Easy BACnet
  1. Home
  2. BACnet points lists
  3. Swegon
  4. SuperWISE (generation 1) BACnet IP - system objects

Other equipment (demand-controlled ventilation system controller) · BACnet points list

Swegon SuperWISE (generation 1) BACnet IP - system objects BACnet points list

Updated 7 November 2026

Short answer

SuperWISE gen 1 is the system controller of Swegon's WISE demand-controlled ventilation system and acts as a BACnet IP server (B-ASC) on its Ethernet port. Its EDE workbook gives fixed system objects (instances 65000 and up): summed supply/extract airflow per zone, the duct-pressure optimisation link to the GOLD air handler, demand flags, alarms, clock and commands. Room, damper and router objects come from per-product sheets whose instances are calculated from the zone, damper and room numbers.

This page lists 81 BACnet objects for the Swegon SuperWISE (generation 1) BACnet IP - system objects — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.

Manufacturer
Swegon
Model
SuperWISE (generation 1) BACnet IP - system objects
Equipment
Other equipment (demand-controlled ventilation system controller)
Equipment type
Other equipment
BACnet objects
81 (32 writable)
Transport
BACnet IP
Firmware
SuperWISE program version 1.25 (BACnet list ver. 1.3, 2014)
Also known as
SuperWISE, Super WISE, WISE gen 1, GB.BACnetSuper WISE.140603, SuperWISE_BACnet_list_ver_1.3
Source document
SuperWISE BACnet list ver 1.3 (BACnet IP, Super WISE program version 1.25), in SuperWISE BACnet PICS gen 1 zip · GB.BACnetSuper WISE.140603 · rev. 2014-06-03
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.

BMS integration notes: Swegon SuperWISE (generation 1) BACnet IP - system objects

Integration in brief

Read the per-zone summed airflows and SumAlarm (AI 65101) and the cooling/heating demand flags. The AV 65200 range is the pressure-optimisation link with the air handler: the AHU (or BMS) writes the real SA/EA pressures and running state, and SuperWISE returns the requested pressures (AI 65041/65042).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 65215WISE_DriftONWrite 1 while the AHU runs, 0 when stoppedWrite
AV 65216WISE_FireAlarmFire alarm; 1 forces all regulators to emergency modeWrite
AV 65200WISE_SA_PaReal supply duct pressure from the AHU, PaWrite
AV 65201WISE_EA_PaReal extract duct pressure from the AHU, PaWrite
AV 65221AlarmResetAlarm reset (returns to 0)Write
AI 65041WISE_SA_ForcPaRequested supply duct pressure for the AHU, PaRead
AI 65042WISE_EA_ForcPaRequested extract duct pressure for the AHU, PaRead
AI 65055CoolDemandFlagAny room needs coolingRead
AI 65056HeatDemandFlagAny room needs heatingRead
AI 65101SumAlarmAny active alarmRead

Enable & remote start

BACnet IP must be switched on in the SuperWISE Admin/Misc tab before the objects respond.

Network setup

Watch out for

Swegon SuperWISE (generation 1) BACnet IP - system objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

