Air handling unit controller · BACnet points list
Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points list
Updated 28 October 2026
Swegon's Compact and GOLD LP air handlers have a built-in BACnet IP interface (B-ASC profile) on the unit controller. The list has 600 objects of four types: analog inputs for airflows, pressures, temperatures and operating modes, analog values for setpoints, regulator tuning, clock and time/year channels, plus binary inputs and values for outputs, alarms and functions. Several numbered 'Reserve' objects are placeholders.
This page lists 600 BACnet objects for the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) — 401 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- Compact / GOLD LP BACnet IP (PV 2.01+)
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 600 (401 writable)
- Transport
- BACnet IP
- Firmware
- Program version 2.01 or later
- Also known as
- COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480
BMS integration notes: Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
Write AV-174 Communication operation mode to run the unit from the BMS (0 hands control back to the unit's own time channels) and read AI-84 Operation mode 1 to see why it is running or stopped. Map supply and extract air temperature, the EA/room setpoint and the low/high speed airflow or pressure setpoints, plus BI-5/BI-6 A/B alarms and BV-0 alarm reset. These are the objects the source's overview page highlights.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 174 | Communication operation mode | BMS stop / low / high / auto command | Write |
| AV 40 | SA Temperature setpoint | Supply air temperature setpoint | Write |
| AV 41 | EA/Room Temperature setpoint | Extract/room temperature setpoint | Write |
| BV 0 | Alarm reset | Resets tripped alarms | Write |
| AI 84 | Operation mode 1 | Current operating reason (stop, speed, channel) | Read |
| AI 27 | SA Temperature | Supply air temperature | Read |
| AI 28 | EA/Room temperature | Extract/room temperature | Read |
| AI 29 | Outdoor temperatur | Outdoor air temp measured by the unit, °C | Read |
| BI 5 | A-alarm. | A-class alarm active | Read |
| BI 6 | B-alarm. | B-class alarm active | Read |
Enable & remote start
AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.
Heartbeat & communication loss
Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.
Sensors & values from the BMS
Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.
Network setup
- BACnet IP only; the device is a B-ASC supporting read/write property, COV and dynamic device/object binding.
- Swegon refers to a separate BACnet PICS and EDE file; device instance and IP settings are not in this document.
Watch out for
- Setpoints exist separately for low and high speed (e.g. AV-0/1 SA airflow, AV-8/9 SA duct pressure).
- Fan regulation mode (AV-97 SA, EA equivalent) decides whether airflow, pressure or demand setpoints are used.
- Clock, time-channel and year-channel AVs (around 120-290) are configuration settings.
- Reserve objects return no meaningful data.
Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | SA Airflow | Present supply airflow. | l/s | Read | |
| AI | 1 | SA Airflow regulator | Present supply airflow regulator setpoint. | l/s | Read | |
| AI | 2 | EA Airflow | Present extract airflow. | l/s | Read | |
| AI | 3 | EA Airflow regulator | Present extract airflow regulator setpoint. | l/s | Read | |
| AI | 4 | SA Duct pressure | Present supply air duct pressure. | Pa | Read | |
| AI | 5 | SA Duct pressure regulator | Present supply air duct pressure regulator setpoint. | Pa | Read | |
| AI | 6 | EA Duct pressure | Present extract air duct pressure. | Pa | Read | |
| AI | 7 | EA Duct pressure regulator | Present extract air duct pressure regulator setpoint. | Pa | Read | |
| AI | 8 | Reserve | Read | |||
| AI | 9 | SA VAV demand regulator | Present supply air VAV demand regulator setpoint. | % | Read | |
| AI | 10 | Reserve | Read | |||
| AI | 11 | EA VAV demand regulator | Present extract air VAV demand regulator setpoint. | % | Read | |
| AI | 12 | SA Fan level | Present running level for the supply air fan. | % | Read | |
| AI | 13 | EA Fan level | Present running level for the extract air fan. | % | Read | |
| AI | 14 | SA Fan effect | Present power consumption level for the supply air fan. | W | Read | |
| AI | 15 | EA Fan effect | Present power consumption level for the extract air fan. | W | Read | |
| AI | 16 | SFP | SFP supply air + extract air. | Read | ||
| AI | 17 | Reserve | Read | |||
| AI | 18 | Reserve | Read | |||
| AI | 19 | SA Voltage | Present voltage level for the supply air fan. | V | Read | |
| AI | 20 | EA Voltage | Present voltage level for the extract air fan. | V | Read | |
| AI | 21 | SA Current | Present current level for the supply air fan. | A | Read | |
| AI | 22 | EA Current | Present current level for the extract air fan. | A | Read | |
| AI | 23 | SA Airflow pressure | Present airflow pressure in the supply air fan inlet. | Pa | Read | |
| AI | 24 | EA Airflow pressure | Present airflow pressure in the extract air fan inlet. | Pa | Read | |
| AI | 25 | SA Temp regulator | Present supply air temperature regulator setpoint. | °C | Read | |
| AI | 26 | EA Temp regulator | Present extract air temperature regulator setpoint. | °C | Read | |
| AImin | 27 | SA Temperature | Present supply air temperature. | °C | Read | |
| AImin | 28 | EA/Room temperature | Present extract air/room temperature in the unit. | °C | Read | |
| AImin | 29 | Outdoor temperatur | Present outdoor air temperature in the unit. | °C | Read | |
| AI | 30 | EA/Room temperature (external) | Present room temperature external from the unit. | °C | Read | |
| AI | 31 | Outdoor temperatur (external) | Present outdoor air temperature external from the unit. | °C | Read | |
| AI | 32 | Anti frost temperature | Present anti frost temperature for water reheating coils. | °C | Read | |
| AI | 33 | Reserve | Read | |||
| AI | 34 | Reserve | Read | |||
| AI | 35 | Rotary heat exchanger level | Present operation level from rotary heat exchanger. | % | Read | |
| AI | 36 | Reheat level | Present level of reheat. | % | Read | |
| AI | 37 | SA Down regulation level | Present level of supply airflow down regulation. | % | Read | |
| AI | 38 | Reserve | Read | |||
| AI | 39 | Cooling level | Present level of cooling. | % | Read | |
| AI | 40 | Heating boost level | Present level of heating boost. | % | Read | |
| AI | 41 | Cooling boost level | Present level of cooling boost. | % | Read | |
| AI | 42 | HX pressure level | Present pressure drop for the rotary heat exchanger. | Pa | Read | |
| AI | 43 | HX pressure alarm limit | Present pressure drop alarm limit for the rotary heat exchanger. | Pa | Read | |
| AI | 44 | HX temperature | Present temperature inside the control unit for the rotary heat exchanger. | °C | Read | |
| AI | 45 | Effect reduction level | Present level of max output signal for electrical reheaters, active during low | % | Read | |
| AI | 46 | Anti frost temp setpoint/operation | Present anti frost temperature setpoint for water reheating coils during unit operation. | °C | Read | |
| AI | 47 | Anti frost temp setpoint/stop | Present anti frost temperature setpoint for water reheating coils when the unit | °C | Read | |
| AI | 48 | Anti frost temp alarm limit | Setting of antifrost temperature alarm limit. | °C | Read | |
