 "manufacturer": "Swegon",
 "manufacturer_slug": "swegon",
 "model": "GOLD generation E (RX/PX/CX/SD) BACnet IP",
 "model_slug": "gold-e-bacnet-ip",
 "aliases": [
  "GOLD E",
  "GOLD RX",
  "GOLD PX",
  "GOLD CX",
  "GOLD SD",
  "IQlogic",
  "GOLD_E_BACnet_150316"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "Swegon GOLD air handling units of generation E (RX, PX, CX and SD versions) running program version 1.10 or later.",
 "summary": "The built-in IQlogic controller in Swegon GOLD generation E air handlers is a native BACnet IP device (B-AAC profile) with no gateway needed. It publishes over 1,400 objects: fan airflow/pressure readings and setpoints, temperatures and regulation levels, heat-exchanger and coil data, accessory functions (Xzone, SMART Link, AYC, MIRU, COOL DX), one binary input per alarm, plus calendars, a schedule and notification classes for intrinsic alarming. The unit is started, stopped and speed-selected from the BMS through a single multistate value.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "Program version 1.10 or later (driver in PV 1.16)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object tables are the same on every unit; points for accessories or heat-exchanger types not fitted read zero or inactive.",
  "The Misc column in the source marks the program version (1.11-1.13) that added some objects.",
  "Most alarms appear as individual BIs named 'Alarm <group>:<number> ...'; BI-13/14 summarize A- and B-class alarms.",
  "Airflows are in l/s and temperatures in °C as published.",
  "BI-104's object name is printed truncated in the source (a pressure-limit sentence) and is kept as printed.",
  "BV-457 Dehumidifying function is marked as moved to MV-457."
 ],
 "source": {
  "title": "BACnet IP GOLD RX/PX/CX/SD, Generation E",
  "doc_number": "GOLD_E_BACnet_150316",
  "revision_date": "2015-03-16",
  "url": "https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-e-2013-2017/functions/_en/gold_e_bacnet_150316.pdf"
 },
 "integration": {
  "summary": "Command the unit with MV-793 Communication operation level (Auto lets the internal time channel run it; other states force stop, low or high speed) and read back MI-592 Operation level plus the low/high speed BIs. Adjust the main temperature setpoints (AV-132 supply, AV-135 extract/room) and airflow or pressure setpoints for low and high speed, and monitor BI-13/14 for A/B alarms with BV-1 to reset. The object summary on page 3 of the source lists these as the key points.",
  "minimum_points": [
   {
    "ref": "MV 793",
    "name": "Communication operation level",
    "why": "BMS start/stop and speed command"
   },
   {
    "ref": "AV 132",
    "name": "SA temperature set point",
    "why": "Supply air temperature setpoint"
   },
   {
    "ref": "AV 135",
    "name": "EA/Room temperature set point",
    "why": "Extract/room temperature setpoint"
   },
   {
    "ref": "BV 1",
    "name": "Alarm reset",
    "why": "Resets all active alarms"
   },
   {
    "ref": "MI 592",
    "name": "Operation level",
    "why": "Actual operating state and who stopped the unit"
   },
   {
    "ref": "AI 64",
    "name": "SA Temperature",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 66",
    "name": "EA Temperature",
    "why": "Extract air temperature"
   },
   {
    "ref": "AI 73",
    "name": "Outdoor temperature",
    "why": "Outdoor air temp measured by the unit, °C"
   },
   {
    "ref": "BI 13",
    "name": "A-alarm active",
    "why": "Any A-class alarm"
   },
   {
    "ref": "BI 14",
    "name": "B-alarm active",
    "why": "Any B-class alarm"
   }
  ],
  "enable": "MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.",
  "heartbeat": null,
  "remote_sensors": "Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).",
  "setup": [
   "BACnet IP only; the device is a B-AAC with intrinsic alarming (notification classes NC-0, 1, 3, 10, 11).",
   "Swegon also publishes a BACnet PICS and an EDE file for GOLD; device instance and IP settings are not given in this document."
  ],
  "gotchas": [
   "Calibration BVs (29-56) trigger pressure-sensor zero calibration.",
   "Setpoints are split by low and high speed (e.g. AV-3/5 SA airflow, AV-19/21 SA duct pressure); write the one for the active speed.",
   "Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is installed.",
   "Schedule #1 values are 1-5 (total stop to extended normal stop) with up to 6 time-values a day."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Component name",
   "description": "",
   "units": "",
   "access": "R",
   "states": "25=IQlogic"
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "SA Air flow",
   "description": "Present supply air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "SA Air flow regulator",
   "description": "Present supply air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "EA Air flow",
   "description": "Present extract air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "EA Air flow regulator",
   "description": "Present extract air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "SA Duct pressure",
   "description": "Present supply air duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "SA Duct pressure regulator",
   "description": "Present supply air duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "EA Duct pressure",
   "description": "Present extract air duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "EA Duct pressure regulator",
   "description": "Present extract air duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Demand input level",
   "description": "Present input signal for demand regulation.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Demand regulator",
   "description": "Present demand regulator set point.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "SA Air flow pressure",
   "description": "Present air flow pressure in the supply air fan inlet.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "EA Air flow pressure",
   "description": "Present air flow pressure in the extract air fan inlet.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "SA Pre-filter pressure level",
   "description": "Present supply air pre-filter pressure drop.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "SA Pre-filter pressure alarm limit",
   "description": "Present supply air pre-filter pressure alarm limit.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "EA Pre-filter pressure level",
   "description": "Present extract air pre-filter pressure drop.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "EA Pre-filter pressure alarm limit",
   "description": "Present extract air pre-filter pressure alarm limit.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "SA AHU filter pressure level",
   "description": "Present supply air filter pressure drop.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "SA AHU filter pressure alarm limit",
   "description": "Present supply air filter pressure alarm limit.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "EA AHU filter pressure level",
   "description": "Present extract air filter pressure drop.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "EA AHU filter pressure alarm limit",
   "description": "Present extract air filter pressure alarm limit.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "SA End-filter pressure level",
   "description": "Present supply air end-filter pressure drop.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "SA End-filter pressure alarm limit",
   "description": "Present supply air end-filter pressure alarm limit.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "SA Fan level",
   "description": "Present fan speed level of the supply air fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "EA Fan level",
   "description": "Present fan speed level of the extract air fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "SA Fan speed",
   "description": "Present fan speed level of the supply air fan.",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "EA Fan speed",
   "description": "Present fan speed level of the extract air fan.",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "SA Voltage",
   "description": "Present voltage level of the supply air fan.",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "EA Voltage",
   "description": "Present voltage level of the extract air fan.",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "SA Fan current",
   "description": "Present current level of the supply air fans.",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "EA Fan current",
   "description": "Present current level of the extract air fans.",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "SA Fan power",
   "description": "Present power level of the supply air fans.",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "EA Fan power",
   "description": "Present power consumption level of the extract air fans.",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "SA Fan kWh",
   "description": "Total power consumption of the supply air fans.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "EA Fan kWh",
   "description": "Total power consumption level of the extract air fans.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "SA Fan MWh",
   "description": "Total power consumption of the supply air fans.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "EA Fan MWh",
   "description": "Total power consumption level of the extract air fans.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "SA Fan operation time",
   "description": "Total operation time of the supply air fan presented in days (24h).",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "EA Fan operation time",
   "description": "Total operation time of the extract air fan presented in days (24h).",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "SA Fan min air flow",
   "description": "Supply air AHU min air flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "EA Fan min air flow",
   "description": "Extract air AHU min air flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "SA Fan max air flow",
   "description": "Supply air AHU max air flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "EA Fan max air flow",
   "description": "Extract air AHU max air flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "SFP",
   "description": "Calculated SFP level.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "SA Temperature",
   "description": "Present supply air temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "SA-D Temperature",
   "description": "Present supply air density temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "EA Temperature",
   "description": "Present extract air temperature in the unit.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "EA-D Temperature",
   "description": "Present extract air density temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "EA Regulation temperature",
   "description": "Present extract air temperature used for regulation.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "EA Temperature PX/CX",
   "description": "Present extract air temperature in the unit (only AHU type PX/CX).",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "EA Temperature SD",
   "description": "Present extract air temperature in the unit (only AHU type SD).",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "Outdoor temperature COOL DX",
   "description": "Present outdoor air temperature in the COOL DX unit.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "Outdoor temperature",
   "description": "Present outdoor air temperature in the unit.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "Outdoor regulation temperature",
   "description": "Present outdoor air temperature used for regulation.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "External outdoor temperature 1",
   "description": "Present external outdoor temperature of sensor 1.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "External outdoor temperature 2",
   "description": "Present external outdoor temperature of sensor 2.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "External outdoor temperature 3",
   "description": "Present external outdoor temperature of sensor 3.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "External outdoor temperature 4",
   "description": "Present external outdoor temperature of sensor 4.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "External outdoor temperature min/max/average",
   "description": "Present calculated min, max or average",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "EA Duct temperature",
   "description": "Present extract air duct air temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "Room temperature 1",
   "description": "Present room temperature of sensor 1.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "Room temperature 2",
   "description": "Present room temperature of sensor 2.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "Room temperature 3",
   "description": "Present room temperature of sensor 3.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "Room temperature 4",
   "description": "Present room temperature of sensor 4.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "Room temperature min/max/average",
   "description": "Present calculated min, max or average",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "SA Temp regulator",
   "description": "Present supply air temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "EA Temp regulator",
   "description": "Present extract air temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Cool exchanger regulator level",
   "description": "Present operation level of cool recovery.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "Heat exchanger regulator level",
   "description": "Present operation level of heat recovery.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "Extra regulation sequence 1 heat regulator level",
   "description": "Present level of extra regulation heat.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "Extra regulation sequence 1 heat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "Reheat regulator level",
   "description": "Present level of reheat.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "Reheat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "ReCO2 heat level",
   "description": "Present level of ReCO2 heat.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "Down regulation level",
   "description": "Present level of fan down regulation.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Heating boost level",
   "description": "Present level of heating boost.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Extra regulation sequence 1 cool regulator level",
   "description": "Present level of extra regulation cool.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Extra regulation sequence 1 cool output level",
   "description": "Present level of extra regulation cool.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Cool regulator level",
   "description": "Present level of cooling.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Cool output level",
   "description": "Present level of cooling.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "ReCO2 cool level",
   "description": "Present level of ReCO2 heat.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Cooling boost level",
   "description": "Present level of cooling boost.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "RHX operation level",
   "description": "Present speed level of the rotary heat exchanger.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "RHX efficiency",
   "description": "Calculated level of rotary heat exchanger efficiency.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "RHX defrost pressure level",
   "description": "Present pressure drop for the rotary heat exchanger.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "RHX defrost pressure alarm limit",
   "description": "Present pressure drop alarm limit for the",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "RHX carry over control pressure level",
   "description": "Present pressure difference for the rotary heat exchangers purging sector.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "RHX operation time",
   "description": "Total operation time of the rotary heat exchanger presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "PX defrost pressure level",
   "description": "PHX-2/3: Present pressure drop for the plate heat exchanger.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 117,
   "name": "PHX-3D Bypass output",
   "description": "PHX-1: Present level of plate heat exchanger bypass output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "PHX-3D Bypass input",
   "description": "PHX-1: Present level of plate heat exchanger bypass input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "PHX-3D Bypass temperature 1",
   "description": "PHX-1: Present bypass temperature sensor 1 in plate heat exchanger.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "PHX-3D Bypass temperature 2",
   "description": "PHX-1: Present bypass temperature sensor 2 in plate heat exchanger.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "PX exchanger damper 1 output",
   "description": "PHX-2: Present level of plate heat exchanger damper 1 output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "PHX-2 Damper 1 input",
   "description": "Present level of plate heat exchanger damper 1 input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "PX exchanger damper 2 output",
   "description": "PHX-2: Present level of plate heat exchanger damper 2 output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "PHX-2 Damper 2 input",
   "description": "Present level of plate heat exchanger damper 2 input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "PX exchanger bypass output",
   "description": "PHX-2: Present level of plate heat exchanger bypass output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "PX exchanger bypass feedback",
   "description": "PHX-2: Present level of plate heat exchanger bypass input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "CHX Valve output",
   "description": "Present level of coil heat exchanger valve output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "CHX Valve input",
   "description": "Present level of coil heat exchanger valve input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "CHX Return water temperature",
   "description": "Present return water temperature for coil heat exchanger.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "PHX/CHX operation time",
   "description": "Total operation time of the coil heat exchanger presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "PHX-1D Bypass output",
   "description": "PHX-3: Present level of plate heat exchanger bypass output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "PHX-1D Bypass input",
   "description": "PHX-3: Present level of plate heat exchanger bypass input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "PHX/CHX Humidity level",
