- GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
Air handling unit controller · BACnet points list
Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 BACnet points list
Updated 7 November 2026
The built-in IQlogic controller in Swegon GOLD E/F air handlers is a native BACnet IP device (B-AAC) with no gateway. This PV 2.48 object list has about 2,160 objects, roughly 700 more than the 2015 generation-E list: fan airflow and pressure, temperatures and regulation levels, heat-exchanger and coil data, accessory functions, energy counters, one binary input per alarm, plus calendars, a schedule and notification classes. The unit is started, stopped and speed-selected from the BMS through one multistate value.
This page lists 2163 BACnet objects for the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 — 817 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 2163 (817 writable)
- Transport
- BACnet IP
- Firmware
- GOLD PV 2.48 (EDE reference file 2.48, 2025-12-02)
- Also known as
- GOLD F, GOLD version F, GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_F_BACnet_251202
Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.
BMS integration notes: Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
Command the unit with MV 793 Communication operation level (Auto lets the internal time channel run it; the other states force stop, low or high speed) and read back MI 592 Operation level. Write the main temperature setpoints (AV 132 supply, AV 135 extract/room), read the supply, extract and outdoor temperatures, and watch BI 13/14 for A/B alarms with BV 1 to reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 793 | Communication operation level | BMS start/stop and speed command | Write |
| AV 132 | SA temperature set point | Supply air temperature setpoint | Write |
| AV 135 | EA/Room temperature set point | Extract/room temperature setpoint | Write |
| BV 1 | Alarm reset | Resets all active alarms | Write |
| MI 592 | Operation level | Actual operating state and who stopped the unit | Read |
| AI 64 | SA Temperature | Supply air temperature | Read |
| AI 66 | EA Temperature | Extract air temperature | Read |
| AI 73 | Outdoor temperature | Outdoor air temp measured by the unit, °C | Read |
| BI 13 | A-alarm active | Any A-class alarm | Read |
| BI 14 | B-alarm active | Any B-class alarm | Read |
Enable & remote start
MV 793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI 592 shows whether a stop or speed came from communication, the hand terminal, a digital input, the time channel or an alarm.
Sensors & values from the BMS
Room temperature can come from the BMS: enable BV 167 'External room temp from BMS function' and write AV 168; outdoor temperature likewise via BV 177 and AV 178. Each has an alarm-time AV in minutes (AV 169, AV 179). Xzone has its own BMS room temperature (BV 379, AV 380, AV 381).
Network setup
- BACnet IP only; the device is a B-AAC with intrinsic alarming through notification classes.
- The EDE gives device instance 0 as the reference value; set the real device instance and IP settings on the unit.
Watch out for
- Setpoints are split by low and high speed (e.g. AV 3/5 SA airflow, AV 19/21 SA duct pressure); write the one for the active speed.
- Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is fitted.
- External override objects (instances 3000 and up) take over fans and heat exchanger for a set time; leave them alone unless that function is planned.
Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Component name | Read | |||
| AI | 4 | SA Air flow | l/s | Read | ||
| AI | 5 | SA Air flow regulator | l/s | Read | ||
| AI | 6 | EA Air flow | l/s | Read | ||
| AI | 7 | EA Air flow regulator | l/s | Read | ||
| AI | 8 | SA Duct pressure | Pa | Read | ||
| AI | 9 | SA Duct pressure regulator | Pa | Read | ||
| AI | 10 | EA Duct pressure | Pa | Read | ||
| AI | 11 | EA Duct pressure regulator | Pa | Read | ||
| AI | 12 | Demand input level | % | Read | ||
| AI | 13 | Demand regulator | % | Read | ||
| AI | 14 | SA Air flow pressure | Pa | Read | ||
| AI | 15 | EA Air flow pressure | Pa | Read | ||
| AI | 18 | Demand CO2 regulator | ppm | Read | ||
| AI | 19 | Demand VOC regulator | ppm | Read | ||
| AI | 23 | SA Pre-filter pressure level | Pa | Read | ||
| AI | 24 | SA Pre-filter pressure alarm limit | Pa | Read | ||
| AI | 25 | EA Pre-filter pressure level | Pa | Read | ||
| AI | 26 | EA Pre-filter pressure alarm limit | Pa | Read | ||
| AI | 27 | SA AHU filter pressure level | Pa | Read | ||
| AI | 28 | SA AHU filter pressure alarm limit | Pa | Read | ||
| AI | 29 | EA AHU filter pressure level | Pa | Read | ||
| AI | 30 | EA AHU filter pressure alarm limit | Pa | Read | ||
| AI | 31 | SA End-filter pressure level | Pa | Read | ||
| AI | 32 | SA End-filter pressure alarm limit | Pa | Read | ||
| AI | 37 | SA Fan level | % | Read | ||
| AI | 38 | EA Fan level | % | Read | ||
| AI | 39 | SA Fan speed | rpm | Read | ||
| AI | 40 | EA Fan speed | rpm | Read | ||
| AI | 41 | SA Voltage | V | Read | ||
| AI | 42 | EA Voltage | V | Read | ||
| AI | 43 | SA Fan current | A | Read | ||
| AI | 44 | EA Fan current | A | Read | ||
| AI | 45 | SA Fan power | kW | Read | ||
| AI | 46 | EA Fan power | kW | Read | ||
| AI | 47 | SA Fan kWh | kWh | Read | ||
| AI | 48 | EA Fan kWh | kWh | Read | ||
| AI | 49 | SA Fan MWh | MWh | Read | ||
| AI | 50 | EA Fan MWh | MWh | Read | ||
| AI | 51 | SA Fan operation time | days | Read | ||
| AI | 52 | EA Fan operation time | days | Read | ||
| AI | 55 | SA Fan min air flow | l/s | Read | ||
| AI | 56 | EA Fan min air flow | l/s | Read | ||
| AI | 57 | SA Fan max air flow | l/s | Read | ||
| AI | 58 | EA Fan max air flow | l/s | Read | ||
| AI | 63 | SFP | Read | |||
| AImin | 64 | SA Temperature | °C | Read | ||
| AI | 65 | SA-D Temperature | °C | Read | ||
| AImin | 66 | EA Temperature | °C | Read | ||
| AI | 67 | EA-D Temperature | °C | Read | ||
| AI | 68 | EA Regulation temperature | °C | Read | ||
| AI | 69 | EA Temperature PX/CX | °C | Read | ||
| AI | 70 | EA Temperature SD | °C | Read | ||
| AI | 72 | Outdoor temperature COOL DX | °C | Read | ||
| AImin | 73 | Outdoor temperature | °C | Read | ||
| AI | 74 | Outdoor regulation temperature | °C | Read | ||
| AI | 75 | External outdoor temperature 1 | °C | Read | ||
| AI | 76 | External outdoor temperature 2 | °C | Read | ||
| AI | 77 | External outdoor temperature 3 | °C | Read | ||
| AI | 78 | External outdoor temperature 4 | °C | Read | ||
| AI | 80 | EA Duct temperature | °C | Read | ||
| AI | 81 | Room temperature 1 | °C | Read | ||
| AI | 82 | Room temperature 2 | °C | Read | ||
| AI | 83 | Room temperature 3 | °C | Read | ||
| AI | 84 | Room temperature 4 | °C | Read | ||
| AI | 87 | SA Temp regulator | °C | Read | ||
| AI | 88 | EA Temp regulator | °C | Read | ||
| AI | 90 | Cool exchanger regulator level | % | Read | ||
| AI | 91 | Heat exchanger regulator level | % | Read | ||
| AI | 92 | Extra regulation sequence 1 heat regulator level | % | Read | ||
| AI | 93 | Extra regulation sequence 1 heat output level | % | Read | ||
| AI | 94 | Reheat regulator level | % | Read | ||
| AI | 95 | Reheat output level | % | Read | ||
| AI | 96 | ReCO2 heat level | % | Read | ||
| AI | 97 | Down regulation level | % | Read | ||
| AI | 98 | Heating boost level | % | Read | ||
| AI | 99 | Extra regulation sequence 1 cool regulator level | % | Read | ||
| AI | 100 | Extra regulation sequence 1 cool output level | % | Read | ||
| AI | 101 | Cool regulator level | % | Read | ||
| AI | 102 | Cool output level | % | Read | ||
| AI | 103 | ReCO2 cool level | % | Read | ||
| AI | 104 | Cooling boost level | % | Read | ||
| AI | 105 | RHX operation level | % | Read | ||
| AI | 106 | RHX/PHX/CHX efficiency | % | Read | ||
| AI | 107 | RHX defrost pressure level | Pa | Read | ||
| AI | 108 | RHX defrost pressure alarm limit | Pa | Read | ||
| AI | 109 | RHX carry over control pressure level | Pa | Read | ||
| AI | 111 | RHX operation time | days | Read | ||
| AI | 112 | PX exchanger bypass 4A output | % | Read | ||
| AI | 113 | PX exchanger bypass 4A feedback | % | Read | ||
| AI | 116 | PX defrost pressure level | Pa | Read | ||
| AI | 117 | PHX-3D Bypass output | % | Read | ||
| AI | 118 | PHX-3D Bypass input | % | Read | ||
| AI | 119 | PHX-3D Bypass temperature 1 | °C | Read | ||
| AI | 120 | PHX-3D Bypass temperature 2 | °C | Read | ||
| AI | 121 | PX exchanger damper 1 output | % | Read | ||
| AI | 122 | PHX-2 Damper 1 input | % | Read | ||
| AI | 123 | PX exchanger damper 2 output | % | Read | ||
| AI | 124 | PHX-2 Damper 2 input | % | Read | ||
| AI | 125 | PX exchanger bypass output | % | Read | ||
| AI | 126 | PX exchanger bypass feedback | % | Read | ||
| AI | 127 | CHX-1 Valve output | % | Read | ||
| AI | 128 | CHX-1 Valve input | % | Read | ||
| AI | 129 | CHX-1 Return water temperature | °C | Read | ||
| AI | 130 | PHX/CHX operation time | days | Read | ||
| AI | 132 | PHX-1D Bypass output | % | Read | ||
| AI | 133 | PHX-1D Bypass input | % | Read | ||
| AI | 134 | CHX-2 Return water temperature | °C | Read | ||
| AI | 135 | CHX-2 Extract coil pressure level | mbar | Read | ||
| AI | 136 | PHX/CHX Humidity level | %RH | Read | ||
| AI | 137 | CHX-2 Valve output | % | Read | ||
| AI | 138 | CHX-2 Valve input | % | Read | ||
| AI | 139 | CHX-2 Pump output | % | Read | ||
| AI | 141 | Extra regulation sequence 1 anti frost temp/overheat input | °C | Read | ||
| AI | 143 | Extra regulation sequence 2 anti frost temp/overheat input | °C | Read | ||
| AI | 144 | Extra regulation sequence 1 temperature guard | °C | Read | ||
| AI | 145 | Extra regulation sequence 2 temperature guard | °C | Read | ||
| AI | 146 | Extra regulation sequence 1 input level | % | Read | ||
| AI | 147 | Extra regulation sequence 1 heat operation time | days | Read | ||
| AI | 148 | Extra regulation sequence 1 cool operation time | days | Read | ||
| AI | 149 | Extra regulation sequence 2 input level | % | Read | ||
| AI | 150 | Extra regulation sequence 2 heat operation time | days | Read | ||
| AI | 151 | Extra regulation sequence 2 cool operation time | days | Read | ||
| AI | 153 | Re-heat anti frost temp/overheat input | °C | Read | ||
| AI | 158 | Re-heat input level | % | Read | ||
| AI | 159 | Re-heat operation time | days | Read | ||
| AI | 164 | Cool water temperature | °C | Read | ||
| AI | 168 | Cool input level | % | Read | ||
| AI | 169 | Cool operation time | days | Read | ||
| AI | 174 | Xzone SA temperature | °C | Read | ||
| AI | 175 | Xzone EA temperature | °C | Read | ||
| AI | 176 | Xzone EA regulation temperature | °C | Read | ||
| AI | 177 | Xzone Room temperature 1 | °C | Read | ||
| AI | 178 | Xzone Room temperature 2 | °C | Read | ||
| AI | 179 | Xzone Room temperature 3 | °C | Read | ||
| AI | 180 | Xzone Room temperature 4 | °C | Read | ||
| AI | 181 | Xzone Room temperature min/max/average | Min, max or average of room sensors 1-4, per configuration | °C | Read | |
| AI | 186 | Xzone SA Temp regulator | °C | Read | ||
| AI | 187 | Xzone EA Temp regulator | °C | Read | ||
| AI | 190 | Xzone re-heat regulator level | % | Read | ||
| AI | 193 | Xzone cool regulator level | % | Read | ||
| AI | 199 | Xzone heat, anti frost temp/overheat input | °C | Read | ||
| AI | 200 | Xzone heat/cool temperature guard | °C | Read | ||
| AI | 203 | Xzone heat, output level | % | Read | ||
| AI | 204 | Xzone heat, input level | % | Read | ||
| AI | 205 | Xzone heat, operation time | days | Read | ||
| AI | 210 | Xzone cool, water temperature | °C | Read | ||
| AI | 211 | Xzone cool temperature guard | °C | Read | ||
| AI | 214 | Xzone cool, output level | % | Read | ||
| AI | 215 | Xzone cool, input level | % | Read | ||
| AI | 216 | Xzone cool, operation time | days | Read | ||
| AI | 220 | Pre-heat temperature | °C | Read | ||
| AI | 221 | Pre-heat temp regulator set point | °C | Read | ||
| AI | 222 | Pre-heat temp regulator level | % | Read | ||
| AI | 225 | Pre-heat anti frost temp/overheat input | °C | Read | ||
| AI | 228 | Pre-heat output level | % | Read | ||
| AI | 229 | Pre-heat input level | % | Read | ||
| AI | 230 | Pre-heat operation time | days | Read | ||
| AI | 233 | ReCO2 recirculation damper output | % | Read | ||
| AI | 234 | ReCO2 recirculation damper input | % | Read | ||
| AI | 235 | ReCO2 outdoor damper output | % | Read | ||
| AI | 236 | ReCO2 outdoor damper input | % | Read | ||
| AI | 237 | ReCO2 outdoor air flow | l/s | Read | ||
| AI | 238 | ReCO2 outdoor air flow regulator set point | l/s | Read | ||
| AI | 244 | SA humidity level | %RH | Read | ||
| AI | 245 | SA humidity temperature | °C | Read | ||
| AI | 246 | SA dew point | °C | Read | ||
| AI | 247 | EA humidity level | %RH | Read | ||
| AI | 248 | EA humidity temperature | °C | Read | ||
| AI | 249 | EA dew point | °C | Read | ||
| AI | 251 | Dehumidifying SA dew point regulator set point | °C | Read | ||
| AI | 252 | Dehumidifying output level | % | Read | ||
| AI | 254 | Humidifying SA regulator set point | %RH | Read | ||
| AI | 255 | Humidifying output level | % | Read | ||
| AI | 260 | Exhaust air humidity | %RH | Read | ||
| AI | 261 | Exhaust air temperature | °C | Read | ||
| AI | 262 | Outdoor air humidity | %RH | Read | ||
| AI | 263 | Outdoor air temperature | °C | Read | ||
| AI | 264 | Room air humidity | %RH | Read | ||
| AI | 265 | Room air temperature | °C | Read | ||
| AI | 266 | VOC level | ppm | Read | ||
| AI | 267 | CO2 level | ppm | Read | ||
| AI | 271 | COOL DX, unit power size | Read | |||
| AI | 274 | COOL DX, compressor 1 low pressure level | kPa | Read | ||
| AI | 275 | COOL DX, compressor 1 high pressure level | kPa | Read | ||
| AI | 276 | COOL DX, compressor 2 low pressure level | kPa | Read | ||
| AI | 277 | COOL DX, compressor 2 high pressure level | kPa | Read | ||
| AI | 281 | Exhaust heat temperature | °C | Read | ||
| AI | 282 | Exhaust heat temp regulator set point | °C | Read | ||
| AI | 283 | Exhaust heat temp regulator level | % | Read | ||
| AI | 285 | Exhaust heat anti frost temp/overheat input | °C | Read | ||
| AI | 286 | Exhaust heat output level | % | Read | ||
| AI | 287 | Exhaust heat input level | % | Read | ||
| AI | 288 | Exhaust heat operation time | days | Read | ||
| AI | 289 | SMART Link, WB outlet water 1 | °C | Read | ||
| AI | 290 | SMART Link, WB outlet water 2 | °C | Read | ||
| AI | 291 | SMART Link, WB outlet water 3 | °C | Read | ||
| AI | 292 | SMART Link, WB outlet water 4 | °C | Read | ||
| AI | 293 | SMART Link, WB outlet water average | °C | Read | ||
| AI | 294 | SMART Link, WB reference water | °C | Read | ||
| AI | 297 | SMART Link WB, heated water set point | °C | Read | ||
| AI | 298 | SMART Link WB, chilled water set point | °C | Read | ||
| AI | 299 | SMART Link WB, Min heated water set point | °C | Read | ||
| AI | 300 | SMART Link WB, Max heated water set point | °C | Read | ||
| AI | 301 | SMART Link WB, Min chilled water set point | °C | Read | ||
| AI | 302 | SMART Link WB, Max chilled water set point | °C | Read | ||
| AI | 327 | SMART Link, DX unit 1 power level set point | % | Read | ||
| AI | 328 | SMART Link, DX unit 1 power level | % | Read | ||
| AI | 329 | SMART Link, DX unit 1 operation time | days | Read | ||
| AI | 338 | SMART Link, DX unit 2 power level set point | % | Read | ||
| AI | 339 | SMART Link, DX unit 2 power level | % | Read | ||
| AI | 340 | SMART Link, DX unit 2 operation time | days | Read | ||
| AI | 349 | SMART Link, DX unit 3 power level set point | % | Read | ||
| AI | 350 | SMART Link, DX unit 3 power level | % | Read | ||
| AI | 351 | SMART Link, DX unit 3 operation time | days | Read | ||
| AI | 360 | SMART Link, DX unit 4 power level set point | % | Read | ||
| AI | 361 | SMART Link, DX unit 4 power level | % | Read | ||
| AI | 362 | SMART Link, DX unit 4 operation time | days | Read | ||
| AI | 374 | AYC Heat, heated water | °C | Read | ||
| AI | 375 | AYC Heated water set point | °C | Read | ||
| AI | 376 | AYC Heat, valve output | % | Read | ||
| AI | 377 | AYC Heat, valve input | % | Read | ||
| AI | 378 | AYC Heat, operation time | days | Read | ||
| AI | 379 | AYC Heated water heat demand | Read | |||
| AI | 387 | AYC Cool, chilled water | °C | Read | ||
| AI | 388 | AYC Chilled water set point | °C | Read | ||
| AI | 389 | AYC Cool, valve output | % | Read | ||
| AI | 390 | AYC Cool, valve input | % | Read | ||
| AI | 391 | AYC Cool, operation time | days | Read | ||
| AI | 392 | AYC Chilled water cool demand | Read | |||
| AI | 400 | MIRU Control 1 Min air flow | Read | |||
| AI | 401 | MIRU Control 1 Max air flow | Read | |||
| AI | 402 | MIRU Control 1 Air flow | l/s | Read | ||
| AI | 403 | MIRU Control 1 Air flow set point | l/s | Read | ||
| AI | 404 | MIRU Control 1 Pressure | Pa | Read | ||
| AI | 405 | MIRU Control 1 Pressure set point | Pa | Read | ||
| AI | 406 | MIRU Control 1 External temperature | °C | Read | ||
| AI | 407 | MIRU Control 1 Operation time | days | Read | ||
| AI | 408 | MIRU Control 1 Fan level | % | Read | ||
| AI | 409 | MIRU Control 1 Fan power | W | Read | ||
| AI | 410 | MIRU Control 1 SFP | Read | |||
| AI | 411 | MIRU Control 1 kWh | kWh | Read | ||
| AI | 412 | MIRU Control 1 MWh | MWh | Read | ||
| AI | 417 | MIRU Control 2 Min air flow | Read | |||
| AI | 418 | MIRU Control 2 Max air flow | Read | |||
| AI | 419 | MIRU Control 2 Air flow | l/s | Read | ||
| AI | 420 | MIRU Control 2 Air flow set point | l/s | Read | ||
| AI | 421 | MIRU Control 2 Pressure | Pa | Read | ||
| AI | 422 | MIRU Control 2 Pressure set point | Pa | Read | ||
| AI | 423 | MIRU Control 2 External temperature | °C | Read | ||
| AI | 424 | MIRU Control 2 Operation time | days | Read | ||
| AI | 425 | MIRU Control 2 Fan level | % | Read | ||
| AI | 426 | MIRU Control 2 Fan power | W | Read | ||
| AI | 427 | MIRU Control 2 SFP | Read | |||
| AI | 428 | MIRU Control 2 kWh | kWh | Read | ||
| AI | 429 | MIRU Control 2 MWh | MWh | Read | ||
| AI | 434 | MIRU Control 3 Min air flow | Read | |||
| AI | 435 | MIRU Control 3 Max air flow | Read | |||
| AI | 436 | MIRU Control 3 Air flow | l/s | Read | ||
| AI | 437 | MIRU Control 3 Air flow set point | l/s | Read | ||
| AI | 438 | MIRU Control 3 Pressure | Pa | Read | ||
| AI | 439 | MIRU Control 3 Pressure set point | Pa | Read | ||
| AI | 440 | MIRU Control 3 External temperature | °C | Read | ||
| AI | 441 | MIRU Control 3 Operation time | days | Read | ||
| AI | 442 | MIRU Control 3 Fan level | % | Read | ||
| AI | 443 | MIRU Control 3 Fan power | W | Read | ||
| AI | 444 | MIRU Control 3 SFP | Read | |||
| AI | 445 | MIRU Control 3 kWh | kWh | Read | ||
| AI | 446 | MIRU Control 3 MWh | MWh | Read | ||
| AI | 451 | MIRU Control 4 Min air flow | Read | |||
| AI | 452 | MIRU Control 4 Max air flow | Read | |||
| AI | 453 | MIRU Control 4 Air flow | l/s | Read | ||
| AI | 454 | MIRU Control 4 Air flow set point | l/s | Read | ||
| AI | 455 | MIRU Control 4 Pressure | Pa | Read | ||
| AI | 456 | MIRU Control 4 Pressure set point | Pa | Read | ||
| AI | 457 | MIRU Control 4 External temperature | °C | Read | ||
| AI | 458 | MIRU Control 4 Operation time | days | Read | ||
| AI | 459 | MIRU Control 4 Fan level | % | Read | ||
| AI | 460 | MIRU Control 4 Fan power | W | Read | ||
| AI | 461 | MIRU Control 4 SFP | Read | |||
| AI | 462 | MIRU Control 4 kWh | kWh | Read | ||
| AI | 463 | MIRU Control 4 MWh | MWh | Read | ||
| AI | 468 | MIRU Control 5 Min air flow | Read | |||
| AI | 469 | MIRU Control 5 Max air flow | Read | |||
| AI | 470 | MIRU Control 5 Air flow | l/s | Read | ||
| AI | 471 | MIRU Control 5 Air flow set point | l/s | Read | ||
| AI | 472 | MIRU Control 5 Pressure | Pa | Read | ||
| AI | 473 | MIRU Control 5 Pressure set point | Pa | Read | ||
| AI | 474 | MIRU Control 5 External temperature | °C | Read | ||
| AI | 475 | MIRU Control 5 Operation time | days | Read | ||
| AI | 476 | MIRU Control 5 Fan level | % | Read | ||
| AI | 477 | MIRU Control 5 Fan power | W | Read | ||
| AI | 478 | MIRU Control 5 SFP | Read | |||
| AI | 479 | MIRU Control 5 kWh | kWh | Read | ||
| AI | 480 | MIRU Control 5 MWh | MWh | Read | ||
| AI | 485 | MIRU Control 6 Min air flow | Read | |||
| AI | 486 | MIRU Control 6 Max air flow | Read | |||
| AI | 487 | MIRU Control 6 Air flow | l/s | Read | ||
| AI | 488 | MIRU Control 6 Air flow set point | l/s | Read | ||
| AI | 489 | MIRU Control 6 Pressure | Pa | Read | ||
| AI | 490 | MIRU Control 6 Pressure set point | Pa | Read | ||
| AI | 491 | MIRU Control 6 External temperature | °C | Read | ||
| AI | 492 | MIRU Control 6 Operation time | days | Read | ||
| AI | 493 | MIRU Control 6 Fan level | % | Read | ||
| AI | 494 | MIRU Control 6 Fan power | W | Read | ||
| AI | 495 | MIRU Control 6 SFP | Read | |||
| AI | 496 | MIRU Control 6 kWh | kWh | Read | ||
| AI | 497 | MIRU Control 6 MWh | MWh | Read | ||
| AI | 502 | MIRU Control 7 Min air flow | Read | |||
| AI | 503 | MIRU Control 7 Max air flow | Read | |||
| AI | 504 | MIRU Control 7 Air flow | l/s | Read | ||
| AI | 505 | MIRU Control 7 Air flow set point | l/s | Read | ||
| AI | 506 | MIRU Control 7 Pressure | Pa | Read | ||
| AI | 507 | MIRU Control 7 Pressure set point | Pa | Read | ||
| AI | 508 | MIRU Control 7 External temperature | °C | Read | ||
| AI | 509 | MIRU Control 7 Operation time | days | Read | ||
| AI | 510 | MIRU Control 7 Fan level | % | Read | ||
| AI | 511 | MIRU Control 7 Fan power | W | Read | ||
| AI | 512 | MIRU Control 7 SFP | Read | |||
| AI | 513 | MIRU Control 7 kWh | kWh | Read | ||
| AI | 514 | MIRU Control 7 MWh | MWh | Read | ||
| AI | 519 | MIRU Control 8 Min air flow | Read | |||
| AI | 520 | MIRU Control 8 Max air flow | Read | |||
| AI | 521 | MIRU Control 8 Air flow | l/s | Read | ||
| AI | 522 | MIRU Control 8 Air flow set point | l/s | Read | ||
| AI | 523 | MIRU Control 8 Pressure | Pa | Read | ||
| AI | 524 | MIRU Control 8 Pressure set point | Pa | Read | ||
| AI | 525 | MIRU Control 8 External temperature | °C | Read | ||
| AI | 526 | MIRU Control 8 Operation time | days | Read | ||
| AI | 527 | MIRU Control 8 Fan level | % | Read | ||
| AI | 528 | MIRU Control 8 Fan power | W | Read | ||
| AI | 529 | MIRU Control 8 SFP | Read | |||
| AI | 530 | MIRU Control 8 kWh | kWh | Read | ||
| AI | 531 | MIRU Control 8 MWh | MWh | Read | ||
| AI | 536 | MIRU Control 9 Min air flow | Read | |||
| AI | 537 | MIRU Control 9 Max air flow | Read | |||
| AI | 538 | MIRU Control 9 Air flow | l/s | Read | ||
| AI | 539 | MIRU Control 9 Air flow set point | l/s | Read | ||
| AI | 540 | MIRU Control 9 Pressure | Pa | Read | ||
| AI | 541 | MIRU Control 9 Pressure set point | Pa | Read | ||
| AI | 542 | MIRU Control 9 External temperature | °C | Read | ||
| AI | 543 | MIRU Control 9 Operation time | days | Read | ||
| AI | 544 | MIRU Control 9 Fan level | % | Read | ||
| AI | 545 | MIRU Control 9 Fan power | W | Read | ||
| AI | 546 | MIRU Control 9 SFP | Read | |||
| AI | 547 | MIRU Control 9 kWh | kWh | Read | ||
| AI | 548 | MIRU Control 9 MWh | MWh | Read | ||
| AI | 553 | MIRU Control 10 Min air flow | Read | |||
| AI | 554 | MIRU Control 10 Max air flow | Read | |||
| AI | 555 | MIRU Control 10 Air flow | l/s | Read | ||
| AI | 556 | MIRU Control 10 Air flow set point | l/s | Read | ||
| AI | 557 | MIRU Control 10 Pressure | Pa | Read | ||
| AI | 558 | MIRU Control 10 Pressure set point | Pa | Read | ||
| AI | 559 | MIRU Control 10 External temperature | °C | Read | ||
| AI | 560 | MIRU Control 10 Operation time | days | Read | ||
| AI | 561 | MIRU Control 10 Fan level | % | Read | ||
| AI | 562 | MIRU Control 10 Fan power | W | Read | ||
| AI | 563 | MIRU Control 10 SFP | Read | |||
| AI | 564 | MIRU Control 10 kWh | kWh | Read | ||
| AI | 565 | MIRU Control 10 MWh | MWh | Read | ||
| AI | 570 | IQlogic software version | Read | |||
| AI | 604 | Triggered alarm #1 | Read | |||
| AI | 605 | Triggered alarm #2 | Read | |||
| AI | 606 | Triggered alarm #3 | Read | |||
| AI | 607 | Triggered alarm #4 | Read | |||
| AI | 608 | Triggered alarm #5 | Read | |||
| AI | 609 | Triggered alarm #6 | Read | |||
| AI | 610 | Triggered alarm #7 | Read | |||
| AI | 611 | Triggered alarm #8 | Read | |||
| AI | 612 | Triggered alarm #9 | Read | |||
| AI | 613 | Triggered alarm #10 | Read | |||
| AI | 614 | Triggered alarm group #1 | Read | |||
| AI | 615 | Triggered alarm group #2 | Read | |||
| AI | 616 | Triggered alarm group #3 | Read | |||
| AI | 617 | Triggered alarm group #4 | Read | |||
| AI | 618 | Triggered alarm group #5 | Read | |||
| AI | 619 | Triggered alarm group #6 | Read | |||
| AI | 620 | Triggered alarm group #7 | Read | |||
| AI | 621 | Triggered alarm group #8 | Read | |||
| AI | 622 | Triggered alarm group #9 | Read | |||
| AI | 623 | Triggered alarm group #10 | Read | |||
| AI | 661 | Prolonged low speed remaining hours | h | Read | ||
| AI | 662 | Prolonged low speed remaining seconds | s | Read | ||
| AI | 663 | Prolonged high speed remaining hours | h | Read | ||
| AI | 664 | Prolonged high speed remaining seconds | s | Read | ||
| AI | 697 | Exhaust heat heat retention at stop | °C | Read | ||
| AI | 698 | Exhaust heat heat retention at operation | °C | Read | ||
| AI | 699 | Exhaust heat frost protection alarm limit | °C | Read | ||
| AI | 700 | Extra regulation sequence 2 heat regulator level | % | Read | ||
| AI | 701 | Extra regulation sequence 2 heat output level | % | Read | ||
| AI | 702 | Extra regulation sequence 2 cool regulator level | % | Read | ||
| AI | 703 | Extra regulation sequence 2 cool output level | % | Read | ||
| AI | 704 | Re-heat retention at stop | °C | Read | ||
| AI | 705 | Re-heat retention at operation | °C | Read | ||
| AI | 706 | Re-heat frost protection alarm limit | °C | Read | ||
| AI | 707 | Pre-heat retention at stop | °C | Read | ||
| AI | 708 | Pre-heat retention at operation | °C | Read | ||
| AI | 709 | Pre-heat frost protection alarm limit | °C | Read | ||
| AI | 710 | Xzone heat retention at stop | °C | Read | ||
| AI | 711 | Xzone heat retention at operation | °C | Read | ||
| AI | 712 | Xzone frost protection alarm limit | °C | Read | ||
| AI | 713 | Extra regulation sequence 1 heat retention at stop | °C | Read | ||
| AI | 714 | Extra regulation sequence 1 heat retention at operation | °C | Read | ||
| AI | 715 | Extra regulation sequence 1 frost protection alarm limit | °C | Read | ||
| AI | 716 | Extra regulation sequence 2 heat retention at stop | °C | Read | ||
| AI | 717 | Extra regulation sequence 2 heat retention at operation | °C | Read | ||
| AI | 718 | Extra regulation sequence 2 frost protection alarm limit | °C | Read | ||
| AI | 719 | Heat exchange motor power consumption W | W | Read | ||
| AI | 720 | Heat exchange motor power consumption kW | kW | Read | ||
| AI | 721 | Heat exchange motor energy consumption kWh | kWh | Read | ||
| AI | 722 | Heat exchange motor energy consumption MWh | MWh | Read | ||
| AI | 723 | Heat power recovery W | W | Read | ||
| AI | 724 | Heat power recovery kW | kW | Read | ||
| AI | 725 | Heat power consumption W | W | Read | ||
| AI | 726 | Heat power consumption kW | kW | Read | ||
| AI | 727 | Cool power recovery W | W | Read | ||
| AI | 728 | Cool power recovery kW | kW | Read | ||
| AI | 729 | Cool power consumption W | W | Read | ||
| AI | 730 | Cool power consumption kW | kW | Read | ||
| AI | 731 | Heat energy recovery kWh | kWh | Read | ||
| AI | 732 | Heat energy recovery MWh | MWh | Read | ||
| AI | 733 | Cool energy recovery kWh | kWh | Read | ||
| AI | 734 | Cool energy recovery MWh | MWh | Read | ||
| AI | 735 | Heat energy consumption kWh | kWh | Read | ||
| AI | 736 | Heat energy consumption MWh | MWh | Read | ||
| AI | 737 | Cool energy consumption kWh | kWh | Read | ||
| AI | 738 | Cool energy consumption MWh | MWh | Read | ||
| AI | 739 | Energy input 1 kWh | kWh | Read | ||
| AI | 740 | Energy input 1 MWh | MWh | Read | ||
| AI | 741 | Energy input 2 kWh | kWh | Read | ||
| AI | 742 | Energy input 2 MWh | MWh | Read | ||
| AI | 743 | Energy input 3 kWh | kWh | Read | ||
| AI | 744 | Energy input 3 MWh | MWh | Read | ||
| AI | 745 | Energy input 4 kWh | kWh | Read | ||
| AI | 746 | Energy input 4 MWh | MWh | Read | ||
| AI | 747 | Re-heat water coil power consumption W | W | Read | ||
| AI | 748 | Re-heat water coil power consumption kW | kW | Read | ||
| AI | 749 | Re-heat water coil energy consumption kWh | kWh | Read | ||
| AI | 750 | Re-heat water coil energy consumption MWh | MWh | Read | ||
| AI | 751 | Cool water coil power consumption W | W | Read | ||
| AI | 752 | Cool water coil power consumption kW | kW | Read | ||
| AI | 753 | Cool water coil energy consumption kWh | kWh | Read | ||
| AI | 754 | Cool water coil energy consumption MWh | MWh | Read | ||
| AI | 755 | Xzone heat water coil power consumption W | W | Read | ||
| AI | 756 | Xzone heat water coil power consumption kW | kW | Read | ||
| AI | 757 | Xzone heat water coil energy consumption kWh | kWh | Read | ||
| AI | 758 | Xzone heat water coil energy consumption MWh | MWh | Read | ||
| AI | 759 | Xzone cool water coil power consumption W | W | Read | ||
| AI | 760 | Xzone cool water coil power consumption kW | kW | Read | ||
| AI | 761 | Xzone cool water coil energy consumption kWh | kWh | Read | ||
| AI | 762 | Xzone cool water coil energy consumption MWh | MWh | Read | ||
| AI | 763 | Re-heat liquid flow level | l/s | Read | ||
| AI | 764 | Cool liquid flow level | l/s | Read | ||
| AI | 765 | Xzone heat liquid flow level | l/s | Read | ||
| AI | 766 | Xzone cool liquid flow level | l/s | Read | ||
| AI | 780 | Re-heat return water temperature | °C | Read | ||
| AI | 781 | Re-heat flow water temperature | °C | Read | ||
| AI | 782 | Cool return water temperature | °C | Read | ||
| AI | 783 | Cool flow water temperature | °C | Read | ||
| AI | 784 | Xzone heat return water temperature | °C | Read | ||
| AI | 785 | Xzone heat flow water temperature | °C | Read | ||
| AI | 786 | Xzone cool return water temperature | °C | Read | ||
| AI | 787 | Xzone cool flow water temperature | °C | Read | ||
| AI | 800 | External operation I/O-module 3, analogue input 1 | % | Read | ||
| AI | 801 | External operation I/O-module 3, analogue input 2 | % | Read | ||
| AI | 804 | External operation I/O-module 3, analogue output 1 | % | Read | ||
| AI | 805 | External operation I/O-module 3, analogue output 2 | % | Read | ||
| AI | 806 | External operation I/O-module 6, analogue input 1 | % | Read | ||
| AI | 807 | External operation I/O-module 6, analogue input 2 | % | Read | ||
| AI | 810 | External operation I/O-module 6, analogue output 1 | % | Read | ||
| AI | 811 | External operation I/O-module 6, analogue output 2 | % | Read | ||
