Motor softstarter · BACnet points list
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet points list
Updated 6 November 2026
The PSTX softstarter talks BACnet MS/TP or BACnet IP through a plug-in Anybus CompactCom module. Binary Values carry run, fault, warning and I/O status plus start/stop, reset, motor heating, emergency mode and relay commands; Analog Values carry mains and motor electrical data, energy, temperatures, event codes and a mailbox for any other parameter. BACnet control starts only after BV 18 Control-Override-Command is set.
This page lists 95 BACnet objects for the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ABB’s own free documentation, linked below.
- Manufacturer
- ABB
- Model
- PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
- Equipment
- Motor softstarter
- Equipment type
- Other equipment
- BACnet objects
- 95 (22 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 4194303
- Also known as
- PSTX, PSTX softstarter, Anybus CompactCom BACnet, 1SFC132381M0201
Reference only, provided as-is: verify against ABB’s current documentation and the live device before use. Not official ABB information. Terms of use.
BMS integration notes: ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
Set 12.02 FB interface connector = Anybus and a valid device instance in 12.33 (the default 4194303 does not work), plus the IP or MS/TP address. Write BV 18 = On to give BACnet control, then start/stop with BV 10 and reset faults with BV 14. Read run, fault and ready status and the motor current.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10 | RUN-STOP-Command-[0=Stop][1=Run] | Start / stop command (1 = run) | Write |
| BV 18 | Control-Override-Command-[0=Off][1=On] | Must be On for BACnet to control the starter | Write |
| BV 14 | Event-Reset-Command-[0=No-Reset][1=Reset] | Reset events / faults | Write |
| BV 0 | RUN-STOP-Monitor-[0=Stop][1=Run] | Running status | Read |
| BV 7 | Ready-To-Start-Monitor-[0=Not-Ready][1=Ready] | Ready to start | Read |
| BV 4 | REMOTE-LOCAL-Monitor-[0=Remote][1=Local] | Remote / local mode | Read |
| AV 4 | Output-Current-[A] | Motor current, A | Read |
| AV 6 | Output-Power-[kW] | Output power, kW | Read |
| BV 2 | Fault-Monitor-[0=OK][1=Fault] | Any active fault | Read |
| AV 125 | Active-Fault | Active fault code | Read |
Enable & remote start
Write BV 18 Control-Override-Command = 1 (On) to put the softstarter in BACnet control; BACnet then overrides the DI logic for start/stop, motor heating, lock parameters, emergency mode, user-defined trip and stand still brake. Local control from the HMI always has priority. Parameter 12.03 Fieldbus control is not needed for control; it only enables the timeout protection.
Heartbeat & communication loss
BACnet has no built-in timeout. To trip on lost communication set 12.03 Fieldbus control = On, 19.03 Fieldbus failure out (event group), 19.04 Fieldbus failure op (action) and 19.12 Fieldbus failure timeout (seconds without a message).
Network setup
- 12.02 FB interface connector = Anybus.
- 12.33 Fieldbus BACnet Device Instance: 0-4194302; the default 4194303 is invalid and communication will not work.
- BACnet IP: 12.05 IP address; foreign device registration with 12.34 BBMD IP, 12.35 BBMD UDP port and 12.36 registration interval.
- BACnet MS/TP: 12.04 MAC address 0-127; baud 9600-76800.
- Power-cycle, or set 12.02 to None and back to Anybus, after changing communication parameters.
Watch out for
- The HMI local mode always beats BACnet control override.
- Restoring default object names needs a full parameter reset from the HMI, which also resets the communication parameters.
- Device Communication Control default password is Admin.
ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | RUN-STOP-Monitor-[0=Stop][1=Run] | Run status (ramp or bypass) | Read | 0=Stop, 1=Run | |
| BVmin | 2 | Fault-Monitor-[0=OK][1=Fault] | Fault status of softstarter | Read | 0=OK, 1=Fault | |
| BVmin | 4 | REMOTE-LOCAL-Monitor-[0=Remote][1=Local] | Operating mode | Read | 0=Remote, 1=Local | |
| BV | 5 | Warning-Monitor-[0=OK][1=Warning] | Warning status of softstarter | Read | 0=OK, 1=Warning | |
| BVmin | 7 | Ready-To-Start-Monitor-[0=Not-Ready][1=Ready] | Ready to start | Read | 0=Not-Ready, 1=Ready | |
| BV | 9 | Enable-Monitor-[0=Disabled][1=Enabled] | Enable status of softstarter | Read | 0=Disabled, 1=Enabled | |
| BVmin | 10 | RUN-STOP-Command-[0=Stop][1=Run] | Start softstarter | Write | 0=Stop, 1=Run | |
| BVmin | 14 | Event-Reset-Command-[0=No-Reset][1=Reset] | Reset event | Write | 0=No-Reset, 1=Reset | |
| BVmin | 18 | Control-Override-Command-[0=Off][1=On] | Take BACnet control of the softstarter (local panel has priority) | Write | 0=Off, 1=On | |
| BV | 19 | Control-Override-Monitor-[0=Off][1=On] | Shows BACnet control override is active | Read | 0=Off, 1=On | |
| BV | 28 | Motor-Heating-Command-[0=Off][1=On] | Run motor heating | Write | 0=Off, 1=On | |
| BV | 29 | Motor-Heating-Monitor-[0=Off][1=On] | Status of motor heating mode | Read | 0=Off, 1=On | |
| BV | 71 | In0-Input-Monitor-[0=Off][1=On] | Status of In0 digital input | Read | 0=Off, 1=On | |
| BV | 72 | In1-Input-Monitor-[0=Off][1=On] | Status of In1 digital input | Read | 0=Off, 1=On | |
| BV | 73 | In2-Input-Monitor-[0=Off][1=On] | Status of In2 digital input | Read | 0=Off, 1=On | |
| BV | 74 | 1DI0-Input-Monitor-[0=Off][1=On] | Status of 1DI0 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 75 | 1DI1-Input-Monitor-[0=Off][1=On] | Status of 1DI1 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 76 | 1DI2-Input-Monitor-[0=Off][1=On] | Status of 1DI2 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 77 | 1DI3-Input-Monitor-[0=Off][1=On] | Status of 1DI3 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 78 | 1DI4-Input-Monitor-[0=Off][1=On] | Status of 1DI4 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 79 | 2DI5-Input-Monitor-[0=Off][1=On] | Status of 2DI5 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 80 | 2DI6-Input-Monitor-[0=Off][1=On] | Status of 2DI6 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 81 | 2DI7-Input-Monitor-[0=Off][1=On] | Status of 2DI7 external I/O digital input | Read | 0=Off, 1=On | |
| BV | 82 | K4-Relay-Monitor-[0=Off][1=On] | Status of K4 relay | Read | 0=Off, 1=On | |
| BV | 83 | K5-Relay-Monitor-[0=Off][1=On] | Status of K5 relay | Read | 0=Off, 1=On | |
| BV | 84 | K6-Relay-Monitor-[0=Off][1=On] | Status of K6 relay | Read | 0=Off, 1=On | |
| BV | 85 | K4-Relay-Command-[0=Off][1=On] | Output state of K4 relay | Write | 0=Off, 1=On | |
| BV | 86 | K5-Relay-Command-[0=Off][1=On] | Output state of K5 relay | Write | 0=Off, 1=On | |
| BV | 87 | K6-Relay-Command-[0=Off][1=On] | Output state of K6 relay | Write | 0=Off, 1=On | |
| BV | 88 | 1DO0-Output-Monitor-[0=Off][1=On] | Status of 1DO0 external I/O digital output | Read | 0=Off, 1=On | |
