Easy BACnet
  1. Home
  2. BACnet points lists
  3. ABB
  4. PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)

Motor softstarter · BACnet points list

ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet points list

Updated 6 November 2026

Short answer

The PSTX softstarter talks BACnet MS/TP or BACnet IP through a plug-in Anybus CompactCom module. Binary Values carry run, fault, warning and I/O status plus start/stop, reset, motor heating, emergency mode and relay commands; Analog Values carry mains and motor electrical data, energy, temperatures, event codes and a mailbox for any other parameter. BACnet control starts only after BV 18 Control-Override-Command is set.

This page lists 95 BACnet objects for the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.

Manufacturer
ABB
Model
PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
Equipment
Motor softstarter
Equipment type
Other equipment
BACnet objects
95 (22 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
4194303
Also known as
PSTX, PSTX softstarter, Anybus CompactCom BACnet, 1SFC132381M0201
Source document
Softstarter type PSTX, Fieldbus communication, Anybus CompactCom BACnet MS/TP and BACnet IP · 1SFC132381M0201 Rev C · rev. 2024-07-27
Download CSV 95 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.

BMS integration notes: ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)

Integration in brief

Set 12.02 FB interface connector = Anybus and a valid device instance in 12.33 (the default 4194303 does not work), plus the IP or MS/TP address. Write BV 18 = On to give BACnet control, then start/stop with BV 10 and reset faults with BV 14. Read run, fault and ready status and the motor current.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10RUN-STOP-Command-[0=Stop][1=Run]Start / stop command (1 = run)Write
BV 18Control-Override-Command-[0=Off][1=On]Must be On for BACnet to control the starterWrite
BV 14Event-Reset-Command-[0=No-Reset][1=Reset]Reset events / faultsWrite
BV 0RUN-STOP-Monitor-[0=Stop][1=Run]Running statusRead
BV 7Ready-To-Start-Monitor-[0=Not-Ready][1=Ready]Ready to startRead
BV 4REMOTE-LOCAL-Monitor-[0=Remote][1=Local]Remote / local modeRead
AV 4Output-Current-[A]Motor current, ARead
AV 6Output-Power-[kW]Output power, kWRead
BV 2Fault-Monitor-[0=OK][1=Fault]Any active faultRead
AV 125Active-FaultActive fault codeRead

Enable & remote start

Write BV 18 Control-Override-Command = 1 (On) to put the softstarter in BACnet control; BACnet then overrides the DI logic for start/stop, motor heating, lock parameters, emergency mode, user-defined trip and stand still brake. Local control from the HMI always has priority. Parameter 12.03 Fieldbus control is not needed for control; it only enables the timeout protection.

Heartbeat & communication loss

BACnet has no built-in timeout. To trip on lost communication set 12.03 Fieldbus control = On, 19.03 Fieldbus failure out (event group), 19.04 Fieldbus failure op (action) and 19.12 Fieldbus failure timeout (seconds without a message).