| AI | 49 | Supply air filter pressure level | Present supply air filter pressure drop. | Pa | Read | |
| AI | 50 | Supply air filter pressure alarm limit. | Present supply air filter pressure alarm limit. | Pa | Read | |
| AI | 51 | Supply air filter pressure level, new | Supply air filter pressure saved from calibration. | Pa | Read | |
| AI | 52 | Extract air filter pressure level | Present extract air filter pressure drop. | Pa | Read | |
| AI | 53 | Extract air filter pressure alarm limit. | Present extract air filter pressure alarm limit. | Pa | Read | |
| AI | 54 | Extract air filter pressure level, new | Extract air filter pressure saved from calibration. | Pa | Read | |
| AI | 55 | Reserve | Read | |||
| AI | 56 | Coil type | Present connected reheat coil type. | Read | ||
| AI | 57 | Cool step time | Present time between cool step shift. | s | Read | |
| AI | 58 | Cool relay 1 restart time | Present time between two starts of cool relay 1. | s | Read | |
| AI | 59 | Cool relay 2 restart time | Present time between two starts of cool relay 2. | s | Read | |
| AI | 60 | Programversion, HMI | Present programversion for the handterminal. | Read | ||
| AI | 61 | Programversion, HMI-slave | Present programversion for the extra handterminal. | Read | ||
| AI | 62 | Programversion, main controller. | Present programversion for the main control unit. | Read | ||
| AI | 63 | Programversion, SA FC-1. | Present programversion for the supply air frequency converter no.1. | Read | ||
| AI | 64 | Programversion, SA FC-2. | Present programversion for the supply air frequency converter no.2. | Read | ||
| AI | 65 | Programversion, EA FC-1. | Present programversion for the extract air frequency converter no.1. | Read | ||
| AI | 66 | Programversion, EA FC-2. | Present programversion for the extract air frequency converter no.2. | Read | ||
| AI | 67 | Programversion, HX control unit | Present programversion for the rotary heat exchange control unit. | Read | ||
| AI | 68 | Weekday | Present weekday for the unit's internal clock. | Read | ||
| AI | 69 | Extended low speed op. Hours | Present time for extended low speed operation. | Read | ||
| AI | 70 | Extended low speed op. Minutes | Present time for extended low speed operation. | Read | ||
| AI | 71 | Extended high speed op. Hours | Present time for extended high speed operation. | Read | ||
| AI | 72 | Extended high speed op. Minutes | Present time for extended high speed operation. | Read | ||
| AI | 73 | SA Fan operation time | Present operation time for the supply air fan, measured in minutes and | Read | ||
| AI | 74 | EA Fan operation time | Present operation time for the extract air fan, measured in minutes and | Read | ||
| AI | 75 | Cool operation time | Present operation time for cooling, measured in minutes and present in days | Read | ||
| AI | 76 | Heat exchange operation time | Present operation time for heat exchange, measured in minutes and present in | Read | ||
| AI | 77 | Reheat operation time | Present operation time for reheat, measured in minutes and present in days | Read | ||
| AI | 78 | Present tripped alarm | Present tripped alarm number with highest priority. | Read | ||
| AI | 79 | Active not tripped alarm no.1 | Present active alarm in delay. | Read | ||
| AI | 80 | Active not tripped alarm no.2 | Present active alarm in delay. | Read | ||
| AI | 81 | Active not tripped alarm no.3 | Present active alarm in delay. | Read | ||
| AI | 82 | SA Fan size | Present supply air fan size. | Read | ||
| AI | 83 | EA Fan size | Present extract air fan size. | Read | ||
| AImin | 84 | Operation mode 1 | Read | 0=Manual stop, 1=Ext. stop, 2=Com. stop 1, 3=Manual high speed, 4=Summer night cooling, 5=Int. night heat, 6=Manual low speed, 7=Ext. high speed, 8=Com. high speed, 9=Year channel stop, 10=Year channel high speed, 11=Year channel low speed, 12=Time channel high speed, 13=Ext. low speed, 14=Com. low speed, 15=Time channel low speed, 16=Time channel stop, 17=Low speed=stop, 18=Com. stop 2 | ||
| AI | 85 | Operation mode 2 | Read | 0=, 1=Coold air recovery, 2=Cooling boost, 3=SA down regulation, 4=HX defrosting, 5=Anti frost func. active, 6=Effect reduction, 7=Startup, 8=Zero calibration, 9=Extended low speed, 10=Extended high speed, 11=Air adjustment, 12=Cooling off, 13=Purging R.HX, 14=Extended R.HX. op, 15=Filter calibration, 16=R.HX. calibration, 17=Morning boost, 18=Heating boost, 19=Alarm, 20=Cooling pressure reduction, 21=Startup extract air fan, 22=Reserve, 23=Airing, 24=Heating | ||
| AI | 86 | Operation mode, manual | Present manual operation set on the unit's handterminal. | Read | 0=Stop, 1=Auto operation, 2=Manual low speed, 3=Manual high speed | |
| AI | 87 | Copy of Input Status 1-16. | Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016 | Read | ||
| AI | 88 | Copy of Input Status 17-32. | Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032 | Read | ||
| AI | 89 | Copy of Input Status 33-48. | Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048 | Read | ||
| AI | 90 | Heat exchanger regulator | Present level of heat exchanger regulator. | % | Read | |
| AI | 91 | Extract air-humidity | Present level of extract air-humidity. | % | Read | |
| AI | 92 | Extract air-humidity temperature | Present temperature inside extract air-humidity sensor. | °C | Read | |
| AI | 93 | Extract air-dewpoint | Calculated extract air-dewpoint. | °C | Read | |
| AI | 94 | AYC chilled water temperature | Present AYC chilled water temperature. | °C | Read | |
| AI | 95 | AYC chilled water temperature regulator | Present AYC chilled water temperature regulator setpoint. | °C | Read | |
| AI | 96 | AYC chilled water output | Present level of AYC chilled water valve output. | % | Read | |
| AI | 97 | Supply air-dewpoint regulator | Present supply air-dewpoint regulator setpoint. | °C | Read | |
| AI | 98 | Supply air-humidity | Present level of supply air-humidity | % | Read | |
| AI | 99 | Supply air-humidity temperature | Present temperature inside supply air-humidity sensor. | °C | Read | |
| AI | 100 | Supply air-dewpoint | Calculated supply air-dewpoint. | °C | Read | |
| AI | 101 | Reserve | Read | |||
| AI | 102 | Reserve | Read | |||
| AI | 103 | Reserve | Read | |||
| AI | 104 | Reserve | Read | |||
| AI | 105 | R.HX. Efficiency | Calculated level of rotary heat exchanger efficiency. | % | Read | |
| AI | 106 | Reserve | Read | |||
| AI | 107 | Reserve | Read | |||
| AI | 108 | Supply air prefilter pressure level | Present supply air prefilter pressure drop. | Pa | Read | |
| AI | 109 | Supply air prefilter pressure alarm limit. | Present supply air prefilter pressure alarm limit. | Pa | Read | |
| AI | 110 | Supply air prefilter pressure level, new | Supply air prefilter pressure saved from calibration. | Pa | Read | |
| AI | 111 | Extract air prefilter pressure level | Present extract air prefilter pressure drop. | Pa | Read | |
| AI | 112 | Extract air prefilter pressure alarm limit. | Present extract air prefilter pressure alarm limit. | Pa | Read | |
| AI | 113 | Extract air prefilter pressure level, new | Extract air prefilter pressure saved from calibration. | Pa | Read | |
| AI | 114 | Reserve | Read | |||
| AI | 115 | Reserve | Read | |||
| AI | 116 | Reserve | Read | |||
| AI | 117 | Reserve | Read | |||
| AI | 118 | Reserve | Read | |||
| AI | 119 | Reserve | Read | |||
| AI | 120 | Reserve | Read | |||
| AI | 121 | Reserve | Read | |||
| AI | 122 | Reserve | Read | |||
