 "manufacturer": "Swegon",
 "manufacturer_slug": "swegon",
 "model": "SuperWISE (generation 1) BACnet IP - system objects",
 "model_slug": "superwise-gen1-bacnet-ip-system",
 "aliases": [
  "SuperWISE",
  "Super WISE",
  "WISE gen 1",
  "GB.BACnetSuper WISE.140603",
  "SuperWISE_BACnet_list_ver_1.3"
 ],
 "equipment_type": "Other equipment (demand-controlled ventilation system controller)",
 "applies_to": "Swegon SuperWISE (first generation) system controllers for WISE demand-controlled ventilation, program version 1.25.",
 "summary": "SuperWISE gen 1 is the system controller of Swegon's WISE demand-controlled ventilation system and acts as a BACnet IP server (B-ASC) on its Ethernet port. Its EDE workbook gives fixed system objects (instances 65000 and up): summed supply/extract airflow per zone, the duct-pressure optimisation link to the GOLD air handler, demand flags, alarms, clock and commands. Room, damper and router objects come from per-product sheets whose instances are calculated from the zone, damper and room numbers.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "SuperWISE program version 1.25 (BACnet list ver. 1.3, 2014)",
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "Taken from the LOCAL sheet of SuperWISE_BACnet_list_ver_1.3.xls in Swegon's SuperWISE gen 1 BACnet zip (EDE layout). The sheet gives no settable column, so access is inferred: AVs as writable, AIs as read-only.",
  "The workbook's per-product sheets (CONTROL Za, Router, CONTROL Ra A3/A4, W1/W3/W4, ADAPT Master/Slave/WBCS, A1) calculate instances from zone (0-9), damper or branch (1-8) and room (1-60) numbers; those objects are not listed here.",
  "The Optimize sheet in the same workbook repeats some LOCAL objects but shows CoolDemandFlag/HeatDemandFlag at 65054/65055 instead of 65055/65056; the LOCAL sheet values are used.",
  "AI and AV objects share some instance numbers (65000-65005); they are different objects."
 ],
 "integration": {
  "summary": "Read the per-zone summed airflows and SumAlarm (AI 65101) and the cooling/heating demand flags. The AV 65200 range is the pressure-optimisation link with the air handler: the AHU (or BMS) writes the real SA/EA pressures and running state, and SuperWISE returns the requested pressures (AI 65041/65042).",
  "minimum_points": [
   {
    "ref": "AV 65215",
    "name": "WISE_DriftON",
    "why": "Write 1 while the AHU runs, 0 when stopped"
   },
   {
    "ref": "AV 65216",
    "name": "WISE_FireAlarm",
    "why": "Fire alarm; 1 forces all regulators to emergency mode"
   },
   {
    "ref": "AV 65200",
    "name": "WISE_SA_Pa",
    "why": "Real supply duct pressure from the AHU, Pa"
   },
   {
    "ref": "AV 65201",
    "name": "WISE_EA_Pa",
    "why": "Real extract duct pressure from the AHU, Pa"
   },
   {
    "ref": "AV 65221",
    "name": "AlarmReset",
    "why": "Alarm reset (returns to 0)"
   },
   {
    "ref": "AI 65041",
    "name": "WISE_SA_ForcPa",
    "why": "Requested supply duct pressure for the AHU, Pa"
   },
   {
    "ref": "AI 65042",
    "name": "WISE_EA_ForcPa",
    "why": "Requested extract duct pressure for the AHU, Pa"
   },
   {
    "ref": "AI 65055",
    "name": "CoolDemandFlag",
    "why": "Any room needs cooling"
   },
   {
    "ref": "AI 65056",
    "name": "HeatDemandFlag",
    "why": "Any room needs heating"
   },
   {
    "ref": "AI 65101",
    "name": "SumAlarm",
    "why": "Any active alarm"
   }
  ],
  "enable": "BACnet IP must be switched on in the SuperWISE Admin/Misc tab before the objects respond.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP on the Ethernet port (E), directly or through a switch; settings in SuperWISE Admin/Misc.",
   "Read input register (relative address 2) of a room controller to see which product sheet applies (8 CONTROL Za, 13 Router, 6 CONTROL Ra A3, 10 W4, 1 W3, 2 W1, 11/12/15 ADAPT)."
  ],
  "gotchas": [
   "AlarmReset, RC_ForceScan and Reboot (AV 65221/65224/65225) are one-shot commands; AV 65225 = 1 reboots the server.",
   "AlarmClear (AV 65242) can delete the alarm history; 2 clears all."