81 of 81 shown
Type
Access
Show
Swegon SuperWISE (generation 1) BACnet IP - system objects BACnet Points List
DescriptionStates
AI65000SuperWISE_SWSuperWISE-Software-Verl/sRead
AI65001SA_SumFlwZone0SumFlow for Sup.Flow Zone-0l/sRead
AI65002SA_SumFlwZone1SumFlow for Sup.Flow Zone-1l/sRead
AI65003SA_SumFlwZone2SumFlow for Sup.Flow Zone-2l/sRead
AI65004SA_SumFlwZone3SumFlow for Sup.Flow Zone-3l/sRead
AI65005SA_SumFlwZone4SumFlow for Sup.Flow Zone-4l/sRead
AI65006SA_SumFlwZone5SumFlow for Sup.Flow Zone-5l/sRead
AI65007SA_SumFlwZone6SumFlow for Sup.Flow Zone-6l/sRead
AI65008SA_SumFlwZone7SumFlow for Sup.Flow Zone-7l/sRead
AI65009SA_SumFlwZone8SumFlow for Sup.Flow Zone-8l/sRead
AI65010SA_SumFlwZone9SumFlow for Sup.Flow Zone-9l/sRead
AI65011EA_SumFlwZone0SumFlow for Exh.Flow Zone-0l/sRead
AI65012EA_SumFlwZone1SumFlow for Exh.Flow Zone-1l/sRead
AI65013EA_SumFlwZone2SumFlow for Exh.Flow Zone-2l/sRead
AI65014EA_SumFlwZone3SumFlow for Exh.Flow Zone-3l/sRead
AI65015EA_SumFlwZone4SumFlow for Exh.Flow Zone-4l/sRead
AI65016EA_SumFlwZone5SumFlow for Exh.Flow Zone-5l/sRead
AI65017EA_SumFlwZone6SumFlow for Exh.Flow Zone-6l/sRead
AI65018EA_SumFlwZone7SumFlow for Exh.Flow Zone-7l/sRead
AI65019EA_SumFlwZone8SumFlow for Exh.Flow Zone-8l/sRead
AI65020EA_SumFlwZone9SumFlow for Exh.Flow Zone-9l/sRead
AI65021EA_SlaveSet_Z0FlowSet for Exh.Slave DC Zone-0l/sRead
AI65022EA_SlaveSet_Z1FlowSet for Exh.Slave DC Zone-1l/sRead
AI65023EA_SlaveSet_Z2FlowSet for Exh.Slave DC Zone-2l/sRead
AI65024EA_SlaveSet_Z3FlowSet for Exh.Slave DC Zone-3l/sRead
AI65025EA_SlaveSet_Z4FlowSet for Exh.Slave DC Zone-4l/sRead
AI65026EA_SlaveSet_Z5FlowSet for Exh.Slave DC Zone-5l/sRead
AI65027EA_SlaveSet_Z6FlowSet for Exh.Slave DC Zone-6l/sRead
AI65028EA_SlaveSet_Z7FlowSet for Exh.Slave DC Zone-7l/sRead
AI65029EA_SlaveSet_Z8FlowSet for Exh.Slave DC Zone-8l/sRead
AI65030EA_SlaveSet_Z9FlowSet for Exh.Slave DC Zone-9l/sRead
AImin65041WISE_SA_ForcPaWISE/Gold-Comm-SA-Pa Set (from WISE)PaRead
AImin65042WISE_EA_ForcPaWISE/Gold-Comm-EA-Pa Set (from WISE)PaRead
AI65043WISE_RegDeleyWISE/Gold-Comm-Reg Start Delay (from WISE)sRead
AI65044WISE_SA_MinAlrWISE/Gold-Comm SA-Press Below MinRead
AI65045WISE_EA_MinAlrWISE/Gold-Comm EA-Press Below MinRead
AI65046WISE_DamperAlrWISE/Gold-Comm Damper = 100% OpenRead
AI65047Optimize_OnOffOptimize On/Off for Gold TCPRead
AI65051OptSA_MaxPosOptimizeReg SA-Max Damper Pos%Read
AI65052OptEA_MaxPosOptimizeReg EA-Max Damper Pos%Read
AI65053OptRegTimeOutOptimize PressRegTimeOutsRead
AImin65055CoolDemandFlagFlag is on if any room needs coolingRead
AImin65056HeatDemandFlagFlag is on if any room needs HeatingRead
AI65060NetScanStatusStatus for ID-Scan. 0-100% (Wrap)%Read
AI65061NetScanFullStatus for ID-Scan. 0-100% Stop at 100%%Read
AI65062NetForceScanStatus for RC-ForceScan. 0-100% Stop at 100%%Read
AI65100Alr_GoldTcpIPAlarm for GOLD TCP/IP connection lostRead
AImin65101SumAlarmStatus for any active alarm in systemRead
AI65500FlashStateReadFlash-Card State ReadRead
AV65000YearCurrent YearWrite
AV65001MonthCurrent MonthWrite
AV65002DateCurrent DateWrite
AV65003TimeCurrent Time (Hour*60 + Minute)Write
AV65004SecCurrent SecondsWrite
AV65005AutoSummerTimeAuto switch Summer/Winter TimeWrite
AV65007CoolDemLimSetCooling Demand Limit (User Set) to set CoolDemandFlag%Write
AV65008HeatDemLimSetHeating Demand (User Set) to set HeatDemandFlag%Write
AVmin65200WISE_SA_PaWISE/Gold-Comm SA-Pa Set (from Gold)PaWrite
AVmin65201WISE_EA_PaWISE/Gold-Comm EA-Pa Set (from Gold)PaWrite
AV65202WISE_RegDelSetWISE/Gold-Comm RegDelaySet (from Gold)minWrite
AV65203WISE__SA_PaMinWISE/Gold-Comm Min Set for SA-PressRegPaWrite
AV65204WISE__SA_PaSetWISE/Gold-Comm Set for SA-PressRegPaWrite
AV65205WISE__SA_PaMaxWISE/Gold-Comm Max Set for SA-PressRegPaWrite
AV65206WISE__EA_PaMinWISE/Gold-Comm Min Set for EA-PressRegPaWrite
AV65207WISE__EA_PaSetWISE/Gold-Comm Set for EA-PressRegPaWrite
AV65208WISE__EA_PaMaxWISE/Gold-Comm Max Set for EA-PressRegPaWrite
AV65209WISE_HiDampLimWISE/Gold-Comm Hi Limit Damper Val%Write
AV65210WISE_LoDampLimWISE/Gold-Comm Lo Limit Damper Val%Write
AV65211WISE_AlrDelayWISE/Gold-Comm Reg Alarm DelayminWrite
AV65212WISE_StepSizeWISE/Gold-Comm Pa StepSize for PressRegPaWrite
AV65213WISE_GroupIntWISE/Gold-Comm GroupDelay (Interval)minWrite
AV65214WISE_AllowedDvWISE/Gold-Comm Allowed PressReg ChangePaWrite
AVmin65215WISE_DriftONWISE/Gold-Comm Reg (Drift) ONWrite
AVmin65216WISE_FireAlarmWISE/Gold-Comm FireAlarmWrite
AV65217WISE_SumNightWISE/Gold-Comm SummerNightWrite
AVmin65221AlarmResetAlarm Reset (AutoReturn to zero)Write
AV65224RC_ForceScanScan RC-Net now (AutoReturn to zero)Write
AV65225Reboot1 -> Reboot ServerWrite
AV65240AlarmBlockageBlockage of Alarms related to AHU when AHU is offWrite
AV65241AlarmShowA_B0 = show A and B alarms; 1/2 = only A (history/room view)Write
AV65242AlarmClear0 = don't clear, 1 = clear reset alarms, 2 = clear allWrite
Object ID lookup: Swegon SuperWISE point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SuperWISE (generation 1) BACnet IP - system objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Swegon SuperWISE (generation 1) BACnet IP - system objects

