Air handling unit controller · BACnet points list
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points list
Updated 28 October 2026
The built-in IQlogic controller in Swegon GOLD generation E air handlers is a native BACnet IP device (B-AAC profile) with no gateway needed. It publishes over 1,400 objects: fan airflow/pressure readings and setpoints, temperatures and regulation levels, heat-exchanger and coil data, accessory functions (Xzone, SMART Link, AYC, MIRU, COOL DX), one binary input per alarm, plus calendars, a schedule and notification classes for intrinsic alarming. The unit is started, stopped and speed-selected from the BMS through a single multistate value.
This page lists 1452 BACnet objects for the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP — 525 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- GOLD generation E (RX/PX/CX/SD) BACnet IP
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 1452 (525 writable)
- Transport
- BACnet IP
- Firmware
- Program version 1.10 or later (driver in PV 1.16)
- Also known as
- GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316
BMS integration notes: Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
Command the unit with MV-793 Communication operation level (Auto lets the internal time channel run it; other states force stop, low or high speed) and read back MI-592 Operation level plus the low/high speed BIs. Adjust the main temperature setpoints (AV-132 supply, AV-135 extract/room) and airflow or pressure setpoints for low and high speed, and monitor BI-13/14 for A/B alarms with BV-1 to reset. The object summary on page 3 of the source lists these as the key points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 793 | Communication operation level | BMS start/stop and speed command | Write |
| AV 132 | SA temperature set point | Supply air temperature setpoint | Write |
| AV 135 | EA/Room temperature set point | Extract/room temperature setpoint | Write |
| BV 1 | Alarm reset | Resets all active alarms | Write |
| MI 592 | Operation level | Actual operating state and who stopped the unit | Read |
| AI 64 | SA Temperature | Supply air temperature | Read |
| AI 66 | EA Temperature | Extract air temperature | Read |
| AI 73 | Outdoor temperature | Outdoor air temp measured by the unit, °C | Read |
| BI 13 | A-alarm active | Any A-class alarm | Read |
| BI 14 | B-alarm active | Any B-class alarm | Read |
Enable & remote start
MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.
Sensors & values from the BMS
Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).
Network setup
- BACnet IP only; the device is a B-AAC with intrinsic alarming (notification classes NC-0, 1, 3, 10, 11).
- Swegon also publishes a BACnet PICS and an EDE file for GOLD; device instance and IP settings are not given in this document.
Watch out for
- Calibration BVs (29-56) trigger pressure-sensor zero calibration.
- Setpoints are split by low and high speed (e.g. AV-3/5 SA airflow, AV-19/21 SA duct pressure); write the one for the active speed.
- Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is installed.
- Schedule #1 values are 1-5 (total stop to extended normal stop) with up to 6 time-values a day.
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Component name | Read | 25=IQlogic | ||
| AI | 4 | SA Air flow | Present supply air flow. | l/s | Read | |
| AI | 5 | SA Air flow regulator | Present supply air flow regulator set point. | l/s | Read | |
| AI | 6 | EA Air flow | Present extract air flow. | l/s | Read | |
| AI | 7 | EA Air flow regulator | Present extract air flow regulator set point. | l/s | Read | |
| AI | 8 | SA Duct pressure | Present supply air duct pressure. | Pa | Read | |
| AI | 9 | SA Duct pressure regulator | Present supply air duct pressure regulator set point. | Pa | Read | |
| AI | 10 | EA Duct pressure | Present extract air duct pressure. | Pa | Read | |
| AI | 11 | EA Duct pressure regulator | Present extract air duct pressure regulator set point. | Pa | Read | |
| AI | 12 | Demand input level | Present input signal for demand regulation. | % | Read | |
| AI | 13 | Demand regulator | Present demand regulator set point. | % | Read | |
| AI | 14 | SA Air flow pressure | Present air flow pressure in the supply air fan inlet. | Pa | Read | |
| AI | 15 | EA Air flow pressure | Present air flow pressure in the extract air fan inlet. | Pa | Read | |
| AI | 23 | SA Pre-filter pressure level | Present supply air pre-filter pressure drop. | Pa | Read | |
| AI | 24 | SA Pre-filter pressure alarm limit | Present supply air pre-filter pressure alarm limit. | Pa | Read | |
| AI | 25 | EA Pre-filter pressure level | Present extract air pre-filter pressure drop. | Pa | Read | |
| AI | 26 | EA Pre-filter pressure alarm limit | Present extract air pre-filter pressure alarm limit. | Pa | Read | |
| AI | 27 | SA AHU filter pressure level | Present supply air filter pressure drop. | Pa | Read | |
| AI | 28 | SA AHU filter pressure alarm limit | Present supply air filter pressure alarm limit. | Pa | Read | |
| AI | 29 | EA AHU filter pressure level | Present extract air filter pressure drop. | Pa | Read | |
| AI | 30 | EA AHU filter pressure alarm limit | Present extract air filter pressure alarm limit. | Pa | Read | |
| AI | 31 | SA End-filter pressure level | Present supply air end-filter pressure drop. | Pa | Read | |
| AI | 32 | SA End-filter pressure alarm limit | Present supply air end-filter pressure alarm limit. | Pa | Read | |
| AI | 37 | SA Fan level | Present fan speed level of the supply air fan. | % | Read | |
| AI | 38 | EA Fan level | Present fan speed level of the extract air fan. | % | Read | |
| AI | 39 | SA Fan speed | Present fan speed level of the supply air fan. | rpm | Read | |
| AI | 40 | EA Fan speed | Present fan speed level of the extract air fan. | rpm | Read | |
| AI | 41 | SA Voltage | Present voltage level of the supply air fan. | V | Read | |
| AI | 42 | EA Voltage | Present voltage level of the extract air fan. | V | Read | |
| AI | 43 | SA Fan current | Present current level of the supply air fans. | A | Read | |
| AI | 44 | EA Fan current | Present current level of the extract air fans. | A | Read | |
| AI | 45 | SA Fan power | Present power level of the supply air fans. | kW | Read | |
| AI | 46 | EA Fan power | Present power consumption level of the extract air fans. | kW | Read | |
| AI | 47 | SA Fan kWh | Total power consumption of the supply air fans. | kWh | Read | |
| AI | 48 | EA Fan kWh | Total power consumption level of the extract air fans. | kWh | Read | |
| AI | 49 | SA Fan MWh | Total power consumption of the supply air fans. | MWh | Read | |
| AI | 50 | EA Fan MWh | Total power consumption level of the extract air fans. | MWh | Read | |
| AI | 51 | SA Fan operation time | Total operation time of the supply air fan presented in days (24h). | days | Read | |
| AI | 52 | EA Fan operation time | Total operation time of the extract air fan presented in days (24h). | days | Read | |
| AI | 55 | SA Fan min air flow | Supply air AHU min air flow | l/s | Read | |
| AI | 56 | EA Fan min air flow | Extract air AHU min air flow | l/s | Read | |
| AI | 57 | SA Fan max air flow | Supply air AHU max air flow | l/s | Read | |
| AI | 58 | EA Fan max air flow | Extract air AHU max air flow | l/s | Read | |
| AI | 63 | SFP | Calculated SFP level. | kW/m3/s | Read | |
| AImin | 64 | SA Temperature | Present supply air temperature. | °C | Read | |
| AI | 65 | SA-D Temperature | Present supply air density temperature. | °C | Read | |
| AImin | 66 | EA Temperature | Present extract air temperature in the unit. | °C | Read | |
| AI | 67 | EA-D Temperature | Present extract air density temperature. | °C | Read | |
| AI | 68 | EA Regulation temperature | Present extract air temperature used for regulation. | °C | Read | |
| AI | 69 | EA Temperature PX/CX | Present extract air temperature in the unit (only AHU type PX/CX). | °C | Read | |
| AI | 70 | EA Temperature SD | Present extract air temperature in the unit (only AHU type SD). | °C | Read | |
| AI | 72 | Outdoor temperature COOL DX | Present outdoor air temperature in the COOL DX unit. | °C | Read | |
| AImin | 73 | Outdoor temperature | Present outdoor air temperature in the unit. | °C | Read | |
| AI | 74 | Outdoor regulation temperature | Present outdoor air temperature used for regulation. | °C | Read | |
| AI | 75 | External outdoor temperature 1 | Present external outdoor temperature of sensor 1. | °C | Read | |
| AI | 76 | External outdoor temperature 2 | Present external outdoor temperature of sensor 2. | °C | Read | |
| AI | 77 | External outdoor temperature 3 | Present external outdoor temperature of sensor 3. | °C | Read | |
| AI | 78 | External outdoor temperature 4 | Present external outdoor temperature of sensor 4. | °C | Read | |
| AI | 79 | External outdoor temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 80 | EA Duct temperature | Present extract air duct air temperature. | °C | Read | |
| AI | 81 | Room temperature 1 | Present room temperature of sensor 1. | °C | Read | |
| AI | 82 | Room temperature 2 | Present room temperature of sensor 2. | °C | Read | |
| AI | 83 | Room temperature 3 | Present room temperature of sensor 3. | °C | Read | |
| AI | 84 | Room temperature 4 | Present room temperature of sensor 4. | °C | Read | |
| AI | 85 | Room temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 87 | SA Temp regulator | Present supply air temperature regulator set point. | °C | Read | |
| AI | 88 | EA Temp regulator | Present extract air temperature regulator set point. | °C | Read | |
| AI | 90 | Cool exchanger regulator level | Present operation level of cool recovery. | % | Read | |
| AI | 91 | Heat exchanger regulator level | Present operation level of heat recovery. | % | Read | |
| AI | 92 | Extra regulation sequence 1 heat regulator level | Present level of extra regulation heat. | % | Read | |
| AI | 93 | Extra regulation sequence 1 heat output level | % | Read | ||
| AI | 94 | Reheat regulator level | Present level of reheat. | % | Read | |
| AI | 95 | Reheat output level | % | Read | ||
| AI | 96 | ReCO2 heat level | Present level of ReCO2 heat. | % | Read | |
| AI | 97 | Down regulation level | Present level of fan down regulation. | % | Read | |
| AI | 98 | Heating boost level | Present level of heating boost. | % | Read | |
| AI | 99 | Extra regulation sequence 1 cool regulator level | Present level of extra regulation cool. | % | Read | |
| AI | 100 | Extra regulation sequence 1 cool output level | Present level of extra regulation cool. | % | Read | |
| AI | 101 | Cool regulator level | Present level of cooling. | % | Read | |
| AI | 102 | Cool output level | Present level of cooling. | % | Read | |
| AI | 103 | ReCO2 cool level | Present level of ReCO2 heat. | % | Read | |
| AI | 104 | Cooling boost level | Present level of cooling boost. | % | Read | |
| AI | 105 | RHX operation level | Present speed level of the rotary heat exchanger. | % | Read | |
| AI | 106 | RHX efficiency | Calculated level of rotary heat exchanger efficiency. | % | Read | |
| AI | 107 | RHX defrost pressure level | Present pressure drop for the rotary heat exchanger. | Pa | Read | |
| AI | 108 | RHX defrost pressure alarm limit | Present pressure drop alarm limit for the | Pa | Read | |
| AI | 109 | RHX carry over control pressure level | Present pressure difference for the rotary heat exchangers purging sector. | Pa | Read | |
| AI | 111 | RHX operation time | Total operation time of the rotary heat exchanger presented in days (24h). | Days | Read | |
| AI | 116 | PX defrost pressure level | PHX-2/3: Present pressure drop for the plate heat exchanger. | Pa | Read | |
| AI | 117 | PHX-3D Bypass output | PHX-1: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 118 | PHX-3D Bypass input | PHX-1: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 119 | PHX-3D Bypass temperature 1 | PHX-1: Present bypass temperature sensor 1 in plate heat exchanger. | °C | Read | |
| AI | 120 | PHX-3D Bypass temperature 2 | PHX-1: Present bypass temperature sensor 2 in plate heat exchanger. | °C | Read | |
| AI | 121 | PX exchanger damper 1 output | PHX-2: Present level of plate heat exchanger damper 1 output. | % | Read | |
| AI | 122 | PHX-2 Damper 1 input | Present level of plate heat exchanger damper 1 input. | % | Read | |
| AI | 123 | PX exchanger damper 2 output | PHX-2: Present level of plate heat exchanger damper 2 output. | % | Read | |
| AI | 124 | PHX-2 Damper 2 input | Present level of plate heat exchanger damper 2 input. | % | Read | |
| AI | 125 | PX exchanger bypass output | PHX-2: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 126 | PX exchanger bypass feedback | PHX-2: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 127 | CHX Valve output | Present level of coil heat exchanger valve output. | % | Read | |
| AI | 128 | CHX Valve input | Present level of coil heat exchanger valve input. | % | Read | |
| AI | 129 | CHX Return water temperature | Present return water temperature for coil heat exchanger. | °C | Read | |
| AI | 130 | PHX/CHX operation time | Total operation time of the coil heat exchanger presented in days (24h). | Days | Read | |
| AI | 132 | PHX-1D Bypass output | PHX-3: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 133 | PHX-1D Bypass input | PHX-3: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 136 | PHX/CHX Humidity level | PHX-1/2: Present level of air-humidity for calculation of bypass/valve | % | Read | |
| AI | 141 | Extra regulation sequence 1 anti frost temp/overheat input | Present extra regulation anti frost temperature for water | °C | Read | |
| AI | 143 | Extra regulation sequence 2 anti frost temp/overheat input | Present extra regulation anti frost temperature for water | °C | Read | |
| AI | 146 | Extra regulation sequence 1 input level | % | Read | ||
| AI | 147 | Extra regulation sequence 1 heat operation time | Total operation time of extra regulation heat presented in days (24h). | Days | Read | |
| AI | 148 | Extra regulation sequence 1 cool operation time | Total operation time of extra regulation cool presented in days (24h). | Days | Read | |
| AI | 149 | Extra regulation sequence 2 input level | % | Read | ||
| AI | 150 | Extra regulation sequence 2 heat operation time | Total operation time of extra regulation heat presented in days (24h). | Days | Read | |
| AI | 151 | Extra regulation sequence 2 cool operation time | Total operation time of extra regulation cool presented in days (24h). | Days | Read | |
| AI | 153 | Re-heat anti frost temp/overheat input | Present anti frost temperature for water | °C | Read | |
| AI | 158 | Re-heat input level | % | Read | ||
| AI | 159 | Re-heat operation time | Total operation time of re-heat presented in days (24h). | Days | Read | |
