Air handling unit controller · BACnet points list

Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points list

Updated 28 October 2026

Short answer

Swegon's Compact and GOLD LP air handlers have a built-in BACnet IP interface (B-ASC profile) on the unit controller. The list has 600 objects of four types: analog inputs for airflows, pressures, temperatures and operating modes, analog values for setpoints, regulator tuning, clock and time/year channels, plus binary inputs and values for outputs, alarms and functions. Several numbered 'Reserve' objects are placeholders.

This page lists 600 BACnet objects for the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) — 401 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.

Manufacturer
Swegon
Model
Compact / GOLD LP BACnet IP (PV 2.01+)
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
600 (401 writable)
Transport
BACnet IP
Firmware
Program version 2.01 or later
Also known as
COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480
Source document
BACnet IP Compact/GOLD LP, program version 2.01 and newer versions · GB.BACnet480.100129 · rev. 2010-01-29
Download CSV 600 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Swegon Compact / GOLD LP BACnet IP (PV 2.01+)

Integration in brief

Write AV-174 Communication operation mode to run the unit from the BMS (0 hands control back to the unit's own time channels) and read AI-84 Operation mode 1 to see why it is running or stopped. Map supply and extract air temperature, the EA/room setpoint and the low/high speed airflow or pressure setpoints, plus BI-5/BI-6 A/B alarms and BV-0 alarm reset. These are the objects the source's overview page highlights.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 174Communication operation modeBMS stop / low / high / auto commandWrite
AV 40SA Temperature setpointSupply air temperature setpointWrite
AV 41EA/Room Temperature setpointExtract/room temperature setpointWrite
BV 0Alarm resetResets tripped alarmsWrite
AI 84Operation mode 1Current operating reason (stop, speed, channel)Read
AI 27SA TemperatureSupply air temperatureRead
AI 28EA/Room temperatureExtract/room temperatureRead
AI 29Outdoor temperaturOutdoor air temp measured by the unit, °CRead
BI 5A-alarm.A-class alarm activeRead
BI 6B-alarm.B-class alarm activeRead

Enable & remote start

AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.

Heartbeat & communication loss

Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.

Sensors & values from the BMS

Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.