| BV | 89 | 1DO1-Output-Monitor-[0=Off][1=On] | Status of 1DO1 external I/O digital output | Read | 0=Off, 1=On | |
| BV | 90 | 2DO2-Output-Monitor-[0=Off][1=On] | Status of 2DO2 external I/O digital output | Read | 0=Off, 1=On | |
| BV | 91 | 2DO3-Output-Monitor-[0=Off][1=On] | Status of 2DO3 external I/O digital output | Read | 0=Off, 1=On | |
| BV | 92 | 1DO0-Output-Command-[0=Off][1=On] | Output state of 1DO0 external I/O digital output | Write | 0=Off, 1=On | |
| BV | 93 | 1DO1-Output-Command-[0=Off][1=On] | Output state of 1DO1 external I/O digital output | Write | 0=Off, 1=On | |
| BV | 94 | 2DO2-Output-Command-[0=Off][1=On] | Output state of 2DO2 external I/O digital output | Write | 0=Off, 1=On | |
| BV | 95 | 2DO3-Output-Command-[0=Off][1=On] | Output state of 2DO3 external I/O digital output | Write | 0=Off, 1=On | |
| BV | 96 | Lock-Parameters-Command-[0=No-Lock][1=Lock] | Lock parameters | Write | 0=No-Lock, 1=Lock | |
| BV | 97 | Event-Monitor-[0=OK][1=Event] | Event status of softstarter | Read | 0=OK, 1=Event | |
| BV | 98 | Stop-Monitor-[0=Not-Stopped][1=Stopped] | Stop status | Read | 0=Not-Stopped, 1=Stopped | |
| BV | 99 | Event-Reset-Monitor-[0=No-Reset][1=Reset] | Event reset status of softstarter | Read | 0=No-Reset, 1=Reset | |
| BV | 100 | Top-Of-Ramp-Monitor-[0=Not-TOR][1=TOR] | Top of ramp: active in bypass mode | Read | 0=Not-TOR, 1=TOR | |
| BV | 101 | Emergency-Mode-Command-[0=Off][1=On] | Set the softstarter in emergency mode | Write | 0=Off, 1=On | |
| BV | 102 | Emergency-Mode-Monitor-[0=Off][1=On] | Emergency mode status of softstarter | Read | 0=Off, 1=On | |
| BV | 103 | User-Defined-Trip-Command-[0=Off][1=On] | Trip the user defined protection function | Write | 0=Off, 1=On | |
| BV | 104 | User-Defined-Trip-Monitor-[0=Off][1=On] | User defined protection trip status | Read | 0=Off, 1=On | |
| BV | 105 | Stand-Still-Brake-Command-[0=Off][1=On] | Run stand still brake | Write | 0=Off, 1=On | |
| BV | 106 | Stand-Still-Brake-Monitor-[0=Off][1=On] | Status of stand still brake mode | Read | 0=Off, 1=On | |
| BV | 107 | Refresh-FB-Parameters-[0=Off][1=On] | Restart fieldbus interface to refresh communication parameters | Write | 0=Off, 1=On | |
| AV | 1 | Mains-Frequency-[Hz] | Mains frequency in Hz | Hz | Read | |
| AV | 3 | Output-Voltage-[percent] | AC output voltage in percent | % | Read | |
| AVmin | 4 | Output-Current-[A] | Output RMS current in A | A | Read | |
| AVmin | 6 | Output-Power-[kW] | Output active power in kW | kW | Read | |
| AV | 7 | Operating-Temperature-Range-[degree] | Thyristor temperature in degrees | Read | ||
| AV | 9 | KiloWatt-Hour-Meter-NR-[kWh] | Softstarter’s cumulative active energy usage in kWh | kWh | Read | |
| AV | 14 | Running-Hours-[h] | Motor’s resettable run time | h | Read | |
| AV | 15 | Motor-Temperature-[percent] | Motor temperature in percent | % | Read | |
| AV | 18 | Active-Event-Code | Most recent active event code (hex, see manual 10.3) | Read | ||
| AV | 21 | Analog-Out-Monitor-[percent] | Output level of Analog output | % | Read | |
| AV | 22 | 1AO0-Analog-Out-Monitor-[percent] | Output level of 1AO0 external I/O Analog output | % | Read | |
