | Write | ||
| IV | 3400 | Trafo CT Ratio L1 L2 L3 Primary | Write | |||
| IV | 3401 | Trafo CT Ratio L1 L2 L3 Secondary | Write | |||
| IV | 3402 | Trafo VT Ratio Primary | Write | |||
| IV | 3403 | Trafo VT Ratio Secondary | Write | |||
| IV | 3404 | Trafo CT Neutral Ratio Primary | M4M 30 only | Write | ||
| IV | 3405 | Trafo CT Neutral Ratio Secondary | M4M 30 only | Write | ||
| MV | 3501 | Wiring scheme | Wiring scheme (writable) | Write | ||
| CSV | 3410 | Serial Number | Read |
No points match these filters.
Object ID lookup: ABB M4M 20 / M4M 30 Network Analyzer point IDs by name
AV201Voltage L1AV202Voltage L2AV203Voltage L3AV204Voltage L1-L2AV205Voltage L2-L3AV206Voltage L1-L3AV210Current 3 PhaseAV211Current L1AV212Current L2AV213Current L3AV214Current NeutralAV100Active energy import totalAV101Active energy import tariff 1AV102Active energy import tariff 2AV103Active energy import tariff 3AV104Active energy import tariff 4AV105Active energy import tariff 5AV106Active energy import tariff 6AV107Active energy export totalAV114Active energy net totalAV130Reactive energy import totalAV137Reactive energy export totalAV144Reactive energy net totalAV160Apparent energy import totalAV167Apparent energy export totalAV174Apparent energy net totalAV220Active power totalAV221Active power L1AV222Active power L2AV223Active power L3AV230Reactive power totalAV231Reactive power L1AV232Reactive power L2AV233Reactive power L3AV240Apparent power totalAV241Apparent power L1AV242Apparent power L2AV243Apparent power L3AV301THD voltage L1AV302THD voltage L2AV303THD voltage L3AV311THD voltage L1-L2AV312THD voltage L2-L3AV313THD voltage L1-L3AV321THD current L1AV322THD current L2AV323THD current L3AV324THD current neutralAV331Unbalance line voltageAV332Unbalance phase voltageAV333Unbalace currentAV341FrequencyAV346Power factor totalAV347Power factor L1AV348Power factor L2AV349Power factor L3AV400Phase angle power totalAV401Phase angle power L1AV402Phase angle power L2AV403Phase angle power L3AV404Phase angle current L1AV405Phase angle current L2AV406Phase angle current L3AV407Phase angle voltage L1AV408Phase angle voltage L2AV409Phase angle voltage L3AV501AVERAGE_VOLTAGE_L1AV502AVERAGE_VOLTAGE_L2AV503AVERAGE_VOLTAGE_L3AV504AVERAGE_VOLTAGE_L1_L2AV505AVERAGE_VOLTAGE_L2_L3AV506AVERAGE_VOLTAGE_L1_L3AV511AVERAGE_CURRENT_L1AV512AVERAGE_CURRENT_L2AV513AVERAGE_CURRENT_L3AV514AVERAGE_CURRENT_NEUTRALAV520AVERAGE_ACTIVE_POWER_TOTALAV521AVERAGE_ACTIVE_POWER_L1AV522AVERAGE_ACTIVE_POWER_L2AV523AVERAGE_ACTIVE_POWER_L3AV530AVERAGE_REACTIVE_POWER_TOTALAV531AVERAGE_REACTIVE_POWER_L1AV532AVERAGE_REACTIVE_POWER_L2AV533AVERAGE_REACTIVE_POWER_L3AV540AVERAGE_APPARENT_POWER_TOTALAV541AVERAGE_APPARENT_POWER_L1AV542AVERAGE_APPARENT_POWER_L2AV543AVERAGE_APPARENT_POWER_L3AV601MIN_VOLTAGE_L1AV602MIN_VOLTAGE_L2AV603MIN_VOLTAGE_L3AV604MIN_VOLTAGE_L1_L2AV605MIN_VOLTAGE_L2_L3AV606MIN_VOLTAGE_L1_L3AV611MIN_CURRENT_L1AV612MIN_CURRENT_L2AV613MIN_CURRENT_L3AV614MIN_CURRENT_NEUTRALAV620MIN_ACTIVE_POWER_TOTALAV621MIN_ACTIVE_POWER_L1AV622MIN_ACTIVE_POWER_L2AV623MIN_ACTIVE_POWER_L3AV630MIN_REACTIVE_POWER_TOTALAV631MIN_REACTIVE_POWER_L1AV632MIN_REACTIVE_POWER_L2AV633MIN_REACTIVE_POWER_L3AV640MIN_APPARENT_POWER_TOTALAV