Network setup

Watch out for

Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

600 of 600 shown
Type
Access
Show
Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet Points List
DescriptionStates
AI0SA AirflowPresent supply airflow.l/sRead
AI1SA Airflow regulatorPresent supply airflow regulator setpoint.l/sRead
AI2EA AirflowPresent extract airflow.l/sRead
AI3EA Airflow regulatorPresent extract airflow regulator setpoint.l/sRead
AI4SA Duct pressurePresent supply air duct pressure.PaRead
AI5SA Duct pressure regulatorPresent supply air duct pressure regulator setpoint.PaRead
AI6EA Duct pressurePresent extract air duct pressure.PaRead
AI7EA Duct pressure regulatorPresent extract air duct pressure regulator setpoint.PaRead
AI8ReserveRead
AI9SA VAV demand regulatorPresent supply air VAV demand regulator setpoint.%Read
AI10ReserveRead
AI11EA VAV demand regulatorPresent extract air VAV demand regulator setpoint.%Read
AI12SA Fan levelPresent running level for the supply air fan.%Read
AI13EA Fan levelPresent running level for the extract air fan.%Read
AI14SA Fan effectPresent power consumption level for the supply air fan.WRead
AI15EA Fan effectPresent power consumption level for the extract air fan.WRead
AI16SFPSFP supply air + extract air.Read
AI17ReserveRead
AI18ReserveRead
AI19SA VoltagePresent voltage level for the supply air fan.VRead
AI20EA VoltagePresent voltage level for the extract air fan.VRead
AI21SA CurrentPresent current level for the supply air fan.ARead
AI22EA CurrentPresent current level for the extract air fan.ARead
AI23SA Airflow pressurePresent airflow pressure in the supply air fan inlet.PaRead
AI24EA Airflow pressurePresent airflow pressure in the extract air fan inlet.PaRead
AI25SA Temp regulatorPresent supply air temperature regulator setpoint.°CRead
AI26EA Temp regulatorPresent extract air temperature regulator setpoint.°CRead
AImin27SA TemperaturePresent supply air temperature.°CRead
AImin28EA/Room temperaturePresent extract air/room temperature in the unit.°CRead
AImin29Outdoor temperaturPresent outdoor air temperature in the unit.°CRead
AI30EA/Room temperature (external)Present room temperature external from the unit.°CRead
AI31Outdoor temperatur (external)Present outdoor air temperature external from the unit.°CRead
AI32Anti frost temperaturePresent anti frost temperature for water reheating coils.°CRead
AI33ReserveRead
AI34ReserveRead
AI35Rotary heat exchanger levelPresent operation level from rotary heat exchanger.%Read
AI36Reheat levelPresent level of reheat.%Read
AI37SA Down regulation levelPresent level of supply airflow down regulation.%Read
AI38ReserveRead
AI39Cooling levelPresent level of cooling.%Read
AI40Heating boost levelPresent level of heating boost.%Read
AI41Cooling boost levelPresent level of cooling boost.%Read
AI42HX pressure levelPresent pressure drop for the rotary heat exchanger.PaRead
AI43HX pressure alarm limitPresent pressure drop alarm limit for the rotary heat exchanger.PaRead
AI44HX temperaturePresent temperature inside the control unit for the rotary heat exchanger.°CRead
AI45Effect reduction levelPresent level of max output signal for electrical reheaters, active during low%Read
AI46Anti frost temp setpoint/operationPresent anti frost temperature setpoint for water reheating coils during unit operation.°CRead
AI47Anti frost temp setpoint/stopPresent anti frost temperature setpoint for water reheating coils when the unit°CRead
AI48Anti frost temp alarm limitSetting of antifrost temperature alarm limit.°CRead
AI49Supply air filter pressure levelPresent supply air filter pressure drop.PaRead
AI50Supply air filter pressure alarm limit.Present supply air filter pressure alarm limit.PaRead
AI51Supply air filter pressure level, newSupply air filter pressure saved from calibration.PaRead
AI52Extract air filter pressure levelPresent extract air filter pressure drop.PaRead
AI53Extract air filter pressure alarm limit.Present extract air filter pressure alarm limit.PaRead
AI54Extract air filter pressure level, newExtract air filter pressure saved from calibration.PaRead
AI55ReserveRead
AI56Coil typePresent connected reheat coil type.Read
AI57Cool step timePresent time between cool step shift.sRead
AI58Cool relay 1 restart timePresent time between two starts of cool relay 1.sRead
AI59Cool relay 2 restart timePresent time between two starts of cool relay 2.sRead
AI60Programversion, HMIPresent programversion for the handterminal.Read
AI61Programversion, HMI-slavePresent programversion for the extra handterminal.Read
AI62Programversion, main controller.Present programversion for the main control unit.Read
AI63Programversion, SA FC-1.Present programversion for the supply air frequency converter no.1.Read
AI64Programversion, SA FC-2.Present programversion for the supply air frequency converter no.2.Read
AI65Programversion, EA FC-1.Present programversion for the extract air frequency converter no.1.Read
AI66Programversion, EA FC-2.Present programversion for the extract air frequency converter no.2.Read
AI67Programversion, HX control unitPresent programversion for the rotary heat exchange control unit.Read
AI68WeekdayPresent weekday for the unit's internal clock.Read
AI69Extended low speed op. HoursPresent time for extended low speed operation.Read
AI70Extended low speed op. MinutesPresent time for extended low speed operation.Read
AI71Extended high speed op. HoursPresent time for extended high speed operation.Read
AI72Extended high speed op. MinutesPresent time for extended high speed operation.Read
AI73SA Fan operation timePresent operation time for the supply air fan, measured in minutes andRead
AI74EA Fan operation timePresent operation time for the extract air fan, measured in minutes andRead
AI75Cool operation timePresent operation time for cooling, measured in minutes and present in daysRead
AI76Heat exchange operation timePresent operation time for heat exchange, measured in minutes and present inRead
AI77Reheat operation timePresent operation time for reheat, measured in minutes and present in daysRead
AI78Present tripped alarmPresent tripped alarm number with highest priority.Read
AI79Active not tripped alarm no.1Present active alarm in delay.Read
AI80Active not tripped alarm no.2Present active alarm in delay.Read
AI81Active not tripped alarm no.3Present active alarm in delay.Read
AI82SA Fan sizePresent supply air fan size.Read
AI83EA Fan sizePresent extract air fan size.Read
AImin84Operation mode 1Read0=Manual stop, 1=Ext. stop, 2=Com. stop 1, 3=Manual high speed, 4=Summer night cooling, 5=Int. night heat, 6=Manual low speed, 7=Ext. high speed, 8=Com. high speed, 9=Year channel stop, 10=Year channel high speed, 11=Year channel low speed, 12=Time channel high speed, 13=Ext. low speed, 14=Com. low speed, 15=Time channel low speed, 16=Time channel stop, 17=Low speed=stop, 18=Com. stop 2
AI85Operation mode 2Read0=, 1=Coold air recovery, 2=Cooling boost, 3=SA down regulation, 4=HX defrosting, 5=Anti frost func. active, 6=Effect reduction, 7=Startup, 8=Zero calibration, 9=Extended low speed, 10=Extended high speed, 11=Air adjustment, 12=Cooling off, 13=Purging R.HX, 14=Extended R.HX. op, 15=Filter calibration, 16=R.HX. calibration, 17=Morning boost, 18=Heating boost, 19=Alarm, 20=Cooling pressure reduction, 21=Startup extract air fan, 22=Reserve, 23=Airing, 24=Heating