  ]
 },
 "source": {
  "title": "SuperWISE BACnet list ver 1.3 (BACnet IP, Super WISE program version 1.25), in SuperWISE BACnet PICS gen 1 zip",
  "doc_number": "GB.BACnetSuper WISE.140603",
  "revision_date": "2014-06-03",
  "url": "https://www.swegon.com/siteassets/_products-documents-archive/flow-control/wise/_multi/superwise-bacnet-pics_gen1.zip"
 },
 "points": [
  {
   "type": "AI",
   "instance": 65000,
   "name": "SuperWISE_SW",
   "description": "SuperWISE-Software-Ver",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65001,
   "name": "SA_SumFlwZone0",
   "description": "SumFlow for Sup.Flow Zone-0",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65002,
   "name": "SA_SumFlwZone1",
   "description": "SumFlow for Sup.Flow Zone-1",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65003,
   "name": "SA_SumFlwZone2",
   "description": "SumFlow for Sup.Flow Zone-2",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65004,
   "name": "SA_SumFlwZone3",
   "description": "SumFlow for Sup.Flow Zone-3",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65005,
   "name": "SA_SumFlwZone4",
   "description": "SumFlow for Sup.Flow Zone-4",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65006,
   "name": "SA_SumFlwZone5",
   "description": "SumFlow for Sup.Flow Zone-5",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65007,
   "name": "SA_SumFlwZone6",
   "description": "SumFlow for Sup.Flow Zone-6",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65008,
   "name": "SA_SumFlwZone7",
   "description": "SumFlow for Sup.Flow Zone-7",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65009,
   "name": "SA_SumFlwZone8",
   "description": "SumFlow for Sup.Flow Zone-8",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65010,
   "name": "SA_SumFlwZone9",
   "description": "SumFlow for Sup.Flow Zone-9",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65011,
   "name": "EA_SumFlwZone0",
   "description": "SumFlow for Exh.Flow Zone-0",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65012,
   "name": "EA_SumFlwZone1",
   "description": "SumFlow for Exh.Flow Zone-1",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65013,
   "name": "EA_SumFlwZone2",
   "description": "SumFlow for Exh.Flow Zone-2",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65014,
   "name": "EA_SumFlwZone3",
   "description": "SumFlow for Exh.Flow Zone-3",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65015,
   "name": "EA_SumFlwZone4",
   "description": "SumFlow for Exh.Flow Zone-4",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65016,
   "name": "EA_SumFlwZone5",
   "description": "SumFlow for Exh.Flow Zone-5",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65017,
   "name": "EA_SumFlwZone6",
   "description": "SumFlow for Exh.Flow Zone-6",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65018,
   "name": "EA_SumFlwZone7",
   "description": "SumFlow for Exh.Flow Zone-7",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65019,
   "name": "EA_SumFlwZone8",
   "description": "SumFlow for Exh.Flow Zone-8",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65020,
   "name": "EA_SumFlwZone9",
   "description": "SumFlow for Exh.Flow Zone-9",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65021,
   "name": "EA_SlaveSet_Z0",
   "description": "FlowSet for Exh.Slave DC Zone-0",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65022,
   "name": "EA_SlaveSet_Z1",
   "description": "FlowSet for Exh.Slave DC Zone-1",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65023,
   "name": "EA_SlaveSet_Z2",
   "description": "FlowSet for Exh.Slave DC Zone-2",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65024,
   "name": "EA_SlaveSet_Z3",
   "description": "FlowSet for Exh.Slave DC Zone-3",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65025,
   "name": "EA_SlaveSet_Z4",
   "description": "FlowSet for Exh.Slave DC Zone-4",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65026,
   "name": "EA_SlaveSet_Z5",
   "description": "FlowSet for Exh.Slave DC Zone-5",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65027,
   "name": "EA_SlaveSet_Z6",
   "description": "FlowSet for Exh.Slave DC Zone-6",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65028,
   "name": "EA_SlaveSet_Z7",
   "description": "FlowSet for Exh.Slave DC Zone-7",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65029,
   "name": "EA_SlaveSet_Z8",
   "description": "FlowSet for Exh.Slave DC Zone-8",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65030,
   "name": "EA_SlaveSet_Z9",
   "description": "FlowSet for Exh.Slave DC Zone-9",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65041,
   "name": "WISE_SA_ForcPa",
   "description": "WISE/Gold-Comm-SA-Pa Set (from WISE)",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65042,
   "name": "WISE_EA_ForcPa",
   "description": "WISE/Gold-Comm-EA-Pa Set (from WISE)",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65043,
   "name": "WISE_RegDeley",
   "description": "WISE/Gold-Comm-Reg Start Delay (from WISE)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65044,
   "name": "WISE_SA_MinAlr",
   "description": "WISE/Gold-Comm SA-Press Below Min",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65045,
   "name": "WISE_EA_MinAlr",
   "description": "WISE/Gold-Comm EA-Press Below Min",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65046,
   "name": "WISE_DamperAlr",
   "description": "WISE/Gold-Comm Damper = 100% Open",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65047,
   "name": "Optimize_OnOff",
   "description": "Optimize On/Off for Gold TCP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65051,
   "name": "OptSA_MaxPos",
   "description": "OptimizeReg SA-Max Damper Pos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65052,
   "name": "OptEA_MaxPos",