641MIN_APPARENT_POWER_L1AV642MIN_APPARENT_POWER_L2AV643MIN_APPARENT_POWER_L3AV701MAX_VOLTAGE_L1AV702MAX_VOLTAGE_L2AV703MAX_VOLTAGE_L3AV704MAX_VOLTAGE_L1_L2AV705MAX_VOLTAGE_L2_L3AV706MAX_VOLTAGE_L1_L3AV711MAX_CURRENT_L1AV712MAX_CURRENT_L2AV713MAX_CURRENT_L3AV714MAX_CURRENT_NEUTRALAV720MAX_ACTIVE_POWER_TOTALAV721MAX_ACTIVE_POWER_L1AV722MAX_ACTIVE_POWER_L2AV723MAX_ACTIVE_POWER_L3AV730MAX_REACTIVE_POWER_TOTALAV731MAX_REACTIVE_POWER_L1AV732MAX_REACTIVE_POWER_L2AV733MAX_REACTIVE_POWER_L3AV740MAX_APPARENT_POWER_TOTALAV741MAX_APPARENT_POWER_L1AV742MAX_APPARENT_POWER_L2AV743MAX_APPARENT_POWER_L3AV11022 Harmonics voltage L1AV11033 Harmonics voltage L1AV11044 Harmonics voltage L1AV11055 Harmonics voltage L1AV11066 Harmonics voltage L1AV11077 Harmonics voltage L1AV11088 Harmonics voltage L1AV11099 Harmonics voltage L1AV111010 Harmonics voltage L1AV111111 Harmonics voltage L1AV111212 Harmonics voltage L1AV111313 Harmonics voltage L1AV111414 Harmonics voltage L1AV111515 Harmonics voltage L1AV111616 Harmonics voltage L1AV111717 Harmonics voltage L1AV111818 Harmonics voltage L1AV111919 Harmonics voltage L1AV112020 Harmonics voltage L1AV112121 Harmonics voltage L1AV112222 Harmonics voltage L1AV112323 Harmonics voltage L1AV112424 Harmonics voltage L1AV112525 Harmonics voltage L1AV112626 Harmonics voltage L1AV112727 Harmonics voltage L1AV112828 Harmonics voltage L1AV112929 Harmonics voltage L1AV113030 Harmonics voltage L1AV113131 Harmonics voltage L1AV113232 Harmonics voltage L1AV113333 Harmonics voltage L1AV113434 Harmonics voltage L1AV113535 Harmonics voltage L1AV113636 Harmonics voltage L1AV113737 Harmonics voltage L1AV113838 Harmonics voltage L1AV113939 Harmonics voltage L1AV114040 Harmonics voltage L1AV12022 Harmonics voltage L2AV12033 Harmonics voltage L2AV12044 Harmonics voltage L2AV12055 Harmonics voltage L2AV12066 Harmonics voltage L2AV12077 Harmonics voltage L2AV12088 Harmonics voltage L2AV12099 Harmonics voltage L2AV121010 Harmonics voltage L2AV121111 Harmonics voltage L2AV121212 Harmonics voltage L2AV121313 Harmonics voltage L2AV121414 Harmonics voltage L2AV121515 Harmonics voltage L2AV121616 Harmonics voltage L2AV121717 Harmonics voltage L2AV121818 Harmonics voltage L2AV121919 Harmonics voltage L2AV122020 Harmonics voltage L2AV122121 Harmonics voltage L2AV122222 Harmonics voltage L2AV122323 Harmonics voltage L2AV122424 Harmonics voltage L2AV122525 Harmonics voltage L2AV122626 Harmonics voltage L2AV122727 Harmonics voltage L2AV122828 Harmonics voltage L2AV122929 Harmonics voltage L2AV123030 Harmonics voltage L2AV123131 Harmonics voltage L2AV123232 Harmonics voltage L2AV123333 Harmonics voltage L2AV123434 Harmonics voltage L2AV123535 Harmonics voltage L2AV123636 Harmonics voltage L2AV123737 Harmonics voltage L2AV123838 Harmonics voltage L2AV123939 Harmonics voltage L2AV124040 Harmonics voltage L2AV13022 Harmonics voltage L3AV13033 Harmonics voltage L3AV13044 Harmonics voltage L3AV13055 Harmonics voltage L3AV13066 Harmonics voltage L3AV13077 Harmonics voltage L3AV13088 Harmonics voltage L3AV13099 Harmonics voltage L3AV131010 Harmonics voltage L3AV131111 Harmonics voltage L3AV131212 Harmonics voltage L3AV131313 Harmonics voltage L3AV131414 Harmonics voltage L3AV131515 