Air handling unit controller · BACnet points list

Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points list

Updated 28 October 2026

Short answer

The built-in IQlogic controller in Swegon GOLD generation E air handlers is a native BACnet IP device (B-AAC profile) with no gateway needed. It publishes over 1,400 objects: fan airflow/pressure readings and setpoints, temperatures and regulation levels, heat-exchanger and coil data, accessory functions (Xzone, SMART Link, AYC, MIRU, COOL DX), one binary input per alarm, plus calendars, a schedule and notification classes for intrinsic alarming. The unit is started, stopped and speed-selected from the BMS through a single multistate value.

This page lists 1452 BACnet objects for the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP — 525 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.

Manufacturer
Swegon
Model
GOLD generation E (RX/PX/CX/SD) BACnet IP
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
1452 (525 writable)
Transport
BACnet IP
Firmware
Program version 1.10 or later (driver in PV 1.16)
Also known as
GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316
Source document
BACnet IP GOLD RX/PX/CX/SD, Generation E · GOLD_E_BACnet_150316 · rev. 2015-03-16
Download CSV 1452 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP

Integration in brief

Command the unit with MV-793 Communication operation level (Auto lets the internal time channel run it; other states force stop, low or high speed) and read back MI-592 Operation level plus the low/high speed BIs. Adjust the main temperature setpoints (AV-132 supply, AV-135 extract/room) and airflow or pressure setpoints for low and high speed, and monitor BI-13/14 for A/B alarms with BV-1 to reset. The object summary on page 3 of the source lists these as the key points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 793Communication operation levelBMS start/stop and speed commandWrite
AV 132SA temperature set pointSupply air temperature setpointWrite
AV 135EA/Room temperature set pointExtract/room temperature setpointWrite
BV 1Alarm resetResets all active alarmsWrite
MI 592Operation levelActual operating state and who stopped the unitRead
AI 64SA TemperatureSupply air temperatureRead
AI 66EA TemperatureExtract air temperatureRead
AI 73Outdoor temperatureOutdoor air temp measured by the unit, °CRead
BI 13A-alarm activeAny A-class alarmRead
BI 14B-alarm activeAny B-class alarmRead

Enable & remote start

MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.

Sensors & values from the BMS

Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).