AI86Operation mode, manualPresent manual operation set on the unit's handterminal.Read0=Stop, 1=Auto operation, 2=Manual low speed, 3=Manual high speed
AI87Copy of Input Status 1-16.Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016Read
AI88Copy of Input Status 17-32.Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032Read
AI89Copy of Input Status 33-48.Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048Read
AI90Heat exchanger regulatorPresent level of heat exchanger regulator.%Read
AI91Extract air-humidityPresent level of extract air-humidity.%Read
AI92Extract air-humidity temperaturePresent temperature inside extract air-humidity sensor.°CRead
AI93Extract air-dewpointCalculated extract air-dewpoint.°CRead
AI94AYC chilled water temperaturePresent AYC chilled water temperature.°CRead
AI95AYC chilled water temperature regulatorPresent AYC chilled water temperature regulator setpoint.°CRead
AI96AYC chilled water outputPresent level of AYC chilled water valve output.%Read
AI97Supply air-dewpoint regulatorPresent supply air-dewpoint regulator setpoint.°CRead
AI98Supply air-humidityPresent level of supply air-humidity%Read
AI99Supply air-humidity temperaturePresent temperature inside supply air-humidity sensor.°CRead
AI100Supply air-dewpointCalculated supply air-dewpoint.°CRead
AI101ReserveRead
AI102ReserveRead
AI103ReserveRead
AI104ReserveRead
AI105R.HX. EfficiencyCalculated level of rotary heat exchanger efficiency.%Read
AI106ReserveRead
AI107ReserveRead
AI108Supply air prefilter pressure levelPresent supply air prefilter pressure drop.PaRead
AI109Supply air prefilter pressure alarm limit.Present supply air prefilter pressure alarm limit.PaRead
AI110Supply air prefilter pressure level, newSupply air prefilter pressure saved from calibration.PaRead
AI111Extract air prefilter pressure levelPresent extract air prefilter pressure drop.PaRead
AI112Extract air prefilter pressure alarm limit.Present extract air prefilter pressure alarm limit.PaRead
AI113Extract air prefilter pressure level, newExtract air prefilter pressure saved from calibration.PaRead
AI114ReserveRead
AI115ReserveRead
AI116ReserveRead
AI117ReserveRead
AI118ReserveRead
AI119ReserveRead
AI120ReserveRead
AI121ReserveRead
AI122ReserveRead
AI123ReserveRead
AI124Pre-heating air temperaturePresent pre-heating air temperature.°CRead
AI125Pre-heating levelPresent level of pre-heating.%Read
AI126Pre-heating anti frost temperaturePresent anti frost temperature for water pre-heating coils.°CRead
AI127ReserveRead
AI128ReserveRead
AI129ReserveRead
AI130ReserveRead
AI131ReserveRead
AI132ReserveRead
AI133Preheat operation timePresent operation time for preheat, measured in minutes and present in daysRead
AI134ReserveRead
AI135ReserveRead
AI136Demand VOC LevelPresent level of demand VOC input.%Read
AI137Demand Vin LevelPresent level of demand 0-10VDC input.%Read
AI138SA Filter level calculatedPresent level of calculated supply air filter.%Read
AI139EA Filter level calculatedPresent level of calculated extract air filter.%Read
AI140AYC heat temperaturePresent AYC heat temperature.°CRead
AI141AYC heat temp regulatorPresent AYC heat temperature regulator setpoint.°CRead
AI142AYC heat valve outputPresent level of AYC heat valve output.%Read
AV0SA Low speed airflow setpointSupply airflow setpoint for the unit when running in low speed operation.l/sWrite
AV1SA High speed airflow setpointSupply airflow setpoint for the unit when running in high speed operation.l/sWrite
AV2SA Max speed airflow setpointSupply airflow max. limit for the unit when the low/high speed operationl/sWrite
AV3SA Min speed airflow setpointSupply airflow min. limit for the unit when the low/high speed operationl/sWrite
AV4EA Low speed airflow setpointExtract airflow setpoint for the unit when running in low speed operation.l/sWrite
AV5EA High speed airflow setpointExtract airflow setpoint for the unit when running in high speed operation.l/sWrite
AV6EA Max speed airflow setpointExtract airflow max. limit for the unit when the low/high speed operationl/sWrite
AV7EA Min speed airflow setpointExtract airflow min. limit for the unit when the low/high speed operationl/sWrite
AV8SA Low speed pressure setpointSupply air duct pressure setpoint for the unit when running in lowPaWrite
AV9SA High speed pressure setpointSupply air duct pressure for the unit when running in high speedPaWrite
AV10SA Max speed output signalMax. limit for the supply air fan speed when running in pressure%Write
AV11SA Max speed pressure setpointSupply air duct pressure max. limit for the unit when the low/highPaWrite
AV12EA Low speed pressure setpointExtract air duct pressure setpoint for the unit when running in lowPaWrite
AV13EA High speed pressure setpointExtract air duct pressure setpoint for the unit when running in highPaWrite
AV14EA Max speed output signalMax. limit for the extract air fan speed when running in pressure%Write
AV15EA Max speed pressure setpointExtract air duct pressure max. limit for the unit when the low/highPaWrite
AV16SA Low speed demand setpointSupply air setpoint for the 0-10V input signal on terminal 35..37 for%Write
AV17SA High speed demand setpointSupply air setpoint for the 0-10V input signal on terminal 35..37 for%Write
AV18EA Low speed demand setpointExtract air setpoint for the 0-10V input signal on terminal 35..37 for%Write
AV19EA High speed demand setpointExtract air setpoint for the 0-10V input signal on terminal 35..37 for%Write
AV20SA Airflow regulation zoneSupply airflow regulation zone setting in % of the present airflow setpointWrite
AV21SA Airflow C-factorSupply airflow regulator affection setting.Write
AV22EA Airflow regulation zoneExtract airflow regulation zone setting in % of the present airflow setpointWrite
AV23EA Airflow C-factorExtract airflow regulator affection setting.Write
AV24SA Pressure regulation zoneSupply air pressure regulation zone setting in % of the present ductWrite
AV25SA Pressure C-factorSupply air pressure regulator affection setting.Write
AV26EA Pressure regulation zoneExtract air pressure regulation zone setting in % of the present ductWrite
AV27EA Pressure C-factorExtract air pressure regulator affection setting.Write
AV28SA Demand P-band.Supply air demand regulator P-band setting.Write
AV29SA Demand C-factorSupply air demand regulator affection setting.Write
AV30EA Demand P-band.Extract air demand regulator P-band setting.Write
AV31EA Demand C-factorExtract air demand regulator affection setting.Write
AV32ERS 1 DiffSupply air temperature difference setting accordning to the diagram for ERS 1.°CWrite
AV33ERS 1 BreakpointBreakpoint setting accordning to the diagram for ERS 1.°CWrite
AV34ERS 2 Breakpoint X1Breakpoint X1 setting accordning to the diagram for ERS 2.°CWrite
AV35ERS 2 Breakpoint Y1Breakpoint Y1 setting accordning to the diagram for ERS 2.°CWrite
AV36ERS 2 Breakpoint X2Breakpoint X2 setting accordning to the diagram for ERS 2.°CWrite
AV37ERS 2 Breakpoint Y2Breakpoint Y2 setting accordning to the diagram for ERS 2.°CWrite
AV38ERS 2 Breakpoint X3Breakpoint X3 setting accordning to the diagram for ERS 2.°CWrite
AV39ERS 2 Breakpoint Y3Breakpoint Y3 setting accordning to the diagram for ERS 2.°CWrite