| AI | 123 | Reserve | Read | |||
| AI | 124 | Pre-heating air temperature | Present pre-heating air temperature. | °C | Read | |
| AI | 125 | Pre-heating level | Present level of pre-heating. | % | Read | |
| AI | 126 | Pre-heating anti frost temperature | Present anti frost temperature for water pre-heating coils. | °C | Read | |
| AI | 127 | Reserve | Read | |||
| AI | 128 | Reserve | Read | |||
| AI | 129 | Reserve | Read | |||
| AI | 130 | Reserve | Read | |||
| AI | 131 | Reserve | Read | |||
| AI | 132 | Reserve | Read | |||
| AI | 133 | Preheat operation time | Present operation time for preheat, measured in minutes and present in days | Read | ||
| AI | 134 | Reserve | Read | |||
| AI | 135 | Reserve | Read | |||
| AI | 136 | Demand VOC Level | Present level of demand VOC input. | % | Read | |
| AI | 137 | Demand Vin Level | Present level of demand 0-10VDC input. | % | Read | |
| AI | 138 | SA Filter level calculated | Present level of calculated supply air filter. | % | Read | |
| AI | 139 | EA Filter level calculated | Present level of calculated extract air filter. | % | Read | |
| AI | 140 | AYC heat temperature | Present AYC heat temperature. | °C | Read | |
| AI | 141 | AYC heat temp regulator | Present AYC heat temperature regulator setpoint. | °C | Read | |
| AI | 142 | AYC heat valve output | Present level of AYC heat valve output. | % | Read | |
| AV | 0 | SA Low speed airflow setpoint | Supply airflow setpoint for the unit when running in low speed operation. | l/s | Write | |
| AV | 1 | SA High speed airflow setpoint | Supply airflow setpoint for the unit when running in high speed operation. | l/s | Write | |
| AV | 2 | SA Max speed airflow setpoint | Supply airflow max. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 3 | SA Min speed airflow setpoint | Supply airflow min. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 4 | EA Low speed airflow setpoint | Extract airflow setpoint for the unit when running in low speed operation. | l/s | Write | |
| AV | 5 | EA High speed airflow setpoint | Extract airflow setpoint for the unit when running in high speed operation. | l/s | Write | |
| AV | 6 | EA Max speed airflow setpoint | Extract airflow max. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 7 | EA Min speed airflow setpoint | Extract airflow min. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 8 | SA Low speed pressure setpoint | Supply air duct pressure setpoint for the unit when running in low | Pa | Write | |
| AV | 9 | SA High speed pressure setpoint | Supply air duct pressure for the unit when running in high speed | Pa | Write | |
| AV | 10 | SA Max speed output signal | Max. limit for the supply air fan speed when running in pressure | % | Write | |
| AV | 11 | SA Max speed pressure setpoint | Supply air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 12 | EA Low speed pressure setpoint | Extract air duct pressure setpoint for the unit when running in low | Pa | Write | |
| AV | 13 | EA High speed pressure setpoint | Extract air duct pressure setpoint for the unit when running in high | Pa | Write | |
| AV | 14 | EA Max speed output signal | Max. limit for the extract air fan speed when running in pressure | % | Write | |
| AV | 15 | EA Max speed pressure setpoint | Extract air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 16 | SA Low speed demand setpoint | Supply air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 17 | SA High speed demand setpoint | Supply air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 18 | EA Low speed demand setpoint | Extract air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 19 | EA High speed demand setpoint | Extract air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 20 | SA Airflow regulation zone | Supply airflow regulation zone setting in % of the present airflow setpoint | Write | ||
| AV | 21 | SA Airflow C-factor | Supply airflow regulator affection setting. | Write | ||
| AV | 22 | EA Airflow regulation zone | Extract airflow regulation zone setting in % of the present airflow setpoint | Write | ||
| AV | 23 | EA Airflow C-factor | Extract airflow regulator affection setting. | Write | ||
| AV | 24 | SA Pressure regulation zone | Supply air pressure regulation zone setting in % of the present duct | Write | ||
| AV | 25 | SA Pressure C-factor | Supply air pressure regulator affection setting. | Write | ||
| AV | 26 | EA Pressure regulation zone | Extract air pressure regulation zone setting in % of the present duct | Write | ||
| AV | 27 | EA Pressure C-factor | Extract air pressure regulator affection setting. | Write | ||
| AV | 28 | SA Demand P-band. | Supply air demand regulator P-band setting. | Write | ||
| AV | 29 | SA Demand C-factor | Supply air demand regulator affection setting. | Write | ||
| AV | 30 | EA Demand P-band. | Extract air demand regulator P-band setting. | Write | ||
| AV | 31 | EA Demand C-factor | Extract air demand regulator affection setting. | Write | ||
| AV | 32 | ERS 1 Diff | Supply air temperature difference setting accordning to the diagram for ERS 1. | °C | Write | |
| AV | 33 | ERS 1 Breakpoint | Breakpoint setting accordning to the diagram for ERS 1. | °C | Write | |
| AV | 34 | ERS 2 Breakpoint X1 | Breakpoint X1 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 35 | ERS 2 Breakpoint Y1 | Breakpoint Y1 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 36 | ERS 2 Breakpoint X2 | Breakpoint X2 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 37 | ERS 2 Breakpoint Y2 | Breakpoint Y2 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 38 | ERS 2 Breakpoint X3 | Breakpoint X3 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 39 | ERS 2 Breakpoint Y3 | Breakpoint Y3 setting accordning to the diagram for ERS 2. | °C | Write | |
| AVmin | 40 | SA Temperature setpoint | Supply air temperature setting, for supply air temp regulation mode. | °C | Write | |
| AVmin | 41 | EA/Room Temperature setpoint | Extract air/room temperature setting, for Extract air/room temp regulation mode. | °C | Write | |
| AV | 42 | SA Min temp setpoint | Supply air min.setpoint during EA/room regulation mode. | °C | Write | |
| AV | 43 | SA Max temp setpoint | Supply air max.setpoint during EA/room regulation mode. | °C | Write | |
| AV | 44 | SA Temperature P-band | Supply air temperature regulator P-band setting. | Write | ||
| AV | 45 | EA/Room Temperature P-band | Extract air/room temperature regulator P-band setting. | Write | ||
| AV | 46 | SA HX. Reg C-factor | Supply air heat exchange regulator affection setting. | Write | ||
| AV | 47 | EA/Room HX. Reg C-factor | Extract air/room heat exchange regulator affection setting. | Write | ||
| AV | 48 | SA Heat Reg C-factor | Supply air reheat regulator affection setting. | Write | ||
| AV | 49 | EA/Room Heat Reg C-factor | Extract air/room reheat regulator affection setting. | Write | ||
| AV | 50 | Reserve | Write | |||
| AV | 51 | Reserve | Write | |||
| AV | 52 | Reserve | Write | |||
| AV | 53 | Reserve | Write | |||
| AV | 54 | SA Down regulation Reg C-factor | Supply air reheat regulator affection setting. | Write | ||
| AV | 55 | Reserve | Write | |||
| AV | 56 | SA Cool reg C-factor | Supply air cool regulator affection setting. | Write | ||
| AV | 57 | EA/Room Cool reg C-factor | Extract air/room cool regulator affection setting. | Write | ||
| AV | 58 | SA Cooling boost C-factor | Supply air cooling boost affection setting. | Write | ||