Harmonics voltage L3AV131616 Harmonics voltage L3AV131717 Harmonics voltage L3AV131818 Harmonics voltage L3AV131919 Harmonics voltage L3AV132020 Harmonics voltage L3AV132121 Harmonics voltage L3AV132222 Harmonics voltage L3AV132323 Harmonics voltage L3AV132424 Harmonics voltage L3AV132525 Harmonics voltage L3AV132626 Harmonics voltage L3AV132727 Harmonics voltage L3AV132828 Harmonics voltage L3AV132929 Harmonics voltage L3AV133030 Harmonics voltage L3AV133131 Harmonics voltage L3AV133232 Harmonics voltage L3AV133333 Harmonics voltage L3AV133434 Harmonics voltage L3AV133535 Harmonics voltage L3AV133636 Harmonics voltage L3AV133737 Harmonics voltage L3AV133838 Harmonics voltage L3AV133939 Harmonics voltage L3AV134040 Harmonics voltage L3AV14022 Harmonics voltage L1-L2AV14033 Harmonics voltage L1-L2AV14044 Harmonics voltage L1-L2AV14055 Harmonics voltage L1-L2AV14066 Harmonics voltage L1-L2AV14077 Harmonics voltage L1-L2AV14088 Harmonics voltage L1-L2AV14099 Harmonics voltage L1-L2AV141010 Harmonics voltage L1-L2AV141111 Harmonics voltage L1-L2AV141212 Harmonics voltage L1-L2AV141313 Harmonics voltage L1-L2AV141414 Harmonics voltage L1-L2AV141515 Harmonics voltage L1-L2AV141616 Harmonics voltage L1-L2AV141717 Harmonics voltage L1-L2AV141818 Harmonics voltage L1-L2AV141919 Harmonics voltage L1-L2AV142020 Harmonics voltage L1-L2AV142121 Harmonics voltage L1-L2AV142222 Harmonics voltage L1-L2AV142323 Harmonics voltage L1-L2AV142424 Harmonics voltage L1-L2AV142525 Harmonics voltage L1-L2AV142626 Harmonics voltage L1-L2AV142727 Harmonics voltage L1-L2AV142828 Harmonics voltage L1-L2AV142929 Harmonics voltage L1-L2AV143030 Harmonics voltage L1-L2AV143131 Harmonics voltage L1-L2AV143232 Harmonics voltage L1-L2AV143333 Harmonics voltage L1-L2AV143434 Harmonics voltage L1-L2AV143535 Harmonics voltage L1-L2AV143636 Harmonics voltage L1-L2AV143737 Harmonics voltage L1-L2AV143838 Harmonics voltage L1-L2AV143939 Harmonics voltage L1-L2AV144040 Harmonics voltage L1-L2AV15022 Harmonics voltage L2-L3AV15033 Harmonics voltage L2-L3AV15044 Harmonics voltage L2-L3AV15055 Harmonics voltage L2-L3AV15066 Harmonics voltage L2-L3AV15077 Harmonics voltage L2-L3AV15088 Harmonics voltage L2-L3AV15099 Harmonics voltage L2-L3AV151010 Harmonics voltage L2-L3AV151111 Harmonics voltage L2-L3AV151212 Harmonics voltage L2-L3AV151313 Harmonics voltage L2-L3AV151414 Harmonics voltage L2-L3AV151515 Harmonics voltage L2-L3AV151616 Harmonics voltage L2-L3AV151717 Harmonics voltage L2-L3AV151818 Harmonics voltage L2-L3AV151919 Harmonics voltage L2-L3AV152020 Harmonics voltage L2-L3AV152121 Harmonics voltage L2-L3AV152222 Harmonics voltage L2-L3AV152323 Harmonics voltage L2-L3AV152424 Harmonics voltage L2-L3AV152525 Harmonics voltage L2-L3AV152626 Harmonics voltage L2-L3AV152727 Harmonics voltage L2-L3AV152828 Harmonics voltage L2-L3AV152929 Harmonics voltage L2-L3AV153030 Harmonics voltage L2-L3AV153131 Harmonics voltage L2-L3AV153232 Harmonics voltage L2-L3AV153333 Harmonics voltage L2-L3AV153434 Harmonics voltage L2-L3AV153535 Harmonics voltage L2-L3AV153636 Harmonics voltage L2-L3AV153737 Harmonics voltage L2-L3AV153838 Harmonics voltage L2-L3AV153939 Harmonics voltage L2-L3AV154040 Harmonics voltage