How many BACnet points does the Swegon SuperWISE (generation 1) BACnet IP - system objects have?

This list has 81 BACnet objects: 49 analog inputs, 32 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Swegon SuperWISE (generation 1) BACnet IP - system objects BACnet points are writable?

32 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Swegon SuperWISE (generation 1) BACnet IP - system objects BACnet documentation?

The source is SuperWISE BACnet list ver 1.3 (BACnet IP, Super WISE program version 1.25), in SuperWISE BACnet PICS gen 1 zip (GB.BACnetSuper WISE.140603), revision 2014-06-03, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/flow-control/wise/_multi/superwise-bacnet-pics_gen1.zip.

What are the minimum BACnet points to integrate the Swegon SuperWISE (generation 1) BACnet IP - system objects?

Start with AV 65215 WISE_DriftON (Write 1 while the AHU runs, 0 when stopped); AV 65216 WISE_FireAlarm (Fire alarm; 1 forces all regulators to emergency mode); AV 65200 WISE_SA_Pa (Real supply duct pressure from the AHU, Pa); AV 65201 WISE_EA_Pa (Real extract duct pressure from the AHU, Pa); AV 65221 AlarmReset (Alarm reset (returns to 0)); AI 65041 WISE_SA_ForcPa (Requested supply duct pressure for the AHU, Pa); AI 65042 WISE_EA_ForcPa (Requested extract duct pressure for the AHU, Pa); AI 65055 CoolDemandFlag (Any room needs cooling); AI 65056 HeatDemandFlag (Any room needs heating); AI 65101 SumAlarm (Any active alarm).

How do I enable BMS control of the Swegon SuperWISE (generation 1) BACnet IP - system objects?

BACnet IP must be switched on in the SuperWISE Admin/Misc tab before the objects respond.

How do I check these points on the real SuperWISE (generation 1) BACnet IP - system objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Swegon BACnet points lists

Source: SuperWISE BACnet list ver 1.3 (BACnet IP, Super WISE program version 1.25), in SuperWISE BACnet PICS gen 1 zip · GB.BACnetSuper WISE.140603 · rev. 2014-06-03. Object names, instances and units are reproduced as published; descriptions are our own.