| AI | 812 | External operation I/O-module A, analogue input | % | Read | ||
| AI | 813 | External operation I/O-module A, temp sensor 1 | °C | Read | ||
| AI | 814 | External operation I/O-module A, temp sensor 2 | °C | Read | ||
| AI | 815 | External operation I/O-module B, analogue input | % | Read | ||
| AI | 816 | External operation I/O-module B, temp sensor 1 | °C | Read | ||
| AI | 817 | External operation I/O-module B, temp sensor 2 | °C | Read | ||
| AI | 818 | External operation I/O-module C, analogue input | % | Read | ||
| AI | 819 | External operation I/O-module C, temp sensor 1 | °C | Read | ||
| AI | 820 | External operation I/O-module C, temp sensor 2 | °C | Read | ||
| AI | 1405 | H/C recirculation defrost damper output | % | Read | ||
| AI | 1406 | H/C recirculation defrost damper input | % | Read | ||
| AI | 1409 | H/C heat anti frost temp/overheat input | °C | Read | ||
| AI | 1413 | H/C operation level | % | Read | ||
| AI | 1414 | H/C heat defrost level | % | Read | ||
| AI | 1415 | H/C defrost pressure level | Pa | Read | ||
| AI | 1416 | H/C defrost pressure start limit | Pa | Read | ||
| AI | 1417 | H/C defrost pressure end limit | Pa | Read | ||
| AI | 1418 | H/C superheat temp | K | Read | ||
| AI | 1419 | H/C discharge temp | °C | Read | ||
| AI | 1420 | H/C suction temp | °C | Read | ||
| AI | 1421 | H/C condensation temp | °C | Read | ||
| AI | 1422 | H/C evaporation temp | °C | Read | ||
| AI | 1423 | H/C high pressure | bar | Read | ||
| AI | 1424 | H/C low pressure | bar | Read | ||
| AI | 3002 | External override, remaining time | min | Read | ||
| AO | 1 | Extract air start up | l/s | Write | ||
| AV | 3 | SA low speed air flow set point | l/s | Write | ||
| AV | 4 | EA low speed air flow set point | l/s | Write | ||
| AV | 5 | SA high speed air flow set point | l/s | Write | ||
| AV | 6 | EA high speed air flow set point | l/s | Write | ||
| AV | 7 | SA max speed air flow set point boost | l/s | Write | ||
| AV | 8 | EA max speed air flow set point boost | l/s | Write | ||
| AV | 9 | SA regulation zone | % | Write | ||
| AV | 10 | EA regulation zone | % | Write | ||
| AV | 11 | SA regulation I-time | s | Write | ||
| AV | 12 | EA regulation I-time | s | Write | ||
| AV | 19 | SA low speed pressure set point | Pa | Write | ||
| AV | 20 | EA low speed pressure set point | Pa | Write | ||
| AV | 21 | SA high speed pressure set point | Pa | Write | ||
| AV | 22 | EA high speed pressure set point | Pa | Write | ||
| AV | 23 | SA max speed pressure set point | Pa | Write | ||
| AV | 24 | EA max speed pressure set point | Pa | Write | ||
| AV | 25 | SA max speed output signal | % | Write | ||
| AV | 26 | EA max speed output signal | % | Write | ||
| AV | 27 | SA pressure regulation zone | % | Write | ||
| AV | 28 | EA pressure regulation zone | % | Write | ||
| AV | 29 | SA pressure I-time | s | Write | ||
| AV | 30 | EA pressure I-time | s | Write | ||
| AV | 33 | Demand low speed CO2 set point | ppm | Write | ||
| AV | 34 | Demand high speed CO2 set point | ppm | Write | ||
| AV | 35 | Demand low speed VOC set point | ppm | Write | ||
| AV | 36 | Demand high speed VOC set point | ppm | Write | ||
| AV | 37 | Demand low speed set point | % | Write | ||
| AV | 38 | Demand high speed set point | % | Write | ||
| AV | 39 | SA min speed air flow set point | l/s | Write | ||
| AV | 40 | EA min speed air flow set point | l/s | Write | ||
| AV | 41 | SA max speed air flow set point demand | l/s | Write | ||
| AV | 42 | EA max speed air flow set point demand | l/s | Write | ||
| AV | 43 | Demand P-band | % | Write | ||
| AV | 44 | Demand I-time | s | Write | ||
| AV | 45 | Demand CO2 P-band | ppm | Write | ||
| AV | 46 | Demand VOC P-band | ppm | Write | ||
| AV | 50 | Slave offset factor | Write | |||
| AV | 51 | SA slave offset air flow | l/s | Write | ||
| AV | 52 | EA slave offset air flow | l/s | Write | ||
| AV | 54 | Outdoor temp compensation X1 | °C | Write | ||
| AV | 55 | Outdoor temp compensation X2 | °C | Write | ||
| AV | 56 | Outdoor temp compensation X3 | °C | Write | ||
| AV | 57 | Outdoor temp compensation X4 | °C | Write | ||
| AV | 58 | Outdoor temp compensation Y1 SA air flow | l/s | Write | ||
| AV | 59 | Outdoor temp compensation Y2 SA air flow | l/s | Write | ||
| AV | 60 | Outdoor temp compensation Y3 SA air flow | l/s | Write | ||
| AV | 61 | Outdoor temp compensation Y4 SA air flow | l/s | Write | ||
| AV | 62 | Outdoor temp compensation Y1 EA air flow | l/s | Write | ||
| AV | 63 | Outdoor temp compensation Y2 EA air flow | l/s | Write | ||
| AV | 64 | Outdoor temp compensation Y3 EA air flow | l/s | Write | ||
| AV | 65 | Outdoor temp compensation Y4 EA air flow | l/s | Write | ||
| AV | 66 | Outdoor temp compensation Y1 SA pressure | Pa | Write | ||
| AV | 67 | Outdoor temp compensation Y2 SA pressure | Pa | Write | ||
| AV | 68 | Outdoor temp compensation Y3 SA pressure | Pa | Write | ||
| AV | 69 | Outdoor temp compensation Y4 SA pressure | Pa | Write | ||
| AV | 70 | Outdoor temp compensation Y1 EA pressure | Pa | Write | ||
| AV | 71 | Outdoor temp compensation Y2 EA pressure | Pa | Write | ||
| AV | 72 | Outdoor temp compensation Y3 EA pressure | Pa | Write | ||
| AV | 73 | Outdoor temp compensation Y4 EA pressure | Pa | Write | ||
| AV | 79 | Down regulation neutral zone | K | Write | ||
| AV | 80 | Down regulation P-band | K | Write | ||
| AV | 81 | Down regulation I-time | s | Write | ||
| AV | 85 | SA fan speed at fire alarm 1 | % | Write | ||
| AV | 86 | EA fan speed at fire alarm 1 | % | Write | ||
| AV | 88 | SA fan speed at fire alarm 2 | % | Write | ||
| AV | 89 | EA fan speed at fire alarm 2 | % | Write | ||
| AV | 91 | SA fan speed at internal fire alarm | % | Write | ||
| AV | 92 | EA fan speed at internal fire alarm | % | Write | ||
| AV | 97 | SA pre-filter alarm limit | Pa | Write | ||
| AV | 98 | EA pre-filter alarm limit | Pa | Write | ||
| AV | 103 | SA AHU-filter alarm limit | Pa | Write | ||
| AV | 104 | EA AHU-filter alarm limit | Pa | Write | ||
| AV | 109 | SA end-filter alarm limit | Pa | Write | ||
| AV | 113 | Seasonal controlled temperature regulation active | °C | Write | ||
| AV | 114 | Seasonal controlled temperature regulation inactive | °C | Write | ||
| AV | 117 | ERS 1 step | Write | |||
| AV | 118 | ERS 1 diff | K | Write | ||
| AV | 119 | ERS 1 breakpoint | °C | Write | ||
| AV | 122 | ERS 2 breakpoint X1 | °C | Write | ||
| AV | 123 | ERS 2 breakpoint X2 | °C | Write | ||
| AV | 124 | ERS 2 breakpoint X3 | °C | Write | ||
| AV | 125 | ERS 2 breakpoint X4 | °C | Write | ||
| AV | 126 | ERS 2 breakpoint Y1 | °C | Write | ||
| AV | 127 | ERS 2 breakpoint Y2 | °C | Write | ||
| AV | 128 | ERS 2 breakpoint Y3 | °C | Write | ||
| AV | 129 | ERS 2 breakpoint Y4 | °C | Write | ||
| AVmin | 132 | SA temperature set point | °C | Write | ||
| AVmin | 135 | EA/Room temperature set point | °C | Write | ||
| AV | 136 | SA min temp set point | °C | Write | ||
| AV | 137 | SA max temp set point | °C | Write | ||
| AV | 138 | EA regultaion P-band | K | Write | ||
| AV | 139 | EA regultaion I-time | s | Write | ||
| AV | 142 | ORS breakpoint X1 | °C | Write | ||
| AV | 143 | ORS breakpoint X2 | °C | Write | ||
| AV | 144 | ORS breakpoint X3 | °C | Write | ||
| AV | 145 | ORS breakpoint X4 | °C | Write | ||
| AV | 146 | ORS breakpoint Y1 | °C | Write | ||
| AV | 147 | ORS breakpoint Y2 | °C | Write | ||
| AV | 148 | ORS breakpoint Y3 | °C | Write | ||
| AV | 149 | ORS breakpoint Y4 | °C | Write | ||
| AV | 152 | ORE breakpoint X1 | °C | Write | ||
| AV | 153 | ORE breakpoint X2 | °C | Write | ||
| AV | 154 | ORE breakpoint X3 | °C | Write | ||
| AV | 155 | ORE breakpoint X4 | °C | Write | ||
| AV | 156 | ORE breakpoint Y1 | °C | Write | ||
| AV | 157 | ORE breakpoint Y2 | °C | Write | ||
| AV | 158 | ORE breakpoint Y3 | °C | Write | ||
| AV | 159 | ORE breakpoint Y4 | °C | Write | ||
| AV | 168 | External room temp from BMS | °C | Write | ||
| AV | 169 | External room temp from BMS alarm time | min | Write | ||
| AV | 178 | External OA temp from BMS | °C | Write | ||
| AV | 179 | External OA temp from BMS alarm time | min | Write | ||
| AV | 184 | RHX defrost start limit | Pa | Write | ||
| AV | 191 | RHX min exhaust air temp set point | °C | Write | ||
| AV | 192 | RHX min exhaust air temp P-band | K | Write | ||
| AV | 193 | RHX min exhaust air temp I-time | s | Write | ||
| AV | 199 | PHX periodic operation interval | h | Write | ||
| AV | 200 | PHX periodic operation time | min | Write | ||
| AV | 202 | PHX supply air temp set point displacement | K | Write | ||
| AV | 207 | CHX periodic operation interval | h | Write | ||
| AV | 208 | CHX periodic operation time | min | Write | ||
| AV | 213 | PHX/CHX Bypass defrost limit | °C | Write | ||
| AV | 214 | PHX/CHX Bypass defrost P-band | K | Write | ||
| AV | 215 | PHX/CHX Bypass defrost I-time | s | Write | ||
| AV | 220 | Heat exchange temperature regulation P-band | K | Write | ||
| AV | 221 | Heat exchange temperature regulation I-time | s | Write | ||
| AV | 222 | Cool exchange temperature regulation P-band | K | Write | ||
| AV | 223 | Cool exchange temperature regulation I-time | s | Write | ||
| AV | 226 | Re-heat P-band | K | Write | ||
| AV | 227 | Re-heat I-time | s | Write | ||
| AV | 230 | Re-heat periodic operation interval | h | Write | ||
| AV | 231 | Re-heat periodic operation time | min | Write | ||
| AV | 239 | Extra regulation sequence 1 heat max output signal | % | Write | ||
| AV | 240 | Extra regulation sequence 1 cool max output signal | % | Write | ||
| AV | 241 | Extra regulation sequence 1 heat P-band | K | Write | ||
| AV | 242 | Extra regulation sequence 1 heat I-time | s | Write | ||
| AV | 243 | Extra regulation sequence 1 cool P-band | K | Write | ||
| AV | 244 | Extra regulation sequence 1 cool I-time | s | Write | ||
| AV | 247 | Extra regulation 1 periodic operation interval | h | Write | ||
| AV | 248 | Extra regulation 1 periodic operation time | min | Write | ||
| AV | 252 | Extra regulation 1 temperature protection temperature | °C | Write | ||
| AV | 253 | Extra regulation 1 temperature protection alarm delay | min | Write | ||
| AV | 258 | Cool step1 min supply air flow limit | l/s | Write | ||
| AV | 259 | Cool step2 min supply air flow limit | l/s | Write | ||
| AV | 260 | Cool step3 min supply air flow limit | l/s | Write | ||
| AV | 262 | Cool SA neutral zone | K | Write | ||
| AV | 263 | Cool EA neutral zone | K | Write | ||
| AV | 264 | Cool outdoor temp limit 1 | °C | Write | ||
| AV | 265 | Cool outdoor temp limit 2 | °C | Write | ||
| AV | 266 | Cool outdoor temp limit 3 | °C | Write | ||
| AV | 267 | Cool 0-10V min supply air flow limit | l/s | Write | ||
| AV | 268 | Cool 0-10V min extract air flow limit | l/s | Write | ||
| AV | 269 | Cool restart time | min | Write | ||
| AV | 270 | Cool step up delay time | min | Write | ||
| AV | 271 | Cool stand still time | min | Write | ||
| AV | 272 | Cool P-band | K | Write | ||
| AV | 273 | Cool I-time | s | Write | ||
| AV | 277 | Cool periodic operation interval | h | Write | ||
| AV | 278 | Cool periodic operation time | min | Write | ||
| AV | 279 | Cool step1 min extract air flow limit | l/s | Write | ||
| AV | 280 | Cool step2 min extract air flow limit | l/s | Write | ||
| AV | 281 | Cool step3 min extract air flow limit | l/s | Write | ||
| AV | 285 | Summer night cool start time (hour) | h | Write | ||
| AV | 286 | Summer night cool start time (minute) | min | Write | ||
| AV | 287 | Summer night cool stop time (hour) | h | Write | ||
| AV | 288 | Summer night cool stop time (minute) | min | Write | ||
| AV | 289 | Summer night cool OA temp start limit | °C | Write | ||
| AV | 290 | Summer night cool EA temp start limit | °C | Write | ||
| AV | 291 | Summer night cool EA temp stop limit | °C | Write | ||
| AV | 292 | Summer night cool SA temp set point | °C | Write | ||
| AV | 293 | Summer night cool SA flow set point | l/s | Write | ||
| AV | 294 | Summer night cool EA flow set point | l/s | Write | ||
| AV | 297 | Intermittent night heat SA flow set point | l/s | Write | ||
| AV | 298 | Intermittent night heat SA duct pressure set point | Pa | Write | ||
| AV | 299 | Intermittent night heat EA temp start limit | °C | Write | ||
| AV | 300 | Intermittent night heat EA temp stop limit | °C | Write | ||
| AV | 301 | Intermittent night heat SA temp set point | °C | Write | ||
| AV | 303 | Intermittent night heat EA flow set point | l/s | Write | ||
| AV | 304 | Intermittent night heat EA duct pressure set point | Pa | Write | ||
| AV | 306 | Morning boost start time (hour) | h | Write | ||
| AV | 307 | Morning boost start time (minute) | min | Write | ||
| AV | 308 | Morning boost air flow set point | l/s | Write | ||
| AV | 309 | Morning boost duct pressure set point | Pa | Write | ||
| AV | 311 | Summer night cool SA duct pressure set point | Pa | Write | ||
| AV | 312 | Summer night cool EA duct pressure set point | Pa | Write | ||
| AV | 314 | Cooling boost comfort start limit | K | Write | ||
| AV | 315 | Cooling boost comfort regulation speed | %/s | Write | ||
| AV | 316 | Cooling boost economy P-band | K | Write | ||
| AV | 317 | Cooling boost economy I-time | s | Write | ||
| AV | 321 | Heating boost comfort start limit | K | Write | ||
| AV | 322 | Heating boost comfort regulation speed | %/s | Write | ||
| AV | 331 | Xzone ERS 1 step | Write | |||
| AV | 332 | Xzone ERS 1 diff | K | Write | ||
| AV | 333 | Xzone ERS 1 breakpoint | °C | Write | ||
| AV | 336 | Xzone ERS 2 breakpoint X1 | °C | Write | ||
| AV | 337 | Xzone ERS 2 breakpoint X2 | °C | Write | ||
| AV | 338 | Xzone ERS 2 breakpoint X3 | °C | Write | ||
| AV | 339 | Xzone ERS 2 breakpoint X4 | °C | Write | ||
| AV | 340 | Xzone ERS 2 breakpoint Y1 | °C | Write | ||
| AV | 341 | Xzone ERS 2 breakpoint Y2 | °C | Write | ||
| AV | 342 | Xzone ERS 2 breakpoint Y3 | °C | Write | ||
| AV | 343 | Xzone ERS 2 breakpoint Y4 | °C | Write | ||
| AV | 346 | Xzone SA temperature set point | °C | Write | ||
| AV | 349 | Xzone EA/Room temperature set point | °C | Write | ||
| AV | 350 | Xzone SA min temp set point | °C | Write | ||
| AV | 351 | Xzone SA max temp set point | °C | Write | ||
| AV | 352 | Xzone EA regultaion P-band | K | Write | ||
| AV | 353 | Xzone EA regultaion I-time | s | Write | ||
| AV | 354 | Xzone ORS breakpoint X1 | °C | Write | ||
| AV | 355 | Xzone ORS breakpoint X2 | °C | Write | ||
| AV | 356 | Xzone ORS breakpoint X3 | °C | Write | ||
| AV | 357 | Xzone ORS breakpoint X4 | °C | Write | ||
| AV | 358 | Xzone ORS breakpoint Y1 | °C | Write | ||
| AV | 359 | Xzone ORS breakpoint Y2 | °C | Write | ||
| AV | 360 | Xzone ORS breakpoint Y3 | °C | Write | ||
| AV | 361 | Xzone ORS breakpoint Y4 | °C | Write | ||
| AV | 364 | Xzone ORE breakpoint X1 | °C | Write | ||
| AV | 365 | Xzone ORE breakpoint X2 | °C | Write | ||
| AV | 366 | Xzone ORE breakpoint X3 | °C | Write | ||
| AV | 367 | Xzone ORE breakpoint X4 | °C | Write | ||
| AV | 368 | Xzone ORE breakpoint Y1 | °C | Write | ||
| AV | 369 | Xzone ORE breakpoint Y2 | °C | Write | ||
| AV | 370 | Xzone ORE breakpoint Y3 | °C | Write | ||
| AV | 371 | Xzone ORE breakpoint Y4 | °C | Write | ||
| AV | 380 | Xzone external room temp from BMS | °C | Write | ||
| AV | 381 | Xzone external room temp from BMS alarm time | min | Write | ||
| AV | 384 | Xzone reheat P-band | K | Write | ||
| AV | 385 | Xzone reheat I-time | s | Write | ||
| AV | 388 | Xzone reheat periodic operation interval | h | Write | ||
| AV | 389 | Xzone reheat periodic operation time | min | Write | ||
| AV | 396 | Xzone Cool SA neutral zone | K | Write | ||
| AV | 397 | Xzone Cool EA neutral zone | K | Write | ||
| AV | 398 | Xzone Cool P-band | K | Write | ||
| AV | 399 | Xzone Cool I-time | s | Write | ||
| AV | 403 | Xzone Cool periodic operation interval | h | Write | ||
| AV | 404 | Xzone Cool periodic operation time | min | Write | ||
| AV | 411 | Pre-heat temperature set point | °C | Write | ||
| AV | 412 | Pre-heat P-band | K | Write | ||
| AV | 413 | Pre-heat I-time | s | Write | ||
| AV | 416 | Pre-heat periodic operation interval | h | Write | ||
| AV | 417 | Pre-heat periodic operation time | min | Write | ||
| AV | 426 | ReCO2-CO2 set point | % | Write | ||
| AV | 427 | ReCO2 min. outdoor air | l/s | Write | ||
| AV | 428 | ReCO2 min. exhaust air | l/s | Write | ||
| AV | 429 | ReCO2-CO2 P-band | % | Write | ||
| AV | 430 | ReCO2-CO2 I-time | s | Write | ||
| AV | 431 | ReCO2-CO2 air flow boost reg. P-band | % | Write | ||
| AV | 432 | ReCO2-CO2 air flow boost reg. I-time | s | Write | ||
| AV | 433 | ReCO2 heat P-band | K | Write | ||
| AV | 434 | ReCO2 heat I-time | s | Write | ||
| AV | 435 | ReCO2 cool P-band | K | Write | ||
| AV | 436 | ReCO2 cool I-time | s | Write | ||
| AV | 437 | ReCO2-CO2 ppm set point | ppm | Write | ||
| AV | 438 | ReCO2-CO2 ppm P-band | ppm | Write | ||
| AV | 439 | ReCO2-VOC ppm set point | ppm | Write | ||
| AV | 440 | ReCO2-VOC ppm P-band | ppm | Write | ||
| AV | 443 | Humidifying on/off start level | %RH | Write | ||
| AV | 444 | Humidifying on/off stop level | %RH | Write | ||
| AV | 448 | Humidifying 0-10V set point | %RH | Write | ||
| AV | 449 | Humidifying 0-10V SA max set point | %RH | Write | ||
| AV | 450 | Humidifying 0-10V SA P-band | %RH | Write | ||
| AV | 451 | Humidifying 0-10V SA I-time | s | Write | ||
| AV | 452 | Humidifying 0-10V EA P-band | %RH | Write | ||
| AV | 453 | Humidifying 0-10V EA I-time | s | Write | ||
| AV | 458 | Dehumidifying SA set point | %RH | Write | ||
| AV | 460 | Dehumidifying EA set point | %RH | Write | ||
| AV | 470 | COOL DX Low pressure stop limit | kPa | Write | ||
| AV | 471 | COOL DX High pressure stop limit | kPa | Write | ||
| AV | 472 | COOL DX Restart time | min | Write | ||
| AV | 474 | Exhaust heat temperature set point | °C | Write | ||
| AV | 475 | Exhaust heat P-band | K | Write | ||
| AV | 476 | Exhaust heat I-time | s | Write | ||
| AV | 479 | Exhaust heat periodic operation interval | h | Write | ||
| AV | 480 | Exhaust heat periodic operation time | min | Write | ||
| AV | 482 | SMART Link WB Heat temperature set point | °C | Write | ||
| AV | 483 | SMART Link WB Heat temperature heat zone | K | Write | ||
| AV | 484 | SMART Link WB Cool temperature set point | °C | Write | ||
| AV | 485 | SMART Link WB Cool temperature heat zone | K | Write | ||
| AV | 491 | SMART Link WB Optimize valve upper limit | % | Write | ||
| AV | 492 | SMART Link WB Optimize valve lower limit | % | Write | ||
| AV | 493 | SMART Link WB Optimize time delay | s | Write | ||
| AV | 494 | SMART Link WB Optimize heat regulation speed | K/min | Write | ||
| AV | 495 | SMART Link WB Optimize cool regulation speed | K/min | Write | ||
| AV | 510 | SMART Link DX Amount of units | Write | |||
| AV | 519 | SMART Link OA operation limit | °C | Write | ||
| AV | 524 | AYC Heated water temp set point | °C | Write | ||
| AV | 526 | AYC Heated water OA temp for start of pump | °C | Write | ||
| AV | 527 | AYC Heated water OA temp for stop of pump | °C | Write | ||
| AV | 532 | AYC Heated water periodic operation interval | h | Write | ||
| AV | 533 | AYC Heated water periodic operation time | min | Write | ||
| AV | 537 | AYC Heated water OA temp compensation X1 | °C | Write | ||
| AV | 538 | AYC Heated water OA temp compensation X2 | °C | Write | ||
| AV | 539 | AYC Heated water OA temp compensation X3 | °C | Write | ||
| AV | 540 | AYC Heated water OA temp compensation X4 | °C | Write | ||
| AV | 541 | AYC Heated water OA temp compensation Y1 | °C | Write | ||
| AV | 542 | AYC Heated water OA temp compensation Y2 | °C | Write | ||
| AV | 543 | AYC Heated water OA temp compensation Y3 | °C | Write | ||
| AV | 544 | AYC Heated water OA temp compensation Y4 | °C | Write | ||
| AV | 549 | AYC Heated water room temp compensation temperature | °C | Write | ||
| AV | 550 | AYC Heated water room temp compensation P-band | K | Write | ||
| AV | 554 | AYC Heated water night temp compensation temp | K | Write | ||
| AV | 556 | AYC Heated water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 557 | AYC Heated water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 558 | AYC Heated water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 559 | AYC Heated water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 563 | AYC Heated water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 564 | AYC Heated water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 565 | AYC Heated water night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 566 | AYC Heated water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 569 | AYC Heated water P-band | K | Write | ||
| AV | 570 | AYC Heated water I-time | s | Write | ||
| AV | 572 | AYC Chilled water temp set point | °C | Write | ||
| AV | 575 | AYC Chilled water OA temp for start of pump | °C | Write | ||
| AV | 576 | AYC Chilled water OA temp for stop of pump | °C | Write | ||
| AV | 581 | AYC Chilled water periodic operation interval | h | Write | ||
| AV | 582 | AYC Chilled water periodic operation time | min | Write | ||
| AV | 586 | AYC Chilled water OA temp compensation X1 | °C | Write | ||
| AV | 587 | AYC Chilled water OA temp compensation X2 | °C | Write | ||
| AV | 588 | AYC Chilled water OA temp compensation X3 | °C | Write | ||
| AV | 589 | AYC Chilled water OA temp compensation X4 | °C | Write | ||
| AV | 590 | AYC Chilled water OA temp compensation Y1 | °C | Write | ||
| AV | 591 | AYC Chilled water OA temp compensation Y2 | °C | Write | ||
| AV | 592 | AYC Chilled water OA temp compensation Y3 | °C | Write | ||
| AV | 593 | AYC Chilled water OA temp compensation Y4 | °C | Write | ||
| AV | 598 | AYC Chilledwater room temp compensation temperature | °C | Write | ||
| AV | 599 | AYC Chilled water room temp compensation P-band | K | Write | ||
| AV | 603 | AYC Chilled water night temp compensation temp | °C | Write | ||
| AV | 605 | AYC Chilled water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 606 | AYC Chilled water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 607 | AYC Chilled water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 608 | AYC Chilled water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 612 | AYC Chilled water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 613 | AYC Chilled water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 614 | AYC Chilledwater night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 615 | AYC Chilled water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 619 | AYC Chilled water dew point compensation neutral zone | K | Write | ||
| AV | 620 | AYC Chilled water dew point compensation regulation speed | % | Write | ||
| AV | 623 | AYC Chilled water P-band | K | Write | ||
| AV | 624 | AYC Chilled water I-time | s | Write | ||
| AV | 638 | Optimize SA pressure set point | Pa | Write | ||
| AV | 639 | Optimize EA pressure set point | Pa | Write | ||
| AV | 672 | MIRU Control 1 Low speed duct pressure set point | Pa | Write | ||
| AV | 673 | MIRU Control 1 High speed duct pressure set point | Pa | Write | ||
| AV | 674 | MIRU Control 1 Low speed air flow set point | l/s | Write | ||
| AV | 675 | MIRU Control 1 High speed air flow set point | l/s | Write | ||
| AV | 676 | MIRU Control 1 offset factor for slave controlled air flow | Write | |||
| AV | 677 | MIRU Control 1 fixed flow offset for slave controlled SA flow | l/s | Write | ||
| AV | 680 | MIRU Control 2 Low speed duct pressure set point | Pa | Write | ||
| AV | 681 | MIRU Control 2 High speed duct pressure set point | Pa | Write | ||
| AV | 682 | MIRU Control 2 Low speed air flow set point | l/s | Write | ||
| AV | 683 | MIRU Control 2 High speed air flow set point | l/s | Write | ||
| AV | 684 | MIRU Control 2 offset factor for slave controlled air flow | Write | |||
| AV | 685 | MIRU Control 2 fixed flow offset for slave controlled SA flow | l/s | Write | ||
| AV | 688 | MIRU Control 3 Low speed duct pressure set point | Pa | Write | ||
| AV | 689 | MIRU Control 3 High speed duct pressure set point | Pa | Write | ||
| AV | 690 | MIRU Control 3 Low speed air flow set point | l/s | Write | ||
| AV | 691 | MIRU Control 3 High speed air flow set point | l/s | Write | ||
| AV | 692 | MIRU Control 3 offset factor for slave controlled air flow | Write | |||
| AV | 693 | MIRU Control 3 fixed flow offset for slave controlled SA flow | l/s | Write | ||
| AV | 696 | MIRU Control 4 Low speed duct pressure set point | Pa | Write | ||
| AV | 697 | MIRU Control 4 High speed duct pressure set point | Pa | Write | ||
| AV | 698 | MIRU Control 4 Low speed air flow set point | l/s | Write | ||
| AV | 699 | MIRU Control 4 High speed air flow set point | l/s | Write | ||
| AV | 704 | MIRU Control 5 Low speed duct pressure set point | Pa | Write | ||
| AV | 705 | MIRU Control 5 High speed duct pressure set point | Pa | Write | ||
| AV | 706 | MIRU Control 5 Low speed air flow set point | l/s | Write | ||
| AV | 707 | MIRU Control 5 High speed air flow set point | l/s | Write | ||
| AV | 712 | MIRU Control 6 Low speed duct pressure set point | Pa | Write | ||
| AV | 713 | MIRU Control 6 High speed duct pressure set point | Pa | Write | ||
| AV | 714 | MIRU Control 6 Low speed air flow set point | l/s | Write | ||
| AV | 715 | MIRU Control 6 High speed air flow set point | l/s | Write | ||
| AV | 720 | MIRU Control 7 Low speed duct pressure set point | Pa | Write | ||
| AV | 721 | MIRU Control 7 High speed duct pressure set point | Pa | Write | ||
| AV | 722 | MIRU Control 7 Low speed air flow set point | l/s | Write | ||
| AV | 723 | MIRU Control 7 High speed air flow set point | l/s | Write | ||
| AV | 728 | MIRU Control 8 Low speed duct pressure set point | Pa | Write | ||
| AV | 729 | MIRU Control 8 High speed duct pressure set point | Pa | Write | ||
| AV | 730 | MIRU Control 8 Low speed air flow set point | l/s | Write | ||
| AV | 731 | MIRU Control 8 High speed air flow set point | l/s | Write | ||
| AV | 736 | MIRU Control 9 Low speed duct pressure set point | Pa | Write | ||
| AV | 737 | MIRU Control 9 High speed duct pressure set point | Pa | Write | ||
| AV | 738 | MIRU Control 9 Low speed air flow set point | l/s | Write | ||
| AV | 739 | MIRU Control 9 High speed air flow set point | l/s | Write | ||
| AV | 744 | MIRU Control 10 Low speed duct pressure set point | Pa | Write | ||
| AV | 745 | MIRU Control 10 High speed duct pressure set point | Pa | Write | ||
| AV | 746 | MIRU Control 10 Low speed air flow set point | l/s | Write | ||
| AV | 747 | MIRU Control 10 High speed air flow set point | l/s | Write | ||
| AV | 752 | Delta temperature alarm limit | K | Write | ||
| AV | 753 | Efficiency alarm limit | % | Write | ||
| AV | 754 | Extra regulation sequence 1 heat neutral zone | K | Write | ||
| AV | 755 | Extra regulation sequence 2 heat neutral zone | K | Write | ||
| AV | 756 | ReCO2 heat neutral zone | K | Write | ||
| AV | 757 | H/C heat neutral zone | K | Write | ||
| AV | 758 | Re-heat neutral zone | K | Write | ||
| AV | 759 | Extra regulation sequence 1 cool neutral zone | K | Write | ||
| AV | 760 | Extra regulation sequence 2 cool neutral zone | K | Write | ||
| AV | 761 | ReCO2 cool neutral zone | K | Write | ||
| AV | 762 | H/C cool neutral zone | K | Write | ||
| AV | 763 | Cool neutral zone | K | Write | ||
| AV | 764 | Cooling boost neutral zone | K | Write | ||
| AV | 776 | Night temp compensation temp | K | Write | ||
| AV | 778 | Night temp compensation start time 1 (hour) | h | Write | ||
| AV | 779 | Night temp compensation start time 1 (minute) | min | Write | ||
| AV | 780 | Night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 781 | Night temp compensation stop time 1 (minute) | min | Write | ||
| AV | 783 | Night temp compensation start time 2 (hour) | h | Write | ||
| AV | 784 | Night temp compensation start time 2 (minute) | min | Write | ||
| AV | 785 | Night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 786 | Night temp compensation stop time 2 (minute) | min | Write | ||
| AV | 800 | External operation I/O-module A, analogue output | % | Write | ||
| AV | 801 | External operation I/O-module B, analogue output | % | Write | ||
| AV | 802 | External operation I/O-module C, analogue output | % | Write | ||
| AV | 818 | Extra regulation sequence 2 heat max output signal | % | Write | ||
| AV | 819 | Extra regulation sequence 2 cool max output signal | % | Write | ||
| AV | 820 | Extra regulation sequence 2 heat P-band | K | Write | ||
| AV | 821 | Extra regulation sequence 2 heat I-time | s | Write | ||
| AV | 822 | Extra regulation sequence 2 cool P-band | K | Write | ||
| AV | 823 | Extra regulation sequence 2 cool I-time | s | Write | ||
| AV | 826 | Extra regulation 2 periodic operation interval | h | Write | ||
| AV | 827 | Extra regulation 2 periodic operation time | min | Write | ||
| AV | 830 | Seasonal controlled supply air | °C | Write | ||
| AV | 831 | Seasonal controlled extract air/room temp | °C | Write | ||
| AV | 832 | Seasonal controlled supply air min temp | °C | Write | ||
| AV | 833 | Seasonal controlled supply air max temp | °C | Write | ||
| AV | 852 | H/C outdoor temperature limit heating | °C | Write | ||
| AV | 853 | H/C outdoor temperature limit cooling | °C | Write | ||
| AV | 854 | H/C air flow limit supply air | l/s | Write | ||
| AV | 855 | H/C air flow limit extract air | l/s | Write | ||
| AV | 891 | Humidifying start time 1 (hour) | h | Write | ||
| AV | 892 | Humidifying start time 1 (minute) | min | Write | ||
| AV | 893 | Humidifying stop time 1 (hour) | h | Write | ||
| AV | 894 | Humidifying stop time 1 (minute) | min | Write | ||
| AV | 896 | Humidifying start time 2 (hour) | h | Write | ||
| AV | 897 | Humidifying start time 2 (minute) | min | Write | ||
| AV | 898 | Humidifying stop time 2 (hour) | h | Write | ||
| AV | 899 | Humidifying stop time 2 (minute) | min | Write | ||
| AV | 901 | Humidifying start time 3 (hour) | h | Write | ||
| AV | 902 | Humidifying start time 3 (minute) | min | Write | ||
| AV | 903 | Humidifying stop time 3 (hour) | h | Write | ||
| AV | 904 | Humidifying stop time 3 (minute) | min | Write | ||
| AV | 906 | Humidifying start time 4 (hour) | h | Write | ||
| AV | 907 | Humidifying start time 4 (minute) | min | Write | ||
| AV | 908 | Humidifying stop time 4 (hour) | h | Write | ||
| AV | 909 | Humidifying stop time 4 (minute) | min | Write | ||
| AV | 910 | Humidifying start time | %RH | Write | ||
| AV | 911 | Humidifying stop time | %RH | Write | ||
| AV | 912 | Humidifying time | %RH | Write | ||
| AV | 1268 | Prolonged low speed hours | h | Write | ||
| AV | 1269 | Prolonged low speed minutes | min | Write | ||