   "description": "PHX-1/2: Present level of air-humidity for calculation of bypass/valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "Extra regulation sequence 1 anti frost temp/overheat input",
   "description": "Present extra regulation anti frost temperature for water",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "Extra regulation sequence 2 anti frost temp/overheat input",
   "description": "Present extra regulation anti frost temperature for water",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "Extra regulation sequence 1 input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "Extra regulation sequence 1 heat operation time",
   "description": "Total operation time of extra regulation heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "Extra regulation sequence 1 cool operation time",
   "description": "Total operation time of extra regulation cool presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "Extra regulation sequence 2 input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "Extra regulation sequence 2 heat operation time",
   "description": "Total operation time of extra regulation heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "Extra regulation sequence 2 cool operation time",
   "description": "Total operation time of extra regulation cool presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "Re-heat anti frost temp/overheat input",
   "description": "Present anti frost temperature for water",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "Re-heat input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "Re-heat operation time",
   "description": "Total operation time of re-heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "Cool water temperature",
   "description": "Present cool water temperature for water cool coil.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "Cool input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "Cool operation time",
   "description": "Total operation time of cool presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "Xzone SA temperature",
   "description": "Present supply air temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 175,
   "name": "Xzone EA temperature",
   "description": "Present extract air temperature in the unit.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 176,
   "name": "Xzone EA regulation temperature",
   "description": "Present extract air temperature used for regulation.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 177,
   "name": "Xzone Room temperature 1",
   "description": "Present room temperature of sensor 1.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 178,
   "name": "Xzone Room temperature 2",
   "description": "Present room temperature of sensor 2.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 179,
   "name": "Xzone Room temperature 3",
   "description": "Present room temperature of sensor 3.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "Xzone Room temperature 4",
   "description": "Present room temperature of sensor 4.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "Xzone Room temperature min/max/average",
   "description": "Present calculated min, max or average",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 186,
   "name": "Xzone SA Temp regulator",
   "description": "Present supply air temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 187,
   "name": "Xzone EA Temp regulator",
   "description": "Present extract air temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "Xzone re-heat regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "Xzone cool regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 199,
   "name": "Xzone heat, anti frost temp/overheat input",
   "description": "Present Xzone heat anti frost temperature for water",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "Xzone heat, output level",
   "description": "Present level of Xzone heat output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "Xzone heat, input level",
   "description": "Present Xzone heat input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "Xzone heat, operation time",
   "description": "Total operation time of Xzone heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "Xzone cool, water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "Xzone cool, output level",
   "description": "Present level of Xzone cool.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 215,
   "name": "Xzone cool, input level",
   "description": "Present Xzone cool valve position.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 216,
   "name": "Xzone cool, operation time",
   "description": "Total operation time of Xzone cool presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "Pre-heat temperature",
   "description": "Present pre-heat temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 221,
   "name": "Pre-heat temp regulator set point",
   "description": "Present pre-heat temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 222,
   "name": "Pre-heat temp regulator level",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 225,
   "name": "Pre-heat anti frost temp/overheat input",
   "description": "Present pre-heat anti frost temperature for water",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 228,
   "name": "Pre-heat output level",
   "description": "Present pre-heat output level.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 229,
   "name": "Pre-heat input level",
   "description": "Present pre-heat input level.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "Pre-heat operation time",
   "description": "Total operation time of pre-heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 233,
   "name": "ReCO2 recirculation damper output",
   "description": "Present output signal to the recirculation damper.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 234,
   "name": "ReCO2 recirculation damper input",
   "description": "Present input signal from the recirculation damper.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 235,
   "name": "ReCO2 outdoor damper output",
   "description": "Present output signal to the outdoor air damper.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 236,
   "name": "ReCO2 outdoor damper input",
   "description": "Present input signal from the outdoor air damper.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 237,
   "name": "ReCO2 outdoor air flow",
   "description": "Present outdoor air flow level.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 238,
   "name": "ReCO2 outdoor air flow regulator set point",
   "description": "Present outdoor air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "SA humidity level",
   "description": "Present level of supply air humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 245,
   "name": "SA humidity temperature",
   "description": "Present temperature inside the supply air humidity sensor.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 246,
   "name": "SA dew point",
   "description": "Calculated supply air dew point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 247,
   "name": "EA humidity level",
   "description": "Present level of extract air humidity.",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 248,
   "name": "EA humidity temperature",
   "description": "Present temperature inside the extract air humidity sensor.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 249,
   "name": "EA dew point",
   "description": "Calculated extract air dew point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Dehumidifying SA dew point regulator set point",
   "description": "Present supply air dew point regulator point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Dehumidifying output level",
   "description": "Present level of the dehumidifying output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "Humidifying SA regulator set point",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 255,
   "name": "Humidifying output level",
   "description": "Present level of the dehumidifying output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 266,
   "name": "VOC level",
   "description": "Present level of VOC",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 271,
   "name": "COOL DX, unit power size",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 274,
   "name": "COOL DX, compressor 1 low pressure level",
   "description": "",
   "units": "Bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 275,
   "name": "COOL DX, compressor 1 high pressure level",
   "description": "",
   "units": "Bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 276,
   "name": "COOL DX, compressor 2 low pressure level",
   "description": "",
   "units": "Bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 277,
   "name": "COOL DX, compressor 2 high pressure level",
   "description": "",
   "units": "Bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "SMART Link, WB outlet water 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "SMART Link, WB outlet water 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 291,
   "name": "SMART Link, WB outlet water 3",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 292,
   "name": "SMART Link, WB outlet water 4",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 293,
   "name": "SMART Link, WB outlet water average",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 294,
   "name": "SMART Link, WB return water",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 297,
   "name": "SMART Link WB, heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 298,
   "name": "SMART Link WB, chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "SMART Link WB, Min heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "SMART Link WB, Max heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "SMART Link WB, Min chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "SMART Link WB, Max chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 327,
   "name": "SMART Link, DX unit 1 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 328,
   "name": "SMART Link, DX unit 1 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 329,
   "name": "SMART Link, DX unit 1 operation time",
   "description": "",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 338,
   "name": "SMART Link, DX unit 2 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 339,
   "name": "SMART Link, DX unit 2 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 340,
   "name": "SMART Link, DX unit 2 operation time",
   "description": "",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 349,
   "name": "SMART Link, DX unit 3 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 350,
   "name": "SMART Link, DX unit 3 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 351,
   "name": "SMART Link, DX unit 3 operation time",
   "description": "",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 360,
   "name": "SMART Link, DX unit 4 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 361,
   "name": "SMART Link, DX unit 4 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 362,
   "name": "SMART Link, DX unit 4 operation time",
   "description": "",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 374,
   "name": "AYC Heat, heated water",
   "description": "Present heat temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 375,
   "name": "AYC Heated water set point",
   "description": "Present heat temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 376,
   "name": "AYC Heat, valve output",
   "description": "Present level of the heat valve output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 377,
   "name": "AYC Heat, valve input",
   "description": "Present level of the heat valve input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 378,
   "name": "AYC Heat, operation time",
   "description": "Total operation time of AYC heat presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 379,
   "name": "AYC Heated water heat demand",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 387,
   "name": "AYC Cool, chilled water",
   "description": "Present cool temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 388,
   "name": "AYC Chilled water set point",
   "description": "Present cool temperature regulator set point.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 389,
   "name": "AYC Cool, valve output",
   "description": "Present cool of the heat valve output.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 390,
   "name": "AYC Cool, valve input",
   "description": "Present cool of the heat valve input.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 391,
   "name": "AYC Cool, operation time",
   "description": "Total operation time of AYC cool presented in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 392,
   "name": "AYC Chilled water cool demand",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 400,
   "name": "MIRU Control 1 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 401,
   "name": "MIRU Control 1 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 402,
   "name": "MIRU Control 1 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 403,
   "name": "MIRU Control 1 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 404,
   "name": "MIRU Control 1 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 405,
   "name": "MIRU Control 1 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 406,
   "name": "MIRU Control 1 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 407,
   "name": "MIRU Control 1 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 408,
   "name": "MIRU Control 1 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 409,
   "name": "MIRU Control 1 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 410,
   "name": "MIRU Control 1 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 411,
   "name": "MIRU Control 1 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 412,
   "name": "MIRU Control 1 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 417,
   "name": "MIRU Control 2 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 418,
   "name": "MIRU Control 2 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 419,
   "name": "MIRU Control 2 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 420,
   "name": "MIRU Control 2 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 421,
   "name": "MIRU Control 2 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 422,
   "name": "MIRU Control 2 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 423,
   "name": "MIRU Control 2 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 424,
   "name": "MIRU Control 2 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 425,
   "name": "MIRU Control 2 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 426,
   "name": "MIRU Control 2 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 427,
   "name": "MIRU Control 2 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 428,
   "name": "MIRU Control 2 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 429,
   "name": "MIRU Control 2 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 434,
   "name": "MIRU Control 3 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 435,
   "name": "MIRU Control 3 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 436,
   "name": "MIRU Control 3 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 437,
   "name": "MIRU Control 3 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 438,
   "name": "MIRU Control 3 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 439,
   "name": "MIRU Control 3 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 440,
   "name": "MIRU Control 3 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 441,
   "name": "MIRU Control 3 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 442,
   "name": "MIRU Control 3 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 443,
   "name": "MIRU Control 3 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 444,
   "name": "MIRU Control 3 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 445,
   "name": "MIRU Control 3 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 446,
   "name": "MIRU Control 3 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 451,
   "name": "MIRU Control 4 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 452,
   "name": "MIRU Control 4 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 453,
   "name": "MIRU Control 4 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 454,
   "name": "MIRU Control 4 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 455,
   "name": "MIRU Control 4 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 456,
   "name": "MIRU Control 4 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 457,
   "name": "MIRU Control 4 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 458,
   "name": "MIRU Control 4 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 459,
   "name": "MIRU Control 4 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 460,
   "name": "MIRU Control 4 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 461,
   "name": "MIRU Control 4 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 462,
   "name": "MIRU Control 4 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 463,
   "name": "MIRU Control 4 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 468,
   "name": "MIRU Control 5 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 469,
   "name": "MIRU Control 5 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 470,
   "name": "MIRU Control 5 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 471,
   "name": "MIRU Control 5 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 472,
   "name": "MIRU Control 5 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 473,
   "name": "MIRU Control 5 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 474,
   "name": "MIRU Control 5 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 475,
   "name": "MIRU Control 5 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 476,
   "name": "MIRU Control 5 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 477,
   "name": "MIRU Control 5 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 478,
   "name": "MIRU Control 5 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 479,
   "name": "MIRU Control 5 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 480,
   "name": "MIRU Control 5 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 485,
   "name": "MIRU Control 6 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 486,
   "name": "MIRU Control 6 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 487,
   "name": "MIRU Control 6 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 488,
   "name": "MIRU Control 6 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 489,
   "name": "MIRU Control 6 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 490,
   "name": "MIRU Control 6 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 491,
   "name": "MIRU Control 6 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 492,
   "name": "MIRU Control 6 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 493,