Network setup

Watch out for

Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

1452 of 1452 shown
Type
Access
Show
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet Points List
DescriptionStates
AI1Component nameRead25=IQlogic
AI4SA Air flowPresent supply air flow.l/sRead
AI5SA Air flow regulatorPresent supply air flow regulator set point.l/sRead
AI6EA Air flowPresent extract air flow.l/sRead
AI7EA Air flow regulatorPresent extract air flow regulator set point.l/sRead
AI8SA Duct pressurePresent supply air duct pressure.PaRead
AI9SA Duct pressure regulatorPresent supply air duct pressure regulator set point.PaRead
AI10EA Duct pressurePresent extract air duct pressure.PaRead
AI11EA Duct pressure regulatorPresent extract air duct pressure regulator set point.PaRead
AI12Demand input levelPresent input signal for demand regulation.%Read
AI13Demand regulatorPresent demand regulator set point.%Read
AI14SA Air flow pressurePresent air flow pressure in the supply air fan inlet.PaRead
AI15EA Air flow pressurePresent air flow pressure in the extract air fan inlet.PaRead
AI23SA Pre-filter pressure levelPresent supply air pre-filter pressure drop.PaRead
AI24SA Pre-filter pressure alarm limitPresent supply air pre-filter pressure alarm limit.PaRead
AI25EA Pre-filter pressure levelPresent extract air pre-filter pressure drop.PaRead
AI26EA Pre-filter pressure alarm limitPresent extract air pre-filter pressure alarm limit.PaRead
AI27SA AHU filter pressure levelPresent supply air filter pressure drop.PaRead
AI28SA AHU filter pressure alarm limitPresent supply air filter pressure alarm limit.PaRead
AI29EA AHU filter pressure levelPresent extract air filter pressure drop.PaRead
AI30EA AHU filter pressure alarm limitPresent extract air filter pressure alarm limit.PaRead
AI31SA End-filter pressure levelPresent supply air end-filter pressure drop.PaRead
AI32SA End-filter pressure alarm limitPresent supply air end-filter pressure alarm limit.PaRead
AI37SA Fan levelPresent fan speed level of the supply air fan.%Read
AI38EA Fan levelPresent fan speed level of the extract air fan.%Read
AI39SA Fan speedPresent fan speed level of the supply air fan.rpmRead
AI40EA Fan speedPresent fan speed level of the extract air fan.rpmRead
AI41SA VoltagePresent voltage level of the supply air fan.VRead
AI42EA VoltagePresent voltage level of the extract air fan.VRead
AI43SA Fan currentPresent current level of the supply air fans.ARead
AI44EA Fan currentPresent current level of the extract air fans.ARead
AI45SA Fan powerPresent power level of the supply air fans.kWRead
AI46EA Fan powerPresent power consumption level of the extract air fans.kWRead
AI47SA Fan kWhTotal power consumption of the supply air fans.kWhRead
AI48EA Fan kWhTotal power consumption level of the extract air fans.kWhRead
AI49SA Fan MWhTotal power consumption of the supply air fans.MWhRead
AI50EA Fan MWhTotal power consumption level of the extract air fans.MWhRead
AI51SA Fan operation timeTotal operation time of the supply air fan presented in days (24h).daysRead
AI52EA Fan operation timeTotal operation time of the extract air fan presented in days (24h).daysRead
AI55SA Fan min air flowSupply air AHU min air flowl/sRead
AI56EA Fan min air flowExtract air AHU min air flowl/sRead
AI57SA Fan max air flowSupply air AHU max air flowl/sRead
AI58EA Fan max air flowExtract air AHU max air flowl/sRead
AI63SFPCalculated SFP level.kW/m3/sRead
AImin64SA TemperaturePresent supply air temperature.°CRead
AI65SA-D TemperaturePresent supply air density temperature.°CRead
AImin66EA TemperaturePresent extract air temperature in the unit.°CRead
AI67EA-D TemperaturePresent extract air density temperature.°CRead
AI68EA Regulation temperaturePresent extract air temperature used for regulation.°CRead
AI69EA Temperature PX/CXPresent extract air temperature in the unit (only AHU type PX/CX).°CRead
AI70EA Temperature SDPresent extract air temperature in the unit (only AHU type SD).°CRead
AI72Outdoor temperature COOL DXPresent outdoor air temperature in the COOL DX unit.°CRead
AImin73Outdoor temperaturePresent outdoor air temperature in the unit.°CRead
AI74Outdoor regulation temperaturePresent outdoor air temperature used for regulation.°CRead
AI75External outdoor temperature 1Present external outdoor temperature of sensor 1.°CRead
AI76External outdoor temperature 2Present external outdoor temperature of sensor 2.°CRead
AI77External outdoor temperature 3Present external outdoor temperature of sensor 3.°CRead
AI78External outdoor temperature 4Present external outdoor temperature of sensor 4.°CRead
AI79External outdoor temperature min/max/averagePresent calculated min, max or average°CRead
AI80EA Duct temperaturePresent extract air duct air temperature.°CRead
AI81Room temperature 1Present room temperature of sensor 1.°CRead
AI82Room temperature 2Present room temperature of sensor 2.°CRead
AI83Room temperature 3Present room temperature of sensor 3.°CRead
AI84Room temperature 4Present room temperature of sensor 4.°CRead
AI85Room temperature min/max/averagePresent calculated min, max or average°CRead
AI87SA Temp regulatorPresent supply air temperature regulator set point.°CRead
AI88EA Temp regulatorPresent extract air temperature regulator set point.°CRead
AI90Cool exchanger regulator levelPresent operation level of cool recovery.%Read
AI91Heat exchanger regulator levelPresent operation level of heat recovery.%Read
AI92Extra regulation sequence 1 heat regulator levelPresent level of extra regulation heat.%Read
AI93Extra regulation sequence 1 heat output level%Read
AI94Reheat regulator levelPresent level of reheat.%Read
AI95Reheat output level%Read
AI96ReCO2 heat levelPresent level of ReCO2 heat.%Read
AI97Down regulation levelPresent level of fan down regulation.%Read
AI98Heating boost levelPresent level of heating boost.%Read
AI99Extra regulation sequence 1 cool regulator levelPresent level of extra regulation cool.%Read
AI100Extra regulation sequence 1 cool output levelPresent level of extra regulation cool.%Read
AI101Cool regulator levelPresent level of cooling.%Read
AI102Cool output levelPresent level of cooling.%Read
AI103ReCO2 cool levelPresent level of ReCO2 heat.%Read
AI104Cooling boost levelPresent level of cooling boost.%Read
AI105RHX operation levelPresent speed level of the rotary heat exchanger.%Read
AI106RHX efficiencyCalculated level of rotary heat exchanger efficiency.%Read
AI107RHX defrost pressure levelPresent pressure drop for the rotary heat exchanger.PaRead
AI108RHX defrost pressure alarm limitPresent pressure drop alarm limit for thePaRead
AI109RHX carry over control pressure levelPresent pressure difference for the rotary heat exchangers purging sector.PaRead
AI111RHX operation timeTotal operation time of the rotary heat exchanger presented in days (24h).DaysRead
AI116PX defrost pressure levelPHX-2/3: Present pressure drop for the plate heat exchanger.PaRead
AI117PHX-3D Bypass outputPHX-1: Present level of plate heat exchanger bypass output.%Read
AI118PHX-3D Bypass inputPHX-1: Present level of plate heat exchanger bypass input.%Read
AI119PHX-3D Bypass temperature 1PHX-1: Present bypass temperature sensor 1 in plate heat exchanger.°CRead
AI120PHX-3D Bypass temperature 2PHX-1: Present bypass temperature sensor 2 in plate heat exchanger.°CRead
AI121PX exchanger damper 1 outputPHX-2: Present level of plate heat exchanger damper 1 output.%Read
AI122PHX-2 Damper 1 inputPresent level of plate heat exchanger damper 1 input.%Read
AI123PX exchanger damper 2 outputPHX-2: Present level of plate heat exchanger damper 2 output.%Read
AI124PHX-2 Damper 2 inputPresent level of plate heat exchanger damper 2 input.%Read
AI125PX exchanger bypass outputPHX-2: Present level of plate heat exchanger bypass output.%Read
AI126PX exchanger bypass feedbackPHX-2: Present level of plate heat exchanger bypass input.%Read
AI127CHX Valve outputPresent level of coil heat exchanger valve output.%Read
AI128CHX Valve inputPresent level of coil heat exchanger valve input.%Read
AI129CHX Return water temperaturePresent return water temperature for coil heat exchanger.°CRead
AI130PHX/CHX operation timeTotal operation time of the coil heat exchanger presented in days (24h).DaysRead
AI132PHX-1D Bypass outputPHX-3: Present level of plate heat exchanger bypass output.%Read
AI133PHX-1D Bypass inputPHX-3: Present level of plate heat exchanger bypass input.%Read
AI136PHX/CHX Humidity levelPHX-1/2: Present level of air-humidity for calculation of bypass/valve%Read
AI141Extra regulation sequence 1 anti frost temp/overheat inputPresent extra regulation anti frost temperature for water°CRead
AI143Extra regulation sequence 2 anti frost temp/overheat inputPresent extra regulation anti frost temperature for water°CRead
AI146Extra regulation sequence 1 input level%Read
AI147Extra regulation sequence 1 heat operation timeTotal operation time of extra regulation heat presented in days (24h).DaysRead
AI148Extra regulation sequence 1 cool operation timeTotal operation time of extra regulation cool presented in days (24h).DaysRead
AI149Extra regulation sequence 2 input level%Read
AI150Extra regulation sequence 2 heat operation timeTotal operation time of extra regulation heat presented in days (24h).DaysRead
AI151Extra regulation sequence 2 cool operation timeTotal operation time of extra regulation cool presented in days (24h).DaysRead
AI153Re-heat anti frost temp/overheat inputPresent anti frost temperature for water°CRead
AI158Re-heat input level%Read
AI159Re-heat operation timeTotal operation time of re-heat presented in days (24h).DaysRead
AI164Cool water temperaturePresent cool water temperature for water cool coil.°CRead
AI168Cool input level%Read
AI169Cool operation timeTotal operation time of cool presented in days (24h).DaysRead
AI174Xzone SA temperaturePresent supply air temperature.°CRead
AI175Xzone EA temperaturePresent extract air temperature in the unit.°CRead
AI176Xzone EA regulation temperaturePresent extract air temperature used for regulation.°CRead
AI177Xzone Room temperature 1Present room temperature of sensor 1.°CRead
AI178Xzone Room temperature 2Present room temperature of sensor 2.°CRead
AI179Xzone Room temperature 3Present room temperature of sensor 3.°CRead
AI180Xzone Room temperature 4Present room temperature of sensor 4.°CRead
AI181Xzone Room temperature min/max/averagePresent calculated min, max or average°CRead
AI186Xzone SA Temp regulatorPresent supply air temperature regulator set point.°CRead
AI187Xzone EA Temp regulatorPresent extract air temperature regulator set point.°CRead
AI190Xzone re-heat regulator level%Read
AI193Xzone cool regulator level%Read
AI199Xzone heat, anti frost temp/overheat inputPresent Xzone heat anti frost temperature for water°CRead
AI203Xzone heat, output levelPresent level of Xzone heat output.%Read
AI204Xzone heat, input levelPresent Xzone heat input.%Read
AI205Xzone heat, operation timeTotal operation time of Xzone heat presented in days (24h).DaysRead
AI210Xzone cool, water temperature°CRead
AI214Xzone cool, output levelPresent level of Xzone cool.%Read
AI215Xzone cool, input levelPresent Xzone cool valve position.%Read
AI216Xzone cool, operation timeTotal operation time of Xzone cool presented in days (24h).DaysRead
AI220Pre-heat temperaturePresent pre-heat temperature.°CRead
AI221Pre-heat temp regulator set pointPresent pre-heat temperature regulator set point.°CRead
AI222Pre-heat temp regulator levelRead
AI225Pre-heat anti frost temp/overheat inputPresent pre-heat anti frost temperature for water°CRead
AI228Pre-heat output levelPresent pre-heat output level.%Read
AI229Pre-heat input levelPresent pre-heat input level.%Read
AI230Pre-heat operation timeTotal operation time of pre-heat presented in days (24h).DaysRead
AI233ReCO2 recirculation damper outputPresent output signal to the recirculation damper.%Read
AI234ReCO2 recirculation damper inputPresent input signal from the recirculation damper.%Read
AI235ReCO2 outdoor damper outputPresent output signal to the outdoor air damper.%Read
AI236ReCO2 outdoor damper inputPresent input signal from the outdoor air damper.%Read
AI237ReCO2 outdoor air flowPresent outdoor air flow level.l/sRead
AI238ReCO2 outdoor air flow regulator set pointPresent outdoor air flow regulator set point.l/sRead
AI244SA humidity levelPresent level of supply air humidity%RHRead
AI245SA humidity temperaturePresent temperature inside the supply air humidity sensor.°CRead
AI246SA dew pointCalculated supply air dew point.°CRead
AI247EA humidity levelPresent level of extract air humidity.%RHRead
AI248EA humidity temperaturePresent temperature inside the extract air humidity sensor.°CRead
AI249EA dew pointCalculated extract air dew point.°CRead
AI251Dehumidifying SA dew point regulator set pointPresent supply air dew point regulator point.°CRead
AI252Dehumidifying output levelPresent level of the dehumidifying output.%Read
AI254Humidifying SA regulator set point%RHRead
AI255Humidifying output levelPresent level of the dehumidifying output.%Read
AI266VOC levelPresent level of VOCppmRead
AI271COOL DX, unit power sizeRead
AI274COOL DX, compressor 1 low pressure levelBarRead
AI275COOL DX, compressor 1 high pressure levelBarRead
AI276COOL DX, compressor 2 low pressure levelBarRead
AI277COOL DX, compressor 2 high pressure levelBarRead
AI289SMART Link, WB outlet water 1°CRead
AI290SMART Link, WB outlet water 2°CRead
AI291SMART Link, WB outlet water 3°CRead
AI292SMART Link, WB outlet water 4°CRead
AI293SMART Link, WB outlet water average°CRead
AI294SMART Link, WB return water°CRead
AI297SMART Link WB, heated water set point°CRead
AI298SMART Link WB, chilled water set point°CRead
AI299SMART Link WB, Min heated water set point°CRead
AI300SMART Link WB, Max heated water set point°CRead
AI301SMART Link WB, Min chilled water set point°CRead
AI302SMART Link WB, Max chilled water set point°CRead
AI327SMART Link, DX unit 1 power level set point%Read
AI328SMART Link, DX unit 1 power level%Read
AI329SMART Link, DX unit 1 operation timeDaysRead
AI338SMART Link, DX unit 2 power level set point%Read
AI339SMART Link, DX unit 2 power level%Read
AI340SMART Link, DX unit 2 operation timeDaysRead
AI349SMART Link, DX unit 3 power level set point%Read
AI350SMART Link, DX unit 3 power level%Read
AI351SMART Link, DX unit 3 operation timeDaysRead
AI360SMART Link, DX unit 4 power level set point%Read
AI361SMART Link, DX unit 4 power level%Read
AI362SMART Link, DX unit 4 operation timeDaysRead
AI374AYC Heat, heated waterPresent heat temperature.°CRead
AI375AYC Heated water set pointPresent heat temperature regulator set point.°CRead
AI376AYC Heat, valve outputPresent level of the heat valve output.%Read
AI377AYC Heat, valve inputPresent level of the heat valve input.%Read
AI378AYC Heat, operation timeTotal operation time of AYC heat presented in days (24h).DaysRead
AI379AYC Heated water heat demand%Read
AI387AYC Cool, chilled waterPresent cool temperature.°CRead
AI388AYC Chilled water set pointPresent cool temperature regulator set point.°CRead
AI389AYC Cool, valve outputPresent cool of the heat valve output.%Read
AI390AYC Cool, valve inputPresent cool of the heat valve input.%Read
AI391AYC Cool, operation timeTotal operation time of AYC cool presented in days (24h).DaysRead
AI392AYC Chilled water cool demand%Read