| AI | 164 | Cool water temperature | Present cool water temperature for water cool coil. | °C | Read | |
| AI | 168 | Cool input level | % | Read | ||
| AI | 169 | Cool operation time | Total operation time of cool presented in days (24h). | Days | Read | |
| AI | 174 | Xzone SA temperature | Present supply air temperature. | °C | Read | |
| AI | 175 | Xzone EA temperature | Present extract air temperature in the unit. | °C | Read | |
| AI | 176 | Xzone EA regulation temperature | Present extract air temperature used for regulation. | °C | Read | |
| AI | 177 | Xzone Room temperature 1 | Present room temperature of sensor 1. | °C | Read | |
| AI | 178 | Xzone Room temperature 2 | Present room temperature of sensor 2. | °C | Read | |
| AI | 179 | Xzone Room temperature 3 | Present room temperature of sensor 3. | °C | Read | |
| AI | 180 | Xzone Room temperature 4 | Present room temperature of sensor 4. | °C | Read | |
| AI | 181 | Xzone Room temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 186 | Xzone SA Temp regulator | Present supply air temperature regulator set point. | °C | Read | |
| AI | 187 | Xzone EA Temp regulator | Present extract air temperature regulator set point. | °C | Read | |
| AI | 190 | Xzone re-heat regulator level | % | Read | ||
| AI | 193 | Xzone cool regulator level | % | Read | ||
| AI | 199 | Xzone heat, anti frost temp/overheat input | Present Xzone heat anti frost temperature for water | °C | Read | |
| AI | 203 | Xzone heat, output level | Present level of Xzone heat output. | % | Read | |
| AI | 204 | Xzone heat, input level | Present Xzone heat input. | % | Read | |
| AI | 205 | Xzone heat, operation time | Total operation time of Xzone heat presented in days (24h). | Days | Read | |
| AI | 210 | Xzone cool, water temperature | °C | Read | ||
| AI | 214 | Xzone cool, output level | Present level of Xzone cool. | % | Read | |
| AI | 215 | Xzone cool, input level | Present Xzone cool valve position. | % | Read | |
| AI | 216 | Xzone cool, operation time | Total operation time of Xzone cool presented in days (24h). | Days | Read | |
| AI | 220 | Pre-heat temperature | Present pre-heat temperature. | °C | Read | |
| AI | 221 | Pre-heat temp regulator set point | Present pre-heat temperature regulator set point. | °C | Read | |
| AI | 222 | Pre-heat temp regulator level | Read | |||
| AI | 225 | Pre-heat anti frost temp/overheat input | Present pre-heat anti frost temperature for water | °C | Read | |
| AI | 228 | Pre-heat output level | Present pre-heat output level. | % | Read | |
| AI | 229 | Pre-heat input level | Present pre-heat input level. | % | Read | |
| AI | 230 | Pre-heat operation time | Total operation time of pre-heat presented in days (24h). | Days | Read | |
| AI | 233 | ReCO2 recirculation damper output | Present output signal to the recirculation damper. | % | Read | |
| AI | 234 | ReCO2 recirculation damper input | Present input signal from the recirculation damper. | % | Read | |
| AI | 235 | ReCO2 outdoor damper output | Present output signal to the outdoor air damper. | % | Read | |
| AI | 236 | ReCO2 outdoor damper input | Present input signal from the outdoor air damper. | % | Read | |
| AI | 237 | ReCO2 outdoor air flow | Present outdoor air flow level. | l/s | Read | |
| AI | 238 | ReCO2 outdoor air flow regulator set point | Present outdoor air flow regulator set point. | l/s | Read | |
| AI | 244 | SA humidity level | Present level of supply air humidity | %RH | Read | |
| AI | 245 | SA humidity temperature | Present temperature inside the supply air humidity sensor. | °C | Read | |
| AI | 246 | SA dew point | Calculated supply air dew point. | °C | Read | |
| AI | 247 | EA humidity level | Present level of extract air humidity. | %RH | Read | |
| AI | 248 | EA humidity temperature | Present temperature inside the extract air humidity sensor. | °C | Read | |
| AI | 249 | EA dew point | Calculated extract air dew point. | °C | Read | |
| AI | 251 | Dehumidifying SA dew point regulator set point | Present supply air dew point regulator point. | °C | Read | |
| AI | 252 | Dehumidifying output level | Present level of the dehumidifying output. | % | Read | |
| AI | 254 | Humidifying SA regulator set point | %RH | Read | ||
| AI | 255 | Humidifying output level | Present level of the dehumidifying output. | % | Read | |
| AI | 266 | VOC level | Present level of VOC | ppm | Read | |
| AI | 271 | COOL DX, unit power size | Read | |||
| AI | 274 | COOL DX, compressor 1 low pressure level | Bar | Read | ||
| AI | 275 | COOL DX, compressor 1 high pressure level | Bar | Read | ||
| AI | 276 | COOL DX, compressor 2 low pressure level | Bar | Read | ||
| AI | 277 | COOL DX, compressor 2 high pressure level | Bar | Read | ||
| AI | 289 | SMART Link, WB outlet water 1 | °C | Read | ||
| AI | 290 | SMART Link, WB outlet water 2 | °C | Read | ||
| AI | 291 | SMART Link, WB outlet water 3 | °C | Read | ||
| AI | 292 | SMART Link, WB outlet water 4 | °C | Read | ||
| AI | 293 | SMART Link, WB outlet water average | °C | Read | ||
| AI | 294 | SMART Link, WB return water | °C | Read | ||
| AI | 297 | SMART Link WB, heated water set point | °C | Read | ||
| AI | 298 | SMART Link WB, chilled water set point | °C | Read | ||
| AI | 299 | SMART Link WB, Min heated water set point | °C | Read | ||
| AI | 300 | SMART Link WB, Max heated water set point | °C | Read | ||
| AI | 301 | SMART Link WB, Min chilled water set point | °C | Read | ||
| AI | 302 | SMART Link WB, Max chilled water set point | °C | Read | ||
| AI | 327 | SMART Link, DX unit 1 power level set point | % | Read | ||
| AI | 328 | SMART Link, DX unit 1 power level | % | Read | ||
| AI | 329 | SMART Link, DX unit 1 operation time | Days | Read | ||
| AI | 338 | SMART Link, DX unit 2 power level set point | % | Read | ||
| AI | 339 | SMART Link, DX unit 2 power level | % | Read | ||
| AI | 340 | SMART Link, DX unit 2 operation time | Days | Read | ||
| AI | 349 | SMART Link, DX unit 3 power level set point | % | Read | ||
| AI | 350 | SMART Link, DX unit 3 power level | % | Read | ||
| AI | 351 | SMART Link, DX unit 3 operation time | Days | Read | ||
| AI | 360 | SMART Link, DX unit 4 power level set point | % | Read | ||
| AI | 361 | SMART Link, DX unit 4 power level | % | Read | ||
| AI | 362 | SMART Link, DX unit 4 operation time | Days | Read | ||
| AI | 374 | AYC Heat, heated water | Present heat temperature. | °C | Read | |
| AI | 375 | AYC Heated water set point | Present heat temperature regulator set point. | °C | Read | |
| AI | 376 | AYC Heat, valve output | Present level of the heat valve output. | % | Read | |
| AI | 377 | AYC Heat, valve input | Present level of the heat valve input. | % | Read | |
| AI | 378 | AYC Heat, operation time | Total operation time of AYC heat presented in days (24h). | Days | Read | |
| AI | 379 | AYC Heated water heat demand | % | Read | ||
| AI | 387 | AYC Cool, chilled water | Present cool temperature. | °C | Read | |
| AI | 388 | AYC Chilled water set point | Present cool temperature regulator set point. | °C | Read | |
| AI | 389 | AYC Cool, valve output | Present cool of the heat valve output. | % | Read | |
| AI | 390 | AYC Cool, valve input | Present cool of the heat valve input. | % | Read | |
| AI | 391 | AYC Cool, operation time | Total operation time of AYC cool presented in days (24h). | Days | Read | |
| AI | 392 | AYC Chilled water cool demand | % | Read | ||
| AI | 400 | MIRU Control 1 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 401 | MIRU Control 1 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 402 | MIRU Control 1 Air flow | Present air flow. | l/s | Read | |
| AI | 403 | MIRU Control 1 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 404 | MIRU Control 1 Pressure | Present duct pressure. | Pa | Read | |
| AI | 405 | MIRU Control 1 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 406 | MIRU Control 1 External temperature | Present external temperature. | °C | Read | |
| AI | 407 | MIRU Control 1 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 408 | MIRU Control 1 Fan level | Present running level of the fan. | % | Read | |
| AI | 409 | MIRU Control 1 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 410 | MIRU Control 1 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 411 | MIRU Control 1 kWh | kWh value. | kWh | Read | |
| AI | 412 | MIRU Control 1 MWh | MWh value. | MWh | Read | |
| AI | 417 | MIRU Control 2 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 418 | MIRU Control 2 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 419 | MIRU Control 2 Air flow | Present air flow. | l/s | Read | |
| AI | 420 | MIRU Control 2 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 421 | MIRU Control 2 Pressure | Present duct pressure. | Pa | Read | |
| AI | 422 | MIRU Control 2 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 423 | MIRU Control 2 External temperature | Present external temperature. | °C | Read | |
| AI | 424 | MIRU Control 2 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 425 | MIRU Control 2 Fan level | Present running level of the fan. | % | Read | |
| AI | 426 | MIRU Control 2 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 427 | MIRU Control 2 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 428 | MIRU Control 2 kWh | kWh value. | kWh | Read | |
| AI | 429 | MIRU Control 2 MWh | MWh value. | MWh | Read | |
| AI | 434 | MIRU Control 3 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 435 | MIRU Control 3 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 436 | MIRU Control 3 Air flow | Present air flow. | l/s | Read | |
| AI | 437 | MIRU Control 3 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 438 | MIRU Control 3 Pressure | Present duct pressure. | Pa | Read | |
| AI | 439 | MIRU Control 3 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 440 | MIRU Control 3 External temperature | Present external temperature. | °C | Read | |
| AI | 441 | MIRU Control 3 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 442 | MIRU Control 3 Fan level | Present running level of the fan. | % | Read | |
| AI | 443 | MIRU Control 3 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 444 | MIRU Control 3 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 445 | MIRU Control 3 kWh | kWh value. | kWh | Read | |
| AI | 446 | MIRU Control 3 MWh | MWh value. | MWh | Read | |
| AI | 451 | MIRU Control 4 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 452 | MIRU Control 4 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 453 | MIRU Control 4 Air flow | Present air flow. | l/s | Read | |
| AI | 454 | MIRU Control 4 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 455 | MIRU Control 4 Pressure | Present duct pressure. | Pa | Read | |
| AI | 456 | MIRU Control 4 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 457 | MIRU Control 4 External temperature | Present external temperature. | °C | Read | |
| AI | 458 | MIRU Control 4 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 459 | MIRU Control 4 Fan level | Present running level of the fan. | % | Read | |
| AI | 460 | MIRU Control 4 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 461 | MIRU Control 4 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 462 | MIRU Control 4 kWh | kWh value. | kWh | Read | |
| AI | 463 | MIRU Control 4 MWh | MWh value. | MWh | Read | |
| AI | 468 | MIRU Control 5 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 469 | MIRU Control 5 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 470 | MIRU Control 5 Air flow | Present air flow. | l/s | Read | |
| AI | 471 | MIRU Control 5 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 472 | MIRU Control 5 Pressure | Present duct pressure. | Pa | Read | |
| AI | 473 | MIRU Control 5 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 474 | MIRU Control 5 External temperature | Present external temperature. | °C | Read | |
| AI | 475 | MIRU Control 5 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 476 | MIRU Control 5 Fan level | Present running level of the fan. | % | Read | |
| AI | 477 | MIRU Control 5 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 478 | MIRU Control 5 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 479 | MIRU Control 5 kWh | kWh value. | kWh | Read | |
| AI | 480 | MIRU Control 5 MWh | MWh value. | MWh | Read | |
| AI | 485 | MIRU Control 6 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 486 | MIRU Control 6 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 487 | MIRU Control 6 Air flow | Present air flow. | l/s | Read | |
| AI | 488 | MIRU Control 6 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 489 | MIRU Control 6 Pressure | Present duct pressure. | Pa | Read | |
| AI | 490 | MIRU Control 6 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 491 | MIRU Control 6 External temperature | Present external temperature. | °C | Read | |
| AI | 492 | MIRU Control 6 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 493 | MIRU Control 6 Fan level | Present running level of the fan. | % | Read | |
| AI | 494 | MIRU Control 6 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 495 | MIRU Control 6 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 496 | MIRU Control 6 kWh | kWh value. | kWh | Read | |
| AI | 497 | MIRU Control 6 MWh | MWh value. | MWh | Read | |
| AI | 502 | MIRU Control 7 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 503 | MIRU Control 7 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 504 | MIRU Control 7 Air flow | Present air flow. | l/s | Read | |
| AI | 505 | MIRU Control 7 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 506 | MIRU Control 7 Pressure | Present duct pressure. | Pa | Read | |
| AI | 507 | MIRU Control 7 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 508 | MIRU Control 7 External temperature | Present external temperature. | °C | Read | |
| AI | 509 | MIRU Control 7 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 510 | MIRU Control 7 Fan level | Present running level of the fan. | % | Read | |
| AI | 511 | MIRU Control 7 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 512 | MIRU Control 7 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 513 | MIRU Control 7 kWh | kWh value. | kWh | Read | |
| AI | 514 | MIRU Control 7 MWh | MWh value. | MWh | Read | |
| AI | 519 | MIRU Control 8 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 520 | MIRU Control 8 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 521 | MIRU Control 8 Air flow | Present air flow. | l/s | Read | |
| AI | 522 | MIRU Control 8 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 523 | MIRU Control 8 Pressure | Present duct pressure. | Pa | Read | |
| AI | 524 | MIRU Control 8 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 525 | MIRU Control 8 External temperature | Present external temperature. | °C | Read | |