| AV | 59 | EA/Room Cooling boost reg C-factor | Extract air/room cooling boost regulator affection setting. | Write | ||
| AV | 60 | HX Pressure alarm set. | Heat exchange pressure alarm limit setting (alarm no.38). | Pa | Write | |
| AV | 61 | Reserve | Write | |||
| AV | 62 | Reserve | Write | |||
| AV | 63 | Cooling off set. | Cooling off airflow setting in % of max. airflow. | % | Write | |
| AV | 64 | SA Down regulation neautral zone | Neutral zone setting before downregulation is permitted. | °C | Write | |
| AV | 65 | Cool Outdoor temp limit.1 | Outdoor temperature limit setting for cooling stage 1. | °C | Write | |
| AV | 66 | Cool Outdoor temp limit.2 | Outdoor temperature limit setting for cooling stage 2. | °C | Write | |
| AV | 67 | Cool Outdoor temp limit.3 | Outdoor temperature limit setting for cooling stage 3. | °C | Write | |
| AV | 68 | Temperature reg. Neutral zone | Neutral zone setting before shift between heating and cooling. | °C | Write | |
| AV | 69 | SA Cool min air flow | Supply air min. air flow setting for cooling. | l/s | Write | |
| AV | 70 | EA Cool min air flow | Extract air min. air flow setting for cooling. | l/s | Write | |
| AV | 71 | Heating boost start limit | Heating boost start temperature limit. | °C | Write | |
| AV | 72 | Cooling boost start limit | Cooling boost (comfort) start temperature limit. | °C | Write | |
| AV | 73 | SA Filter alarm limit | Supply air filter pressure alarm limit setting. | Pa | Write | |
| AV | 74 | EA Filter alarm limit | Extract air filter pressure alarm limit setting. | Pa | Write | |
| AV | 75 | Int. Night heat room start temp | Intermittent night heat function, extract air temperature setting for start. | °C | Write | |
| AV | 76 | Int. Night heat room stop temp | Intermittent night heat function, extract air temperature setting for stop. | °C | Write | |
| AV | 77 | Int. Night heat SA temp setpoint | Intermittent night heat function, supply air temperature setpoint during night heat. | °C | Write | |
| AV | 78 | Int. Night heat SA airflow setpoint | Intermittent night heat function, supply airflow setpoint during night heat. | l/s | Write | |
| AV | 79 | Int. Night heat EA airflow setpoint | Intermittent night heat function, extract airflow setpoint during night heat. | l/s | Write | |
| AV | 80 | Summer night cool EA start temp | Summer night cool function, extract air temperature setting for start. | °C | Write | |
| AV | 81 | Summer night cool EA stop temp | Summer night cool function, extract air temperature setting for stop. | °C | Write | |
| AV | 82 | Summer night cool outdoor temp limit | Summer night cool function, outdoor temperature limit. | °C | Write | |
| AV | 83 | Summer night cool SA temp setpoint | Summer night cool function, supply air temperature setpoint during summer night cool. | °C | Write | |
| AV | 84 | Outdoor temp comp. Winter X1. | Endpoint of winter compensation. | (-10.00)°C | Write | |
| AV | 85 | Outdoor temp comp. Winter X2. | Startpoint of winter compensation. | °C | Write | |
| AV | 86 | Outdoor temp comp. Winter Y1. | Level of winter compensation at X1. | °C | Write | |
| AV | 87 | Outdoor temp comp. Summer X3. | Startpoint of summer compensation. | °C | Write | |
| AV | 88 | Outdoor temp comp. Summer X4. | Endpoint of summer compensation. | °C | Write | |
| AV | 89 | Outdoor temp comp. Summer Y2. | Level of summer compensation at X4. | °C | Write | |
| AV | 90 | Outdoor airflow comp. Winter X1. | Endpoint of winter compensation. | (-10.00)°C | Write | |
| AV | 91 | Outdoor airflow comp. Winter X2. | Startpoint of winter compensation. | °C | Write | |
| AV | 92 | Outdoor airflow comp. Winter Y1. | Level of airflow compensation at X1. | % | Write | |
| AV | 93 | Reserve | Write | |||
| AV | 94 | EA/Room min temp alarm limit | Setting for min extract air /room temp alarm no.40. | °C | Write | |
| AV | 95 | SA Deviation alarm limit | Setting for supply air temperature below present setpoint, alarm no.41. | °C | Write | |
| AV | 96 | Reserve | Write | |||
| AV | 97 | SA Fan regulation mode | Setting of regulation type for the supply air fan. | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan | |
| AV | 98 | EA Fan regulation mode | Setting of regulation type for the extract air fan. | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan | |
| AV | 99 | ERS Step | Setting of curve when temperature is above breakpoint. | Write | ||
| AV | 100 | Temperature regulation mode. | Setting of temperature regulation type. | Write | 0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg | |
| AV | 101 | Cooling off periode | Time setting for cooling off electrical heating coil. | s | Write | |
| AV | 102 | Cool step time | Time setting between cool step shift. | s | Write | |
| AV | 103 | Cool restart time | Setting of time between two starts of the cool relays. | s | Write | |
| AV | 104 | Cool regulation mode | Setting of cool regulation type | Write | 0=Controlled 0-10V, 1=Controlled 10-0V, 2=On/Off 1-step, 3=On/Off 2-steps, 4=On/Off 3-steps binary | |
| AV | 105 | Heating boost regulation mode. | Setting for heating boost function. | Write | 0=Inactive, 1=Active | |
| AV | 106 | Cooling boost regulation mode. | Setting of cooling boost regulation type. | Write | 0=Inactive, 1=Comfort, 2=Economy, 3=Sequence, 4=Comfort+economy, 5=Economy+sequence | |
| AV | 107 | Filter calibration mode | Setting for required filter calibration. | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter, 4=HX | |
| AV | 108 | Air adjustment time, minutes | Setting for amount of minutes to air adjustment function. | Write | ||
| AV | 109 | Air adjustment time, hours | Setting for amount of hours to air adjustment function. | Write | ||
| AV | 110 | Handterminal language | Write | 0=Svenska, 1=Norsk, 2=Dansk, 3=Suomi, 4=English, 5=Français, 6=Deutsch, 7=Polski, 8=Český, 9=Italiano, 10=Español, 11=Português, 12=Pycckий, 13=Eesti, 14=Latviesu, 15=Lietiviu, 16=Nederlands, 17=Magyar, 18=Türkçe | ||
| AV | 111 | Summer night cool start, hour | Setting for start time of summer night cooling function. | Write | ||
| AV | 112 | Summer night cool start, minute | Setting for start time of summer night cooling function. | Write | ||
| AV | 113 | Summer night cool stop, hour | Setting for stop time of summer night cooling function. | Write | ||
| AV | 114 | Summer night cool stop, minute | Setting for stop time of summer night cooling function. | Write | ||
| AV | 115 | Reserve | Write | |||
| AV | 116 | Reserve | Write | |||
| AV | 117 | Morning boost time, hours | Setting of morning boost time before normal operation. | Write | ||
| AV | 118 | Morning boost time, minutes | Setting of morning boost time before normal operation. | Write | ||
| AV | 119 | Startup time | Setting of time for startup when the unit regulator is running with | s | Write | |
| AV | 120 | Start delay SA fan. | Setting of start delay time for the supply air fan. | s | Write | |
| AV | 121 | Start delay EA fan. | Setting of start delay time for the extract air fan after supply | s | Write | |
| AV | 122 | Air flow unit | Setting of air flow unit presented in the unit's handterminal and WEB. | Write | 0=l/s, 1=m3/s, 2=m3/h | |
| AV | 123 | Reserve | Write | |||
| AV | 124 | Year | Setting for the unit's internal clock. | Write | ||
| AV | 125 | Month | Setting for the unit's internal clock. | Write | ||
| AV | 126 | Date | Setting for the unit's internal clock. | Write | ||