| AV | 1270 | Prolonged high speed hours | h | Write | ||
| AV | 1271 | Prolonged high speed minutes | min | Write | ||
| AV | 3000 | External override code 1 | Write | |||
| AV | 3001 | External override code 2 | Write | |||
| AV | 3002 | External override, duration | h | Write | ||
| AV | 3010 | External override value, Supply air fan level | % | Write | ||
| AV | 3011 | External override value, Extract air fan level | % | Write | ||
| AV | 3020 | External override value, RX HX level | % | Write | ||
| AV | 3030 | External override value, PX HX damper 3A | % | Write | ||
| AV | 3031 | External override value, PX HX damper 1A | % | Write | ||
| AV | 3032 | External override value, PX HX bypass 2A | % | Write | ||
| AV | 3033 | External override value, PX HX bypass 4A | % | Write | ||
| AV | 3040 | External override value, CX HX valve | % | Write | ||
| AV | 3041 | External override value, CX HX pump level | % | Write | ||
| AV | 3050 | External override value, Pre-heat level | % | Write | ||
| AV | 3060 | External override value, Reheat level | % | Write | ||
| AV | 3070 | External override value, Xzone heat level | % | Write | ||
| AV | 3080 | External override value, Extra reg. 1 level | % | Write | ||
| AV | 3090 | External override value, Extra reg. 2 level | % | Write | ||
| AV | 3100 | External override value, Cool level | % | Write | ||
| AV | 3110 | External override value, Xzone cool level | % | Write | ||
| AV | 3130 | External override value, HC comp. level | % | Write | ||
| AV | 3131 | External override value, HC defrost recirc. level | % | Write | ||
| AV | 3132 | External override value, HC defrost el. heat level | % | Write | ||
| AV | 3150 | External override value, SMART Link DX 1 comp. level | % | Write | ||
| AV | 3151 | External override value, SMART Link DX 2 comp. level | % | Write | ||
| AV | 3152 | External override value, SMART Link DX 3 comp. level | % | Write | ||
| AV | 3153 | External override value, SMART Link DX 4 comp. level | % | Write | ||
| AV | 3170 | External override value, Humidifying level | % | Write | ||
| AV | 3180 | External override value, ReCO2 recirculation damper | % | Write | ||
| AV | 3181 | External override value, ReCO2 outdoor damper | % | Write | ||
| AV | 3190 | External override value, AYC heat valve level | % | Write | ||
| AV | 3191 | External override value, AYC cool valve level | % | Write | ||
| AV | 3220 | External override value, Miru 1 fan level | % | Write | ||
| AV | 3221 | External override value, Miru 2 fan level | % | Write | ||
| AV | 3222 | External override value, Miru 3 fan level | % | Write | ||
| AV | 3230 | External override value, Exhaust heat level | % | Write | ||
| BI | 1 | Operation active | Read | |||
| BI | 2 | Damper operation active | Read | |||
| BI | 3 | Low speed operation active | Read | |||
| BI | 4 | High speed operation active | Read | |||
| BI | 5 | Intermittent night heat active | Read | |||
| BI | 6 | Morning boost active | Read | |||
| BI | 7 | Heating boost active | Read | |||
| BI | 8 | Cooling boost active | Read | |||
| BI | 9 | Summer night cool active | Read | |||
| BImin | 13 | A-alarm active | Read | |||
| BImin | 14 | B-alarm active | Read | |||
| BI | 17 | HX operation active | Read | |||
| BI | 18 | HX cool recovery active | Read | |||
| BI | 19 | HX defrost active | Read | |||
| BI | 22 | RHX speed monitor signal | Read | |||
| BI | 27 | CHX pump output | Read | |||
| BI | 28 | CHX pump input | Read | |||
| BI | 30 | Seasonal controlled temperature regulation indication | Read | |||
| BI | 31 | Season heat, extra regulation sequence allowed | Read | |||
| BI | 32 | Season heat, re-heat allowed | Read | |||
| BI | 33 | Extra regulation sequence 1, output | Read | |||
| BI | 34 | Extra regulation sequence 1, power reduction active | Read | |||
| BI | 35 | Extra regulation sequence 1, anti-frost regulation active | Read | |||
| BI | 36 | Extra regulation sequence 1 combi coil input | Read | |||
| BI | 37 | Extra regulation sequence 1 combi coil output | Read | |||
| BI | 38 | Re-heat output | Read | |||
| BI | 39 | Re-heat power reduction active | Read | |||
| BI | 40 | Re-heat anti-frost regulation active | Read | |||
| BI | 43 | Cool output 1 | Read | |||
| BI | 44 | Cool output 2 | Read | |||
| BI | 46 | Extra regulation sequence 2 combi coil input | Read | |||
| BI | 47 | Extra regulation sequence 2 combi coil output | Read | |||
| BI | 48 | Extra regulation sequence 2, output | Read | |||
| BI | 49 | Extra regulation sequence 2, power reduction active | Read | |||
| BI | 50 | Extra regulation sequence 2, anti-frost regulation active | Read | |||
| BI | 51 | Pre-heat output | Read | |||
| BI | 52 | Pre-heat power reduction active | Read | |||
| BI | 53 | Pre-heat anti-frost regulation active | Read | |||
| BI | 56 | Xzone heat output | Read | |||
| BI | 57 | Xzone heat power reduction active | Read | |||
| BI | 58 | Xzone heat anti-frost regulation active | Read | |||
| BI | 63 | Xzone cool output 1 | Read | |||
| BI | 64 | Xzone cool output 2 | Read | |||
| BI | 65 | Xzone combi coil module A input | Read | |||
| BI | 66 | Xzone combi coil module A output | Read | |||
| BI | 67 | Xzone combi coil module B input | Read | |||
| BI | 68 | Xzone combi coil module B output | Read | |||
| BI | 75 | Exhaust heat pump output | Read | |||
| BI | 76 | Exhaust heat heating power reduction active | Read | |||
| BI | 77 | Exhaust heat anti-frost regulation active | Read | |||
| BI | 99 | AYC heat pump output | Read | |||
| BI | 100 | AYC heat pump input | Read | |||
| BI | 104 | AYC cool pump output | Read | |||
| BI | 105 | AYC cool pump input | Read | |||
| BI | 109 | COOL DX compressor 1 output | Read | |||
| BI | 110 | COOL DX compressor 1 input | Read | |||
| BI | 115 | COOL DX compressor 2 output | Read | |||
| BI | 116 | COOL DX compressor 2 input | Read | |||
| BI | 199 | Wireless AP active | Read | |||
| BI | 200 | External operation I/O-module 3, digital input 1 | Read | |||
| BI | 201 | External operation I/O-module 3, digital input 2 | Read | |||
| BI | 202 | External operation I/O-module 3, digital output 1 | Read | |||
| BI | 203 | External operation I/O-module 3, digital output 2 | Read | |||
| BI | 204 | External operation I/O-module 6, digital input 1 | Read | |||
| BI | 205 | External operation I/O-module 6, digital input 2 | Read | |||
| BI | 206 | External operation I/O-module 6, digital output 1 | Read | |||
| BI | 207 | External operation I/O-module 6, digital output 2 | Read | |||
| BI | 208 | External operation I/O-module A, digital input | Read | |||
| BI | 209 | External operation I/O-module B, digital input | Read | |||
| BI | 210 | External operation I/O-module C, digital input | Read | |||
| BI | 319 | SMART Link, WB operation | Read | |||
| BI | 323 | SMART Link, DX unit 1 operation | Read | |||
| BI | 324 | SMART Link, DX unit 1 cool mode | Read | |||
| BI | 325 | SMART Link, DX unit 1 defrost request | Read | |||
| BI | 326 | SMART Link, DX unit 1 defrost active | Read | |||
| BI | 334 | SMART Link, DX unit 2 operation | Read | |||
| BI | 335 | SMART Link, DX unit 2 cool mode | Read | |||
| BI | 336 | SMART Link, DX unit 2 defrost request | Read | |||
| BI | 337 | SMART Link, DX unit 2 defrost active | Read | |||
| BI | 345 | SMART Link, DX unit 3 operation | Read | |||
| BI | 346 | SMART Link, DX unit 3 cool mode | Read | |||
| BI | 347 | SMART Link, DX unit 3 defrost request | Read | |||
| BI | 348 | SMART Link, DX unit 3 defrost active | Read | |||
| BI | 356 | SMART Link, DX unit 4 operation | Read | |||
| BI | 357 | SMART Link, DX unit 4 cool mode | Read | |||
| BI | 358 | SMART Link, DX unit 4 defrost request | Read | |||
| BI | 359 | SMART Link, DX unit 4 defrost active | Read | |||
| BI | 367 | SMART Link, DX Defrost airflow increase status | Read | |||
| BI | 501 | Alarm 1:1 External fire alarm no. 1 tripped | Read | |||
| BI | 502 | Alarm 1:2 External fire alarm no. 2 tripped | Read | |||
| BI | 503 | Alarm 1:3 Internal fire alarm tripped | Read | |||
| BI | 516 | Alarm 2:1 External alarm no. 1 tripped | Read | |||
| BI | 517 | Alarm 2:2 External alarm no. 2 tripped | Read | |||
| BI | 531 | Alarm 3:1 Pre-heat I/O-module no. 9 com. error | Read | |||
| BI | 532 | Alarm 3:2 Pre-heat electrical heater overheat protection tripped | Read | |||
| BI | 533 | Alarm 3:3 Pre-heat frost protection tripped | Read | |||
| BI | 534 | Alarm 3:4 Pre-heat frost protection temperature sensor defective | Read | |||
| BI | 535 | Alarm 3:5 Pre-heat temperature sensor defective | Read | |||
| BI | 536 | Alarm 3:6 Pre-heat valve monitoring tripped | Read | |||
| BI | 537 | Alarm 3:7 Pre-heat temperature below set point alarm limit | Read | |||
| BI | 538 | Alarm 3:8 Pre-heat alarm input tripped | Read | |||
| BI | 546 | Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. error | Read | |||
| BI | 547 | Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection tripped | Read | |||
| BI | 548 | Alarm 4:3 Extra reg. sequence 1 frost protection tripped | Read | |||
| BI | 549 | Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor defective | Read | |||
| BI | 550 | Alarm 4:5 Extra reg. sequence 1 valve monitoring tripped | Read | |||
| BI | 551 | Alarm 4:6 Extra reg. sequence 1 alarm input tripped | Read | |||
| BI | 552 | Alarm 4:7 Extra reg. sequence 1 temperature protection from com. error | Read | |||
| BI | 553 | Alarm 4:8 Extra reg. sequence 1 combi coil temperature sensor defective | Read | |||
| BI | 554 | Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. error | Read | |||
| BI | 555 | Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection tripped | Read | |||
| BI | 556 | Alarm 4:11 Extra reg. sequence 2 frost protection tripped | Read | |||
| BI | 557 | Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor defective | Read | |||
| BI | 558 | Alarm 4:13 Extra reg. sequence 2 valve monitoring tripped | Read | |||
| BI | 559 | Alarm 4:14 Extra reg. sequence 2 alarm input tripped | Read | |||
| BI | 560 | Alarm 4:15 Extra reg. sequence 2 combi coil temperature sensor defective | Read | |||
| BI | 561 | Alarm 5:1 Re-heat electrical heater over heat protection tripped | Read | |||
| BI | 562 | Alarm 5:2 Re-heat frost protection tripped | Read | |||
| BI | 563 | Alarm 5:3 Re-heat frost protection temperature sensor defective | Read | |||
| BI | 564 | Alarm 5:4 Re-heat valve monitoring tripped | Read | |||
| BI | 565 | Alarm 5:5 Re-heat alarm input tripped | Read | |||
| BI | 576 | Alarm 6:1 Xzone I/O-module no. A com. error | Read | |||
| BI | 577 | Alarm 6:2 Xzone electrical heater overheat protection tripped | Read | |||
| BI | 578 | Alarm 6:3 Xzone frost protection tripped | Read | |||
| BI | 579 | Alarm 6:4 Xzone frost protection temperature sensor defective | Read | |||
| BI | 580 | Alarm 6:5 Xzone supply air temperature sensor defective | Read | |||
| BI | 581 | Alarm 6:6 Xzone heat valve monitoring tripped | Read | |||
| BI | 582 | Alarm 6:7 Xzone supply air temperature below set point alarm limit | Read | |||
| BI | 583 | Alarm 6:8 Xzone supply air temperature above set point alarm limit | Read | |||
| BI | 584 | Alarm 6:9 Xzone heat alarm input tripped | Read | |||
| BI | 585 | Alarm 6:10 Xzone combi coil module A temperature sensor defective | Read | |||
| BI | 586 | Alarm 6:11 Xzone temperature protection I/O-module no. 9 com. error | Read | |||
| BI | 591 | Alarm 7:1 Xzone I/O-module no. B com. error | Read | |||
| BI | 592 | Alarm 7:2 Xzone extract air temperature sensor defective | Read | |||
| BI | 593 | Alarm 7:3 Xzone cool valve monitoring tripped | Read | |||
| BI | 594 | Alarm 7:4 Xzone extract air temperature below set point alarm limit | Read | |||
| BI | 595 | Alarm 7:5 Xzone cool alarm input 1 tripped | Read | |||
| BI | 596 | Alarm 7:6 Xzone cool alarm input 2 tripped | Read | |||
| BI | 597 | Alarm 7:7 Xzone combi coil module B temperature sensor defective | Read | |||
| BI | 610 | Alarm 8:5 Cool valve monitoring tripped | Read | |||
| BI | 611 | Alarm 8:6 Cool alarm input 1 tripped | Read | |||
| BI | 612 | Alarm 8:7 Cool alarm input 2 tripped | Read | |||
| BI | 621 | Alarm 9:1 Exhaust heat I/O-module no. 4 com error | Read | |||
| BI | 622 | Alarm 9:2 Exhaust heat electrical heater overheat protection tripped | Read | |||
| BI | 623 | Alarm 9:3 Exhaust heat frost protection tripped | Read | |||
| BI | 624 | Alarm 9:4 Exhaust heat frost protection temperature sensor defective | Read | |||
| BI | 625 | Alarm 9:5 Exhaust heat temperature sensor defective | Read | |||
| BI | 626 | Alarm 9:6 Exhaust heat valve monitoring tripped | Read | |||
| BI | 627 | Alarm 9:7 Exhaust heat temperature below set point alarm limit | Read | |||
| BI | 628 | Alarm 9:8 Exhaust heat alarm input tripped | Read | |||
| BI | 636 | Alarm 10:1 Supply air temperature sensor defective | Read | |||
| BI | 637 | Alarm 10:2 Supply air temperature sensor for density compensation defective | Read | |||
| BI | 638 | Alarm 10:3 Extract air temperature sensor defective | Read | |||
| BI | 639 | Alarm 10:4 Extract air temperature sensor for density compensation defective | Read | |||
| BI | 640 | Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def. | Read | |||
| BI | 641 | Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def. | Read | |||
| BI | 642 | Alarm 10:7 Extract air duct temperature sensor defective | Read | |||
| BI | 645 | Alarm 10:10 Outdoor air temperature sensor defective | Read | |||
| BI | 651 | Alarm 11:1 Room temperature sensor no. 1 defective | Read | |||
| BI | 652 | Alarm 11:2 Room temperature sensor no. 2 defective | Read | |||
| BI | 653 | Alarm 11:3 Room temperature sensor no. 3 defective | Read | |||
| BI | 654 | Alarm 11:4 Room temperature sensor no. 4 defective | Read | |||
| BI | 655 | Alarm 11:5 Xzone room temperature sensor no. 5 defective | Read | |||
| BI | 656 | Alarm 11:6 Xzone room temperature sensor no. 6 defective | Read | |||
| BI | 657 | Alarm 11:7 Xzone room temperature sensor no. 7 defective | Read | |||
| BI | 658 | Alarm 11:8 Xzone room temperature sensor no. 8 defective | Read | |||
| BI | 659 | Alarm 11:9 Outdoor temperature sensor no. A defective | Read | |||
| BI | 660 | Alarm 11:10 Outdoor temperature sensor no. B defective | Read | |||
| BI | 661 | Alarm 11:11 Outdoor temperature sensor no. C defective | Read | |||
| BI | 662 | Alarm 11:12 Outdoor temperature sensor no. D defective | Read | |||
| BI | 663 | Alarm 11:13 Room temperature from com. error | Read | |||
| BI | 664 | Alarm 11:14 Xzone room temperature from com. error | Read | |||
| BI | 665 | Alarm 11:15 Outdoor temperature from com. error | Read | |||
| BI | 666 | Alarm 12:1 Supply air temperature below set point alarm limit | Read | |||
| BI | 667 | Alarm 12:2 Supply air temperature above set point alarm limit | Read | |||
| BI | 671 | Alarm 12:6 Extract air temperature below alarm limit | Read | |||
| BI | 676 | Alarm 12:11 Temperature guard below alarm limit | Read | |||
| BI | 678 | Alarm 12:13 Heat exchange efficiency below alarm limit | Read | |||
| BI | 681 | Alarm 13:1 Humidification I/O-module no. 4 com. error | Read | |||
| BI | 682 | Alarm 13:2 Supply air humidity sensor defective | Read | |||
| BI | 683 | Alarm 13:3 Extract air humidity sensor defective | Read | |||
| BI | 684 | Alarm 13:4 Exhaust air humidity sensor defective | Read | |||
| BI | 685 | Alarm 13:5 Outdoor air humidity sensor defective | Read | |||
| BI | 686 | Alarm 13:6 Room humidity sensor defective | Read | |||
| BI | 689 | Alarm 13:9 Humidifier alarm output tripped | Read | |||
| BI | 691 | Alarm 13:11 VOC sensor com. error | Read | |||
| BI | 692 | Alarm 13:12 VOC sensor internal com. error | Read | |||
| BI | 693 | Alarm 13:13 VOC sensor internal error | Read | |||
| BI | 694 | Alarm 13:14 VOC sensor level below/above set point alarm limit | Read | |||
| BI | 696 | Alarm 14:1 Re-heat liquid flow measurement I/O-module no. 6 com. error | Read | |||
| BI | 697 | Alarm 14:2 Re-heat liquid flow measurement temp. sensor no. 1 defective | Read | |||
| BI | 698 | Alarm 14:3 Re-heat liquid flow measurement temp. sensor no. 2 defective | Read | |||
| BI | 699 | Alarm 14:4 Re-heat liquid flow measurement valve leakage | Read | |||
| BI | 700 | Alarm 14:5 Re-heat liquid flow measurement flow sensor defective | Read | |||
| BI | 703 | Alarm 14:8 Cool liquid flow measurement I/O-module no. 7 com. error | Read | |||
| BI | 704 | Alarm 14:9 Cool liquid flow measurement temp. sensor no. 1 defective | Read | |||
| BI | 705 | Alarm 14:10 Cool liquid flow measurement temp. sensor no. 2 defective | Read | |||
| BI | 706 | Alarm 14:11 Cool liquid flow measurement valve leakage | Read | |||
| BI | 707 | Alarm 14:12 Cool liquid flow measurement flow sensor defective | Read | |||
| BI | 711 | Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. error | Read | |||
| BI | 712 | Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defective | Read | |||
| BI | 713 | Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defective | Read | |||
| BI | 714 | Alarm 15:4 Plate heat exchanger damper monitor tripped | Read | |||
| BI | 716 | Alarm 15:6 Plate heat exchanger bypass damper 4A monitor tripped | Read | |||
| BI | 717 | Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 718 | Alarm 15:8 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 719 | Alarm 15:9 Plate heat exchanger damper no. 1 monitor tripped | Read | |||
| BI | 720 | Alarm 15:10 Plate heat exchanger damper no. 2 monitor tripped | Read | |||
| BI | 721 | Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 722 | Alarm 15:12 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 723 | Alarm 15:13 Plate counter flow heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 724 | Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. error | Read | |||
| BI | 725 | Alarm 15:15 Plate heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 726 | Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. error | Read | |||
| BI | 727 | Alarm 16:2 Coil heat exchanger temperature sensor defective | Read | |||
| BI | 728 | Alarm 16:3 Coil heat exchanger valve monitor tripped | Read | |||
| BI | 729 | Alarm 16:4 Coil heat exchanger pump monitor tripped | Read | |||
| BI | 730 | Alarm 16:5 Coil heat exchanger I/O-module no. C communication error | Read | |||
| BI | 731 | Alarm 16:6 Coil heat exchanger pressure sensor defective | Read | |||
| BI | 732 | Alarm 16:7 Coil heat exchanger low pressure brine circuit | Read | |||
| BI | 733 | Alarm 16:8 Coil heat exchanger pressure below alarm limit | Read | |||
| BI | 741 | Alarm 17:1 Rotary heat exchanger motor controller com. error | Read | |||
| BI | 742 | Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. error | Read | |||
| BI | 743 | Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 744 | Alarm 17:4 Rotary heat exchanger speed monitor tripped | Read | |||
| BI | 745 | Alarm 17:5 Rotary heat exchanger motor controller over current | Read | |||
| BI | 746 | Alarm 17:6 Rotary heat exchanger motor controller under voltage | Read | |||
| BI | 747 | Alarm 17:7 Rotary heat exchanger motor controller over voltage | Read | |||
| BI | 748 | Alarm 17:8 Rotary heat exchanger motor controller over temperature | Read | |||
| BI | 749 | Alarm 17:9 Rotary heat exchanger motor controller start error | Read | |||
| BI | 750 | Alarm 17:10 Rotary heat exchanger motor controller internal error | Read | |||
| BI | 751 | Alarm 17:11 Rotary heat exchanger motor controller phase error | Read | |||
| BI | 752 | Alarm 17:12 Rotary heat exchanger motor controller internal memory error | Read | |||
| BI | 753 | Alarm 17:13 Rotary heat exchanger motor controller current reduction | Read | |||
| BI | 754 | Alarm 17:14 Rotary heat exchanger motor controller internal com. error | Read | |||
| BI | 755 | Alarm 17:15 Rotary heat exchanger I/O-module com. error | Read | |||
| BI | 756 | Alarm 18:1 AYC I/O-module no. 7 com. error | Read | |||
| BI | 757 | Alarm 18:2 AYC heat temperature sensor defective | Read | |||
| BI | 758 | Alarm 18:3 AYC heat valve monitor tripped | Read | |||
| BI | 759 | Alarm 18:4 AYC heat pump monitor tripped | Read | |||
| BI | 760 | Alarm 18:5 AYC heat temperature below set point alarm limit | Read | |||
| BI | 761 | Alarm 18:6 AYC heat temperature above set point alarm limit | Read | |||
| BI | 764 | Alarm 18:9 AYC cool temperature sensor defective | Read | |||
| BI | 765 | Alarm 18:10 AYC cool valve monitor tripped | Read | |||
| BI | 766 | Alarm 18:11 AYC cool pump monitor tripped | Read | |||
| BI | 767 | Alarm 18:12 AYC cool temperature below set point alarm limit | Read | |||
| BI | 768 | Alarm 18:13 AYC cool temperature above set point alarm limit | Read | |||
| BI | 771 | Alarm 19:1 Rotary heat exchanger AQC pressure sensor no. E com. error | Read | |||
| BI | 772 | Alarm 19:2 Rotary heat exchanger AQC pressure below set point alarm limit | Read | |||
| BI | 773 | Alarm 19:3 Rotary heat exchanger AQC damper monitoring tripped | Read | |||
| BI | 801 | Alarm 21:1 COOL DX I/O-module no. 2 com. error | Read | |||
| BI | 802 | Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defective | Read | |||
| BI | 803 | Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limit | Read | |||
| BI | 804 | Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defective | Read | |||
| BI | 805 | Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limit | Read | |||
| BI | 806 | Alarm 21:6 COOL DX compressor no. 1 monitor tripped | Read | |||
| BI | 807 | Alarm 21:7 COOL DX compressor no. 1 restart error | Read | |||
| BI | 808 | Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defective | Read | |||
| BI | 809 | Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limit | Read | |||
| BI | 810 | Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defective | Read | |||
| BI | 811 | Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limit | Read | |||
| BI | 812 | Alarm 21:12 COOL DX compressor no. 2 monitor tripped | Read | |||
| BI | 813 | Alarm 21:13 COOL DX compressor no. 2 restart error | Read | |||
| BI | 814 | Alarm 21:14 COOL DX outdoor air temperature sensor defective | Read | |||
| BI | 815 | Alarm 21:15 COOL DX phase sequence error or supply voltage missing | Read | |||
| BI | 816 | Alarm 22:1 Xzone heat liquid flow measurement I/O-module no. D com. error | Read | |||
| BI | 817 | Alarm 22:2 Xzone heat liquid flow measurement temp. sensor no. 1 defective | Read | |||
| BI | 818 | Alarm 22:3 Xzone heat liquid flow measurement temp. sensor no. 2 defective | Read | |||
| BI | 819 | Alarm 22:4 Xzone heat liquid flow measurement valve leakage | Read | |||
| BI | 820 | Alarm 22:5 Xzone heat liquid flow measurement flow sensor defective | Read | |||
| BI | 823 | Alarm 22:8 Xzone cool liquid flow measurement I/O-module no. E com. error | Read | |||
| BI | 824 | Alarm 22:9 Xzone cool liquid flow measurement temp. sensor no. 1 defective | Read | |||
| BI | 825 | Alarm 22:10 Xzone cool liquid flow measurement temp. sensor no. 2 defective | Read | |||
| BI | 826 | Alarm 22:11 Xzone cool liquid flow measurement valve leakage | Read | |||
| BI | 827 | Alarm 22:12 Xzone cool liquid flow measurement flow sensor defective | Read | |||
| BI | 831 | Alarm 23:1 SMART Link com. error | Read | |||
| BI | 832 | Alarm 23:2 SMART Link alarm level 1 tripped | Read | |||
| BI | 833 | Alarm 23:3 SMART Link alarm level 2 tripped | Read | |||
| BI | 834 | Alarm 23:4 SMART Link alarm level 3 tripped | Read | |||
| BI | 840 | Alarm 23:10 AQUA Link I/O-module no. 5 com. error | Read | |||
| BI | 841 | Alarm 23:11 AQUA Link pump monitor tripped | Read | |||
| BI | 846 | Alarm 24:1 SMART Link no. 1 com. error | Read | |||
| BI | 847 | Alarm 24:2 SMART Link no. 1 alarm tripped | Read | |||
| BI | 849 | Alarm 24:4 SMART Link no. 2 com. error | Read | |||
| BI | 850 | Alarm 24:5 SMART Link no. 2 alarm tripped | Read | |||
| BI | 852 | Alarm 24:7 SMART Link no. 3 com. error | Read | |||
| BI | 853 | Alarm 24:8 SMART Link no. 3 alarm tripped | Read | |||
| BI | 855 | Alarm 24:10 SMART Link no. 4 com. error | Read | |||
| BI | 856 | Alarm 24:11 SMART Link no. 4 alarm tripped | Read | |||
| BI | 858 | Alarm 24:13 SMART Link supply air flow below alarm limit | Read | |||
| BI | 861 | Alarm 25:1 SMART Link+ cooling circuit A com. error | Read | |||
| BI | 862 | Alarm 25:2 SMART Link+ cooling circuit B com. error | Read | |||
| BI | 863 | Alarm 25:3 SMART Link+ heating circuit A com. error | Read | |||
| BI | 864 | Alarm 25:4 SMART Link+ heating circuit B com. error | Read | |||
| BI | 876 | Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. error | Read | |||
| BI | 877 | Alarm 26:2 Pre-filter supply air dirty | Read | |||
| BI | 882 | Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. error | Read | |||
| BI | 883 | Alarm 26:8 Pre-filter extract air dirty | Read | |||
| BI | 891 | Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. error | Read | |||
| BI | 892 | Alarm 27:2 AHU filter supply air dirty | Read | |||
| BI | 897 | Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. error | Read | |||
| BI | 898 | Alarm 27:8 AHU filter extract air dirty | Read | |||
| BI | 906 | Alarm 28:1 End filter supply air pressure sensor no. A com. error | Read | |||
| BI | 907 | Alarm 28:2 End filter supply air dirty | Read | |||
| BI | 921 | Alarm 29:1 Energy monitoring pulse counter com. error | Read | |||
| BI | 936 | Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. error | Read | |||
| BI | 937 | Alarm 30:2 Air flow measurement supply air flow below set point alarm limit | Read | |||
| BI | 938 | Alarm 30:3 Air flow measurement supply air flow above set point alarm limit | Read | |||
| BI | 941 | Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. error | Read | |||
| BI | 942 | Alarm 30:7 Air flow measurement extract air flow below set point alarm limit | Read | |||
| BI | 943 | Alarm 30:8 Air flow measurement extract air flow above set point alarm limit | Read | |||
| BI | 946 | Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. error | Read | |||
| BI | 951 | Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. error | Read | |||
| BI | 952 | Alarm 31:2 Pressure regulation supply air pressure below set point alarm limit | Read | |||
| BI | 953 | Alarm 31:3 Pressure regulation supply air pressure above set point alarm limit | Read | |||
| BI | 956 | Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. error | Read | |||
| BI | 957 | Alarm 31:7 Pressure regulation extract air press. below set point alarm limit | Read | |||
| BI | 958 | Alarm 31:8 Pressure regulation extract air press. above set point alarm limit | Read | |||
| BI | 966 | Alarm 32:1 ReCO2 I/O-module no. 0 com. error | Read | |||
| BI | 967 | Alarm 32:2 ReCO2 pressure sensor no. 0 com. error | Read | |||
| BI | 968 | Alarm 32:3 ReCO2 recirculation damper monitoring tripped | Read | |||
| BI | 969 | Alarm 32:4 ReCO2 outdoor air damper monitoring tripped | Read | |||
| BI | 981 | Alarm 33:1 Service period above alarm limit | Read | |||
| BI | 995 | Alarm 33:15 Lock function tripped | Read | |||
| BI | 996 | Alarm 34:1 External control I/O-module no. 3 com. error | Read | |||
| BI | 997 | Alarm 34:2 External control I/O-module no. 6 com. error | Read | |||
| BI | 1011 | Alarm 35:1 Booster diffusers I/O-module no. 8 com. error | Read | |||
| BI | 1026 | Alarm 36:1 External BMS control I/O-module no. A communication error | Read | |||
| BI | 1027 | Alarm 36:2 External BMS control I/O-module no. A temp. sensor no. 1 defective | Read | |||
| BI | 1028 | Alarm 36:3 External BMS control I/O-module no. A temp. sensor no. 2 defective | Read | |||
| BI | 1031 | Alarm 36:6 External BMS control I/O-module no. B communication error | Read | |||
| BI | 1032 | Alarm 36:7 External BMS control I/O-module no. B temp. sensor no. 1 defective | Read | |||
| BI | 1033 | Alarm 36:8 External BMS control I/O-module no. B temp. sensor no. 2 defective | Read | |||
| BI | 1036 | Alarm 36:11 External BMS control I/O-module no. C communication error | Read | |||
| BI | 1037 | Alarm 36:12 External BMS control I/O-module no. C temp. sensor no. 1 defective | Read | |||
| BI | 1038 | Alarm 36:13 External BMS control I/O-module no. C temp. sensor no. 2 defective | Read | |||
| BI | 1041 | Alarm 37:1 Multilogic com. error | Read | |||
| BI | 1056 | Alarm 38:1 MIRU 1 com. error | Read | |||
| BI | 1057 | Alarm 38:2 MIRU 1 motor controller alarm tripped | Read | |||
| BI | 1058 | Alarm 38:3 MIRU 1 motor controller com. error | Read | |||
| BI | 1059 | Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1060 | Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1061 | Alarm 38:6 MIRU 1 temperature sensor defective | Read | |||
| BI | 1062 | Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1063 | Alarm 38:8 MIRU 1 air flow below set point alarm limit | Read | |||
| BI | 1064 | Alarm 38:9 MIRU 1 air flow above set point alarm limit | Read | |||
| BI | 1065 | Alarm 38:10 MIRU 1 pressure below set point alarm limit | Read | |||
| BI | 1066 | Alarm 38:11 MIRU 1 pressure above set point alarm limit | Read | |||
| BI | 1071 | Alarm 39:1 MIRU 2 com. error | Read | |||
| BI | 1072 | Alarm 39:2 MIRU 2 motor controller alarm tripped | Read | |||
| BI | 1073 | Alarm 39:3 MIRU 2 motor controller com. error | Read | |||
| BI | 1074 | Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1075 | Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1076 | Alarm 39:6 MIRU 2 temperature sensor defective | Read | |||
| BI | 1077 | Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1078 | Alarm 39:8 MIRU 2 air flow below set point alarm limit | Read | |||
| BI | 1079 | Alarm 39:9 MIRU 2 air flow above set point alarm limit | Read | |||
| BI | 1080 | Alarm 39:10 MIRU 2 pressure below set point alarm limit | Read | |||
| BI | 1081 | Alarm 39:11 MIRU 2 pressure above set point alarm limit | Read | |||
| BI | 1086 | Alarm 40:1 MIRU 3 com. error | Read | |||
| BI | 1087 | Alarm 40:2 MIRU 3 motor controller alarm tripped | Read | |||
| BI | 1088 | Alarm 40:3 MIRU 3 motor controller com. error | Read | |||
| BI | 1089 | Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1090 | Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1091 | Alarm 40:6 MIRU 3 temperature sensor defective | Read | |||
| BI | 1092 | Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1093 | Alarm 40:8 MIRU 3 air flow below set point alarm limit | Read | |||
| BI | 1094 | Alarm 40:9 MIRU 3 air flow above set point alarm limit | Read | |||
| BI | 1095 | Alarm 40:10 MIRU 3 pressure below set point alarm limit | Read | |||
| BI | 1096 | Alarm 40:11 MIRU 3 pressure above set point alarm limit | Read | |||
| BI | 1101 | Alarm 41:1 MIRU 4 com. error | Read | |||