| AV | 25 | Mailbox-Parameter | Fieldbus ID of the parameter for the mailbox | Write | ||
| AV | 26 | Mailbox-Data | Mailbox data: reads or writes the parameter in AV 25 | Write | ||
| AV | 28 | Motor-Heating-Capacity-[W] | Set the heating capacity in W to be generated in the motor | W | Write | |
| AV | 32 | Output-Current-Range-[percent] | Motor current in percent of rated current IE | % | Read | |
| AV | 104 | L1-Current-[A] | Phase L1 RMS current in A | A | Read | |
| AV | 105 | L2-Current-[A] | Phase L2 RMS current in A | A | Read | |
| AV | 106 | L3-Current-[A] | Phase L3 RMS current in A | A | Read | |
| AV | 107 | Output-Power-[HP] | Output active power in HP | hp | Read | |
| AV | 108 | Apparent-Power-[kVA] | Apparent power in kVA | kVA | Read | |
| AV | 109 | Reactive-Power-[kVAr] | Reactive power in kVAr | kVAR | Read | |
| AV | 110 | Mains-Voltage-[V] | Mains voltage in V | V | Read | |
| AV | 111 | Power-Factor | Power factor | Read | ||
| AV | 112 | Reactive-Energy-[kVArH] | Softstarter’s cumulative reactive energy usage in kVArH | kVARh | Read | |
| AV | 113 | EOL-Time-To-Trip-[s] | Time until the EOL protection trips | s | Read | |
| AV | 114 | EOL-Time-To-Cool-[s] | Time until reset is possible after an EOL trip | s | Read | |
| AV | 115 | Max-Phase-Current-[A] | Max of the three RMS phase currents in [A] | A | Read | |
| AV | 116 | Thyristor-Running-Hours-[h] | Thyristor run time in hours | h | Read | |
| AV | 117 | Number-Of-Starts | Total number of starts | Read | ||
| AV | 118 | PT100-Temperature-[degree] | PT100 temperature in degrees | Read | ||
| AV | 119 | PTC-Resistance-[Ohm] | PTC resistance in Ohm | Ω | Read | |
| AV | 120 | Rem-Time-To-Start-[s] | Remaining time to start in seconds | s | Read | |
| AV | 121 | Operating-Temperature-Range-[percent] | Thyristor temperature in percent | % | Read | |
| AV | 122 | Heat-Sink-Temperature-Range-[degree] | Heat sink temperature in degrees | Read | ||
| AV | 123 | Analog-Out-Command-[percent] | Controls Analog output | % | Write | |
| AV | 124 | 1AO0-Analog-Out-Command-[percent] | Controls 1AO0 External I/O Analog output | % | Write | |
| AVmin | 125 | Active-Fault | Most recent active fault code (see notes) | Read | ||
| AV | 126 | Active-Warning | Most recent active warning code | Read | ||
| AV | 127 | Active-Protection | Most recent active protection code | Read | ||
| AV | 128 | Motor-Connection | Motor connection detected | Read | 0=Auto, 1=In Line, 2=Inside delta UI, 3=Inside delta IU, 4=Two phase (L1 shorted), 5=Two phase (L2 shorted), 6=Two phase (L3 shorted), 7=Unknown | |
| AV | 129 | Phase-Sequence | Phase sequence detected | Read | 0=L1->L2->L3, 1=L1->L3->L2, 2=Unknown | |
| AV | 130 | Kilowatt-Hour-This-Hour-[kWh] | Current hour energy consumption in kWh | kWh | Read | |
| AV | 131 | Kilowatt-Hour-Last-Hour-[kWh] | Last hour energy consumption in kWh | kWh | Read | |
| AV | 132 | Kilowatt-Hour-This-Day-[kWh] | Current day energy consumption in kWh | kWh | Read | |
| AV | 133 | Kilowatt-Hour-Last-Day-[kWh] | Last day energy consumption in kWh | kWh | Read | |
| AV | 134 | Stand-Still-Brake-Strength-[percent] | Set the stand still brake strength in percent | % | Write |
No points match these filters.