| AI | 526 | MIRU Control 8 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 527 | MIRU Control 8 Fan level | Present running level of the fan. | % | Read | |
| AI | 528 | MIRU Control 8 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 529 | MIRU Control 8 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 530 | MIRU Control 8 kWh | kWh value. | kWh | Read | |
| AI | 531 | MIRU Control 8 MWh | MWh value. | MWh | Read | |
| AI | 536 | MIRU Control 9 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 537 | MIRU Control 9 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 538 | MIRU Control 9 Air flow | Present air flow. | l/s | Read | |
| AI | 539 | MIRU Control 9 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 540 | MIRU Control 9 Pressure | Present duct pressure. | Pa | Read | |
| AI | 541 | MIRU Control 9 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 542 | MIRU Control 9 External temperature | Present external temperature. | °C | Read | |
| AI | 543 | MIRU Control 9 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 544 | MIRU Control 9 Fan level | Present running level of the fan. | % | Read | |
| AI | 545 | MIRU Control 9 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 546 | MIRU Control 9 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 547 | MIRU Control 9 kWh | kWh value. | kWh | Read | |
| AI | 548 | MIRU Control 9 MWh | MWh value. | MWh | Read | |
| AI | 553 | MIRU Control 10 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 554 | MIRU Control 10 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 555 | MIRU Control 10 Air flow | Present air flow. | l/s | Read | |
| AI | 556 | MIRU Control 10 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 557 | MIRU Control 10 Pressure | Present duct pressure. | Pa | Read | |
| AI | 558 | MIRU Control 10 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 559 | MIRU Control 10 External temperature | Present external temperature. | °C | Read | |
| AI | 560 | MIRU Control 10 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 561 | MIRU Control 10 Fan level | Present running level of the fan. | % | Read | |
| AI | 562 | MIRU Control 10 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 563 | MIRU Control 10 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 564 | MIRU Control 10 kWh | kWh value. | kWh | Read | |
| AI | 565 | MIRU Control 10 MWh | MWh value. | MWh | Read | |
| AI | 570 | IQlogic software version | Present controller software version | Read | ||
| AI | 604 | Triggered alarm #1 | ((Alarm group - 1) x 15) + alarm number in group=Triggered alarm | Read | ||
| AI | 605 | Triggered alarm #2 | Read | |||
| AI | 606 | Triggered alarm #3 | Read | |||
| AI | 607 | Triggered alarm #4 | Read | |||
| AI | 608 | Triggered alarm #5 | Read | |||
| AI | 609 | Triggered alarm #6 | Read | |||
| AI | 610 | Triggered alarm #7 | Read | |||
| AI | 611 | Triggered alarm #8 | Read | |||
| AI | 612 | Triggered alarm #9 | Read | |||
| AI | 613 | Triggered alarm #10 | Read | |||
| AI | 614 | Triggered alarm group #1 | Zero if no triggered alarm group. | Read | ||
| AI | 615 | Triggered alarm group #2 | Read | |||
| AI | 616 | Triggered alarm group #3 | Read | |||
| AI | 617 | Triggered alarm group #4 | Read | |||
| AI | 618 | Triggered alarm group #5 | Read | |||
| AI | 619 | Triggered alarm group #6 | Read | |||
| AI | 620 | Triggered alarm group #7 | Read | |||
| AI | 621 | Triggered alarm group #8 | Read | |||
| AI | 622 | Triggered alarm group #9 | Read | |||
| AI | 623 | Triggered alarm group #10 | Read | |||
| AO | 1 | Extract air start up | Extract air start up flow. | l/s | Write | |
| AV | 3 | SA low speed air flow set point | Supply air flow set point for the unit when running in low | l/s | Write | |
| AV | 4 | EA low speed air flow set point | Extract air flow set point for the unit when running in low | l/s | Write | |
| AV | 5 | SA high speed air flow set point | Supply air flow set point for the unit when running in high | l/s | Write | |
| AV | 6 | EA high speed air flow set point | Extract air flow set point for the unit when running in high | l/s | Write | |
| AV | 7 | SA max speed air flow set point | Supply air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 8 | EA max speed air flow set point | Extract air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 9 | SA regulation zone | Supply air flow regulation zone setting in % of the present air | % | Write | |
| AV | 10 | EA regulation zone | Extract air flow regulation zone setting in % of the present air | % | Write | |
| AV | 11 | SA regulation I-time | Supply air flow regulator affection setting. | s | Write | |
| AV | 12 | EA regulation I-time | Extract air flow regulator affection setting. | s | Write | |
| AV | 19 | SA low speed pressure set point | Supply air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 20 | EA low speed pressure set point | Extract air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 21 | SA high speed pressure set point | Supply air duct pressure for the unit when running in high speed | Pa | Write | |
| AV | 22 | EA high speed pressure set point | Extract air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 23 | SA max speed pressure set point | Supply air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 24 | EA max speed pressure set point | Extract air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 25 | SA max speed output signal | Max. limit for the supply air fan speed when running in pressure | % | Write | |
| AV | 26 | EA max speed output signal | Max. limit for the extract air fan speed when running in pressure | % | Write | |
| AV | 27 | SA pressure regulation zone | Supply air pressure regulation zone setting in % of the present duct | % | Write | |
| AV | 28 | EA pressure regulation zone | Extract air pressure regulation zone setting in % of the present duct | % | Write | |
| AV | 29 | SA pressure I-time | Supply air pressure regulator affection setting. | s | Write | |
| AV | 30 | EA pressure I-time | Extract air pressure regulator affection setting. | s | Write | |
| AV | 37 | Demand low speed demand set point | Set point for the 0..10V input signal for the unit when running | % | Write | |
| AV | 38 | Demand high speed demand set point | Set point for the 0..10V input signal for the unit when running | % | Write | |
| AV | 39 | SA min speed air flow set point | Supply air flow min. limit for the unit when the low/high speed | l/s | Write | |
| AV | 40 | EA min speed air flow set point | Extract air flow min. limit for the unit when the low/high speed | l/s | Write | |
| AV | 41 | SA max speed air flow set point | Supply air flow max limit for the unit when the low/high speed | l/s | Write | |
| AV | 42 | EA max speed air flow set point | Extract air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 43 | SA demand P-band | Supply air demand regulator P-band setting. | % | Write | |
| AV | 44 | SA demand I-time | Supply air demand regulator affection setting. | s | Write | |
| AV | 50 | Slave offset factor | % | Write | ||
| AV | 54 | Outdoor temp compensation X1 | °C | Write | ||
| AV | 55 | Outdoor temp compensation X2 | °C | Write | ||
| AV | 56 | Outdoor temp compensation X3 | °C | Write | ||
| AV | 57 | Outdoor temp compensation X4 | °C | Write | ||
| AV | 58 | Outdoor temp compensation Y1 SA air flow | l/s | Write | ||
| AV | 59 | Outdoor temp compensation Y2 SA air flow | l/s | Write | ||
| AV | 60 | Outdoor temp compensation Y3 SA air flow | l/s | Write | ||
| AV | 61 | Outdoor temp compensation Y4 SA air flow | l/s | Write | ||
| AV | 62 | Outdoor temp compensation Y1 EA air flow | l/s | Write | ||
| AV | 63 | Outdoor temp compensation Y2 EA air flow | l/s | Write | ||
| AV | 64 | Outdoor temp compensation Y3 EA air flow | l/s | Write | ||
| AV | 65 | Outdoor temp compensation Y4 EA air flow | l/s | Write | ||
| AV | 66 | Outdoor temp compensation Y1 SA pressure | Pa | Write | ||
| AV | 67 | Outdoor temp compensation Y2 SA pressure | Pa | Write | ||
| AV | 68 | Outdoor temp compensation Y3 SA pressure | Pa | Write | ||
| AV | 69 | Outdoor temp compensation Y4 SA pressure | Pa | Write | ||
| AV | 70 | Outdoor temp compensation Y1 EA pressure | Pa | Write | ||
| AV | 71 | Outdoor temp compensation Y2 EA pressure | Pa | Write | ||
| AV | 72 | Outdoor temp compensation Y3 EA pressure | Pa | Write | ||
| AV | 73 | Outdoor temp compensation Y4 EA pressure | Pa | Write | ||
| AV | 79 | Down regulation neutralzone | K | Write | ||
| AV | 80 | Down regulation P-band | K | Write | ||
| AV | 81 | Down regulation I-time | s | Write | ||
| AV | 85 | SA fan speed at fire alarm 1 | % | Write | ||
| AV | 86 | EA fan speed at fire alarm 1 | % | Write | ||
| AV | 88 | SA fan speed at fire alarm 2 | % | Write | ||
| AV | 89 | EA fan speed at fire alarm 2 | % | Write | ||
| AV | 91 | SA fan speed at internal fire alarm | % | Write | ||
| AV | 92 | EA fan speed at internal fire alarm | % | Write | ||
| AV | 97 | SA pre-filter alarm limit | Pa | Write | ||
| AV | 98 | EA pre-filter alarm limit | Pa | Write | ||
| AV | 103 | SA AHU-filter alarm limit | Pa | Write | ||
| AV | 104 | EA AHU-filter alarm limit | Pa | Write | ||
| AV | 109 | SA end-filter alarm limit | Pa | Write | ||
| AV | 117 | ERS 1 step | Curve setting according to the diagram for ERS 1. | Write | ||
| AV | 118 | ERS 1 diff | Supply air temp difference setting according to the diagram for ERS 1. | K | Write | |
| AV | 119 | ERS 1 breakpoint | Breakpoint temp setting according to the diagram for ERS 1. | °C | Write | |
| AV | 122 | ERS 2 breakpoint X1 | Breakpoint X1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 123 | ERS 2 breakpoint X2 | Breakpoint X2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 124 | ERS 2 breakpoint X3 | Breakpoint X3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 125 | ERS 2 breakpoint X4 | Breakpoint X4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 126 | ERS 2 breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 127 | ERS 2 breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 128 | ERS 2 breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 129 | ERS 2 breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ERS 2. | °C | Write | |
| AVmin | 132 | SA temperature set point | Supply air temperature setting | °C | Write | |
| AVmin | 135 | EA/Room temperature set point | Extract air/room temperature setting | °C | Write | |
| AV | 136 | SA min temp set point | Supply air min. set point during EA/room | °C | Write | |
| AV | 137 | SA max temp set point | Supply air max. set point during EA/room | °C | Write | |
| AV | 138 | EA regultaion P-band | K | Write | ||
| AV | 139 | EA regultaion I-time | s | Write | ||
| AV | 142 | ORS breakpoint X1 | Breakpoint X1 setting according to the diagram for ORS. | °C | Write | |
| AV | 143 | ORS breakpoint X2 | Breakpoint X2 setting according to the diagram for ORS. | °C | Write | |
| AV | 144 | ORS breakpoint X3 | Breakpoint X3 setting according to the diagram for ORS. | °C | Write | |
| AV | 145 | ORS breakpoint X4 | Breakpoint X4 setting according to the diagram for ORS. | °C | Write | |
| AV | 146 | ORS breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORS. | °C | Write | |
| AV | 147 | ORS breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORS. | °C | Write | |
| AV | 148 | ORS breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORS. | °C | Write | |
| AV | 149 | ORS breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORS. | °C | Write | |
| AV | 152 | ORE breakpoint X1 | Breakpoint X1 setting according to the diagram for ORE. | °C | Write | |
| AV | 153 | ORE breakpoint X2 | Breakpoint X2 setting according to the diagram for ORE. | °C | Write | |
| AV | 154 | ORE breakpoint X3 | Breakpoint X3 setting according to the diagram for ORE. | °C | Write | |
| AV | 155 | ORE breakpoint X4 | Breakpoint X4 setting according to the diagram for ORE. | °C | Write | |
| AV | 156 | ORE breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORE. | °C | Write | |
| AV | 157 | ORE breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORE. | °C | Write | |
| AV | 158 | ORE breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORE. | °C | Write | |
| AV | 159 | ORE breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORE. | °C | Write | |
| AV | 168 | External room temp from BMS | °C | Write | ||
| AV | 169 | External room temp from BMS alarm time | min | Write | ||
| AV | 178 | External OA temp from BMS | °C | Write | ||
| AV | 179 | External OA temp from BMS alarm time | min | Write | ||
| AV | 184 | RHX defrost start limit | Pa | Write | ||
| AV | 188 | RHX sorption rotor function | Moved to Multistate Value 188 | Write | ||
| AV | 191 | RHX min exhaust air temp set point | °C | Write | ||
| AV | 192 | RHX min exhaust air temp P-band | K | Write | ||
| AV | 193 | RHX min exhaust air temp I-time | s | Write | ||
| AV | 199 | PHX periodic operation interval | h | Write | ||
| AV | 200 | PHX periodic operation time | min | Write | ||
| AV | 207 | CHX periodic operation interval | h | Write | ||
| AV | 208 | CHX periodic operation time | min | Write | ||
| AV | 213 | PHX/CHX Bypass defrost limit | PHX is default 3°C, CHX is default 5°C. | °C | Write | |
| AV | 214 | PHX/CHX Bypass defrost P-band | K | Write | ||
| AV | 215 | PHX/CHX Bypass defrost I-time | s | Write | ||
| AV | 220 | Heat exchange temperature regulation P-band | K | Write | ||
| AV | 221 | Heat exchange temperature regulation I-time | s | Write | ||
| AV | 222 | Cool exchange temperature regulation P-band | K | Write | ||
| AV | 223 | Cool exchange temperature regulation I-time | s | Write | ||
| AV | 226 | Re-heat P-band | K | Write | ||
| AV | 227 | Re-heat I-time | s | Write | ||
| AV | 230 | Re-heat periodic operation interval | h | Write | ||
| AV | 231 | Re-heat periodic operation time | min | Write | ||
| AV | 239 | Extra regulation sequence 1 heat max output signal | Maximum output signal setting for the extra regulation sequence. | % | Write | |
| AV | 240 | Extra regulation sequence 1 cool max output signal | Maximum output signal setting for the extra regulation sequence. | % | Write | |
| AV | 241 | Extra regulation sequence 1 heat P-band | K | Write | ||
| AV | 242 | Extra regulation sequence 1 heat I-time | s | Write | ||
| AV | 243 | Extra regulation sequence 1 cool P-band | K | Write | ||
| AV | 244 | Extra regulation sequence 1 cool I-time | s | Write | ||
| AV | 247 | Extra regulation 1 periodic operation interval | h | Write | ||
| AV | 248 | Extra regulation 1 periodic operation time | min | Write | ||
| AV | 252 | Extra regulation 1 temperature protection temperature | °C | Write | ||
| AV | 253 | Extra regulation 1 temperature protection alarm delay | min | Write | ||