AI400MIRU Control 1 Min air flowMin possible air flow settingl/sRead
AI401MIRU Control 1 Max air flowMax possible air flow settingl/sRead
AI402MIRU Control 1 Air flowPresent air flow.l/sRead
AI403MIRU Control 1 Air flow set pointPresent air flow regulator set point.l/sRead
AI404MIRU Control 1 PressurePresent duct pressure.PaRead
AI405MIRU Control 1 Pressure set pointPresent duct pressure regulator set point.PaRead
AI406MIRU Control 1 External temperaturePresent external temperature.°CRead
AI407MIRU Control 1 Operation timePresent operation time, present in days (24h).DaysRead
AI408MIRU Control 1 Fan levelPresent running level of the fan.%Read
AI409MIRU Control 1 Fan powerPresent power consumption level of the fan.WRead
AI410MIRU Control 1 SFPPresent SFP value.kW/m3/sRead
AI411MIRU Control 1 kWhkWh value.kWhRead
AI412MIRU Control 1 MWhMWh value.MWhRead
AI417MIRU Control 2 Min air flowMin possible air flow settingl/sRead
AI418MIRU Control 2 Max air flowMax possible air flow settingl/sRead
AI419MIRU Control 2 Air flowPresent air flow.l/sRead
AI420MIRU Control 2 Air flow set pointPresent air flow regulator set point.l/sRead
AI421MIRU Control 2 PressurePresent duct pressure.PaRead
AI422MIRU Control 2 Pressure set pointPresent duct pressure regulator set point.PaRead
AI423MIRU Control 2 External temperaturePresent external temperature.°CRead
AI424MIRU Control 2 Operation timePresent operation time, present in days (24h).DaysRead
AI425MIRU Control 2 Fan levelPresent running level of the fan.%Read
AI426MIRU Control 2 Fan powerPresent power consumption level of the fan.WRead
AI427MIRU Control 2 SFPPresent SFP value.kW/m3/sRead
AI428MIRU Control 2 kWhkWh value.kWhRead
AI429MIRU Control 2 MWhMWh value.MWhRead
AI434MIRU Control 3 Min air flowMin possible air flow settingl/sRead
AI435MIRU Control 3 Max air flowMax possible air flow settingl/sRead
AI436MIRU Control 3 Air flowPresent air flow.l/sRead
AI437MIRU Control 3 Air flow set pointPresent air flow regulator set point.l/sRead
AI438MIRU Control 3 PressurePresent duct pressure.PaRead
AI439MIRU Control 3 Pressure set pointPresent duct pressure regulator set point.PaRead
AI440MIRU Control 3 External temperaturePresent external temperature.°CRead
AI441MIRU Control 3 Operation timePresent operation time, present in days (24h).DaysRead
AI442MIRU Control 3 Fan levelPresent running level of the fan.%Read
AI443MIRU Control 3 Fan powerPresent power consumption level of the fan.WRead
AI444MIRU Control 3 SFPPresent SFP value.kW/m3/sRead
AI445MIRU Control 3 kWhkWh value.kWhRead
AI446MIRU Control 3 MWhMWh value.MWhRead
AI451MIRU Control 4 Min air flowMin possible air flow settingl/sRead
AI452MIRU Control 4 Max air flowMax possible air flow settingl/sRead
AI453MIRU Control 4 Air flowPresent air flow.l/sRead
AI454MIRU Control 4 Air flow set pointPresent air flow regulator set point.l/sRead
AI455MIRU Control 4 PressurePresent duct pressure.PaRead
AI456MIRU Control 4 Pressure set pointPresent duct pressure regulator set point.PaRead
AI457MIRU Control 4 External temperaturePresent external temperature.°CRead
AI458MIRU Control 4 Operation timePresent operation time, present in days (24h).DaysRead
AI459MIRU Control 4 Fan levelPresent running level of the fan.%Read
AI460MIRU Control 4 Fan powerPresent power consumption level of the fan.WRead
AI461MIRU Control 4 SFPPresent SFP value.kW/m3/sRead
AI462MIRU Control 4 kWhkWh value.kWhRead
AI463MIRU Control 4 MWhMWh value.MWhRead
AI468MIRU Control 5 Min air flowMin possible air flow settingl/sRead
AI469MIRU Control 5 Max air flowMax possible air flow settingl/sRead
AI470MIRU Control 5 Air flowPresent air flow.l/sRead
AI471MIRU Control 5 Air flow set pointPresent air flow regulator set point.l/sRead
AI472MIRU Control 5 PressurePresent duct pressure.PaRead
AI473MIRU Control 5 Pressure set pointPresent duct pressure regulator set point.PaRead
AI474MIRU Control 5 External temperaturePresent external temperature.°CRead
AI475MIRU Control 5 Operation timePresent operation time, present in days (24h).DaysRead
AI476MIRU Control 5 Fan levelPresent running level of the fan.%Read
AI477MIRU Control 5 Fan powerPresent power consumption level of the fan.WRead
AI478MIRU Control 5 SFPPresent SFP value.kW/m3/sRead
AI479MIRU Control 5 kWhkWh value.kWhRead
AI480MIRU Control 5 MWhMWh value.MWhRead
AI485MIRU Control 6 Min air flowMin possible air flow settingl/sRead
AI486MIRU Control 6 Max air flowMax possible air flow settingl/sRead
AI487MIRU Control 6 Air flowPresent air flow.l/sRead
AI488MIRU Control 6 Air flow set pointPresent air flow regulator set point.l/sRead
AI489MIRU Control 6 PressurePresent duct pressure.PaRead
AI490MIRU Control 6 Pressure set pointPresent duct pressure regulator set point.PaRead
AI491MIRU Control 6 External temperaturePresent external temperature.°CRead
AI492MIRU Control 6 Operation timePresent operation time, present in days (24h).DaysRead
AI493MIRU Control 6 Fan levelPresent running level of the fan.%Read
AI494MIRU Control 6 Fan powerPresent power consumption level of the fan.WRead
AI495MIRU Control 6 SFPPresent SFP value.kW/m3/sRead
AI496MIRU Control 6 kWhkWh value.kWhRead
AI497MIRU Control 6 MWhMWh value.MWhRead
AI502MIRU Control 7 Min air flowMin possible air flow settingl/sRead
AI503MIRU Control 7 Max air flowMax possible air flow settingl/sRead
AI504MIRU Control 7 Air flowPresent air flow.l/sRead
AI505MIRU Control 7 Air flow set pointPresent air flow regulator set point.l/sRead
AI506MIRU Control 7 PressurePresent duct pressure.PaRead
AI507MIRU Control 7 Pressure set pointPresent duct pressure regulator set point.PaRead
AI508MIRU Control 7 External temperaturePresent external temperature.°CRead
AI509MIRU Control 7 Operation timePresent operation time, present in days (24h).DaysRead
AI510MIRU Control 7 Fan levelPresent running level of the fan.%Read
AI511MIRU Control 7 Fan powerPresent power consumption level of the fan.WRead
AI512MIRU Control 7 SFPPresent SFP value.kW/m3/sRead
AI513MIRU Control 7 kWhkWh value.kWhRead
AI514MIRU Control 7 MWhMWh value.MWhRead
AI519MIRU Control 8 Min air flowMin possible air flow settingl/sRead
AI520MIRU Control 8 Max air flowMax possible air flow settingl/sRead
AI521MIRU Control 8 Air flowPresent air flow.l/sRead
AI522MIRU Control 8 Air flow set pointPresent air flow regulator set point.l/sRead
AI523MIRU Control 8 PressurePresent duct pressure.PaRead
AI524MIRU Control 8 Pressure set pointPresent duct pressure regulator set point.PaRead
AI525MIRU Control 8 External temperaturePresent external temperature.°CRead
AI526MIRU Control 8 Operation timePresent operation time, present in days (24h).DaysRead
AI527MIRU Control 8 Fan levelPresent running level of the fan.%Read
AI528MIRU Control 8 Fan powerPresent power consumption level of the fan.WRead
AI529MIRU Control 8 SFPPresent SFP value.kW/m3/sRead
AI530MIRU Control 8 kWhkWh value.kWhRead
AI531MIRU Control 8 MWhMWh value.MWhRead
AI536MIRU Control 9 Min air flowMin possible air flow settingl/sRead
AI537MIRU Control 9 Max air flowMax possible air flow settingl/sRead
AI538MIRU Control 9 Air flowPresent air flow.l/sRead
AI539MIRU Control 9 Air flow set pointPresent air flow regulator set point.l/sRead
AI540MIRU Control 9 PressurePresent duct pressure.PaRead
AI541MIRU Control 9 Pressure set pointPresent duct pressure regulator set point.PaRead
AI542MIRU Control 9 External temperaturePresent external temperature.°CRead
AI543MIRU Control 9 Operation timePresent operation time, present in days (24h).DaysRead
AI544MIRU Control 9 Fan levelPresent running level of the fan.%Read
AI545MIRU Control 9 Fan powerPresent power consumption level of the fan.WRead
AI546MIRU Control 9 SFPPresent SFP value.kW/m3/sRead
AI547MIRU Control 9 kWhkWh value.kWhRead
AI548MIRU Control 9 MWhMWh value.MWhRead
AI553MIRU Control 10 Min air flowMin possible air flow settingl/sRead
AI554MIRU Control 10 Max air flowMax possible air flow settingl/sRead
AI555MIRU Control 10 Air flowPresent air flow.l/sRead
AI556MIRU Control 10 Air flow set pointPresent air flow regulator set point.l/sRead
AI557MIRU Control 10 PressurePresent duct pressure.PaRead
AI558MIRU Control 10 Pressure set pointPresent duct pressure regulator set point.PaRead
AI559MIRU Control 10 External temperaturePresent external temperature.°CRead
AI560MIRU Control 10 Operation timePresent operation time, present in days (24h).DaysRead
AI561MIRU Control 10 Fan levelPresent running level of the fan.%Read
AI562MIRU Control 10 Fan powerPresent power consumption level of the fan.WRead
AI563MIRU Control 10 SFPPresent SFP value.kW/m3/sRead
AI564MIRU Control 10 kWhkWh value.kWhRead
AI565MIRU Control 10 MWhMWh value.MWhRead
AI570IQlogic software versionPresent controller software versionRead
AI604Triggered alarm #1((Alarm group - 1) x 15) + alarm number in group=Triggered alarmRead
AI605Triggered alarm #2Read
AI606Triggered alarm #3Read
AI607Triggered alarm #4Read
AI608Triggered alarm #5Read
AI609Triggered alarm #6Read
AI610Triggered alarm #7Read
AI611Triggered alarm #8Read
AI612Triggered alarm #9Read
AI613Triggered alarm #10Read
AI614Triggered alarm group #1Zero if no triggered alarm group.Read
AI615Triggered alarm group #2Read
AI616Triggered alarm group #3Read
AI617Triggered alarm group #4Read
AI618Triggered alarm group #5Read
AI619Triggered alarm group #6Read
AI620Triggered alarm group #7Read
AI621Triggered alarm group #8Read
AI622Triggered alarm group #9Read
AI623Triggered alarm group #10Read
AO1Extract air start upExtract air start up flow.l/sWrite
AV3SA low speed air flow set pointSupply air flow set point for the unit when running in lowl/sWrite
AV4EA low speed air flow set pointExtract air flow set point for the unit when running in lowl/sWrite
AV5SA high speed air flow set pointSupply air flow set point for the unit when running in highl/sWrite
AV6EA high speed air flow set pointExtract air flow set point for the unit when running in highl/sWrite
AV7SA max speed air flow set pointSupply air flow max. limit for the unit when the low/high speedl/sWrite
AV8EA max speed air flow set pointExtract air flow max. limit for the unit when the low/high speedl/sWrite
AV9SA regulation zoneSupply air flow regulation zone setting in % of the present air%Write
AV10EA regulation zoneExtract air flow regulation zone setting in % of the present air%Write
AV11SA regulation I-timeSupply air flow regulator affection setting.sWrite
AV12EA regulation I-timeExtract air flow regulator affection setting.sWrite
AV19SA low speed pressure set pointSupply air duct pressure set point for the unit when running inPaWrite
AV20EA low speed pressure set pointExtract air duct pressure set point for the unit when running inPaWrite
AV21SA high speed pressure set pointSupply air duct pressure for the unit when running in high speedPaWrite
AV22EA high speed pressure set pointExtract air duct pressure set point for the unit when running inPaWrite
AV23SA max speed pressure set pointSupply air duct pressure max. limit for the unit when the low/highPaWrite
AV24EA max speed pressure set pointExtract air duct pressure max. limit for the unit when the low/highPaWrite
AV25SA max speed output signalMax. limit for the supply air fan speed when running in pressure%Write
AV26EA max speed output signalMax. limit for the extract air fan speed when running in pressure%Write
AV27SA pressure regulation zoneSupply air pressure regulation zone setting in % of the present duct%Write
AV28EA pressure regulation zoneExtract air pressure regulation zone setting in % of the present duct%Write
AV29SA pressure I-timeSupply air pressure regulator affection setting.sWrite
AV30EA pressure I-timeExtract air pressure regulator affection setting.sWrite
AV37Demand low speed demand set pointSet point for the 0..10V input signal for the unit when running%Write
AV38Demand high speed demand set pointSet point for the 0..10V input signal for the unit when running%Write
AV39SA min speed air flow set pointSupply air flow min. limit for the unit when the low/high speedl/sWrite
AV40EA min speed air flow set pointExtract air flow min. limit for the unit when the low/high speedl/sWrite
AV41SA max speed air flow set pointSupply air flow max limit for the unit when the low/high speedl/sWrite
AV42EA max speed air flow set pointExtract air flow max. limit for the unit when the low/high speedl/sWrite
AV43SA demand P-bandSupply air demand regulator P-band setting.%Write
AV44SA demand I-timeSupply air demand regulator affection setting.sWrite
AV50Slave offset factor%Write
AV54Outdoor temp compensation X1°CWrite
AV55Outdoor temp compensation X2°CWrite
AV56Outdoor temp compensation X3°CWrite
AV57Outdoor temp compensation X4°CWrite
AV58Outdoor temp compensation Y1 SA air flowl/sWrite
AV59Outdoor temp compensation Y2 SA air flowl/sWrite
AV60Outdoor temp compensation Y3 SA air flowl/sWrite
AV61Outdoor temp compensation Y4 SA air flowl/sWrite
AV62Outdoor temp compensation Y1 EA air flowl/sWrite
AV63Outdoor temp compensation Y2 EA air flowl/sWrite
AV64Outdoor temp compensation Y3 EA air flowl/sWrite
AV65Outdoor temp compensation Y4 EA air flowl/sWrite
AV66Outdoor temp compensation Y1 SA pressurePaWrite
AV67Outdoor temp compensation Y2 SA pressurePaWrite
AV68Outdoor temp compensation Y3 SA pressurePaWrite
AV69Outdoor temp compensation Y4 SA pressurePaWrite
AV70Outdoor temp compensation Y1 EA pressurePaWrite
AV71Outdoor temp compensation Y2 EA pressurePaWrite
AV72Outdoor temp compensation Y3 EA pressurePaWrite
AV73Outdoor temp compensation Y4 EA pressurePaWrite
AV79Down regulation neutralzoneKWrite
AV80Down regulation P-bandKWrite
AV81Down regulation I-timesWrite
AV85SA fan speed at fire alarm 1%Write
AV86EA fan speed at fire alarm 1%Write
AV88SA fan speed at fire alarm 2%Write
AV89EA fan speed at fire alarm 2%Write
AV91SA fan speed at internal fire alarm%Write
AV92EA fan speed at internal fire alarm%Write
AV97SA pre-filter alarm limitPaWrite
AV98EA pre-filter alarm limitPaWrite
AV103SA AHU-filter alarm limitPaWrite
AV104EA AHU-filter alarm limitPaWrite
AV109SA end-filter alarm limitPaWrite
AV117ERS 1 stepCurve setting according to the diagram for ERS 1.Write
AV118ERS 1 diffSupply air temp difference setting according to the diagram for ERS 1.KWrite
AV119ERS 1 breakpointBreakpoint temp setting according to the diagram for ERS 1.°CWrite
AV122ERS 2 breakpoint X1Breakpoint X1 setting according to the diagram for ERS 2.°CWrite
AV123ERS 2 breakpoint X2Breakpoint X2 setting according to the diagram for ERS 2.°CWrite
AV124ERS 2 breakpoint X3Breakpoint X3 setting according to the diagram for ERS 2.°CWrite
AV125ERS 2 breakpoint X4Breakpoint X4 setting according to the diagram for ERS 2.°CWrite
AV126ERS 2 breakpoint Y1Breakpoint Y1 setting according to the diagram for ERS 2.°CWrite
AV127ERS 2 breakpoint Y2Breakpoint Y2 setting according to the diagram for ERS 2.°CWrite
AV128ERS 2 breakpoint Y3Breakpoint Y3 setting according to the diagram for ERS 2.°CWrite
AV129ERS 2 breakpoint Y4Breakpoint Y4 setting according to the diagram for ERS 2.°CWrite
AVmin132SA temperature set pointSupply air temperature setting°CWrite
AVmin135EA/Room temperature set pointExtract air/room temperature setting°CWrite
AV136SA min temp set pointSupply air min. set point during EA/room°CWrite
AV137SA max temp set pointSupply air max. set point during EA/room°CWrite