   "description": "OptimizeReg EA-Max Damper Pos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65053,
   "name": "OptRegTimeOut",
   "description": "Optimize PressRegTimeOut",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65055,
   "name": "CoolDemandFlag",
   "description": "Flag is on if any room needs cooling",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65056,
   "name": "HeatDemandFlag",
   "description": "Flag is on if any room needs Heating",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65060,
   "name": "NetScanStatus",
   "description": "Status for ID-Scan. 0-100% (Wrap)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65061,
   "name": "NetScanFull",
   "description": "Status for ID-Scan. 0-100% Stop at 100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65062,
   "name": "NetForceScan",
   "description": "Status for RC-ForceScan. 0-100% Stop at 100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65100,
   "name": "Alr_GoldTcpIP",
   "description": "Alarm for GOLD TCP/IP connection lost",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65101,
   "name": "SumAlarm",
   "description": "Status for any active alarm in system",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65500,
   "name": "FlashStateRead",
   "description": "Flash-Card State Read",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65000,
   "name": "Year",
   "description": "Current Year",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65001,
   "name": "Month",
   "description": "Current Month",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65002,
   "name": "Date",
   "description": "Current Date",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65003,
   "name": "Time",
   "description": "Current Time (Hour*60 + Minute)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65004,
   "name": "Sec",
   "description": "Current Seconds",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65005,
   "name": "AutoSummerTime",
   "description": "Auto switch Summer/Winter Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65007,
   "name": "CoolDemLimSet",
   "description": "Cooling Demand Limit (User Set) to set CoolDemandFlag",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65008,
   "name": "HeatDemLimSet",
   "description": "Heating Demand (User Set) to set HeatDemandFlag",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65200,
   "name": "WISE_SA_Pa",
   "description": "WISE/Gold-Comm SA-Pa Set (from Gold)",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65201,
   "name": "WISE_EA_Pa",
   "description": "WISE/Gold-Comm EA-Pa Set (from Gold)",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65202,
   "name": "WISE_RegDelSet",
   "description": "WISE/Gold-Comm RegDelaySet (from Gold)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65203,
   "name": "WISE__SA_PaMin",
   "description": "WISE/Gold-Comm Min Set for SA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65204,
   "name": "WISE__SA_PaSet",
   "description": "WISE/Gold-Comm Set for SA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65205,
   "name": "WISE__SA_PaMax",
   "description": "WISE/Gold-Comm Max Set for SA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65206,
   "name": "WISE__EA_PaMin",
   "description": "WISE/Gold-Comm Min Set for EA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65207,
   "name": "WISE__EA_PaSet",
   "description": "WISE/Gold-Comm Set for EA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65208,
   "name": "WISE__EA_PaMax",
   "description": "WISE/Gold-Comm Max Set for EA-PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65209,
   "name": "WISE_HiDampLim",
   "description": "WISE/Gold-Comm Hi Limit Damper Val",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65210,
   "name": "WISE_LoDampLim",
   "description": "WISE/Gold-Comm Lo Limit Damper Val",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65211,
   "name": "WISE_AlrDelay",
   "description": "WISE/Gold-Comm Reg Alarm Delay",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65212,
   "name": "WISE_StepSize",
   "description": "WISE/Gold-Comm Pa StepSize for PressReg",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65213,
   "name": "WISE_GroupInt",
   "description": "WISE/Gold-Comm GroupDelay (Interval)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65214,
   "name": "WISE_AllowedDv",
   "description": "WISE/Gold-Comm Allowed PressReg Change",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65215,
   "name": "WISE_DriftON",
   "description": "WISE/Gold-Comm Reg (Drift) ON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65216,
   "name": "WISE_FireAlarm",
   "description": "WISE/Gold-Comm FireAlarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65217,
   "name": "WISE_SumNight",
   "description": "WISE/Gold-Comm SummerNight",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65221,
   "name": "AlarmReset",
   "description": "Alarm Reset (AutoReturn to zero)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65224,
   "name": "RC_ForceScan",
   "description": "Scan RC-Net now (AutoReturn to zero)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65225,
   "name": "Reboot",
   "description": "1 -> Reboot Server",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65240,
   "name": "AlarmBlockage",
   "description": "Blockage of Alarms related to AHU when AHU is off",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65241,
   "name": "AlarmShowA_B",
   "description": "0 = show A and B alarms; 1/2 = only A (history/room view)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65242,
   "name": "AlarmClear",
   "description": "0 = don't clear, 1 = clear reset alarms, 2 = clear all",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/swegon/superwise-gen1-bacnet-ip-system",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}