| AV | 258 | Cool step 1 min supply air flow limit | l/s | Write | ||
| AV | 259 | Cool step 2 min supply air flow limit | l/s | Write | ||
| AV | 260 | Cool step 3 min supply air flow limit | l/s | Write | ||
| AV | 262 | Cool SA neutral zone | K | Write | ||
| AV | 263 | Cool EA neutral zone | K | Write | ||
| AV | 264 | Cool outdoor temp limit 1 | °C | Write | ||
| AV | 265 | Cool outdoor temp limit 2 | °C | Write | ||
| AV | 266 | Cool outdoor temp limit 3 | °C | Write | ||
| AV | 267 | Cool 0-10V min supply air flow limit | l/s | Write | ||
| AV | 268 | Cool 0-10V min extract air flow limit | l/s | Write | ||
| AV | 269 | Cool restart time | Setting of cool restart time between start-start. | min | Write | |
| AV | 270 | Cool step up delay time | Setting of on/off cooling and COOL DX time delay between steps. | min | Write | |
| AV | 271 | Cool stand still time | Setting of on/off cooling and COOL DX time delay before stop-start | min | Write | |
| AV | 272 | Cool P-band | K | Write | ||
| AV | 273 | Cool I-time | s | Write | ||
| AV | 277 | Cool periodic operation interval | h | Write | ||
| AV | 278 | Cool periodic operation time | min | Write | ||
| AV | 279 | Cool step 1 min extract air flow limit | l/s | Write | ||
| AV | 280 | Cool step 2 min extract air flow limit | l/s | Write | ||
| AV | 281 | Cool step 3 min extract air flow limit | l/s | Write | ||
| AV | 285 | Summer night cool start time (hour) | h | Write | ||
| AV | 286 | Summer night cool start time (minute) | min | Write | ||
| AV | 287 | Summer night cool stop time (hour) | h | Write | ||
| AV | 288 | Summer night cool stop time (minute) | min | Write | ||
| AV | 289 | Summer night cool OA temp start limit | °C | Write | ||
| AV | 290 | Summer night cool EA temp start limit | °C | Write | ||
| AV | 291 | Summer night cool EA temp stop limit | °C | Write | ||
| AV | 292 | Summer night cool SA temp set point | °C | Write | ||
| AV | 297 | Intermittent night heat SA flow set point | l/s | Write | ||
| AV | 298 | Intermittent night heat SA duct pressure set point | Pa | Write | ||
| AV | 299 | Intermittent night heat EA temp start limit | °C | Write | ||
| AV | 300 | Intermittent night heat EA temp stop limit | °C | Write | ||
| AV | 301 | Intermittent night heat SA temp set point | °C | Write | ||
| AV | 303 | Intermittent night heat EA flow set point | l/s | Write | ||
| AV | 304 | Intermittent night heat EA duct pressure set point | Pa | Write | ||
| AV | 306 | Morning boost start time (hour) | h | Write | ||
| AV | 307 | Morning boost start time (minute) | min | Write | ||
| AV | 308 | Morning boost air flow set point | l/s | Write | ||
| AV | 309 | Morning boost duct pressure set point | Pa | Write | ||
| AV | 314 | Cooling boost comfort start limit | K | Write | ||
| AV | 315 | Cooling boost comfort regulation speed | %/s | Write | ||
| AV | 316 | Cooling boost economy P-band | K | Write | ||
| AV | 317 | Cooling boost economy I-time | s | Write | ||
| AV | 321 | Heating boost comfort start limit | K | Write | ||
| AV | 322 | Heating boost comfort regulation speed | %/s | Write | ||
| AV | 331 | Xzone ERS 1 step | Curve setting according to the diagram for ERS 1. | Write | ||
| AV | 332 | Xzone ERS 1 diff | Supply air temp differental setting according to the diagram for ERS 1. | K | Write | |
| AV | 333 | Xzone ERS 1 breakpoint | Breakpoint temp setting according to the diagram for ERS 1. | °C | Write | |
| AV | 336 | Xzone ERS 2 breakpoint X1 | Breakpoint X1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 337 | Xzone ERS 2 breakpoint X2 | Breakpoint X2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 338 | Xzone ERS 2 breakpoint X3 | Breakpoint X3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 339 | Xzone ERS 2 breakpoint X4 | Breakpoint X4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 340 | Xzone ERS 2 breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 341 | Xzone ERS 2 breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 342 | Xzone ERS 2 breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 343 | Xzone ERS 2 breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 346 | Xzone SA temperature set point | Supply air temperature setting, for supply air temp regulation mode. | °C | Write | |
| AV | 349 | Xzone EA/Room temperature set point | Extract air/room temperature setting | °C | Write | |
| AV | 350 | Xzone SA min temp set point | Supply air min. set point during EA/room | °C | Write | |
| AV | 351 | Xzone SA max temp set point | Supply air max. set point during EA/room | °C | Write | |
| AV | 352 | Xzone EA regultaion P-band | K | Write | ||
| AV | 353 | Xzone EA regultaion I-time | s | Write | ||
| AV | 354 | Xzone ORS breakpoint X1 | Breakpoint X1 setting according to the diagram for ORS. | °C | Write | |
| AV | 355 | Xzone ORS breakpoint X2 | Breakpoint X2 setting according to the diagram for ORS. | °C | Write | |
| AV | 356 | Xzone ORS breakpoint X3 | Breakpoint X3 setting according to the diagram for ORS. | °C | Write | |
| AV | 357 | Xzone ORS breakpoint X4 | Breakpoint X4 setting according to the diagram for ORS. | °C | Write | |
| AV | 358 | Xzone ORS breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORS. | °C | Write | |
| AV | 359 | Xzone ORS breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORS. | °C | Write | |
| AV | 360 | Xzone ORS breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORS. | °C | Write | |
| AV | 361 | Xzone ORS breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORS. | °C | Write | |
| AV | 364 | Xzone ORE breakpoint X1 | Breakpoint X1 setting according to the diagram for ORE. | °C | Write | |
| AV | 365 | Xzone ORE breakpoint X2 | Breakpoint X2 setting according to the diagram for ORE. | °C | Write | |
| AV | 366 | Xzone ORE breakpoint X3 | Breakpoint X3 setting according to the diagram for ORE. | °C | Write | |
| AV | 367 | Xzone ORE breakpoint X4 | Breakpoint X4 setting according to the diagram for ORE. | °C | Write | |
| AV | 368 | Xzone ORE breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORE. | °C | Write | |
| AV | 369 | Xzone ORE breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORE. | °C | Write | |
| AV | 370 | Xzone ORE breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORE. | °C | Write | |
| AV | 371 | Xzone ORE breakpoint Y4 | °C | Write | ||
| AV | 380 | Xzone external room temp from BMS | °C | Write | ||
| AV | 381 | Xzone external room temp from BMS alarm time | min | Write | ||
| AV | 384 | Xzone reheat P-band | K | Write | ||
| AV | 385 | Xzone reheat I-time | s | Write | ||
| AV | 388 | Xzone reheat periodic operation interval | h | Write | ||
| AV | 389 | Xzone reheat periodic operation time | min | Write | ||
| AV | 396 | Xzone Cool SA neutral zone | K | Write | ||
| AV | 397 | Xzone Cool EA neutral zone | K | Write | ||
| AV | 398 | Xzone Cool P-band | K | Write | ||
| AV | 399 | Xzone Cool I-time | s | Write | ||
| AV | 403 | Xzone Cool periodic operation interval | h | Write | ||
| AV | 404 | Xzone Cool periodic operation time | min | Write | ||
| AV | 411 | Pre-heat temperature set point | °C | Write | ||
| AV | 412 | Pre-heat P-band | K | Write | ||
| AV | 413 | Pre-heat I-time | s | Write | ||
| AV | 416 | Pre-heat periodic operation interval | h | Write | ||
| AV | 417 | Pre-heat periodic operation time | min | Write | ||
| AV | 426 | ReCO2-CO2 set point | % | Write | ||
| AV | 427 | ReCO2 min. outdoor air | l/s | Write | ||
| AV | 428 | ReCO2 min. exhaust air | l/s | Write | ||
| AV | 429 | ReCO2-CO2 P-band | % | Write | ||
| AV | 430 | ReCO2-CO2 I-time | s | Write | ||
| AV | 431 | ReCO2-CO2 air flow boost reg. P-band | % | Write | ||
| AV | 432 | ReCO2-CO2 air flow boost reg. I-time | s | Write | ||
| AV | 433 | ReCO2 heat P-band | K | Write | ||
| AV | 434 | ReCO2 heat I-time | s | Write | ||
| AV | 435 | ReCO2 cool P-band | K | Write | ||
| AV | 436 | ReCO2 cool I-time | s | Write | ||
| AV | 443 | Humidifying on/off start level | %RH | Write | ||
| AV | 444 | Humidifying on/off stop level | %RH | Write | ||
| AV | 448 | Humidifying 0-10V set point | %RH | Write | ||
| AV | 449 | Humidifying 0-10V SA max set point | %RH | Write | ||
| AV | 450 | Humidifying 0-10V SA P-band | %RH | Write | ||
| AV | 451 | Humidifying 0-10V SA I-time | s | Write | ||
| AV | 452 | Humidifying 0-10V EA P-band | %RH | Write | ||
| AV | 453 | Humidifying 0-10V EA I-time | s | Write | ||
| AV | 458 | Dehumidifying set point | %RH | Write | ||
| AV | 470 | COOL DX Low pressure stop limit | Bar | Write | ||
| AV | 471 | COOL DX High pressure stop limit | Bar | Write | ||
| AV | 472 | COOL DX Restart time | Time setting between start - start | min | Write | |
| AV | 482 | SMART Link WB Heat temperature set point | °C | Write | ||
| AV | 483 | SMART Link WB Heat temperature heat zone | K | Write | ||
| AV | 484 | SMART Link WB Cool temperature set point | °C | Write | ||
| AV | 485 | SMART Link WB Cool temperature heat zone | K | Write | ||
| AV | 491 | SMART Link WB Optimize valve upper limit | % | Write | ||
| AV | 492 | SMART Link WB Optimize valve lower limit | % | Write | ||
| AV | 493 | SMART Link WB Optimize time delay | s | Write | ||
| AV | 494 | SMART Link WB Optimize heat regulation speed | K/s | Write | ||
| AV | 495 | SMART Link WB Optimize cool regulation speed | K/s | Write | ||
| AV | 510 | SMART Link DX Amount of units | Write | |||
| AV | 519 | SMART Link OA temp limit | °C | Write | ||
| AV | 524 | AYC Heated water temp set point | °C | Write | ||
| AV | 526 | AYC Heated water OA temp for start of pump | °C | Write | ||
| AV | 527 | AYC Heated water OA temp for stop of pump | °C | Write | ||
| AV | 532 | AYC Heated water periodic operation interval | h | Write | ||
| AV | 533 | AYC Heated water periodic operation time | min | Write | ||
| AV | 537 | AYC Heated water OA temp compensation X1 | °C | Write | ||
| AV | 538 | AYC Heated water OA temp compensation X2 | °C | Write | ||
| AV | 539 | AYC Heated water OA temp compensation X3 | °C | Write | ||
| AV | 540 | AYC Heated water OA temp compensation X4 | °C | Write | ||
| AV | 541 | AYC Heated water OA temp compensation Y1 | °C | Write | ||
| AV | 542 | AYC Heated water OA temp compensation Y2 | °C | Write | ||
| AV | 543 | AYC Heated water OA temp compensation Y3 | °C | Write | ||
| AV | 544 | AYC Heated water OA temp compensation Y4 | °C | Write | ||
| AV | 549 | AYC Heated water room temp compensation temperature | °C | Write | ||
| AV | 550 | AYC Heated water room temp compensation P-band | K | Write | ||
| AV | 554 | AYC Heated water night temp compensation temp | K | Write | ||
| AV | 556 | AYC Heated water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 557 | AYC Heated water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 558 | AYC Heated water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 559 | AYC Heated water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 563 | AYC Heated water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 564 | AYC Heated water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 565 | AYC Heated water night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 566 | AYC Heated water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 569 | AYC Heated water P-band | K | Write | ||
| AV | 570 | AYC Heated water I-time | s | Write | ||
| AV | 572 | AYC Chilled water temp set point | °C | Write | ||
| AV | 575 | AYC Chilled water OA temp for start of pump | °C | Write | ||
| AV | 576 | AYC Chilled water OA temp for stop of pump | °C | Write | ||
| AV | 581 | AYC Chilled water periodic operation interval | h | Write | ||
| AV | 582 | AYC Chilled water periodic operation time | min | Write | ||
| AV | 586 | AYC Chilled water OA temp compensation X1 | °C | Write | ||
| AV | 587 | AYC Chilled water OA temp compensation X2 | °C | Write | ||
| AV | 588 | AYC Chilled water OA temp compensation X3 | °C | Write | ||
| AV | 589 | AYC Chilled water OA temp compensation X4 | °C | Write | ||
| AV | 590 | AYC Chilled water OA temp compensation Y1 | °C | Write | ||
| AV | 591 | AYC Chilled water OA temp compensation Y2 | °C | Write | ||
| AV | 592 | AYC Chilled water OA temp compensation Y3 | °C | Write | ||
| AV | 593 | AYC Chilled water OA temp compensation Y4 | °C | Write | ||
| AV | 598 | AYC Chilledwater room temp compensation temperature | °C | Write | ||
| AV | 599 | AYC Chilled water room temp compensation P-band | K | Write | ||
| AV | 603 | AYC Chilled water night temp compensation temp | K | Write | ||
| AV | 605 | AYC Chilled water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 606 | AYC Chilled water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 607 | AYC Chilled water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 608 | AYC Chilled water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 612 | AYC Chilled water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 613 | AYC Chilled water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 614 | AYC Chilledwater night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 615 | AYC Chilled water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 619 | AYC Chilled water dew point compensation neutral zone | K | Write | ||
| AV | 620 | AYC Chilled water dew point compensation regulation speed | Percent air flow boost of each increased chilled water set point. | %/K | Write | |
| AV | 623 | AYC Chilled water P-band | K | Write | ||
| AV | 624 | AYC Chilled water I-time | s | Write | ||
| AV | 638 | Optimize SA pressure set point | Pa | Write | ||
| AV | 639 | Optimize EA pressure set point | Pa | Write | ||
| AV | 672 | MIRU Control 1 Low speed duct pressure set point | Pa | Write | ||
| AV | 673 | MIRU Control 1 High speed duct pressure set point | Pa | Write | ||
| AV | 674 | MIRU Control 1 Low speed air flow set point | l/s | Write | ||
| AV | 675 | MIRU Control 1 High speed air flow set point | l/s | Write | ||
| AV | 680 | MIRU Control 2 Low speed duct pressure set point | Pa | Write | ||
| AV | 681 | MIRU Control 2 High speed duct pressure set point | Pa | Write | ||
| AV | 682 | MIRU Control 2 Low speed air flow set point | l/s | Write | ||
| AV | 683 | MIRU Control 2 High speed air flow set point | l/s | Write | ||
| AV | 688 | MIRU Control 3 Low speed duct pressure set point | Pa | Write | ||
| AV | 689 | MIRU Control 3 High speed duct pressure set point | Pa | Write | ||
| AV | 690 | MIRU Control 3 Low speed air flow set point | l/s | Write | ||
| AV | 691 | MIRU Control 3 High speed air flow set point | l/s | Write | ||
| AV | 696 | MIRU Control 4 Low speed duct pressure set point | Pa | Write | ||
| AV | 697 | MIRU Control 4 High speed duct pressure set point | Pa | Write | ||
| AV | 698 | MIRU Control 4 Low speed air flow set point | l/s | Write | ||