| AV | 127 | Hour | Setting for the unit's internal clock. | Write | ||
| AV | 128 | Minute | Setting for the unit's internal clock. | Write | ||
| AV | 129 | Second | Setting for the unit's internal clock. | Write | ||
| AV | 130 | Time channel 1 status | Low speed High speed | Write | 0=Inactive 16=Inactive, 1=Monday 17=Monday, 2=Tuesday 18=Tuesday, 3=Wednesday 19=Wednesday, 4=Thursday 20=Thursday, 5=Friday 21=Friday, 6=Saturday 22=Saturday, 7=Sunday 23=Sunday, 8=Monday..Friday 24=Monday..Friday, 9=Monday..Sunday 25=Monday..Sunday, 10=Saturday..Sunday 26=Saturday..Sunday | |
| AV | 131 | Time channel 1 start hour | Write | |||
| AV | 132 | Time channel 1 start minute | Write | |||
| AV | 133 | Time channel 1 stop hour | Write | |||
| AV | 134 | Time channel 1 stop minute | Write | |||
| AV | 135 | Time channel 2 status | Write | |||
| AV | 136 | Time channel 2 start hour | Write | |||
| AV | 137 | Time channel 2 start minute | Write | |||
| AV | 138 | Time channel 2 stop hour | Write | |||
| AV | 139 | Time channel 2 stop minute | Write | |||
| AV | 140 | Time channel 3 status | Write | |||
| AV | 141 | Time channel 3 start hour | Write | |||
| AV | 142 | Time channel 3 start minute | Write | |||
| AV | 143 | Time channel 3 stop hour | Write | |||
| AV | 144 | Time channel 3 stop minute | Write | |||
| AV | 145 | Time channel 4 status | Write | |||
| AV | 146 | Time channel 4 start hour | Write | |||
| AV | 147 | Time channel 4 start minute | Write | |||
| AV | 148 | Time channel 4 stop hour | Write | |||
| AV | 149 | Time channel 4 stop minute | Write | |||
| AV | 150 | Time channel 5 status | Write | |||
| AV | 151 | Time channel 5 start hour | Write | |||
| AV | 152 | Time channel 5 start minute | Write | |||
| AV | 153 | Time channel 5 stop hour | Write | |||
| AV | 154 | Time channel 5 stop minute | Write | |||
| AV | 155 | Time channel 6 status | Write | |||
| AV | 156 | Time channel 6 start hour | Write | |||
| AV | 157 | Time channel 6 start minute | Write | |||
| AV | 158 | Time channel 6 stop hour | Write | |||
| AV | 159 | Time channel 6 stop minute | Write | |||
| AV | 160 | Time channel 7 status | Write | |||
| AV | 161 | Time channel 7 start hour | Write | |||
| AV | 162 | Time channel 7 start minute | Write | |||
| AV | 163 | Time channel 7 stop hour | Write | |||
| AV | 164 | Time channel 7 stop minute | Write | |||
| AV | 165 | Time channel 8 status | Write | |||
| AV | 166 | Time channel 8 start hour | Write | |||
| AV | 167 | Time channel 8 start minute | Write | |||
| AV | 168 | Time channel 8 stop hour | Write | |||
| AV | 169 | Time channel 8 stop minute | Write | |||
| AV | 170 | Extended low speed op. Hours | Setting for extended low speed operation. | Write | ||
| AV | 171 | Extended low speed op. Minutes | Setting for extended low speed operation. | Write | ||
| AV | 172 | Extended high speed op. Hours | Setting for extended low speed operation. | Write | ||
| AV | 173 | Extended high speed op. Minutes | Setting for extended low speed operation. | Write | ||
| AVmin | 174 | Communication operation mode | Setting of unit operation mode from communication. Summer night cool, intermittent night | Write | 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 | |
| AV | 175 | Service periode alarm. | Setting for delay time in months before service alarm. | Write | ||
| AV | 176 | External alarm 1 delay | Setting of delay time for external alarm no 1 | s | Write | |
| AV | 177 | External alarm 2 delay | Setting of delay time for external alarm no 2 | s | Write | |
| AV | 178 | Int. Night heat SA pressure setpoint | Intermittent night heat function, supply pressure setpoint during night heat. | Pa | Write | |
| AV | 179 | Int. Night heat EA pressure setpoint | Intermittent night heat function, extract pressure setpoint during night heat. | Pa | Write | |
| AV | 180 | Copy of Coil Status 1-16 | Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016 | Write | ||
| AV | 181 | Copy of Coil Statust 17-32 | Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032 | Write | ||
| AV | 182 | Copy of Coil Status 33-48 | Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048 | Write | ||
| AV | 183 | Heat relay periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 184 | Cool relay 1 periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 185 | Cool relay 2 periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 186 | Slave control C-factor | Slave regulator affection setting. | Write | ||
| AV | 187 | SA dehumid P-band | SA dehumid regulator P-band setting. | Write | ||
| AV | 188 | SA dehumid C-factor | SA dehumid regulator affection setting. | Write | ||
| AV | 189 | Dewpoint reg. P-band | Dewpoint regulator P-band setting. | Write | ||
| AV | 190 | Dewpoint reg. C-factor | Dewpoint regulator affection setting. | Write | ||
| AV | 191 | AYC chilled water temperature | Setting of AYC chilled water temperature setpoint. | °C | Write | |
| AV | 192 | Dewpoint neutralzone | Dewpoint neutralzone setting. | °C | Write | |
| AV | 193 | Comp. airflow | Setting of comp. airflow. | % | Write | |
| AV | 194 | Supply air-humidity | Setting of supply air-humidity. | % | Write | |
| AV | 195 | Water heating periodic op. time | Setting of periodic op. time (minute). | min | Write | |
| AV | 196 | Water heating interval | Setting of water heating interval time (hour). | h | Write | |
| AV | 197 | Cool periodic op. time | Setting of periodic op. time (minute). | min | Write | |
| AV | 198 | Cool interval | Setting of cool interval time (hour). | h | Write | |
| AV | 199 | Reserve | Write | |||
| AV | 200 | EA/Room temperature (external) func. | Setting of EA/Room temperature (external) function. | Write | 0=Inactive, 1=IQnomic, 2=Communication (4x0202) | |
| AV | 201 | EA/Room temperature com. | Setting of EA/Room temperature via communication. | °C | Write | |
| AV | 202 | Outdoor temperature (external) func. | Setting of outdoor temperature (external) function. | Write | 0=Inactive, 1=IQnomic, 2=Communication (4x0204) | |
| AV | 203 | Outdoor temperature com. | Setting of outdoor temperature via communication. | °C | Write | |
| AV | 204 | Timeout temperature com. | Setting of timeout for temperature via communication (4x0202, 4x0204). | min | Write | |
| AV | 205 | Flow at fire function. | Setting for activating the air fan operation at fire function | Write | 0=Inactive, 1=SA, 2=EA, 3=SA+EA | |
| AV | 206 | Air fan down regulation func. | Setting for activating the air fan down regulation function | Write | 0=Inactive, 1=SA, 2=SA+EA | |
| AV | 207 | SA speed at fire. | Setting of supply air speed at fire. | % | Write | |
| AV | 208 | EA speed at fire. | Setting of extract air speed at fire. | % | Write | |
| AV | 209 | Reserve | Write | |||
| AV | 210 | Reserve | Write | |||
| AV | 211 | Supply air min P-band. | Supply air min regulator P-band setting. | Write | ||
| AV | 212 | Supply air min C-factor. | Supply air min regulator affection setting. | Write | ||
| AV | 213 | Supply air max P-band. | Supply air max regulator P-band setting. | Write | ||
| AV | 214 | Supply air max C-factor. | Supply air max regulator affection setting. | Write | ||
| AV | 215 | Year channel 1 function. | Write | 0=Inactive, 1=Stop, 2=Low speed, 3=High speed | ||
| AV | 216 | Year channel 1 start year. | Write | |||
| AV | 217 | Year channel 1 start month. | Write | |||
| AV | 218 | Year channel 1 start date. | Write | |||
| AV | 219 | Year channel 1 start hour. | Write | |||