Object ID lookup: ABB PSTX Softstarter BACnet point IDs by name
BV0RUN-STOP-Monitor-[0=Stop][1=Run]BV2Fault-Monitor-[0=OK][1=Fault]BV4REMOTE-LOCAL-Monitor-[0=Remote][1=Local]BV5Warning-Monitor-[0=OK][1=Warning]BV7Ready-To-Start-Monitor-[0=Not-Ready][1=Ready]BV9Enable-Monitor-[0=Disabled][1=Enabled]BV10RUN-STOP-Command-[0=Stop][1=Run]BV14Event-Reset-Command-[0=No-Reset][1=Reset]BV18Control-Override-Command-[0=Off][1=On]BV19Control-Override-Monitor-[0=Off][1=On]BV28Motor-Heating-Command-[0=Off][1=On]BV29Motor-Heating-Monitor-[0=Off][1=On]BV71In0-Input-Monitor-[0=Off][1=On]BV72In1-Input-Monitor-[0=Off][1=On]BV73In2-Input-Monitor-[0=Off][1=On]BV741DI0-Input-Monitor-[0=Off][1=On]BV751DI1-Input-Monitor-[0=Off][1=On]BV761DI2-Input-Monitor-[0=Off][1=On]BV771DI3-Input-Monitor-[0=Off][1=On]BV781DI4-Input-Monitor-[0=Off][1=On]BV792DI5-Input-Monitor-[0=Off][1=On]BV802DI6-Input-Monitor-[0=Off][1=On]BV812DI7-Input-Monitor-[0=Off][1=On]BV82K4-Relay-Monitor-[0=Off][1=On]BV83K5-Relay-Monitor-[0=Off][1=On]BV84K6-Relay-Monitor-[0=Off][1=On]BV85K4-Relay-Command-[0=Off][1=On]BV86K5-Relay-Command-[0=Off][1=On]BV87K6-Relay-Command-[0=Off][1=On]BV881DO0-Output-Monitor-[0=Off][1=On]BV891DO1-Output-Monitor-[0=Off][1=On]BV902DO2-Output-Monitor-[0=Off][1=On]BV912DO3-Output-Monitor-[0=Off][1=On]BV921DO0-Output-Command-[0=Off][1=On]BV931DO1-Output-Command-[0=Off][1=On]BV942DO2-Output-Command-[0=Off][1=On]BV952DO3-Output-Command-[0=Off][1=On]BV96Lock-Parameters-Command-[0=No-Lock][1=Lock]BV97Event-Monitor-[0=OK][1=Event]BV98Stop-Monitor-[0=Not-Stopped][1=Stopped]BV99Event-Reset-Monitor-[0=No-Reset][1=Reset]BV100Top-Of-Ramp-Monitor-[0=Not-TOR][1=TOR]BV101Emergency-Mode-Command-[0=Off][1=On]BV102Emergency-Mode-Monitor-[0=Off][1=On]BV103User-Defined-Trip-Command-[0=Off][1=On]BV104User-Defined-Trip-Monitor-[0=Off][1=On]BV105Stand-Still-Brake-Command-[0=Off][1=On]BV106Stand-Still-Brake-Monitor-[0=Off][1=On]BV107Refresh-FB-Parameters-[0=Off][1=On]AV1Mains-Frequency-[Hz]AV3Output-Voltage-[percent]AV4Output-Current-[A]AV6Output-Power-[kW]AV7Operating-Temperature-Range-[degree]AV9KiloWatt-Hour-Meter-NR-[kWh]AV14Running-Hours-[h]AV15Motor-Temperature-[percent]AV18Active-Event-CodeAV21Analog-Out-Monitor-[percent]AV221AO0-Analog-Out-Monitor-[percent]AV25Mailbox-ParameterAV26Mailbox-DataAV28Motor-Heating-Capacity-[W]AV32Output-Current-Range-[percent]AV104L1-Current-[A]AV105L2-Current-[A]AV106L3-Current-[A]AV107Output-Power-[HP]AV108Apparent-Power-[kVA]AV109Reactive-Power-[kVAr]AV110Mains-Voltage-[V]AV111Power-FactorAV112Reactive-Energy-[kVArH]AV113EOL-Time-To-Trip-[s]AV114EOL-Time-To-Cool-[s]AV115Max-Phase-Current-[A]AV116Thyristor-Running-Hours-[h]AV117Number-Of-StartsAV118PT100-Temperature-[degree]AV119PTC-Resistance-[Ohm]AV120Rem-Time-To-Start-[s]AV121Operating-Temperature-Range-[percent]AV122Heat-Sink-Temperature-Range-[degree]AV123Analog-Out-Command-[percent]AV1241AO0-Analog-Out-Command-[percent]AV125Active-FaultAV126Active-WarningAV127Active-ProtectionAV128Motor-ConnectionAV129Phase-SequenceAV130Kilowatt-Hour-This-Hour-[kWh]AV131Kilowatt-Hour-Last-Hour-[kWh]AV132Kilowatt-Hour-This-Day-[kWh]AV133Kilowatt-Hour-Last-Day-[kWh]AV134Stand-Still-Brake-Strength-[percent]
Integration notes
- Instance gaps are reserved by ABB and do not exist.