| BI | 1102 | Alarm 41:2 MIRU 4 motor controller alarm tripped | Read | |||
| BI | 1103 | Alarm 41:3 MIRU 4 motor controller com. error | Read | |||
| BI | 1104 | Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1105 | Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1106 | Alarm 41:6 MIRU 4 temperature sensor defective | Read | |||
| BI | 1107 | Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1116 | Alarm 42:1 MIRU 5 com. error | Read | |||
| BI | 1117 | Alarm 42:2 MIRU 5 motor controller alarm tripped | Read | |||
| BI | 1118 | Alarm 42:3 MIRU 5 motor controller com. error | Read | |||
| BI | 1119 | Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1120 | Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1121 | Alarm 42:6 MIRU 5 temperature sensor defective | Read | |||
| BI | 1122 | Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1131 | Alarm 43:1 MIRU 6 com. error | Read | |||
| BI | 1132 | Alarm 43:2 MIRU 6 motor controller alarm tripped | Read | |||
| BI | 1133 | Alarm 43:3 MIRU 6 motor controller com. error | Read | |||
| BI | 1134 | Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1135 | Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1136 | Alarm 43:6 MIRU 6 temperature sensor defective | Read | |||
| BI | 1137 | Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1146 | Alarm 44:1 MIRU 7 com. error | Read | |||
| BI | 1147 | Alarm 44:2 MIRU 7 motor controller alarm tripped | Read | |||
| BI | 1148 | Alarm 44:3 MIRU 7 motor controller com. error | Read | |||
| BI | 1149 | Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1150 | Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1151 | Alarm 44:6 MIRU 7 temperature sensor defective | Read | |||
| BI | 1152 | Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1161 | Alarm 45:1 MIRU 8 com. error | Read | |||
| BI | 1162 | Alarm 45:2 MIRU 8 motor controller alarm tripped | Read | |||
| BI | 1163 | Alarm 45:3 MIRU 8 motor controller com. error | Read | |||
| BI | 1164 | Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1165 | Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1166 | Alarm 45:6 MIRU 8 temperature sensor defective | Read | |||
| BI | 1167 | Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1176 | Alarm 46:1 MIRU 9 com. error | Read | |||
| BI | 1177 | Alarm 46:2 MIRU 9 motor controller alarm tripped | Read | |||
| BI | 1178 | Alarm 46:3 MIRU 9 motor controller com. error | Read | |||
| BI | 1179 | Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1180 | Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1181 | Alarm 46:6 MIRU 9 temperature sensor defective | Read | |||
| BI | 1182 | Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1191 | Alarm 47:1 MIRU 10 com. error | Read | |||
| BI | 1192 | Alarm 47:2 MIRU 10 motor controller alarm tripped | Read | |||
| BI | 1193 | Alarm 47:3 MIRU 10 motor controller com. error | Read | |||
| BI | 1194 | Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1195 | Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1196 | Alarm 47:6 MIRU 10 temperature sensor defective | Read | |||
| BI | 1197 | Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1221 | Alarm 49:1 Supply air fan no. 1A com. error | Read | |||
| BI | 1222 | Alarm 49:2 Supply air fan no. 1A motor controller over current | Read | |||
| BI | 1223 | Alarm 49:3 Supply air fan no. 1A motor controller under voltage | Read | |||
| BI | 1224 | Alarm 49:4 Supply air fan no. 1A motor controller over voltage | Read | |||
| BI | 1225 | Alarm 49:5 Supply air fan no. 1A motor controller over temperature | Read | |||
| BI | 1226 | Alarm 49:6 Supply air fan no. 1A motor controller start error | Read | |||
| BI | 1227 | Alarm 49:7 Supply air fan no. 1A motor controller ripple error | Read | |||
| BI | 1228 | Alarm 49:8 Supply air fan no. 1A motor controller phase error | Read | |||
| BI | 1229 | Alarm 49:9 Supply air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1230 | Alarm 49:10 Supply air fan no. 1A motor controller current reduction | Read | |||
| BI | 1231 | Alarm 49:11 Supply air fan no. 1A motor controller internal com. error | Read | |||
| BI | 1236 | Alarm 50:1 Supply air fan no. 2A com. error | Read | |||
| BI | 1237 | Alarm 50:2 Supply air fan no. 2A motor controller over current | Read | |||
| BI | 1238 | Alarm 50:3 Supply air fan no. 2A motor controller under voltage | Read | |||
| BI | 1239 | Alarm 50:4 Supply air fan no. 2A motor controller over voltage | Read | |||
| BI | 1240 | Alarm 50:5 Supply air fan no. 2A motor controller over temperature | Read | |||
| BI | 1241 | Alarm 50:6 Supply air fan no. 2A motor controller start error | Read | |||
| BI | 1242 | Alarm 50:7 Supply air fan no. 2A motor controller ripple error | Read | |||
| BI | 1243 | Alarm 50:8 Supply air fan no. 2A motor controller phase error | Read | |||
| BI | 1244 | Alarm 50:9 Supply air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1245 | Alarm 50:10 Supply air fan no. 2A motor controller current reduction | Read | |||
| BI | 1246 | Alarm 50:11 Supply air fan no. 2A motor controller internal com. error | Read | |||
| BI | 1251 | Alarm 51:1 Supply air fan no. 3A com. error | Read | |||
| BI | 1252 | Alarm 51:2 Supply air fan no. 3A motor controller over current | Read | |||
| BI | 1253 | Alarm 51:3 Supply air fan no. 3A motor controller under voltage | Read | |||
| BI | 1254 | Alarm 51:4 Supply air fan no. 3A motor controller over voltage | Read | |||
| BI | 1255 | Alarm 51:5 Supply air fan no. 3A motor controller over temperature | Read | |||
| BI | 1256 | Alarm 51:6 Supply air fan no. 3A motor controller start error | Read | |||
| BI | 1257 | Alarm 51:7 Supply air fan no. 3A motor controller ripple error | Read | |||
| BI | 1258 | Alarm 51:8 Supply air fan no. 3A motor controller phase error | Read | |||
| BI | 1259 | Alarm 51:9 Supply air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1260 | Alarm 51:10 Supply air fan no. 3A motor controller current reduction | Read | |||
| BI | 1261 | Alarm 51:11 Supply air fan no. 3A motor controller internal com. error | Read | |||
| BI | 1266 | Alarm 52:1 Supply air fan no. 1B com. error | Read | |||
| BI | 1267 | Alarm 52:2 Supply air fan no. 1B motor controller over current | Read | |||
| BI | 1268 | Alarm 52:3 Supply air fan no. 1B motor controller under voltage | Read | |||
| BI | 1269 | Alarm 52:4 Supply air fan no. 1B motor controller over voltage | Read | |||
| BI | 1270 | Alarm 52:5 Supply air fan no. 1B motor controller over temperature | Read | |||
| BI | 1271 | Alarm 52:6 Supply air fan no. 1B motor controller start error | Read | |||
| BI | 1272 | Alarm 52:7 Supply air fan no. 1B motor controller ripple error | Read | |||
| BI | 1273 | Alarm 52:8 Supply air fan no. 1B motor controller phase error | Read | |||
| BI | 1274 | Alarm 52:9 Supply air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1275 | Alarm 52:10 Supply air fan no. 1B motor controller current reduction | Read | |||
| BI | 1281 | Alarm 53:1 Supply air fan no. 2B com. error | Read | |||
| BI | 1282 | Alarm 53:2 Supply air fan no. 2B motor controller over current | Read | |||
| BI | 1283 | Alarm 53:3 Supply air fan no. 2B motor controller under voltage | Read | |||
| BI | 1284 | Alarm 53:4 Supply air fan no. 2B motor controller over voltage | Read | |||
| BI | 1285 | Alarm 53:5 Supply air fan no. 2B motor controller over temperature | Read | |||
| BI | 1286 | Alarm 53:6 Supply air fan no. 2B motor controller start error | Read | |||
| BI | 1287 | Alarm 53:7 Supply air fan no. 2B motor controller ripple error | Read | |||
| BI | 1288 | Alarm 53:8 Supply air fan no. 2B motor controller phase error | Read | |||
| BI | 1289 | Alarm 53:9 Supply air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1290 | Alarm 53:10 Supply air fan no. 2B motor controller current reduction | Read | |||
| BI | 1296 | Alarm 54:1 Supply air fan no. 3B com. error | Read | |||
| BI | 1297 | Alarm 54:2 Supply air fan no. 3B motor controller over current | Read | |||
| BI | 1298 | Alarm 54:3 Supply air fan no. 3B motor controller under voltage | Read | |||
| BI | 1299 | Alarm 54:4 Supply air fan no. 3B motor controller over voltage | Read | |||
| BI | 1300 | Alarm 54:5 Supply air fan no. 3B motor controller over temperature | Read | |||
| BI | 1301 | Alarm 54:6 Supply air fan no. 3B motor controller start error | Read | |||
| BI | 1302 | Alarm 54:7 Supply air fan no. 3B motor controller ripple error | Read | |||
| BI | 1303 | Alarm 54:8 Supply air fan no. 3B motor controller phase error | Read | |||
| BI | 1304 | Alarm 54:9 Supply air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1305 | Alarm 54:10 Supply air fan no. 3B motor controller current reduction | Read | |||
| BI | 1311 | Alarm 55:1 Extract air fan no. 1A com. error | Read | |||
| BI | 1312 | Alarm 55:2 Extract air fan no. 1A motor controller over current | Read | |||
| BI | 1313 | Alarm 55:3 Extract air fan no. 1A motor controller under voltage | Read | |||
| BI | 1314 | Alarm 55:4 Extract air fan no. 1A motor controller over voltage | Read | |||
| BI | 1315 | Alarm 55:5 Extract air fan no. 1A motor controller over temperature | Read | |||
| BI | 1316 | Alarm 55:6 Extract air fan no. 1A motor controller start error | Read | |||
| BI | 1317 | Alarm 55:7 Extract air fan no. 1A motor controller ripple error | Read | |||
| BI | 1318 | Alarm 55:8 Extract air fan no. 1A motor controller phase error | Read | |||
| BI | 1319 | Alarm 55:9 Extract air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1320 | Alarm 55:10 Extract air fan no. 1A motor controller current reduction | Read | |||
| BI | 1321 | Alarm 55:11 Extract air fan no. 1A motor controller internal com. error | Read | |||
| BI | 1326 | Alarm 56:1 Extract air fan no. 2A com. error | Read | |||
| BI | 1327 | Alarm 56:2 Extract air fan no. 2A motor controller over current | Read | |||
| BI | 1328 | Alarm 56:3 Extract air fan no. 2A motor controller under voltage | Read | |||
| BI | 1329 | Alarm 56:4 Extract air fan no. 2A motor controller over voltage | Read | |||
| BI | 1330 | Alarm 56:5 Extract air fan no. 2A motor controller over temperature | Read | |||
| BI | 1331 | Alarm 56:6 Extract air fan no. 2A motor controller start error | Read | |||
| BI | 1332 | Alarm 56:7 Extract air fan no. 2A motor controller ripple error | Read | |||
| BI | 1333 | Alarm 56:8 Extract air fan no. 2A motor controller phase error | Read | |||
| BI | 1334 | Alarm 56:9 Extract air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1335 | Alarm 56:10 Extract air fan no. 2A motor controller current reduction | Read | |||
| BI | 1336 | Alarm 56:11 Extract air fan no. 2A motor controller internal com. error | Read | |||
| BI | 1341 | Alarm 57:1 Extract air fan no. 3A com. error | Read | |||
| BI | 1342 | Alarm 57:2 Extract air fan no. 3A motor controller over current | Read | |||
| BI | 1343 | Alarm 57:3 Extract air fan no. 3A motor controller under voltage | Read | |||
| BI | 1344 | Alarm 57:4 Extract air fan no. 3A motor controller over voltage | Read | |||
| BI | 1345 | Alarm 57:5 Extract air fan no. 3A motor controller over temperature | Read | |||
| BI | 1346 | Alarm 57:6 Extract air fan no. 3A motor controller start error | Read | |||
| BI | 1347 | Alarm 57:7 Extract air fan no. 3A motor controller ripple error | Read | |||
| BI | 1348 | Alarm 57:8 Extract air fan no. 3A motor controller phase error | Read | |||
| BI | 1349 | Alarm 57:9 Extract air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1350 | Alarm 57:10 Extract air fan no. 3A motor controller current reduction | Read | |||
| BI | 1351 | Alarm 57:11 Extract air fan no. 3A motor controller internal com. error | Read | |||
| BI | 1356 | Alarm 58:1 Extract air fan no. 1B com. error | Read | |||
| BI | 1357 | Alarm 58:2 Extract air fan no. 1B motor controller over current | Read | |||
| BI | 1358 | Alarm 58:3 Extract air fan no. 1B motor controller under voltage | Read | |||
| BI | 1359 | Alarm 58:4 Extract air fan no. 1B motor controller over voltage | Read | |||
| BI | 1360 | Alarm 58:5 Extract air fan no. 1B motor controller over temperature | Read | |||
| BI | 1361 | Alarm 58:6 Extract air fan no. 1B motor controller start error | Read | |||
| BI | 1362 | Alarm 58:7 Extract air fan no. 1B motor controller ripple error | Read | |||
| BI | 1363 | Alarm 58:8 Extract air fan no. 1B motor controller phase error | Read | |||
| BI | 1364 | Alarm 58:9 Extract air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1365 | Alarm 58:10 Extract air fan no. 1B motor controller current reduction | Read | |||
| BI | 1371 | Alarm 59:1 Extract air fan no. 2B com. error | Read | |||
| BI | 1372 | Alarm 59:2 Extract air fan no. 2B motor controller over current | Read | |||
| BI | 1373 | Alarm 59:3 Extract air fan no. 2B motor controller under voltage | Read | |||
| BI | 1374 | Alarm 59:4 Extract air fan no. 2B motor controller over voltage | Read | |||
| BI | 1375 | Alarm 59:5 Extract air fan no. 2B motor controller over temperature | Read | |||
| BI | 1376 | Alarm 59:6 Extract air fan no. 2B motor controller start error | Read | |||
| BI | 1377 | Alarm 59:7 Extract air fan no. 2B motor controller ripple error | Read | |||
| BI | 1378 | Alarm 59:8 Extract air fan no. 2B motor controller phase error | Read | |||
| BI | 1379 | Alarm 59:9 Extract air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1380 | Alarm 59:10 Extract air fan no. 2B motor controller current reduction | Read | |||
| BI | 1386 | Alarm 60:1 Extract air fan no. 3B com. error | Read | |||
| BI | 1387 | Alarm 60:2 Extract air fan no. 3B motor controller over current | Read | |||
| BI | 1388 | Alarm 60:3 Extract air fan no. 3B motor controller under voltage | Read | |||
| BI | 1389 | Alarm 60:4 Extract air fan no. 3B motor controller over voltage | Read | |||
| BI | 1390 | Alarm 60:5 Extract air fan no. 3B motor controller over temperature | Read | |||
| BI | 1391 | Alarm 60:6 Extract air fan no. 3B motor controller start error | Read | |||
| BI | 1392 | Alarm 60:7 Extract air fan no. 3B motor controller ripple error | Read | |||
| BI | 1393 | Alarm 60:8 Extract air fan no. 3B motor controller phase error | Read | |||
| BI | 1394 | Alarm 60:9 Extract air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1395 | Alarm 60:10 Extract air fan no. 3B motor controller current reduction | Read | |||
| BI | 1401 | Alarm 61:1 Supply air fan no. 1A I/O-module com. error | Read | |||
| BI | 1406 | Alarm 61:6 Supply air fan no. 2A I/O-module com. error | Read | |||
| BI | 1411 | Alarm 61:11 Supply air fan no. 3A I/O-module com. error | Read | |||
| BI | 1416 | Alarm 62:1 Extract air fan no. 1A I/O-module com. error | Read | |||
| BI | 1421 | Alarm 62:6 Extract air fan no. 2A I/O-module com. error | Read | |||
| BI | 1426 | Alarm 62:11 Extract air fan no. 3A I/O-module com. error | Read | |||
| BI | 1431 | Alarm 63:1 MIRU 1 I/O-module com. error | Read | |||
| BI | 1436 | Alarm 63:6 MIRU 2 I/O-module com. error | Read | |||
| BI | 1441 | Alarm 63:11 MIRU 3 I/O-module com. error | Read | |||
| BI | 1446 | Alarm 64:1 Supply air fan no. 1A common A-alarm | Read | |||
| BI | 1448 | Alarm 64:3 Supply air fan no. 1A common B-alarm | Read | |||
| BI | 1450 | Alarm 64:5 Supply air fan no. 1A common warning | Read | |||
| BI | 1451 | Alarm 64:6 Supply air fan no. 2A common A-alarm | Read | |||
| BI | 1453 | Alarm 64:8 Supply air fan no. 2A common B-alarm | Read | |||
| BI | 1455 | Alarm 64:10 Supply air fan no. 2A common warning | Read | |||
| BI | 1456 | Alarm 64:11 Supply air fan no. 3A common A-alarm | Read | |||
| BI | 1458 | Alarm 64:13 Supply air fan no. 3A common B-alarm | Read | |||
| BI | 1460 | Alarm 64:15 Supply air fan no. 3A common warning | Read | |||
| BI | 1461 | Alarm 65:1 Extract air fan no. 1A common A-alarm | Read | |||
| BI | 1463 | Alarm 65:3 Extract air fan no. 1A common B-alarm | Read | |||
| BI | 1465 | Alarm 65:5 Extract air fan no. 1A common warning | Read | |||
| BI | 1466 | Alarm 65:6 Extract air fan no. 2A common A-alarm | Read | |||
| BI | 1468 | Alarm 65:8 Extract air fan no. 2A common B-alarm | Read | |||
| BI | 1470 | Alarm 65:10 Extract air fan no. 2A common warning | Read | |||
| BI | 1471 | Alarm 65:11 Extract air fan no. 3A common A-alarm | Read | |||
| BI | 1473 | Alarm 65:13 Extract air fan no. 3A common B-alarm | Read | |||
| BI | 1475 | Alarm 65:15 Extract air fan no. 3A common warning | Read | |||
| BI | 1536 | Alarm 70:1 H/C controls com. error | Read | |||
| BI | 1537 | Alarm 70:2 H/C controls internal memory error | Read | |||
| BI | 1538 | Alarm 70:3 H/C controls clock circuit defective | Read | |||
| BI | 1540 | Alarm 70:5 H/C defrost pressure sensor no. D com. error | Read | |||
| BI | 1541 | Alarm 70:6 H/C defrost I/O-module no. 5 com. error | Read | |||
| BI | 1542 | Alarm 70:7 H/C defrost recirculation damper monitoring tripped | Read | |||
| BI | 1543 | Alarm 70:8 H/C defrost electrical heater overheat protection tripped | Read | |||
| BI | 1544 | Alarm 70:9 H/C defrost time above alarm limit | Read | |||
| BI | 1546 | Alarm 70:11 H/C defrost interval above alarm limit | Read | |||
| BI | 1547 | Alarm 70:12 H/C wrong phase sequence | Read | |||
| BI | 1551 | Alarm 71:1 H/C compressor motor control com. error | Read | |||
| BI | 1552 | Alarm 71:2 H/C compressor motor control start error | Read | |||
| BI | 1553 | Alarm 71:3 H/C compressor motor controller over or under voltage | Read | |||
| BI | 1554 | Alarm 71:4 H/C compressor out of operation range | Read | |||
| BI | 1559 | Alarm 71:9 H/C expansion valve controller com. error | Read | |||
| BI | 1566 | Alarm 72:1 H/C high pressure switch tripped | Read | |||
| BI | 1567 | Alarm 72:2 H/C high pressure above alarm limit | Read | |||
| BI | 1568 | Alarm 72:3 H/C thermal switch compressor no. 1 tripped | Read | |||
| BI | 1569 | Alarm 72:4 H/C discharge temperature above alarm limit | Read | |||
| BI | 1570 | Alarm 72:5 H/C discharge temperature sensor defective | Read | |||
| BI | 1571 | Alarm 72:6 H/C high pressure sensor defective | Read | |||
| BI | 1572 | Alarm 72:7 H/C low pressure sensor defective | Read | |||
| BI | 1573 | Alarm 72:8 H/C suction temperature sensor defective | Read | |||
| BI | 1574 | Alarm 72:9 H/C pressure difference below alarm limit | Read | |||
| BI | 1575 | Alarm 72:10 H/C maintenance and compressor | Read | |||
| BI | 1576 | Alarm 72:11 H/C superheat temperature below alarm limit | Read | |||
| BI | 1577 | Alarm 72:12 H/C unloading of low pressure | Read | |||
| BI | 1578 | Alarm 72:13 H/C unloading of high pressure | Read | |||
| BI | 1579 | Alarm 72:14 H/C low pressure below alarm limit | Read | |||
| BI | 1580 | Alarm 72:15 H/C thermal switch compressor no. 2 tripped | Read | |||
| BI | 1642 | Alarm 77:2 MIRU 1 motor controller over current | Read | |||
| BI | 1643 | Alarm 77:3 MIRU 1 motor controller under voltage | Read | |||
| BI | 1644 | Alarm 77:4 MIRU 1 motor controller over voltage | Read | |||
| BI | 1645 | Alarm 77:5 MIRU 1 motor controller over temperature | Read | |||
| BI | 1646 | Alarm 77:6 MIRU 1 motor controller start error | Read | |||
| BI | 1647 | Alarm 77:7 MIRU 1 motor controller ripple error | Read | |||
| BI | 1648 | Alarm 77:8 MIRU 1 motor controller phase error | Read | |||
| BI | 1649 | Alarm 77:9 MIRU 1 motor controller internal memory error | Read | |||
| BI | 1650 | Alarm 77:10 MIRU 1 motor controller current reduction | Read | |||
| BI | 1651 | Alarm 77:11 MIRU 1 motor controller internal com. error | Read | |||
| BI | 1657 | Alarm 78:2 MIRU 2 motor controller over current | Read | |||
| BI | 1658 | Alarm 78:3 MIRU 2 motor controller under voltage | Read | |||
| BI | 1659 | Alarm 78:4 MIRU 2 motor controller over voltage | Read | |||
| BI | 1660 | Alarm 78:5 MIRU 2 motor controller over temperature | Read | |||
| BI | 1661 | Alarm 78:6 MIRU 2 motor controller start error | Read | |||
| BI | 1662 | Alarm 78:7 MIRU 2 motor controller ripple error | Read | |||
| BI | 1663 | Alarm 78:8 MIRU 2 motor controller phase error | Read | |||
| BI | 1664 | Alarm 78:9 MIRU 2 motor controller internal memory error | Read | |||
| BI | 1665 | Alarm 78:10 MIRU 2 motor controller current reduction | Read | |||
| BI | 1666 | Alarm 78:11 MIRU 2 motor controller internal com. error | Read | |||
| BI | 1672 | Alarm 79:2 MIRU 3 motor controller over current | Read | |||
| BI | 1673 | Alarm 79:3 MIRU 3 motor controller under voltage | Read | |||
| BI | 1674 | Alarm 79:4 MIRU 3 motor controller over voltage | Read | |||
| BI | 1675 | Alarm 79:5 MIRU 3 motor controller over temperature | Read | |||
| BI | 1676 | Alarm 79:6 MIRU 3 motor controller start error | Read | |||
| BI | 1677 | Alarm 79:7 MIRU 3 motor controller ripple error | Read | |||
| BI | 1678 | Alarm 79:8 MIRU 3 motor controller phase error | Read | |||
| BI | 1679 | Alarm 79:9 MIRU 3 motor controller internal memory error | Read | |||
| BI | 1680 | Alarm 79:10 MIRU 3 motor controller current reduction | Read | |||
| BI | 1681 | Alarm 79:11 MIRU 3 motor controller internal com. error | Read | |||
| BI | 1702 | Alarm 81:2 SMART Link no. 1 supply air flow below defrost alarm limit | Read | |||
| BI | 1703 | Alarm 81:3 SMART Link no. 1 High pressure switch tripped | Read | |||
| BI | 1704 | Alarm 81:4 SMART Link no. 1 High pressure above alarm limit | Read | |||
| BI | 1705 | Alarm 81:5 SMART Link no. 1 Low pressure below alarm limit | Read | |||
| BI | 1706 | Alarm 81:6 SMART Link no. 1 Evaporation temperature below alarm limit | Read | |||
| BI | 1707 | Alarm 81:7 SMART Link no. 1 Inverter group alarm (Power+) | Read | |||
| BI | 1708 | Alarm 81:8 SMART Link no. 1 Envelope alarm. | Read | |||
| BI | 1709 | Alarm 81:9 SMART Link no. 1 Starting up of faulty compressor | Read | |||
| BI | 1710 | Alarm 81:10 SMART Link no. 1 Discharge temperature above alarm limit | Read | |||
| BI | 1711 | Alarm 81:11 SMART Link no. 1 Pressure difference below alarm limit | Read | |||
| BI | 1717 | Alarm 82:2 SMART Link no. 2 supply air flow below defrost alarm limit | Read | |||
| BI | 1718 | Alarm 82:3 SMART Link no. 2 High pressure switch tripped | Read | |||
| BI | 1719 | Alarm 82:4 SMART Link no. 2 High pressure above alarm limit | Read | |||
| BI | 1720 | Alarm 82:5 SMART Link no. 2 Low pressure below alarm limit | Read | |||
| BI | 1721 | Alarm 82:6 SMART Link no. 2 Evaporation temperature below alarm limit | Read | |||
| BI | 1722 | Alarm 82:7 SMART Link no. 2 Inverter group alarm (Power+) | Read | |||
| BI | 1723 | Alarm 82:8 SMART Link no. 2 Envelope alarm. | Read | |||
| BI | 1724 | Alarm 82:9 SMART Link no. 2 Starting up of faulty compressor | Read | |||
| BI | 1725 | Alarm 82:10 SMART Link no. 2 Discharge temperature above alarm limit | Read | |||
| BI | 1726 | Alarm 82:11 SMART Link no. 2 Pressure difference below alarm limit | Read | |||
| BI | 1732 | Alarm 83:2 SMART Link no. 3 supply air flow below defrost alarm limit | Read | |||
| BI | 1733 | Alarm 83:3 SMART Link no. 3 High pressure switch tripped | Read | |||
| BI | 1734 | Alarm 83:4 SMART Link no. 3 High pressure above alarm limit | Read | |||
| BI | 1735 | Alarm 83:5 SMART Link no. 3 Low pressure below alarm limit | Read | |||
| BI | 1736 | Alarm 83:6 SMART Link no. 3 Evaporation temperature below alarm limit | Read | |||
| BI | 1737 | Alarm 83:7 SMART Link no. 3 Inverter group alarm (Power+) | Read | |||
| BI | 1738 | Alarm 83:8 SMART Link no. 3 Envelope alarm. | Read | |||
| BI | 1739 | Alarm 83:9 SMART Link no. 3 Starting up of faulty compressor | Read | |||
| BI | 1740 | Alarm 83:10 SMART Link no. 3 Discharge temperature above alarm limit | Read | |||
| BI | 1741 | Alarm 83:11 SMART Link no. 3 Pressure difference below alarm limit | Read | |||
| BI | 1747 | Alarm 84:2 SMART Link no. 4 supply air flow below defrost alarm limit | Read | |||
| BI | 1748 | Alarm 84:3 SMART Link no. 4 High pressure switch tripped | Read | |||
| BI | 1749 | Alarm 84:4 SMART Link no. 4 High pressure above alarm limit | Read | |||
| BI | 1750 | Alarm 84:5 SMART Link no. 4 Low pressure below alarm limit | Read | |||
| BI | 1751 | Alarm 84:6 SMART Link no. 4 Evaporation temperature below alarm limit | Read | |||
| BI | 1752 | Alarm 84:7 SMART Link no. 4 Inverter group alarm (Power+) | Read | |||
| BI | 1753 | Alarm 84:8 SMART Link no. 4 Envelope alarm. | Read | |||
| BI | 1754 | Alarm 84:9 SMART Link no. 4 Starting up of faulty compressor | Read | |||
| BI | 1755 | Alarm 84:10 SMART Link no. 4 Discharge temperature above alarm limit | Read | |||
| BI | 1756 | Alarm 84:11 SMART Link no. 4 Pressure difference below alarm limit | Read | |||
| BI | 1911 | Info 95:1 Supply air pre filter calibration performed at low air flow | Read | |||
| BI | 1912 | Info 95:2 Extract air pre filter calibration performed at low air flow | Read | |||
| BI | 1913 | Info 95:3 Supply air AHU filter calibration performed at low air flow | Read | |||
| BI | 1914 | Info 95:4 Extract air AHU filter calibration performed at low air flow | Read | |||
| BI | 1915 | Info 95:5 End filter calibration performed at low air flow | Read | |||
| BI | 1924 | Info 95:14 Reduced humidity recovery time above alarm limit | Read | |||
| BI | 1925 | Info 95:15 Supply air humidity level above outdoor air level | Read | |||
| BI | 1926 | Info 96:1 H/C defrost calibration not performed | Read | |||
| BI | 1927 | Info 96:2 H/C defrost calibration not approved | Read | |||
| BI | 1928 | Info 96:3 H/C minimum SA flow limit below factory setting | Read | |||
| BI | 1929 | Info 96:4 H/C minimum EA flow limit below factory setting | Read | |||
| BI | 1930 | Info 96:5 H/C OA temp limit for heating below factory setting | Read | |||
| BI | 1941 | Info 97:1 Cloud connection offline | Read | |||
| BI | 1942 | Info 97:2 Cloud certificate missing/expired | Read | |||
| BI | 1952 | Info 97:12 Plate heat exchanger bypass optimization not performed | Read | |||
| BI | 1953 | Info 97:13 Plate heat exchanger bypass optimization not approved | Read | |||
| BI | 1954 | Info 97:14 Plate heat exchanger defrost calibration not performed | Read | |||
| BI | 1955 | Info 97:15 Plate heat exchanger defrost calibration not approved | Read | |||
| BI | 1956 | Info 98:1 Supply air pre-filter calibration not performed | Read | |||
| BI | 1957 | Info 98:2 Supply air pre-filter calibration not approved | Read | |||
| BI | 1958 | Info 98:3 Extract air pre-filter calibration not performed | Read | |||
| BI | 1959 | Info 98:4 Extract air pre-filter calibration not approved | Read | |||
| BI | 1960 | Info 98:5 Supply air air handling unit filter calibration not performed | Read | |||
| BI | 1961 | Info 98:6 Supply air air handling unit filter calibration not approved | Read | |||
| BI | 1962 | Info 98:7 Extract air air handling unit filter calibration not performed | Read | |||
| BI | 1963 | Info 98:8 Extract air air handling unit filter calibration not approved | Read | |||
| BI | 1964 | Info 98:9 Supply air end filter calibration not performed | Read | |||
| BI | 1965 | Info 98:10 Supply air end filter calibration not approved | Read | |||
| BI | 1966 | Info 98:11 Rotary heat exchanger defrost calibration not performed | Read | |||
| BI | 1967 | Info 98:12 Rotary heat exchanger defrost calibration not approved | Read | |||
| BI | 1968 | Info 98:13 ReCO2 calibration not performed | Read | |||
| BI | 1969 | Info 98:14 ReCO2 calibration not approved | Read | |||
| BI | 1970 | Info 98:15 ReCO2 incorrect setting | Read | |||
| BI | 1971 | Info 99:1 E-mail error | Read | |||
| BI | 1975 | Info 99:5 FTP error | Read | |||
| BI | 1976 | Info 99:6 Schedule invalid data auto corrected | Read | |||
| BI | 1977 | Info 99:7 SD card memory soon full. Oldest log data will soon be deleted | Read | |||
| BI | 1978 | Info 99:8 SD card memory full. Oldest log data deleted | Read | |||
| BI | 1979 | Info 99:9 IQlogic CPU2 reboot caused by corrupt SD card remove and replace | Read | |||
| BI | 1981 | Info 99:11 No external outdoor air temp. sensor connected for heat retention | Read | |||
| BI | 1982 | Info 99:12 No extract air/room temperature sensor connected | Read | |||
| BI | 1984 | Info 99:14 Internal serial memory error CPU 1 | Read | |||
| BI | 1985 | Info 99:15 Clock circuit defective | Read | |||
| BI | 2001 | Active alarm group 1 | Read | |||
| BI | 2002 | Active alarm group 2 | Read | |||
| BI | 2003 | Active alarm group 3 | Read | |||
| BI | 2004 | Active alarm group 4 | Read | |||
| BI | 2005 | Active alarm group 5 | Read | |||
| BI | 2006 | Active alarm group 6 | Read | |||
| BI | 2007 | Active alarm group 7 | Read | |||
| BI | 2008 | Active alarm group 8 | Read | |||
| BI | 2009 | Active alarm group 9 | Read | |||
| BI | 2010 | Active alarm group 10 | Read | |||
| BI | 2011 | Active alarm group 11 | Read | |||
| BI | 2012 | Active alarm group 12 | Read | |||
| BI | 2013 | Active alarm group 13 | Read | |||
| BI | 2014 | Active alarm group 14 | Read | |||
| BI | 2015 | Active alarm group 15 | Read | |||
| BI | 2016 | Active alarm group 16 | Read | |||
| BI | 2017 | Active alarm group 17 | Read | |||
| BI | 2018 | Active alarm group 18 | Read | |||
| BI | 2019 | Active alarm group 19 | Read | |||
| BI | 2020 | Active alarm group 20 | Read | |||
| BI | 2021 | Active alarm group 21 | Read | |||
| BI | 2022 | Active alarm group 22 | Read | |||
| BI | 2023 | Active alarm group 23 | Read | |||
| BI | 2024 | Active alarm group 24 | Read | |||
| BI | 2025 | Active alarm group 25 | Read | |||
| BI | 2026 | Active alarm group 26 | Read | |||
| BI | 2027 | Active alarm group 27 | Read | |||
| BI | 2028 | Active alarm group 28 | Read | |||
| BI | 2029 | Active alarm group 29 | Read | |||
| BI | 2030 | Active alarm group 30 | Read | |||
| BI | 2031 | Active alarm group 31 | Read | |||
| BI | 2032 | Active alarm group 32 | Read | |||
| BI | 2033 | Active alarm group 33 | Read | |||
| BI | 2034 | Active alarm group 34 | Read | |||
| BI | 2035 | Active alarm group 35 | Read | |||
| BI | 2036 | Active alarm group 36 | Read | |||
| BI | 2037 | Active alarm group 37 | Read | |||
| BI | 2038 | Active alarm group 38 | Read | |||
| BI | 2039 | Active alarm group 39 | Read | |||
| BI | 2040 | Active alarm group 40 | Read | |||
| BI | 2041 | Active alarm group 41 | Read | |||
| BI | 2042 | Active alarm group 42 | Read | |||
| BI | 2043 | Active alarm group 43 | Read | |||
| BI | 2044 | Active alarm group 44 | Read | |||
| BI | 2045 | Active alarm group 45 | Read | |||
| BI | 2046 | Active alarm group 46 | Read | |||
| BI | 2047 | Active alarm group 47 | Read | |||
| BI | 2048 | Active alarm group 48 | Read | |||
| BI | 2049 | Active alarm group 49 | Read | |||
| BI | 2050 | Active alarm group 50 | Read | |||
| BI | 2051 | Active alarm group 51 | Read | |||