| AV | 699 | MIRU Control 4 High speed air flow set point | l/s | Write | ||
| AV | 704 | MIRU Control 5 Low speed duct pressure set point | Pa | Write | ||
| AV | 705 | MIRU Control 5 High speed duct pressure set point | Pa | Write | ||
| AV | 706 | MIRU Control 5 Low speed air flow set point | l/s | Write | ||
| AV | 707 | MIRU Control 5 High speed air flow set point | l/s | Write | ||
| AV | 712 | MIRU Control 6 Low speed duct pressure set point | Pa | Write | ||
| AV | 713 | MIRU Control 6 High speed duct pressure set point | Pa | Write | ||
| AV | 714 | MIRU Control 6 Low speed air flow set point | l/s | Write | ||
| AV | 715 | MIRU Control 6 High speed air flow set point | l/s | Write | ||
| AV | 720 | MIRU Control 7 Low speed duct pressure set point | Pa | Write | ||
| AV | 721 | MIRU Control 7 High speed duct pressure set point | Pa | Write | ||
| AV | 722 | MIRU Control 7 Low speed air flow set point | l/s | Write | ||
| AV | 723 | MIRU Control 7 High speed air flow set point | l/s | Write | ||
| AV | 728 | MIRU Control 8 Low speed duct pressure set point | Pa | Write | ||
| AV | 729 | MIRU Control 8 High speed duct pressure set point | Pa | Write | ||
| AV | 730 | MIRU Control 8 Low speed air flow set point | l/s | Write | ||
| AV | 731 | MIRU Control 8 High speed air flow set point | l/s | Write | ||
| AV | 736 | MIRU Control 9 Low speed duct pressure set point | Pa | Write | ||
| AV | 737 | MIRU Control 9 High speed duct pressure set point | Pa | Write | ||
| AV | 738 | MIRU Control 9 Low speed air flow set point | l/s | Write | ||
| AV | 739 | MIRU Control 9 High speed air flow set point | l/s | Write | ||
| AV | 744 | MIRU Control 10 Low speed duct pressure set point | Pa | Write | ||
| AV | 745 | MIRU Control 10 High speed duct pressure set point | Pa | Write | ||
| AV | 746 | MIRU Control 10 Low speed air flow set point | l/s | Write | ||
| AV | 747 | MIRU Control 10 High speed air flow set point | l/s | Write | ||
| BI | 1 | Operation active | Relay output status | Read | ||
| BI | 2 | Damper operation active | Relay output status | Read | ||
| BI | 3 | Low speed operation active | Low speed operation status | Read | ||
| BI | 4 | High speed operation active | High speed operation status | Read | ||
| BI | 5 | Intermittent night heat active | Read | |||
| BI | 6 | Morning boost active | Read | |||
| BI | 7 | Heating boost active | Read | |||
| BI | 8 | Cooling boost active | Read | |||
| BI | 9 | Summer night cool active | Read | |||
| BImin | 13 | A-alarm active | Any alarm with priority class A active | Read | ||
| BImin | 14 | B-alarm active | Any alarm with priority class B active | Read | ||
| BI | 17 | HX operation active | HX status | Read | ||
| BI | 18 | HX cool recovery active | HX cool recovery status | Read | ||
| BI | 19 | HX defrost active | HX defrost status | Read | ||
| BI | 22 | RHX speed monitor signal | RHX speed monitor status | Read | ||
| BI | 27 | CHX pump output | Relay output status | Read | ||
| BI | 28 | CHX pump input | Digital input status | Read | ||
| BI | 31 | Season heat, extra regulation sequence allowed | Read | |||
| BI | 32 | Season heat, re-heat allowed | Read | |||
| BI | 33 | Extra regulation sequence 1, output | Relay output status | Read | ||
| BI | 34 | Extra regulation sequence 1, power reduction active | Read | |||
| BI | 35 | Extra regulation sequence 1, anti-frost regulation active | Read | |||
| BI | 38 | Re-heat output | Relay output status | Read | ||
| BI | 39 | Re-heat power reduction active | Read | |||
| BI | 40 | Re-heat anti-frost regulation active | Read | |||
| BI | 43 | Cool output 1 | Relay output status | Read | ||
| BI | 44 | Cool output 2 | Relay output status | Read | ||
| BI | 48 | Extra regulation sequence 2, output | Relay output status | Read | ||
| BI | 49 | Extra regulation sequence 2, power reduction active | Read | |||
| BI | 50 | Extra regulation sequence 2, anti-frost regulation active | Read | |||
| BI | 51 | Pre-heat output | Relay output status | Read | ||
| BI | 52 | Pre-heat power reduction active | Read | |||
| BI | 53 | Pre-heat anti-frost regulation active | Read | |||
| BI | 56 | Xzone heat output | Relay output status | Read | ||
| BI | 57 | Xzone heat power reduction active | Read | |||
| BI | 58 | Xzone heat anti-frost regulation active | Read | |||
| BI | 63 | Xzone cool output 1 | Relay output status | Read | ||
| BI | 64 | Xzone cool output 2 | Relay output status | Read | ||
| BI | 99 | AYC heat pump output | Relay output status | Read | ||
| BI | 100 | AYC heat pump input | Digital input status | Read | ||
| BI | 104 | Max. limit for the supply air fan speed when running in pressure regulation mo | Relay output status | Read | ||
| BI | 105 | AYC cool pump input | Digital input status | Read | ||
| BI | 109 | COOL DX compressor 1 output | Relay output status | Read | ||
| BI | 110 | COOL DX compressor 1 input | Digital input status | Read | ||
| BI | 115 | COOL DX compressor 2 output | Relay output status | Read | ||
| BI | 116 | COOL DX compressor 2 input | Digital input status | Read | ||
| BI | 319 | SMART Link, DX operation | Read | |||
| BI | 323 | SMART Link, DX unit 1 operation | Read | |||
| BI | 324 | SMART Link, DX unit 1 cool mode | Read | |||
| BI | 325 | SMART Link, DX unit 1 defrost request | Read | |||
| BI | 326 | SMART Link, DX unit 1 defrost active | Read | |||
| BI | 334 | SMART Link, DX unit 2 operation | Read | |||
| BI | 335 | SMART Link, DX unit 2 cool mode | Read | |||
| BI | 336 | SMART Link, DX unit 2 defrost request | Read | |||
| BI | 337 | SMART Link, DX unit 2 defrost active | Read | |||
| BI | 345 | SMART Link, DX unit 3 operation | Read | |||
| BI | 346 | SMART Link, DX unit 3 cool mode | Read | |||
| BI | 347 | SMART Link, DX unit 3 defrost request | Read | |||
| BI | 348 | SMART Link, DX unit 3 defrost active | Read | |||
| BI | 356 | SMART Link, DX unit 4 operation | Read | |||
| BI | 357 | SMART Link, DX unit 4 cool mode | Read | |||
| BI | 358 | SMART Link, DX unit 4 defrost request | Read | |||
| BI | 359 | SMART Link, DX unit 4 power defrost active | Read | |||
| BI | 501 | Alarm 1:1 External fire alarm no. 1 tripped | Read | |||
| BI | 502 | Alarm 1:2 External fire alarm no. 2 tripped | Read | |||
| BI | 503 | Alarm 1:3 Internal fire alarm tripped | Read | |||
| BI | 516 | Alarm 2:1 External alarm no. 1 tripped | Read | |||
| BI | 517 | Alarm 2:2 External alarm no. 2 tripped | Read | |||
| BI | 531 | Alarm 3:1 Pre-heat I/O-module no. 9 com. error | Read | |||
| BI | 532 | Alarm 3:2 Pre-heat electrical heater overheat protection tripped | Read | |||
| BI | 533 | Alarm 3:3 Pre-heat frost protection tripped | Read | |||
| BI | 534 | Alarm 3:4 Pre-heat frost protection temperature sensor defective | Read | |||
| BI | 535 | Alarm 3:5 Pre-heat temperature sensor defective | Read | |||
| BI | 536 | Alarm 3:6 Pre-heat valve monitoring tripped | Read | |||
| BI | 537 | Alarm 3:7 Pre-heat temperature below set point alarm limit | Read | |||
| BI | 538 | Alarm 3:8 Pre-heat alarm input tripped | Read | |||
| BI | 546 | Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. error | Read | |||
| BI | 547 | Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection tripped | Read | |||
| BI | 548 | Alarm 4:3 Extra reg. sequence 1 frost protection tripped | Read | |||
| BI | 549 | Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor | Read | |||
| BI | 550 | Alarm 4:5 Extra reg. sequence 1 valve monitoring tripped | Read | |||
| BI | 551 | Alarm 4:6 Extra reg. sequence 1 alarm input tripped | Read | |||
| BI | 552 | Alarm 4:7 Extra reg. sequence 1 temperature protection from com. Error | Read | |||
| BI | 554 | Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. error | Read | |||
| BI | 555 | Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection tripped | Read | |||
| BI | 556 | Alarm 4:11 Extra reg. sequence 2 frost protection tripped | Read | |||
| BI | 557 | Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor | Read | |||
| BI | 558 | Alarm 4:13 Extra reg. sequence 2 valve monitoring tripped | Read | |||
| BI | 559 | Alarm 4:14 Extra reg. sequence 2 alarm input tripped | Read | |||
| BI | 561 | Alarm 5:1 Re-heat electrical heater over heat protection tripped | Read | |||
| BI | 562 | Alarm 5:2 Re-heat frost protection tripped | Read | |||
| BI | 563 | Alarm 5:3 Re-heat frost protection temperature sensor defective | Read | |||
| BI | 564 | Alarm 5:4 Re-heat heat valve monitoring tripped | Read | |||
| BI | 576 | Alarm 6:1 Xzone I/O-module no. A com. error | Read | |||
| BI | 577 | Alarm 6:2 Xzone electrical heater overheat protection tripped | Read | |||
| BI | 578 | Alarm 6:3 Xzone frost protection tripped | Read | |||
| BI | 579 | Alarm 6:4 Xzone frost protection temperature sensor defective | Read | |||
| BI | 580 | Alarm 6:5 Xzone supply air temperature sensor defective | Read | |||
| BI | 581 | Alarm 6:6 Xzone heat valve monitoring tripped | Read | |||
| BI | 582 | Alarm 6:7 Xzone supply air temperature below set point alarm limit | Read | |||
| BI | 583 | Alarm 6:8 Xzone supply air temperature above set point alarm limit | Read | |||
| BI | 584 | Alarm 6:9 Xzone heat alarm input tripped | Read | |||
| BI | 591 | Alarm 7:1 Xzone I/O-module no. B com. error | Read | |||
| BI | 592 | Alarm 7:2 Xzone extract air temperature sensor defective | Read | |||
| BI | 593 | Alarm 7:3 Xzone cool valve monitoring tripped | Read | |||
| BI | 594 | Alarm 7:4 Xzone extract air temperature below set point alarm limit | Read | |||
| BI | 595 | Alarm 7:5 Xzone cool alarm input 1 tripped | Read | |||
| BI | 596 | Alarm 7:6 Xzone cool alarm input 2 tripped | Read | |||
| BI | 610 | Alarm 8:5 Cool valve monitoring tripped | Read | |||
| BI | 636 | Alarm 10:1 Supply air temperature sensor defective | Read | |||
| BI | 637 | Alarm 10:2 Supply air temperature sensor for density compensation defective | Read | |||
| BI | 638 | Alarm 10:3 Extract air temperature sensor defective | Read | |||
| BI | 639 | Alarm 10:4 Extract air temperature sensor for density compensation defective | Read | |||
| BI | 640 | Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def. | Read | |||
| BI | 641 | Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def. | Read | |||
| BI | 642 | Alarm 10:7 Extract air duct temperature sensor defective | Read | |||
| BI | 645 | Alarm 10:10 Outdoor air temperature sensor defective | Read | |||
| BI | 651 | Alarm 11:1 Room temperature sensor no. 1 defective | Read | |||
| BI | 652 | Alarm 11:2 Room temperature sensor no. 2 defective | Read | |||
| BI | 653 | Alarm 11:3 Room temperature sensor no. 3 defective | Read | |||
| BI | 654 | Alarm 11:4 Room temperature sensor no. 4 defective | Read | |||
| BI | 655 | Alarm 11:5 Xzone room temperature sensor no. 5 defective | Read | |||
| BI | 656 | Alarm 11:6 Xzone room temperature sensor no. 6 defective | Read | |||
| BI | 657 | Alarm 11:7 Xzone room temperature sensor no. 7 defective | Read | |||
| BI | 658 | Alarm 11:8 Xzone room temperature sensor no. 8 defective | Read | |||
| BI | 659 | Alarm 11:9 Outdoor temperature sensor no. A defective | Read | |||
| BI | 660 | Alarm 11:10 Outdoor temperature sensor no. B defective | Read | |||
| BI | 661 | Alarm 11:11 Outdoor temperature sensor no. C defective | Read | |||
| BI | 662 | Alarm 11:12 Outdoor temperature sensor no. D defective | Read | |||
| BI | 663 | Alarm 11:13 Room temperature from com. error | Read | |||
| BI | 664 | Alarm 11:14 Xzone room temperature from com. error | Read | |||
| BI | 665 | Alarm 11:15 Outdoor temperature from com. error | Read | |||
| BI | 666 | Alarm 12:1 Supply air temperature below set point alarm limit | Read | |||
| BI | 667 | Alarm 12:2 Supply air temperature above set point alarm limit | Read | |||
| BI | 671 | Alarm 12:6 Extract air temperature below alarm limit | Read | |||
| BI | 676 | Alarm 12:11 Temperature guard below alarm limit | Read | |||
| BI | 681 | Alarm 13:1 Humidification I/O-module no. 4 com. error | Read | |||
| BI | 682 | Alarm 13:2 Supply air humidity sensor defective | Read | |||
| BI | 683 | Alarm 13:3 Extract air humidity sensor defective | Read | |||
| BI | 689 | Alarm 13:9 Humidifier alarm output tripped | Read | |||
| BI | 691 | Alarm 13:11 VOC sensor com. error | Read | |||
| BI | 692 | Alarm 13:12 VOC sensor internal com. error | Read | |||
| BI | 693 | Alarm 13:13 VOC sensor internal error | Read | |||
| BI | 694 | Alarm 13:14 VOC sensor level below/above set point alarm limit | Read | |||
| BI | 711 | Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. error | Read | |||
| BI | 712 | Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defective | Read | |||
| BI | 713 | Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defective | Read | |||
| BI | 714 | Alarm 15:4 Plate heat exchanger damper monitor tripped | Read | |||
| BI | 717 | Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 718 | Alarm 15:8 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 719 | Alarm 15:9 Plate heat exchanger damper no. 1 monitor tripped | Read | |||
| BI | 720 | Alarm 15:10 Plate heat exchanger damper no. 2 monitor tripped | Read | |||
| BI | 721 | Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 722 | Alarm 15:12 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 724 | Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. error | Read | |||
| BI | 725 | Alarm 15:15 Plate heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 726 | Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. error | Read | |||
| BI | 727 | Alarm 16:2 Coil heat exchanger temperature sensor defective | Read | |||
| BI | 728 | Alarm 16:3 Coil heat exchanger valve monitor tripped | Read | |||
| BI | 729 | Alarm 16:4 Coil heat exchanger pump monitor tripped | Read | |||
| BI | 741 | Alarm 17:1 Rotary heat exchanger motor controller com. error | Read | |||
| BI | 742 | Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. error | Read | |||
| BI | 743 | Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 744 | Alarm 17:4 Rotary heat exchanger speed monitor tripped | Read | |||
| BI | 745 | Alarm 17:5 Rotary heat exchanger motor controller over current | Read | |||
| BI | 746 | Alarm 17:6 Rotary heat exchanger motor controller under voltage | Read | |||
| BI | 747 | Alarm 17:7 Rotary heat exchanger motor controller over voltage | Read | |||
| BI | 748 | Alarm 17:8 Rotary heat exchanger motor controller over temperature | Read | |||
| BI | 749 | Alarm 17:9 Rotary heat exchanger motor controller start error | Read | |||
| BI | 756 | Alarm 18:1 AYC I/O-module no. 7 com. error | Read | |||
| BI | 757 | Alarm 18:2 AYC heat temperature sensor defective | Read | |||
| BI | 758 | Alarm 18:3 AYC heat valve monitor tripped | Read | |||
| BI | 759 | Alarm 18:4 AYC heat pump monitor tripped | Read | |||
| BI | 760 | Alarm 18:5 AYC heat temperature below set point alarm limit | Read | |||