- BV 9 Enable-Monitor has no access mark in the manual; listed as read-only.
- AV 125 fault codes include 0 none, 1 high current, 2 phase loss, 3 heat sink overtemperature, 4 bad network quality and more; AV 126 / AV 127 list warning and protection codes the same way (see the manual pp24-25).
- Temperatures are printed as 'in degrees' without a unit; no unit is shown.
- Ranges such as '10 x nominal current' depend on the softstarter size.
- Any other PSTX parameter can be read or written through the mailbox: write its fieldbus ID to AV 25, then read or write AV 26.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)
How many BACnet points does the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) have?
This list has 95 BACnet objects: 46 analog values, 49 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet points are writable?
22 of the 95 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) BACnet documentation?
The source is Softstarter type PSTX, Fieldbus communication, Anybus CompactCom BACnet MS/TP and BACnet IP (1SFC132381M0201 Rev C), revision 2024-07-27, published free by ABB at https://library.e.abb.com/public/f4d2da121be743f4b4172f7534c2c19c/1SFC132381M0201_PSTX_AB_BACnet.pdf.
What are the minimum BACnet points to integrate the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?
Start with BV 10 RUN-STOP-Command-[0=Stop][1=Run] (Start / stop command (1 = run)); BV 18 Control-Override-Command-[0=Off][1=On] (Must be On for BACnet to control the starter); BV 14 Event-Reset-Command-[0=No-Reset][1=Reset] (Reset events / faults); BV 0 RUN-STOP-Monitor-[0=Stop][1=Run] (Running status); BV 7 Ready-To-Start-Monitor-[0=Not-Ready][1=Ready] (Ready to start); BV 4 REMOTE-LOCAL-Monitor-[0=Remote][1=Local] (Remote / local mode); AV 4 Output-Current-[A] (Motor current, A); AV 6 Output-Power-[kW] (Output power, kW); BV 2 Fault-Monitor-[0=OK][1=Fault] (Any active fault); AV 125 Active-Fault (Active fault code).
How do I enable BMS control of the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?
Write BV 18 Control-Override-Command = 1 (On) to put the softstarter in BACnet control; BACnet then overrides the DI logic for start/stop, motor heating, lock parameters, emergency mode, user-defined trip and stand still brake. Local control from the HMI always has priority. Parameter 12.03 Fieldbus control is not needed for control; it only enables the timeout protection.
Does the ABB PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP) need a BACnet heartbeat or have a communication timeout?
BACnet has no built-in timeout. To trip on lost communication set 12.03 Fieldbus control = On, 19.03 Fieldbus failure out (event group), 19.04 Fieldbus failure op (action) and 19.12 Fieldbus failure timeout (seconds without a message).