AVmin40SA Temperature setpointSupply air temperature setting, for supply air temp regulation mode.°CWrite
AVmin41EA/Room Temperature setpointExtract air/room temperature setting, for Extract air/room temp regulation mode.°CWrite
AV42SA Min temp setpointSupply air min.setpoint during EA/room regulation mode.°CWrite
AV43SA Max temp setpointSupply air max.setpoint during EA/room regulation mode.°CWrite
AV44SA Temperature P-bandSupply air temperature regulator P-band setting.Write
AV45EA/Room Temperature P-bandExtract air/room temperature regulator P-band setting.Write
AV46SA HX. Reg C-factorSupply air heat exchange regulator affection setting.Write
AV47EA/Room HX. Reg C-factorExtract air/room heat exchange regulator affection setting.Write
AV48SA Heat Reg C-factorSupply air reheat regulator affection setting.Write
AV49EA/Room Heat Reg C-factorExtract air/room reheat regulator affection setting.Write
AV50ReserveWrite
AV51ReserveWrite
AV52ReserveWrite
AV53ReserveWrite
AV54SA Down regulation Reg C-factorSupply air reheat regulator affection setting.Write
AV55ReserveWrite
AV56SA Cool reg C-factorSupply air cool regulator affection setting.Write
AV57EA/Room Cool reg C-factorExtract air/room cool regulator affection setting.Write
AV58SA Cooling boost C-factorSupply air cooling boost affection setting.Write
AV59EA/Room Cooling boost reg C-factorExtract air/room cooling boost regulator affection setting.Write
AV60HX Pressure alarm set.Heat exchange pressure alarm limit setting (alarm no.38).PaWrite
AV61ReserveWrite
AV62ReserveWrite
AV63Cooling off set.Cooling off airflow setting in % of max. airflow.%Write
AV64SA Down regulation neautral zoneNeutral zone setting before downregulation is permitted.°CWrite
AV65Cool Outdoor temp limit.1Outdoor temperature limit setting for cooling stage 1.°CWrite
AV66Cool Outdoor temp limit.2Outdoor temperature limit setting for cooling stage 2.°CWrite
AV67Cool Outdoor temp limit.3Outdoor temperature limit setting for cooling stage 3.°CWrite
AV68Temperature reg. Neutral zoneNeutral zone setting before shift between heating and cooling.°CWrite
AV69SA Cool min air flowSupply air min. air flow setting for cooling.l/sWrite
AV70EA Cool min air flowExtract air min. air flow setting for cooling.l/sWrite
AV71Heating boost start limitHeating boost start temperature limit.°CWrite
AV72Cooling boost start limitCooling boost (comfort) start temperature limit.°CWrite
AV73SA Filter alarm limitSupply air filter pressure alarm limit setting.PaWrite
AV74EA Filter alarm limitExtract air filter pressure alarm limit setting.PaWrite
AV75Int. Night heat room start tempIntermittent night heat function, extract air temperature setting for start.°CWrite
AV76Int. Night heat room stop tempIntermittent night heat function, extract air temperature setting for stop.°CWrite
AV77Int. Night heat SA temp setpointIntermittent night heat function, supply air temperature setpoint during night heat.°CWrite
AV78Int. Night heat SA airflow setpointIntermittent night heat function, supply airflow setpoint during night heat.l/sWrite
AV79Int. Night heat EA airflow setpointIntermittent night heat function, extract airflow setpoint during night heat.l/sWrite
AV80Summer night cool EA start tempSummer night cool function, extract air temperature setting for start.°CWrite
AV81Summer night cool EA stop tempSummer night cool function, extract air temperature setting for stop.°CWrite
AV82Summer night cool outdoor temp limitSummer night cool function, outdoor temperature limit.°CWrite
AV83Summer night cool SA temp setpointSummer night cool function, supply air temperature setpoint during summer night cool.°CWrite
AV84Outdoor temp comp. Winter X1.Endpoint of winter compensation.(-10.00)°CWrite
AV85Outdoor temp comp. Winter X2.Startpoint of winter compensation.°CWrite
AV86Outdoor temp comp. Winter Y1.Level of winter compensation at X1.°CWrite
AV87Outdoor temp comp. Summer X3.Startpoint of summer compensation.°CWrite
AV88Outdoor temp comp. Summer X4.Endpoint of summer compensation.°CWrite
AV89Outdoor temp comp. Summer Y2.Level of summer compensation at X4.°CWrite
AV90Outdoor airflow comp. Winter X1.Endpoint of winter compensation.(-10.00)°CWrite
AV91Outdoor airflow comp. Winter X2.Startpoint of winter compensation.°CWrite
AV92Outdoor airflow comp. Winter Y1.Level of airflow compensation at X1.%Write
AV93ReserveWrite
AV94EA/Room min temp alarm limitSetting for min extract air /room temp alarm no.40.°CWrite
AV95SA Deviation alarm limitSetting for supply air temperature below present setpoint, alarm no.41.°CWrite
AV96ReserveWrite
AV97SA Fan regulation modeSetting of regulation type for the supply air fan.Write0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan
AV98EA Fan regulation modeSetting of regulation type for the extract air fan.Write0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan
AV99ERS StepSetting of curve when temperature is above breakpoint.Write
AV100Temperature regulation mode.Setting of temperature regulation type.Write0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg
AV101Cooling off periodeTime setting for cooling off electrical heating coil.sWrite
AV102Cool step timeTime setting between cool step shift.sWrite
AV103Cool restart timeSetting of time between two starts of the cool relays.sWrite
AV104Cool regulation modeSetting of cool regulation typeWrite0=Controlled 0-10V, 1=Controlled 10-0V, 2=On/Off 1-step, 3=On/Off 2-steps, 4=On/Off 3-steps binary
AV105Heating boost regulation mode.Setting for heating boost function.Write0=Inactive, 1=Active
AV106Cooling boost regulation mode.Setting of cooling boost regulation type.Write0=Inactive, 1=Comfort, 2=Economy, 3=Sequence, 4=Comfort+economy, 5=Economy+sequence
AV107Filter calibration modeSetting for required filter calibration.Write0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter, 4=HX
AV108Air adjustment time, minutesSetting for amount of minutes to air adjustment function.Write
AV109Air adjustment time, hoursSetting for amount of hours to air adjustment function.Write
AV110Handterminal languageWrite0=Svenska, 1=Norsk, 2=Dansk, 3=Suomi, 4=English, 5=Français, 6=Deutsch, 7=Polski, 8=Český, 9=Italiano, 10=Español, 11=Português, 12=Pycckий, 13=Eesti, 14=Latviesu, 15=Lietiviu, 16=Nederlands, 17=Magyar, 18=Türkçe
AV111Summer night cool start, hourSetting for start time of summer night cooling function.Write
AV112Summer night cool start, minuteSetting for start time of summer night cooling function.Write
AV113Summer night cool stop, hourSetting for stop time of summer night cooling function.Write
AV114Summer night cool stop, minuteSetting for stop time of summer night cooling function.Write
AV115ReserveWrite
AV116ReserveWrite
AV117Morning boost time, hoursSetting of morning boost time before normal operation.Write
AV118Morning boost time, minutesSetting of morning boost time before normal operation.Write
AV119Startup timeSetting of time for startup when the unit regulator is running withsWrite
AV120Start delay SA fan.Setting of start delay time for the supply air fan.sWrite
AV121Start delay EA fan.Setting of start delay time for the extract air fan after supplysWrite
AV122Air flow unitSetting of air flow unit presented in the unit's handterminal and WEB.Write0=l/s, 1=m3/s, 2=m3/h
AV123ReserveWrite
AV124YearSetting for the unit's internal clock.Write