| BI | 761 | Alarm 18:6 AYC heat temperature above set point alarm limit | Read | |||
| BI | 764 | Alarm 18:9 AYC cool temperature sensor defective | Read | |||
| BI | 765 | Alarm 18:10 AYC cool valve monitor tripped | Read | |||
| BI | 766 | Alarm 18:11 AYC cool pump monitor tripped | Read | |||
| BI | 767 | Alarm 18:12 AYC cool temperature below set point alarm limit | Read | |||
| BI | 768 | Alarm 18:13 AYC cool temperature above set point alarm limit | Read | |||
| BI | 801 | Alarm 21:1 COOL DX I/O-module no. 2 com. error | Read | |||
| BI | 802 | Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defective | Read | |||
| BI | 803 | Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limit | Read | |||
| BI | 804 | Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defective | Read | |||
| BI | 805 | Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limit | Read | |||
| BI | 806 | Alarm 21:6 COOL DX compressor no. 1 monitor tripped | Read | |||
| BI | 807 | Alarm 21:7 COOL DX compressor no. 1 restart error | Read | |||
| BI | 808 | Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defective | Read | |||
| BI | 809 | Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limit | Read | |||
| BI | 810 | Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defective | Read | |||
| BI | 811 | Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limit | Read | |||
| BI | 812 | Alarm 21:12 COOL DX compressor no. 2 monitor tripped | Read | |||
| BI | 813 | Alarm 21:13 COOL DX compressor no. 2 restart error | Read | |||
| BI | 814 | Alarm 21:14 COOL DX outdoor air temperature sensor defective | Read | |||
| BI | 815 | Alarm 21:15 COOL DX phase sequence error | Read | |||
| BI | 831 | Alarm 23:1 SMART Link com. error | Read | |||
| BI | 832 | Alarm 23:2 SMART Link alarm level 1 tripped | Read | |||
| BI | 833 | Alarm 23:3 SMART Link alarm level 2 tripped | Read | |||
| BI | 834 | Alarm 23:4 SMART Link alarm level 3 tripped | Read | |||
| BI | 840 | Alarm 23:10 AQUA Link I/O-module no. 5 com. error | Read | |||
| BI | 841 | Alarm 23:11 AQUA Link pump monitor tripped | Read | |||
| BI | 846 | Alarm 24:1 SMART Link no. 1 com. error | Read | |||
| BI | 847 | Alarm 24:2 SMART Link no. 1 alarm tripped | Read | |||
| BI | 849 | Alarm 24:4 SMART Link no. 2 com. error | Read | |||
| BI | 850 | Alarm 24:5 SMART Link no. 2 alarm tripped | Read | |||
| BI | 852 | Alarm 24:7 SMART Link no. 3 com. error | Read | |||
| BI | 853 | Alarm 24:8 SMART Link no. 3 alarm tripped | Read | |||
| BI | 855 | Alarm 24:10 SMART Link no. 4 com. error | Read | |||
| BI | 856 | Alarm 24:11 SMART Link no. 4 alarm tripped | Read | |||
| BI | 876 | Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. error | Read | |||
| BI | 877 | Alarm 26:2 Pre-filter supply air dirty | Read | |||
| BI | 882 | Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. error | Read | |||
| BI | 883 | Alarm 26:8 Pre-filter extract air dirty | Read | |||
| BI | 891 | Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. error | Read | |||
| BI | 892 | Alarm 27:2 AHU filter supply air dirty | Read | |||
| BI | 897 | Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. error | Read | |||
| BI | 898 | Alarm 27:8 AHU filter extract air dirty | Read | |||
| BI | 906 | Alarm 28:1 End filter supply air pressure sensor no. A com. error | Read | |||
| BI | 907 | Alarm 28:2 End filter supply air dirty | Read | |||
| BI | 936 | Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. | Read | |||
| BI | 937 | Alarm 30:2 Air flow measurement supply air flow below set point alarm limit | Read | |||
| BI | 938 | Alarm 30:3 Air flow measurement supply air flow above set point alarm limit | Read | |||
| BI | 941 | Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. | Read | |||
| BI | 942 | Alarm 30:7 Air flow measurement extract air flow below set point alarm limit | Read | |||
| BI | 943 | Alarm 30:8 Air flow measurement extract air flow above set point alarm limit | Read | |||
| BI | 946 | Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. error | Read | |||
| BI | 951 | Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. error | Read | |||
| BI | 952 | Alarm 31:2 Pressure regulation supply air pressure below set point alarm limit | Read | |||
| BI | 953 | Alarm 31:3 Pressure regulation supply air pressure above set point alarm | Read | |||
| BI | 956 | Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. error | Read | |||
| BI | 957 | Alarm 31:7 Pressure regulation extract air press. below set point alarm limit | Read | |||
| BI | 958 | Alarm 31:8 Pressure regulation extract air press. above set point alarm limit | Read | |||
| BI | 966 | Alarm 32:1 ReCO2 I/O-module no. 0 com. error | Read | |||
| BI | 967 | Alarm 32:2 ReCO2 pressure sensor no. 0 com. error | Read | |||
| BI | 968 | Alarm 32:3 ReCO2 recirculation damper monitoring tripped | Read | |||
| BI | 969 | Alarm 32:4 ReCO2 outdoor air damper monitoring tripped | Read | |||
| BI | 981 | Alarm 33:1 Service period above alarm limit | Read | |||
| BI | 995 | Alarm 33:15 Lock function tripped | Read | |||
| BI | 996 | Alarm 34:1 External control I/O-module no. 3 com. error | Read | |||
| BI | 997 | Alarm 34:2 External control I/O-module no. 6 com. error | Read | |||
| BI | 1011 | Alarm 35:1 Booster diffusers I/O-module no. 8 com. error | Read | |||
| BI | 1056 | Alarm 38:1 MIRU 1 com. error | Read | |||
| BI | 1057 | Alarm 38:2 MIRU 1 motor controller alarm tripped | Read | |||
| BI | 1058 | Alarm 38:3 MIRU 1 motor controller com. error | Read | |||
| BI | 1059 | Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1060 | Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1061 | Alarm 38:6 MIRU 1 temperature sensor defective | Read | |||
| BI | 1062 | Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1071 | Alarm 39:1 MIRU 2 com. error | Read | |||
| BI | 1072 | Alarm 39:2 MIRU 2 motor controller alarm tripped | Read | |||
| BI | 1073 | Alarm 39:3 MIRU 2 motor controller com. error | Read | |||
| BI | 1074 | Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1075 | Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1076 | Alarm 39:6 MIRU 2 temperature sensor defective | Read | |||
| BI | 1077 | Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1086 | Alarm 40:1 MIRU 3 com. error | Read | |||
| BI | 1087 | Alarm 40:2 MIRU 3 motor controller alarm tripped | Read | |||
| BI | 1088 | Alarm 40:3 MIRU 3 motor controller com. error | Read | |||
| BI | 1089 | Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1090 | Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1091 | Alarm 40:6 MIRU 3 temperature sensor defective | Read | |||
| BI | 1092 | Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1101 | Alarm 41:1 MIRU 4 com. error | Read | |||
| BI | 1102 | Alarm 41:2 MIRU 4 motor controller alarm tripped | Read | |||
| BI | 1103 | Alarm 41:3 MIRU 4 motor controller com. error | Read | |||
| BI | 1104 | Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1105 | Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1106 | Alarm 41:6 MIRU 4 temperature sensor defective | Read | |||
| BI | 1107 | Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1116 | Alarm 42:1 MIRU 5 com. error | Read | |||
| BI | 1117 | Alarm 42:2 MIRU 5 motor controller alarm tripped | Read | |||
| BI | 1118 | Alarm 42:3 MIRU 5 motor controller com. error | Read | |||
| BI | 1119 | Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1120 | Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1121 | Alarm 42:6 MIRU 5 temperature sensor defective | Read | |||
| BI | 1122 | Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1131 | Alarm 43:1 MIRU 6 com. error | Read | |||
| BI | 1132 | Alarm 43:2 MIRU 6 motor controller alarm tripped | Read | |||
| BI | 1133 | Alarm 43:3 MIRU 6 motor controller com. error | Read | |||
| BI | 1134 | Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1135 | Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1136 | Alarm 43:6 MIRU 6 temperature sensor defective | Read | |||
| BI | 1137 | Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1146 | Alarm 44:1 MIRU 7 com. error | Read | |||
| BI | 1147 | Alarm 44:2 MIRU 7 motor controller alarm tripped | Read | |||
| BI | 1148 | Alarm 44:3 MIRU 7 motor controller com. error | Read | |||
| BI | 1149 | Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1150 | Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1151 | Alarm 44:6 MIRU 7 temperature sensor defective | Read | |||
| BI | 1152 | Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1161 | Alarm 45:1 MIRU 8 com. error | Read | |||
| BI | 1162 | Alarm 45:2 MIRU 8 motor controller alarm tripped | Read | |||
| BI | 1163 | Alarm 45:3 MIRU 8 motor controller com. error | Read | |||
| BI | 1164 | Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1165 | Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1166 | Alarm 45:6 MIRU 8 temperature sensor defective | Read | |||
| BI | 1167 | Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1176 | Alarm 46:1 MIRU 9 com. error | Read | |||
| BI | 1177 | Alarm 46:2 MIRU 9 motor controller alarm tripped | Read | |||
| BI | 1178 | Alarm 46:3 MIRU 9 motor controller com. error | Read | |||
| BI | 1179 | Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1180 | Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1181 | Alarm 46:6 MIRU 9 temperature sensor defective | Read | |||
| BI | 1182 | Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1191 | Alarm 47:1 MIRU 10 com. error | Read | |||
| BI | 1192 | Alarm 47:2 MIRU 10 motor controller alarm tripped | Read | |||
| BI | 1193 | Alarm 47:3 MIRU 10 motor controller com. error | Read | |||
| BI | 1194 | Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1195 | Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1196 | Alarm 47:6 MIRU 10 temperature sensor defective | Read | |||
| BI | 1197 | Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1221 | Alarm 49:1 Supply air fan no. 1A com. error | Read | |||
| BI | 1222 | Alarm 49:2 Supply air fan no. 1A motor controller over current | Read | |||
| BI | 1223 | Alarm 49:3 Supply air fan no. 1A motor controller under voltage | Read | |||
| BI | 1224 | Alarm 49:4 Supply air fan no. 1A motor controller over voltage | Read | |||
| BI | 1225 | Alarm 49:5 Supply air fan no. 1A motor controller over temperature | Read | |||
| BI | 1226 | Alarm 49:6 Supply air fan no. 1A motor controller start error | Read | |||
| BI | 1227 | Alarm 49:7 Supply air fan no. 1A motor controller ripple error | Read | |||
| BI | 1228 | Alarm 49:8 Supply air fan no. 1A motor controller phase error | Read | |||
| BI | 1229 | Alarm 49:9 Supply air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1230 | Alarm 49:10 Supply air fan no. 1A motor controller current reduction | Read | |||
| BI | 1236 | Alarm 50:1 Supply air fan no. 2A com. error | Read | |||
| BI | 1237 | Alarm 50:2 Supply air fan no. 2A motor controller over current | Read | |||
| BI | 1238 | Alarm 50:3 Supply air fan no. 2A motor controller under voltage | Read | |||
| BI | 1239 | Alarm 50:4 Supply air fan no. 2A motor controller over voltage | Read | |||
| BI | 1240 | Alarm 50:5 Supply air fan no. 2A motor controller over temperature | Read | |||
| BI | 1241 | Alarm 50:6 Supply air fan no. 2A motor controller start error | Read | |||
| BI | 1242 | Alarm 50:7 Supply air fan no. 2A motor controller ripple error | Read | |||
| BI | 1243 | Alarm 50:8 Supply air fan no. 2A motor controller phase error | Read | |||
| BI | 1244 | Alarm 50:9 Supply air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1245 | Alarm 50:10 Supply air fan no. 2A motor controller current reduction | Read | |||
| BI | 1251 | Alarm 51:1 Supply air fan no. 3A com. error | Read | |||
| BI | 1252 | Alarm 51:2 Supply air fan no. 3A motor controller over current | Read | |||
| BI | 1253 | Alarm 51:3 Supply air fan no. 3A motor controller under voltage | Read | |||
| BI | 1254 | Alarm 51:4 Supply air fan no. 3A motor controller over voltage | Read | |||
| BI | 1255 | Alarm 51:5 Supply air fan no. 3A motor controller over temperature | Read | |||
| BI | 1256 | Alarm 51:6 Supply air fan no. 3A motor controller start error | Read | |||
| BI | 1257 | Alarm 51:7 Supply air fan no. 3A motor controller ripple error | Read | |||
| BI | 1258 | Alarm 51:8 Supply air fan no. 3A motor controller phase error | Read | |||
| BI | 1259 | Alarm 51:9 Supply air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1260 | Alarm 51:10 Supply air fan no. 3A motor controller current reduction | Read | |||
| BI | 1266 | Alarm 52:1 Supply air fan no. 1B com. error | Read | |||
| BI | 1267 | Alarm 52:2 Supply air fan no. 1B motor controller over current | Read | |||
| BI | 1268 | Alarm 52:3 Supply air fan no. 1B motor controller under voltage | Read | |||
| BI | 1269 | Alarm 52:4 Supply air fan no. 1B motor controller over voltage | Read | |||
| BI | 1270 | Alarm 52:5 Supply air fan no. 1B motor controller over temperature | Read | |||
| BI | 1271 | Alarm 52:6 Supply air fan no. 1B motor controller start error | Read | |||
| BI | 1272 | Alarm 52:7 Supply air fan no. 1B motor controller ripple error | Read | |||
| BI | 1273 | Alarm 52:8 Supply air fan no. 1B motor controller phase error | Read | |||
| BI | 1274 | Alarm 52:9 Supply air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1275 | Alarm 52:10 Supply air fan no. 1B motor controller current reduction | Read | |||
| BI | 1281 | Alarm 53:1 Supply air fan no. 2B com. error | Read | |||
| BI | 1282 | Alarm 53:2 Supply air fan no. 2B motor controller over current | Read | |||
| BI | 1283 | Alarm 53:3 Supply air fan no. 2B motor controller under voltage | Read | |||
| BI | 1284 | Alarm 53:4 Supply air fan no. 2B motor controller over voltage | Read | |||
| BI | 1285 | Alarm 53:5 Supply air fan no. 2B motor controller over temperature | Read | |||
| BI | 1286 | Alarm 53:6 Supply air fan no. 2B motor controller start error | Read | |||
| BI | 1287 | Alarm 53:7 Supply air fan no. 2B motor controller ripple error | Read | |||
| BI | 1288 | Alarm 53:8 Supply air fan no. 2B motor controller phase error | Read | |||
| BI | 1289 | Alarm 53:9 Supply air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1290 | Alarm 53:10 Supply air fan no. 2B motor controller current reduction | Read | |||
| BI | 1296 | Alarm 54:1 Supply air fan no. 3B com. error | Read | |||
| BI | 1297 | Alarm 54:2 Supply air fan no. 3B motor controller over current | Read | |||
| BI | 1298 | Alarm 54:3 Supply air fan no. 3B motor controller under voltage | Read | |||
| BI | 1299 | Alarm 54:4 Supply air fan no. 3B motor controller over voltage | Read | |||
| BI | 1300 | Alarm 54:5 Supply air fan no. 3B motor controller over temperature | Read | |||
| BI | 1301 | Alarm 54:6 Supply air fan no. 3B motor controller start error | Read | |||