| BI | 2052 | Active alarm group 52 | Read | |||
| BI | 2053 | Active alarm group 53 | Read | |||
| BI | 2054 | Active alarm group 54 | Read | |||
| BI | 2055 | Active alarm group 55 | Read | |||
| BI | 2056 | Active alarm group 56 | Read | |||
| BI | 2057 | Active alarm group 57 | Read | |||
| BI | 2058 | Active alarm group 58 | Read | |||
| BI | 2059 | Active alarm group 59 | Read | |||
| BI | 2060 | Active alarm group 60 | Read | |||
| BI | 2061 | Active alarm group 61 | Read | |||
| BI | 2062 | Active alarm group 62 | Read | |||
| BI | 2063 | Active alarm group 63 | Read | |||
| BI | 2064 | Active alarm group 64 | Read | |||
| BI | 2065 | Active alarm group 65 | Read | |||
| BI | 2066 | Active alarm group 66 | Read | |||
| BI | 2067 | Active alarm group 67 | Read | |||
| BI | 2068 | Active alarm group 68 | Read | |||
| BI | 2069 | Active alarm group 69 | Read | |||
| BI | 2070 | Active alarm group 70 | Read | |||
| BI | 2071 | Active alarm group 71 | Read | |||
| BI | 2072 | Active alarm group 72 | Read | |||
| BI | 2073 | Active alarm group 73 | Read | |||
| BI | 2074 | Active alarm group 74 | Read | |||
| BI | 2075 | Active alarm group 75 | Read | |||
| BI | 2076 | Active alarm group 76 | Read | |||
| BI | 2077 | Active alarm group 77 | Read | |||
| BI | 2078 | Active alarm group 78 | Read | |||
| BI | 2079 | Active alarm group 79 | Read | |||
| BI | 2080 | Active alarm group 80 | Read | |||
| BI | 2081 | Active alarm group 81 | Read | |||
| BI | 2082 | Active alarm group 82 | Read | |||
| BI | 2083 | Active alarm group 83 | Read | |||
| BI | 2084 | Active alarm group 84 | Read | |||
| BI | 2085 | Active alarm group 85 | Read | |||
| BI | 2086 | Active alarm group 86 | Read | |||
| BI | 2087 | Active alarm group 87 | Read | |||
| BI | 2088 | Active alarm group 88 | Read | |||
| BI | 2089 | Active alarm group 89 | Read | |||
| BI | 2090 | Active alarm group 90 | Read | |||
| BI | 2091 | Active alarm group 91 | Read | |||
| BI | 2092 | Active alarm group 92 | Read | |||
| BI | 2093 | Active alarm group 93 | Read | |||
| BI | 2094 | Active alarm group 94 | Read | |||
| BI | 2095 | Active alarm group 95 | Read | |||
| BI | 2096 | Active alarm group 96 | Read | |||
| BI | 2097 | Active alarm group 97 | Read | |||
| BI | 2098 | Active alarm group 98 | Read | |||
| BI | 2099 | Active alarm group 99 | Read | |||
| BI | 2100 | Active alarm group 100 | Read | |||
| BO | 1 | Booster diffusers | Write | |||
| BVmin | 1 | Alarm reset | Write | |||
| BV | 3 | Internal fire alarm function | Write | |||
| BV | 29 | SA flow pressure sensor auto zero calibration | Write | |||
| BV | 30 | EA flow pressure sensor auto zero calibration | Write | |||
| BV | 31 | SA duct pressure sensor auto zero calibration | Write | |||
| BV | 32 | EA duct pressure sensor auto zero calibration | Write | |||
| BV | 33 | ReCO2 pressure sensor auto zero calibration | Write | |||
| BV | 34 | RHX defrost pressure sensor auto calibration | Write | |||
| BV | 35 | Carry over control pressure sensor auto calibration | Write | |||
| BV | 36 | SA filter pressure sensor auto zero calibration | Write | |||
| BV | 37 | EA filter pressure sensor auto zero calibration | Write | |||
| BV | 38 | SA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 39 | EA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 40 | SA end-filter pressure sensor auto zero calibration | Write | |||
| BV | 41 | PX heat exchange pressure sensor auto calibration | Write | |||
| BV | 42 | Air quality control pressure sensor auto calibration | Write | |||
| BV | 43 | HC defrost sensor auto calibration | Write | |||
| BV | 46 | SA flow pressure sensor activate zero calibration | Write | |||
| BV | 47 | EA flow pressure sensor activate zero calibration | Write | |||
| BV | 48 | SA duct pressure sensor activate zero calibration | Write | |||
| BV | 49 | EA duct pressure sensor activate zero calibration | Write | |||
| BV | 50 | ReCO2 pressure sensor activate calibration | Write | |||
| BV | 51 | RHX Defrost pressure sensor activate calibration | Write | |||
| BV | 52 | Carry over control pressure sensor activate zero calibration | Write | |||
| BV | 53 | SA filter pressure sensor activate zero calibration | Write | |||
| BV | 54 | EA filter pressure sensor activate zero calibration | Write | |||
| BV | 55 | SA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 56 | EA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 57 | SA end-filter pressure sensor activate zero calibration | Write | |||
| BV | 58 | PX heat exchange pressure sensor activate zero calibration | Write | |||
| BV | 59 | Air quality control pressure sensor activate zero calibration | Write | |||
| BV | 60 | HC defrost pressure sensor activate zero calibration | Write | |||
| BV | 162 | External room sensor 1 function | Write | |||
| BV | 163 | External room sensor 2 function | Write | |||
| BV | 164 | External room sensor 3 function | Write | |||
| BV | 165 | External room sensor 4 function | Write | |||
| BV | 167 | External room temp from BMS function | Write | |||
| BV | 172 | External OA sensor 1 function | Write | |||
| BV | 173 | External OA sensor 2 function | Write | |||
| BV | 174 | External OA sensor 3 function | Write | |||
| BV | 175 | External OA sensor 4 function | Write | |||
| BV | 177 | External OA temp from BMS function | Write | |||
| BV | 182 | RHX defrost function | Write | |||
| BV | 183 | RHX defrost calibration | Write | |||
| BV | 187 | RHX carry over control function | Write | |||
| BV | 190 | RHX min exhaust air temp function | Write | |||
| BV | 198 | PHX periodic operation of bypass damper function | Write | |||
| BV | 201 | PX bypass optimize | Write | |||
| BV | 205 | CHX periodic operation of pump function | Write | |||
| BV | 206 | CHX periodic operation of valve function | Write | |||
| BV | 228 | Re-heat periodic operation of pump function | Write | |||
| BV | 229 | Re-heat periodic operation of valve function | Write | |||
| BV | 245 | Extra regulation 1 periodic operation of pump function | Write | |||
| BV | 246 | Extra regulation 1 periodic operation of valve function | Write | |||
| BV | 274 | Cool relay 1 periodic operation of pump function | Write | |||
| BV | 275 | Cool relay 2 periodic operation of pump function | Write | |||
| BV | 276 | Cool periodic operation of valve function | Write | |||
| BV | 296 | Intermittent night heat function | Write | |||
| BV | 302 | Intermittent night heat recirculation function | Write | |||
| BV | 305 | Morning boost function | Write | |||
| BV | 320 | Heating boost function | Write | |||
| BV | 325 | Xzone heat function | Write | |||
| BV | 327 | Xzone cool function | Write | |||
| BV | 374 | Xzone external room sensor 1 function | Write | |||
| BV | 375 | Xzone external room sensor 2 function | Write | |||
| BV | 376 | Xzone external room sensor 3 function | Write | |||
| BV | 377 | Xzone external room sensor 4 function | Write | |||
| BV | 379 | Xzone external room temp from BMS function | Write | |||
| BV | 386 | Xzone reheat periodic operation of pump function | Write | |||
| BV | 387 | Xzone reheat periodic operation of valve function | Write | |||
| BV | 400 | Xzone Cool relay 1 periodic operation of pump function | Write | |||
| BV | 401 | Xzone Cool relay 2 periodic operation of pump function | Write | |||
| BV | 402 | Xzone Cool periodic operation of valve function | Write | |||
| BV | 410 | Pre-heat function | Write | |||
| BV | 414 | Pre-heat periodic operation of pump function | Write | |||
| BV | 415 | Pre-heat periodic operation of valve function | Write | |||
| BV | 425 | ReCO2 Calibration | Write | |||
| BV | 459 | Heat exchange active in dehumidifying sequence | Write | |||
| BV | 477 | Exhaust heat periodic operation of pump function | Write | |||
| BV | 478 | Exhaust heat periodic operation of valve function | Write | |||
| BV | 489 | SMART Link WB Cooling Optimize function | Write | |||
| BV | 490 | SMART Link WB Heating Optimize function | Write | |||
| BV | 504 | AQUA Link Function | Write | |||
| BV | 530 | AYC Heated water periodic operation of pump | Write | |||
| BV | 531 | AYC Heated water periodic operation of valve | Write | |||
| BV | 536 | AYC Heated water OA temp compensation | Write | |||
| BV | 547 | AYC Heated water room temp compensation function | Write | |||
| BV | 548 | AYC Heated water room temp compensation at night | Write | |||
| BV | 553 | AYC Heated water night temp compensation function | Write | |||
| BV | 579 | AYC Chilled water periodic operation of pump | Write | |||
| BV | 580 | AYC Chilled water periodic operation of valve | Write | |||
| BV | 585 | AYC Chilled water OA temp compensation | Write | |||
| BV | 596 | AYC Chilled water room temp compensation function | Write | |||
| BV | 597 | AYC Chilled water room temp compensation at night | Write | |||
| BV | 602 | AYC Chilled water night temp compensation function | Write | |||
| BV | 618 | AYC Chilled water dew point compensation air flow boost | Write | |||
| BV | 637 | Optimize function | Write | |||
| BV | 775 | Night temp compensation function | Write | |||
| BV | 824 | Extra regulation 2 periodic operation of pump function | Write | |||
| BV | 825 | Extra regulation 2 periodic operation of valve function | Write | |||
| BV | 1000 | External operation I/O-module A, function | Write | |||
| BV | 1001 | External operation I/O-module A, temp sensor 1 function | Write | |||
| BV | 1002 | External operation I/O-module A, temp sensor 2 function | Write | |||
| BV | 1003 | External operation I/O-module A, digital output | Write | |||
| BV | 1004 | External operation I/O-module B, function | Write | |||
| BV | 1005 | External operation I/O-module B, temp sensor 1 function | Write | |||
| BV | 1006 | External operation I/O-module B, temp sensor 2 function | Write | |||
| BV | 1007 | External operation I/O-module B, digital output | Write | |||
| BV | 1008 | External operation I/O-module C, function | Write | |||
| BV | 1009 | External operation I/O-module C, temp sensor 1 function | Write | |||
| BV | 1010 | External operation I/O-module C, temp sensor 2 function | Write | |||
| BV | 1011 | External operation I/O-module C, digital output | Write | |||
| BV | 3000 | External override function, on/off | Write | |||
| BV | 3010 | External override value, Supply air fan, on/off | Write | |||
| BV | 3011 | External override value, Extract air fan, on/off | Write | |||
| BV | 3050 | External override value, Pre-heat relay, on/off | Write | |||
| BV | 3060 | External override value, Reheat relay, on/off | Write | |||
| BV | 3070 | External override value, Xzone heat relay, on/off | Write | |||
| BV | 3080 | External override value, Extra reg. 1 relay 1, on/off | Write | |||
| BV | 3081 | External override value, Extra reg. 1 relay 2, on/off | Write | |||
| BV | 3090 | External override value, Extra reg. 2 relay 1, on/off | Write | |||
| BV | 3091 | External override value, Extra reg. 2 relay 2, on/off | Write | |||
| BV | 3100 | External override value, Cool relay 1, on/off | Write | |||
| BV | 3101 | External override value, Cool relay 2, on/off | Write | |||
| BV | 3110 | External override value, Xzone cool relay 1, on/off | Write | |||
| BV | 3111 | External override value, Xzone cool relay 2, on/off | Write | |||
| BV | 3120 | External override value, COOL DX comp. 1 on/off | Write | |||
| BV | 3121 | External override value, COOL DX comp. 2 on/off | Write | |||
| BV | 3130 | External override value, HC, on/off | Write | |||
| BV | 3131 | External override value, HC cool/heat, on/off | Write | |||
| BV | 3132 | External override value, HC defrost, on/off | Write | |||
| BV | 3140 | External override value, SMART Link WB, on/off | Write | |||
| BV | 3141 | External override value, SMART Link WB, SMART Link WB cool/heat, on/off | Write | |||
| BV | 3150 | External override value, SMART Link DX 1, on/off | Write | |||
| BV | 3151 | External override value, SMART Link DX 1 cool/heat, on/off | Write | |||
| BV | 3152 | External override value, SMART Link DX 2, on/off | Write | |||
| BV | 3153 | External override value, SMART Link DX 2 cool/heat, on/off | Write | |||
| BV | 3154 | External override value, SMART Link DX 3, on/off | Write | |||
| BV | 3155 | External override value, SMART Link DX 3 cool/heat, on/off | Write | |||
| BV | 3156 | External override value, SMART Link DX 4, on/off | Write | |||
| BV | 3157 | External override value, SMART Link DX 4 cool/heat, on/off | Write | |||
| BV | 3160 | External override value, AQUA Link pump, on/off | Write | |||
| BV | 3170 | External override value, Humidifying relay, on/off | Write | |||
| BV | 3190 | External override value, AYC heat pump, on/off | Write | |||
| BV | 3191 | External override value, AYC cool pump, on/off | Write | |||
| BV | 3200 | External override value, AHU damper relay, on/off | Write | |||
| BV | 3201 | External override value, AHU operation relay, on/off | Write | |||
| BV | 3210 | External override value, Booster heat relay, on/off | Write | |||
| BV | 3211 | External override value, Booster cool relay, on/off | Write | |||
| BV | 3220 | External override value, Miru 1 fan, on/off | Write | |||
| BV | 3221 | External override value, Miru 2 fan, on/off | Write | |||
| BV | 3222 | External override value, Miru 3 fan, on/off | Write | |||
| BV | 3230 | External override value, Exhaust heat relay, on/off | Write | |||
| BV | 4010 | External override activate, Supply air fan, on/off | Write | |||
| BV | 4011 | External override activate, Extract air fan, on/off | Write | |||
| BV | 4050 | External override activate, Pre-heat relay, on/off | Write | |||
| BV | 4060 | External override activate, Reheat relay, on/off | Write | |||
| BV | 4070 | External override activate, Xzone heat relay, on/off | Write | |||
| BV | 4080 | External override activate, Extra reg. 1 relay 1, on/off | Write | |||
| BV | 4081 | External override activate, Extra reg. 1 relay 2, on/off | Write | |||
| BV | 4090 | External override activate, Extra reg. 2 relay 1, on/off | Write | |||
| BV | 4091 | External override activate, Extra reg. 2 relay 2, on/off | Write | |||
| BV | 4100 | External override activate, Cool relay 1, on/off | Write | |||
| BV | 4101 | External override activate, Cool relay 2, on/off | Write | |||
| BV | 4110 | External override activate, Xzone cool relay 1, on/off | Write | |||
| BV | 4111 | External override activate, Xzone cool relay 2, on/off | Write | |||
| BV | 4120 | External override activate, COOL DX comp. 1 on/off | Write | |||
| BV | 4121 | External override activate, COOL DX comp. 2 on/off | Write | |||
| BV | 4130 | External override activate, HC, on/off | Write | |||
| BV | 4131 | External override activate, HC cool/heat, on/off | Write | |||
| BV | 4132 | External override activate, HC defrost, on/off | Write | |||
| BV | 4140 | External override activate, SMART Link WB, on/off | Write | |||
| BV | 4141 | External override activate, SMART Link WB, SMART Link WB cool/heat, on/off | Write | |||
| BV | 4150 | External override activate, SMART Link DX 1, on/off | Write | |||
| BV | 4151 | External override activate, SMART Link DX 1 cool/heat, on/off | Write | |||
| BV | 4152 | External override activate, SMART Link DX 2, on/off | Write | |||
| BV | 4153 | External override activate, SMART Link DX 2 cool/heat, on/off | Write | |||
| BV | 4154 | External override activate, SMART Link DX 3, on/off | Write | |||
| BV | 4155 | External override activate, SMART Link DX 3 cool/heat, on/off | Write | |||
| BV | 4156 | External override activate, SMART Link DX 4, on/off | Write | |||
| BV | 4157 | External override activate, SMART Link DX 4 cool/heat, on/off | Write | |||
| BV | 4160 | External override activate, AQUA Link pump, on/off | Write | |||
| BV | 4170 | External override activate, Humidifying relay, on/off | Write | |||
| BV | 4190 | External override activate, AYC heat pump, on/off | Write | |||
| BV | 4191 | External override activate, AYC cool pump, on/off | Write | |||
| BV | 4200 | External override activate, AHU damper relay, on/off | Write | |||
| BV | 4201 | External override activate, AHU operation relay, on/off | Write | |||
| BV | 4210 | External override activate, Booster heat relay, on/off | Write | |||
| BV | 4211 | External override activate, Booster cool relay, on/off | Write | |||
| BV | 4220 | External override activate, Miru 1 fan, on/off | Write | |||
| BV | 4221 | External override activate, Miru 2 fan, on/off | Write | |||
| BV | 4222 | External override activate, Miru 3 fan, on/off | Write | |||
| BV | 4230 | External override activate, Exhaust heat relay, on/off | Write | |||
| BV | 5010 | External override activate, Supply air fan level | Write | |||
| BV | 5011 | External override activate, Extract air fan level | Write | |||
| BV | 5020 | External override activate, RX HX level | Write | |||
| BV | 5030 | External override activate, PX HX damper 3A | Write | |||
| BV | 5031 | External override activate, PX HX damper 1A | Write | |||
| BV | 5032 | External override activate, PX HX bypass 2A | Write | |||
| BV | 5033 | External override activate, PX HX bypass 4A | Write | |||
| BV | 5040 | External override activate, CX HX valve | Write | |||
| BV | 5041 | External override activate, CX HX pump level | Write | |||
| BV | 5050 | External override activate, Pre-heat level | Write | |||
| BV | 5060 | External override activate, Reheat level | Write | |||
| BV | 5070 | External override activate, Xzone heat level | Write | |||
| BV | 5080 | External override activate, Extra reg. 1 level | Write | |||
| BV | 5090 | External override activate, Extra reg. 2 level | Write | |||
| BV | 5100 | External override activate, Cool level | Write | |||
| BV | 5110 | External override activate, Xzone cool level | Write | |||
| BV | 5130 | External override activate, HC comp. level | Write | |||
| BV | 5131 | External override activate, HC defrost recirc. level | Write | |||
| BV | 5132 | External override activate, HC defrost el. heat level | Write | |||
| BV | 5150 | External override activate, SMART Link DX 1 comp. level | Write | |||
| BV | 5151 | External override activate, SMART Link DX 2 comp. level | Write | |||
| BV | 5152 | External override activate, SMART Link DX 3 comp. level | Write | |||
| BV | 5153 | External override activate, SMART Link DX 4 comp. level | Write | |||
| BV | 5170 | External override activate, Humidifying level | Write | |||
| BV | 5180 | External override activate, ReCO2 recirculation damper | Write | |||
| BV | 5181 | External override activate, ReCO2 outdoor damper | Write | |||
| BV | 5190 | External override activate, AYC heat valve level | Write | |||
| BV | 5191 | External override activate, AYC cool valve level | Write | |||
| BV | 5220 | External override activate, Miru 1 fan level | Write | |||
| BV | 5221 | External override activate, Miru 2 fan level | Write | |||
| BV | 5222 | External override activate, Miru 3 fan level | Write | |||
| BV | 5230 | External override activate, Exhaust heat level | Write | |||
| CAL | 0 | Calendar #1 | Read | |||
| CAL | 1 | Calendar #2 | Read | |||
| MI | 2 | Application id/AHU Type | Read | 1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX | ||
| MI | 3 | Air flow direction | Read | 1=Fan no.2 as SA, 2=Fan no.1 as SA | ||
| MI | 110 | PHX bypass type | Read | 1=Center, 2=Side | ||
| MI | 114 | PHX-2 3D Type | Read | 1=Cross flow, 2=Counter flow | ||
| MI | 115 | PHX type | Read | 1=PHX-1 1D HS, 2=PHX-2 3D, 3=PHX-3 1D 1PS | ||
| MI | 140 | Extra regulation sequence 1 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 142 | Extra regulation sequence 2 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 152 | Re-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 163 | Cool coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 198 | Xzone heat, coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 209 | Xzone cool, coil type | Read | 1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used | ||
| MI | 224 | Pre-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 284 | Exhaust heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 320 | SMART Link, WB cool mode | Read | 1=Heat, 2=Cool | ||
| MI | 591 | AHU Version | Read | 1=Version 1, 2=Version 2, 3=Version 3, 4=Version 4, 5=Version A, 6=Version B, 7=Version C, 8=Version D, 9=Version E, 10=Version F | ||
| MImin | 592 | Operation level | Read | 1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation, 15=Morning boost stop, 16=Intermittent night heat stop, 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment | ||
| MI | 665 | Schedule exception invalid data | Read | 1=Inactive, 2=Active | ||
| MI | 666 | Calendar 1 invalid data | Read | 1=Inactive, 2=Active | ||
| MI | 667 | Calendar 2 invalid data | Read | 1=Inactive, 2=Active | ||
| MI | 1400 | H/C mode | Read | 1=Inactive, 2=Active | ||
| MI | 1401 | H/C defrost accessory | Read | 1=Inactive, 2=Recirculation, 3=Electric heat | ||
| MI | 1402 | H/C recirculation defrost active | Read | 1=Inactive, 2=Active | ||
| MI | 1403 | H/C defrost active | Read | 1=Inactive, 2=Active | ||
| MI | 1407 | H/C heat type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 1410 | H/C operation mode | Read | 1=Inactive, 2=Stop, 3=Stabilization, 4=Normal operation, 5=Comfort operation, 6=Economy operation, 7=Defrost, 8=Defrost, 9=Oil recovery | ||
| MI | 1411 | H/C defrost mode | Read | 1=Inactive, 2=Start delay, 3=Initializing, 4=Pre-defrosting, 5=Defrosting, 6=Draining | ||
| MI | 1412 | H/C heat/cool mode | Read | 1=Heating, 2=Cooling | ||
| MO | 1 | Boost Supply air | Write | 1=Off, 2=On | ||
| MO | 2 | Boost Extract air | Write | 1=Off, 2=On | ||
| NC | 0 | NC 00 A-Alarm | Read | |||
| NC | 1 | NC 01 B-Alarm | Read | |||
| NC | 3 | NC 03 Alarms specified in BACnet | Read | |||
| NC | 10 | NC 10 Info message | Read | |||
| NC | 11 | NC 11 Events specified in BACnet | Read | |||
| SCH | 0 | Schedule #1 | Read | |||
| MV | 1 | SA Fan regulation mode | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan | ||
| MV | 2 | EA Fan regulation mode | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan | ||
| MV | 4 | Internal fire alarm reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 7 | External fire alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 8 | External fire alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 11 | External alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 12 | External alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 15 | External alarm no. 1 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 16 | External alarm no. 2 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 53 | Outdoor temp compensation function | Write | 1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed | ||
| MV | 78 | Down regulation function | Write | 1=Inactive, 2=SA, 3=SA and EA | ||
| MV | 84 | Fans in operation at fire alarm 1 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 87 | Fans in operation at fire alarm 2 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 90 | Fans in operation at internal fire alarm function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 95 | Pre-filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 96 | Pre-filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 101 | AHU filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 102 | AHU filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 107 | SA end filter function | Write | 1=Inactive, 2=SA | ||
| MV | 108 | SA end filter calibration | Write | 1=Inactive, 2=SA | ||
| MV | 111 | Seasonal controlled temperature regulation | Write | 1=Inactive, 2=Active | ||
| MV | 112 | Seasonal controlled temperature regulation mode | Write | 1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE | ||
| MV | 115 | Temperature regulation mode | Write | 1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE | ||
| MV | 166 | External room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 176 | External OA sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 188 | RHX sorption rotor function | Write | 1=Inactive, 2=Sorption max at cool, 3=Sorption always max | ||
| MV | 189 | Rotor type | Write | 1=RECOnomic, 2=STE, 3=MPE, 4=MTE | ||
| MV | 236 | Extra regulation 1 combi coil output indication | Write | 1=Heat, 2=Cool | ||
| MV | 237 | Extra regulation sequence 1 function | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | ||
| MV | 238 | Extra regulation sequence 1 output function | Write | 1=0-10V, 2=10-0V | ||
| MV | 249 | Extra regulation 1 combi coil external signal indication | Write | 1=Heat, 2=Cool | ||
| MV | 250 | Extra regulation 1 combi coil external signal value | Write | 1=Inactive, 2=Active | ||
| MV | 251 | Extra regulation 1 temperature protection function | Write | 1=Inactive, 2=Active | ||
| MV | 254 | Season heat function | Write | 1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode | ||
| MV | 255 | Season heat manual setting | Write | 1=Re-heat, 2=Extra regulation sequence | ||
| MV | 261 | Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 284 | Summer night cool function | Write | 1=Inactive, 2=Internal, 3=External | ||
| MV | 295 | Summer night cool from communication | Write | 1=Inactive, 2=Active | ||
| MV | 313 | Cooling boost function | Write | 1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence, 7=Sequence and Comfort, 8=Comfort, Economy and Sequence | ||
| MV | 329 | Xzone temperature regulation mode | Write | 1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE | ||
| MV | 378 | Xzone external room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 390 | Xzone combi coil module A external signal indication | Write | 1=Heat, 2=Cool | ||
| MV | 391 | Xzone combi coil module A output indication | Write | 1=Heat, 2=Cool | ||
| MV | 392 | Xzone combi coil module A external signal value | Write | 1=Inactive, 2=Active | ||
| MV | 395 | Xzone Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 405 | Xzone combi coil module B external signal indication | Write | 1=Heat, 2=Cool | ||
| MV | 406 | Xzone combi coil module B output indication | Write | 1=Heat, 2=Cool | ||
| MV | 407 | Xzone combi coil module B external signal value | Write | 1=Inactive, 2=Active | ||
| MV | 423 | ReCO2-CO2 function | Write | 1=Inactive, 2=CO2, 3=CO2 and air flow boost | ||
| MV | 424 | ReCO2 temperature regulation sequence function | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | ||
| MV | 441 | Humidifying function | Write | 1=Inactive, 2=On/Off, 3=0-10V | ||
| MV | 442 | Humidifying sensor | Write | 1=SA, 2=EA, 3=Room | ||
| MV | 457 | DeHumidifying function | Write | 1=Inactive, 2=SA, 3=EA, 4=Room | ||
| MV | 465 | VOC sensor function | Write | 1=Inactive, 2=Monitoring only, 3=Monitoring and regulation | ||
| MV | 469 | COOL DX Function | Write | 1=Inactive, 2=Economy, 3=Comfort, 4=Top | ||
| MV | 473 | Constant exhaust air temperature function | Write | 1=Inactive, 2=Active | ||
| MV | 481 | SMART Link Function | Write | 1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible | ||
| MV | 505 | AQUA Link Pump alarm function | Write | 1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function) | ||
| MV | 521 | AYC Function | Write | 1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water | ||
| MV | 528 | AYC Heated water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 555 | AYC Heated water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 562 | AYC Heated water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 577 | AYC Chilled water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 604 | AYC Chilled water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 611 | AYC Chilled water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 660 | MIRU Control 1 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 661 | MIRU Control 2 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 662 | MIRU Control 3 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 663 | MIRU Control 4 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 664 | MIRU Control 5 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 665 | MIRU Control 6 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 666 | MIRU Control 7 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 667 | MIRU Control 8 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 668 | MIRU Control 9 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 669 | MIRU Control 10 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed | ||
| MV | 671 | MIRU Control 1 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 679 | MIRU Control 2 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 687 | MIRU Control 3 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 695 | MIRU Control 4 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 703 | MIRU Control 5 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 711 | MIRU Control 6 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 719 | MIRU Control 7 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 727 | MIRU Control 8 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 735 | MIRU Control 9 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 743 | MIRU Control 10 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 765 | Heat neutral zone function | Write | 1=Set point, 2=Start limit | ||
| MV | 766 | Cool neutral zone function | Write | 1=Set point, 2=Start limit | ||
| MV | 777 | Night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 782 | Night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MVmin | 793 | Communication operation level | Write | 1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop | ||
| MV | 794 | Schedule operation level | Write | 1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop | ||
| MV | 816 | Extra regulation sequence 2 function | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | ||
| MV | 817 | Extra regulation sequence 2 output function | Write | 1=0-10V, 2=10-0V | ||
| MV | 828 | Extra regulation 2 combi coil external signal indication | Write | 1=Heat, 2=Cool | ||
| MV | 829 | Extra regulation 2 combi coil external signal value | Write | 1=Inactive, 2=Active | ||
| MV | 834 | Extra regulation 2 combi coil output indication | Write | 1=Heat, 2=Cool | ||
| MV | 850 | H/C heat mode | Write | 1=Standard, 2=Comfort | ||
| MV | 851 | H/C cool mode | Write | 1=Standard, 2=Comfort | ||
| MV | 890 | Humidifying time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 895 | Humidifying time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 900 | Humidifying time 3 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 905 | Humidifying time 4 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday |
No points match these filters.