   "name": "MIRU Control 6 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 494,
   "name": "MIRU Control 6 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 495,
   "name": "MIRU Control 6 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 496,
   "name": "MIRU Control 6 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 497,
   "name": "MIRU Control 6 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 502,
   "name": "MIRU Control 7 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 503,
   "name": "MIRU Control 7 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 504,
   "name": "MIRU Control 7 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 505,
   "name": "MIRU Control 7 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 506,
   "name": "MIRU Control 7 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 507,
   "name": "MIRU Control 7 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 508,
   "name": "MIRU Control 7 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 509,
   "name": "MIRU Control 7 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 510,
   "name": "MIRU Control 7 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 511,
   "name": "MIRU Control 7 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 512,
   "name": "MIRU Control 7 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 513,
   "name": "MIRU Control 7 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 514,
   "name": "MIRU Control 7 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 519,
   "name": "MIRU Control 8 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 520,
   "name": "MIRU Control 8 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 521,
   "name": "MIRU Control 8 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 522,
   "name": "MIRU Control 8 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 523,
   "name": "MIRU Control 8 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 524,
   "name": "MIRU Control 8 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 525,
   "name": "MIRU Control 8 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 526,
   "name": "MIRU Control 8 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 527,
   "name": "MIRU Control 8 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 528,
   "name": "MIRU Control 8 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 529,
   "name": "MIRU Control 8 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 530,
   "name": "MIRU Control 8 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 531,
   "name": "MIRU Control 8 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 536,
   "name": "MIRU Control 9 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 537,
   "name": "MIRU Control 9 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 538,
   "name": "MIRU Control 9 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 539,
   "name": "MIRU Control 9 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 540,
   "name": "MIRU Control 9 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 541,
   "name": "MIRU Control 9 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 542,
   "name": "MIRU Control 9 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 543,
   "name": "MIRU Control 9 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 544,
   "name": "MIRU Control 9 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 545,
   "name": "MIRU Control 9 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 546,
   "name": "MIRU Control 9 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 547,
   "name": "MIRU Control 9 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 548,
   "name": "MIRU Control 9 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 553,
   "name": "MIRU Control 10 Min air flow",
   "description": "Min possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 554,
   "name": "MIRU Control 10 Max air flow",
   "description": "Max possible air flow setting",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 555,
   "name": "MIRU Control 10 Air flow",
   "description": "Present air flow.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 556,
   "name": "MIRU Control 10 Air flow set point",
   "description": "Present air flow regulator set point.",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 557,
   "name": "MIRU Control 10 Pressure",
   "description": "Present duct pressure.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 558,
   "name": "MIRU Control 10 Pressure set point",
   "description": "Present duct pressure regulator set point.",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 559,
   "name": "MIRU Control 10 External temperature",
   "description": "Present external temperature.",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 560,
   "name": "MIRU Control 10 Operation time",
   "description": "Present operation time, present in days (24h).",
   "units": "Days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 561,
   "name": "MIRU Control 10 Fan level",
   "description": "Present running level of the fan.",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 562,
   "name": "MIRU Control 10 Fan power",
   "description": "Present power consumption level of the fan.",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 563,
   "name": "MIRU Control 10 SFP",
   "description": "Present SFP value.",
   "units": "kW/m3/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 564,
   "name": "MIRU Control 10 kWh",
   "description": "kWh value.",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 565,
   "name": "MIRU Control 10 MWh",
   "description": "MWh value.",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 570,
   "name": "IQlogic software version",
   "description": "Present controller software version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 604,
   "name": "Triggered alarm #1",
   "description": "((Alarm group - 1) x 15) + alarm number in group=Triggered alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 605,
   "name": "Triggered alarm #2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 606,
   "name": "Triggered alarm #3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 607,
   "name": "Triggered alarm #4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 608,
   "name": "Triggered alarm #5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 609,
   "name": "Triggered alarm #6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 610,
   "name": "Triggered alarm #7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 611,
   "name": "Triggered alarm #8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 612,
   "name": "Triggered alarm #9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 613,
   "name": "Triggered alarm #10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 614,
   "name": "Triggered alarm group #1",
   "description": "Zero if no triggered alarm group.",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 615,
   "name": "Triggered alarm group #2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 616,
   "name": "Triggered alarm group #3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 617,
   "name": "Triggered alarm group #4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 618,
   "name": "Triggered alarm group #5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 619,
   "name": "Triggered alarm group #6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 620,
   "name": "Triggered alarm group #7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 621,
   "name": "Triggered alarm group #8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 622,
   "name": "Triggered alarm group #9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 623,
   "name": "Triggered alarm group #10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Extract air start up",
   "description": "Extract air start up flow.",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "SA low speed air flow set point",
   "description": "Supply air flow set point for the unit when running in low",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "EA low speed air flow set point",
   "description": "Extract air flow set point for the unit when running in low",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "SA high speed air flow set point",
   "description": "Supply air flow set point for the unit when running in high",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "EA high speed air flow set point",
   "description": "Extract air flow set point for the unit when running in high",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "SA max speed air flow set point",
   "description": "Supply air flow max. limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "EA max speed air flow set point",
   "description": "Extract air flow max. limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "SA regulation zone",
   "description": "Supply air flow regulation zone setting in % of the present air",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "EA regulation zone",
   "description": "Extract air flow regulation zone setting in % of the present air",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SA regulation I-time",
   "description": "Supply air flow regulator affection setting.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "EA regulation I-time",
   "description": "Extract air flow regulator affection setting.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "SA low speed pressure set point",
   "description": "Supply air duct pressure set point for the unit when running in",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "EA low speed pressure set point",
   "description": "Extract air duct pressure set point for the unit when running in",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "SA high speed pressure set point",
   "description": "Supply air duct pressure for the unit when running in high speed",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "EA high speed pressure set point",
   "description": "Extract air duct pressure set point for the unit when running in",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "SA max speed pressure set point",
   "description": "Supply air duct pressure max. limit for the unit when the low/high",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "EA max speed pressure set point",
   "description": "Extract air duct pressure max. limit for the unit when the low/high",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "SA max speed output signal",
   "description": "Max. limit for the supply air fan speed when running in pressure",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "EA max speed output signal",
   "description": "Max. limit for the extract air fan speed when running in pressure",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "SA pressure regulation zone",
   "description": "Supply air pressure regulation zone setting in % of the present duct",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "EA pressure regulation zone",
   "description": "Extract air pressure regulation zone setting in % of the present duct",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "SA pressure I-time",
   "description": "Supply air pressure regulator affection setting.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "EA pressure I-time",
   "description": "Extract air pressure regulator affection setting.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Demand low speed demand set point",
   "description": "Set point for the 0..10V input signal for the unit when running",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Demand high speed demand set point",
   "description": "Set point for the 0..10V input signal for the unit when running",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SA min speed air flow set point",
   "description": "Supply air flow min. limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "EA min speed air flow set point",
   "description": "Extract air flow min. limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SA max speed air flow set point",
   "description": "Supply air flow max limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "EA max speed air flow set point",
   "description": "Extract air flow max. limit for the unit when the low/high speed",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "SA demand P-band",
   "description": "Supply air demand regulator P-band setting.",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "SA demand I-time",
   "description": "Supply air demand regulator affection setting.",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Slave offset factor",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Outdoor temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Outdoor temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Outdoor temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Outdoor temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Outdoor temp compensation Y1 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Outdoor temp compensation Y2 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Outdoor temp compensation Y3 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "Outdoor temp compensation Y4 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Outdoor temp compensation Y1 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Outdoor temp compensation Y2 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Outdoor temp compensation Y3 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Outdoor temp compensation Y4 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Outdoor temp compensation Y1 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Outdoor temp compensation Y2 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "Outdoor temp compensation Y3 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Outdoor temp compensation Y4 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "Outdoor temp compensation Y1 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Outdoor temp compensation Y2 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Outdoor temp compensation Y3 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Outdoor temp compensation Y4 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "Down regulation neutralzone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "Down regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "Down regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "SA fan speed at fire alarm 1",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "EA fan speed at fire alarm 1",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "SA fan speed at fire alarm 2",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "EA fan speed at fire alarm 2",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "SA fan speed at internal fire alarm",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "EA fan speed at internal fire alarm",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "SA pre-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "EA pre-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "SA AHU-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "EA AHU-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "SA end-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "ERS 1 step",
   "description": "Curve setting according to the diagram for ERS 1.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "ERS 1 diff",
   "description": "Supply air temp difference setting according to the diagram for ERS 1.",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "ERS 1 breakpoint",
   "description": "Breakpoint temp setting according to the diagram for ERS 1.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "ERS 2 breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "ERS 2 breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "ERS 2 breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "ERS 2 breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "ERS 2 breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "ERS 2 breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "ERS 2 breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "ERS 2 breakpoint Y4",
   "description": "Breakpoint Y4 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "SA temperature set point",
   "description": "Supply air temperature setting",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "EA/Room temperature set point",
   "description": "Extract air/room temperature setting",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "SA min temp set point",
   "description": "Supply air min. set point during EA/room",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "SA max temp set point",
   "description": "Supply air max. set point during EA/room",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "EA regultaion P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "EA regultaion I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "ORS breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "ORS breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "ORS breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "ORS breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "ORS breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "ORS breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "ORS breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "ORS breakpoint Y4",
   "description": "Breakpoint Y4 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "ORE breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "ORE breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "ORE breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "ORE breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "ORE breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "ORE breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "ORE breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "ORE breakpoint Y4",
   "description": "Breakpoint Y4 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "External room temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "External room temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "External OA temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "External OA temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "RHX defrost start limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "RHX sorption rotor function",
   "description": "Moved to Multistate Value 188",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "RHX min exhaust air temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "RHX min exhaust air temp P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "RHX min exhaust air temp I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "PHX periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "PHX periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "CHX periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "CHX periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "PHX/CHX Bypass defrost limit",