Network setup

Watch out for

ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

95 of 95 shown
Type
AnalogBinary
Access
Show
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet Points List
DescriptionStates
BVmin0RUN-STOP-Monitor-[0=Stop][1=Run]Run status (ramp or bypass)Read0=Stop, 1=Run
BVmin2Fault-Monitor-[0=OK][1=Fault]Fault status of softstarterRead0=OK, 1=Fault
BVmin4REMOTE-LOCAL-Monitor-[0=Remote][1=Local]Operating modeRead0=Remote, 1=Local
BV5Warning-Monitor-[0=OK][1=Warning]Warning status of softstarterRead0=OK, 1=Warning
BVmin7Ready-To-Start-Monitor-[0=Not-Ready][1=Ready]Ready to startRead0=Not-Ready, 1=Ready
BV9Enable-Monitor-[0=Disabled][1=Enabled]Enable status of softstarterRead0=Disabled, 1=Enabled
BVmin10RUN-STOP-Command-[0=Stop][1=Run]Start softstarterWrite0=Stop, 1=Run
BVmin14Event-Reset-Command-[0=No-Reset][1=Reset]Reset eventWrite0=No-Reset, 1=Reset
BVmin18Control-Override-Command-[0=Off][1=On]Take BACnet control of the softstarter (local panel has priority)Write0=Off, 1=On
BV19Control-Override-Monitor-[0=Off][1=On]Shows BACnet control override is activeRead0=Off, 1=On
BV28Motor-Heating-Command-[0=Off][1=On]Run motor heatingWrite0=Off, 1=On
BV29Motor-Heating-Monitor-[0=Off][1=On]Status of motor heating modeRead0=Off, 1=On
BV71In0-Input-Monitor-[0=Off][1=On]Status of In0 digital inputRead0=Off, 1=On
BV72In1-Input-Monitor-[0=Off][1=On]Status of In1 digital inputRead0=Off, 1=On
BV73In2-Input-Monitor-[0=Off][1=On]Status of In2 digital inputRead0=Off, 1=On
BV741DI0-Input-Monitor-[0=Off][1=On]Status of 1DI0 external I/O digital inputRead0=Off, 1=On
BV751DI1-Input-Monitor-[0=Off][1=On]Status of 1DI1 external I/O digital inputRead0=Off, 1=On
BV761DI2-Input-Monitor-[0=Off][1=On]Status of 1DI2 external I/O digital inputRead0=Off, 1=On
BV771DI3-Input-Monitor-[0=Off][1=On]Status of 1DI3 external I/O digital inputRead0=Off, 1=On
BV781DI4-Input-Monitor-[0=Off][1=On]Status of 1DI4 external I/O digital inputRead0=Off, 1=On
BV792DI5-Input-Monitor-[0=Off][1=On]Status of 2DI5 external I/O digital inputRead0=Off, 1=On
BV802DI6-Input-Monitor-[0=Off][1=On]Status of 2DI6 external I/O digital inputRead0=Off, 1=On
BV812DI7-Input-Monitor-[0=Off][1=On]Status of 2DI7 external I/O digital inputRead0=Off, 1=On
BV82K4-Relay-Monitor-[0=Off][1=On]Status of K4 relayRead0=Off, 1=On
BV83K5-Relay-Monitor-[0=Off][1=On]Status of K5 relayRead0=Off, 1=On
BV84K6-Relay-Monitor-[0=Off][1=On]Status of K6 relayRead0=Off, 1=On
BV85K4-Relay-Command-[0=Off][1=On]Output state of K4 relayWrite0=Off, 1=On
BV86K5-Relay-Command-[0=Off][1=On]Output state of K5 relayWrite0=Off, 1=On
BV87K6-Relay-Command-[0=Off][1=On]Output state of K6 relayWrite0=Off, 1=On
BV881DO0-Output-Monitor-[0=Off][1=On]Status of 1DO0 external I/O digital outputRead0=Off, 1=On
BV891DO1-Output-Monitor-[0=Off][1=On]Status of 1DO1 external I/O digital outputRead0=Off, 1=On
BV902DO2-Output-Monitor-[0=Off][1=On]Status of 2DO2 external I/O digital outputRead0=Off, 1=On
BV912DO3-Output-Monitor-[0=Off][1=On]Status of 2DO3 external I/O digital outputRead0=Off, 1=On
BV921DO0-Output-Command-[0=Off][1=On]Output state of 1DO0 external I/O digital outputWrite0=Off, 1=On
BV931DO1-Output-Command-[0=Off][1=On]Output state of 1DO1 external I/O digital outputWrite0=Off, 1=On
BV942DO2-Output-Command-[0=Off][1=On]Output state of 2DO2 external I/O digital outputWrite0=Off, 1=On
BV952DO3-Output-Command-[0=Off][1=On]Output state of 2DO3 external I/O digital outputWrite0=Off, 1=On
BV96Lock-Parameters-Command-[0=No-Lock][1=Lock]Lock parametersWrite0=No-Lock, 1=Lock
BV97Event-Monitor-[0=OK][1=Event]Event status of softstarterRead0=OK, 1=Event
BV98Stop-Monitor-[0=Not-Stopped][1=Stopped]Stop statusRead0=Not-Stopped, 1=Stopped
BV99Event-Reset-Monitor-[0=No-Reset][1=Reset]Event reset status of softstarterRead0=No-Reset, 1=Reset
BV100Top-Of-Ramp-Monitor-[0=Not-TOR][1=TOR]Top of ramp: active in bypass modeRead0=Not-TOR, 1=TOR
BV101Emergency-Mode-Command-[0=Off][1=On]Set the softstarter in emergency modeWrite0=Off, 1=On