AV138EA regultaion P-bandKWrite
AV139EA regultaion I-timesWrite
AV142ORS breakpoint X1Breakpoint X1 setting according to the diagram for ORS.°CWrite
AV143ORS breakpoint X2Breakpoint X2 setting according to the diagram for ORS.°CWrite
AV144ORS breakpoint X3Breakpoint X3 setting according to the diagram for ORS.°CWrite
AV145ORS breakpoint X4Breakpoint X4 setting according to the diagram for ORS.°CWrite
AV146ORS breakpoint Y1Breakpoint Y1 setting according to the diagram for ORS.°CWrite
AV147ORS breakpoint Y2Breakpoint Y2 setting according to the diagram for ORS.°CWrite
AV148ORS breakpoint Y3Breakpoint Y3 setting according to the diagram for ORS.°CWrite
AV149ORS breakpoint Y4Breakpoint Y4 setting according to the diagram for ORS.°CWrite
AV152ORE breakpoint X1Breakpoint X1 setting according to the diagram for ORE.°CWrite
AV153ORE breakpoint X2Breakpoint X2 setting according to the diagram for ORE.°CWrite
AV154ORE breakpoint X3Breakpoint X3 setting according to the diagram for ORE.°CWrite
AV155ORE breakpoint X4Breakpoint X4 setting according to the diagram for ORE.°CWrite
AV156ORE breakpoint Y1Breakpoint Y1 setting according to the diagram for ORE.°CWrite
AV157ORE breakpoint Y2Breakpoint Y2 setting according to the diagram for ORE.°CWrite
AV158ORE breakpoint Y3Breakpoint Y3 setting according to the diagram for ORE.°CWrite
AV159ORE breakpoint Y4Breakpoint Y4 setting according to the diagram for ORE.°CWrite
AV168External room temp from BMS°CWrite
AV169External room temp from BMS alarm timeminWrite
AV178External OA temp from BMS°CWrite
AV179External OA temp from BMS alarm timeminWrite
AV184RHX defrost start limitPaWrite
AV188RHX sorption rotor functionMoved to Multistate Value 188Write
AV191RHX min exhaust air temp set point°CWrite
AV192RHX min exhaust air temp P-bandKWrite
AV193RHX min exhaust air temp I-timesWrite
AV199PHX periodic operation intervalhWrite
AV200PHX periodic operation timeminWrite
AV207CHX periodic operation intervalhWrite
AV208CHX periodic operation timeminWrite
AV213PHX/CHX Bypass defrost limitPHX is default 3°C, CHX is default 5°C.°CWrite
AV214PHX/CHX Bypass defrost P-bandKWrite
AV215PHX/CHX Bypass defrost I-timesWrite
AV220Heat exchange temperature regulation P-bandKWrite
AV221Heat exchange temperature regulation I-timesWrite
AV222Cool exchange temperature regulation P-bandKWrite
AV223Cool exchange temperature regulation I-timesWrite
AV226Re-heat P-bandKWrite
AV227Re-heat I-timesWrite
AV230Re-heat periodic operation intervalhWrite
AV231Re-heat periodic operation timeminWrite
AV239Extra regulation sequence 1 heat max output signalMaximum output signal setting for the extra regulation sequence.%Write
AV240Extra regulation sequence 1 cool max output signalMaximum output signal setting for the extra regulation sequence.%Write
AV241Extra regulation sequence 1 heat P-bandKWrite
AV242Extra regulation sequence 1 heat I-timesWrite
AV243Extra regulation sequence 1 cool P-bandKWrite
AV244Extra regulation sequence 1 cool I-timesWrite
AV247Extra regulation 1 periodic operation intervalhWrite
AV248Extra regulation 1 periodic operation timeminWrite
AV252Extra regulation 1 temperature protection temperature°CWrite
AV253Extra regulation 1 temperature protection alarm delayminWrite
AV258Cool step 1 min supply air flow limitl/sWrite
AV259Cool step 2 min supply air flow limitl/sWrite
AV260Cool step 3 min supply air flow limitl/sWrite
AV262Cool SA neutral zoneKWrite
AV263Cool EA neutral zoneKWrite
AV264Cool outdoor temp limit 1°CWrite
AV265Cool outdoor temp limit 2°CWrite
AV266Cool outdoor temp limit 3°CWrite
AV267Cool 0-10V min supply air flow limitl/sWrite
AV268Cool 0-10V min extract air flow limitl/sWrite
AV269Cool restart timeSetting of cool restart time between start-start.minWrite
AV270Cool step up delay timeSetting of on/off cooling and COOL DX time delay between steps.minWrite
AV271Cool stand still timeSetting of on/off cooling and COOL DX time delay before stop-startminWrite
AV272Cool P-bandKWrite
AV273Cool I-timesWrite
AV277Cool periodic operation intervalhWrite
AV278Cool periodic operation timeminWrite
AV279Cool step 1 min extract air flow limitl/sWrite
AV280Cool step 2 min extract air flow limitl/sWrite
AV281Cool step 3 min extract air flow limitl/sWrite
AV285Summer night cool start time (hour)hWrite
AV286Summer night cool start time (minute)minWrite
AV287Summer night cool stop time (hour)hWrite
AV288Summer night cool stop time (minute)minWrite
AV289Summer night cool OA temp start limit°CWrite
AV290Summer night cool EA temp start limit°CWrite
AV291Summer night cool EA temp stop limit°CWrite
AV292Summer night cool SA temp set point°CWrite
AV297Intermittent night heat SA flow set pointl/sWrite
AV298Intermittent night heat SA duct pressure set pointPaWrite
AV299Intermittent night heat EA temp start limit°CWrite
AV300Intermittent night heat EA temp stop limit°CWrite
AV301Intermittent night heat SA temp set point°CWrite
AV303Intermittent night heat EA flow set pointl/sWrite
AV304Intermittent night heat EA duct pressure set pointPaWrite
AV306Morning boost start time (hour)hWrite
AV307Morning boost start time (minute)minWrite
AV308Morning boost air flow set pointl/sWrite
AV309Morning boost duct pressure set pointPaWrite
AV314Cooling boost comfort start limitKWrite
AV315Cooling boost comfort regulation speed%/sWrite
AV316Cooling boost economy P-bandKWrite
AV317Cooling boost economy I-timesWrite
AV321Heating boost comfort start limitKWrite
AV322Heating boost comfort regulation speed%/sWrite
AV331Xzone ERS 1 stepCurve setting according to the diagram for ERS 1.Write
AV332Xzone ERS 1 diffSupply air temp differental setting according to the diagram for ERS 1.KWrite
AV333Xzone ERS 1 breakpointBreakpoint temp setting according to the diagram for ERS 1.°CWrite
AV336Xzone ERS 2 breakpoint X1Breakpoint X1 setting according to the diagram for ERS 2.°CWrite
AV337Xzone ERS 2 breakpoint X2Breakpoint X2 setting according to the diagram for ERS 2.°CWrite
AV338Xzone ERS 2 breakpoint X3Breakpoint X3 setting according to the diagram for ERS 2.°CWrite
AV339Xzone ERS 2 breakpoint X4Breakpoint X4 setting according to the diagram for ERS 2.°CWrite
AV340Xzone ERS 2 breakpoint Y1Breakpoint Y1 setting according to the diagram for ERS 2.°CWrite
AV341Xzone ERS 2 breakpoint Y2Breakpoint Y2 setting according to the diagram for ERS 2.°CWrite
AV342Xzone ERS 2 breakpoint Y3Breakpoint Y3 setting according to the diagram for ERS 2.°CWrite
AV343Xzone ERS 2 breakpoint Y4Breakpoint Y4 setting according to the diagram for ERS 2.°CWrite
AV346Xzone SA temperature set pointSupply air temperature setting, for supply air temp regulation mode.°CWrite
AV349Xzone EA/Room temperature set pointExtract air/room temperature setting°CWrite
AV350Xzone SA min temp set pointSupply air min. set point during EA/room°CWrite
AV351Xzone SA max temp set pointSupply air max. set point during EA/room°CWrite
AV352Xzone EA regultaion P-bandKWrite
AV353Xzone EA regultaion I-timesWrite
AV354Xzone ORS breakpoint X1Breakpoint X1 setting according to the diagram for ORS.°CWrite
AV355Xzone ORS breakpoint X2Breakpoint X2 setting according to the diagram for ORS.°CWrite
AV356Xzone ORS breakpoint X3Breakpoint X3 setting according to the diagram for ORS.°CWrite
AV357Xzone ORS breakpoint X4Breakpoint X4 setting according to the diagram for ORS.°CWrite
AV358Xzone ORS breakpoint Y1Breakpoint Y1 setting according to the diagram for ORS.°CWrite
AV359Xzone ORS breakpoint Y2Breakpoint Y2 setting according to the diagram for ORS.°CWrite
AV360Xzone ORS breakpoint Y3Breakpoint Y3 setting according to the diagram for ORS.°CWrite
AV361Xzone ORS breakpoint Y4Breakpoint Y4 setting according to the diagram for ORS.°CWrite
AV364Xzone ORE breakpoint X1Breakpoint X1 setting according to the diagram for ORE.°CWrite
AV365Xzone ORE breakpoint X2Breakpoint X2 setting according to the diagram for ORE.°CWrite
AV366Xzone ORE breakpoint X3Breakpoint X3 setting according to the diagram for ORE.°CWrite
AV367Xzone ORE breakpoint X4Breakpoint X4 setting according to the diagram for ORE.°CWrite
AV368Xzone ORE breakpoint Y1Breakpoint Y1 setting according to the diagram for ORE.°CWrite
AV369Xzone ORE breakpoint Y2Breakpoint Y2 setting according to the diagram for ORE.°CWrite
AV370Xzone ORE breakpoint Y3Breakpoint Y3 setting according to the diagram for ORE.°CWrite
AV371Xzone ORE breakpoint Y4°CWrite
AV380Xzone external room temp from BMS°CWrite
AV381Xzone external room temp from BMS alarm timeminWrite
AV384Xzone reheat P-bandKWrite
AV385Xzone reheat I-timesWrite
AV388Xzone reheat periodic operation intervalhWrite
AV389Xzone reheat periodic operation timeminWrite
AV396Xzone Cool SA neutral zoneKWrite
AV397Xzone Cool EA neutral zoneKWrite
AV398Xzone Cool P-bandKWrite
AV399Xzone Cool I-timesWrite
AV403Xzone Cool periodic operation intervalhWrite
AV404Xzone Cool periodic operation timeminWrite
AV411Pre-heat temperature set point°CWrite
AV412Pre-heat P-bandKWrite
AV413Pre-heat I-timesWrite
AV416Pre-heat periodic operation intervalhWrite
AV417Pre-heat periodic operation timeminWrite
AV426ReCO2-CO2 set point%Write
AV427ReCO2 min. outdoor airl/sWrite
AV428ReCO2 min. exhaust airl/sWrite
AV429ReCO2-CO2 P-band%Write
AV430ReCO2-CO2 I-timesWrite
AV431ReCO2-CO2 air flow boost reg. P-band%Write
AV432ReCO2-CO2 air flow boost reg. I-timesWrite
AV433ReCO2 heat P-bandKWrite
AV434ReCO2 heat I-timesWrite
AV435ReCO2 cool P-bandKWrite
AV436ReCO2 cool I-timesWrite
AV443Humidifying on/off start level%RHWrite
AV444Humidifying on/off stop level%RHWrite
AV448Humidifying 0-10V set point%RHWrite
AV449Humidifying 0-10V SA max set point%RHWrite
AV450Humidifying 0-10V SA P-band%RHWrite
AV451Humidifying 0-10V SA I-timesWrite
AV452Humidifying 0-10V EA P-band%RHWrite
AV453Humidifying 0-10V EA I-timesWrite
AV458Dehumidifying set point%RHWrite
AV470COOL DX Low pressure stop limitBarWrite
AV471COOL DX High pressure stop limitBarWrite
AV472COOL DX Restart timeTime setting between start - startminWrite
AV482SMART Link WB Heat temperature set point°CWrite
AV483SMART Link WB Heat temperature heat zoneKWrite
AV484SMART Link WB Cool temperature set point°CWrite
AV485SMART Link WB Cool temperature heat zoneKWrite
AV491SMART Link WB Optimize valve upper limit%Write
AV492SMART Link WB Optimize valve lower limit%Write
AV493SMART Link WB Optimize time delaysWrite
AV494SMART Link WB Optimize heat regulation speedK/sWrite
AV495SMART Link WB Optimize cool regulation speedK/sWrite
AV510SMART Link DX Amount of unitsWrite
AV519SMART Link OA temp limit°CWrite
AV524AYC Heated water temp set point°CWrite
AV526AYC Heated water OA temp for start of pump°CWrite
AV527AYC Heated water OA temp for stop of pump°CWrite
AV532AYC Heated water periodic operation intervalhWrite
AV533AYC Heated water periodic operation timeminWrite
AV537AYC Heated water OA temp compensation X1°CWrite
AV538AYC Heated water OA temp compensation X2°CWrite
AV539AYC Heated water OA temp compensation X3°CWrite
AV540AYC Heated water OA temp compensation X4°CWrite
AV541AYC Heated water OA temp compensation Y1°CWrite
AV542AYC Heated water OA temp compensation Y2°CWrite
AV543AYC Heated water OA temp compensation Y3°CWrite
AV544AYC Heated water OA temp compensation Y4°CWrite
AV549AYC Heated water room temp compensation temperature°CWrite
AV550AYC Heated water room temp compensation P-bandKWrite
AV554AYC Heated water night temp compensation tempKWrite
AV556AYC Heated water night temp compensation start time 1 (hour)hWrite
AV557AYC Heated water night temp compensation start time 1 (minutes)minWrite
AV558AYC Heated water night temp compensation stop time 1 (hour)hWrite
AV559AYC Heated water night temp compensation stop time 1 (minutes)minWrite
AV563AYC Heated water night temp compensation start time 2 (hour)hWrite
AV564AYC Heated water night temp compensation start time 2 (minutes)minWrite
AV565AYC Heated water night temp compensation stop time 2 (hour)hWrite
AV566AYC Heated water night temp compensation stop time 2 (minutes)minWrite
AV569AYC Heated water P-bandKWrite
AV570AYC Heated water I-timesWrite
AV572AYC Chilled water temp set point°CWrite
AV575AYC Chilled water OA temp for start of pump°CWrite
AV576AYC Chilled water OA temp for stop of pump°CWrite
AV581AYC Chilled water periodic operation intervalhWrite
AV582AYC Chilled water periodic operation timeminWrite
AV586AYC Chilled water OA temp compensation X1°CWrite
AV587AYC Chilled water OA temp compensation X2°CWrite
AV588AYC Chilled water OA temp compensation X3°CWrite
AV589AYC Chilled water OA temp compensation X4°CWrite
AV590AYC Chilled water OA temp compensation Y1°CWrite
AV591AYC Chilled water OA temp compensation Y2°CWrite
AV592AYC Chilled water OA temp compensation Y3°CWrite
AV593AYC Chilled water OA temp compensation Y4°CWrite
AV598AYC Chilledwater room temp compensation temperature°CWrite
AV599AYC Chilled water room temp compensation P-bandKWrite
AV603AYC Chilled water night temp compensation tempKWrite
AV605AYC Chilled water night temp compensation start time 1 (hour)hWrite
AV606AYC Chilled water night temp compensation start time 1 (minutes)minWrite
AV607AYC Chilled water night temp compensation stop time 1 (hour)hWrite
AV608AYC Chilled water night temp compensation stop time 1 (minutes)minWrite
AV612AYC Chilled water night temp compensation start time 2 (hour)hWrite
AV613AYC Chilled water night temp compensation start time 2 (minutes)minWrite
AV614AYC Chilledwater night temp compensation stop time 2 (hour)hWrite
AV615AYC Chilled water night temp compensation stop time 2 (minutes)minWrite
AV619AYC Chilled water dew point compensation neutral zoneKWrite
AV620AYC Chilled water dew point compensation regulation speedPercent air flow boost of each increased chilled water set point.%/KWrite
AV623AYC Chilled water P-bandKWrite
AV624AYC Chilled water I-timesWrite
AV638Optimize SA pressure set pointPaWrite
AV639Optimize EA pressure set pointPaWrite
AV672MIRU Control 1 Low speed duct pressure set pointPaWrite
AV673MIRU Control 1 High speed duct pressure set pointPaWrite
AV674MIRU Control 1 Low speed air flow set pointl/sWrite
AV675MIRU Control 1 High speed air flow set pointl/sWrite
AV680MIRU Control 2 Low speed duct pressure set pointPaWrite
AV681MIRU Control 2 High speed duct pressure set pointPaWrite
AV682MIRU Control 2 Low speed air flow set pointl/sWrite
AV683MIRU Control 2 High speed air flow set pointl/sWrite
AV688MIRU Control 3 Low speed duct pressure set pointPaWrite
AV689MIRU Control 3 High speed duct pressure set pointPaWrite
AV690MIRU Control 3 Low speed air flow set pointl/sWrite
AV691MIRU Control 3 High speed air flow set pointl/sWrite
AV696MIRU Control 4 Low speed duct pressure set pointPaWrite
AV697MIRU Control 4 High speed duct pressure set pointPaWrite
AV698MIRU Control 4 Low speed air flow set pointl/sWrite
AV699MIRU Control 4 High speed air flow set pointl/sWrite
AV704MIRU Control 5 Low speed duct pressure set pointPaWrite
AV705MIRU Control 5 High speed duct pressure set pointPaWrite
AV706MIRU Control 5 Low speed air flow set pointl/sWrite
AV707MIRU Control 5 High speed air flow set pointl/sWrite
AV712MIRU Control 6 Low speed duct pressure set pointPaWrite
AV713MIRU Control 6 High speed duct pressure set pointPaWrite
AV714MIRU Control 6 Low speed air flow set pointl/sWrite
AV715MIRU Control 6 High speed air flow set pointl/sWrite