L2-L3AV16022 Harmonics voltage L1-L3AV16033 Harmonics voltage L1-L3AV16044 Harmonics voltage L1-L3AV16055 Harmonics voltage L1-L3AV16066 Harmonics voltage L1-L3AV16077 Harmonics voltage L1-L3AV16088 Harmonics voltage L1-L3AV16099 Harmonics voltage L1-L3AV161010 Harmonics voltage L1-L3AV161111 Harmonics voltage L1-L3AV161212 Harmonics voltage L1-L3AV161313 Harmonics voltage L1-L3AV161414 Harmonics voltage L1-L3AV161515 Harmonics voltage L1-L3AV161616 Harmonics voltage L1-L3AV161717 Harmonics voltage L1-L3AV161818 Harmonics voltage L1-L3AV161919 Harmonics voltage L1-L3AV162020 Harmonics voltage L1-L3AV162121 Harmonics voltage L1-L3AV162222 Harmonics voltage L1-L3AV162323 Harmonics voltage L1-L3AV162424 Harmonics voltage L1-L3AV162525 Harmonics voltage L1-L3AV162626 Harmonics voltage L1-L3AV162727 Harmonics voltage L1-L3AV162828 Harmonics voltage L1-L3AV162929 Harmonics voltage L1-L3AV163030 Harmonics voltage L1-L3AV163131 Harmonics voltage L1-L3AV163232 Harmonics voltage L1-L3AV163333 Harmonics voltage L1-L3AV163434 Harmonics voltage L1-L3AV163535 Harmonics voltage L1-L3AV163636 Harmonics voltage L1-L3AV163737 Harmonics voltage L1-L3AV163838 Harmonics voltage L1-L3AV163939 Harmonics voltage L1-L3AV164040 Harmonics voltage L1-L3AV17022 Harmonics current L1AV17033 Harmonics current L1AV17044 Harmonics current L1AV17055 Harmonics current L1AV17066 Harmonics current L1AV17077 Harmonics current L1AV17088 Harmonics current L1AV17099 Harmonics current L1AV171010 Harmonics current L1AV171111 Harmonics current L1AV171212 Harmonics current L1AV171313 Harmonics current L1AV171414 Harmonics current L1AV171515 Harmonics current L1AV171616 Harmonics current L1AV171717 Harmonics current L1AV171818 Harmonics current L1AV171919 Harmonics current L1AV172020 Harmonics current L1AV172121 Harmonics current L1AV172222 Harmonics current L1AV172323 Harmonics current L1AV172424 Harmonics current L1AV172525 Harmonics current L1AV172626 Harmonics current L1AV172727 Harmonics current L1AV172828 Harmonics current L1AV172929 Harmonics current L1AV173030 Harmonics current L1AV173131 Harmonics current L1AV173232 Harmonics current L1AV173333 Harmonics current L1AV173434 Harmonics current L1AV173535 Harmonics current L1AV173636 Harmonics current L1AV173737 Harmonics current L1AV173838 Harmonics current L1AV173939 Harmonics current L1AV174040 Harmonics current L1AV18022 Harmonics current L2AV18033 Harmonics current L2AV18044 Harmonics current L2AV18055 Harmonics current L2AV18066 Harmonics current L2AV18077 Harmonics current L2AV18088 Harmonics current L2AV18099 Harmonics current L2AV181010 Harmonics current L2AV181111 Harmonics current L2AV181212 Harmonics current L2AV181313 Harmonics current L2AV181414 Harmonics current L2AV181515 Harmonics current L2AV181616 Harmonics current L2AV181717 Harmonics current L2AV181818 Harmonics current L2AV181919 Harmonics current L2AV182020 Harmonics current L2AV182121 Harmonics current L2AV182222 Harmonics current L2AV182323 Harmonics current L2AV182424 Harmonics current L2AV182525 Harmonics current L2AV182626 Harmonics current L2AV182727 Harmonics current L2AV182828 Harmonics current L2AV182929 Harmonics current L2AV183030 Harmonics current L2AV183131 Harmonics