Object ID lookup: Swegon GOLD generation E/F BACnet IP, PV 2.48 point IDs by name
AI1Component nameAI4SA Air flowAI5SA Air flow regulatorAI6EA Air flowAI7EA Air flow regulatorAI8SA Duct pressureAI9SA Duct pressure regulatorAI10EA Duct pressureAI11EA Duct pressure regulatorAI12Demand input levelAI13Demand regulatorAI14SA Air flow pressureAI15EA Air flow pressureAI18Demand CO2 regulatorAI19Demand VOC regulatorAI23SA Pre-filter pressure levelAI24SA Pre-filter pressure alarm limitAI25EA Pre-filter pressure levelAI26EA Pre-filter pressure alarm limitAI27SA AHU filter pressure levelAI28SA AHU filter pressure alarm limitAI29EA AHU filter pressure levelAI30EA AHU filter pressure alarm limitAI31SA End-filter pressure levelAI32SA End-filter pressure alarm limitAI37SA Fan levelAI38EA Fan levelAI39SA Fan speedAI40EA Fan speedAI41SA VoltageAI42EA VoltageAI43SA Fan currentAI44EA Fan currentAI45SA Fan powerAI46EA Fan powerAI47SA Fan kWhAI48EA Fan kWhAI49SA Fan MWhAI50EA Fan MWhAI51SA Fan operation timeAI52EA Fan operation timeAI55SA Fan min air flowAI56EA Fan min air flowAI57SA Fan max air flowAI58EA Fan max air flowAI63SFPAI64SA TemperatureAI65SA-D TemperatureAI66EA TemperatureAI67EA-D TemperatureAI68EA Regulation temperatureAI69EA Temperature PX/CXAI70EA Temperature SDAI72Outdoor temperature COOL DXAI73Outdoor temperatureAI74Outdoor regulation temperatureAI75External outdoor temperature 1AI76External outdoor temperature 2AI77External outdoor temperature 3AI78External outdoor temperature 4AI80EA Duct temperatureAI81Room temperature 1AI82Room temperature 2AI83Room temperature 3AI84Room temperature 4AI87SA Temp regulatorAI88EA Temp regulatorAI90Cool exchanger regulator levelAI91Heat exchanger regulator levelAI92Extra regulation sequence 1 heat regulator levelAI93Extra regulation sequence 1 heat output levelAI94Reheat regulator levelAI95Reheat output levelAI96ReCO2 heat levelAI97Down regulation levelAI98Heating boost levelAI99Extra regulation sequence 1 cool regulator levelAI100Extra regulation sequence 1 cool output levelAI101Cool regulator levelAI102Cool output levelAI103ReCO2 cool levelAI104Cooling boost levelAI105RHX operation levelAI106RHX/PHX/CHX efficiencyAI107RHX defrost pressure levelAI108RHX defrost pressure alarm limitAI109RHX carry over control pressure levelAI111RHX operation timeAI112PX exchanger bypass 4A outputAI113PX exchanger bypass 4A feedbackAI116PX defrost pressure levelAI117PHX-3D Bypass outputAI118PHX-3D Bypass inputAI119PHX-3D Bypass temperature 1AI120PHX-3D Bypass temperature 2AI121PX exchanger damper 1 outputAI122PHX-2 Damper 1 inputAI123PX exchanger damper 2 outputAI124PHX-2 Damper 2 inputAI125PX exchanger bypass outputAI126PX exchanger bypass feedbackAI127CHX-1 Valve outputAI128CHX-1 Valve inputAI129CHX-1 Return water temperatureAI130PHX/CHX operation timeAI132PHX-1D Bypass outputAI133PHX-1D Bypass inputAI134CHX-2 Return water temperatureAI135CHX-2 Extract coil pressure levelAI136PHX/CHX Humidity levelAI137CHX-2 Valve outputAI138CHX-2 Valve inputAI139CHX-2 Pump outputAI141Extra regulation sequence 1 anti frost temp/overheat inputAI143Extra regulation sequence 2 anti frost temp/overheat inputAI144Extra regulation sequence 1 temperature guardAI145Extra regulation sequence 2 temperature guardAI146Extra regulation sequence 1 input levelAI147Extra regulation sequence 1 heat operation timeAI148Extra regulation sequence 1 cool operation timeAI149Extra regulation sequence 2 input levelAI150Extra regulation sequence 2 heat operation timeAI151Extra regulation sequence 2 cool operation timeAI153Re-heat anti frost temp/overheat inputAI158Re-heat input levelAI159Re-heat operation timeAI164Cool water temperatureAI168Cool input levelAI169Cool operation timeAI174Xzone SA temperatureAI175Xzone EA temperatureAI176Xzone EA regulation temperatureAI177Xzone Room temperature 1AI178Xzone Room temperature 2AI179Xzone Room temperature 3AI180Xzone Room temperature 4AI181Xzone Room temperature min/max/averageAI186Xzone SA Temp regulatorAI187Xzone EA Temp regulatorAI190Xzone re-heat regulator levelAI193Xzone cool regulator levelAI199Xzone heat, anti frost temp/overheat inputAI200Xzone heat/cool temperature guardAI203Xzone heat, output levelAI204Xzone heat, input levelAI205Xzone heat, operation timeAI210Xzone cool, water temperatureAI211Xzone cool temperature guardAI214Xzone cool, output levelAI215Xzone cool, input levelAI216Xzone cool, operation timeAI220Pre-heat temperatureAI221Pre-heat temp regulator set pointAI222Pre-heat temp regulator levelAI225Pre-heat anti frost temp/overheat inputAI228Pre-heat output levelAI229Pre-heat input levelAI230Pre-heat operation timeAI233ReCO2 recirculation damper outputAI234ReCO2 recirculation damper inputAI235ReCO2 outdoor damper outputAI236ReCO2 outdoor damper inputAI237ReCO2 outdoor air flowAI238ReCO2 outdoor air flow regulator set pointAI244SA humidity levelAI245SA humidity temperatureAI246SA dew pointAI247EA humidity levelAI248EA humidity temperatureAI249EA dew pointAI251Dehumidifying SA dew point regulator set pointAI252Dehumidifying output levelAI254Humidifying SA regulator set pointAI255Humidifying output levelAI260Exhaust air humidityAI261Exhaust air temperatureAI262Outdoor air humidityAI263Outdoor air temperatureAI264Room air humidityAI265Room air temperatureAI266VOC levelAI267CO2 levelAI271COOL DX, unit power sizeAI274COOL DX, compressor 1 low pressure levelAI275COOL DX, compressor 1 high pressure levelAI276COOL DX, compressor 2 low pressure levelAI277COOL DX, compressor 2 high pressure levelAI281Exhaust heat temperatureAI282Exhaust heat temp regulator set pointAI283Exhaust heat temp regulator levelAI285Exhaust heat anti frost temp/overheat inputAI286Exhaust heat output levelAI287Exhaust heat input levelAI288Exhaust heat operation timeAI289SMART Link, WB outlet water 1AI290SMART Link, WB outlet water 2AI291SMART Link, WB outlet water 3AI292SMART Link, WB outlet water 4AI293SMART Link, WB outlet water averageAI294SMART Link, WB reference waterAI297SMART Link WB, heated water set pointAI298SMART Link WB, chilled water set pointAI299SMART Link WB, Min heated water set pointAI300SMART Link WB, Max heated water set pointAI301SMART Link WB, Min chilled water set pointAI302SMART Link WB, Max chilled water set pointAI327SMART Link, DX unit 1 power level set pointAI328SMART Link, DX unit 1 power levelAI329SMART Link, DX unit 1 operation timeAI338SMART Link, DX unit 2 power level set pointAI339SMART Link, DX unit 2 power levelAI340SMART Link, DX unit 2 operation timeAI349SMART Link, DX unit 3 power level set pointAI350SMART Link, DX unit 3 power levelAI351SMART Link, DX unit 3 operation timeAI360SMART Link, DX unit 4 power level set pointAI361SMART Link, DX unit 4 power levelAI362SMART Link, DX unit 4 operation timeAI374AYC Heat, heated waterAI375AYC Heated water set pointAI376AYC Heat, valve outputAI377AYC Heat, valve inputAI378AYC Heat, operation timeAI379AYC Heated water heat demandAI387AYC Cool, chilled waterAI388AYC Chilled water set pointAI389AYC Cool, valve outputAI390AYC Cool, valve inputAI391AYC Cool, operation timeAI392AYC Chilled water cool demandAI400MIRU Control 1 Min air flowAI401MIRU Control 1 Max air flowAI402MIRU Control 1 Air flowAI403MIRU Control 1 Air flow set pointAI404MIRU Control 1 PressureAI405MIRU Control 1 Pressure set pointAI406MIRU Control 1 External temperatureAI407MIRU Control 1 Operation timeAI408MIRU Control 1 Fan levelAI409MIRU Control 1 Fan powerAI410MIRU Control 1 SFPAI411MIRU Control 1 kWhAI412MIRU Control 1 MWhAI417MIRU Control 2 Min air flowAI418MIRU Control 2 Max air flowAI419MIRU Control 2 Air flowAI420MIRU Control 2 Air flow set pointAI421MIRU Control 2 PressureAI422MIRU Control 2 Pressure set pointAI423MIRU Control 2 External temperatureAI424MIRU Control 2 Operation timeAI425MIRU Control 2 Fan levelAI426MIRU Control 2 Fan powerAI427MIRU Control 2 SFPAI428MIRU Control 2 kWhAI429MIRU Control 2 MWhAI434MIRU Control 3 Min air flowAI435MIRU Control 3 Max air flowAI436MIRU Control 3 Air flowAI437MIRU Control 3 Air flow set pointAI438MIRU Control 3 PressureAI439MIRU Control 3 Pressure set pointAI440MIRU Control 3 External temperatureAI441MIRU Control 3 Operation timeAI442MIRU Control 3 Fan levelAI443MIRU Control 3 Fan powerAI444MIRU Control 3 SFPAI445MIRU Control 3 kWhAI446MIRU Control 3 MWhAI451MIRU Control 4 Min air flowAI452MIRU Control 4 Max air flowAI453MIRU Control 4 Air flowAI454MIRU Control 4 Air flow set pointAI455MIRU Control 4 PressureAI456MIRU Control 4 Pressure set pointAI457MIRU Control 4 External temperatureAI458MIRU Control 4 Operation timeAI459MIRU Control 4 Fan levelAI460MIRU Control 4 Fan powerAI461MIRU Control 4 SFPAI462MIRU Control 4 kWhAI463MIRU Control 4 MWhAI468MIRU Control 5 Min air flowAI469MIRU Control 5 Max air flowAI470MIRU Control 5 Air flowAI471MIRU Control 5 Air flow set pointAI472MIRU Control 5 PressureAI473MIRU Control 5 Pressure set pointAI474MIRU Control 5 External temperatureAI475MIRU Control 5 Operation timeAI476MIRU Control 5 Fan levelAI477MIRU Control 5 Fan powerAI478MIRU Control 5 SFPAI479MIRU Control 5 kWhAI480MIRU Control 5 MWhAI485MIRU Control 6 Min air flowAI486MIRU Control 6 Max air flowAI487MIRU Control 6 Air flowAI488MIRU Control 6 Air flow set pointAI489MIRU Control 6 PressureAI490MIRU Control 6 Pressure set pointAI491MIRU Control 6 External temperatureAI492MIRU Control 6 Operation timeAI493MIRU Control 6 Fan levelAI494MIRU Control 6 Fan powerAI495MIRU Control 6 SFPAI496MIRU Control 6 kWhAI497MIRU Control 6 MWhAI502MIRU Control 7 Min air flowAI503MIRU Control 7 Max air flowAI504MIRU Control 7 Air flowAI505MIRU Control 7 Air flow set pointAI506MIRU Control 7 PressureAI507MIRU Control 7 Pressure set pointAI508MIRU Control 7 External temperatureAI509MIRU Control 7 Operation timeAI510MIRU Control 7 Fan levelAI511MIRU Control 7 Fan powerAI512MIRU Control 7 SFPAI513MIRU Control 7 kWhAI514MIRU Control 7 MWhAI519MIRU Control 8 Min air flowAI520MIRU Control 8 Max air flowAI521MIRU Control 8 Air flowAI522MIRU Control 8 Air flow set pointAI523MIRU Control 8 PressureAI524MIRU Control 8 Pressure set pointAI525MIRU Control 8 External temperatureAI526MIRU Control 8 Operation timeAI527MIRU Control 8 Fan levelAI528MIRU Control 8 Fan powerAI529MIRU Control 8 SFPAI530MIRU Control 8 kWhAI531MIRU Control 8 MWhAI536MIRU Control 9 Min air flowAI537MIRU Control 9 Max air flowAI538MIRU Control 9 Air flowAI539MIRU Control 9 Air flow set pointAI540MIRU Control 9 PressureAI541MIRU Control 9 Pressure set pointAI542MIRU Control 9 External temperatureAI543MIRU Control 9 Operation timeAI544MIRU Control 9 Fan levelAI545MIRU Control 9 Fan powerAI546MIRU Control 9 SFPAI547MIRU Control 9 kWhAI548MIRU Control 9 MWhAI553MIRU Control 10 Min air flowAI554MIRU Control 10 Max air flowAI555MIRU Control 10 Air flowAI556MIRU Control 10 Air flow set pointAI557MIRU Control 10 PressureAI558MIRU Control 10 Pressure set pointAI559MIRU Control 10 External temperatureAI560MIRU Control 10 Operation timeAI561MIRU Control 10 Fan levelAI562MIRU Control 10 Fan powerAI563MIRU Control 10 SFPAI564MIRU Control 10 kWhAI565MIRU Control 10 MWhAI570IQlogic software versionAI604Triggered alarm #1AI605Triggered alarm #2AI606Triggered alarm #3AI607Triggered alarm #4AI608Triggered alarm #5AI609Triggered alarm #6AI610Triggered alarm #7AI611Triggered alarm #8AI612Triggered alarm #9AI613Triggered alarm #10AI614Triggered alarm group #1AI615Triggered alarm group #2AI616Triggered alarm group #3AI617Triggered alarm group #4AI618Triggered alarm group #5AI619Triggered alarm group #6AI620Triggered alarm group #7AI621Triggered alarm group #8AI622Triggered alarm group #9AI623Triggered alarm group #10AI661Prolonged low speed remaining hoursAI662Prolonged low speed remaining secondsAI663Prolonged high speed remaining hoursAI664Prolonged high speed remaining secondsAI697Exhaust heat heat retention at stopAI698Exhaust heat heat retention at operationAI699Exhaust heat frost protection alarm limitAI700Extra regulation sequence 2 heat regulator levelAI701Extra regulation sequence 2 heat output levelAI702Extra regulation sequence 2 cool regulator levelAI703Extra regulation sequence 2 cool output levelAI704Re-heat retention at stopAI705Re-heat retention at operationAI706Re-heat frost protection alarm limitAI707Pre-heat retention at stopAI708Pre-heat retention at operationAI709Pre-heat frost protection alarm limitAI710Xzone heat retention at stopAI711Xzone heat retention at operationAI712Xzone frost protection alarm limitAI713Extra regulation sequence 1 heat retention at stopAI714Extra regulation sequence 1 heat retention at operationAI715Extra regulation sequence 1 frost protection alarm limitAI716Extra regulation sequence 2 heat retention at stopAI717Extra regulation sequence 2 heat retention at operationAI718Extra regulation sequence 2 frost protection alarm limitAI719Heat exchange motor power consumption WAI720Heat exchange motor power consumption kWAI721Heat exchange motor energy consumption kWhAI722Heat exchange motor energy consumption MWhAI723Heat power recovery WAI724Heat power recovery kWAI725Heat power consumption WAI726Heat power consumption kWAI727Cool power recovery WAI728Cool power recovery kWAI729Cool power consumption WAI730Cool power consumption kWAI731Heat energy recovery kWhAI732Heat energy recovery MWhAI733Cool energy recovery kWhAI734Cool energy recovery MWhAI735Heat energy consumption kWhAI736Heat energy consumption MWhAI737Cool energy consumption kWhAI738Cool energy consumption MWhAI739Energy input 1 kWhAI740Energy input 1 MWhAI741Energy input 2 kWhAI742Energy input 2 MWhAI743Energy input 3 kWhAI744Energy input 3 MWhAI745Energy input 4 kWhAI746Energy input 4 MWhAI747Re-heat water coil power consumption WAI748Re-heat water coil power consumption kWAI749Re-heat water coil energy consumption kWhAI750Re-heat water coil energy consumption MWhAI751Cool water coil power consumption WAI752Cool water coil power consumption kWAI753Cool water coil energy consumption kWhAI754Cool water coil energy consumption MWhAI755Xzone heat water coil power consumption WAI756Xzone heat water coil power consumption kWAI757Xzone heat water coil energy consumption kWhAI758Xzone heat water coil energy consumption MWhAI759Xzone cool water coil power consumption WAI760Xzone cool water coil power consumption kWAI761Xzone cool water coil energy consumption kWhAI762Xzone cool water coil energy consumption MWhAI763Re-heat liquid flow levelAI764Cool liquid flow levelAI765Xzone heat liquid flow levelAI766Xzone cool liquid flow levelAI780Re-heat return water temperatureAI781Re-heat flow water temperatureAI782Cool return water temperatureAI783Cool flow water temperatureAI784Xzone heat return water temperatureAI785Xzone heat flow water temperatureAI786Xzone cool return water temperatureAI787Xzone cool flow water temperatureAI800External operation I/O-module 3, analogue input 1AI801External operation I/O-module 3, analogue input 2AI804External operation I/O-module 3, analogue output 1AI805External operation I/O-module 3, analogue output 2AI806External operation I/O-module 6, analogue input 1AI807External operation I/O-module 6, analogue input 2AI810External operation I/O-module 6, analogue output 1AI811External operation I/O-module 6, analogue output 2AI812External operation I/O-module A, analogue inputAI813External operation I/O-module A, temp sensor 1AI814External operation I/O-module A, temp sensor 2AI815External operation I/O-module B, analogue inputAI816External operation I/O-module B, temp sensor 1AI817External operation I/O-module B, temp sensor 2AI818External operation I/O-module C, analogue inputAI819External operation I/O-module C, temp sensor 1AI820External operation I/O-module C, temp sensor 2AI1405H/C recirculation defrost damper outputAI1406H/C recirculation defrost damper inputAI1409H/C heat anti frost temp/overheat inputAI1413H/C operation levelAI1414H/C heat defrost levelAI1415H/C defrost pressure levelAI1416H/C defrost pressure start limitAI1417H/C defrost pressure end limitAI1418H/C superheat tempAI1419H/C discharge tempAI1420H/C suction tempAI1421H/C condensation tempAI1422H/C evaporation tempAI1423H/C high pressureAI1424H/C low pressureAI3002External override, remaining timeAO1Extract air start upAV3SA low speed air flow set pointAV4EA low speed air flow set pointAV5SA high speed air flow set pointAV6EA high speed air flow set pointAV7SA max speed air flow set point boostAV8EA max speed air flow set point boostAV9SA regulation zoneAV10EA regulation zoneAV11SA regulation I-timeAV12EA regulation I-timeAV19SA low speed pressure set pointAV20EA low speed pressure set pointAV21SA high speed pressure set pointAV22EA high speed pressure set pointAV23SA max speed pressure set pointAV24EA max speed pressure set pointAV25SA max speed output signalAV26EA max speed output signalAV27SA pressure regulation zoneAV28EA pressure regulation zoneAV29SA pressure I-timeAV30EA pressure I-timeAV33Demand low speed CO2 set pointAV34Demand high speed CO2 set pointAV35Demand low speed VOC set pointAV36Demand high speed VOC set pointAV37Demand low speed set pointAV38Demand high speed set pointAV39SA min speed air flow set pointAV40EA min speed air flow set pointAV41SA max speed air flow set point demandAV42EA max speed air flow set point demandAV43Demand P-bandAV44Demand I-timeAV45Demand CO2 P-bandAV46Demand VOC P-bandAV50Slave offset factorAV51SA slave offset air flowAV52EA slave offset air flowAV54Outdoor temp compensation X1AV55Outdoor temp compensation X2AV56Outdoor temp compensation X3AV57Outdoor temp compensation X4AV58Outdoor temp compensation Y1 SA air flowAV59Outdoor temp compensation Y2 SA air flowAV60Outdoor temp compensation Y3 SA air flowAV61Outdoor temp compensation Y4 SA air flowAV62Outdoor temp compensation Y1 EA air flowAV63Outdoor temp compensation Y2 EA air flowAV64Outdoor temp compensation Y3 EA air flowAV65Outdoor temp compensation Y4 EA air flowAV66Outdoor temp compensation Y1 SA pressureAV67Outdoor temp compensation Y2 SA pressureAV68Outdoor temp compensation Y3 SA pressureAV69Outdoor temp compensation Y4 SA pressureAV70Outdoor temp compensation Y1 EA pressureAV71Outdoor temp compensation Y2 EA pressureAV72Outdoor temp compensation Y3 EA pressureAV73Outdoor temp compensation Y4 EA pressureAV79Down regulation neutral zoneAV80Down regulation P-bandAV81Down regulation I-timeAV85SA fan speed at fire alarm 1AV86EA fan speed at fire alarm 1AV88SA fan speed at fire alarm 2AV89EA fan speed at fire alarm 2AV91SA fan speed at internal fire alarmAV92EA fan speed at internal fire alarmAV97SA pre-filter alarm limitAV98EA pre-filter alarm limitAV103SA AHU-filter alarm limitAV104EA AHU-filter alarm limitAV109SA end-filter alarm limitAV113Seasonal controlled temperature regulation activeAV114Seasonal controlled temperature regulation inactiveAV117ERS 1 stepAV118ERS 1 diffAV119ERS 1 breakpointAV122ERS 2 breakpoint X1AV123ERS 2 breakpoint X2AV124ERS 2 breakpoint X3AV125ERS 2 breakpoint X4AV126ERS 2 breakpoint Y1AV127ERS 2 breakpoint Y2AV128ERS 2 breakpoint Y3AV129ERS 2 breakpoint Y4AV132SA temperature set pointAV135EA/Room temperature set pointAV136SA min temp set pointAV137SA max temp set pointAV138EA regultaion P-bandAV139EA regultaion I-timeAV142ORS breakpoint X1AV143ORS breakpoint X2AV144ORS breakpoint X3AV145ORS breakpoint X4AV146ORS breakpoint Y1AV147ORS breakpoint Y2AV148ORS breakpoint Y3AV149ORS breakpoint Y4AV152ORE breakpoint X1AV153ORE breakpoint X2AV154ORE breakpoint X3AV155ORE breakpoint X4AV156ORE breakpoint Y1AV157ORE breakpoint Y2AV158ORE breakpoint Y3AV159ORE breakpoint Y4AV168External room temp from BMSAV169External room temp from BMS alarm timeAV178External OA temp from BMSAV179External OA temp from BMS alarm timeAV184RHX defrost start limitAV191RHX min exhaust air temp set pointAV192RHX min exhaust air temp P-bandAV193RHX min exhaust air temp I-timeAV199PHX periodic operation intervalAV200PHX periodic operation timeAV202PHX supply air temp set point displacementAV207CHX periodic operation intervalAV208CHX periodic operation timeAV213PHX/CHX Bypass defrost limitAV214PHX/CHX Bypass defrost P-bandAV215PHX/CHX Bypass defrost I-timeAV220Heat exchange temperature regulation P-bandAV221Heat exchange temperature regulation I-timeAV222Cool exchange temperature regulation P-bandAV223Cool exchange temperature regulation I-timeAV226Re-heat P-bandAV227Re-heat I-timeAV230Re-heat periodic operation intervalAV231Re-heat periodic operation timeAV239Extra regulation sequence 1 heat max output signalAV240Extra regulation sequence 1 cool max output signalAV241Extra regulation sequence 1 heat P-bandAV242Extra regulation sequence 1 heat I-timeAV243Extra regulation sequence 1 cool P-bandAV244Extra regulation sequence 1 cool I-timeAV247Extra regulation 1 periodic operation intervalAV248Extra regulation 1 periodic operation timeAV252Extra regulation 1 temperature protection temperatureAV253Extra regulation 1 temperature protection alarm delayAV258Cool step1 min supply air flow limitAV259Cool step2 min supply air flow limitAV260Cool step3 min supply air flow limitAV262Cool SA neutral zoneAV263Cool EA neutral zoneAV264Cool outdoor temp limit 1AV265Cool outdoor temp limit 2AV266Cool outdoor temp limit 3AV267Cool 0-10V min supply air flow limitAV268Cool 0-10V min extract air flow limitAV269Cool restart timeAV270Cool step up delay timeAV271Cool stand still timeAV272Cool P-bandAV273Cool I-timeAV277Cool periodic operation intervalAV278Cool periodic operation timeAV279Cool step1 min extract air flow limitAV280Cool step2 min extract air flow limitAV281Cool step3 min extract air flow limitAV285Summer night cool start time (hour)AV286Summer night cool start time (minute)AV287Summer night cool stop time (hour)AV288Summer night cool stop time (minute)AV289Summer night cool OA temp start limitAV290Summer night cool EA temp start limitAV291Summer night cool EA temp stop limitAV292Summer night cool SA temp set pointAV293Summer night cool SA flow set pointAV294Summer night cool EA flow set pointAV297Intermittent night heat SA flow set pointAV298Intermittent night heat SA duct pressure set pointAV299Intermittent night heat EA temp start limitAV300Intermittent night heat EA temp stop limitAV301Intermittent night heat SA temp set pointAV303Intermittent night heat EA flow set pointAV304Intermittent night heat EA duct pressure set pointAV306Morning boost start time (hour)AV307Morning boost start time (minute)AV308Morning boost air flow set pointAV309Morning boost duct pressure set pointAV311Summer night cool SA duct pressure set pointAV312Summer night cool EA duct pressure set pointAV314Cooling boost comfort start limitAV315Cooling boost comfort regulation speedAV316Cooling boost economy P-bandAV317Cooling boost economy I-timeAV321Heating boost comfort start limitAV322Heating boost comfort regulation speedAV331Xzone ERS 1 stepAV332Xzone ERS 1 diffAV333Xzone ERS 1 breakpointAV336Xzone ERS 2 breakpoint X1AV337Xzone ERS 2 breakpoint X2AV338Xzone ERS 2 breakpoint X3AV339Xzone ERS 2 breakpoint X4AV340Xzone ERS 2 breakpoint Y1AV341Xzone ERS 2 breakpoint Y2AV342Xzone ERS 2 breakpoint Y3AV343Xzone ERS 2 breakpoint Y4AV346Xzone SA temperature set pointAV349Xzone EA/Room temperature set pointAV350Xzone SA min temp set pointAV351Xzone SA max temp set pointAV352Xzone EA regultaion P-bandAV353Xzone EA regultaion I-timeAV354Xzone ORS breakpoint X1AV355Xzone ORS breakpoint X2AV356Xzone ORS breakpoint X3AV357Xzone ORS breakpoint X4AV358Xzone ORS breakpoint Y1AV359Xzone ORS breakpoint Y2AV360Xzone ORS breakpoint Y3AV361Xzone ORS breakpoint Y4AV364Xzone ORE breakpoint X1AV365Xzone ORE breakpoint X2AV366Xzone ORE breakpoint X3AV367Xzone ORE breakpoint X4AV368Xzone ORE breakpoint Y1AV369Xzone ORE breakpoint Y2AV370Xzone ORE breakpoint Y3AV371Xzone ORE breakpoint Y4AV380Xzone external room temp from BMSAV381Xzone external room temp from BMS alarm timeAV384Xzone reheat P-bandAV385Xzone reheat I-timeAV388Xzone reheat periodic operation intervalAV389Xzone reheat periodic operation timeAV396Xzone Cool SA neutral zoneAV397Xzone Cool EA neutral zoneAV398Xzone Cool P-bandAV399Xzone Cool I-timeAV403Xzone Cool periodic operation intervalAV404Xzone Cool periodic operation timeAV411Pre-heat temperature set pointAV412Pre-heat P-bandAV413Pre-heat I-timeAV416Pre-heat periodic operation intervalAV417Pre-heat periodic operation timeAV426ReCO2-CO2 set pointAV427ReCO2 min. outdoor airAV428ReCO2 min. exhaust airAV429ReCO2-CO2 P-bandAV430ReCO2-CO2 I-timeAV431ReCO2-CO2 air flow boost reg. P-bandAV432ReCO2-CO2 air flow boost reg. I-timeAV433ReCO2 heat P-bandAV434ReCO2 heat I-timeAV435ReCO2 cool P-bandAV436ReCO2 cool I-timeAV437ReCO2-CO2 ppm set pointAV438ReCO2-CO2 ppm P-bandAV439ReCO2-VOC ppm set pointAV440ReCO2-VOC ppm P-bandAV443Humidifying on/off start levelAV444Humidifying on/off stop levelAV448Humidifying 0-10V set pointAV449Humidifying 0-10V SA max set pointAV450Humidifying 0-10V SA P-bandAV451Humidifying 0-10V SA I-timeAV452Humidifying 0-10V EA P-bandAV453Humidifying 0-10V EA I-timeAV458Dehumidifying SA set pointAV460Dehumidifying EA set pointAV470COOL DX Low pressure stop limitAV471COOL DX High pressure stop limitAV472COOL DX Restart timeAV474Exhaust heat temperature set pointAV475Exhaust heat P-bandAV476Exhaust heat I-timeAV479Exhaust heat periodic operation intervalAV480Exhaust heat periodic operation timeAV482SMART Link WB Heat temperature set pointAV483SMART Link WB Heat temperature heat zoneAV484SMART Link WB Cool temperature set pointAV485SMART Link WB Cool temperature heat zoneAV491SMART Link WB Optimize valve upper limitAV492SMART Link WB Optimize valve lower limitAV493SMART Link WB Optimize time delayAV494SMART Link WB Optimize heat regulation speedAV495SMART Link WB Optimize cool regulation speedAV510SMART Link DX Amount of unitsAV519SMART Link OA operation limitAV524AYC Heated water temp set pointAV526AYC Heated water OA temp for start of pumpAV527AYC Heated water OA temp for stop of pumpAV532AYC Heated water periodic operation intervalAV533AYC Heated water periodic operation timeAV537AYC Heated water OA temp compensation X1AV538AYC Heated water OA temp compensation X2AV539AYC Heated water OA temp compensation X3AV540AYC Heated water OA temp compensation X4AV541AYC Heated water OA temp compensation Y1AV542AYC Heated water OA temp compensation Y2AV543AYC Heated water OA temp compensation Y3AV544AYC Heated water OA temp compensation Y4AV549AYC Heated water room temp compensation temperatureAV550AYC Heated water room temp compensation P-bandAV554AYC Heated water night temp compensation tempAV556AYC Heated water night temp compensation start time 1 (hour)AV557AYC Heated water night temp compensation start time 1 (minutes)AV558AYC Heated water night temp compensation stop time 1 (hour)AV559AYC Heated water night temp compensation stop time 1 (minutes)AV563AYC Heated water night temp compensation start time 2 (hour)AV564AYC Heated water night temp compensation start time 2 (minutes)AV565AYC Heated water night temp compensation stop time 2 (hour)AV566AYC Heated water night temp compensation stop time 2 (minutes)AV569AYC Heated water P-bandAV570AYC Heated water I-timeAV572AYC Chilled water temp set pointAV575AYC Chilled water OA temp for start of pumpAV576AYC Chilled water OA temp for stop of pumpAV581AYC Chilled water periodic operation intervalAV582AYC Chilled water periodic operation timeAV586AYC Chilled water OA temp compensation X1AV587AYC Chilled water OA temp compensation X2AV588AYC Chilled water OA temp compensation X3AV589AYC Chilled water OA temp compensation X4AV590AYC Chilled water OA temp compensation Y1AV591AYC Chilled water OA temp compensation Y2AV592AYC Chilled water OA temp compensation Y3AV593AYC Chilled water OA temp compensation Y4AV598AYC Chilledwater room temp compensation temperatureAV599AYC Chilled water room temp compensation P-bandAV603AYC Chilled water night temp compensation tempAV605AYC Chilled water night temp compensation start time 1 (hour)AV606AYC Chilled water night temp compensation start time 1 (minutes)AV607AYC Chilled water night temp compensation stop time 1 (hour)AV608AYC Chilled water night temp compensation stop time 1 (minutes)AV612AYC Chilled water night temp compensation start time 2 (hour)AV613AYC Chilled water night temp compensation start time 2 (minutes)AV614AYC Chilledwater night temp compensation stop time 2 (hour)AV615AYC Chilled water night temp compensation stop time 2 (minutes)AV619AYC Chilled water dew point compensation neutral zoneAV620AYC Chilled water dew point compensation regulation speedAV623AYC Chilled water P-bandAV624AYC Chilled water I-timeAV638Optimize SA pressure set pointAV639Optimize EA pressure set pointAV672MIRU Control 1 Low speed duct pressure set pointAV673MIRU Control 1 High speed duct pressure set pointAV674MIRU Control 1 Low speed air flow set pointAV675MIRU Control 1 High speed air flow set pointAV676MIRU Control 1 offset factor for slave controlled air flowAV677MIRU Control 1 fixed flow offset for slave controlled SA flowAV680MIRU Control 2 Low speed duct pressure set pointAV681MIRU Control 2 High speed duct pressure set pointAV682MIRU Control 2 Low speed air flow set pointAV683MIRU Control 2 High speed air flow set pointAV684MIRU Control 2 offset factor for slave controlled air flowAV685MIRU Control 2 fixed flow offset for slave controlled SA flowAV688MIRU Control 3 Low speed duct pressure set pointAV689MIRU Control 3 High speed duct pressure set pointAV690MIRU Control 3 Low speed air flow set pointAV691MIRU Control 3 High speed air flow set pointAV692MIRU Control 3 offset factor for slave controlled air flowAV693MIRU Control 3 fixed flow offset for slave controlled SA flowAV696MIRU Control 4 Low speed duct pressure set pointAV697MIRU Control 4 High speed duct pressure set pointAV698MIRU Control 4 Low speed air flow set pointAV699MIRU Control 4 High speed air flow set pointAV704MIRU Control 5 Low speed duct pressure set pointAV705MIRU Control 5 High speed duct pressure set pointAV706MIRU Control 5 Low speed air flow set pointAV707MIRU Control 5 High speed air flow set pointAV712MIRU Control 6 Low speed duct pressure set pointAV713MIRU Control 6 High speed duct pressure set pointAV714MIRU Control 6 Low speed air flow set pointAV715MIRU Control 6 High speed air flow set pointAV720MIRU Control 7 Low speed duct pressure set pointAV721MIRU Control 7 High speed duct pressure set pointAV722MIRU Control 7 Low speed air flow set pointAV723MIRU Control 7 High speed air flow set pointAV728MIRU Control 8 Low speed duct pressure set pointAV729MIRU Control 8 High speed duct pressure set pointAV730MIRU Control 8 Low speed air flow set pointAV731MIRU Control 8 High speed air flow set pointAV736MIRU Control 9 Low speed duct pressure set pointAV737MIRU Control 9 High speed duct pressure set pointAV738MIRU Control 9 Low speed air flow set pointAV739MIRU Control 9 High speed air flow set pointAV744MIRU Control 10 Low speed duct pressure set pointAV745MIRU Control 10 High speed duct pressure set pointAV746MIRU Control 10 Low speed air flow set pointAV747MIRU Control 10 High speed air flow set pointAV752Delta temperature alarm limitAV753Efficiency alarm limitAV754Extra regulation sequence 1 heat neutral zoneAV755Extra regulation sequence 2 heat neutral zoneAV756ReCO2 heat neutral zoneAV757H/C heat neutral zoneAV758Re-heat neutral zoneAV759Extra regulation sequence 1 cool neutral zoneAV760Extra regulation sequence 2 cool neutral zoneAV761ReCO2 cool neutral zoneAV762H/C cool neutral zoneAV763Cool neutral zoneAV764Cooling boost neutral zoneAV776Night temp compensation tempAV778Night temp compensation start time 1 (hour)AV779Night temp compensation start time 1 (minute)AV780Night temp compensation stop time 1 (hour)AV781Night temp compensation stop time 1 (minute)AV783Night temp compensation start time 2 (hour)AV784Night temp compensation start time 2 (minute)AV785Night temp compensation stop time 2 (hour)AV786Night temp compensation stop time 2 (minute)AV800External operation I/O-module A, analogue outputAV801External operation I/O-module B, analogue outputAV802External operation I/O-module C, analogue outputAV818Extra regulation sequence 2 heat max output signalAV819Extra regulation sequence 2 cool max output signalAV820Extra regulation sequence 2 heat P-bandAV821Extra regulation sequence 2 heat I-timeAV822Extra regulation sequence 2 cool P-bandAV823Extra regulation sequence 2 cool I-timeAV826Extra regulation 2 periodic operation intervalAV827Extra regulation 2 periodic operation timeAV830Seasonal controlled supply airAV831Seasonal controlled extract air/room tempAV832Seasonal controlled supply air min tempAV833Seasonal controlled supply air max tempAV852H/C outdoor temperature limit heatingAV853H/C outdoor temperature limit coolingAV854H/C air flow limit supply airAV855H/C air flow limit extract airAV891Humidifying start time 1 (hour)AV892Humidifying start time 1 (minute)AV893Humidifying stop time 1 (hour)AV894Humidifying stop time 1 (minute)AV896Humidifying start time 2 (hour)AV897Humidifying start time 2 (minute)AV898Humidifying stop time 2 (hour)AV899Humidifying stop time 2 (minute)AV901Humidifying start time 3 (hour)AV902Humidifying start time 3 (minute)AV903Humidifying stop time 3 (hour)AV904Humidifying stop time 3 (minute)AV906Humidifying start time 4 (hour)AV907Humidifying start time 4 (minute)AV908Humidifying stop time 4 (hour)AV909Humidifying stop time 4 (minute)AV910Humidifying start timeAV911Humidifying stop timeAV912Humidifying timeAV1268Prolonged low speed hoursAV1269Prolonged low speed minutesAV1270Prolonged high speed