AV720MIRU Control 7 Low speed duct pressure set pointPaWrite
AV721MIRU Control 7 High speed duct pressure set pointPaWrite
AV722MIRU Control 7 Low speed air flow set pointl/sWrite
AV723MIRU Control 7 High speed air flow set pointl/sWrite
AV728MIRU Control 8 Low speed duct pressure set pointPaWrite
AV729MIRU Control 8 High speed duct pressure set pointPaWrite
AV730MIRU Control 8 Low speed air flow set pointl/sWrite
AV731MIRU Control 8 High speed air flow set pointl/sWrite
AV736MIRU Control 9 Low speed duct pressure set pointPaWrite
AV737MIRU Control 9 High speed duct pressure set pointPaWrite
AV738MIRU Control 9 Low speed air flow set pointl/sWrite
AV739MIRU Control 9 High speed air flow set pointl/sWrite
AV744MIRU Control 10 Low speed duct pressure set pointPaWrite
AV745MIRU Control 10 High speed duct pressure set pointPaWrite
AV746MIRU Control 10 Low speed air flow set pointl/sWrite
AV747MIRU Control 10 High speed air flow set pointl/sWrite
BI1Operation activeRelay output statusRead
BI2Damper operation activeRelay output statusRead
BI3Low speed operation activeLow speed operation statusRead
BI4High speed operation activeHigh speed operation statusRead
BI5Intermittent night heat activeRead
BI6Morning boost activeRead
BI7Heating boost activeRead
BI8Cooling boost activeRead
BI9Summer night cool activeRead
BImin13A-alarm activeAny alarm with priority class A activeRead
BImin14B-alarm activeAny alarm with priority class B activeRead
BI17HX operation activeHX statusRead
BI18HX cool recovery activeHX cool recovery statusRead
BI19HX defrost activeHX defrost statusRead
BI22RHX speed monitor signalRHX speed monitor statusRead
BI27CHX pump outputRelay output statusRead
BI28CHX pump inputDigital input statusRead
BI31Season heat, extra regulation sequence allowedRead
BI32Season heat, re-heat allowedRead
BI33Extra regulation sequence 1, outputRelay output statusRead
BI34Extra regulation sequence 1, power reduction activeRead
BI35Extra regulation sequence 1, anti-frost regulation activeRead
BI38Re-heat outputRelay output statusRead
BI39Re-heat power reduction activeRead
BI40Re-heat anti-frost regulation activeRead
BI43Cool output 1Relay output statusRead
BI44Cool output 2Relay output statusRead
BI48Extra regulation sequence 2, outputRelay output statusRead
BI49Extra regulation sequence 2, power reduction activeRead
BI50Extra regulation sequence 2, anti-frost regulation activeRead
BI51Pre-heat outputRelay output statusRead
BI52Pre-heat power reduction activeRead
BI53Pre-heat anti-frost regulation activeRead
BI56Xzone heat outputRelay output statusRead
BI57Xzone heat power reduction activeRead
BI58Xzone heat anti-frost regulation activeRead
BI63Xzone cool output 1Relay output statusRead
BI64Xzone cool output 2Relay output statusRead
BI99AYC heat pump outputRelay output statusRead
BI100AYC heat pump inputDigital input statusRead
BI104Max. limit for the supply air fan speed when running in pressure regulation moRelay output statusRead
BI105AYC cool pump inputDigital input statusRead
BI109COOL DX compressor 1 outputRelay output statusRead
BI110COOL DX compressor 1 inputDigital input statusRead
BI115COOL DX compressor 2 outputRelay output statusRead
BI116COOL DX compressor 2 inputDigital input statusRead
BI319SMART Link, DX operationRead
BI323SMART Link, DX unit 1 operationRead
BI324SMART Link, DX unit 1 cool modeRead
BI325SMART Link, DX unit 1 defrost requestRead
BI326SMART Link, DX unit 1 defrost activeRead
BI334SMART Link, DX unit 2 operationRead
BI335SMART Link, DX unit 2 cool modeRead
BI336SMART Link, DX unit 2 defrost requestRead
BI337SMART Link, DX unit 2 defrost activeRead
BI345SMART Link, DX unit 3 operationRead
BI346SMART Link, DX unit 3 cool modeRead
BI347SMART Link, DX unit 3 defrost requestRead
BI348SMART Link, DX unit 3 defrost activeRead
BI356SMART Link, DX unit 4 operationRead
BI357SMART Link, DX unit 4 cool modeRead
BI358SMART Link, DX unit 4 defrost requestRead
BI359SMART Link, DX unit 4 power defrost activeRead
BI501Alarm 1:1 External fire alarm no. 1 trippedRead
BI502Alarm 1:2 External fire alarm no. 2 trippedRead
BI503Alarm 1:3 Internal fire alarm trippedRead
BI516Alarm 2:1 External alarm no. 1 trippedRead
BI517Alarm 2:2 External alarm no. 2 trippedRead
BI531Alarm 3:1 Pre-heat I/O-module no. 9 com. errorRead
BI532Alarm 3:2 Pre-heat electrical heater overheat protection trippedRead
BI533Alarm 3:3 Pre-heat frost protection trippedRead
BI534Alarm 3:4 Pre-heat frost protection temperature sensor defectiveRead
BI535Alarm 3:5 Pre-heat temperature sensor defectiveRead
BI536Alarm 3:6 Pre-heat valve monitoring trippedRead
BI537Alarm 3:7 Pre-heat temperature below set point alarm limitRead
BI538Alarm 3:8 Pre-heat alarm input trippedRead
BI546Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. errorRead
BI547Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection trippedRead
BI548Alarm 4:3 Extra reg. sequence 1 frost protection trippedRead
BI549Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensorRead
BI550Alarm 4:5 Extra reg. sequence 1 valve monitoring trippedRead
BI551Alarm 4:6 Extra reg. sequence 1 alarm input trippedRead
BI552Alarm 4:7 Extra reg. sequence 1 temperature protection from com. ErrorRead
BI554Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. errorRead
BI555Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection trippedRead
BI556Alarm 4:11 Extra reg. sequence 2 frost protection trippedRead
BI557Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensorRead
BI558Alarm 4:13 Extra reg. sequence 2 valve monitoring trippedRead
BI559Alarm 4:14 Extra reg. sequence 2 alarm input trippedRead
BI561Alarm 5:1 Re-heat electrical heater over heat protection trippedRead
BI562Alarm 5:2 Re-heat frost protection trippedRead
BI563Alarm 5:3 Re-heat frost protection temperature sensor defectiveRead
BI564Alarm 5:4 Re-heat heat valve monitoring trippedRead
BI576Alarm 6:1 Xzone I/O-module no. A com. errorRead
BI577Alarm 6:2 Xzone electrical heater overheat protection trippedRead
BI578Alarm 6:3 Xzone frost protection trippedRead
BI579Alarm 6:4 Xzone frost protection temperature sensor defectiveRead
BI580Alarm 6:5 Xzone supply air temperature sensor defectiveRead
BI581Alarm 6:6 Xzone heat valve monitoring trippedRead
BI582Alarm 6:7 Xzone supply air temperature below set point alarm limitRead
BI583Alarm 6:8 Xzone supply air temperature above set point alarm limitRead
BI584Alarm 6:9 Xzone heat alarm input trippedRead
BI591Alarm 7:1 Xzone I/O-module no. B com. errorRead
BI592Alarm 7:2 Xzone extract air temperature sensor defectiveRead
BI593Alarm 7:3 Xzone cool valve monitoring trippedRead
BI594Alarm 7:4 Xzone extract air temperature below set point alarm limitRead
BI595Alarm 7:5 Xzone cool alarm input 1 trippedRead
BI596Alarm 7:6 Xzone cool alarm input 2 trippedRead
BI610Alarm 8:5 Cool valve monitoring trippedRead
BI636Alarm 10:1 Supply air temperature sensor defectiveRead
BI637Alarm 10:2 Supply air temperature sensor for density compensation defectiveRead
BI638Alarm 10:3 Extract air temperature sensor defectiveRead
BI639Alarm 10:4 Extract air temperature sensor for density compensation defectiveRead
BI640Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def.Read
BI641Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def.Read
BI642Alarm 10:7 Extract air duct temperature sensor defectiveRead
BI645Alarm 10:10 Outdoor air temperature sensor defectiveRead
BI651Alarm 11:1 Room temperature sensor no. 1 defectiveRead
BI652Alarm 11:2 Room temperature sensor no. 2 defectiveRead
BI653Alarm 11:3 Room temperature sensor no. 3 defectiveRead
BI654Alarm 11:4 Room temperature sensor no. 4 defectiveRead
BI655Alarm 11:5 Xzone room temperature sensor no. 5 defectiveRead
BI656Alarm 11:6 Xzone room temperature sensor no. 6 defectiveRead
BI657Alarm 11:7 Xzone room temperature sensor no. 7 defectiveRead
BI658Alarm 11:8 Xzone room temperature sensor no. 8 defectiveRead
BI659Alarm 11:9 Outdoor temperature sensor no. A defectiveRead
BI660Alarm 11:10 Outdoor temperature sensor no. B defectiveRead
BI661Alarm 11:11 Outdoor temperature sensor no. C defectiveRead
BI662Alarm 11:12 Outdoor temperature sensor no. D defectiveRead
BI663Alarm 11:13 Room temperature from com. errorRead
BI664Alarm 11:14 Xzone room temperature from com. errorRead
BI665Alarm 11:15 Outdoor temperature from com. errorRead
BI666Alarm 12:1 Supply air temperature below set point alarm limitRead
BI667Alarm 12:2 Supply air temperature above set point alarm limitRead
BI671Alarm 12:6 Extract air temperature below alarm limitRead
BI676Alarm 12:11 Temperature guard below alarm limitRead
BI681Alarm 13:1 Humidification I/O-module no. 4 com. errorRead
BI682Alarm 13:2 Supply air humidity sensor defectiveRead
BI683Alarm 13:3 Extract air humidity sensor defectiveRead
BI689Alarm 13:9 Humidifier alarm output trippedRead
BI691Alarm 13:11 VOC sensor com. errorRead
BI692Alarm 13:12 VOC sensor internal com. errorRead
BI693Alarm 13:13 VOC sensor internal errorRead
BI694Alarm 13:14 VOC sensor level below/above set point alarm limitRead
BI711Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. errorRead
BI712Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defectiveRead
BI713Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defectiveRead
BI714Alarm 15:4 Plate heat exchanger damper monitor trippedRead
BI717Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. errorRead
BI718Alarm 15:8 Plate heat exchanger bypass damper monitor trippedRead
BI719Alarm 15:9 Plate heat exchanger damper no. 1 monitor trippedRead
BI720Alarm 15:10 Plate heat exchanger damper no. 2 monitor trippedRead
BI721Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. errorRead
BI722Alarm 15:12 Plate heat exchanger bypass damper monitor trippedRead
BI724Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. errorRead
BI725Alarm 15:15 Plate heat exchanger defrost pressure above alarm limitRead
BI726Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. errorRead
BI727Alarm 16:2 Coil heat exchanger temperature sensor defectiveRead
BI728Alarm 16:3 Coil heat exchanger valve monitor trippedRead
BI729Alarm 16:4 Coil heat exchanger pump monitor trippedRead
BI741Alarm 17:1 Rotary heat exchanger motor controller com. errorRead
BI742Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. errorRead
BI743Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limitRead
BI744Alarm 17:4 Rotary heat exchanger speed monitor trippedRead
BI745Alarm 17:5 Rotary heat exchanger motor controller over currentRead
BI746Alarm 17:6 Rotary heat exchanger motor controller under voltageRead
BI747Alarm 17:7 Rotary heat exchanger motor controller over voltageRead
BI748Alarm 17:8 Rotary heat exchanger motor controller over temperatureRead
BI749Alarm 17:9 Rotary heat exchanger motor controller start errorRead
BI756Alarm 18:1 AYC I/O-module no. 7 com. errorRead
BI757Alarm 18:2 AYC heat temperature sensor defectiveRead
BI758Alarm 18:3 AYC heat valve monitor trippedRead
BI759Alarm 18:4 AYC heat pump monitor trippedRead
BI760Alarm 18:5 AYC heat temperature below set point alarm limitRead
BI761Alarm 18:6 AYC heat temperature above set point alarm limitRead
BI764Alarm 18:9 AYC cool temperature sensor defectiveRead
BI765Alarm 18:10 AYC cool valve monitor trippedRead
BI766Alarm 18:11 AYC cool pump monitor trippedRead
BI767Alarm 18:12 AYC cool temperature below set point alarm limitRead
BI768Alarm 18:13 AYC cool temperature above set point alarm limitRead
BI801Alarm 21:1 COOL DX I/O-module no. 2 com. errorRead
BI802Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defectiveRead
BI803Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limitRead
BI804Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defectiveRead
BI805Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limitRead
BI806Alarm 21:6 COOL DX compressor no. 1 monitor trippedRead
BI807Alarm 21:7 COOL DX compressor no. 1 restart errorRead
BI808Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defectiveRead
BI809Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limitRead
BI810Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defectiveRead
BI811Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limitRead
BI812Alarm 21:12 COOL DX compressor no. 2 monitor trippedRead
BI813Alarm 21:13 COOL DX compressor no. 2 restart errorRead
BI814Alarm 21:14 COOL DX outdoor air temperature sensor defectiveRead
BI815Alarm 21:15 COOL DX phase sequence errorRead
BI831Alarm 23:1 SMART Link com. errorRead
BI832Alarm 23:2 SMART Link alarm level 1 trippedRead
BI833Alarm 23:3 SMART Link alarm level 2 trippedRead
BI834Alarm 23:4 SMART Link alarm level 3 trippedRead
BI840Alarm 23:10 AQUA Link I/O-module no. 5 com. errorRead
BI841Alarm 23:11 AQUA Link pump monitor trippedRead
BI846Alarm 24:1 SMART Link no. 1 com. errorRead
BI847Alarm 24:2 SMART Link no. 1 alarm trippedRead
BI849Alarm 24:4 SMART Link no. 2 com. errorRead
BI850Alarm 24:5 SMART Link no. 2 alarm trippedRead
BI852Alarm 24:7 SMART Link no. 3 com. errorRead
BI853Alarm 24:8 SMART Link no. 3 alarm trippedRead
BI855Alarm 24:10 SMART Link no. 4 com. errorRead
BI856Alarm 24:11 SMART Link no. 4 alarm trippedRead
BI876Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. errorRead
BI877Alarm 26:2 Pre-filter supply air dirtyRead
BI882Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. errorRead
BI883Alarm 26:8 Pre-filter extract air dirtyRead
BI891Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. errorRead
BI892Alarm 27:2 AHU filter supply air dirtyRead
BI897Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. errorRead
BI898Alarm 27:8 AHU filter extract air dirtyRead
BI906Alarm 28:1 End filter supply air pressure sensor no. A com. errorRead
BI907Alarm 28:2 End filter supply air dirtyRead
BI936Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com.Read
BI937Alarm 30:2 Air flow measurement supply air flow below set point alarm limitRead
BI938Alarm 30:3 Air flow measurement supply air flow above set point alarm limitRead
BI941Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com.Read
BI942Alarm 30:7 Air flow measurement extract air flow below set point alarm limitRead
BI943Alarm 30:8 Air flow measurement extract air flow above set point alarm limitRead
BI946Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. errorRead
BI951Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. errorRead
BI952Alarm 31:2 Pressure regulation supply air pressure below set point alarm limitRead
BI953Alarm 31:3 Pressure regulation supply air pressure above set point alarmRead
BI956Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. errorRead
BI957Alarm 31:7 Pressure regulation extract air press. below set point alarm limitRead
BI958Alarm 31:8 Pressure regulation extract air press. above set point alarm limitRead
BI966Alarm 32:1 ReCO2 I/O-module no. 0 com. errorRead
BI967Alarm 32:2 ReCO2 pressure sensor no. 0 com. errorRead
BI968Alarm 32:3 ReCO2 recirculation damper monitoring trippedRead
BI969Alarm 32:4 ReCO2 outdoor air damper monitoring trippedRead
BI981Alarm 33:1 Service period above alarm limitRead
BI995Alarm 33:15 Lock function trippedRead
BI996Alarm 34:1 External control I/O-module no. 3 com. errorRead
BI997Alarm 34:2 External control I/O-module no. 6 com. errorRead
BI1011Alarm 35:1 Booster diffusers I/O-module no. 8 com. errorRead