current L2AV183232 Harmonics current L2AV183333 Harmonics current L2AV183434 Harmonics current L2AV183535 Harmonics current L2AV183636 Harmonics current L2AV183737 Harmonics current L2AV183838 Harmonics current L2AV183939 Harmonics current L2AV184040 Harmonics current L2AV19022 Harmonics current L3AV19033 Harmonics current L3AV19044 Harmonics current L3AV19055 Harmonics current L3AV19066 Harmonics current L3AV19077 Harmonics current L3AV19088 Harmonics current L3AV19099 Harmonics current L3AV191010 Harmonics current L3AV191111 Harmonics current L3AV191212 Harmonics current L3AV191313 Harmonics current L3AV191414 Harmonics current L3AV191515 Harmonics current L3AV191616 Harmonics current L3AV191717 Harmonics current L3AV191818 Harmonics current L3AV191919 Harmonics current L3AV192020 Harmonics current L3AV192121 Harmonics current L3AV192222 Harmonics current L3AV192323 Harmonics current L3AV192424 Harmonics current L3AV192525 Harmonics current L3AV192626 Harmonics current L3AV192727 Harmonics current L3AV192828 Harmonics current L3AV192929 Harmonics current L3AV193030 Harmonics current L3AV193131 Harmonics current L3AV193232 Harmonics current L3AV193333 Harmonics current L3AV193434 Harmonics current L3AV193535 Harmonics current L3AV193636 Harmonics current L3AV193737 Harmonics current L3AV193838 Harmonics current L3AV193939 Harmonics current L3AV194040 Harmonics current L3IV3301Active tariffIV3400Trafo CT Ratio L1 L2 L3 PrimaryIV3401Trafo CT Ratio L1 L2 L3 SecondaryIV3402Trafo VT Ratio PrimaryIV3403Trafo VT Ratio SecondaryIV3404Trafo CT Neutral Ratio PrimaryIV3405Trafo CT Neutral Ratio SecondaryMV3501Wiring schemeCSV3410Serial Number
Integration notes
- The manual gives no units and no access column for the measurement objects; they are read-only measurements (access inferred). The configuration IVs and the MV are marked writable in the manual.
- Harmonics objects 1102-1940 (2nd-40th harmonic of voltages L1, L2, L3, L1-L2, L2-L3, L1-L3 and currents L1, L2, L3) exist on the M4M 30 only.
- Object types come from the section headings: 3.2.2-3.2.9 Analog Value, 3.2.10 Integer Value, 3.2.11 Multi-state Value, 3.2.12 Characterstring Value.
- Some names are printed with typos (e.g. 'Unbalace current'); kept as printed.
- No segmentation; max APDU 480 octets, so split large ReadPropertyMultiple requests.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the M4M 20 / M4M 30 network analyzer (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ABB M4M 20 / M4M 30 network analyzer (BACnet IP)
How many BACnet points does the ABB M4M 20 / M4M 30 network analyzer (BACnet IP) have?
This list has 492 BACnet objects: 483 analog values, 1 multi-state value, 1 characterstring value, 7 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ABB M4M 20 / M4M 30 network analyzer (BACnet IP) BACnet points are writable?
8 of the 492 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official ABB M4M 20 / M4M 30 network analyzer (BACnet IP) BACnet documentation?
The source is M4M Network analyzers, Communication protocol BACnet manual (2CSG445052D0201 V1.00), published free by ABB at https://library.e.abb.com/public/d62e1fd302c44ea2be4506b67caae3ad/M4M%20Bacnet%20communication.pdf.