AV125MonthSetting for the unit's internal clock.Write
AV126DateSetting for the unit's internal clock.Write
AV127HourSetting for the unit's internal clock.Write
AV128MinuteSetting for the unit's internal clock.Write
AV129SecondSetting for the unit's internal clock.Write
AV130Time channel 1 statusLow speed High speedWrite0=Inactive 16=Inactive, 1=Monday 17=Monday, 2=Tuesday 18=Tuesday, 3=Wednesday 19=Wednesday, 4=Thursday 20=Thursday, 5=Friday 21=Friday, 6=Saturday 22=Saturday, 7=Sunday 23=Sunday, 8=Monday..Friday 24=Monday..Friday, 9=Monday..Sunday 25=Monday..Sunday, 10=Saturday..Sunday 26=Saturday..Sunday
AV131Time channel 1 start hourWrite
AV132Time channel 1 start minuteWrite
AV133Time channel 1 stop hourWrite
AV134Time channel 1 stop minuteWrite
AV135Time channel 2 statusWrite
AV136Time channel 2 start hourWrite
AV137Time channel 2 start minuteWrite
AV138Time channel 2 stop hourWrite
AV139Time channel 2 stop minuteWrite
AV140Time channel 3 statusWrite
AV141Time channel 3 start hourWrite
AV142Time channel 3 start minuteWrite
AV143Time channel 3 stop hourWrite
AV144Time channel 3 stop minuteWrite
AV145Time channel 4 statusWrite
AV146Time channel 4 start hourWrite
AV147Time channel 4 start minuteWrite
AV148Time channel 4 stop hourWrite
AV149Time channel 4 stop minuteWrite
AV150Time channel 5 statusWrite
AV151Time channel 5 start hourWrite
AV152Time channel 5 start minuteWrite
AV153Time channel 5 stop hourWrite
AV154Time channel 5 stop minuteWrite
AV155Time channel 6 statusWrite
AV156Time channel 6 start hourWrite
AV157Time channel 6 start minuteWrite
AV158Time channel 6 stop hourWrite
AV159Time channel 6 stop minuteWrite
AV160Time channel 7 statusWrite
AV161Time channel 7 start hourWrite
AV162Time channel 7 start minuteWrite
AV163Time channel 7 stop hourWrite
AV164Time channel 7 stop minuteWrite
AV165Time channel 8 statusWrite
AV166Time channel 8 start hourWrite
AV167Time channel 8 start minuteWrite
AV168Time channel 8 stop hourWrite
AV169Time channel 8 stop minuteWrite
AV170Extended low speed op. HoursSetting for extended low speed operation.Write
AV171Extended low speed op. MinutesSetting for extended low speed operation.Write
AV172Extended high speed op. HoursSetting for extended low speed operation.Write
AV173Extended high speed op. MinutesSetting for extended low speed operation.Write
AVmin174Communication operation modeSetting of unit operation mode from communication. Summer night cool, intermittent nightWrite0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2
AV175Service periode alarm.Setting for delay time in months before service alarm.Write
AV176External alarm 1 delaySetting of delay time for external alarm no 1sWrite
AV177External alarm 2 delaySetting of delay time for external alarm no 2sWrite
AV178Int. Night heat SA pressure setpointIntermittent night heat function, supply pressure setpoint during night heat.PaWrite
AV179Int. Night heat EA pressure setpointIntermittent night heat function, extract pressure setpoint during night heat.PaWrite
AV180Copy of Coil Status 1-16Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016Write
AV181Copy of Coil Statust 17-32Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032Write
AV182Copy of Coil Status 33-48Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048Write
AV183Heat relay periodic func.Setting of periodic operation.Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV184Cool relay 1 periodic func.Setting of periodic operation.Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV185Cool relay 2 periodic func.Setting of periodic operation.Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV186Slave control C-factorSlave regulator affection setting.Write
AV187SA dehumid P-bandSA dehumid regulator P-band setting.Write
AV188SA dehumid C-factorSA dehumid regulator affection setting.Write
AV189Dewpoint reg. P-bandDewpoint regulator P-band setting.Write
AV190Dewpoint reg. C-factorDewpoint regulator affection setting.Write
AV191AYC chilled water temperatureSetting of AYC chilled water temperature setpoint.°CWrite
AV192Dewpoint neutralzoneDewpoint neutralzone setting.°CWrite
AV193Comp. airflowSetting of comp. airflow.%Write
AV194Supply air-humiditySetting of supply air-humidity.%Write
AV195Water heating periodic op. timeSetting of periodic op. time (minute).minWrite
AV196Water heating intervalSetting of water heating interval time (hour).hWrite
AV197Cool periodic op. timeSetting of periodic op. time (minute).minWrite
AV198Cool intervalSetting of cool interval time (hour).hWrite
AV199ReserveWrite
AV200EA/Room temperature (external) func.Setting of EA/Room temperature (external) function.Write0=Inactive, 1=IQnomic, 2=Communication (4x0202)
AV201EA/Room temperature com.Setting of EA/Room temperature via communication.°CWrite
AV202Outdoor temperature (external) func.Setting of outdoor temperature (external) function.Write0=Inactive, 1=IQnomic, 2=Communication (4x0204)
AV203Outdoor temperature com.Setting of outdoor temperature via communication.°CWrite
AV204Timeout temperature com.Setting of timeout for temperature via communication (4x0202, 4x0204).minWrite
AV205Flow at fire function.Setting for activating the air fan operation at fire functionWrite0=Inactive, 1=SA, 2=EA, 3=SA+EA
AV206Air fan down regulation func.Setting for activating the air fan down regulation functionWrite0=Inactive, 1=SA, 2=SA+EA
AV207SA speed at fire.Setting of supply air speed at fire.%Write
AV208EA speed at fire.Setting of extract air speed at fire.%Write
AV209ReserveWrite
AV210ReserveWrite
AV211Supply air min P-band.Supply air min regulator P-band setting.Write
AV212Supply air min C-factor.Supply air min regulator affection setting.Write
AV213Supply air max P-band.Supply air max regulator P-band setting.Write
AV214Supply air max C-factor.Supply air max regulator affection setting.Write
AV215Year channel 1 function.Write0=Inactive, 1=Stop, 2=Low speed, 3=High speed
AV216Year channel 1 start year.Write
AV217Year channel 1 start month.Write
AV218Year channel 1 start date.Write
AV219Year channel 1 start hour.Write
AV220Year channel 1 start minute.Write
AV221Year channel 1 stop year.Write
AV222Year channel 1 stop month.Write
AV223Year channel 1 stop date.Write
AV224Year channel 1 stop hour.Write
AV225Year channel 1 stop minute.Write
AV226Year channel 2 function.Write
AV227Year channel 2 start year.Write
AV228Year channel 2 start month.Write
AV229Year channel 2 start date.Write
AV230Year channel 2 start hour.Write
AV231Year channel 2 start minute.Write
AV232Year channel 2 stop year.Write
AV233Year channel 2 stop month.Write
AV234Year channel 2 stop date.Write
AV235Year channel 2 stop hour.Write
AV236Year channel 2 stop minute.Write
AV237Year channel 3 function.Write
AV238Year channel 3 start year.Write
AV239Year channel 3 start month.Write
AV240Year channel 3 start date.Write
AV241Year channel 3 start hour.Write
AV242Year channel 3 start minute.Write
AV243Year channel 3 stop year.Write
AV244Year channel 3 stop month.Write
AV245Year channel 3 stop date.Write
AV246Year channel 3 stop hour.Write
AV247Year channel 3 stop minute.Write
AV248Year channel 4 function.Write
AV249Year channel 4 start year.Write
AV250Year channel 4 start month.Write
AV251Year channel 4 start date.Write
AV252Year channel 4 start hour.Write