   "description": "PHX is default 3°C, CHX is default 5°C.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "PHX/CHX Bypass defrost P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "PHX/CHX Bypass defrost I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "Heat exchange temperature regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "Heat exchange temperature regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "Cool exchange temperature regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "Cool exchange temperature regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "Re-heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "Re-heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Re-heat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "Re-heat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "Extra regulation sequence 1 heat max output signal",
   "description": "Maximum output signal setting for the extra regulation sequence.",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "Extra regulation sequence 1 cool max output signal",
   "description": "Maximum output signal setting for the extra regulation sequence.",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "Extra regulation sequence 1 heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "Extra regulation sequence 1 heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "Extra regulation sequence 1 cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "Extra regulation sequence 1 cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "Extra regulation 1 periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "Extra regulation 1 periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 252,
   "name": "Extra regulation 1 temperature protection temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 253,
   "name": "Extra regulation 1 temperature protection alarm delay",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 258,
   "name": "Cool step 1 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 259,
   "name": "Cool step 2 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 260,
   "name": "Cool step 3 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 262,
   "name": "Cool SA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 263,
   "name": "Cool EA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 264,
   "name": "Cool outdoor temp limit 1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "Cool outdoor temp limit 2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "Cool outdoor temp limit 3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "Cool 0-10V min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "Cool 0-10V min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "Cool restart time",
   "description": "Setting of cool restart time between start-start.",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "Cool step up delay time",
   "description": "Setting of on/off cooling and COOL DX time delay between steps.",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "Cool stand still time",
   "description": "Setting of on/off cooling and COOL DX time delay before stop-start",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "Cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "Cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "Cool periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "Cool periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "Cool step 1 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "Cool step 2 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "Cool step 3 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "Summer night cool start time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "Summer night cool start time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "Summer night cool stop time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "Summer night cool stop time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "Summer night cool OA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "Summer night cool EA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "Summer night cool EA temp stop limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "Summer night cool SA temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "Intermittent night heat SA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "Intermittent night heat SA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 299,
   "name": "Intermittent night heat EA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "Intermittent night heat EA temp stop limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "Intermittent night heat SA temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "Intermittent night heat EA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 304,
   "name": "Intermittent night heat EA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 306,
   "name": "Morning boost start time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 307,
   "name": "Morning boost start time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 308,
   "name": "Morning boost air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 309,
   "name": "Morning boost duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "Cooling boost comfort start limit",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "Cooling boost comfort regulation speed",
   "description": "",
   "units": "%/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "Cooling boost economy P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "Cooling boost economy I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "Heating boost comfort start limit",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "Heating boost comfort regulation speed",
   "description": "",
   "units": "%/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 331,
   "name": "Xzone ERS 1 step",
   "description": "Curve setting according to the diagram for ERS 1.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 332,
   "name": "Xzone ERS 1 diff",
   "description": "Supply air temp differental setting according to the diagram for ERS 1.",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 333,
   "name": "Xzone ERS 1 breakpoint",
   "description": "Breakpoint temp setting according to the diagram for ERS 1.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 336,
   "name": "Xzone ERS 2 breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 337,
   "name": "Xzone ERS 2 breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338,
   "name": "Xzone ERS 2 breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339,
   "name": "Xzone ERS 2 breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 340,
   "name": "Xzone ERS 2 breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 341,
   "name": "Xzone ERS 2 breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 342,
   "name": "Xzone ERS 2 breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 343,
   "name": "Xzone ERS 2 breakpoint Y4",
   "description": "Breakpoint Y4 setting according to the diagram for ERS 2.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 346,
   "name": "Xzone SA temperature set point",
   "description": "Supply air temperature setting, for supply air temp regulation mode.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 349,
   "name": "Xzone EA/Room temperature set point",
   "description": "Extract air/room temperature setting",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 350,
   "name": "Xzone SA min temp set point",
   "description": "Supply air min. set point during EA/room",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 351,
   "name": "Xzone SA max temp set point",
   "description": "Supply air max. set point during EA/room",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 352,
   "name": "Xzone EA regultaion P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 353,
   "name": "Xzone EA regultaion I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 354,
   "name": "Xzone ORS breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 355,
   "name": "Xzone ORS breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 356,
   "name": "Xzone ORS breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 357,
   "name": "Xzone ORS breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 358,
   "name": "Xzone ORS breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 359,
   "name": "Xzone ORS breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 360,
   "name": "Xzone ORS breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 361,
   "name": "Xzone ORS breakpoint Y4",
   "description": "Breakpoint Y4 setting according to the diagram for ORS.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 364,
   "name": "Xzone ORE breakpoint X1",
   "description": "Breakpoint X1 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 365,
   "name": "Xzone ORE breakpoint X2",
   "description": "Breakpoint X2 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 366,
   "name": "Xzone ORE breakpoint X3",
   "description": "Breakpoint X3 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 367,
   "name": "Xzone ORE breakpoint X4",
   "description": "Breakpoint X4 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 368,
   "name": "Xzone ORE breakpoint Y1",
   "description": "Breakpoint Y1 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 369,
   "name": "Xzone ORE breakpoint Y2",
   "description": "Breakpoint Y2 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 370,
   "name": "Xzone ORE breakpoint Y3",
   "description": "Breakpoint Y3 setting according to the diagram for ORE.",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 371,
   "name": "Xzone ORE breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 380,
   "name": "Xzone external room temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 381,
   "name": "Xzone external room temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 384,
   "name": "Xzone reheat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 385,
   "name": "Xzone reheat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 388,
   "name": "Xzone reheat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "Xzone reheat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "Xzone Cool SA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 397,
   "name": "Xzone Cool EA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "Xzone Cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "Xzone Cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 403,
   "name": "Xzone Cool periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 404,
   "name": "Xzone Cool periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "Pre-heat temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "Pre-heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "Pre-heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 416,
   "name": "Pre-heat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 417,
   "name": "Pre-heat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 426,
   "name": "ReCO2-CO2 set point",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 427,
   "name": "ReCO2 min. outdoor air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 428,
   "name": "ReCO2 min. exhaust air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 429,
   "name": "ReCO2-CO2 P-band",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 430,
   "name": "ReCO2-CO2 I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 431,
   "name": "ReCO2-CO2 air flow boost reg. P-band",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 432,
   "name": "ReCO2-CO2 air flow boost reg. I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 433,
   "name": "ReCO2 heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 434,
   "name": "ReCO2 heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 435,
   "name": "ReCO2 cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 436,
   "name": "ReCO2 cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 443,
   "name": "Humidifying on/off start level",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "Humidifying on/off stop level",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 448,
   "name": "Humidifying 0-10V set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 449,
   "name": "Humidifying 0-10V SA max set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 450,
   "name": "Humidifying 0-10V SA P-band",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 451,
   "name": "Humidifying 0-10V SA I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 452,
   "name": "Humidifying 0-10V EA P-band",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 453,
   "name": "Humidifying 0-10V EA I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 458,
   "name": "Dehumidifying set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 470,
   "name": "COOL DX Low pressure stop limit",
   "description": "",
   "units": "Bar",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 471,
   "name": "COOL DX High pressure stop limit",
   "description": "",
   "units": "Bar",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 472,
   "name": "COOL DX Restart time",
   "description": "Time setting between start - start",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 482,
   "name": "SMART Link WB Heat temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 483,
   "name": "SMART Link WB Heat temperature heat zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 484,
   "name": "SMART Link WB Cool temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 485,
   "name": "SMART Link WB Cool temperature heat zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 491,
   "name": "SMART Link WB Optimize valve upper limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 492,
   "name": "SMART Link WB Optimize valve lower limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 493,
   "name": "SMART Link WB Optimize time delay",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 494,
   "name": "SMART Link WB Optimize heat regulation speed",
   "description": "",
   "units": "K/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 495,
   "name": "SMART Link WB Optimize cool regulation speed",
   "description": "",
   "units": "K/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 510,
   "name": "SMART Link DX Amount of units",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 519,
   "name": "SMART Link OA temp limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 524,
   "name": "AYC Heated water temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 526,
   "name": "AYC Heated water OA temp for start of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 527,
   "name": "AYC Heated water OA temp for stop of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 532,
   "name": "AYC Heated water periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 533,
   "name": "AYC Heated water periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "AYC Heated water OA temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "AYC Heated water OA temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 539,
   "name": "AYC Heated water OA temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540,
   "name": "AYC Heated water OA temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 541,
   "name": "AYC Heated water OA temp compensation Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542,
   "name": "AYC Heated water OA temp compensation Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 543,
   "name": "AYC Heated water OA temp compensation Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544,
   "name": "AYC Heated water OA temp compensation Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 549,
   "name": "AYC Heated water room temp compensation temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 550,
   "name": "AYC Heated water room temp compensation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 554,
   "name": "AYC Heated water night temp compensation temp",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 556,
   "name": "AYC Heated water night temp compensation start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 557,
   "name": "AYC Heated water night temp compensation start time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 558,
   "name": "AYC Heated water night temp compensation stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 559,
   "name": "AYC Heated water night temp compensation stop time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 563,
   "name": "AYC Heated water night temp compensation start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 564,
   "name": "AYC Heated water night temp compensation start time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 565,
   "name": "AYC Heated water night temp compensation stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 566,
   "name": "AYC Heated water night temp compensation stop time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 569,
   "name": "AYC Heated water P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 570,
   "name": "AYC Heated water I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 572,
   "name": "AYC Chilled water temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 575,
   "name": "AYC Chilled water OA temp for start of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 576,
   "name": "AYC Chilled water OA temp for stop of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 581,
   "name": "AYC Chilled water periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582,
   "name": "AYC Chilled water periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 586,
   "name": "AYC Chilled water OA temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 587,
   "name": "AYC Chilled water OA temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 588,
   "name": "AYC Chilled water OA temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 589,
   "name": "AYC Chilled water OA temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 590,
   "name": "AYC Chilled water OA temp compensation Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 591,
   "name": "AYC Chilled water OA temp compensation Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 592,
   "name": "AYC Chilled water OA temp compensation Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 593,
   "name": "AYC Chilled water OA temp compensation Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 598,
   "name": "AYC Chilledwater room temp compensation temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 599,
   "name": "AYC Chilled water room temp compensation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 603,
   "name": "AYC Chilled water night temp compensation temp",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 605,
   "name": "AYC Chilled water night temp compensation start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 606,
   "name": "AYC Chilled water night temp compensation start time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 607,
   "name": "AYC Chilled water night temp compensation stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 608,