hoursAV1271Prolonged high speed minutesAV3000External override code 1AV3001External override code 2AV3002External override, durationAV3010External override value, Supply air fan levelAV3011External override value, Extract air fan levelAV3020External override value, RX HX levelAV3030External override value, PX HX damper 3AAV3031External override value, PX HX damper 1AAV3032External override value, PX HX bypass 2AAV3033External override value, PX HX bypass 4AAV3040External override value, CX HX valveAV3041External override value, CX HX pump levelAV3050External override value, Pre-heat levelAV3060External override value, Reheat levelAV3070External override value, Xzone heat levelAV3080External override value, Extra reg. 1 levelAV3090External override value, Extra reg. 2 levelAV3100External override value, Cool levelAV3110External override value, Xzone cool levelAV3130External override value, HC comp. levelAV3131External override value, HC defrost recirc. levelAV3132External override value, HC defrost el. heat levelAV3150External override value, SMART Link DX 1 comp. levelAV3151External override value, SMART Link DX 2 comp. levelAV3152External override value, SMART Link DX 3 comp. levelAV3153External override value, SMART Link DX 4 comp. levelAV3170External override value, Humidifying levelAV3180External override value, ReCO2 recirculation damperAV3181External override value, ReCO2 outdoor damperAV3190External override value, AYC heat valve levelAV3191External override value, AYC cool valve levelAV3220External override value, Miru 1 fan levelAV3221External override value, Miru 2 fan levelAV3222External override value, Miru 3 fan levelAV3230External override value, Exhaust heat levelBI1Operation activeBI2Damper operation activeBI3Low speed operation activeBI4High speed operation activeBI5Intermittent night heat activeBI6Morning boost activeBI7Heating boost activeBI8Cooling boost activeBI9Summer night cool activeBI13A-alarm activeBI14B-alarm activeBI17HX operation activeBI18HX cool recovery activeBI19HX defrost activeBI22RHX speed monitor signalBI27CHX pump outputBI28CHX pump inputBI30Seasonal controlled temperature regulation indicationBI31Season heat, extra regulation sequence allowedBI32Season heat, re-heat allowedBI33Extra regulation sequence 1, outputBI34Extra regulation sequence 1, power reduction activeBI35Extra regulation sequence 1, anti-frost regulation activeBI36Extra regulation sequence 1 combi coil inputBI37Extra regulation sequence 1 combi coil outputBI38Re-heat outputBI39Re-heat power reduction activeBI40Re-heat anti-frost regulation activeBI43Cool output 1BI44Cool output 2BI46Extra regulation sequence 2 combi coil inputBI47Extra regulation sequence 2 combi coil outputBI48Extra regulation sequence 2, outputBI49Extra regulation sequence 2, power reduction activeBI50Extra regulation sequence 2, anti-frost regulation activeBI51Pre-heat outputBI52Pre-heat power reduction activeBI53Pre-heat anti-frost regulation activeBI56Xzone heat outputBI57Xzone heat power reduction activeBI58Xzone heat anti-frost regulation activeBI63Xzone cool output 1BI64Xzone cool output 2BI65Xzone combi coil module A inputBI66Xzone combi coil module A outputBI67Xzone combi coil module B inputBI68Xzone combi coil module B outputBI75Exhaust heat pump outputBI76Exhaust heat heating power reduction activeBI77Exhaust heat anti-frost regulation activeBI99AYC heat pump outputBI100AYC heat pump inputBI104AYC cool pump outputBI105AYC cool pump inputBI109COOL DX compressor 1 outputBI110COOL DX compressor 1 inputBI115COOL DX compressor 2 outputBI116COOL DX compressor 2 inputBI199Wireless AP activeBI200External operation I/O-module 3, digital input 1BI201External operation I/O-module 3, digital input 2BI202External operation I/O-module 3, digital output 1BI203External operation I/O-module 3, digital output 2BI204External operation I/O-module 6, digital input 1BI205External operation I/O-module 6, digital input 2BI206External operation I/O-module 6, digital output 1BI207External operation I/O-module 6, digital output 2BI208External operation I/O-module A, digital inputBI209External operation I/O-module B, digital inputBI210External operation I/O-module C, digital inputBI319SMART Link, WB operationBI323SMART Link, DX unit 1 operationBI324SMART Link, DX unit 1 cool modeBI325SMART Link, DX unit 1 defrost requestBI326SMART Link, DX unit 1 defrost activeBI334SMART Link, DX unit 2 operationBI335SMART Link, DX unit 2 cool modeBI336SMART Link, DX unit 2 defrost requestBI337SMART Link, DX unit 2 defrost activeBI345SMART Link, DX unit 3 operationBI346SMART Link, DX unit 3 cool modeBI347SMART Link, DX unit 3 defrost requestBI348SMART Link, DX unit 3 defrost activeBI356SMART Link, DX unit 4 operationBI357SMART Link, DX unit 4 cool modeBI358SMART Link, DX unit 4 defrost requestBI359SMART Link, DX unit 4 defrost activeBI367SMART Link, DX Defrost airflow increase statusBI501Alarm 1:1 External fire alarm no. 1 trippedBI502Alarm 1:2 External fire alarm no. 2 trippedBI503Alarm 1:3 Internal fire alarm trippedBI516Alarm 2:1 External alarm no. 1 trippedBI517Alarm 2:2 External alarm no. 2 trippedBI531Alarm 3:1 Pre-heat I/O-module no. 9 com. errorBI532Alarm 3:2 Pre-heat electrical heater overheat protection trippedBI533Alarm 3:3 Pre-heat frost protection trippedBI534Alarm 3:4 Pre-heat frost protection temperature sensor defectiveBI535Alarm 3:5 Pre-heat temperature sensor defectiveBI536Alarm 3:6 Pre-heat valve monitoring trippedBI537Alarm 3:7 Pre-heat temperature below set point alarm limitBI538Alarm 3:8 Pre-heat alarm input trippedBI546Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. errorBI547Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection trippedBI548Alarm 4:3 Extra reg. sequence 1 frost protection trippedBI549Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor defectiveBI550Alarm 4:5 Extra reg. sequence 1 valve monitoring trippedBI551Alarm 4:6 Extra reg. sequence 1 alarm input trippedBI552Alarm 4:7 Extra reg. sequence 1 temperature protection from com. errorBI553Alarm 4:8 Extra reg. sequence 1 combi coil temperature sensor defectiveBI554Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. errorBI555Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection trippedBI556Alarm 4:11 Extra reg. sequence 2 frost protection trippedBI557Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor defectiveBI558Alarm 4:13 Extra reg. sequence 2 valve monitoring trippedBI559Alarm 4:14 Extra reg. sequence 2 alarm input trippedBI560Alarm 4:15 Extra reg. sequence 2 combi coil temperature sensor defectiveBI561Alarm 5:1 Re-heat electrical heater over heat protection trippedBI562Alarm 5:2 Re-heat frost protection trippedBI563Alarm 5:3 Re-heat frost protection temperature sensor defectiveBI564Alarm 5:4 Re-heat valve monitoring trippedBI565Alarm 5:5 Re-heat alarm input trippedBI576Alarm 6:1 Xzone I/O-module no. A com. errorBI577Alarm 6:2 Xzone electrical heater overheat protection trippedBI578Alarm 6:3 Xzone frost protection trippedBI579Alarm 6:4 Xzone frost protection temperature sensor defectiveBI580Alarm 6:5 Xzone supply air temperature sensor defectiveBI581Alarm 6:6 Xzone heat valve monitoring trippedBI582Alarm 6:7 Xzone supply air temperature below set point alarm limitBI583Alarm 6:8 Xzone supply air temperature above set point alarm limitBI584Alarm 6:9 Xzone heat alarm input trippedBI585Alarm 6:10 Xzone combi coil module A temperature sensor defectiveBI586Alarm 6:11 Xzone temperature protection I/O-module no. 9 com. errorBI591Alarm 7:1 Xzone I/O-module no. B com. errorBI592Alarm 7:2 Xzone extract air temperature sensor defectiveBI593Alarm 7:3 Xzone cool valve monitoring trippedBI594Alarm 7:4 Xzone extract air temperature below set point alarm limitBI595Alarm 7:5 Xzone cool alarm input 1 trippedBI596Alarm 7:6 Xzone cool alarm input 2 trippedBI597Alarm 7:7 Xzone combi coil module B temperature sensor defectiveBI610Alarm 8:5 Cool valve monitoring trippedBI611Alarm 8:6 Cool alarm input 1 trippedBI612Alarm 8:7 Cool alarm input 2 trippedBI621Alarm 9:1 Exhaust heat I/O-module no. 4 com errorBI622Alarm 9:2 Exhaust heat electrical heater overheat protection trippedBI623Alarm 9:3 Exhaust heat frost protection trippedBI624Alarm 9:4 Exhaust heat frost protection temperature sensor defectiveBI625Alarm 9:5 Exhaust heat temperature sensor defectiveBI626Alarm 9:6 Exhaust heat valve monitoring trippedBI627Alarm 9:7 Exhaust heat temperature below set point alarm limitBI628Alarm 9:8 Exhaust heat alarm input trippedBI636Alarm 10:1 Supply air temperature sensor defectiveBI637Alarm 10:2 Supply air temperature sensor for density compensation defectiveBI638Alarm 10:3 Extract air temperature sensor defectiveBI639Alarm 10:4 Extract air temperature sensor for density compensation defectiveBI640Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def.BI641Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def.BI642Alarm 10:7 Extract air duct temperature sensor defectiveBI645Alarm 10:10 Outdoor air temperature sensor defectiveBI651Alarm 11:1 Room temperature sensor no. 1 defectiveBI652Alarm 11:2 Room temperature sensor no. 2 defectiveBI653Alarm 11:3 Room temperature sensor no. 3 defectiveBI654Alarm 11:4 Room temperature sensor no. 4 defectiveBI655Alarm 11:5 Xzone room temperature sensor no. 5 defectiveBI656Alarm 11:6 Xzone room temperature sensor no. 6 defectiveBI657Alarm 11:7 Xzone room temperature sensor no. 7 defectiveBI658Alarm 11:8 Xzone room temperature sensor no. 8 defectiveBI659Alarm 11:9 Outdoor temperature sensor no. A defectiveBI660Alarm 11:10 Outdoor temperature sensor no. B defectiveBI661Alarm 11:11 Outdoor temperature sensor no. C defectiveBI662Alarm 11:12 Outdoor temperature sensor no. D defectiveBI663Alarm 11:13 Room temperature from com. errorBI664Alarm 11:14 Xzone room temperature from com. errorBI665Alarm 11:15 Outdoor temperature from com. errorBI666Alarm 12:1 Supply air temperature below set point alarm limitBI667Alarm 12:2 Supply air temperature above set point alarm limitBI671Alarm 12:6 Extract air temperature below alarm limitBI676Alarm 12:11 Temperature guard below alarm limitBI678Alarm 12:13 Heat exchange efficiency below alarm limitBI681Alarm 13:1 Humidification I/O-module no. 4 com. errorBI682Alarm 13:2 Supply air humidity sensor defectiveBI683Alarm 13:3 Extract air humidity sensor defectiveBI684Alarm 13:4 Exhaust air humidity sensor defectiveBI685Alarm 13:5 Outdoor air humidity sensor defectiveBI686Alarm 13:6 Room humidity sensor defectiveBI689Alarm 13:9 Humidifier alarm output trippedBI691Alarm 13:11 VOC sensor com. errorBI692Alarm 13:12 VOC sensor internal com. errorBI693Alarm 13:13 VOC sensor internal errorBI694Alarm 13:14 VOC sensor level below/above set point alarm limitBI696Alarm 14:1 Re-heat liquid flow measurement I/O-module no. 6 com. errorBI697Alarm 14:2 Re-heat liquid flow measurement temp. sensor no. 1 defectiveBI698Alarm 14:3 Re-heat liquid flow measurement temp. sensor no. 2 defectiveBI699Alarm 14:4 Re-heat liquid flow measurement valve leakageBI700Alarm 14:5 Re-heat liquid flow measurement flow sensor defectiveBI703Alarm 14:8 Cool liquid flow measurement I/O-module no. 7 com. errorBI704Alarm 14:9 Cool liquid flow measurement temp. sensor no. 1 defectiveBI705Alarm 14:10 Cool liquid flow measurement temp. sensor no. 2 defectiveBI706Alarm 14:11 Cool liquid flow measurement valve leakageBI707Alarm 14:12 Cool liquid flow measurement flow sensor defectiveBI711Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. errorBI712Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defectiveBI713Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defectiveBI714Alarm 15:4 Plate heat exchanger damper monitor trippedBI716Alarm 15:6 Plate heat exchanger bypass damper 4A monitor trippedBI717Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. errorBI718Alarm 15:8 Plate heat exchanger bypass damper monitor trippedBI719Alarm 15:9 Plate heat exchanger damper no. 1 monitor trippedBI720Alarm 15:10 Plate heat exchanger damper no. 2 monitor trippedBI721Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. errorBI722Alarm 15:12 Plate heat exchanger bypass damper monitor trippedBI723Alarm 15:13 Plate counter flow heat exchanger defrost pressure above alarm limitBI724Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. errorBI725Alarm 15:15 Plate heat exchanger defrost pressure above alarm limitBI726Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. errorBI727Alarm 16:2 Coil heat exchanger temperature sensor defectiveBI728Alarm 16:3 Coil heat exchanger valve monitor trippedBI729Alarm 16:4 Coil heat exchanger pump monitor trippedBI730Alarm 16:5 Coil heat exchanger I/O-module no. C communication errorBI731Alarm 16:6 Coil heat exchanger pressure sensor defectiveBI732Alarm 16:7 Coil heat exchanger low pressure brine circuitBI733Alarm 16:8 Coil heat exchanger pressure below alarm limitBI741Alarm 17:1 Rotary heat exchanger motor controller com. errorBI742Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. errorBI743Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limitBI744Alarm 17:4 Rotary heat exchanger speed monitor trippedBI745Alarm 17:5 Rotary heat exchanger motor controller over currentBI746Alarm 17:6 Rotary heat exchanger motor controller under voltageBI747Alarm 17:7 Rotary heat exchanger motor controller over voltageBI748Alarm 17:8 Rotary heat exchanger motor controller over temperatureBI749Alarm 17:9 Rotary heat exchanger motor controller start errorBI750Alarm 17:10 Rotary heat exchanger motor controller internal errorBI751Alarm 17:11 Rotary heat exchanger motor controller phase errorBI752Alarm 17:12 Rotary heat exchanger motor controller internal memory errorBI753Alarm 17:13 Rotary heat exchanger motor controller current reductionBI754Alarm 17:14 Rotary heat exchanger motor controller internal com. errorBI755Alarm 17:15 Rotary heat exchanger I/O-module com. errorBI756Alarm 18:1 AYC I/O-module no. 7 com. errorBI757Alarm 18:2 AYC heat temperature sensor defectiveBI758Alarm 18:3 AYC heat valve monitor trippedBI759Alarm 18:4 AYC heat pump monitor trippedBI760Alarm 18:5 AYC heat temperature below set point alarm limitBI761Alarm 18:6 AYC heat temperature above set point alarm limitBI764Alarm 18:9 AYC cool temperature sensor defectiveBI765Alarm 18:10 AYC cool valve monitor trippedBI766Alarm 18:11 AYC cool pump monitor trippedBI767Alarm 18:12 AYC cool temperature below set point alarm limitBI768Alarm 18:13 AYC cool temperature above set point alarm limitBI771Alarm 19:1 Rotary heat exchanger AQC pressure sensor no. E com. errorBI772Alarm 19:2 Rotary heat exchanger AQC pressure below set point alarm limitBI773Alarm 19:3 Rotary heat exchanger AQC damper monitoring trippedBI801Alarm 21:1 COOL DX I/O-module no. 2 com. errorBI802Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defectiveBI803Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limitBI804Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defectiveBI805Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limitBI806Alarm 21:6 COOL DX compressor no. 1 monitor trippedBI807Alarm 21:7 COOL DX compressor no. 1 restart errorBI808Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defectiveBI809Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limitBI810Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defectiveBI811Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limitBI812Alarm 21:12 COOL DX compressor no. 2 monitor trippedBI813Alarm 21:13 COOL DX compressor no. 2 restart errorBI814Alarm 21:14 COOL DX outdoor air temperature sensor defectiveBI815Alarm 21:15 COOL DX phase sequence error or supply voltage missingBI816Alarm 22:1 Xzone heat liquid flow measurement I/O-module no. D com. errorBI817Alarm 22:2 Xzone heat liquid flow measurement temp. sensor no. 1 defectiveBI818Alarm 22:3 Xzone heat liquid flow measurement temp. sensor no. 2 defectiveBI819Alarm 22:4 Xzone heat liquid flow measurement valve leakageBI820Alarm 22:5 Xzone heat liquid flow measurement flow sensor defectiveBI823Alarm 22:8 Xzone cool liquid flow measurement I/O-module no. E com. errorBI824Alarm 22:9 Xzone cool liquid flow measurement temp. sensor no. 1 defectiveBI825Alarm 22:10 Xzone cool liquid flow measurement temp. sensor no. 2 defectiveBI826Alarm 22:11 Xzone cool liquid flow measurement valve leakageBI827Alarm 22:12 Xzone cool liquid flow measurement flow sensor defectiveBI831Alarm 23:1 SMART Link com. errorBI832Alarm 23:2 SMART Link alarm level 1 trippedBI833Alarm 23:3 SMART Link alarm level 2 trippedBI834Alarm 23:4 SMART Link alarm level 3 trippedBI840Alarm 23:10 AQUA Link I/O-module no. 5 com. errorBI841Alarm 23:11 AQUA Link pump monitor trippedBI846Alarm 24:1 SMART Link no. 1 com. errorBI847Alarm 24:2 SMART Link no. 1 alarm trippedBI849Alarm 24:4 SMART Link no. 2 com. errorBI850Alarm 24:5 SMART Link no. 2 alarm trippedBI852Alarm 24:7 SMART Link no. 3 com. errorBI853Alarm 24:8 SMART Link no. 3 alarm trippedBI855Alarm 24:10 SMART Link no. 4 com. errorBI856Alarm 24:11 SMART Link no. 4 alarm trippedBI858Alarm 24:13 SMART Link supply air flow below alarm limitBI861Alarm 25:1 SMART Link+ cooling circuit A com. errorBI862Alarm 25:2 SMART Link+ cooling circuit B com. errorBI863Alarm 25:3 SMART Link+ heating circuit A com. errorBI864Alarm 25:4 SMART Link+ heating circuit B com. errorBI876Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. errorBI877Alarm 26:2 Pre-filter supply air dirtyBI882Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. errorBI883Alarm 26:8 Pre-filter extract air dirtyBI891Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. errorBI892Alarm 27:2 AHU filter supply air dirtyBI897Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. errorBI898Alarm 27:8 AHU filter extract air dirtyBI906Alarm 28:1 End filter supply air pressure sensor no. A com. errorBI907Alarm 28:2 End filter supply air dirtyBI921Alarm 29:1 Energy monitoring pulse counter com. errorBI936Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. errorBI937Alarm 30:2 Air flow measurement supply air flow below set point alarm limitBI938Alarm 30:3 Air flow measurement supply air flow above set point alarm limitBI941Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. errorBI942Alarm 30:7 Air flow measurement extract air flow below set point alarm limitBI943Alarm 30:8 Air flow measurement extract air flow above set point alarm limitBI946Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. errorBI951Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. errorBI952Alarm 31:2 Pressure regulation supply air pressure below set point alarm limitBI953Alarm 31:3 Pressure regulation supply air pressure above set point alarm limitBI956Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. errorBI957Alarm 31:7 Pressure regulation extract air press. below set point alarm limitBI958Alarm 31:8 Pressure regulation extract air press. above set point alarm limitBI966Alarm 32:1 ReCO2 I/O-module no. 0 com. errorBI967Alarm 32:2 ReCO2 pressure sensor no. 0 com. errorBI968Alarm 32:3 ReCO2 recirculation damper monitoring trippedBI969Alarm 32:4 ReCO2 outdoor air damper monitoring trippedBI981Alarm 33:1 Service period above alarm limitBI995Alarm 33:15 Lock function trippedBI996Alarm 34:1 External control I/O-module no. 3 com. errorBI997Alarm 34:2 External control I/O-module no. 6 com. errorBI1011Alarm 35:1 Booster diffusers I/O-module no. 8 com. errorBI1026Alarm 36:1 External BMS control I/O-module no. A communication errorBI1027Alarm 36:2 External BMS control I/O-module no. A temp. sensor no. 1 defectiveBI1028Alarm 36:3 External BMS control I/O-module no. A temp. sensor no. 2 defectiveBI1031Alarm 36:6 External BMS control I/O-module no. B communication errorBI1032Alarm 36:7 External BMS control I/O-module no. B temp. sensor no. 1 defectiveBI1033Alarm 36:8 External BMS control I/O-module no. B temp. sensor no. 2 defectiveBI1036Alarm 36:11 External BMS control I/O-module no. C communication errorBI1037Alarm 36:12 External BMS control I/O-module no. C temp. sensor no. 1 defectiveBI1038Alarm 36:13 External BMS control I/O-module no. C temp. sensor no. 2 defectiveBI1041Alarm 37:1 Multilogic com. errorBI1056Alarm 38:1 MIRU 1 com. errorBI1057Alarm 38:2 MIRU 1 motor controller alarm trippedBI1058Alarm 38:3 MIRU 1 motor controller com. errorBI1059Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. errorBI1060Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. errorBI1061Alarm 38:6 MIRU 1 temperature sensor defectiveBI1062Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limitBI1063Alarm 38:8 MIRU 1 air flow below set point alarm limitBI1064Alarm 38:9 MIRU 1 air flow above set point alarm limitBI1065Alarm 38:10 MIRU 1 pressure below set point alarm limitBI1066Alarm 38:11 MIRU 1 pressure above set point alarm limitBI1071Alarm 39:1 MIRU 2 com. errorBI1072Alarm 39:2 MIRU 2 motor controller alarm trippedBI1073Alarm 39:3 MIRU 2 motor controller com. errorBI1074Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. errorBI1075Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. errorBI1076Alarm 39:6 MIRU 2 temperature sensor defectiveBI1077Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limitBI1078Alarm 39:8 MIRU 2 air flow below set point alarm limitBI1079Alarm 39:9 MIRU 2 air flow above set point alarm limitBI1080Alarm 39:10 MIRU 2 pressure below set point alarm limitBI1081Alarm 39:11 MIRU 2 pressure above set point alarm limitBI1086Alarm 40:1 MIRU 3 com. errorBI1087Alarm 40:2 MIRU 3 motor controller alarm trippedBI1088Alarm 40:3 MIRU 3 motor controller com. errorBI1089Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. errorBI1090Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. errorBI1091Alarm 40:6 MIRU 3 temperature sensor defectiveBI1092Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limitBI1093Alarm 40:8 MIRU 3 air flow below set point alarm limitBI1094Alarm 40:9 MIRU 3 air flow above set point alarm limitBI1095Alarm 40:10 MIRU 3 pressure below set point alarm limitBI1096Alarm 40:11 MIRU 3 pressure above set point alarm limitBI1101Alarm 41:1 MIRU 4 com. errorBI1102Alarm 41:2 MIRU 4 motor controller alarm trippedBI1103Alarm 41:3 MIRU 4 motor controller com. errorBI1104Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. errorBI1105Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. errorBI1106Alarm 41:6 MIRU 4 temperature sensor defectiveBI1107Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limitBI1116Alarm 42:1 MIRU 5 com. errorBI1117Alarm 42:2 MIRU 5 motor controller alarm trippedBI1118Alarm 42:3 MIRU 5 motor controller com. errorBI1119Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. errorBI1120Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. errorBI1121Alarm 42:6 MIRU 5 temperature sensor defectiveBI1122Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limitBI1131Alarm 43:1 MIRU 6 com. errorBI1132Alarm 43:2 MIRU 6 motor controller alarm trippedBI1133Alarm 43:3 MIRU 6 motor controller com. errorBI1134Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. errorBI1135Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. errorBI1136Alarm 43:6 MIRU 6 temperature sensor defectiveBI1137Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limitBI1146Alarm 44:1 MIRU 7 com. errorBI1147Alarm 44:2 MIRU 7 motor controller alarm trippedBI1148Alarm 44:3 MIRU 7 motor controller com. errorBI1149Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. errorBI1150Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. errorBI1151Alarm 44:6 MIRU 7 temperature sensor defectiveBI1152Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limitBI1161Alarm 45:1 MIRU 8 com. errorBI1162Alarm 45:2 MIRU 8 motor controller alarm trippedBI1163Alarm 45:3 MIRU 8 motor controller com. errorBI1164Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. errorBI1165Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. errorBI1166Alarm 45:6 MIRU 8 temperature sensor defectiveBI1167Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limitBI1176Alarm 46:1 MIRU 9 com. errorBI1177Alarm 46:2 MIRU 9 motor controller alarm trippedBI1178Alarm 46:3 MIRU 9 motor controller com. errorBI1179Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. errorBI1180Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. errorBI1181Alarm 46:6 MIRU 9 temperature sensor defectiveBI1182Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limitBI1191Alarm 47:1 MIRU 10 com. errorBI1192Alarm 47:2 MIRU 10 motor controller alarm trippedBI1193Alarm 47:3 MIRU 10 motor controller com. errorBI1194Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. errorBI1195Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. errorBI1196Alarm 47:6 MIRU 10 temperature sensor defectiveBI1197Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limitBI1221Alarm 49:1 Supply air fan no. 1A com. errorBI1222Alarm 49:2 Supply air fan no. 1A motor controller over currentBI1223Alarm 49:3 Supply air fan no. 1A motor controller under voltageBI1224Alarm 49:4 Supply air fan no. 1A motor controller over voltageBI1225Alarm 49:5 Supply air fan no. 1A motor controller over temperatureBI1226Alarm 49:6 Supply air fan no. 1A motor controller start errorBI1227Alarm 49:7 Supply air fan no. 1A motor controller ripple errorBI1228Alarm 49:8 Supply air fan no. 1A motor controller phase errorBI1229Alarm 49:9 Supply air fan no. 1A motor controller internal memory errorBI1230Alarm 49:10 Supply air fan no. 1A motor controller current reductionBI1231Alarm 49:11 Supply air fan no. 1A motor controller internal com. errorBI1236Alarm 50:1 Supply air fan no. 2A com. errorBI1237Alarm 50:2 Supply air fan no. 2A motor controller over currentBI1238Alarm 50:3 Supply air fan no. 2A motor controller under voltageBI1239Alarm 50:4 Supply air fan no. 2A motor controller over voltageBI1240Alarm 50:5 Supply air fan no. 2A motor controller over temperatureBI1241Alarm 50:6 Supply air fan no. 2A motor controller start errorBI1242Alarm 50:7 Supply air fan no. 2A motor controller ripple errorBI1243Alarm 50:8 Supply air fan no. 2A motor controller phase errorBI1244Alarm 50:9 Supply air fan no. 2A motor controller internal memory errorBI1245Alarm 50:10 Supply air fan no. 2A motor controller current reductionBI1246Alarm 50:11 Supply air fan no. 2A motor controller internal com. errorBI1251Alarm 51:1 Supply air fan no. 3A com. errorBI1252Alarm 51:2 Supply air fan no. 3A motor controller over currentBI1253Alarm 51:3 Supply air fan no. 3A motor controller under voltageBI1254Alarm 51:4 Supply air fan no. 3A motor controller over voltageBI1255Alarm 51:5 Supply air fan no. 3A motor controller over temperatureBI1256Alarm 51:6 Supply air fan no. 3A motor controller start errorBI1257Alarm 51:7 Supply air fan no. 3A motor controller ripple errorBI1258Alarm 51:8 Supply air fan no. 3A motor controller phase errorBI1259Alarm 51:9 Supply air fan no. 3A motor controller internal memory errorBI1260Alarm 51:10 Supply air fan no. 3A motor controller current reductionBI1261Alarm 51:11 Supply air fan no. 3A motor controller internal com. errorBI1266Alarm 52:1 Supply air fan no. 1B com. errorBI1267Alarm 52:2 Supply air fan no. 1B motor controller over currentBI1268Alarm 52:3 Supply air fan no. 1B motor controller under voltageBI1269Alarm 52:4 Supply air fan no. 1B motor controller over voltageBI1270Alarm 52:5 Supply air fan no. 1B motor controller over temperatureBI1271Alarm 52:6 Supply air fan no. 1B motor controller start errorBI1272Alarm 52:7 Supply air fan no. 1B motor controller ripple errorBI1273Alarm 52:8 Supply air fan no. 1B motor controller phase errorBI1274Alarm 52:9 Supply air fan no. 1B motor controller internal memory errorBI1275Alarm 52:10 Supply air fan no. 1B motor controller current reductionBI1281Alarm 53:1 Supply air fan no. 2B com. errorBI1282Alarm 53:2 Supply air fan no. 2B motor controller over currentBI1283Alarm 53:3 Supply air fan no. 2B motor controller under voltageBI1284Alarm 53:4 Supply air fan no. 2B motor controller over voltageBI1285Alarm 53:5 Supply air fan no. 2B motor controller over temperatureBI1286Alarm 53:6 Supply air fan no. 2B motor controller start errorBI1287Alarm 53:7 Supply air fan no. 2B motor controller ripple errorBI1288Alarm 53:8 Supply air fan no. 2B motor controller phase errorBI1289Alarm 53:9 Supply air fan no. 2B motor controller internal memory errorBI1290Alarm 53:10 Supply air fan no. 2B motor controller current reductionBI1296Alarm 54:1 Supply air fan no. 3B com. errorBI1297Alarm 54:2 Supply air fan no. 3B motor controller over currentBI1298Alarm 54:3 Supply air fan no. 3B motor controller under voltageBI1299Alarm 54:4 Supply air fan no. 3B motor controller over voltageBI1300Alarm 54:5 Supply air fan no. 3B motor controller over temperatureBI1301Alarm 54:6 Supply air fan no. 3B motor controller start errorBI1302Alarm 54:7 Supply air fan no. 3B motor controller ripple errorBI1303Alarm 54:8 Supply air fan no. 3B motor controller phase errorBI1304Alarm 54:9 Supply air fan no. 3B motor controller internal memory errorBI1305Alarm 54:10 Supply air fan no. 3B motor controller current reductionBI1311Alarm 55:1 Extract air fan no. 1A com. errorBI1312Alarm 55:2 Extract air fan no. 1A motor controller over currentBI1313Alarm 55:3 Extract air fan no. 1A motor controller under voltageBI1314Alarm 55:4 Extract air fan no. 1A motor controller over voltageBI1315Alarm 55:5 Extract air fan no. 1A motor controller over temperatureBI1316Alarm 55:6 Extract air fan no. 1A motor controller start errorBI1317Alarm 55:7 Extract air fan no. 1A motor controller ripple errorBI1318Alarm 55:8 Extract air fan no. 1A motor controller phase errorBI1319Alarm 55:9 Extract air fan no. 1A motor controller internal memory errorBI1320Alarm 55:10 Extract air fan no. 1A motor controller current reductionBI1321Alarm 55:11 Extract air fan no. 1A motor controller internal com. errorBI1326Alarm 56:1 Extract air fan no. 2A com. errorBI1327Alarm 56:2 Extract air fan no. 2A motor controller over currentBI1328Alarm 56:3 Extract air fan no. 2A motor controller under voltageBI1329Alarm 56:4 Extract air fan no. 2A motor controller over voltageBI1330Alarm 56:5 Extract air fan no. 2A motor controller over temperatureBI1331Alarm 56:6 Extract air fan no. 2A motor controller start errorBI1332Alarm 56:7 Extract air fan no. 2A motor controller ripple errorBI1333Alarm 56:8 Extract air fan no. 2A motor controller phase errorBI1334Alarm 56:9 Extract air fan no. 2A motor controller internal memory errorBI1335Alarm 56:10 Extract air fan no. 2A motor controller current reductionBI1336Alarm 56:11 Extract air fan no. 2A motor controller internal com. errorBI1341Alarm 57:1 Extract air fan no. 3A com. errorBI1342Alarm 57:2 Extract air fan no. 3A motor controller over currentBI1343Alarm 57:3 Extract air fan no. 3A motor controller under voltageBI1344Alarm 57:4 Extract air fan no. 3A motor controller over voltageBI1345Alarm 57:5 Extract air fan no. 3A motor controller over temperatureBI1346Alarm 57:6 Extract air fan no. 3A motor controller start errorBI1347Alarm 57:7 Extract air fan no. 3A motor controller ripple errorBI1348Alarm 57:8 Extract air fan no. 3A motor controller phase errorBI1349Alarm 57:9 Extract air fan no. 3A motor controller internal memory errorBI1350Alarm 57:10 Extract air fan no. 3A motor controller current reductionBI1351Alarm 57:11 Extract air fan no. 3A motor controller internal com. errorBI1356Alarm 58:1 Extract air fan no. 1B com. errorBI1357Alarm 58:2 Extract air fan no. 1B motor controller over currentBI1358Alarm 58:3 Extract air fan no. 1B motor controller under voltageBI1359Alarm 58:4 Extract air fan no. 1B motor controller over voltageBI1360Alarm 58:5 Extract air fan no. 1B motor controller over temperatureBI1361Alarm 58:6 Extract air fan no. 1B motor controller start errorBI1362Alarm 58:7 Extract air fan no. 1B motor controller ripple errorBI1363Alarm 58:8 Extract air fan no. 1B motor controller phase errorBI1364Alarm 58:9 Extract air fan no. 1B motor controller internal memory errorBI1365Alarm 58:10 Extract air fan no. 1B motor controller current reductionBI1371Alarm 59:1 Extract air fan no. 2B com. errorBI1372Alarm 59:2 Extract air fan no. 2B motor controller over currentBI1373Alarm 59:3 Extract air fan no. 2B motor controller under voltageBI1374Alarm 59:4 Extract air fan no. 2B motor controller over voltageBI1375Alarm 59:5 Extract air fan no. 2B motor controller over temperatureBI1376Alarm 59:6 Extract air fan no. 2B motor controller start errorBI1377Alarm 59:7 Extract air fan no. 2B motor controller ripple errorBI1378Alarm 59:8 Extract air fan no. 2B motor controller phase errorBI1379Alarm 59:9 Extract air fan no. 2B motor controller internal memory errorBI1380Alarm 59:10 Extract air fan no. 2B motor controller current reductionBI1386Alarm 60:1 Extract air fan no. 3B com. errorBI1387Alarm 60:2 Extract air fan no. 3B motor controller over currentBI1388Alarm 60:3 Extract air fan no. 3B motor controller under voltageBI1389Alarm 60:4 Extract air fan no. 3B motor controller over voltageBI1390Alarm 60:5 Extract air fan no. 3B motor controller over temperatureBI1391Alarm 60:6 Extract air fan no. 3B motor controller start errorBI1392Alarm 60:7 Extract air fan no. 3B motor controller ripple errorBI1393Alarm 60:8 Extract air fan no. 3B motor controller phase errorBI1394Alarm 60:9 Extract air fan no. 3B motor controller internal memory errorBI1395Alarm 60:10 Extract air fan no. 3B motor controller current reductionBI1401Alarm 61:1 Supply air fan no. 1A I/O-module com. errorBI1406Alarm 61:6 Supply air fan no. 2A I/O-module com. errorBI1411Alarm 61:11 Supply air fan no. 3A I/O-module