AV253Year channel 4 start minute.Write
AV254Year channel 4 stop year.Write
AV255Year channel 4 stop month.Write
AV256Year channel 4 stop date.Write
AV257Year channel 4 stop hour.Write
AV258Year channel 4 stop minute.Write
AV259Year channel 5 function.Write
AV260Year channel 5 start year.Write
AV261Year channel 5 start month.Write
AV262Year channel 5 start date.Write
AV263Year channel 5 start hour.Write
AV264Year channel 5 start minute.Write
AV265Year channel 5 stop year.Write
AV266Year channel 5 stop month.Write
AV267Year channel 5 stop date.Write
AV268Year channel 5 stop hour.Write
AV269Year channel 5 stop minute.Write
AV270Year channel 6 function.Write
AV271Year channel 6 start year.Write
AV272Year channel 6 start month.Write
AV273Year channel 6 start date.Write
AV274Year channel 6 start hour.Write
AV275Year channel 6 start minute.Write
AV276Year channel 6 stop year.Write
AV277Year channel 6 stop month.Write
AV278Year channel 6 stop date.Write
AV279Year channel 6 stop hour.Write
AV280Year channel 6 stop minute.Write
AV281Year channel 7 function.Write
AV282Year channel 7 start year.Write
AV283Year channel 7 start month.Write
AV284Year channel 7 start date.Write
AV285Year channel 7 start hour.Write
AV286Year channel 7 start minute.Write
AV287Year channel 7 stop year.Write
AV288Year channel 7 stop month.Write
AV289Year channel 7 stop date.Write
AV290Year channel 7 stop hour.Write
AV291Year channel 7 stop minute.Write
AV292Year channel 8 function.Write
AV293Year channel 8 start year.Write
AV294Year channel 8 start month.Write
AV295Year channel 8 start date.Write
AV296Year channel 8 start hour.Write
AV297Year channel 8 start minute.Write
AV298Year channel 8 stop year.Write
AV299Year channel 8 stop month.Write
AV300Year channel 8 stop date.Write
AV301Year channel 8 stop hour.Write
AV302Year channel 8 stop minute.Write
AV303Filter select.Setting for filter select function.Write0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA
AV304Prefilter select.Setting for prefilter select function.Write0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA
AV305SA prefilter alarm limit.Supply air prefilter pressure alarm limit setting.PaWrite
AV306EA prefilter alarm limit.Extract air prefilter pressure alarm limit setting.PaWrite
AV307Prefilter calibration mode.Setting for requiered filtercalibration.Write0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter
AV308Preheating function.Setting of preheating function.Write0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP
AV309Preheating setpoint.Setting of preheating temperature setpoint.°CWrite
AV310Preheat P-band.Preheat regulator P-band setting.Write
AV311Preheat C-factor.Preheat regulator affection setting.Write
AV312SA Filter calculated alarm levelSupply air filter calculated alarm limit setting.%Write
AV313EA Filter calculated alarm levelExtract air filter calculated alarm limit setting.%Write
AV314Mode digital output relay 1Setting of mode output relay 1 function.Write0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2
AV315Mode digital output relay 2Setting of mode output relay 2 function.Write0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2
AV316Mode digital input 1Setting of mode input 1 function.Write0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire
AV317Mode digital input 2Setting of mode input 2 function.Write0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire
AV318Manual morning boost time hourSetting of manual morning boost time before normal operation.Write
AV319Manual morning boost time minutesSetting of manual morning boost time before normal operation.Write
AV320Airing temp setSetting of airing temperature setpoint.°CWrite
AV321Airing time setSetting of airing time in minutes.Write
AV322Manual operation drift modeSetting of manual operation drift mode.Write0=Normal operation, 1=Extended operation, 2=Airing, 3=Heating, 4=Heating+Recirc
AV323AYC function.Setting of AYC function.Write0=Inactive, 1=Cool, 2=Heat, 3=Cool+heat
AV324AYC heat temp set.Setting of AYC heated water temperature setpoint.°CWrite
AV325AYC night comp. channel.Setting of AYC night compensation channel.Write1=Channel 1, 2=Channel 2
AV326AYC channel start hour.Setting of AYC channel start time (hour).hWrite
AV327AYC channel start minute.Setting of AYC channel start time (minute).minWrite
AV328AYC channel stop hour.Setting of AYC channel stop time (hour).hWrite
AV329AYC channel stop minute.Setting of AYC channel stop time (minute).minWrite
AV330AYC channel period.Setting of AYC channel period.Write0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday
AV331AYC heat P-band.AYC heat regulator P-band setting.Write
AV332AYC heat C-factor.AYC heat regulator affection setting.Write
AV333AYC cool P-band.AYC cool regulator P-band setting.Write
AV334AYC cool C-factor.AYC cool regulator affection setting.Write
AV335AYC heat out comp. X1.AYC outdoor compensation of heated water, outdoor temp X1 setting.°CWrite
AV336AYC heat out comp. Y1.AYC outdoor compensation of heated water, heated water temp Y1 setting.°CWrite
AV337AYC heat out comp. X2.AYC outdoor compensation of heated water, outdoor temp X2 setting.°CWrite
AV338AYC heat out comp. Y2.AYC outdoor compensation of heated water, heated water temp Y2 setting.°CWrite
AV339AYC heat out comp. X3.AYC outdoor compensation of heated water, outdoor temp X3 setting.°CWrite
AV340AYC heat out comp. Y3.AYC outdoor compensation of heated water, heated water temp Y3 setting.°CWrite
AV341AYC heat room comp. temp limit.AYC room compensation of heated water, heated water temp limit setting.°CWrite
AV342AYC heat room comp P-band.AYC room compensation of heated water, heated water P-band setting.°CWrite
AV343AYC heat night comp temp.AYC night compensation of heated water, heated water night setting.°CWrite
AV344AYC heat pump on temp.AYC pump operation of heated water, outdoor temp start setting.°CWrite
AV345AYC heat pump off temp.AYC pump operation of heated water, outdoor temp stop setting.°CWrite
AV346AYC heat pump alarm.Setting for selecting the AYC heated water pump alarm function.Write0=Inactive, 1=Open, 2=Closed, 3=Contactor
AV347AYC heat per op function.Setting for selecting the AYC heated water periodic operation function.Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve
AV348AYC heat per op time.AYC periodic operation of heated water, time (minute) setting.minWrite
AV349AYC heat per op interval.AYC periodic operation of heated water, interval time (hour) setting.hWrite
AV350AYC cool out comp. X1.AYC outdoor compensation of chilled water, outdoor temp X1 setting.°CWrite
AV351AYC cool out comp. Y1.AYC outdoor compensation of chilled water, chilled water temp Y1 setting.°CWrite
AV352AYC cool out comp. X2.AYC outdoor compensation of chilled water, outdoor temp X2 setting.°CWrite
AV353AYC cool out comp. Y2.AYC outdoor compensation of chilled water, chilled water temp Y2 setting.°CWrite
AV354AYC cool out comp. X3.AYC outdoor compensation of chilled water, outdoor temp X3 setting.°CWrite
AV355AYC cool out comp. Y3.AYC outdoor compensation of chilled water, chilled water temp Y3 setting.°CWrite
AV356AYC cool room comp. temp limit.AYC room compensation of chilled water, chilled water temp limit setting.°CWrite