| AV | 220 | Year channel 1 start minute. | Write | |||
| AV | 221 | Year channel 1 stop year. | Write | |||
| AV | 222 | Year channel 1 stop month. | Write | |||
| AV | 223 | Year channel 1 stop date. | Write | |||
| AV | 224 | Year channel 1 stop hour. | Write | |||
| AV | 225 | Year channel 1 stop minute. | Write | |||
| AV | 226 | Year channel 2 function. | Write | |||
| AV | 227 | Year channel 2 start year. | Write | |||
| AV | 228 | Year channel 2 start month. | Write | |||
| AV | 229 | Year channel 2 start date. | Write | |||
| AV | 230 | Year channel 2 start hour. | Write | |||
| AV | 231 | Year channel 2 start minute. | Write | |||
| AV | 232 | Year channel 2 stop year. | Write | |||
| AV | 233 | Year channel 2 stop month. | Write | |||
| AV | 234 | Year channel 2 stop date. | Write | |||
| AV | 235 | Year channel 2 stop hour. | Write | |||
| AV | 236 | Year channel 2 stop minute. | Write | |||
| AV | 237 | Year channel 3 function. | Write | |||
| AV | 238 | Year channel 3 start year. | Write | |||
| AV | 239 | Year channel 3 start month. | Write | |||
| AV | 240 | Year channel 3 start date. | Write | |||
| AV | 241 | Year channel 3 start hour. | Write | |||
| AV | 242 | Year channel 3 start minute. | Write | |||
| AV | 243 | Year channel 3 stop year. | Write | |||
| AV | 244 | Year channel 3 stop month. | Write | |||
| AV | 245 | Year channel 3 stop date. | Write | |||
| AV | 246 | Year channel 3 stop hour. | Write | |||
| AV | 247 | Year channel 3 stop minute. | Write | |||
| AV | 248 | Year channel 4 function. | Write | |||
| AV | 249 | Year channel 4 start year. | Write | |||
| AV | 250 | Year channel 4 start month. | Write | |||
| AV | 251 | Year channel 4 start date. | Write | |||
| AV | 252 | Year channel 4 start hour. | Write | |||
| AV | 253 | Year channel 4 start minute. | Write | |||
| AV | 254 | Year channel 4 stop year. | Write | |||
| AV | 255 | Year channel 4 stop month. | Write | |||
| AV | 256 | Year channel 4 stop date. | Write | |||
| AV | 257 | Year channel 4 stop hour. | Write | |||
| AV | 258 | Year channel 4 stop minute. | Write | |||
| AV | 259 | Year channel 5 function. | Write | |||
| AV | 260 | Year channel 5 start year. | Write | |||
| AV | 261 | Year channel 5 start month. | Write | |||
| AV | 262 | Year channel 5 start date. | Write | |||
| AV | 263 | Year channel 5 start hour. | Write | |||
| AV | 264 | Year channel 5 start minute. | Write | |||
| AV | 265 | Year channel 5 stop year. | Write | |||
| AV | 266 | Year channel 5 stop month. | Write | |||
| AV | 267 | Year channel 5 stop date. | Write | |||
| AV | 268 | Year channel 5 stop hour. | Write | |||
| AV | 269 | Year channel 5 stop minute. | Write | |||
| AV | 270 | Year channel 6 function. | Write | |||
| AV | 271 | Year channel 6 start year. | Write | |||
| AV | 272 | Year channel 6 start month. | Write | |||
| AV | 273 | Year channel 6 start date. | Write | |||
| AV | 274 | Year channel 6 start hour. | Write | |||
| AV | 275 | Year channel 6 start minute. | Write | |||
| AV | 276 | Year channel 6 stop year. | Write | |||
| AV | 277 | Year channel 6 stop month. | Write | |||
| AV | 278 | Year channel 6 stop date. | Write | |||
| AV | 279 | Year channel 6 stop hour. | Write | |||
| AV | 280 | Year channel 6 stop minute. | Write | |||
| AV | 281 | Year channel 7 function. | Write | |||
| AV | 282 | Year channel 7 start year. | Write | |||
| AV | 283 | Year channel 7 start month. | Write | |||
| AV | 284 | Year channel 7 start date. | Write | |||
| AV | 285 | Year channel 7 start hour. | Write | |||
| AV | 286 | Year channel 7 start minute. | Write | |||
| AV | 287 | Year channel 7 stop year. | Write | |||
| AV | 288 | Year channel 7 stop month. | Write | |||
| AV | 289 | Year channel 7 stop date. | Write | |||
| AV | 290 | Year channel 7 stop hour. | Write | |||
| AV | 291 | Year channel 7 stop minute. | Write | |||
| AV | 292 | Year channel 8 function. | Write | |||
| AV | 293 | Year channel 8 start year. | Write | |||
| AV | 294 | Year channel 8 start month. | Write | |||
| AV | 295 | Year channel 8 start date. | Write | |||
| AV | 296 | Year channel 8 start hour. | Write | |||
| AV | 297 | Year channel 8 start minute. | Write | |||
| AV | 298 | Year channel 8 stop year. | Write | |||
| AV | 299 | Year channel 8 stop month. | Write | |||
| AV | 300 | Year channel 8 stop date. | Write | |||
| AV | 301 | Year channel 8 stop hour. | Write | |||
| AV | 302 | Year channel 8 stop minute. | Write | |||
| AV | 303 | Filter select. | Setting for filter select function. | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 304 | Prefilter select. | Setting for prefilter select function. | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 305 | SA prefilter alarm limit. | Supply air prefilter pressure alarm limit setting. | Pa | Write | |
| AV | 306 | EA prefilter alarm limit. | Extract air prefilter pressure alarm limit setting. | Pa | Write | |
| AV | 307 | Prefilter calibration mode. | Setting for requiered filtercalibration. | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter | |
| AV | 308 | Preheating function. | Setting of preheating function. | Write | 0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP | |
| AV | 309 | Preheating setpoint. | Setting of preheating temperature setpoint. | °C | Write | |
| AV | 310 | Preheat P-band. | Preheat regulator P-band setting. | Write | ||
| AV | 311 | Preheat C-factor. | Preheat regulator affection setting. | Write | ||
| AV | 312 | SA Filter calculated alarm level | Supply air filter calculated alarm limit setting. | % | Write | |
| AV | 313 | EA Filter calculated alarm level | Extract air filter calculated alarm limit setting. | % | Write | |
| AV | 314 | Mode digital output relay 1 | Setting of mode output relay 1 function. | Write | 0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2 | |
| AV | 315 | Mode digital output relay 2 | Setting of mode output relay 2 function. | Write | 0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2 | |
| AV | 316 | Mode digital input 1 | Setting of mode input 1 function. | Write | 0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire | |
| AV | 317 | Mode digital input 2 | Setting of mode input 2 function. | Write | 0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire | |
| AV | 318 | Manual morning boost time hour | Setting of manual morning boost time before normal operation. | Write | ||
| AV | 319 | Manual morning boost time minutes | Setting of manual morning boost time before normal operation. | Write | ||
| AV | 320 | Airing temp set | Setting of airing temperature setpoint. | °C | Write | |
| AV | 321 | Airing time set | Setting of airing time in minutes. | Write | ||
| AV | 322 | Manual operation drift mode | Setting of manual operation drift mode. | Write | 0=Normal operation, 1=Extended operation, 2=Airing, 3=Heating, 4=Heating+Recirc | |
| AV | 323 | AYC function. | Setting of AYC function. | Write | 0=Inactive, 1=Cool, 2=Heat, 3=Cool+heat | |
| AV | 324 | AYC heat temp set. | Setting of AYC heated water temperature setpoint. | °C | Write | |
| AV | 325 | AYC night comp. channel. | Setting of AYC night compensation channel. | Write | 1=Channel 1, 2=Channel 2 | |
| AV | 326 | AYC channel start hour. | Setting of AYC channel start time (hour). | h | Write | |
| AV | 327 | AYC channel start minute. | Setting of AYC channel start time (minute). | min | Write | |