   "name": "AYC Chilled water night temp compensation stop time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 612,
   "name": "AYC Chilled water night temp compensation start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 613,
   "name": "AYC Chilled water night temp compensation start time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 614,
   "name": "AYC Chilledwater night temp compensation stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 615,
   "name": "AYC Chilled water night temp compensation stop time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 619,
   "name": "AYC Chilled water dew point compensation neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 620,
   "name": "AYC Chilled water dew point compensation regulation speed",
   "description": "Percent air flow boost of each increased chilled water set point.",
   "units": "%/K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 623,
   "name": "AYC Chilled water P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 624,
   "name": "AYC Chilled water I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 638,
   "name": "Optimize SA pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 639,
   "name": "Optimize EA pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 672,
   "name": "MIRU Control 1 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 673,
   "name": "MIRU Control 1 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 674,
   "name": "MIRU Control 1 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 675,
   "name": "MIRU Control 1 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 680,
   "name": "MIRU Control 2 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 681,
   "name": "MIRU Control 2 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 682,
   "name": "MIRU Control 2 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 683,
   "name": "MIRU Control 2 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 688,
   "name": "MIRU Control 3 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 689,
   "name": "MIRU Control 3 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 690,
   "name": "MIRU Control 3 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 691,
   "name": "MIRU Control 3 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 696,
   "name": "MIRU Control 4 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 697,
   "name": "MIRU Control 4 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 698,
   "name": "MIRU Control 4 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 699,
   "name": "MIRU Control 4 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 704,
   "name": "MIRU Control 5 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 705,
   "name": "MIRU Control 5 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 706,
   "name": "MIRU Control 5 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 707,
   "name": "MIRU Control 5 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 712,
   "name": "MIRU Control 6 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 713,
   "name": "MIRU Control 6 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 714,
   "name": "MIRU Control 6 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 715,
   "name": "MIRU Control 6 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 720,
   "name": "MIRU Control 7 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 721,
   "name": "MIRU Control 7 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 722,
   "name": "MIRU Control 7 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 723,
   "name": "MIRU Control 7 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 728,
   "name": "MIRU Control 8 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 729,
   "name": "MIRU Control 8 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 730,
   "name": "MIRU Control 8 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 731,
   "name": "MIRU Control 8 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 736,
   "name": "MIRU Control 9 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 737,
   "name": "MIRU Control 9 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 738,
   "name": "MIRU Control 9 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 739,
   "name": "MIRU Control 9 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 744,
   "name": "MIRU Control 10 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 745,
   "name": "MIRU Control 10 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 746,
   "name": "MIRU Control 10 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 747,
   "name": "MIRU Control 10 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Operation active",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Damper operation active",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Low speed operation active",
   "description": "Low speed operation status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "High speed operation active",
   "description": "High speed operation status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Intermittent night heat active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Morning boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Heating boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Cooling boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Summer night cool active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "A-alarm active",
   "description": "Any alarm with priority class A active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "B-alarm active",
   "description": "Any alarm with priority class B active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "HX operation active",
   "description": "HX status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "HX cool recovery active",
   "description": "HX cool recovery status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "HX defrost active",
   "description": "HX defrost status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "RHX speed monitor signal",
   "description": "RHX speed monitor status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "CHX pump output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "CHX pump input",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "Season heat, extra regulation sequence allowed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Season heat, re-heat allowed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Extra regulation sequence 1, output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "Extra regulation sequence 1, power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Extra regulation sequence 1, anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Re-heat output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "Re-heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "Re-heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Cool output 1",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Cool output 2",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "Extra regulation sequence 2, output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "Extra regulation sequence 2, power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "Extra regulation sequence 2, anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "Pre-heat output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "Pre-heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "Pre-heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "Xzone heat output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "Xzone heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "Xzone heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "Xzone cool output 1",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "Xzone cool output 2",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 99,
   "name": "AYC heat pump output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "AYC heat pump input",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "Max. limit for the supply air fan speed when running in pressure regulation mo",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "AYC cool pump input",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "COOL DX compressor 1 output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "COOL DX compressor 1 input",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 115,
   "name": "COOL DX compressor 2 output",
   "description": "Relay output status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 116,
   "name": "COOL DX compressor 2 input",
   "description": "Digital input status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 319,
   "name": "SMART Link, DX operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 323,
   "name": "SMART Link, DX unit 1 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 324,
   "name": "SMART Link, DX unit 1 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 325,
   "name": "SMART Link, DX unit 1 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 326,
   "name": "SMART Link, DX unit 1 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 334,
   "name": "SMART Link, DX unit 2 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 335,
   "name": "SMART Link, DX unit 2 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 336,
   "name": "SMART Link, DX unit 2 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 337,
   "name": "SMART Link, DX unit 2 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 345,
   "name": "SMART Link, DX unit 3 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 346,
   "name": "SMART Link, DX unit 3 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 347,
   "name": "SMART Link, DX unit 3 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 348,
   "name": "SMART Link, DX unit 3 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 356,
   "name": "SMART Link, DX unit 4 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 357,
   "name": "SMART Link, DX unit 4 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 358,
   "name": "SMART Link, DX unit 4 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 359,
   "name": "SMART Link, DX unit 4 power defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 501,
   "name": "Alarm 1:1 External fire alarm no. 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 502,
   "name": "Alarm 1:2 External fire alarm no. 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 503,
   "name": "Alarm 1:3 Internal fire alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 516,
   "name": "Alarm 2:1 External alarm no. 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 517,
   "name": "Alarm 2:2 External alarm no. 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 531,
   "name": "Alarm 3:1 Pre-heat I/O-module no. 9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 532,
   "name": "Alarm 3:2 Pre-heat electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 533,
   "name": "Alarm 3:3 Pre-heat frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 534,
   "name": "Alarm 3:4 Pre-heat frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 535,
   "name": "Alarm 3:5 Pre-heat temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 536,
   "name": "Alarm 3:6 Pre-heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 537,
   "name": "Alarm 3:7 Pre-heat temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 538,
   "name": "Alarm 3:8 Pre-heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 546,
   "name": "Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 547,
   "name": "Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 548,
   "name": "Alarm 4:3 Extra reg. sequence 1 frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 549,
   "name": "Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 550,
   "name": "Alarm 4:5 Extra reg. sequence 1 valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 551,
   "name": "Alarm 4:6 Extra reg. sequence 1 alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 552,
   "name": "Alarm 4:7 Extra reg. sequence 1 temperature protection from com. Error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 554,
   "name": "Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 555,
   "name": "Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 556,
   "name": "Alarm 4:11 Extra reg. sequence 2 frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 557,
   "name": "Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 558,
   "name": "Alarm 4:13 Extra reg. sequence 2 valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 559,
   "name": "Alarm 4:14 Extra reg. sequence 2 alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 561,
   "name": "Alarm 5:1 Re-heat electrical heater over heat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 562,
   "name": "Alarm 5:2 Re-heat frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 563,
   "name": "Alarm 5:3 Re-heat frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 564,
   "name": "Alarm 5:4 Re-heat heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 576,
   "name": "Alarm 6:1 Xzone I/O-module no. A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 577,
   "name": "Alarm 6:2 Xzone electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 578,
   "name": "Alarm 6:3 Xzone frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 579,
   "name": "Alarm 6:4 Xzone frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 580,
   "name": "Alarm 6:5 Xzone supply air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 581,
   "name": "Alarm 6:6 Xzone heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 582,
   "name": "Alarm 6:7 Xzone supply air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 583,
   "name": "Alarm 6:8 Xzone supply air temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 584,
   "name": "Alarm 6:9 Xzone heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 591,
   "name": "Alarm 7:1 Xzone I/O-module no. B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 592,
   "name": "Alarm 7:2 Xzone extract air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 593,
   "name": "Alarm 7:3 Xzone cool valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 594,
   "name": "Alarm 7:4 Xzone extract air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 595,
   "name": "Alarm 7:5 Xzone cool alarm input 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 596,
   "name": "Alarm 7:6 Xzone cool alarm input 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 610,
   "name": "Alarm 8:5 Cool valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 636,
   "name": "Alarm 10:1 Supply air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 637,
   "name": "Alarm 10:2 Supply air temperature sensor for density compensation defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 638,
   "name": "Alarm 10:3 Extract air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 639,
   "name": "Alarm 10:4 Extract air temperature sensor for density compensation defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 640,
   "name": "Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 641,
   "name": "Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 642,
   "name": "Alarm 10:7 Extract air duct temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 645,
   "name": "Alarm 10:10 Outdoor air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 651,
   "name": "Alarm 11:1 Room temperature sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 652,
   "name": "Alarm 11:2 Room temperature sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 653,
   "name": "Alarm 11:3 Room temperature sensor no. 3 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 654,
   "name": "Alarm 11:4 Room temperature sensor no. 4 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 655,
   "name": "Alarm 11:5 Xzone room temperature sensor no. 5 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 656,
   "name": "Alarm 11:6 Xzone room temperature sensor no. 6 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 657,
   "name": "Alarm 11:7 Xzone room temperature sensor no. 7 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 658,
   "name": "Alarm 11:8 Xzone room temperature sensor no. 8 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 659,
   "name": "Alarm 11:9 Outdoor temperature sensor no. A defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 660,
   "name": "Alarm 11:10 Outdoor temperature sensor no. B defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 661,
   "name": "Alarm 11:11 Outdoor temperature sensor no. C defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 662,
   "name": "Alarm 11:12 Outdoor temperature sensor no. D defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 663,
   "name": "Alarm 11:13 Room temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 664,
   "name": "Alarm 11:14 Xzone room temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 665,
   "name": "Alarm 11:15 Outdoor temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 666,
   "name": "Alarm 12:1 Supply air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 667,
   "name": "Alarm 12:2 Supply air temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 671,
   "name": "Alarm 12:6 Extract air temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 676,
   "name": "Alarm 12:11 Temperature guard below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 681,
   "name": "Alarm 13:1 Humidification I/O-module no. 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 682,
   "name": "Alarm 13:2 Supply air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 683,
   "name": "Alarm 13:3 Extract air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 689,
   "name": "Alarm 13:9 Humidifier alarm output tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 691,
   "name": "Alarm 13:11 VOC sensor com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 692,
   "name": "Alarm 13:12 VOC sensor internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 693,
   "name": "Alarm 13:13 VOC sensor internal error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 694,
   "name": "Alarm 13:14 VOC sensor level below/above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 711,
   "name": "Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 712,
   "name": "Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 713,
   "name": "Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 714,
   "name": "Alarm 15:4 Plate heat exchanger damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 717,
   "name": "Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 718,
   "name": "Alarm 15:8 Plate heat exchanger bypass damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 719,
   "name": "Alarm 15:9 Plate heat exchanger damper no. 1 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 720,
   "name": "Alarm 15:10 Plate heat exchanger damper no. 2 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 721,
   "name": "Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 722,