AV357AYC cool room comp. P-band.AYC room compensation of chilled water, chilled water P-band setting.°CWrite
AV358AYC cool night comp temp.AYC night compensation of chilled water, chilled water night setting.°CWrite
AV359AYC cool pump on temp.AYC pump operation of chilled water, outdoor temp start setting.°CWrite
AV360AYC cool pump off temp.AYC pump operation of chilled water, outdoor temp stop setting.°CWrite
AV361AYC cool pump alarm.Setting for selecting the AYC chilled water pump alarm function.Write0=Inactive, 1=Open, 2=Closed, 3=Contactor
AV362AYC cool per op function.Setting for selecting the AYC chilled water periodic operation function.Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve
AV363AYC cool per op time.AYC periodic operation of chilled water, time (minute) setting.minWrite
AV364AYC cool per op interval.AYC periodic operation of chilled water, interval time (hour) setting.hWrite
AV365IO-mod 3 output 1 function.Setting of I/O-module no. 3 relay 1 output.Write0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost
AV366IO-mod 3 output 2 function.Setting of I/O-module no. 3 relay 2 output.Write0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost
BI0Heat outputStatus for relay output.Read
BI1Cool output 1Status for relay output.Read
BI2Cool output 2Status for relay output.Read
BI3Low speed outputStatus for relay output.Read
BI4High speed outputStatus for relay output.Read
BImin5A-alarm.Status for relay output.Read
BImin6B-alarm.Status for relay output.Read
BI7Operation outputStatus for relay output.Read
BI8Damper outputStatus for relay output.Read
BI9External low speed inputStatus for digital input.Read
BI10External high speed inputStatus for digital input.Read
BI11External alarm 1 inputStatus for digital input.Read
BI12External alarm 2 inputStatus for digital input.Read
BI13External fire alarm input.Status for digital input.Read
BI14External stop inputStatus for digital input.Read
BI15DIP Switch 1Status for dip switch setting.Read
BI16DIP Switch 2Status for dip switch setting.Read
BI17DIP Switch 3Status for dip switch setting.Read
BI18DIP Switch 4Status for dip switch setting.Read
BI19DIP Switch 5Status for dip switch setting.Read
BI20DIP Switch 6Status for dip switch setting.Read
BI21AYC heat pump outputStatus for AYC heat pump output.Read
BI22AYC cool pump outputStatus for AYC cool pump output.Read
BI23Reserve 9Read
BI24R.HX rotation monitorStatus from the rotation detector.Read
BI25Reserve 10Read
BI26Reserve 11Read
BI27Reserve 12Read
BI28Pre-heat outputStatus for relay output.Read
BI29Recirculation outputStatus for I/O-module no. 3 relay 1 output.Read
BI30Booster outputStatus for I/O-module no. 3 relay 2 output.Read
BI31IO-mod 3 output 1Status for I/O-module no. 3 relay 1 output.Read
BI32IO-mod 3 output 2Status for I/O-module no. 3 relay 2 output.Read
BI33Reserve 13Read
BI34Reserve 14Read
BI35Reserve 15Read
BI36Reserve 16Read
BI37Reserve 17Read
BI38Reserve 18Read
BI39Reserve 19Read
BI40Reserve 20Read
BI41Reserve 21Read
BI42Reserve 22Read
BI43Reserve 23Read
BI44Reserve 24Read
BI45Reserve 25Read
BI46Reserve 26Read
BI47Reserve 27Read
BI48Alarm number 1Status if alarm number 1 is active.Read
BI49Alarm number 2Status if alarm number 2 is active.Read
BI50Alarm number 3Status if alarm number 3 is active.Read
BI247Alarm number 200Status if alarm number 200 is active.Read
BI248Info number 1Status if info number 1 is active.Read
BI249Info number 2Status if info number 2 is active.Read
BI250Info number 3Status if info number 3 is active.Read
BI347Info number 100Status if info number 100 is active.Read
BVmin0Alarm resetResets tripped alarms.Write
BV1R.HX. Defrost func.Setting for activating the defrost function for the rotary heat exchanger.Write
BV2Cool operation modeSetting for cooling between off and auto operation.Write
BV3Int. Night heat func.Setting for activating the intermittent night heat function.Write
BV4Damper func.Setting for activating the damper output relay during int. night heat.Write
BV5Summer night coolingSetting for activating the suumer night cool function.Write
BV6Outdoor temp compensationSetting for activating the outdoor temperature compensation function.Write
BV7Outdoor airflow compensationSetting for activating the outdoor airflow compensation function.Write
BV8Auto. Summer/winter switchSetting for activating the automatic switch between summer/winter time function.Write
BV9Switch clock func.Setting for switch clock function type.Write0=Stop - low speed - high speed, 1=Low speed - high speed
BV10Internal fire alarm func.Setting for activating the internal fire alarm function.Write
BV11External alarm 1 active at closureSetting for external alarm number 1 condition to be activated.Write0=Alarm at closed input, 1=Alarm at open input
BV12External alarm 2 active at closureSetting for external alarm number 2 condition to be activated.Write0=Alarm at closed input, 1=Alarm at open input
BV13Dewpoint reg. func.Setting for activating the dewpoint regulator funktion.Write
BV14Dehumid reg. func.Setting for activating the dehumid regulator funktion.Write
BV15External fire alarm func.Setting for external fire resetting function.Write0=Manual, 1=Automatic
BV16External alarm 1 func.Setting for external alarm 1 resetting function.Write0=Manual, 1=Automatic
BV17External alarm 2 func.Setting for external alarm 2 resetting function.Write0=Manual, 1=Automatic
BV18Int. Night heat output func.Setting for selecting the intermittent night heat output function.Write0=IQnomic, 1=IQnomic+
BV19Morningboost damper func.Setting for activating the morningboost damper function.Write0=Inactive, 1=Active
BV20Morningboost extract func.Setting for activating the morningboost extract air fan function.Write0=Inactive, 1=Active
BV21Filter func.Setting for filter between calculated and pressure sensors.Write0=Calculated, 1=Pressure sensors
BV22Iqnomic Plus module no.6 CoolingSetting for activating Iqnomiq Plus no.6 Cooling module.Write0=Inactive, 1=Active
BV23Airing auto func.Setting for activating the airing auto function.Write0=Inactive, 1=Active
BV24AYC heat out comp. func.Setting for selecting the AYC outdoor comp. heated water function.Write0=Inactive, 1=Active
BV25AYC heat room comp. func.Setting for selecting the AYC room comp. heated water function.Write0=Inactive, 1=Active
BV26AYC heat room comp. night block func.Setting for selecting the AYC room comp. heated water night block function.Write0=Inactive, 1=Active
BV27AYC heat night comp. func.Setting for selecting the AYC night comp. heated water function.Write0=Inactive, 1=Active
BV28AYC heat valve signal func.Setting for selecting the AYC valve signal heated water alarm function.Write0=Inactive, 1=Active
BV29AYC cool out comp. func.Setting for selecting the AYC outdoor comp. chilled water function.Write0=Inactive, 1=Active
BV30AYC cool room comp. func.Setting for selecting the AYC room comp. chilled water function.Write0=Inactive, 1=Active
BV31AYC cool room comp. night block func.Setting for selecting the AYC room comp. chilled water night block function.Write0=Inactive, 1=Active
BV32AYC cool night comp. func.Setting for selecting the AYC night comp. chilled water function.Write0=Inactive, 1=Active
BV33AYC cool valve signal func.Setting for selecting the AYC valve signal chilled water alarm function.Write0=Inactive, 1=Active