| BI | 1302 | Alarm 54:7 Supply air fan no. 3B motor controller ripple error | Read | |||
| BI | 1303 | Alarm 54:8 Supply air fan no. 3B motor controller phase error | Read | |||
| BI | 1304 | Alarm 54:9 Supply air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1305 | Alarm 54:10 Supply air fan no. 3B motor controller current reduction | Read | |||
| BI | 1311 | Alarm 55:1 Extract air fan no. 1A com. error | Read | |||
| BI | 1312 | Alarm 55:2 Extract air fan no. 1A motor controller over current | Read | |||
| BI | 1313 | Alarm 55:3 Extract air fan no. 1A motor controller under voltage | Read | |||
| BI | 1314 | Alarm 55:4 Extract air fan no. 1A motor controller over voltage | Read | |||
| BI | 1315 | Alarm 55:5 Extract air fan no. 1A motor controller over temperature | Read | |||
| BI | 1316 | Alarm 55:6 Extract air fan no. 1A motor controller start error | Read | |||
| BI | 1317 | Alarm 55:7 Extract air fan no. 1A motor controller ripple error | Read | |||
| BI | 1318 | Alarm 55:8 Extract air fan no. 1A motor controller phase error | Read | |||
| BI | 1319 | Alarm 55:9 Extract air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1320 | Alarm 55:10 Extract air fan no. 1A motor controller current reduction | Read | |||
| BI | 1326 | Alarm 56:1 Extract air fan no. 2A com. error | Read | |||
| BI | 1327 | Alarm 56:2 Extract air fan no. 2A motor controller over current | Read | |||
| BI | 1328 | Alarm 56:3 Extract air fan no. 2A motor controller under voltage | Read | |||
| BI | 1329 | Alarm 56:4 Extract air fan no. 2A motor controller over voltage | Read | |||
| BI | 1330 | Alarm 56:5 Extract air fan no. 2A motor controller over temperature | Read | |||
| BI | 1331 | Alarm 56:6 Extract air fan no. 2A motor controller start error | Read | |||
| BI | 1332 | Alarm 56:7 Extract air fan no. 2A motor controller ripple error | Read | |||
| BI | 1333 | Alarm 56:8 Extract air fan no. 2A motor controller phase error | Read | |||
| BI | 1334 | Alarm 56:9 Extract air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1335 | Alarm 56:10 Extract air fan no. 2A motor controller current reduction | Read | |||
| BI | 1341 | Alarm 57:1 Extract air fan no. 3A com. error | Read | |||
| BI | 1342 | Alarm 57:2 Extract air fan no. 3A motor controller over current | Read | |||
| BI | 1343 | Alarm 57:3 Extract air fan no. 3A motor controller under voltage | Read | |||
| BI | 1344 | Alarm 57:4 Extract air fan no. 3A motor controller over voltage | Read | |||
| BI | 1345 | Alarm 57:5 Extract air fan no. 3A motor controller over temperature | Read | |||
| BI | 1346 | Alarm 57:6 Extract air fan no. 3A motor controller start error | Read | |||
| BI | 1347 | Alarm 57:7 Extract air fan no. 3A motor controller ripple error | Read | |||
| BI | 1348 | Alarm 57:8 Extract air fan no. 3A motor controller phase error | Read | |||
| BI | 1349 | Alarm 57:9 Extract air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1350 | Alarm 57:10 Extract air fan no. 3A motor controller current reduction | Read | |||
| BI | 1356 | Alarm 58:1 Extract air fan no. 1B com. error | Read | |||
| BI | 1357 | Alarm 58:2 Extract air fan no. 1B motor controller over current | Read | |||
| BI | 1358 | Alarm 58:3 Extract air fan no. 1B motor controller under voltage | Read | |||
| BI | 1359 | Alarm 58:4 Extract air fan no. 1B motor controller over voltage | Read | |||
| BI | 1360 | Alarm 58:5 Extract air fan no. 1B motor controller over temperature | Read | |||
| BI | 1361 | Alarm 58:6 Extract air fan no. 1B motor controller start error | Read | |||
| BI | 1362 | Alarm 58:7 Extract air fan no. 1B motor controller ripple error | Read | |||
| BI | 1363 | Alarm 58:8 Extract air fan no. 1B motor controller phase error | Read | |||
| BI | 1364 | Alarm 58:9 Extract air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1365 | Alarm 58:10 Extract air fan no. 1B motor controller current reduction | Read | |||
| BI | 1371 | Alarm 59:1 Extract air fan no. 2B com. error | Read | |||
| BI | 1372 | Alarm 59:2 Extract air fan no. 2B motor controller over current | Read | |||
| BI | 1373 | Alarm 59:3 Extract air fan no. 2B motor controller under voltage | Read | |||
| BI | 1374 | Alarm 59:4 Extract air fan no. 2B motor controller over voltage | Read | |||
| BI | 1375 | Alarm 59:5 Extract air fan no. 2B motor controller over temperature | Read | |||
| BI | 1376 | Alarm 59:6 Extract air fan no. 2B motor controller start error | Read | |||
| BI | 1377 | Alarm 59:7 Extract air fan no. 2B motor controller ripple error | Read | |||
| BI | 1378 | Alarm 59:8 Extract air fan no. 2B motor controller phase error | Read | |||
| BI | 1379 | Alarm 59:9 Extract air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1380 | Alarm 59:10 Extract air fan no. 2B motor controller current reduction | Read | |||
| BI | 1386 | Alarm 60:1 Extract air fan no. 3B com. error | Read | |||
| BI | 1387 | Alarm 60:2 Extract air fan no. 3B motor controller over current | Read | |||
| BI | 1388 | Alarm 60:3 Extract air fan no. 3B motor controller under voltage | Read | |||
| BI | 1389 | Alarm 60:4 Extract air fan no. 3B motor controller over voltage | Read | |||
| BI | 1390 | Alarm 60:5 Extract air fan no. 3B motor controller over temperature | Read | |||
| BI | 1391 | Alarm 60:6 Extract air fan no. 3B motor controller start error | Read | |||
| BI | 1392 | Alarm 60:7 Extract air fan no. 3B motor controller ripple error | Read | |||
| BI | 1393 | Alarm 60:8 Extract air fan no. 3B motor controller phase error | Read | |||
| BI | 1394 | Alarm 60:9 Extract air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1395 | Alarm 60:10 Extract air fan no. 3B motor controller current reduction | Read | |||
| BI | 1952 | Info 97:12 Plate heat exchanger bypass optimization not performed | Read | |||
| BI | 1953 | Info 97:13 Plate heat exchanger bypass optimization not approved | Read | |||
| BI | 1954 | Info 97:14 Plate heat exchanger defrost calibration not performed | Read | |||
| BI | 1955 | Info 97:15 Plate heat exchanger defrost calibration not approved | Read | |||
| BI | 1956 | Info 98:1 Supply air pre-filter calibration not performed | Read | |||
| BI | 1957 | Info 98:2 Supply air pre-filter calibration not approved | Read | |||
| BI | 1958 | Info 98:3 Extract air pre-filter calibration not performed | Read | |||
| BI | 1959 | Info 98:4 Extract air pre-filter calibration not approved | Read | |||
| BI | 1960 | Info 98:5 Supply air air handling unit filter calibration not performed | Read | |||
| BI | 1961 | Info 98:6 Supply air air handling unit filter calibration not approved | Read | |||
| BI | 1962 | Info 98:7 Extract air air handling unit filter calibration not performed | Read | |||
| BI | 1963 | Info 98:8 Extract air air handling unit filter calibration not approved | Read | |||
| BI | 1964 | Info 98:9 Supply air end filter calibration not performed | Read | |||
| BI | 1965 | Info 98:10 Supply air end filter calibration not approved | Read | |||
| BI | 1966 | Info 98:11 Rotary heat exchanger defrost calibration not performed | Read | |||
| BI | 1967 | Info 98:12 Rotary heat exchanger defrost calibration not approved | Read | |||
| BI | 1968 | Info 98:13 ReCO2 calibration not performed | Read | |||
| BI | 1969 | Info 98:14 ReCO2 calibration not approved | Read | |||
| BI | 1970 | Info 98:15 ReCO2 incorrect setting | Read | |||
| BI | 1971 | Info 99:1 E-mail error | Read | |||
| BI | 1977 | Info 99:7 SD card memory soon full. Oldest log data will soon be deleted | Read | |||
| BI | 1978 | Info 99:8 SD card memory full. Oldest log data deleted | Read | |||
| BI | 1984 | Info 99:14 Internal serial memory error CPU 1 | Read | |||
| BI | 1985 | Info 99:15 Clock circuit defective | Read | |||
| BI | 2001 | Active alarm group 1 | Read | |||
| BI | 2002 | Active alarm group 2 | Read | |||
| BI | 2003 | Active alarm group 3 | Read | |||
| BI | 2004 | Active alarm group 4 | Read | |||
| BI | 2005 | Active alarm group 5 | Read | |||
| BI | 2006 | Active alarm group 6 | Read | |||
| BI | 2007 | Active alarm group 7 | Read | |||
| BI | 2008 | Active alarm group 8 | Read | |||
| BI | 2009 | Active alarm group 9 | Read | |||
| BI | 2010 | Active alarm group 10 | Read | |||
| BI | 2011 | Active alarm group 11 | Read | |||
| BI | 2012 | Active alarm group 12 | Read | |||
| BI | 2013 | Active alarm group 13 | Read | |||
| BI | 2014 | Active alarm group 14 | Read | |||
| BI | 2015 | Active alarm group 15 | Read | |||
| BI | 2016 | Active alarm group 16 | Read | |||
| BI | 2017 | Active alarm group 17 | Read | |||
| BI | 2018 | Active alarm group 18 | Read | |||
| BI | 2019 | Active alarm group 19 | Read | |||
| BI | 2020 | Active alarm group 20 | Read | |||
| BI | 2021 | Active alarm group 21 | Read | |||
| BI | 2022 | Active alarm group 22 | Read | |||
| BI | 2023 | Active alarm group 23 | Read | |||
| BI | 2024 | Active alarm group 24 | Read | |||
| BI | 2025 | Active alarm group 25 | Read | |||
| BI | 2026 | Active alarm group 26 | Read | |||
| BI | 2027 | Active alarm group 27 | Read | |||
| BI | 2028 | Active alarm group 28 | Read | |||
| BI | 2029 | Active alarm group 29 | Read | |||
| BI | 2030 | Active alarm group 30 | Read | |||
| BI | 2031 | Active alarm group 31 | Read | |||
| BI | 2032 | Active alarm group 32 | Read | |||
| BI | 2033 | Active alarm group 33 | Read | |||
| BI | 2034 | Active alarm group 34 | Read | |||
| BI | 2035 | Active alarm group 35 | Read | |||
| BI | 2036 | Active alarm group 36 | Read | |||
| BI | 2037 | Active alarm group 37 | Read | |||
| BI | 2038 | Active alarm group 38 | Read | |||
| BI | 2039 | Active alarm group 39 | Read | |||
| BI | 2040 | Active alarm group 40 | Read | |||
| BI | 2041 | Active alarm group 41 | Read | |||
| BI | 2042 | Active alarm group 42 | Read | |||
| BI | 2043 | Active alarm group 43 | Read | |||
| BI | 2044 | Active alarm group 44 | Read | |||
| BI | 2045 | Active alarm group 45 | Read | |||
| BI | 2046 | Active alarm group 46 | Read | |||
| BI | 2047 | Active alarm group 47 | Read | |||
| BI | 2048 | Active alarm group 48 | Read | |||
| BI | 2049 | Active alarm group 49 | Read | |||
| BI | 2050 | Active alarm group 50 | Read | |||
| BI | 2051 | Active alarm group 51 | Read | |||
| BI | 2052 | Active alarm group 52 | Read | |||
| BI | 2053 | Active alarm group 53 | Read | |||
| BI | 2054 | Active alarm group 54 | Read | |||
| BI | 2055 | Active alarm group 55 | Read | |||
| BI | 2056 | Active alarm group 56 | Read | |||
| BI | 2057 | Active alarm group 57 | Read | |||
| BI | 2058 | Active alarm group 58 | Read | |||
| BI | 2059 | Active alarm group 59 | Read | |||
| BI | 2060 | Active alarm group 60 | Read | |||
| BI | 2061 | Active alarm group 61 | Read | |||
| BI | 2062 | Active alarm group 62 | Read | |||
| BI | 2063 | Active alarm group 63 | Read | |||
| BI | 2064 | Active alarm group 64 | Read | |||
| BI | 2065 | Active alarm group 65 | Read | |||
| BI | 2066 | Active alarm group 66 | Read | |||
| BI | 2067 | Active alarm group 67 | Read | |||
| BI | 2068 | Active alarm group 68 | Read | |||
| BI | 2069 | Active alarm group 69 | Read | |||
| BI | 2070 | Active alarm group 70 | Read | |||
| BI | 2071 | Active alarm group 71 | Read | |||
| BI | 2072 | Active alarm group 72 | Read | |||
| BI | 2073 | Active alarm group 73 | Read | |||
| BI | 2074 | Active alarm group 74 | Read | |||
| BI | 2075 | Active alarm group 75 | Read | |||
| BI | 2076 | Active alarm group 76 | Read | |||
| BI | 2077 | Active alarm group 77 | Read | |||
| BI | 2078 | Active alarm group 78 | Read | |||
| BI | 2079 | Active alarm group 79 | Read | |||
| BI | 2080 | Active alarm group 80 | Read | |||
| BI | 2081 | Active alarm group 81 | Read | |||
| BI | 2082 | Active alarm group 82 | Read | |||
| BI | 2083 | Active alarm group 83 | Read | |||
| BI | 2084 | Active alarm group 84 | Read | |||
| BI | 2085 | Active alarm group 85 | Read | |||
| BI | 2086 | Active alarm group 86 | Read | |||
| BI | 2087 | Active alarm group 87 | Read | |||
| BI | 2088 | Active alarm group 88 | Read | |||
| BI | 2089 | Active alarm group 89 | Read | |||
| BI | 2090 | Active alarm group 90 | Read | |||
| BI | 2091 | Active alarm group 91 | Read | |||
| BI | 2092 | Active alarm group 92 | Read | |||
| BI | 2093 | Active alarm group 93 | Read | |||
| BI | 2094 | Active alarm group 94 | Read | |||
| BI | 2095 | Active alarm group 95 | Read | |||
| BI | 2096 | Active alarm group 96 | Read | |||
| BI | 2097 | Active alarm group 97 | Read | |||
| BI | 2098 | Active alarm group 98 | Read | |||
| BI | 2099 | Active alarm group 99 | Read | |||
| BO | 1 | Booster diffusers | Booster diffusers function. | Write | ||
| BVmin | 1 | Alarm reset | Resets all active alarms | Write | ||
| BV | 3 | Internal fire alarm function | Write | |||
| BV | 29 | SA flow pressure sensor auto zero calibration | Write | |||
| BV | 30 | EA flow pressure sensor auto zero calibration | Write | |||
| BV | 31 | SA duct pressure sensor auto zero calibration | Write | |||
| BV | 32 | EA duct pressure sensor auto zero calibration | Write | |||
| BV | 33 | ReCO2 pressure sensor auto zero calibration | Write | |||
| BV | 34 | RHX defrost pressure sensor auto calibration | Write | |||
| BV | 35 | Carry over control pressure sensor auto calibration | Write | |||
| BV | 36 | SA filter pressure sensor auto zero calibration | Write | |||
| BV | 37 | EA filter pressure sensor auto zero calibration | Write | |||
| BV | 38 | SA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 39 | EA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 40 | SA end-filter pressure sensor auto zero calibration | Write | |||
| BV | 46 | SA flow pressure sensor activate zero calibration | If value is set to 1 for min 1s calibration will be | Write | ||
| BV | 47 | EA flow pressure sensor activate zero calibration | Write | |||
| BV | 48 | SA duct pressure sensor activate zero calibration | Write | |||
| BV | 49 | EA duct pressure sensor activate zero calibration | Write | |||
| BV | 50 | ReCO2 pressure sensor activate calibration | Write | |||
| BV | 51 | RHX Defrost pressure sensor activate calibration | Write | |||
| BV | 52 | Carry over control pressure sensor activate zero calibration | Write | |||
| BV | 53 | SA filter pressure sensor activate zero calibration | Write | |||
| BV | 54 | EA filter pressure sensor activate zero calibration | Write | |||
| BV | 55 | SA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 56 | EA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 57 | SA end-filter pressure sensor activate zero calibration | Write | |||
| BV | 162 | External room sensor 1 function | Write | |||
| BV | 163 | External room sensor 2 function | Write | |||
| BV | 164 | External room sensor 3 function | Write | |||
| BV | 165 | External room sensor 4 function | Write | |||
| BV | 167 | External room temp from BMS function | Write | |||