   "name": "Alarm 15:12 Plate heat exchanger bypass damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 724,
   "name": "Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 725,
   "name": "Alarm 15:15 Plate heat exchanger defrost pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 726,
   "name": "Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 727,
   "name": "Alarm 16:2 Coil heat exchanger temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 728,
   "name": "Alarm 16:3 Coil heat exchanger valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 729,
   "name": "Alarm 16:4 Coil heat exchanger pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 741,
   "name": "Alarm 17:1 Rotary heat exchanger motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 742,
   "name": "Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 743,
   "name": "Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 744,
   "name": "Alarm 17:4 Rotary heat exchanger speed monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 745,
   "name": "Alarm 17:5 Rotary heat exchanger motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 746,
   "name": "Alarm 17:6 Rotary heat exchanger motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 747,
   "name": "Alarm 17:7 Rotary heat exchanger motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 748,
   "name": "Alarm 17:8 Rotary heat exchanger motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 749,
   "name": "Alarm 17:9 Rotary heat exchanger motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 756,
   "name": "Alarm 18:1 AYC I/O-module no. 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 757,
   "name": "Alarm 18:2 AYC heat temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 758,
   "name": "Alarm 18:3 AYC heat valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 759,
   "name": "Alarm 18:4 AYC heat pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 760,
   "name": "Alarm 18:5 AYC heat temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 761,
   "name": "Alarm 18:6 AYC heat temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 764,
   "name": "Alarm 18:9 AYC cool temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 765,
   "name": "Alarm 18:10 AYC cool valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 766,
   "name": "Alarm 18:11 AYC cool pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 767,
   "name": "Alarm 18:12 AYC cool temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 768,
   "name": "Alarm 18:13 AYC cool temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 801,
   "name": "Alarm 21:1 COOL DX I/O-module no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 802,
   "name": "Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 803,
   "name": "Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 804,
   "name": "Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 805,
   "name": "Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 806,
   "name": "Alarm 21:6 COOL DX compressor no. 1 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 807,
   "name": "Alarm 21:7 COOL DX compressor no. 1 restart error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 808,
   "name": "Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 809,
   "name": "Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 810,
   "name": "Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 811,
   "name": "Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 812,
   "name": "Alarm 21:12 COOL DX compressor no. 2 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 813,
   "name": "Alarm 21:13 COOL DX compressor no. 2 restart error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 814,
   "name": "Alarm 21:14 COOL DX outdoor air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 815,
   "name": "Alarm 21:15 COOL DX phase sequence error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 831,
   "name": "Alarm 23:1 SMART Link com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 832,
   "name": "Alarm 23:2 SMART Link alarm level 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 833,
   "name": "Alarm 23:3 SMART Link alarm level 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 834,
   "name": "Alarm 23:4 SMART Link alarm level 3 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 840,
   "name": "Alarm 23:10 AQUA Link I/O-module no. 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 841,
   "name": "Alarm 23:11 AQUA Link pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 846,
   "name": "Alarm 24:1 SMART Link no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 847,
   "name": "Alarm 24:2 SMART Link no. 1 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 849,
   "name": "Alarm 24:4 SMART Link no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 850,
   "name": "Alarm 24:5 SMART Link no. 2 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 852,
   "name": "Alarm 24:7 SMART Link no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 853,
   "name": "Alarm 24:8 SMART Link no. 3 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 855,
   "name": "Alarm 24:10 SMART Link no. 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 856,
   "name": "Alarm 24:11 SMART Link no. 4 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 876,
   "name": "Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 877,
   "name": "Alarm 26:2 Pre-filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 882,
   "name": "Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 883,
   "name": "Alarm 26:8 Pre-filter extract air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 891,
   "name": "Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 892,
   "name": "Alarm 27:2 AHU filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 897,
   "name": "Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 898,
   "name": "Alarm 27:8 AHU filter extract air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 906,
   "name": "Alarm 28:1 End filter supply air pressure sensor no. A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 907,
   "name": "Alarm 28:2 End filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 936,
   "name": "Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 937,
   "name": "Alarm 30:2 Air flow measurement supply air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 938,
   "name": "Alarm 30:3 Air flow measurement supply air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 941,
   "name": "Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 942,
   "name": "Alarm 30:7 Air flow measurement extract air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 943,
   "name": "Alarm 30:8 Air flow measurement extract air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 946,
   "name": "Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 951,
   "name": "Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 952,
   "name": "Alarm 31:2 Pressure regulation supply air pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 953,
   "name": "Alarm 31:3 Pressure regulation supply air pressure above set point alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 956,
   "name": "Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 957,
   "name": "Alarm 31:7 Pressure regulation extract air press. below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 958,
   "name": "Alarm 31:8 Pressure regulation extract air press. above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 966,
   "name": "Alarm 32:1 ReCO2 I/O-module no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 967,
   "name": "Alarm 32:2 ReCO2 pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 968,
   "name": "Alarm 32:3 ReCO2 recirculation damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 969,
   "name": "Alarm 32:4 ReCO2 outdoor air damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 981,
   "name": "Alarm 33:1 Service period above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 995,
   "name": "Alarm 33:15 Lock function tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 996,
   "name": "Alarm 34:1 External control I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 997,
   "name": "Alarm 34:2 External control I/O-module no. 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1011,
   "name": "Alarm 35:1 Booster diffusers I/O-module no. 8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1056,
   "name": "Alarm 38:1 MIRU 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1057,
   "name": "Alarm 38:2 MIRU 1 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1058,
   "name": "Alarm 38:3 MIRU 1 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1059,
   "name": "Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1060,
   "name": "Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1061,
   "name": "Alarm 38:6 MIRU 1 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1062,
   "name": "Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1071,
   "name": "Alarm 39:1 MIRU 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1072,
   "name": "Alarm 39:2 MIRU 2 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1073,
   "name": "Alarm 39:3 MIRU 2 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1074,
   "name": "Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1075,
   "name": "Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1076,
   "name": "Alarm 39:6 MIRU 2 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1077,
   "name": "Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1086,
   "name": "Alarm 40:1 MIRU 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1087,
   "name": "Alarm 40:2 MIRU 3 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1088,
   "name": "Alarm 40:3 MIRU 3 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1089,
   "name": "Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1090,
   "name": "Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1091,
   "name": "Alarm 40:6 MIRU 3 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1092,
   "name": "Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1101,
   "name": "Alarm 41:1 MIRU 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1102,
   "name": "Alarm 41:2 MIRU 4 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1103,
   "name": "Alarm 41:3 MIRU 4 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1104,
   "name": "Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1105,
   "name": "Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1106,
   "name": "Alarm 41:6 MIRU 4 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1107,
   "name": "Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1116,
   "name": "Alarm 42:1 MIRU 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1117,
   "name": "Alarm 42:2 MIRU 5 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1118,
   "name": "Alarm 42:3 MIRU 5 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1119,
   "name": "Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1120,
   "name": "Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1121,
   "name": "Alarm 42:6 MIRU 5 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1122,
   "name": "Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1131,
   "name": "Alarm 43:1 MIRU 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1132,
   "name": "Alarm 43:2 MIRU 6 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1133,
   "name": "Alarm 43:3 MIRU 6 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1134,
   "name": "Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1135,
   "name": "Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1136,
   "name": "Alarm 43:6 MIRU 6 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1137,
   "name": "Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1146,
   "name": "Alarm 44:1 MIRU 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1147,
   "name": "Alarm 44:2 MIRU 7 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1148,
   "name": "Alarm 44:3 MIRU 7 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1149,
   "name": "Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1150,
   "name": "Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1151,
   "name": "Alarm 44:6 MIRU 7 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1152,
   "name": "Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1161,
   "name": "Alarm 45:1 MIRU 8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1162,
   "name": "Alarm 45:2 MIRU 8 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1163,
   "name": "Alarm 45:3 MIRU 8 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1164,
   "name": "Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1165,
   "name": "Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1166,
   "name": "Alarm 45:6 MIRU 8 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1167,
   "name": "Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1176,
   "name": "Alarm 46:1 MIRU 9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1177,
   "name": "Alarm 46:2 MIRU 9 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1178,
   "name": "Alarm 46:3 MIRU 9 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1179,
   "name": "Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1180,
   "name": "Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1181,
   "name": "Alarm 46:6 MIRU 9 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1182,
   "name": "Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1191,
   "name": "Alarm 47:1 MIRU 10 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1192,
   "name": "Alarm 47:2 MIRU 10 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1193,
   "name": "Alarm 47:3 MIRU 10 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1194,
   "name": "Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1195,
   "name": "Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1196,
   "name": "Alarm 47:6 MIRU 10 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1197,
   "name": "Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1221,
   "name": "Alarm 49:1 Supply air fan no. 1A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1222,
   "name": "Alarm 49:2 Supply air fan no. 1A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1223,
   "name": "Alarm 49:3 Supply air fan no. 1A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1224,
   "name": "Alarm 49:4 Supply air fan no. 1A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1225,
   "name": "Alarm 49:5 Supply air fan no. 1A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1226,
   "name": "Alarm 49:6 Supply air fan no. 1A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1227,
   "name": "Alarm 49:7 Supply air fan no. 1A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1228,
   "name": "Alarm 49:8 Supply air fan no. 1A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1229,
   "name": "Alarm 49:9 Supply air fan no. 1A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1230,
   "name": "Alarm 49:10 Supply air fan no. 1A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1236,
   "name": "Alarm 50:1 Supply air fan no. 2A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1237,
   "name": "Alarm 50:2 Supply air fan no. 2A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1238,
   "name": "Alarm 50:3 Supply air fan no. 2A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1239,
   "name": "Alarm 50:4 Supply air fan no. 2A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1240,
   "name": "Alarm 50:5 Supply air fan no. 2A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1241,
   "name": "Alarm 50:6 Supply air fan no. 2A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1242,
   "name": "Alarm 50:7 Supply air fan no. 2A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1243,
   "name": "Alarm 50:8 Supply air fan no. 2A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1244,
   "name": "Alarm 50:9 Supply air fan no. 2A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1245,
   "name": "Alarm 50:10 Supply air fan no. 2A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1251,
   "name": "Alarm 51:1 Supply air fan no. 3A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1252,
   "name": "Alarm 51:2 Supply air fan no. 3A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1253,
   "name": "Alarm 51:3 Supply air fan no. 3A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1254,
   "name": "Alarm 51:4 Supply air fan no. 3A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1255,
   "name": "Alarm 51:5 Supply air fan no. 3A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1256,
   "name": "Alarm 51:6 Supply air fan no. 3A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1257,
   "name": "Alarm 51:7 Supply air fan no. 3A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1258,
   "name": "Alarm 51:8 Supply air fan no. 3A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1259,
   "name": "Alarm 51:9 Supply air fan no. 3A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1260,
   "name": "Alarm 51:10 Supply air fan no. 3A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1266,
   "name": "Alarm 52:1 Supply air fan no. 1B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1267,
   "name": "Alarm 52:2 Supply air fan no. 1B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1268,
   "name": "Alarm 52:3 Supply air fan no. 1B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1269,
   "name": "Alarm 52:4 Supply air fan no. 1B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1270,
   "name": "Alarm 52:5 Supply air fan no. 1B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1271,
   "name": "Alarm 52:6 Supply air fan no. 1B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1272,
   "name": "Alarm 52:7 Supply air fan no. 1B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1273,
   "name": "Alarm 52:8 Supply air fan no. 1B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1274,
   "name": "Alarm 52:9 Supply air fan no. 1B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1275,
   "name": "Alarm 52:10 Supply air fan no. 1B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1281,
   "name": "Alarm 53:1 Supply air fan no. 2B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1282,
   "name": "Alarm 53:2 Supply air fan no. 2B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1283,
   "name": "Alarm 53:3 Supply air fan no. 2B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1284,
   "name": "Alarm 53:4 Supply air fan no. 2B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1285,
   "name": "Alarm 53:5 Supply air fan no. 2B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1286,
   "name": "Alarm 53:6 Supply air fan no. 2B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1287,
   "name": "Alarm 53:7 Supply air fan no. 2B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1288,
   "name": "Alarm 53:8 Supply air fan no. 2B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1289,
   "name": "Alarm 53:9 Supply air fan no. 2B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1290,
   "name": "Alarm 53:10 Supply air fan no. 2B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1296,