What are the minimum BACnet points to integrate the ABB M4M 20 / M4M 30 network analyzer (BACnet IP)?
Start with AV 100 Active energy import total (Imported active energy, total); AV 220 Active power total (Total active power); AV 201 Voltage L1 (Voltage L1-N); AV 204 Voltage L1-L2 (Voltage L1-L2); AV 211 Current L1 (Current L1); AV 341 Frequency (Frequency); AV 346 Power factor total (Total power factor).
How do I check these points on the real M4M 20 / M4M 30 network analyzer (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ABB BACnet points lists
- Variable frequency drive (HVAC)
ABB ACH180 HVAC drive (embedded BACnet MS/TP)
ABB ACH180 compact HVAC drives using the built-in EFB (RS-485) port with protocol set to BACnet MS/TP.
Also known as: ACH180, ACH180-01, ACH180 HVAC control program, 3AXD50000955893 - Variable frequency drive (HVAC)
ABB ACH550 HVAC drive (embedded BACnet MS/TP)
ABB ACH550 HVAC drives using the built-in RS-485 port with native BACnet MS/TP.
Also known as: ACH550, ACH550-01, ACH550-UH, ACH550 E-Clipse - Variable frequency drive bypass controller (HVAC)
ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)
ABB ACH580 drives with the E-Clipse bypass or packaged bypass (US); this list covers the bypass controller's own BACnet MS/TP objects.
Also known as: ACH580 E-Clipse, E-Clipse bypass, ACH580 packaged bypass, ACH580-BxR, 3AXD50000289554 - Variable frequency drive (HVAC)
ABB ACH580 HVAC drive (embedded BACnet MS/TP)
ABB ACH580 HVAC drives using the built-in EFB port with protocol set to BACnet MS/TP.
Also known as: ACH580, ACH580-01, ACH580-31, ACH580 E-Clipse, ACH580 HVAC control program, 3AXD50000027537 - Variable frequency drive (HVAC)
ABB ACS355 HVAC with BACnet (+N831)
ABB ACS355 machinery drives with the HVAC with BACnet firmware (option +N831, firmware 6502 or later).
Also known as: ACS355, ACS355 +N831, ACS355 HVAC, ACS355 BACnet, 3AXD50000024172 - Variable frequency drive via BACnet gateway
ABB ACS800 drive (ProtoNode FPC-N54 profile)
ABB ACS800 drives (6-pulse or active front end, standard firmware) fitted with an RMBA-01 Modbus adapter and an FPC-N54 ProtoNode.
Also known as: ACS800 BACnet, FPC-N54 ACS800, ABB ProtoNode - Variable frequency drive via BACnet gateway
ABB ACS880 drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with standard firmware (6-pulse or active front end) wired to an FPC-N54 ProtoNode over embedded Modbus RTU.
Also known as: ACS880 BACnet, FPC-N54 ACS880, ABB ProtoNode - Variable frequency drive via BACnet gateway (cooling tower fan)
ABB ACS880-CTDD cooling tower direct drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with Cooling Tower Direct Drive firmware (+N5350) that run permanent-magnet cooling tower fan motors, through an FPC-N54 ProtoNode.
Also known as: ACS880 CTDD BACnet, ACS880 +N5350, Cooling Tower Direct Drive, FPC-N54 ACS880-CTDD - Variable frequency drive (BACnet/IP adapter module)
ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
ABB FBIP-21 BACnet/IP adapter fitted to ACH480 (with BAPO-01) and ACH580 / ACH580 E-Clipse bypass drives (with CMOD-01 or CMOD-02).
Also known as: FBIP-21, FBIP21, ACH580 BACnet/IP, ACH480 BACnet/IP, ACH580 E-Clipse BACnet IP, 3AXD50000028468 - Motor softstarter
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
ABB PSTX softstarters fitted with the Anybus CompactCom BACnet MS/TP or BACnet IP fieldbus module.
Also known as: PSTX, PSTX softstarter, Anybus CompactCom BACnet, 1SFC132381M0201
Source: M4M Network analyzers, Communication protocol BACnet manual · 2CSG445052D0201 V1.00. Object names, instances and units are reproduced as published; descriptions are our own.