com. errorBI1416Alarm 62:1 Extract air fan no. 1A I/O-module com. errorBI1421Alarm 62:6 Extract air fan no. 2A I/O-module com. errorBI1426Alarm 62:11 Extract air fan no. 3A I/O-module com. errorBI1431Alarm 63:1 MIRU 1 I/O-module com. errorBI1436Alarm 63:6 MIRU 2 I/O-module com. errorBI1441Alarm 63:11 MIRU 3 I/O-module com. errorBI1446Alarm 64:1 Supply air fan no. 1A common A-alarmBI1448Alarm 64:3 Supply air fan no. 1A common B-alarmBI1450Alarm 64:5 Supply air fan no. 1A common warningBI1451Alarm 64:6 Supply air fan no. 2A common A-alarmBI1453Alarm 64:8 Supply air fan no. 2A common B-alarmBI1455Alarm 64:10 Supply air fan no. 2A common warningBI1456Alarm 64:11 Supply air fan no. 3A common A-alarmBI1458Alarm 64:13 Supply air fan no. 3A common B-alarmBI1460Alarm 64:15 Supply air fan no. 3A common warningBI1461Alarm 65:1 Extract air fan no. 1A common A-alarmBI1463Alarm 65:3 Extract air fan no. 1A common B-alarmBI1465Alarm 65:5 Extract air fan no. 1A common warningBI1466Alarm 65:6 Extract air fan no. 2A common A-alarmBI1468Alarm 65:8 Extract air fan no. 2A common B-alarmBI1470Alarm 65:10 Extract air fan no. 2A common warningBI1471Alarm 65:11 Extract air fan no. 3A common A-alarmBI1473Alarm 65:13 Extract air fan no. 3A common B-alarmBI1475Alarm 65:15 Extract air fan no. 3A common warningBI1536Alarm 70:1 H/C controls com. errorBI1537Alarm 70:2 H/C controls internal memory errorBI1538Alarm 70:3 H/C controls clock circuit defectiveBI1540Alarm 70:5 H/C defrost pressure sensor no. D com. errorBI1541Alarm 70:6 H/C defrost I/O-module no. 5 com. errorBI1542Alarm 70:7 H/C defrost recirculation damper monitoring trippedBI1543Alarm 70:8 H/C defrost electrical heater overheat protection trippedBI1544Alarm 70:9 H/C defrost time above alarm limitBI1546Alarm 70:11 H/C defrost interval above alarm limitBI1547Alarm 70:12 H/C wrong phase sequenceBI1551Alarm 71:1 H/C compressor motor control com. errorBI1552Alarm 71:2 H/C compressor motor control start errorBI1553Alarm 71:3 H/C compressor motor controller over or under voltageBI1554Alarm 71:4 H/C compressor out of operation rangeBI1559Alarm 71:9 H/C expansion valve controller com. errorBI1566Alarm 72:1 H/C high pressure switch trippedBI1567Alarm 72:2 H/C high pressure above alarm limitBI1568Alarm 72:3 H/C thermal switch compressor no. 1 trippedBI1569Alarm 72:4 H/C discharge temperature above alarm limitBI1570Alarm 72:5 H/C discharge temperature sensor defectiveBI1571Alarm 72:6 H/C high pressure sensor defectiveBI1572Alarm 72:7 H/C low pressure sensor defectiveBI1573Alarm 72:8 H/C suction temperature sensor defectiveBI1574Alarm 72:9 H/C pressure difference below alarm limitBI1575Alarm 72:10 H/C maintenance and compressorBI1576Alarm 72:11 H/C superheat temperature below alarm limitBI1577Alarm 72:12 H/C unloading of low pressureBI1578Alarm 72:13 H/C unloading of high pressureBI1579Alarm 72:14 H/C low pressure below alarm limitBI1580Alarm 72:15 H/C thermal switch compressor no. 2 trippedBI1642Alarm 77:2 MIRU 1 motor controller over currentBI1643Alarm 77:3 MIRU 1 motor controller under voltageBI1644Alarm 77:4 MIRU 1 motor controller over voltageBI1645Alarm 77:5 MIRU 1 motor controller over temperatureBI1646Alarm 77:6 MIRU 1 motor controller start errorBI1647Alarm 77:7 MIRU 1 motor controller ripple errorBI1648Alarm 77:8 MIRU 1 motor controller phase errorBI1649Alarm 77:9 MIRU 1 motor controller internal memory errorBI1650Alarm 77:10 MIRU 1 motor controller current reductionBI1651Alarm 77:11 MIRU 1 motor controller internal com. errorBI1657Alarm 78:2 MIRU 2 motor controller over currentBI1658Alarm 78:3 MIRU 2 motor controller under voltageBI1659Alarm 78:4 MIRU 2 motor controller over voltageBI1660Alarm 78:5 MIRU 2 motor controller over temperatureBI1661Alarm 78:6 MIRU 2 motor controller start errorBI1662Alarm 78:7 MIRU 2 motor controller ripple errorBI1663Alarm 78:8 MIRU 2 motor controller phase errorBI1664Alarm 78:9 MIRU 2 motor controller internal memory errorBI1665Alarm 78:10 MIRU 2 motor controller current reductionBI1666Alarm 78:11 MIRU 2 motor controller internal com. errorBI1672Alarm 79:2 MIRU 3 motor controller over currentBI1673Alarm 79:3 MIRU 3 motor controller under voltageBI1674Alarm 79:4 MIRU 3 motor controller over voltageBI1675Alarm 79:5 MIRU 3 motor controller over temperatureBI1676Alarm 79:6 MIRU 3 motor controller start errorBI1677Alarm 79:7 MIRU 3 motor controller ripple errorBI1678Alarm 79:8 MIRU 3 motor controller phase errorBI1679Alarm 79:9 MIRU 3 motor controller internal memory errorBI1680Alarm 79:10 MIRU 3 motor controller current reductionBI1681Alarm 79:11 MIRU 3 motor controller internal com. errorBI1702Alarm 81:2 SMART Link no. 1 supply air flow below defrost alarm limitBI1703Alarm 81:3 SMART Link no. 1 High pressure switch trippedBI1704Alarm 81:4 SMART Link no. 1 High pressure above alarm limitBI1705Alarm 81:5 SMART Link no. 1 Low pressure below alarm limitBI1706Alarm 81:6 SMART Link no. 1 Evaporation temperature below alarm limitBI1707Alarm 81:7 SMART Link no. 1 Inverter group alarm (Power+)BI1708Alarm 81:8 SMART Link no. 1 Envelope alarm.BI1709Alarm 81:9 SMART Link no. 1 Starting up of faulty compressorBI1710Alarm 81:10 SMART Link no. 1 Discharge temperature above alarm limitBI1711Alarm 81:11 SMART Link no. 1 Pressure difference below alarm limitBI1717Alarm 82:2 SMART Link no. 2 supply air flow below defrost alarm limitBI1718Alarm 82:3 SMART Link no. 2 High pressure switch trippedBI1719Alarm 82:4 SMART Link no. 2 High pressure above alarm limitBI1720Alarm 82:5 SMART Link no. 2 Low pressure below alarm limitBI1721Alarm 82:6 SMART Link no. 2 Evaporation temperature below alarm limitBI1722Alarm 82:7 SMART Link no. 2 Inverter group alarm (Power+)BI1723Alarm 82:8 SMART Link no. 2 Envelope alarm.BI1724Alarm 82:9 SMART Link no. 2 Starting up of faulty compressorBI1725Alarm 82:10 SMART Link no. 2 Discharge temperature above alarm limitBI1726Alarm 82:11 SMART Link no. 2 Pressure difference below alarm limitBI1732Alarm 83:2 SMART Link no. 3 supply air flow below defrost alarm limitBI1733Alarm 83:3 SMART Link no. 3 High pressure switch trippedBI1734Alarm 83:4 SMART Link no. 3 High pressure above alarm limitBI1735Alarm 83:5 SMART Link no. 3 Low pressure below alarm limitBI1736Alarm 83:6 SMART Link no. 3 Evaporation temperature below alarm limitBI1737Alarm 83:7 SMART Link no. 3 Inverter group alarm (Power+)BI1738Alarm 83:8 SMART Link no. 3 Envelope alarm.BI1739Alarm 83:9 SMART Link no. 3 Starting up of faulty compressorBI1740Alarm 83:10 SMART Link no. 3 Discharge temperature above alarm limitBI1741Alarm 83:11 SMART Link no. 3 Pressure difference below alarm limitBI1747Alarm 84:2 SMART Link no. 4 supply air flow below defrost alarm limitBI1748Alarm 84:3 SMART Link no. 4 High pressure switch trippedBI1749Alarm 84:4 SMART Link no. 4 High pressure above alarm limitBI1750Alarm 84:5 SMART Link no. 4 Low pressure below alarm limitBI1751Alarm 84:6 SMART Link no. 4 Evaporation temperature below alarm limitBI1752Alarm 84:7 SMART Link no. 4 Inverter group alarm (Power+)BI1753Alarm 84:8 SMART Link no. 4 Envelope alarm.BI1754Alarm 84:9 SMART Link no. 4 Starting up of faulty compressorBI1755Alarm 84:10 SMART Link no. 4 Discharge temperature above alarm limitBI1756Alarm 84:11 SMART Link no. 4 Pressure difference below alarm limitBI1911Info 95:1 Supply air pre filter calibration performed at low air flowBI1912Info 95:2 Extract air pre filter calibration performed at low air flowBI1913Info 95:3 Supply air AHU filter calibration performed at low air flowBI1914Info 95:4 Extract air AHU filter calibration performed at low air flowBI1915Info 95:5 End filter calibration performed at low air flowBI1924Info 95:14 Reduced humidity recovery time above alarm limitBI1925Info 95:15 Supply air humidity level above outdoor air levelBI1926Info 96:1 H/C defrost calibration not performedBI1927Info 96:2 H/C defrost calibration not approvedBI1928Info 96:3 H/C minimum SA flow limit below factory settingBI1929Info 96:4 H/C minimum EA flow limit below factory settingBI1930Info 96:5 H/C OA temp limit for heating below factory settingBI1941Info 97:1 Cloud connection offlineBI1942Info 97:2 Cloud certificate missing/expiredBI1952Info 97:12 Plate heat exchanger bypass optimization not performedBI1953Info 97:13 Plate heat exchanger bypass optimization not approvedBI1954Info 97:14 Plate heat exchanger defrost calibration not performedBI1955Info 97:15 Plate heat exchanger defrost calibration not approvedBI1956Info 98:1 Supply air pre-filter calibration not performedBI1957Info 98:2 Supply air pre-filter calibration not approvedBI1958Info 98:3 Extract air pre-filter calibration not performedBI1959Info 98:4 Extract air pre-filter calibration not approvedBI1960Info 98:5 Supply air air handling unit filter calibration not performedBI1961Info 98:6 Supply air air handling unit filter calibration not approvedBI1962Info 98:7 Extract air air handling unit filter calibration not performedBI1963Info 98:8 Extract air air handling unit filter calibration not approvedBI1964Info 98:9 Supply air end filter calibration not performedBI1965Info 98:10 Supply air end filter calibration not approvedBI1966Info 98:11 Rotary heat exchanger defrost calibration not performedBI1967Info 98:12 Rotary heat exchanger defrost calibration not approvedBI1968Info 98:13 ReCO2 calibration not performedBI1969Info 98:14 ReCO2 calibration not approvedBI1970Info 98:15 ReCO2 incorrect settingBI1971Info 99:1 E-mail errorBI1975Info 99:5 FTP errorBI1976Info 99:6 Schedule invalid data auto correctedBI1977Info 99:7 SD card memory soon full. Oldest log data will soon be deletedBI1978Info 99:8 SD card memory full. Oldest log data deletedBI1979Info 99:9 IQlogic CPU2 reboot caused by corrupt SD card remove and replaceBI1981Info 99:11 No external outdoor air temp. sensor connected for heat retentionBI1982Info 99:12 No extract air/room temperature sensor connectedBI1984Info 99:14 Internal serial memory error CPU 1BI1985Info 99:15 Clock circuit defectiveBI2001Active alarm group 1BI2002Active alarm group 2BI2003Active alarm group 3BI2004Active alarm group 4BI2005Active alarm group 5BI2006Active alarm group 6BI2007Active alarm group 7BI2008Active alarm group 8BI2009Active alarm group 9BI2010Active alarm group 10BI2011Active alarm group 11BI2012Active alarm group 12BI2013Active alarm group 13BI2014Active alarm group 14BI2015Active alarm group 15BI2016Active alarm group 16BI2017Active alarm group 17BI2018Active alarm group 18BI2019Active alarm group 19BI2020Active alarm group 20BI2021Active alarm group 21BI2022Active alarm group 22BI2023Active alarm group 23BI2024Active alarm group 24BI2025Active alarm group 25BI2026Active alarm group 26BI2027Active alarm group 27BI2028Active alarm group 28BI2029Active alarm group 29BI2030Active alarm group 30BI2031Active alarm group 31BI2032Active alarm group 32BI2033Active alarm group 33BI2034Active alarm group 34BI2035Active alarm group 35BI2036Active alarm group 36BI2037Active alarm group 37BI2038Active alarm group 38BI2039Active alarm group 39BI2040Active alarm group 40BI2041Active alarm group 41BI2042Active alarm group 42BI2043Active alarm group 43BI2044Active alarm group 44BI2045Active alarm group 45BI2046Active alarm group 46BI2047Active alarm group 47BI2048Active alarm group 48BI2049Active alarm group 49BI2050Active alarm group 50BI2051Active alarm group 51BI2052Active alarm group 52BI2053Active alarm group 53BI2054Active alarm group 54BI2055Active alarm group 55BI2056Active alarm group 56BI2057Active alarm group 57BI2058Active alarm group 58BI2059Active alarm group 59BI2060Active alarm group 60BI2061Active alarm group 61BI2062Active alarm group 62BI2063Active alarm group 63BI2064Active alarm group 64BI2065Active alarm group 65BI2066Active alarm group 66BI2067Active alarm group 67BI2068Active alarm group 68BI2069Active alarm group 69BI2070Active alarm group 70BI2071Active alarm group 71BI2072Active alarm group 72BI2073Active alarm group 73BI2074Active alarm group 74BI2075Active alarm group 75BI2076Active alarm group 76BI2077Active alarm group 77BI2078Active alarm group 78BI2079Active alarm group 79BI2080Active alarm group 80BI2081Active alarm group 81BI2082Active alarm group 82BI2083Active alarm group 83BI2084Active alarm group 84BI2085Active alarm group 85BI2086Active alarm group 86BI2087Active alarm group 87BI2088Active alarm group 88BI2089Active alarm group 89BI2090Active alarm group 90BI2091Active alarm group 91BI2092Active alarm group 92BI2093Active alarm group 93BI2094Active alarm group 94BI2095Active alarm group 95BI2096Active alarm group 96BI2097Active alarm group 97BI2098Active alarm group 98BI2099Active alarm group 99BI2100Active alarm group 100BO1Booster diffusersBV1Alarm resetBV3Internal fire alarm functionBV29SA flow pressure sensor auto zero calibrationBV30EA flow pressure sensor auto zero calibrationBV31SA duct pressure sensor auto zero calibrationBV32EA duct pressure sensor auto zero calibrationBV33ReCO2 pressure sensor auto zero calibrationBV34RHX defrost pressure sensor auto calibrationBV35Carry over control pressure sensor auto calibrationBV36SA filter pressure sensor auto zero calibrationBV37EA filter pressure sensor auto zero calibrationBV38SA pre-filter pressure sensor auto zero calibrationBV39EA pre-filter pressure sensor auto zero calibrationBV40SA end-filter pressure sensor auto zero calibrationBV41PX heat exchange pressure sensor auto calibrationBV42Air quality control pressure sensor auto calibrationBV43HC defrost sensor auto calibrationBV46SA flow pressure sensor activate zero calibrationBV47EA flow pressure sensor activate zero calibrationBV48SA duct pressure sensor activate zero calibrationBV49EA duct pressure sensor activate zero calibrationBV50ReCO2 pressure sensor activate calibrationBV51RHX Defrost pressure sensor activate calibrationBV52Carry over control pressure sensor activate zero calibrationBV53SA filter pressure sensor activate zero calibrationBV54EA filter pressure sensor activate zero calibrationBV55SA pre-filter pressure sensor activate zero calibrationBV56EA pre-filter pressure sensor activate zero calibrationBV57SA end-filter pressure sensor activate zero calibrationBV58PX heat exchange pressure sensor activate zero calibrationBV59Air quality control pressure sensor activate zero calibrationBV60HC defrost pressure sensor activate zero calibrationBV162External room sensor 1 functionBV163External room sensor 2 functionBV164External room sensor 3 functionBV165External room sensor 4 functionBV167External room temp from BMS functionBV172External OA sensor 1 functionBV173External OA sensor 2 functionBV174External OA sensor 3 functionBV175External OA sensor 4 functionBV177External OA temp from BMS functionBV182RHX defrost functionBV183RHX defrost calibrationBV187RHX carry over control functionBV190RHX min exhaust air temp functionBV198PHX periodic operation of bypass damper functionBV201PX bypass optimizeBV205CHX periodic operation of pump functionBV206CHX periodic operation of valve functionBV228Re-heat periodic operation of pump functionBV229Re-heat periodic operation of valve functionBV245Extra regulation 1 periodic operation of pump functionBV246Extra regulation 1 periodic operation of valve functionBV274Cool relay 1 periodic operation of pump functionBV275Cool relay 2 periodic operation of pump functionBV276Cool periodic operation of valve functionBV296Intermittent night heat functionBV302Intermittent night heat recirculation functionBV305Morning boost functionBV320Heating boost functionBV325Xzone heat functionBV327Xzone cool functionBV374Xzone external room sensor 1 functionBV375Xzone external room sensor 2 functionBV376Xzone external room sensor 3 functionBV377Xzone external room sensor 4 functionBV379Xzone external room temp from BMS functionBV386Xzone reheat periodic operation of pump functionBV387Xzone reheat periodic operation of valve functionBV400Xzone Cool relay 1 periodic operation of pump functionBV401Xzone Cool relay 2 periodic operation of pump functionBV402Xzone Cool periodic operation of valve functionBV410Pre-heat functionBV414Pre-heat periodic operation of pump functionBV415Pre-heat periodic operation of valve functionBV425ReCO2 CalibrationBV459Heat exchange active in dehumidifying sequenceBV477Exhaust heat periodic operation of pump functionBV478Exhaust heat periodic operation of valve functionBV489SMART Link WB Cooling Optimize functionBV490SMART Link WB Heating Optimize functionBV504AQUA Link FunctionBV530AYC Heated water periodic operation of pumpBV531AYC Heated water periodic operation of valveBV536AYC Heated water OA temp compensationBV547AYC Heated water room temp compensation functionBV548AYC Heated water room temp compensation at nightBV553AYC Heated water night temp compensation functionBV579AYC Chilled water periodic operation of pumpBV580AYC Chilled water periodic operation of valveBV585AYC Chilled water OA temp compensationBV596AYC Chilled water room temp compensation functionBV597AYC Chilled water room temp compensation at nightBV602AYC Chilled water night temp compensation functionBV618AYC Chilled water dew point compensation air flow boostBV637Optimize functionBV775Night temp compensation functionBV824Extra regulation 2 periodic operation of pump functionBV825Extra regulation 2 periodic operation of valve functionBV1000External operation I/O-module A, functionBV1001External operation I/O-module A, temp sensor 1 functionBV1002External operation I/O-module A, temp sensor 2 functionBV1003External operation I/O-module A, digital outputBV1004External operation I/O-module B, functionBV1005External operation I/O-module B, temp sensor 1 functionBV1006External operation I/O-module B, temp sensor 2 functionBV1007External operation I/O-module B, digital outputBV1008External operation I/O-module C, functionBV1009External operation I/O-module C, temp sensor 1 functionBV1010External operation I/O-module C, temp sensor 2 functionBV1011External operation I/O-module C, digital outputBV3000External override function, on/offBV3010External override value, Supply air fan, on/offBV3011External override value, Extract air fan, on/offBV3050External override value, Pre-heat relay, on/offBV3060External override value, Reheat relay, on/offBV3070External override value, Xzone heat relay, on/offBV3080External override value, Extra reg. 1 relay 1, on/offBV3081External override value, Extra reg. 1 relay 2, on/offBV3090External override value, Extra reg. 2 relay 1, on/offBV3091External override value, Extra reg. 2 relay 2, on/offBV3100External override value, Cool relay 1, on/offBV3101External override value, Cool relay 2, on/offBV3110External override value, Xzone cool relay 1, on/offBV3111External override value, Xzone cool relay 2, on/offBV3120External override value, COOL DX comp. 1 on/offBV3121External override value, COOL DX comp. 2 on/offBV3130External override value, HC, on/offBV3131External override value, HC cool/heat, on/offBV3132External override value, HC defrost, on/offBV3140External override value, SMART Link WB, on/offBV3141External override value, SMART Link WB, SMART Link WB cool/heat, on/offBV3150External override value, SMART Link DX 1, on/offBV3151External override value, SMART Link DX 1 cool/heat, on/offBV3152External override value, SMART Link DX 2, on/offBV3153External override value, SMART Link DX 2 cool/heat, on/offBV3154External override value, SMART Link DX 3, on/offBV3155External override value, SMART Link DX 3 cool/heat, on/offBV3156External override value, SMART Link DX 4, on/offBV3157External override value, SMART Link DX 4 cool/heat, on/offBV3160External override value, AQUA Link pump, on/offBV3170External override value, Humidifying relay, on/offBV3190External override value, AYC heat pump, on/offBV3191External override value, AYC cool pump, on/offBV3200External override value, AHU damper relay, on/offBV3201External override value, AHU operation relay, on/offBV3210External override value, Booster heat relay, on/offBV3211External override value, Booster cool relay, on/offBV3220External override value, Miru 1 fan, on/offBV3221External override value, Miru 2 fan, on/offBV3222External override value, Miru 3 fan, on/offBV3230External override value, Exhaust heat relay, on/offBV4010External override activate, Supply air fan, on/offBV4011External override activate, Extract air fan, on/offBV4050External override activate, Pre-heat relay, on/offBV4060External override activate, Reheat relay, on/offBV4070External override activate, Xzone heat relay, on/offBV4080External override activate, Extra reg. 1 relay 1, on/offBV4081External override activate, Extra reg. 1 relay 2, on/offBV4090External override activate, Extra reg. 2 relay 1, on/offBV4091External override activate, Extra reg. 2 relay 2, on/offBV4100External override activate, Cool relay 1, on/offBV4101External override activate, Cool relay 2, on/offBV4110External override activate, Xzone cool relay 1, on/offBV4111External override activate, Xzone cool relay 2, on/offBV4120External override activate, COOL DX comp. 1 on/offBV4121External override activate, COOL DX comp. 2 on/offBV4130External override activate, HC, on/offBV4131External override activate, HC cool/heat, on/offBV4132External override activate, HC defrost, on/offBV4140External override activate, SMART Link WB, on/offBV4141External override activate, SMART Link WB, SMART Link WB cool/heat, on/offBV4150External override activate, SMART Link DX 1, on/offBV4151External override activate, SMART Link DX 1 cool/heat, on/offBV4152External override activate, SMART Link DX 2, on/offBV4153External override activate, SMART Link DX 2 cool/heat, on/offBV4154External override activate, SMART Link DX 3, on/offBV4155External override activate, SMART Link DX 3 cool/heat, on/offBV4156External override activate, SMART Link DX 4, on/offBV4157External override activate, SMART Link DX 4 cool/heat, on/offBV4160External override activate, AQUA Link pump, on/offBV4170External override activate, Humidifying relay, on/offBV4190External override activate, AYC heat pump, on/offBV4191External override activate, AYC cool pump, on/offBV4200External override activate, AHU damper relay, on/offBV4201External override activate, AHU operation relay, on/offBV4210External override activate, Booster heat relay, on/offBV4211External override activate, Booster cool relay, on/offBV4220External override activate, Miru 1 fan, on/offBV4221External override activate, Miru 2 fan, on/offBV4222External override activate, Miru 3 fan, on/offBV4230External override activate, Exhaust heat relay, on/offBV5010External override activate, Supply air fan levelBV5011External override activate, Extract air fan levelBV5020External override activate, RX HX levelBV5030External override activate, PX HX damper 3ABV5031External override activate, PX HX damper 1ABV5032External override activate, PX HX bypass 2ABV5033External override activate, PX HX bypass 4ABV5040External override activate, CX HX valveBV5041External override activate, CX HX pump levelBV5050External override activate, Pre-heat levelBV5060External override activate, Reheat levelBV5070External override activate, Xzone heat levelBV5080External override activate, Extra reg. 1 levelBV5090External override activate, Extra reg. 2 levelBV5100External override activate, Cool levelBV5110External override activate, Xzone cool levelBV5130External override activate, HC comp. levelBV5131External override activate, HC defrost recirc. levelBV5132External override activate, HC defrost el. heat levelBV5150External override activate, SMART Link DX 1 comp. levelBV5151External override activate, SMART Link DX 2 comp. levelBV5152External override activate, SMART Link DX 3 comp. levelBV5153External override activate, SMART Link DX 4 comp. levelBV5170External override activate, Humidifying levelBV5180External override activate, ReCO2 recirculation damperBV5181External override activate, ReCO2 outdoor damperBV5190External override activate, AYC heat valve levelBV5191External override activate, AYC cool valve levelBV5220External override activate, Miru 1 fan levelBV5221External override activate, Miru 2 fan levelBV5222External override activate, Miru 3 fan levelBV5230External override activate, Exhaust heat levelCAL0Calendar #1CAL1Calendar #2MI2Application id/AHU TypeMI3Air flow directionMI110PHX bypass typeMI114PHX-2 3D TypeMI115PHX typeMI140Extra regulation sequence 1 coil typeMI142Extra regulation sequence 2 coil typeMI152Re-heat coil typeMI163Cool coil typeMI198Xzone heat, coil typeMI209Xzone cool, coil typeMI224Pre-heat coil typeMI284Exhaust heat coil typeMI320SMART Link, WB cool modeMI591AHU VersionMI592Operation levelMI665Schedule exception invalid dataMI666Calendar 1 invalid dataMI667Calendar 2 invalid dataMI1400H/C modeMI1401H/C defrost accessoryMI1402H/C recirculation defrost activeMI1403H/C defrost activeMI1407H/C heat typeMI1410H/C operation modeMI1411H/C defrost modeMI1412H/C heat/cool modeMO1Boost Supply airMO2Boost Extract airNC0NC 00 A-AlarmNC1NC 01 B-AlarmNC3NC 03 Alarms specified in BACnetNC10NC 10 Info messageNC11NC 11 Events specified in BACnetSCH0Schedule #1MV1SA Fan regulation modeMV2EA Fan regulation modeMV4Internal fire alarm reset functionMV7External fire alarm no. 1 reset functionMV8External fire alarm no. 2 reset functionMV11External alarm no. 1 reset functionMV12External alarm no. 2 reset functionMV15External alarm no. 1 input functionMV16External alarm no. 2 input functionMV53Outdoor temp compensation functionMV78Down regulation functionMV84Fans in operation at fire alarm 1 functionMV87Fans in operation at fire alarm 2 functionMV90Fans in operation at internal fire alarm functionMV95Pre-filter functionMV96Pre-filter calibrationMV101AHU filter functionMV102AHU filter calibrationMV107SA end filter functionMV108SA end filter calibrationMV111Seasonal controlled temperature regulationMV112Seasonal controlled temperature regulation modeMV115Temperature regulation modeMV166External room sensors measurement functionMV176External OA sensors measurement functionMV188RHX sorption rotor functionMV189Rotor typeMV236Extra regulation 1 combi coil output indicationMV237Extra regulation sequence 1 functionMV238Extra regulation sequence 1 output functionMV249Extra regulation 1 combi coil external signal indicationMV250Extra regulation 1 combi coil external signal valueMV251Extra regulation 1 temperature protection functionMV254Season heat functionMV255Season heat manual settingMV261Cool on/off regulation functionMV284Summer night cool functionMV295Summer night cool from communicationMV313Cooling boost functionMV329Xzone temperature regulation modeMV378Xzone external room sensors measurement functionMV390Xzone combi coil module A external signal indicationMV391Xzone combi coil module A output indicationMV392Xzone combi coil module A external signal valueMV395Xzone Cool on/off regulation functionMV405Xzone combi coil module B external signal indicationMV406Xzone combi coil module B output indicationMV407Xzone combi coil module B external signal valueMV423ReCO2-CO2 functionMV424ReCO2 temperature regulation sequence functionMV441Humidifying functionMV442Humidifying sensorMV457DeHumidifying functionMV465VOC sensor functionMV469COOL DX FunctionMV473Constant exhaust air temperature functionMV481SMART Link FunctionMV505AQUA Link Pump alarm functionMV521AYC FunctionMV528AYC Heated water signal monitor function for pumpMV555AYC Heated water night temp compensation time 1 (days)MV562AYC Heated water night temp compensation time 2 (days)MV577AYC Chilled water signal monitor function for pumpMV604AYC Chilled water night temp compensation time 1 (days)MV611AYC Chilled water night temp compensation time 2 (days)MV660MIRU Control 1 functionMV661MIRU Control 2 functionMV662MIRU Control 3 functionMV663MIRU Control 4 functionMV664MIRU Control 5 functionMV665MIRU Control 6 functionMV666MIRU Control 7 functionMV667MIRU Control 8 functionMV668MIRU Control 9 functionMV669MIRU Control 10 functionMV671MIRU Control 1 Balanced air flow functionMV679MIRU Control 2 Balanced air flow functionMV687MIRU Control 3 Balanced air flow functionMV695MIRU Control 4 Balanced air flow functionMV703MIRU Control 5 Balanced air flow functionMV711MIRU Control 6 Balanced air flow functionMV719MIRU Control 7 Balanced air flow functionMV727MIRU Control 8 Balanced air flow functionMV735MIRU Control 9 Balanced air flow functionMV743MIRU Control 10 Balanced air flow functionMV765Heat neutral zone functionMV766Cool neutral zone functionMV777Night temp compensation time 1 (days)MV782Night temp compensation time 2 (days)MV793Communication operation levelMV794Schedule operation levelMV816Extra regulation sequence 2 functionMV817Extra regulation sequence 2 output functionMV828Extra regulation 2 combi coil external signal indicationMV829Extra regulation 2 combi coil external signal valueMV834Extra regulation 2 combi coil output indicationMV850H/C heat modeMV851H/C cool modeMV890Humidifying time 1 (days)MV895Humidifying time 2 (days)MV900Humidifying time 3 (days)MV905Humidifying time 4 (days)
Integration notes
- Built from the EDE file in Swegon's GOLD E/F BACnet zip and checked against the PDF/xlsx object list in the same zip (GOLD_E_F_BACnet_251202). Access W = marked settable in the EDE. AI 181 is in the PDF but missing from the EDE and was added from the PDF; BI 1536 and BV 3230 are in the EDE only.
- One object list covers all RX, PX, CX and SD versions and every accessory; many objects only apply when the related function is fitted.
- The zip also has a variant of the list without the External override objects (instances 3000 and up) for units where that function is not wanted.
- Most alarms are individual BIs named 'Alarm <group>:<number> ...'; BI 13 and BI 14 summarize A- and B-class alarms.
- Where the EDE and PDF names differ, the EDE (device) name is used: the PDF calls AI 739-746 'Pulse counter input n kWh/MWh' and AV 519 'SMART Link OA temp limit'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
How many BACnet points does the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 have?
This list has 2163 BACnet objects: 496 analog inputs, 1 analog output, 486 analog values, 815 binary inputs, 1 binary output, 225 binary values, 2 calendars, 27 multi-state inputs, 2 multi-state outputs, 5 notification classs, 1 schedule, 102 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 BACnet points are writable?
817 of the 2163 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48 BACnet documentation?
The source is BACnet IP GOLD RX/PX/CX/SD, Generation E/F (with EDE, PICS and state/unit files) (GOLD_E_F_BACnet_251202 (Swegon doc 9307)), revision 2025-12-02, published free by Swegon at https://www.swegon.com/globalassets/digizuite/9307-en-gold_e_bacnet_pv110_other_en.zip.
What are the minimum BACnet points to integrate the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48?
Start with MV 793 Communication operation level (BMS start/stop and speed command); AV 132 SA temperature set point (Supply air temperature setpoint); AV 135 EA/Room temperature set point (Extract/room temperature setpoint); BV 1 Alarm reset (Resets all active alarms); MI 592 Operation level (Actual operating state and who stopped the unit); AI 64 SA Temperature (Supply air temperature); AI 66 EA Temperature (Extract air temperature); AI 73 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 13 A-alarm active (Any A-class alarm); BI 14 B-alarm active (Any B-class alarm).
How do I enable BMS control of the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48?
MV 793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI 592 shows whether a stop or speed came from communication, the hand terminal, a digital input, the time channel or an alarm.
Can the BMS supply sensor values to the Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48?
Room temperature can come from the BMS: enable BV 167 'External room temp from BMS function' and write AV 168; outdoor temperature likewise via BV 177 and AV 178. Each has an alarm-time AV in minutes (AV 169, AV 179). Xzone has its own BMS room temperature (BV 379, AV 380, AV 381).
How do I check these points on the real GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
- Air handling unit controller
Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
Swegon COMPACT and GOLD LP air handling units with controller program version 2.01 or later.
Also known as: COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480 - Air handling unit controller
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation C and D (RX, PX, CX and SD versions, built about 2010-2013) running program version 6.08 or later.
Also known as: GOLD C, GOLD D, GOLD RX, GOLD PX, GOLD CX, GOLD SD, GOLD version D, GB.BACnet480.121017, BACnet480 - Air handling unit controller
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation E (RX, PX, CX and SD versions) running program version 1.10 or later.
Also known as: GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316 - Other equipment (demand-controlled ventilation system controller)
Swegon SuperWISE (generation 1) BACnet IP - system objects
Swegon SuperWISE (first generation) system controllers for WISE demand-controlled ventilation, program version 1.25.
Also known as: SuperWISE, Super WISE, WISE gen 1, GB.BACnetSuper WISE.140603, SuperWISE_BACnet_list_ver_1.3
Source: BACnet IP GOLD RX/PX/CX/SD, Generation E/F (with EDE, PICS and state/unit files) · GOLD_E_F_BACnet_251202 (Swegon doc 9307) · rev. 2025-12-02. Object names, instances and units are reproduced as published; descriptions are our own.