| AV | 328 | AYC channel stop hour. | Setting of AYC channel stop time (hour). | h | Write | |
| AV | 329 | AYC channel stop minute. | Setting of AYC channel stop time (minute). | min | Write | |
| AV | 330 | AYC channel period. | Setting of AYC channel period. | Write | 0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday | |
| AV | 331 | AYC heat P-band. | AYC heat regulator P-band setting. | Write | ||
| AV | 332 | AYC heat C-factor. | AYC heat regulator affection setting. | Write | ||
| AV | 333 | AYC cool P-band. | AYC cool regulator P-band setting. | Write | ||
| AV | 334 | AYC cool C-factor. | AYC cool regulator affection setting. | Write | ||
| AV | 335 | AYC heat out comp. X1. | AYC outdoor compensation of heated water, outdoor temp X1 setting. | °C | Write | |
| AV | 336 | AYC heat out comp. Y1. | AYC outdoor compensation of heated water, heated water temp Y1 setting. | °C | Write | |
| AV | 337 | AYC heat out comp. X2. | AYC outdoor compensation of heated water, outdoor temp X2 setting. | °C | Write | |
| AV | 338 | AYC heat out comp. Y2. | AYC outdoor compensation of heated water, heated water temp Y2 setting. | °C | Write | |
| AV | 339 | AYC heat out comp. X3. | AYC outdoor compensation of heated water, outdoor temp X3 setting. | °C | Write | |
| AV | 340 | AYC heat out comp. Y3. | AYC outdoor compensation of heated water, heated water temp Y3 setting. | °C | Write | |
| AV | 341 | AYC heat room comp. temp limit. | AYC room compensation of heated water, heated water temp limit setting. | °C | Write | |
| AV | 342 | AYC heat room comp P-band. | AYC room compensation of heated water, heated water P-band setting. | °C | Write | |
| AV | 343 | AYC heat night comp temp. | AYC night compensation of heated water, heated water night setting. | °C | Write | |
| AV | 344 | AYC heat pump on temp. | AYC pump operation of heated water, outdoor temp start setting. | °C | Write | |
| AV | 345 | AYC heat pump off temp. | AYC pump operation of heated water, outdoor temp stop setting. | °C | Write | |
| AV | 346 | AYC heat pump alarm. | Setting for selecting the AYC heated water pump alarm function. | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 347 | AYC heat per op function. | Setting for selecting the AYC heated water periodic operation function. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 348 | AYC heat per op time. | AYC periodic operation of heated water, time (minute) setting. | min | Write | |
| AV | 349 | AYC heat per op interval. | AYC periodic operation of heated water, interval time (hour) setting. | h | Write | |
| AV | 350 | AYC cool out comp. X1. | AYC outdoor compensation of chilled water, outdoor temp X1 setting. | °C | Write | |
| AV | 351 | AYC cool out comp. Y1. | AYC outdoor compensation of chilled water, chilled water temp Y1 setting. | °C | Write | |
| AV | 352 | AYC cool out comp. X2. | AYC outdoor compensation of chilled water, outdoor temp X2 setting. | °C | Write | |
| AV | 353 | AYC cool out comp. Y2. | AYC outdoor compensation of chilled water, chilled water temp Y2 setting. | °C | Write | |
| AV | 354 | AYC cool out comp. X3. | AYC outdoor compensation of chilled water, outdoor temp X3 setting. | °C | Write | |
| AV | 355 | AYC cool out comp. Y3. | AYC outdoor compensation of chilled water, chilled water temp Y3 setting. | °C | Write | |
| AV | 356 | AYC cool room comp. temp limit. | AYC room compensation of chilled water, chilled water temp limit setting. | °C | Write | |
| AV | 357 | AYC cool room comp. P-band. | AYC room compensation of chilled water, chilled water P-band setting. | °C | Write | |
| AV | 358 | AYC cool night comp temp. | AYC night compensation of chilled water, chilled water night setting. | °C | Write | |
| AV | 359 | AYC cool pump on temp. | AYC pump operation of chilled water, outdoor temp start setting. | °C | Write | |
| AV | 360 | AYC cool pump off temp. | AYC pump operation of chilled water, outdoor temp stop setting. | °C | Write | |
| AV | 361 | AYC cool pump alarm. | Setting for selecting the AYC chilled water pump alarm function. | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 362 | AYC cool per op function. | Setting for selecting the AYC chilled water periodic operation function. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 363 | AYC cool per op time. | AYC periodic operation of chilled water, time (minute) setting. | min | Write | |
| AV | 364 | AYC cool per op interval. | AYC periodic operation of chilled water, interval time (hour) setting. | h | Write | |
| AV | 365 | IO-mod 3 output 1 function. | Setting of I/O-module no. 3 relay 1 output. | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| AV | 366 | IO-mod 3 output 2 function. | Setting of I/O-module no. 3 relay 2 output. | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| BI | 0 | Heat output | Status for relay output. | Read | ||
| BI | 1 | Cool output 1 | Status for relay output. | Read | ||
| BI | 2 | Cool output 2 | Status for relay output. | Read | ||
| BI | 3 | Low speed output | Status for relay output. | Read | ||
| BI | 4 | High speed output | Status for relay output. | Read | ||
| BImin | 5 | A-alarm. | Status for relay output. | Read | ||
| BImin | 6 | B-alarm. | Status for relay output. | Read | ||
| BI | 7 | Operation output | Status for relay output. | Read | ||
| BI | 8 | Damper output | Status for relay output. | Read | ||
| BI | 9 | External low speed input | Status for digital input. | Read | ||
| BI | 10 | External high speed input | Status for digital input. | Read | ||
| BI | 11 | External alarm 1 input | Status for digital input. | Read | ||
| BI | 12 | External alarm 2 input | Status for digital input. | Read | ||
| BI | 13 | External fire alarm input. | Status for digital input. | Read | ||
| BI | 14 | External stop input | Status for digital input. | Read | ||
| BI | 15 | DIP Switch 1 | Status for dip switch setting. | Read | ||
| BI | 16 | DIP Switch 2 | Status for dip switch setting. | Read | ||
| BI | 17 | DIP Switch 3 | Status for dip switch setting. | Read | ||
| BI | 18 | DIP Switch 4 | Status for dip switch setting. | Read | ||
| BI | 19 | DIP Switch 5 | Status for dip switch setting. | Read | ||
| BI | 20 | DIP Switch 6 | Status for dip switch setting. | Read | ||
| BI | 21 | AYC heat pump output | Status for AYC heat pump output. | Read | ||
| BI | 22 | AYC cool pump output | Status for AYC cool pump output. | Read | ||
| BI | 23 | Reserve 9 | Read | |||
| BI | 24 | R.HX rotation monitor | Status from the rotation detector. | Read | ||
| BI | 25 | Reserve 10 | Read | |||
| BI | 26 | Reserve 11 | Read | |||
| BI | 27 | Reserve 12 | Read | |||
| BI | 28 | Pre-heat output | Status for relay output. | Read | ||
| BI | 29 | Recirculation output | Status for I/O-module no. 3 relay 1 output. | Read | ||
| BI | 30 | Booster output | Status for I/O-module no. 3 relay 2 output. | Read | ||
| BI | 31 | IO-mod 3 output 1 | Status for I/O-module no. 3 relay 1 output. | Read | ||
| BI | 32 | IO-mod 3 output 2 | Status for I/O-module no. 3 relay 2 output. | Read | ||
| BI | 33 | Reserve 13 | Read | |||
| BI | 34 | Reserve 14 | Read | |||
| BI | 35 | Reserve 15 | Read | |||
| BI | 36 | Reserve 16 | Read | |||
| BI | 37 | Reserve 17 | Read | |||
| BI | 38 | Reserve 18 | Read | |||
| BI | 39 | Reserve 19 | Read | |||
| BI | 40 | Reserve 20 | Read | |||
| BI | 41 | Reserve 21 | Read | |||
| BI | 42 | Reserve 22 | Read | |||
| BI | 43 | Reserve 23 | Read | |||
| BI | 44 | Reserve 24 | Read | |||