| BV | 172 | External OA sensor 1 function | Write | |||
| BV | 173 | External OA sensor 2 function | Write | |||
| BV | 174 | External OA sensor 3 function | Write | |||
| BV | 175 | External OA sensor 4 function | Write | |||
| BV | 177 | External OA temp from BMS function | Write | |||
| BV | 182 | RHX defrost function | Setting for activating the defrost function for the rotary heat | Write | ||
| BV | 183 | RHX defrost calibration | Write | |||
| BV | 187 | RHX carry over control function | Setting for activating the carry over control function for the rotary heat | Write | ||
| BV | 190 | RHX min exhaust air temp function | Write | |||
| BV | 198 | PHX periodic operation of bypass damper function | Write | |||
| BV | 201 | PX bypass optimize | Write | |||
| BV | 205 | CHX periodic operation of pump function | Write | |||
| BV | 206 | CHX periodic operation of valve function | Write | |||
| BV | 228 | Re-heat periodic operation of pump function | Write | |||
| BV | 229 | Re-heat periodic operation of valve function | Write | |||
| BV | 245 | Extra regulation 1 periodic operation of pump function | Write | |||
| BV | 246 | Extra regulation 1 periodic operation of valve function | Write | |||
| BV | 274 | Cool relay 1 periodic operation of pump function | Write | |||
| BV | 275 | Cool relay 2 periodic operation of pump function | Write | |||
| BV | 276 | Cool periodic operation of valve function | Write | |||
| BV | 284 | Summer night cool function | Write | |||
| BV | 296 | Intermittent night heat function | Write | |||
| BV | 302 | Intermittent night heat recirculation function | Write | |||
| BV | 305 | Morning boost function | Write | |||
| BV | 320 | Heating boost function | Write | |||
| BV | 325 | Xzone heat function | Write | |||
| BV | 327 | Xzone cool function | Write | |||
| BV | 374 | Xzone external room sensor 1 function | Write | |||
| BV | 375 | Xzone external room sensor 2 function | Write | |||
| BV | 376 | Xzone external room sensor 3 function | Write | |||
| BV | 377 | Xzone external room sensor 4 function | Write | |||
| BV | 379 | Xzone external room temp from BMS function | Write | |||
| BV | 386 | Xzone reheat periodic operation of pump function | Write | |||
| BV | 387 | Xzone reheat periodic operation of valve function | Write | |||
| BV | 400 | Xzone Cool relay 1 periodic operation of pump function | Write | |||
| BV | 401 | Xzone Cool relay 2 periodic operation of pump function | Write | |||
| BV | 402 | Xzone Cool periodic operation of valve function | Write | |||
| BV | 410 | Pre-heat function | Write | |||
| BV | 414 | Pre-heat periodic operation of pump function | Write | |||
| BV | 415 | Pre-heat periodic operation of valve function | Write | |||
| BV | 425 | ReCO2 Calibration | Write | |||
| BV | 457 | Dehumidifying function | Moved to Multistate Value 457 | Write | ||
| BV | 459 | Heat exchange active in dehumidifying sequence | Write | |||
| BV | 465 | VOC sensor function | Write | |||
| BV | 490 | SMART Link WB Optimize function | Write | |||
| BV | 504 | AQUA Link Function | Write | |||
| BV | 530 | AYC Heated water periodic operation of pump | Write | |||
| BV | 531 | AYC Heated water periodic operation of valve | Write | |||
| BV | 536 | AYC Heated water OA temp compensation | Write | |||
| BV | 547 | AYC Heated water room temp compensation function | Write | |||
| BV | 548 | AYC Heated water room temp compensation at night | Write | 0=Enabled during night, 1=Disabled during night | ||
| BV | 553 | AYC Heated water night temp compensation function | Write | |||
| BV | 579 | AYC Chilled water periodic operation of pump | Write | |||
| BV | 580 | AYC Chilled water periodic operation of valve | Write | |||
| BV | 585 | AYC Chilled water OA temp compensation | Write | |||
| BV | 596 | AYC Chilled water room temp compensation function | Write | |||
| BV | 597 | AYC Chilled water room temp compensation at night | Write | 0=Enabled during night, 1=Disabled during night | ||
| BV | 602 | AYC Chilled water night temp compensation function | Write | |||
| BV | 618 | AYC Chilled water dew point compensation air flow boost | Write | |||
| BV | 637 | Optimize function | Write | |||
| MI | 2 | Application id/AHU Type | Read | 1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX | ||
| MI | 3 | Air flow direction | Read | 1=Fan no.2 as SA, 2=Fan no.1 as SA | ||
| MI | 115 | PHX type | Read | 1=PHX-1 1D HS (one damper and humidity sensor), 2=PHX-2 3D (three dampers), 3=PHX-3 1D 1PS (one damper and pressure sensor) | ||
| MI | 140 | Extra regulation sequence 1 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 142 | Extra regulation sequence 2 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 152 | Re-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 163 | Cool coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 198 | Xzone heat, coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 209 | Xzone cool, coil type | Read | 1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used | ||
| MI | 224 | Pre-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 320 | SMART Link, DX cool mode | Read | 1=Heat, 2=Cool | ||
| MImin | 592 | Operation level | Read | 1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation(1.11), 15=Morning boost stop(1.11), 16=Intermittent night heat stop(1.11), 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment(1.12) | ||
| MO | 1 | Boost Supply air | Write | 1=Off, 2=On | ||
| MO | 2 | Boost Extract air | Write | 1=Off, 2=On | ||
| MV | 1 | SA Fan regulation mode | Setting of regulation type for the supply air fan. | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan | |
| MV | 2 | EA Fan regulation mode | Setting of regulation type for the extract air fan. | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan | |
| MV | 4 | Internal fire alarm reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 7 | External fire alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 8 | External fire alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 11 | External alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 12 | External alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 15 | External alarm no. 1 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 16 | External alarm no. 2 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 53 | Outdoor temp compensation function | Write | 1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed | ||
| MV | 78 | Down regulation function | Write | 1=Inactive, 2=SA, 3=SA and EA | ||
| MV | 84 | Fans in operation at fire alarm 1 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 87 | Fans in operation at fire alarm 2 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 90 | Fans in operation at internal fire alarm function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 95 | Pre-filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 96 | Pre-filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 101 | AHU filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 102 | AHU filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 107 | SA end filter function | Write | 1=Inactive, 2=SA | ||
| MV | 108 | SA end filter calibration | Write | 1=Inactive, 2=SA | ||
| MV | 115 | Temperature regulation mode | Write | 1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE | ||
| MV | 166 | External room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 176 | External OA sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 188 | RHX sorption rotor function | Setting for activating the sorption rotor control function for the rotary heat | Write | 1=Inactive, 2=Sorption max at cool, 3=Sorption always max | |
| MV | 237 | Extra regulation sequence 1 function | State text | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | |
| MV | 238 | Extra regulation sequence 1 output function | Write | 1=0-10V, 2=10-0V | ||
| MV | 251 | Extra regulation 1 temperature protection function | Write | 1=Inactive, 2=Active | ||
| MV | 254 | Season heat function | Write | 1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode | ||
| MV | 255 | Season heat manual setting | Write | 1=Re-heat, 2=Extra regulation sequence | ||
| MV | 261 | Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 313 | Cooling boost function | Write | 1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence | ||
| MV | 329 | Xzone temperature regulation mode | Write | 1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE | ||
| MV | 378 | Xzone external room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 395 | Xzone Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 423 | ReCO2-CO2 function | Write | 1=Inactive, 2=CO2, 3=CO2 and air flow boost | ||
| MV | 424 | ReCO2 temperature regulation sequence function | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | ||
| MV | 441 | Humidifying function | Write | 1=Inactive, 2=On/Off, 3=0-10V | ||
| MV | 442 | Humidifying sensor | Write | 1=SA, 2=EA | ||
| MV | 457 | DeHumidifying function | Write | 0=Inactive, 1=SA, 2=EA | ||
| MV | 469 | COOL DX Function | Write | 1=Inactive, 2=Economy, 3=Comfort, 4=Top | ||
| MV | 481 | SMART Link Function | Write | 1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible | ||
| MV | 505 | AQUA Link Pump alarm function | Write | 1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function) | ||
| MV | 521 | AYC Function | Write | 1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water | ||
| MV | 528 | AYC Heated water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 555 | AYC Heated water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 562 | AYC Heated water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 577 | AYC Chilled water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 604 | AYC Chilled water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 611 | AYC Chilled water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 660 | MIRU Control 1 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 661 | MIRU Control 2 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 662 | MIRU Control 3 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 663 | MIRU Control 4 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 664 | MIRU Control 5 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 665 | MIRU Control 6 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 666 | MIRU Control 7 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 667 | MIRU Control 8 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 668 | MIRU Control 9 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 669 | MIRU Control 10 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 671 | MIRU Control 1 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 679 | MIRU Control 2 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 687 | MIRU Control 3 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 695 | MIRU Control 4 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 703 | MIRU Control 5 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 711 | MIRU Control 6 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 719 | MIRU Control 7 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 727 | MIRU Control 8 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 735 | MIRU Control 9 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 743 | MIRU Control 10 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MVmin | 793 | Communication operation level | Write | 1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop | ||
| CAL | 0 | Calendar #1 | Date list, up to 10 dates | Write | ||
| CAL | 1 | Calendar #2 | Date list, up to 10 dates | Write | ||
| NC | 0 | NC 00 A-Alarm | Notification class for AHU A-alarms | Read | ||
| NC | 1 | NC 01 B-Alarm | Notification class for AHU B-alarms | Read | ||
| NC | 3 | NC 03 Alarms specified in BACnet | Notification class for alarms set in BACnet objects | Read | ||
| NC | 10 | NC 10 Info message | Notification class for AHU info messages | Read | ||
| NC | 11 | NC 11 Events specified in BACnet | Notification class for events set in BACnet objects | Read | ||
| SCH | 0 | Schedule #1 | Weekly schedule, 6 time-values per day, 2 exceptions | Write | 1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop |
No points match these filters.
Integration notes
- Object tables are the same on every unit; points for accessories or heat-exchanger types not fitted read zero or inactive.
- The Misc column in the source marks the program version (1.11-1.13) that added some objects.
- Most alarms appear as individual BIs named 'Alarm <group>:<number> ...'; BI-13/14 summarize A- and B-class alarms.
- Airflows are in l/s and temperatures in °C as published.
- BI-104's object name is printed truncated in the source (a pressure-limit sentence) and is kept as printed.
- BV-457 Dehumidifying function is marked as moved to MV-457.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation E (RX/PX/CX/SD) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
How many BACnet points does the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP have?
This list has 1452 BACnet objects: 356 analog inputs, 1 analog output, 357 analog values, 554 binary inputs, 1 binary output, 91 binary values, 2 calendars, 12 multi-state inputs, 2 multi-state outputs, 5 notification classs, 1 schedule, 70 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points are writable?
525 of the 1452 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet documentation?
The source is BACnet IP GOLD RX/PX/CX/SD, Generation E (GOLD_E_BACnet_150316), revision 2015-03-16, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-e-2013-2017/functions/_en/gold_e_bacnet_150316.pdf.
What are the minimum BACnet points to integrate the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
Start with MV 793 Communication operation level (BMS start/stop and speed command); AV 132 SA temperature set point (Supply air temperature setpoint); AV 135 EA/Room temperature set point (Extract/room temperature setpoint); BV 1 Alarm reset (Resets all active alarms); MI 592 Operation level (Actual operating state and who stopped the unit); AI 64 SA Temperature (Supply air temperature); AI 66 EA Temperature (Extract air temperature); AI 73 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 13 A-alarm active (Any A-class alarm); BI 14 B-alarm active (Any B-class alarm).
How do I enable BMS control of the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.
Can the BMS supply sensor values to the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).
How do I check these points on the real GOLD generation E (RX/PX/CX/SD) BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
Source: BACnet IP GOLD RX/PX/CX/SD, Generation E · GOLD_E_BACnet_150316 · rev. 2015-03-16. Object names, instances and units are reproduced as published; descriptions are our own.