How do I check these points on the real PSTX softstarter with Anybus CompactCom BACnet (MS/TP and IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ABB BACnet points lists
- Variable frequency drive (HVAC)
ABB ACH180 HVAC drive (embedded BACnet MS/TP)
ABB ACH180 compact HVAC drives using the built-in EFB (RS-485) port with protocol set to BACnet MS/TP.
Also known as: ACH180, ACH180-01, ACH180 HVAC control program, 3AXD50000955893 - Variable frequency drive (HVAC)
ABB ACH550 HVAC drive (embedded BACnet MS/TP)
ABB ACH550 HVAC drives using the built-in RS-485 port with native BACnet MS/TP.
Also known as: ACH550, ACH550-01, ACH550-UH, ACH550 E-Clipse - Variable frequency drive bypass controller (HVAC)
ABB ACH580 E-Clipse and packaged bypass (bypass BACnet objects)
ABB ACH580 drives with the E-Clipse bypass or packaged bypass (US); this list covers the bypass controller's own BACnet MS/TP objects.
Also known as: ACH580 E-Clipse, E-Clipse bypass, ACH580 packaged bypass, ACH580-BxR, 3AXD50000289554 - Variable frequency drive (HVAC)
ABB ACH580 HVAC drive (embedded BACnet MS/TP)
ABB ACH580 HVAC drives using the built-in EFB port with protocol set to BACnet MS/TP.
Also known as: ACH580, ACH580-01, ACH580-31, ACH580 E-Clipse, ACH580 HVAC control program, 3AXD50000027537 - Variable frequency drive (HVAC)
ABB ACS355 HVAC with BACnet (+N831)
ABB ACS355 machinery drives with the HVAC with BACnet firmware (option +N831, firmware 6502 or later).
Also known as: ACS355, ACS355 +N831, ACS355 HVAC, ACS355 BACnet, 3AXD50000024172 - Variable frequency drive via BACnet gateway
ABB ACS800 drive (ProtoNode FPC-N54 profile)
ABB ACS800 drives (6-pulse or active front end, standard firmware) fitted with an RMBA-01 Modbus adapter and an FPC-N54 ProtoNode.
Also known as: ACS800 BACnet, FPC-N54 ACS800, ABB ProtoNode - Variable frequency drive via BACnet gateway
ABB ACS880 drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with standard firmware (6-pulse or active front end) wired to an FPC-N54 ProtoNode over embedded Modbus RTU.
Also known as: ACS880 BACnet, FPC-N54 ACS880, ABB ProtoNode - Variable frequency drive via BACnet gateway (cooling tower fan)
ABB ACS880-CTDD cooling tower direct drive (ProtoNode FPC-N54 profile)
ABB ACS880 drives with Cooling Tower Direct Drive firmware (+N5350) that run permanent-magnet cooling tower fan motors, through an FPC-N54 ProtoNode.
Also known as: ACS880 CTDD BACnet, ACS880 +N5350, Cooling Tower Direct Drive, FPC-N54 ACS880-CTDD - Variable frequency drive (BACnet/IP adapter module)
ABB FBIP-21 BACnet/IP adapter (ACH480 / ACH580)
ABB FBIP-21 BACnet/IP adapter fitted to ACH480 (with BAPO-01) and ACH580 / ACH580 E-Clipse bypass drives (with CMOD-01 or CMOD-02).
Also known as: FBIP-21, FBIP21, ACH580 BACnet/IP, ACH480 BACnet/IP, ACH580 E-Clipse BACnet IP, 3AXD50000028468 - Power meter / network analyzer
ABB M4M 20 / M4M 30 network analyzer (BACnet IP)
ABB M4M 20 and M4M 30 panel network analyzers in their BACnet versions; harmonics and some settings are on the M4M 30 only.
Also known as: M4M 20 BACnet, M4M 30 BACnet, M4M 30SBA, M4M network analyzer, 2CSG445052D0201
Source: Softstarter type PSTX, Fieldbus communication, Anybus CompactCom BACnet MS/TP and BACnet IP · 1SFC132381M0201 Rev C · rev. 2024-07-27. Object names, instances and units are reproduced as published; descriptions are our own.