BI1056Alarm 38:1 MIRU 1 com. errorRead
BI1057Alarm 38:2 MIRU 1 motor controller alarm trippedRead
BI1058Alarm 38:3 MIRU 1 motor controller com. errorRead
BI1059Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. errorRead
BI1060Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. errorRead
BI1061Alarm 38:6 MIRU 1 temperature sensor defectiveRead
BI1062Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limitRead
BI1071Alarm 39:1 MIRU 2 com. errorRead
BI1072Alarm 39:2 MIRU 2 motor controller alarm trippedRead
BI1073Alarm 39:3 MIRU 2 motor controller com. errorRead
BI1074Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. errorRead
BI1075Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. errorRead
BI1076Alarm 39:6 MIRU 2 temperature sensor defectiveRead
BI1077Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limitRead
BI1086Alarm 40:1 MIRU 3 com. errorRead
BI1087Alarm 40:2 MIRU 3 motor controller alarm trippedRead
BI1088Alarm 40:3 MIRU 3 motor controller com. errorRead
BI1089Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. errorRead
BI1090Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. errorRead
BI1091Alarm 40:6 MIRU 3 temperature sensor defectiveRead
BI1092Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limitRead
BI1101Alarm 41:1 MIRU 4 com. errorRead
BI1102Alarm 41:2 MIRU 4 motor controller alarm trippedRead
BI1103Alarm 41:3 MIRU 4 motor controller com. errorRead
BI1104Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. errorRead
BI1105Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. errorRead
BI1106Alarm 41:6 MIRU 4 temperature sensor defectiveRead
BI1107Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limitRead
BI1116Alarm 42:1 MIRU 5 com. errorRead
BI1117Alarm 42:2 MIRU 5 motor controller alarm trippedRead
BI1118Alarm 42:3 MIRU 5 motor controller com. errorRead
BI1119Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. errorRead
BI1120Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. errorRead
BI1121Alarm 42:6 MIRU 5 temperature sensor defectiveRead
BI1122Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limitRead
BI1131Alarm 43:1 MIRU 6 com. errorRead
BI1132Alarm 43:2 MIRU 6 motor controller alarm trippedRead
BI1133Alarm 43:3 MIRU 6 motor controller com. errorRead
BI1134Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. errorRead
BI1135Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. errorRead
BI1136Alarm 43:6 MIRU 6 temperature sensor defectiveRead
BI1137Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limitRead
BI1146Alarm 44:1 MIRU 7 com. errorRead
BI1147Alarm 44:2 MIRU 7 motor controller alarm trippedRead
BI1148Alarm 44:3 MIRU 7 motor controller com. errorRead
BI1149Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. errorRead
BI1150Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. errorRead
BI1151Alarm 44:6 MIRU 7 temperature sensor defectiveRead
BI1152Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limitRead
BI1161Alarm 45:1 MIRU 8 com. errorRead
BI1162Alarm 45:2 MIRU 8 motor controller alarm trippedRead
BI1163Alarm 45:3 MIRU 8 motor controller com. errorRead
BI1164Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. errorRead
BI1165Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. errorRead
BI1166Alarm 45:6 MIRU 8 temperature sensor defectiveRead
BI1167Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limitRead
BI1176Alarm 46:1 MIRU 9 com. errorRead
BI1177Alarm 46:2 MIRU 9 motor controller alarm trippedRead
BI1178Alarm 46:3 MIRU 9 motor controller com. errorRead
BI1179Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. errorRead
BI1180Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. errorRead
BI1181Alarm 46:6 MIRU 9 temperature sensor defectiveRead
BI1182Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limitRead
BI1191Alarm 47:1 MIRU 10 com. errorRead
BI1192Alarm 47:2 MIRU 10 motor controller alarm trippedRead
BI1193Alarm 47:3 MIRU 10 motor controller com. errorRead
BI1194Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. errorRead
BI1195Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. errorRead
BI1196Alarm 47:6 MIRU 10 temperature sensor defectiveRead
BI1197Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limitRead
BI1221Alarm 49:1 Supply air fan no. 1A com. errorRead
BI1222Alarm 49:2 Supply air fan no. 1A motor controller over currentRead
BI1223Alarm 49:3 Supply air fan no. 1A motor controller under voltageRead
BI1224Alarm 49:4 Supply air fan no. 1A motor controller over voltageRead
BI1225Alarm 49:5 Supply air fan no. 1A motor controller over temperatureRead
BI1226Alarm 49:6 Supply air fan no. 1A motor controller start errorRead
BI1227Alarm 49:7 Supply air fan no. 1A motor controller ripple errorRead
BI1228Alarm 49:8 Supply air fan no. 1A motor controller phase errorRead
BI1229Alarm 49:9 Supply air fan no. 1A motor controller internal memory errorRead
BI1230Alarm 49:10 Supply air fan no. 1A motor controller current reductionRead
BI1236Alarm 50:1 Supply air fan no. 2A com. errorRead
BI1237Alarm 50:2 Supply air fan no. 2A motor controller over currentRead
BI1238Alarm 50:3 Supply air fan no. 2A motor controller under voltageRead
BI1239Alarm 50:4 Supply air fan no. 2A motor controller over voltageRead
BI1240Alarm 50:5 Supply air fan no. 2A motor controller over temperatureRead
BI1241Alarm 50:6 Supply air fan no. 2A motor controller start errorRead
BI1242Alarm 50:7 Supply air fan no. 2A motor controller ripple errorRead
BI1243Alarm 50:8 Supply air fan no. 2A motor controller phase errorRead
BI1244Alarm 50:9 Supply air fan no. 2A motor controller internal memory errorRead
BI1245Alarm 50:10 Supply air fan no. 2A motor controller current reductionRead
BI1251Alarm 51:1 Supply air fan no. 3A com. errorRead
BI1252Alarm 51:2 Supply air fan no. 3A motor controller over currentRead
BI1253Alarm 51:3 Supply air fan no. 3A motor controller under voltageRead
BI1254Alarm 51:4 Supply air fan no. 3A motor controller over voltageRead
BI1255Alarm 51:5 Supply air fan no. 3A motor controller over temperatureRead
BI1256Alarm 51:6 Supply air fan no. 3A motor controller start errorRead
BI1257Alarm 51:7 Supply air fan no. 3A motor controller ripple errorRead
BI1258Alarm 51:8 Supply air fan no. 3A motor controller phase errorRead
BI1259Alarm 51:9 Supply air fan no. 3A motor controller internal memory errorRead
BI1260Alarm 51:10 Supply air fan no. 3A motor controller current reductionRead
BI1266Alarm 52:1 Supply air fan no. 1B com. errorRead
BI1267Alarm 52:2 Supply air fan no. 1B motor controller over currentRead
BI1268Alarm 52:3 Supply air fan no. 1B motor controller under voltageRead
BI1269Alarm 52:4 Supply air fan no. 1B motor controller over voltageRead
BI1270Alarm 52:5 Supply air fan no. 1B motor controller over temperatureRead
BI1271Alarm 52:6 Supply air fan no. 1B motor controller start errorRead
BI1272Alarm 52:7 Supply air fan no. 1B motor controller ripple errorRead
BI1273Alarm 52:8 Supply air fan no. 1B motor controller phase errorRead
BI1274Alarm 52:9 Supply air fan no. 1B motor controller internal memory errorRead
BI1275Alarm 52:10 Supply air fan no. 1B motor controller current reductionRead
BI1281Alarm 53:1 Supply air fan no. 2B com. errorRead
BI1282Alarm 53:2 Supply air fan no. 2B motor controller over currentRead
BI1283Alarm 53:3 Supply air fan no. 2B motor controller under voltageRead
BI1284Alarm 53:4 Supply air fan no. 2B motor controller over voltageRead
BI1285Alarm 53:5 Supply air fan no. 2B motor controller over temperatureRead
BI1286Alarm 53:6 Supply air fan no. 2B motor controller start errorRead
BI1287Alarm 53:7 Supply air fan no. 2B motor controller ripple errorRead
BI1288Alarm 53:8 Supply air fan no. 2B motor controller phase errorRead
BI1289Alarm 53:9 Supply air fan no. 2B motor controller internal memory errorRead
BI1290Alarm 53:10 Supply air fan no. 2B motor controller current reductionRead
BI1296Alarm 54:1 Supply air fan no. 3B com. errorRead
BI1297Alarm 54:2 Supply air fan no. 3B motor controller over currentRead
BI1298Alarm 54:3 Supply air fan no. 3B motor controller under voltageRead
BI1299Alarm 54:4 Supply air fan no. 3B motor controller over voltageRead
BI1300Alarm 54:5 Supply air fan no. 3B motor controller over temperatureRead
BI1301Alarm 54:6 Supply air fan no. 3B motor controller start errorRead
BI1302Alarm 54:7 Supply air fan no. 3B motor controller ripple errorRead
BI1303Alarm 54:8 Supply air fan no. 3B motor controller phase errorRead
BI1304Alarm 54:9 Supply air fan no. 3B motor controller internal memory errorRead
BI1305Alarm 54:10 Supply air fan no. 3B motor controller current reductionRead
BI1311Alarm 55:1 Extract air fan no. 1A com. errorRead
BI1312Alarm 55:2 Extract air fan no. 1A motor controller over currentRead
BI1313Alarm 55:3 Extract air fan no. 1A motor controller under voltageRead
BI1314Alarm 55:4 Extract air fan no. 1A motor controller over voltageRead
BI1315Alarm 55:5 Extract air fan no. 1A motor controller over temperatureRead
BI1316Alarm 55:6 Extract air fan no. 1A motor controller start errorRead
BI1317Alarm 55:7 Extract air fan no. 1A motor controller ripple errorRead
BI1318Alarm 55:8 Extract air fan no. 1A motor controller phase errorRead
BI1319Alarm 55:9 Extract air fan no. 1A motor controller internal memory errorRead
BI1320Alarm 55:10 Extract air fan no. 1A motor controller current reductionRead
BI1326Alarm 56:1 Extract air fan no. 2A com. errorRead
BI1327Alarm 56:2 Extract air fan no. 2A motor controller over currentRead
BI1328Alarm 56:3 Extract air fan no. 2A motor controller under voltageRead
BI1329Alarm 56:4 Extract air fan no. 2A motor controller over voltageRead
BI1330Alarm 56:5 Extract air fan no. 2A motor controller over temperatureRead
BI1331Alarm 56:6 Extract air fan no. 2A motor controller start errorRead
BI1332Alarm 56:7 Extract air fan no. 2A motor controller ripple errorRead
BI1333Alarm 56:8 Extract air fan no. 2A motor controller phase errorRead
BI1334Alarm 56:9 Extract air fan no. 2A motor controller internal memory errorRead
BI1335Alarm 56:10 Extract air fan no. 2A motor controller current reductionRead
BI1341Alarm 57:1 Extract air fan no. 3A com. errorRead
BI1342Alarm 57:2 Extract air fan no. 3A motor controller over currentRead
BI1343Alarm 57:3 Extract air fan no. 3A motor controller under voltageRead
BI1344Alarm 57:4 Extract air fan no. 3A motor controller over voltageRead
BI1345Alarm 57:5 Extract air fan no. 3A motor controller over temperatureRead
BI1346Alarm 57:6 Extract air fan no. 3A motor controller start errorRead
BI1347Alarm 57:7 Extract air fan no. 3A motor controller ripple errorRead
BI1348Alarm 57:8 Extract air fan no. 3A motor controller phase errorRead
BI1349Alarm 57:9 Extract air fan no. 3A motor controller internal memory errorRead
BI1350Alarm 57:10 Extract air fan no. 3A motor controller current reductionRead
BI1356Alarm 58:1 Extract air fan no. 1B com. errorRead
BI1357Alarm 58:2 Extract air fan no. 1B motor controller over currentRead
BI1358Alarm 58:3 Extract air fan no. 1B motor controller under voltageRead
BI1359Alarm 58:4 Extract air fan no. 1B motor controller over voltageRead
BI1360Alarm 58:5 Extract air fan no. 1B motor controller over temperatureRead
BI1361Alarm 58:6 Extract air fan no. 1B motor controller start errorRead
BI1362Alarm 58:7 Extract air fan no. 1B motor controller ripple errorRead
BI1363Alarm 58:8 Extract air fan no. 1B motor controller phase errorRead
BI1364Alarm 58:9 Extract air fan no. 1B motor controller internal memory errorRead
BI1365Alarm 58:10 Extract air fan no. 1B motor controller current reductionRead
BI1371Alarm 59:1 Extract air fan no. 2B com. errorRead
BI1372Alarm 59:2 Extract air fan no. 2B motor controller over currentRead
BI1373Alarm 59:3 Extract air fan no. 2B motor controller under voltageRead
BI1374Alarm 59:4 Extract air fan no. 2B motor controller over voltageRead
BI1375Alarm 59:5 Extract air fan no. 2B motor controller over temperatureRead
BI1376Alarm 59:6 Extract air fan no. 2B motor controller start errorRead
BI1377Alarm 59:7 Extract air fan no. 2B motor controller ripple errorRead
BI1378Alarm 59:8 Extract air fan no. 2B motor controller phase errorRead
BI1379Alarm 59:9 Extract air fan no. 2B motor controller internal memory errorRead
BI1380Alarm 59:10 Extract air fan no. 2B motor controller current reductionRead
BI1386Alarm 60:1 Extract air fan no. 3B com. errorRead
BI1387Alarm 60:2 Extract air fan no. 3B motor controller over currentRead
BI1388Alarm 60:3 Extract air fan no. 3B motor controller under voltageRead
BI1389Alarm 60:4 Extract air fan no. 3B motor controller over voltageRead
BI1390Alarm 60:5 Extract air fan no. 3B motor controller over temperatureRead
BI1391Alarm 60:6 Extract air fan no. 3B motor controller start errorRead
BI1392Alarm 60:7 Extract air fan no. 3B motor controller ripple errorRead
BI1393Alarm 60:8 Extract air fan no. 3B motor controller phase errorRead
BI1394Alarm 60:9 Extract air fan no. 3B motor controller internal memory errorRead
BI1395Alarm 60:10 Extract air fan no. 3B motor controller current reductionRead
BI1952Info 97:12 Plate heat exchanger bypass optimization not performedRead
BI1953Info 97:13 Plate heat exchanger bypass optimization not approvedRead
BI1954Info 97:14 Plate heat exchanger defrost calibration not performedRead
BI1955Info 97:15 Plate heat exchanger defrost calibration not approvedRead
BI1956Info 98:1 Supply air pre-filter calibration not performedRead
BI1957Info 98:2 Supply air pre-filter calibration not approvedRead
BI1958Info 98:3 Extract air pre-filter calibration not performedRead
BI1959Info 98:4 Extract air pre-filter calibration not approvedRead
BI1960Info 98:5 Supply air air handling unit filter calibration not performedRead
BI1961Info 98:6 Supply air air handling unit filter calibration not approvedRead
BI1962Info 98:7 Extract air air handling unit filter calibration not performedRead
BI1963Info 98:8 Extract air air handling unit filter calibration not approvedRead
BI1964Info 98:9 Supply air end filter calibration not performedRead
BI1965Info 98:10 Supply air end filter calibration not approvedRead
BI1966Info 98:11 Rotary heat exchanger defrost calibration not performedRead
BI1967Info 98:12 Rotary heat exchanger defrost calibration not approvedRead
BI1968Info 98:13 ReCO2 calibration not performedRead
BI1969Info 98:14 ReCO2 calibration not approvedRead
BI1970Info 98:15 ReCO2 incorrect settingRead
BI1971Info 99:1 E-mail errorRead
BI1977Info 99:7 SD card memory soon full. Oldest log data will soon be deletedRead
BI1978Info 99:8 SD card memory full. Oldest log data deletedRead
BI1984Info 99:14 Internal serial memory error CPU 1Read
BI1985Info 99:15 Clock circuit defectiveRead
BI2001Active alarm group 1Read
BI2002Active alarm group 2Read
BI2003Active alarm group 3Read
BI2004Active alarm group 4Read
BI2005Active alarm group 5Read
BI2006Active alarm group 6Read
BI2007Active alarm group 7Read
BI2008Active alarm group 8Read
BI2009Active alarm group 9Read
BI2010Active alarm group 10Read
BI2011Active alarm group 11Read
BI2012Active alarm group 12Read
BI2013Active alarm group 13Read
BI2014Active alarm group 14Read
BI2015Active alarm group 15Read
BI2016Active alarm group 16Read
BI2017Active alarm group 17Read
BI2018Active alarm group 18Read
BI2019Active alarm group 19Read
BI2020Active alarm group 20Read
BI2021Active alarm group 21Read