| BI | 45 | Reserve 25 | Read | |||
| BI | 46 | Reserve 26 | Read | |||
| BI | 47 | Reserve 27 | Read | |||
| BI | 48 | Alarm number 1 | Status if alarm number 1 is active. | Read | ||
| BI | 49 | Alarm number 2 | Status if alarm number 2 is active. | Read | ||
| BI | 50 | Alarm number 3 | Status if alarm number 3 is active. | Read | ||
| BI | 247 | Alarm number 200 | Status if alarm number 200 is active. | Read | ||
| BI | 248 | Info number 1 | Status if info number 1 is active. | Read | ||
| BI | 249 | Info number 2 | Status if info number 2 is active. | Read | ||
| BI | 250 | Info number 3 | Status if info number 3 is active. | Read | ||
| BI | 347 | Info number 100 | Status if info number 100 is active. | Read | ||
| BVmin | 0 | Alarm reset | Resets tripped alarms. | Write | ||
| BV | 1 | R.HX. Defrost func. | Setting for activating the defrost function for the rotary heat exchanger. | Write | ||
| BV | 2 | Cool operation mode | Setting for cooling between off and auto operation. | Write | ||
| BV | 3 | Int. Night heat func. | Setting for activating the intermittent night heat function. | Write | ||
| BV | 4 | Damper func. | Setting for activating the damper output relay during int. night heat. | Write | ||
| BV | 5 | Summer night cooling | Setting for activating the suumer night cool function. | Write | ||
| BV | 6 | Outdoor temp compensation | Setting for activating the outdoor temperature compensation function. | Write | ||
| BV | 7 | Outdoor airflow compensation | Setting for activating the outdoor airflow compensation function. | Write | ||
| BV | 8 | Auto. Summer/winter switch | Setting for activating the automatic switch between summer/winter time function. | Write | ||
| BV | 9 | Switch clock func. | Setting for switch clock function type. | Write | 0=Stop - low speed - high speed, 1=Low speed - high speed | |
| BV | 10 | Internal fire alarm func. | Setting for activating the internal fire alarm function. | Write | ||
| BV | 11 | External alarm 1 active at closure | Setting for external alarm number 1 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 12 | External alarm 2 active at closure | Setting for external alarm number 2 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 13 | Dewpoint reg. func. | Setting for activating the dewpoint regulator funktion. | Write | ||
| BV | 14 | Dehumid reg. func. | Setting for activating the dehumid regulator funktion. | Write | ||
| BV | 15 | External fire alarm func. | Setting for external fire resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 16 | External alarm 1 func. | Setting for external alarm 1 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 17 | External alarm 2 func. | Setting for external alarm 2 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 18 | Int. Night heat output func. | Setting for selecting the intermittent night heat output function. | Write | 0=IQnomic, 1=IQnomic+ | |
| BV | 19 | Morningboost damper func. | Setting for activating the morningboost damper function. | Write | 0=Inactive, 1=Active | |
| BV | 20 | Morningboost extract func. | Setting for activating the morningboost extract air fan function. | Write | 0=Inactive, 1=Active | |
| BV | 21 | Filter func. | Setting for filter between calculated and pressure sensors. | Write | 0=Calculated, 1=Pressure sensors | |
| BV | 22 | Iqnomic Plus module no.6 Cooling | Setting for activating Iqnomiq Plus no.6 Cooling module. | Write | 0=Inactive, 1=Active | |
| BV | 23 | Airing auto func. | Setting for activating the airing auto function. | Write | 0=Inactive, 1=Active | |
| BV | 24 | AYC heat out comp. func. | Setting for selecting the AYC outdoor comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 25 | AYC heat room comp. func. | Setting for selecting the AYC room comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 26 | AYC heat room comp. night block func. | Setting for selecting the AYC room comp. heated water night block function. | Write | 0=Inactive, 1=Active | |
| BV | 27 | AYC heat night comp. func. | Setting for selecting the AYC night comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 28 | AYC heat valve signal func. | Setting for selecting the AYC valve signal heated water alarm function. | Write | 0=Inactive, 1=Active | |
| BV | 29 | AYC cool out comp. func. | Setting for selecting the AYC outdoor comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 30 | AYC cool room comp. func. | Setting for selecting the AYC room comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 31 | AYC cool room comp. night block func. | Setting for selecting the AYC room comp. chilled water night block function. | Write | 0=Inactive, 1=Active | |
| BV | 32 | AYC cool night comp. func. | Setting for selecting the AYC night comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 33 | AYC cool valve signal func. | Setting for selecting the AYC valve signal chilled water alarm function. | Write | 0=Inactive, 1=Active |
No points match these filters.
Integration notes
- Only AI, AV, BI and BV objects are used; modes and selections are AVs with numbered states.
- Instances are not contiguous and 'Reserve' objects carry no data.
- Units are taken from the Min/Max column (l/s, Pa, °C, %, s, min); unitless ranges are left blank.
- Operating state is reported as codes in AI-84 Operation mode 1 and AI-85 Operation mode 2.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Compact / GOLD LP BACnet IP (PV 2.01+) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
How many BACnet points does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) have?
This list has 600 BACnet objects: 143 analog inputs, 367 analog values, 56 binary inputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points are writable?
401 of the 600 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet documentation?
The source is BACnet IP Compact/GOLD LP, program version 2.01 and newer versions (GB.BACnet480.100129), revision 2010-01-29, published free by Swegon at https://www.swegon.com/globalassets/digizuite/11562-en-compactair_bacnet480_other_en.pdf.
What are the minimum BACnet points to integrate the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
Start with AV 174 Communication operation mode (BMS stop / low / high / auto command); AV 40 SA Temperature setpoint (Supply air temperature setpoint); AV 41 EA/Room Temperature setpoint (Extract/room temperature setpoint); BV 0 Alarm reset (Resets tripped alarms); AI 84 Operation mode 1 (Current operating reason (stop, speed, channel)); AI 27 SA Temperature (Supply air temperature); AI 28 EA/Room temperature (Extract/room temperature); AI 29 Outdoor temperatur (Outdoor air temp measured by the unit, °C); BI 5 A-alarm. (A-class alarm active); BI 6 B-alarm. (B-class alarm active).
How do I enable BMS control of the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.
Does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) need a BACnet heartbeat or have a communication timeout?
Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.
Can the BMS supply sensor values to the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.
How do I check these points on the real Compact / GOLD LP BACnet IP (PV 2.01+)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
Source: BACnet IP Compact/GOLD LP, program version 2.01 and newer versions · GB.BACnet480.100129 · rev. 2010-01-29. Object names, instances and units are reproduced as published; descriptions are our own.