BV102Emergency-Mode-Monitor-[0=Off][1=On]Emergency mode status of softstarterRead0=Off, 1=On
BV103User-Defined-Trip-Command-[0=Off][1=On]Trip the user defined protection functionWrite0=Off, 1=On
BV104User-Defined-Trip-Monitor-[0=Off][1=On]User defined protection trip statusRead0=Off, 1=On
BV105Stand-Still-Brake-Command-[0=Off][1=On]Run stand still brakeWrite0=Off, 1=On
BV106Stand-Still-Brake-Monitor-[0=Off][1=On]Status of stand still brake modeRead0=Off, 1=On
BV107Refresh-FB-Parameters-[0=Off][1=On]Restart fieldbus interface to refresh communication parametersWrite0=Off, 1=On
AV1Mains-Frequency-[Hz]Mains frequency in HzHzRead
AV3Output-Voltage-[percent]AC output voltage in percent%Read
AVmin4Output-Current-[A]Output RMS current in AARead
AVmin6Output-Power-[kW]Output active power in kWkWRead
AV7Operating-Temperature-Range-[degree]Thyristor temperature in degreesRead
AV9KiloWatt-Hour-Meter-NR-[kWh]Softstarter’s cumulative active energy usage in kWhkWhRead
AV14Running-Hours-[h]Motor’s resettable run timehRead
AV15Motor-Temperature-[percent]Motor temperature in percent%Read
AV18Active-Event-CodeMost recent active event code (hex, see manual 10.3)Read
AV21Analog-Out-Monitor-[percent]Output level of Analog output%Read
AV221AO0-Analog-Out-Monitor-[percent]Output level of 1AO0 external I/O Analog output%Read
AV25Mailbox-ParameterFieldbus ID of the parameter for the mailboxWrite
AV26Mailbox-DataMailbox data: reads or writes the parameter in AV 25Write
AV28Motor-Heating-Capacity-[W]Set the heating capacity in W to be generated in the motorWWrite
AV32Output-Current-Range-[percent]Motor current in percent of rated current IE%Read
AV104L1-Current-[A]Phase L1 RMS current in AARead
AV105L2-Current-[A]Phase L2 RMS current in AARead
AV106L3-Current-[A]Phase L3 RMS current in AARead
AV107Output-Power-[HP]Output active power in HPhpRead
AV108Apparent-Power-[kVA]Apparent power in kVAkVARead
AV109Reactive-Power-[kVAr]Reactive power in kVArkVARRead
AV110Mains-Voltage-[V]Mains voltage in VVRead
AV111Power-FactorPower factorRead
AV112Reactive-Energy-[kVArH]Softstarter’s cumulative reactive energy usage in kVArHkVARhRead
AV113EOL-Time-To-Trip-[s]Time until the EOL protection tripssRead
AV114EOL-Time-To-Cool-[s]Time until reset is possible after an EOL tripsRead
AV115Max-Phase-Current-[A]Max of the three RMS phase currents in [A]ARead
AV116Thyristor-Running-Hours-[h]Thyristor run time in hourshRead
AV117Number-Of-StartsTotal number of startsRead
AV118PT100-Temperature-[degree]PT100 temperature in degreesRead
AV119PTC-Resistance-[Ohm]PTC resistance in OhmΩRead
AV120Rem-Time-To-Start-[s]Remaining time to start in secondssRead
AV121Operating-Temperature-Range-[percent]Thyristor temperature in percent%Read
AV122Heat-Sink-Temperature-Range-[degree]Heat sink temperature in degreesRead
AV123Analog-Out-Command-[percent]Controls Analog output%Write
AV1241AO0-Analog-Out-Command-[percent]Controls 1AO0 External I/O Analog output%Write
AVmin125Active-FaultMost recent active fault code (see notes)Read
AV126Active-WarningMost recent active warning codeRead
AV127Active-ProtectionMost recent active protection codeRead
AV128Motor-ConnectionMotor connection detectedRead0=Auto, 1=In Line, 2=Inside delta UI, 3=Inside delta IU, 4=Two phase (L1 shorted), 5=Two phase (L2 shorted), 6=Two phase (L3 shorted), 7=Unknown
AV129Phase-SequencePhase sequence detectedRead0=L1->L2->L3, 1=L1->L3->L2, 2=Unknown
AV130Kilowatt-Hour-This-Hour-[kWh]Current hour energy consumption in kWhkWhRead
AV131Kilowatt-Hour-Last-Hour-[kWh]Last hour energy consumption in kWhkWhRead
AV132Kilowatt-Hour-This-Day-[kWh]Current day energy consumption in kWhkWhRead
AV133Kilowatt-Hour-Last-Day-[kWh]Last day energy consumption in kWhkWhRead
AV134Stand-Still-Brake-Strength-[percent]Set the stand still brake strength in percent%Write
Object ID lookup: ABB PSTX Softstarter BACnet point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)