BI2022Active alarm group 22Read
BI2023Active alarm group 23Read
BI2024Active alarm group 24Read
BI2025Active alarm group 25Read
BI2026Active alarm group 26Read
BI2027Active alarm group 27Read
BI2028Active alarm group 28Read
BI2029Active alarm group 29Read
BI2030Active alarm group 30Read
BI2031Active alarm group 31Read
BI2032Active alarm group 32Read
BI2033Active alarm group 33Read
BI2034Active alarm group 34Read
BI2035Active alarm group 35Read
BI2036Active alarm group 36Read
BI2037Active alarm group 37Read
BI2038Active alarm group 38Read
BI2039Active alarm group 39Read
BI2040Active alarm group 40Read
BI2041Active alarm group 41Read
BI2042Active alarm group 42Read
BI2043Active alarm group 43Read
BI2044Active alarm group 44Read
BI2045Active alarm group 45Read
BI2046Active alarm group 46Read
BI2047Active alarm group 47Read
BI2048Active alarm group 48Read
BI2049Active alarm group 49Read
BI2050Active alarm group 50Read
BI2051Active alarm group 51Read
BI2052Active alarm group 52Read
BI2053Active alarm group 53Read
BI2054Active alarm group 54Read
BI2055Active alarm group 55Read
BI2056Active alarm group 56Read
BI2057Active alarm group 57Read
BI2058Active alarm group 58Read
BI2059Active alarm group 59Read
BI2060Active alarm group 60Read
BI2061Active alarm group 61Read
BI2062Active alarm group 62Read
BI2063Active alarm group 63Read
BI2064Active alarm group 64Read
BI2065Active alarm group 65Read
BI2066Active alarm group 66Read
BI2067Active alarm group 67Read
BI2068Active alarm group 68Read
BI2069Active alarm group 69Read
BI2070Active alarm group 70Read
BI2071Active alarm group 71Read
BI2072Active alarm group 72Read
BI2073Active alarm group 73Read
BI2074Active alarm group 74Read
BI2075Active alarm group 75Read
BI2076Active alarm group 76Read
BI2077Active alarm group 77Read
BI2078Active alarm group 78Read
BI2079Active alarm group 79Read
BI2080Active alarm group 80Read
BI2081Active alarm group 81Read
BI2082Active alarm group 82Read
BI2083Active alarm group 83Read
BI2084Active alarm group 84Read
BI2085Active alarm group 85Read
BI2086Active alarm group 86Read
BI2087Active alarm group 87Read
BI2088Active alarm group 88Read
BI2089Active alarm group 89Read
BI2090Active alarm group 90Read
BI2091Active alarm group 91Read
BI2092Active alarm group 92Read
BI2093Active alarm group 93Read
BI2094Active alarm group 94Read
BI2095Active alarm group 95Read
BI2096Active alarm group 96Read
BI2097Active alarm group 97Read
BI2098Active alarm group 98Read
BI2099Active alarm group 99Read
BO1Booster diffusersBooster diffusers function.Write
BVmin1Alarm resetResets all active alarmsWrite
BV3Internal fire alarm functionWrite
BV29SA flow pressure sensor auto zero calibrationWrite
BV30EA flow pressure sensor auto zero calibrationWrite
BV31SA duct pressure sensor auto zero calibrationWrite
BV32EA duct pressure sensor auto zero calibrationWrite
BV33ReCO2 pressure sensor auto zero calibrationWrite
BV34RHX defrost pressure sensor auto calibrationWrite
BV35Carry over control pressure sensor auto calibrationWrite
BV36SA filter pressure sensor auto zero calibrationWrite
BV37EA filter pressure sensor auto zero calibrationWrite
BV38SA pre-filter pressure sensor auto zero calibrationWrite
BV39EA pre-filter pressure sensor auto zero calibrationWrite
BV40SA end-filter pressure sensor auto zero calibrationWrite
BV46SA flow pressure sensor activate zero calibrationIf value is set to 1 for min 1s calibration will beWrite
BV47EA flow pressure sensor activate zero calibrationWrite
BV48SA duct pressure sensor activate zero calibrationWrite
BV49EA duct pressure sensor activate zero calibrationWrite
BV50ReCO2 pressure sensor activate calibrationWrite
BV51RHX Defrost pressure sensor activate calibrationWrite
BV52Carry over control pressure sensor activate zero calibrationWrite
BV53SA filter pressure sensor activate zero calibrationWrite
BV54EA filter pressure sensor activate zero calibrationWrite
BV55SA pre-filter pressure sensor activate zero calibrationWrite
BV56EA pre-filter pressure sensor activate zero calibrationWrite
BV57SA end-filter pressure sensor activate zero calibrationWrite
BV162External room sensor 1 functionWrite
BV163External room sensor 2 functionWrite
BV164External room sensor 3 functionWrite
BV165External room sensor 4 functionWrite
BV167External room temp from BMS functionWrite
BV172External OA sensor 1 functionWrite
BV173External OA sensor 2 functionWrite
BV174External OA sensor 3 functionWrite
BV175External OA sensor 4 functionWrite
BV177External OA temp from BMS functionWrite
BV182RHX defrost functionSetting for activating the defrost function for the rotary heatWrite
BV183RHX defrost calibrationWrite
BV187RHX carry over control functionSetting for activating the carry over control function for the rotary heatWrite
BV190RHX min exhaust air temp functionWrite
BV198PHX periodic operation of bypass damper functionWrite
BV201PX bypass optimizeWrite
BV205CHX periodic operation of pump functionWrite
BV206CHX periodic operation of valve functionWrite
BV228Re-heat periodic operation of pump functionWrite
BV229Re-heat periodic operation of valve functionWrite
BV245Extra regulation 1 periodic operation of pump functionWrite
BV246Extra regulation 1 periodic operation of valve functionWrite
BV274Cool relay 1 periodic operation of pump functionWrite
BV275Cool relay 2 periodic operation of pump functionWrite
BV276Cool periodic operation of valve functionWrite
BV284Summer night cool functionWrite
BV296Intermittent night heat functionWrite
BV302Intermittent night heat recirculation functionWrite
BV305Morning boost functionWrite
BV320Heating boost functionWrite
BV325Xzone heat functionWrite
BV327Xzone cool functionWrite
BV374Xzone external room sensor 1 functionWrite
BV375Xzone external room sensor 2 functionWrite
BV376Xzone external room sensor 3 functionWrite
BV377Xzone external room sensor 4 functionWrite
BV379Xzone external room temp from BMS functionWrite
BV386Xzone reheat periodic operation of pump functionWrite
BV387Xzone reheat periodic operation of valve functionWrite
BV400Xzone Cool relay 1 periodic operation of pump functionWrite
BV401Xzone Cool relay 2 periodic operation of pump functionWrite
BV402Xzone Cool periodic operation of valve functionWrite
BV410Pre-heat functionWrite
BV414Pre-heat periodic operation of pump functionWrite
BV415Pre-heat periodic operation of valve functionWrite
BV425ReCO2 CalibrationWrite
BV457Dehumidifying functionMoved to Multistate Value 457Write
BV459Heat exchange active in dehumidifying sequenceWrite
BV465VOC sensor functionWrite
BV490SMART Link WB Optimize functionWrite
BV504AQUA Link FunctionWrite
BV530AYC Heated water periodic operation of pumpWrite
BV531AYC Heated water periodic operation of valveWrite
BV536AYC Heated water OA temp compensationWrite
BV547AYC Heated water room temp compensation functionWrite
BV548AYC Heated water room temp compensation at nightWrite0=Enabled during night, 1=Disabled during night
BV553AYC Heated water night temp compensation functionWrite
BV579AYC Chilled water periodic operation of pumpWrite
BV580AYC Chilled water periodic operation of valveWrite
BV585AYC Chilled water OA temp compensationWrite
BV596AYC Chilled water room temp compensation functionWrite
BV597AYC Chilled water room temp compensation at nightWrite0=Enabled during night, 1=Disabled during night
BV602AYC Chilled water night temp compensation functionWrite
BV618AYC Chilled water dew point compensation air flow boostWrite
BV637Optimize functionWrite
MI2Application id/AHU TypeRead1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX
MI3Air flow directionRead1=Fan no.2 as SA, 2=Fan no.1 as SA
MI115PHX typeRead1=PHX-1 1D HS (one damper and humidity sensor), 2=PHX-2 3D (three dampers), 3=PHX-3 1D 1PS (one damper and pressure sensor)
MI140Extra regulation sequence 1 coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI142Extra regulation sequence 2 coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI152Re-heat coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI163Cool coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI198Xzone heat, coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI209Xzone cool, coil typeRead1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used
MI224Pre-heat coil typeRead1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric
MI320SMART Link, DX cool modeRead1=Heat, 2=Cool
MImin592Operation levelRead1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation(1.11), 15=Morning boost stop(1.11), 16=Intermittent night heat stop(1.11), 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment(1.12)
MO1Boost Supply airWrite1=Off, 2=On
MO2Boost Extract airWrite1=Off, 2=On
MV1SA Fan regulation modeSetting of regulation type for the supply air fan.Write1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan
MV2EA Fan regulation modeSetting of regulation type for the extract air fan.Write1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan
MV4Internal fire alarm reset functionWrite1=Manual reset, 2=Auto reset
MV7External fire alarm no. 1 reset functionWrite1=Manual reset, 2=Auto reset
MV8External fire alarm no. 2 reset functionWrite1=Manual reset, 2=Auto reset
MV11External alarm no. 1 reset functionWrite1=Manual reset, 2=Auto reset
MV12External alarm no. 2 reset functionWrite1=Manual reset, 2=Auto reset
MV15External alarm no. 1 input functionWrite1=Alarm at closed contact, 2=Alarm at open contact
MV16External alarm no. 2 input functionWrite1=Alarm at closed contact, 2=Alarm at open contact
MV53Outdoor temp compensation functionWrite1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed
MV78Down regulation functionWrite1=Inactive, 2=SA, 3=SA and EA
MV84Fans in operation at fire alarm 1 functionWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV87Fans in operation at fire alarm 2 functionWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV90Fans in operation at internal fire alarm functionWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV95Pre-filter functionWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV96Pre-filter calibrationWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV101AHU filter functionWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV102AHU filter calibrationWrite1=Inactive, 2=SA, 3=EA, 4=SA and EA
MV107SA end filter functionWrite1=Inactive, 2=SA
MV108SA end filter calibrationWrite1=Inactive, 2=SA
MV115Temperature regulation modeWrite1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE
MV166External room sensors measurement functionWrite1=Average, 2=Min, 3=Max
MV176External OA sensors measurement functionWrite1=Average, 2=Min, 3=Max
MV188RHX sorption rotor functionSetting for activating the sorption rotor control function for the rotary heatWrite1=Inactive, 2=Sorption max at cool, 3=Sorption always max
MV237Extra regulation sequence 1 functionState textWrite1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool
MV238Extra regulation sequence 1 output functionWrite1=0-10V, 2=10-0V
MV251Extra regulation 1 temperature protection functionWrite1=Inactive, 2=Active
MV254Season heat functionWrite1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode
MV255Season heat manual settingWrite1=Re-heat, 2=Extra regulation sequence
MV261Cool on/off regulation functionWrite1=Inactive, 2=1 step, 3=2 steps, 4=3 steps
MV313Cooling boost functionWrite1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence
MV329Xzone temperature regulation modeWrite1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE
MV378Xzone external room sensors measurement functionWrite1=Average, 2=Min, 3=Max
MV395Xzone Cool on/off regulation functionWrite1=Inactive, 2=1 step, 3=2 steps, 4=3 steps
MV423ReCO2-CO2 functionWrite1=Inactive, 2=CO2, 3=CO2 and air flow boost
MV424ReCO2 temperature regulation sequence functionWrite1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool
MV441Humidifying functionWrite1=Inactive, 2=On/Off, 3=0-10V
MV442Humidifying sensorWrite1=SA, 2=EA
MV457DeHumidifying functionWrite0=Inactive, 1=SA, 2=EA
MV469COOL DX FunctionWrite1=Inactive, 2=Economy, 3=Comfort, 4=Top
MV481SMART Link FunctionWrite1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible
MV505AQUA Link Pump alarm functionWrite1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function)
MV521AYC FunctionWrite1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water
MV528AYC Heated water signal monitor function for pumpWrite1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function
MV555AYC Heated water night temp compensation time 1 (days)Write1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday
MV562AYC Heated water night temp compensation time 2 (days)Write1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday
MV577AYC Chilled water signal monitor function for pumpWrite1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function
MV604AYC Chilled water night temp compensation time 1 (days)Write1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday
MV611AYC Chilled water night temp compensation time 2 (days)Write1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday
MV660MIRU Control 1 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV661MIRU Control 2 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV662MIRU Control 3 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV663MIRU Control 4 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV664MIRU Control 5 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV665MIRU Control 6 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV666MIRU Control 7 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV667MIRU Control 8 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV668MIRU Control 9 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV669MIRU Control 10 functionWrite1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed
MV671MIRU Control 1 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV679MIRU Control 2 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV687MIRU Control 3 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV695MIRU Control 4 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV703MIRU Control 5 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV711MIRU Control 6 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV719MIRU Control 7 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV727MIRU Control 8 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV735MIRU Control 9 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MV743MIRU Control 10 Balanced air flow functionWrite1=Inactive, 2=SA, 3=EA
MVmin793Communication operation levelWrite1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop
CAL0Calendar #1Date list, up to 10 datesWrite
CAL1Calendar #2Date list, up to 10 datesWrite
NC0NC 00 A-AlarmNotification class for AHU A-alarmsRead
NC1NC 01 B-AlarmNotification class for AHU B-alarmsRead
NC3NC 03 Alarms specified in BACnetNotification class for alarms set in BACnet objectsRead
NC10NC 10 Info messageNotification class for AHU info messagesRead
NC11NC 11 Events specified in BACnetNotification class for events set in BACnet objectsRead
SCH0Schedule #1Weekly schedule, 6 time-values per day, 2 exceptionsWrite1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation E (RX/PX/CX/SD) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP

How many BACnet points does the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP have?

This list has 1452 BACnet objects: 356 analog inputs, 1 analog output, 357 analog values, 554 binary inputs, 1 binary output, 91 binary values, 2 calendars, 12 multi-state inputs, 2 multi-state outputs, 5 notification classs, 1 schedule, 70 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points are writable?

525 of the 1452 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet documentation?

The source is BACnet IP GOLD RX/PX/CX/SD, Generation E (GOLD_E_BACnet_150316), revision 2015-03-16, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-e-2013-2017/functions/_en/gold_e_bacnet_150316.pdf.

What are the minimum BACnet points to integrate the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?

Start with MV 793 Communication operation level (BMS start/stop and speed command); AV 132 SA temperature set point (Supply air temperature setpoint); AV 135 EA/Room temperature set point (Extract/room temperature setpoint); BV 1 Alarm reset (Resets all active alarms); MI 592 Operation level (Actual operating state and who stopped the unit); AI 64 SA Temperature (Supply air temperature); AI 66 EA Temperature (Extract air temperature); AI 73 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 13 A-alarm active (Any A-class alarm); BI 14 B-alarm active (Any B-class alarm).

How do I enable BMS control of the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?

MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.

Can the BMS supply sensor values to the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?

Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).

How do I check these points on the real GOLD generation E (RX/PX/CX/SD) BACnet IP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Swegon BACnet points lists

Source: BACnet IP GOLD RX/PX/CX/SD, Generation E · GOLD_E_BACnet_150316 · rev. 2015-03-16. Object names, instances and units are reproduced as published; descriptions are our own.