   "name": "Alarm 54:1 Supply air fan no. 3B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1297,
   "name": "Alarm 54:2 Supply air fan no. 3B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1298,
   "name": "Alarm 54:3 Supply air fan no. 3B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1299,
   "name": "Alarm 54:4 Supply air fan no. 3B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1300,
   "name": "Alarm 54:5 Supply air fan no. 3B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1301,
   "name": "Alarm 54:6 Supply air fan no. 3B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1302,
   "name": "Alarm 54:7 Supply air fan no. 3B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1303,
   "name": "Alarm 54:8 Supply air fan no. 3B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1304,
   "name": "Alarm 54:9 Supply air fan no. 3B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1305,
   "name": "Alarm 54:10 Supply air fan no. 3B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1311,
   "name": "Alarm 55:1 Extract air fan no. 1A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1312,
   "name": "Alarm 55:2 Extract air fan no. 1A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1313,
   "name": "Alarm 55:3 Extract air fan no. 1A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1314,
   "name": "Alarm 55:4 Extract air fan no. 1A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1315,
   "name": "Alarm 55:5 Extract air fan no. 1A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1316,
   "name": "Alarm 55:6 Extract air fan no. 1A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1317,
   "name": "Alarm 55:7 Extract air fan no. 1A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1318,
   "name": "Alarm 55:8 Extract air fan no. 1A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1319,
   "name": "Alarm 55:9 Extract air fan no. 1A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1320,
   "name": "Alarm 55:10 Extract air fan no. 1A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1326,
   "name": "Alarm 56:1 Extract air fan no. 2A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1327,
   "name": "Alarm 56:2 Extract air fan no. 2A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1328,
   "name": "Alarm 56:3 Extract air fan no. 2A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1329,
   "name": "Alarm 56:4 Extract air fan no. 2A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1330,
   "name": "Alarm 56:5 Extract air fan no. 2A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1331,
   "name": "Alarm 56:6 Extract air fan no. 2A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1332,
   "name": "Alarm 56:7 Extract air fan no. 2A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1333,
   "name": "Alarm 56:8 Extract air fan no. 2A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1334,
   "name": "Alarm 56:9 Extract air fan no. 2A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1335,
   "name": "Alarm 56:10 Extract air fan no. 2A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1341,
   "name": "Alarm 57:1 Extract air fan no. 3A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1342,
   "name": "Alarm 57:2 Extract air fan no. 3A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1343,
   "name": "Alarm 57:3 Extract air fan no. 3A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1344,
   "name": "Alarm 57:4 Extract air fan no. 3A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1345,
   "name": "Alarm 57:5 Extract air fan no. 3A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1346,
   "name": "Alarm 57:6 Extract air fan no. 3A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1347,
   "name": "Alarm 57:7 Extract air fan no. 3A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1348,
   "name": "Alarm 57:8 Extract air fan no. 3A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1349,
   "name": "Alarm 57:9 Extract air fan no. 3A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1350,
   "name": "Alarm 57:10 Extract air fan no. 3A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1356,
   "name": "Alarm 58:1 Extract air fan no. 1B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1357,
   "name": "Alarm 58:2 Extract air fan no. 1B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1358,
   "name": "Alarm 58:3 Extract air fan no. 1B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1359,
   "name": "Alarm 58:4 Extract air fan no. 1B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1360,
   "name": "Alarm 58:5 Extract air fan no. 1B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1361,
   "name": "Alarm 58:6 Extract air fan no. 1B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1362,
   "name": "Alarm 58:7 Extract air fan no. 1B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1363,
   "name": "Alarm 58:8 Extract air fan no. 1B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1364,
   "name": "Alarm 58:9 Extract air fan no. 1B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1365,
   "name": "Alarm 58:10 Extract air fan no. 1B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1371,
   "name": "Alarm 59:1 Extract air fan no. 2B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1372,
   "name": "Alarm 59:2 Extract air fan no. 2B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1373,
   "name": "Alarm 59:3 Extract air fan no. 2B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1374,
   "name": "Alarm 59:4 Extract air fan no. 2B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1375,
   "name": "Alarm 59:5 Extract air fan no. 2B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1376,
   "name": "Alarm 59:6 Extract air fan no. 2B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1377,
   "name": "Alarm 59:7 Extract air fan no. 2B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1378,
   "name": "Alarm 59:8 Extract air fan no. 2B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1379,
   "name": "Alarm 59:9 Extract air fan no. 2B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1380,
   "name": "Alarm 59:10 Extract air fan no. 2B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1386,
   "name": "Alarm 60:1 Extract air fan no. 3B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1387,
   "name": "Alarm 60:2 Extract air fan no. 3B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1388,
   "name": "Alarm 60:3 Extract air fan no. 3B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1389,
   "name": "Alarm 60:4 Extract air fan no. 3B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1390,
   "name": "Alarm 60:5 Extract air fan no. 3B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1391,
   "name": "Alarm 60:6 Extract air fan no. 3B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1392,
   "name": "Alarm 60:7 Extract air fan no. 3B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1393,
   "name": "Alarm 60:8 Extract air fan no. 3B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1394,
   "name": "Alarm 60:9 Extract air fan no. 3B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1395,
   "name": "Alarm 60:10 Extract air fan no. 3B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1952,
   "name": "Info 97:12 Plate heat exchanger bypass optimization not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1953,
   "name": "Info 97:13 Plate heat exchanger bypass optimization not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1954,
   "name": "Info 97:14 Plate heat exchanger defrost calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1955,
   "name": "Info 97:15 Plate heat exchanger defrost calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1956,
   "name": "Info 98:1 Supply air pre-filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1957,
   "name": "Info 98:2 Supply air pre-filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1958,
   "name": "Info 98:3 Extract air pre-filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1959,
   "name": "Info 98:4 Extract air pre-filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1960,
   "name": "Info 98:5 Supply air air handling unit filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1961,
   "name": "Info 98:6 Supply air air handling unit filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1962,
   "name": "Info 98:7 Extract air air handling unit filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1963,
   "name": "Info 98:8 Extract air air handling unit filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1964,
   "name": "Info 98:9 Supply air end filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1965,
   "name": "Info 98:10 Supply air end filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1966,
   "name": "Info 98:11 Rotary heat exchanger defrost calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1967,
   "name": "Info 98:12 Rotary heat exchanger defrost calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1968,
   "name": "Info 98:13 ReCO2 calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1969,
   "name": "Info 98:14 ReCO2 calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1970,
   "name": "Info 98:15 ReCO2 incorrect setting",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1971,
   "name": "Info 99:1 E-mail error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1977,
   "name": "Info 99:7 SD card memory soon full. Oldest log data will soon be deleted",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1978,
   "name": "Info 99:8 SD card memory full. Oldest log data deleted",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1984,
   "name": "Info 99:14 Internal serial memory error CPU 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1985,
   "name": "Info 99:15 Clock circuit defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2001,
   "name": "Active alarm group 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2002,
   "name": "Active alarm group 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2003,
   "name": "Active alarm group 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2004,
   "name": "Active alarm group 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2005,
   "name": "Active alarm group 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2006,
   "name": "Active alarm group 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2007,
   "name": "Active alarm group 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2008,
   "name": "Active alarm group 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2009,
   "name": "Active alarm group 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2010,
   "name": "Active alarm group 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2011,
   "name": "Active alarm group 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2012,
   "name": "Active alarm group 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2013,
   "name": "Active alarm group 13",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2014,
   "name": "Active alarm group 14",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2015,
   "name": "Active alarm group 15",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2016,
   "name": "Active alarm group 16",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2017,
   "name": "Active alarm group 17",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2018,
   "name": "Active alarm group 18",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2019,
   "name": "Active alarm group 19",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2020,
   "name": "Active alarm group 20",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2021,
   "name": "Active alarm group 21",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2022,
   "name": "Active alarm group 22",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2023,
   "name": "Active alarm group 23",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2024,
   "name": "Active alarm group 24",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2025,
   "name": "Active alarm group 25",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2026,
   "name": "Active alarm group 26",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2027,
   "name": "Active alarm group 27",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2028,
   "name": "Active alarm group 28",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2029,
   "name": "Active alarm group 29",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2030,
   "name": "Active alarm group 30",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2031,
   "name": "Active alarm group 31",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2032,
   "name": "Active alarm group 32",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2033,
   "name": "Active alarm group 33",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2034,
   "name": "Active alarm group 34",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2035,
   "name": "Active alarm group 35",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2036,
   "name": "Active alarm group 36",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2037,
   "name": "Active alarm group 37",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2038,
   "name": "Active alarm group 38",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2039,
   "name": "Active alarm group 39",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2040,
   "name": "Active alarm group 40",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2041,
   "name": "Active alarm group 41",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2042,
   "name": "Active alarm group 42",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2043,
   "name": "Active alarm group 43",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2044,
   "name": "Active alarm group 44",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2045,
   "name": "Active alarm group 45",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2046,
   "name": "Active alarm group 46",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2047,
   "name": "Active alarm group 47",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2048,
   "name": "Active alarm group 48",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2049,
   "name": "Active alarm group 49",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2050,
   "name": "Active alarm group 50",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2051,
   "name": "Active alarm group 51",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2052,
   "name": "Active alarm group 52",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2053,
   "name": "Active alarm group 53",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2054,
   "name": "Active alarm group 54",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2055,
   "name": "Active alarm group 55",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2056,
   "name": "Active alarm group 56",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2057,
   "name": "Active alarm group 57",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2058,
   "name": "Active alarm group 58",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2059,
   "name": "Active alarm group 59",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2060,
   "name": "Active alarm group 60",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2061,
   "name": "Active alarm group 61",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2062,
   "name": "Active alarm group 62",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2063,
   "name": "Active alarm group 63",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2064,
   "name": "Active alarm group 64",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2065,
   "name": "Active alarm group 65",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2066,
   "name": "Active alarm group 66",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2067,
   "name": "Active alarm group 67",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2068,
   "name": "Active alarm group 68",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2069,
   "name": "Active alarm group 69",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2070,
   "name": "Active alarm group 70",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2071,
   "name": "Active alarm group 71",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2072,
   "name": "Active alarm group 72",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2073,
   "name": "Active alarm group 73",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2074,
   "name": "Active alarm group 74",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2075,
   "name": "Active alarm group 75",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2076,
   "name": "Active alarm group 76",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2077,
   "name": "Active alarm group 77",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2078,
   "name": "Active alarm group 78",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2079,
   "name": "Active alarm group 79",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2080,
   "name": "Active alarm group 80",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2081,
   "name": "Active alarm group 81",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2082,
   "name": "Active alarm group 82",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2083,
   "name": "Active alarm group 83",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2084,
   "name": "Active alarm group 84",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2085,
   "name": "Active alarm group 85",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2086,
   "name": "Active alarm group 86",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2087,
   "name": "Active alarm group 87",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2088,
   "name": "Active alarm group 88",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2089,
   "name": "Active alarm group 89",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2090,
   "name": "Active alarm group 90",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2091,
   "name": "Active alarm group 91",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2092,
   "name": "Active alarm group 92",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2093,
   "name": "Active alarm group 93",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2094,
   "name": "Active alarm group 94",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2095,
   "name": "Active alarm group 95",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2096,
   "name": "Active alarm group 96",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2097,
   "name": "Active alarm group 97",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2098,
   "name": "Active alarm group 98",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2099,
   "name": "Active alarm group 99",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Booster diffusers",