How many BACnet points does the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) have?

This list has 95 BACnet objects: 46 analog values, 49 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet points are writable?

22 of the 95 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet documentation?

The source is Softstarter type PSTX, Fieldbus communication, Anybus CompactCom BACnet MS/TP and BACnet IP (1SFC132381M0201 Rev C), revision 2024-07-27, published free by ABB at https://library.e.abb.com/public/f4d2da121be743f4b4172f7534c2c19c/1SFC132381M0201_PSTX_AB_BACnet.pdf.

What are the minimum BACnet points to integrate the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?

Start with BV 10 RUN-STOP-Command-[0=Stop][1=Run] (Start / stop command (1 = run)); BV 18 Control-Override-Command-[0=Off][1=On] (Must be On for BACnet to control the starter); BV 14 Event-Reset-Command-[0=No-Reset][1=Reset] (Reset events / faults); BV 0 RUN-STOP-Monitor-[0=Stop][1=Run] (Running status); BV 7 Ready-To-Start-Monitor-[0=Not-Ready][1=Ready] (Ready to start); BV 4 REMOTE-LOCAL-Monitor-[0=Remote][1=Local] (Remote / local mode); AV 4 Output-Current-[A] (Motor current, A); AV 6 Output-Power-[kW] (Output power, kW); BV 2 Fault-Monitor-[0=OK][1=Fault] (Any active fault); AV 125 Active-Fault (Active fault code).

How do I enable BMS control of the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?

Write BV 18 Control-Override-Command = 1 (On) to put the softstarter in BACnet control; BACnet then overrides the DI logic for start/stop, motor heating, lock parameters, emergency mode, user-defined trip and stand still brake. Local control from the HMI always has priority. Parameter 12.03 Fieldbus control is not needed for control; it only enables the timeout protection.

Does the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) need a BACnet heartbeat or have a communication timeout?

BACnet has no built-in timeout. To trip on lost communication set 12.03 Fieldbus control = On, 19.03 Fieldbus failure out (event group), 19.04 Fieldbus failure op (action) and 19.12 Fieldbus failure timeout (seconds without a message).

How do I check these points on the real PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ABB BACnet points lists

Source: Softstarter type PSTX, Fieldbus communication, Anybus CompactCom BACnet MS/TP and BACnet IP · 1SFC132381M0201 Rev C · rev. 2024-07-27. Object names, instances and units are reproduced as published; descriptions are our own.