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Compact / GOLD LP BACnet IP (PV 2.01+) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)

How many BACnet points does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) have?

This list has 600 BACnet objects: 143 analog inputs, 367 analog values, 56 binary inputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points are writable?

401 of the 600 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet documentation?

The source is BACnet IP Compact/GOLD LP, program version 2.01 and newer versions (GB.BACnet480.100129), revision 2010-01-29, published free by Swegon at https://www.swegon.com/globalassets/digizuite/11562-en-compactair_bacnet480_other_en.pdf.

What are the minimum BACnet points to integrate the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?

Start with AV 174 Communication operation mode (BMS stop / low / high / auto command); AV 40 SA Temperature setpoint (Supply air temperature setpoint); AV 41 EA/Room Temperature setpoint (Extract/room temperature setpoint); BV 0 Alarm reset (Resets tripped alarms); AI 84 Operation mode 1 (Current operating reason (stop, speed, channel)); AI 27 SA Temperature (Supply air temperature); AI 28 EA/Room temperature (Extract/room temperature); AI 29 Outdoor temperatur (Outdoor air temp measured by the unit, °C); BI 5 A-alarm. (A-class alarm active); BI 6 B-alarm. (B-class alarm active).

How do I enable BMS control of the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?

AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.

Does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) need a BACnet heartbeat or have a communication timeout?

Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.

Can the BMS supply sensor values to the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?

Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.

How do I check these points on the real Compact / GOLD LP BACnet IP (PV 2.01+)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Swegon BACnet points lists

Source: BACnet IP Compact/GOLD LP, program version 2.01 and newer versions · GB.BACnet480.100129 · rev. 2010-01-29. Object names, instances and units are reproduced as published; descriptions are our own.