   "description": "Booster diffusers function.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Alarm reset",
   "description": "Resets all active alarms",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Internal fire alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "SA flow pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "EA flow pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "SA duct pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "EA duct pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "ReCO2 pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "RHX defrost pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Carry over control pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "SA filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "EA filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "SA pre-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "EA pre-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "SA end-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "SA flow pressure sensor activate zero calibration",
   "description": "If value is set to 1 for min 1s calibration will be",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "EA flow pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "SA duct pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "EA duct pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "ReCO2 pressure sensor activate calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "RHX Defrost pressure sensor activate calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "Carry over control pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "SA filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "EA filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "SA pre-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "EA pre-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "SA end-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "External room sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "External room sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "External room sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 165,
   "name": "External room sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 167,
   "name": "External room temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "External OA sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "External OA sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "External OA sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "External OA sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "External OA temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 182,
   "name": "RHX defrost function",
   "description": "Setting for activating the defrost function for the rotary heat",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 183,
   "name": "RHX defrost calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 187,
   "name": "RHX carry over control function",
   "description": "Setting for activating the carry over control function for the rotary heat",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 190,
   "name": "RHX min exhaust air temp function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "PHX periodic operation of bypass damper function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "PX bypass optimize",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "CHX periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "CHX periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 228,
   "name": "Re-heat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 229,
   "name": "Re-heat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 245,
   "name": "Extra regulation 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 246,
   "name": "Extra regulation 1 periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 274,
   "name": "Cool relay 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 275,
   "name": "Cool relay 2 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 276,
   "name": "Cool periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 284,
   "name": "Summer night cool function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 296,
   "name": "Intermittent night heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 302,
   "name": "Intermittent night heat recirculation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "Morning boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 320,
   "name": "Heating boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 325,
   "name": "Xzone heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 327,
   "name": "Xzone cool function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 374,
   "name": "Xzone external room sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 375,
   "name": "Xzone external room sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 376,
   "name": "Xzone external room sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 377,
   "name": "Xzone external room sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 379,
   "name": "Xzone external room temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 386,
   "name": "Xzone reheat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 387,
   "name": "Xzone reheat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 400,
   "name": "Xzone Cool relay 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 401,
   "name": "Xzone Cool relay 2 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "Xzone Cool periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 410,
   "name": "Pre-heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 414,
   "name": "Pre-heat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 415,
   "name": "Pre-heat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 425,
   "name": "ReCO2 Calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 457,
   "name": "Dehumidifying function",
   "description": "Moved to Multistate Value 457",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 459,
   "name": "Heat exchange active in dehumidifying sequence",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 465,
   "name": "VOC sensor function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 490,
   "name": "SMART Link WB Optimize function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 504,
   "name": "AQUA Link Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 530,
   "name": "AYC Heated water periodic operation of pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 531,
   "name": "AYC Heated water periodic operation of valve",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 536,
   "name": "AYC Heated water OA temp compensation",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 547,
   "name": "AYC Heated water room temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 548,
   "name": "AYC Heated water room temp compensation at night",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Enabled during night, 1=Disabled during night"
  },
  {
   "type": "BV",
   "instance": 553,
   "name": "AYC Heated water night temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 579,
   "name": "AYC Chilled water periodic operation of pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 580,
   "name": "AYC Chilled water periodic operation of valve",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 585,
   "name": "AYC Chilled water OA temp compensation",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 596,
   "name": "AYC Chilled water room temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 597,
   "name": "AYC Chilled water room temp compensation at night",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Enabled during night, 1=Disabled during night"
  },
  {
   "type": "BV",
   "instance": 602,
   "name": "AYC Chilled water night temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 618,
   "name": "AYC Chilled water dew point compensation air flow boost",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 637,
   "name": "Optimize function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Application id/AHU Type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Air flow direction",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Fan no.2 as SA, 2=Fan no.1 as SA"
  },
  {
   "type": "MI",
   "instance": 115,
   "name": "PHX type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=PHX-1 1D HS (one damper and humidity sensor), 2=PHX-2 3D (three dampers), 3=PHX-3 1D 1PS (one damper and pressure sensor)"
  },
  {
   "type": "MI",
   "instance": 140,
   "name": "Extra regulation sequence 1 coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 142,
   "name": "Extra regulation sequence 2 coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 152,
   "name": "Re-heat coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 163,
   "name": "Cool coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 198,
   "name": "Xzone heat, coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 209,
   "name": "Xzone cool, coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used"
  },
  {
   "type": "MI",
   "instance": 224,
   "name": "Pre-heat coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 320,
   "name": "SMART Link, DX cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MI",
   "instance": 592,
   "name": "Operation level",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation(1.11), 15=Morning boost stop(1.11), 16=Intermittent night heat stop(1.11), 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment(1.12)"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Boost Supply air",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Boost Extract air",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "SA Fan regulation mode",
   "description": "Setting of regulation type for the supply air fan.",
   "units": "",
   "access": "W",
   "states": "1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "EA Fan regulation mode",
   "description": "Setting of regulation type for the extract air fan.",
   "units": "",
   "access": "W",
   "states": "1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Internal fire alarm reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "External fire alarm no. 1 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "External fire alarm no. 2 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "External alarm no. 1 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "External alarm no. 2 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "External alarm no. 1 input function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Alarm at closed contact, 2=Alarm at open contact"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "External alarm no. 2 input function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Alarm at closed contact, 2=Alarm at open contact"
  },
  {
   "type": "MV",
   "instance": 53,
   "name": "Outdoor temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed"
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "Down regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=SA and EA"
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "Fans in operation at fire alarm 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 87,
   "name": "Fans in operation at fire alarm 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 90,
   "name": "Fans in operation at internal fire alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "Pre-filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "Pre-filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "AHU filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "AHU filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "SA end filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA"
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "SA end filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "Temperature regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE"
  },
  {
   "type": "MV",
   "instance": 166,
   "name": "External room sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 176,
   "name": "External OA sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 188,
   "name": "RHX sorption rotor function",
   "description": "Setting for activating the sorption rotor control function for the rotary heat",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Sorption max at cool, 3=Sorption always max"
  },
  {
   "type": "MV",
   "instance": 237,
   "name": "Extra regulation sequence 1 function",
   "description": "State text",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool"
  },
  {
   "type": "MV",
   "instance": 238,
   "name": "Extra regulation sequence 1 output function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=0-10V, 2=10-0V"
  },
  {
   "type": "MV",
   "instance": 251,
   "name": "Extra regulation 1 temperature protection function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 254,
   "name": "Season heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode"
  },
  {
   "type": "MV",
   "instance": 255,
   "name": "Season heat manual setting",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Re-heat, 2=Extra regulation sequence"
  },
  {
   "type": "MV",
   "instance": 261,
   "name": "Cool on/off regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=1 step, 3=2 steps, 4=3 steps"
  },
  {
   "type": "MV",
   "instance": 313,
   "name": "Cooling boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence"
  },
  {
   "type": "MV",
   "instance": 329,
   "name": "Xzone temperature regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE"
  },
  {
   "type": "MV",
   "instance": 378,
   "name": "Xzone external room sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 395,
   "name": "Xzone Cool on/off regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=1 step, 3=2 steps, 4=3 steps"
  },
  {
   "type": "MV",
   "instance": 423,
   "name": "ReCO2-CO2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=CO2, 3=CO2 and air flow boost"
  },
  {
   "type": "MV",
   "instance": 424,
   "name": "ReCO2 temperature regulation sequence function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool"
  },
  {
   "type": "MV",
   "instance": 441,
   "name": "Humidifying function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=On/Off, 3=0-10V"
  },
  {
   "type": "MV",
   "instance": 442,
   "name": "Humidifying sensor",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=SA, 2=EA"
  },
  {
   "type": "MV",
   "instance": 457,
   "name": "DeHumidifying function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=SA, 2=EA"
  },
  {
   "type": "MV",
   "instance": 469,
   "name": "COOL DX Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Economy, 3=Comfort, 4=Top"
  },
  {
   "type": "MV",
   "instance": 481,
   "name": "SMART Link Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible"
  },
  {
   "type": "MV",
   "instance": 505,
   "name": "AQUA Link Pump alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function)"
  },
  {
   "type": "MV",
   "instance": 521,
   "name": "AYC Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water"
  },
  {
   "type": "MV",
   "instance": 528,
   "name": "AYC Heated water signal monitor function for pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function"
  },
  {
   "type": "MV",
   "instance": 555,
   "name": "AYC Heated water night temp compensation time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 562,
   "name": "AYC Heated water night temp compensation time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 577,
   "name": "AYC Chilled water signal monitor function for pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function"
  },
  {
   "type": "MV",
   "instance": 604,
   "name": "AYC Chilled water night temp compensation time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 611,
   "name": "AYC Chilled water night temp compensation time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 660,
   "name": "MIRU Control 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 661,
   "name": "MIRU Control 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 662,
   "name": "MIRU Control 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 663,
   "name": "MIRU Control 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 664,
   "name": "MIRU Control 5 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 665,
   "name": "MIRU Control 6 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 666,
   "name": "MIRU Control 7 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 667,
   "name": "MIRU Control 8 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 668,
   "name": "MIRU Control 9 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 669,
   "name": "MIRU Control 10 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed"
  },
  {
   "type": "MV",
   "instance": 671,
   "name": "MIRU Control 1 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 679,
   "name": "MIRU Control 2 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 687,
   "name": "MIRU Control 3 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 695,
   "name": "MIRU Control 4 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 703,
   "name": "MIRU Control 5 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 711,
   "name": "MIRU Control 6 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 719,
   "name": "MIRU Control 7 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 727,
   "name": "MIRU Control 8 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 735,
   "name": "MIRU Control 9 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 743,
   "name": "MIRU Control 10 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 793,
   "name": "Communication operation level",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop"
  },
  {
   "type": "CAL",
   "instance": 0,
   "name": "Calendar #1",
   "description": "Date list, up to 10 dates",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 1,
   "name": "Calendar #2",
   "description": "Date list, up to 10 dates",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 0,
   "name": "NC 00 A-Alarm",
   "description": "Notification class for AHU A-alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 1,
   "name": "NC 01 B-Alarm",
   "description": "Notification class for AHU B-alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 3,
   "name": "NC 03 Alarms specified in BACnet",
   "description": "Notification class for alarms set in BACnet objects",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 10,
   "name": "NC 10 Info message",
   "description": "Notification class for AHU info messages",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 11,
   "name": "NC 11 Events specified in BACnet",
   "description": "Notification class for events set in BACnet objects",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 0,
   "name": "Schedule #1",
   "description": "Weekly schedule, 6 time-values per day, 2 exceptions",
   "units": "",
   "access": "W",
   "states": "1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/swegon/gold-e-bacnet-ip",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}