Air handling unit controller · BACnet points list
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet points list
Updated 6 November 2026
GOLD generation C/D air handlers have a BACnet IP driver built into the unit controller (program version 6.08), acting as a B-ASC; no gateway is needed. The list covers fan airflows, pressures, levels and power, temperatures and regulator setpoints, heat exchanger and coil data, accessory functions (Xzone, ReCO2, AYC, MIRU, Blue Box, steam humidifier), time and year channels, one binary input per alarm and info number, and calibration commands. The BMS starts, stops and selects speed through one analog value.
This page lists 852 BACnet objects for the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP — 531 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- GOLD generation C/D (RX/PX/CX/SD) BACnet IP
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 852 (531 writable)
- Transport
- BACnet IP
- Firmware
- Program version 6.08 or later
- Also known as
- GOLD C, GOLD D, GOLD RX, GOLD PX, GOLD CX, GOLD SD, GOLD version D, GB.BACnet480.121017, BACnet480
Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.
BMS integration notes: Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP
Command the unit with AV 174 Communication operation mode (0 = Auto lets the time channels run it; 1-4 force stop or low/high speed) and read back AI 84 Operation mode 1 plus the low/high speed BIs. Adjust the main temperature setpoints (AV 40 supply, AV 41 extract/room) and the low/high speed airflow or pressure setpoints, and monitor BI 5/BI 6 for A/B alarms with BV 0 to reset. Page 3 of the guide lists these as the key points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 174 | Communication operation mode | BMS stop / low / high speed command (0 = Auto) | Write |
| AV 40 | SA Temperature setpoint | Supply air temperature setpoint | Write |
| AV 41 | EA/Room Temperature setpoint | Extract/room temperature setpoint | Write |
| BV 0 | Alarm reset | Resets alarms | Write |
| AI 84 | Operation mode 1 | Actual operating mode and what stopped the unit | Read |
| AI 27 | SA Temperature | Supply air temperature | Read |
| AI 28 | EA/Room temperature | Extract/room temperature | Read |
| AI 29 | Outdoor temperature | Outdoor air temp measured by the unit, °C | Read |
| BI 5 | A-alarm. | Any A-class alarm | Read |
| BI 6 | B-alarm. | Any B-class alarm | Read |
Enable & remote start
AV 174 Communication operation mode: 0=Auto (normal stop when the time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (PV 5.00 or later; intermittent night heat and morning boost still work). AI 84 Operation mode 1 shows whether the unit is stopped or running from the hand terminal, an external input, communication or a time/year channel.
Sensors & values from the BMS
Room temperature can come from the BMS: set AV 200 EA/Room temperature external func. to 2 (Communication) and write AV 201. Outdoor temperature works the same with AV 202 = 2 and AV 203. AV 204 sets the timeout for these communicated temperatures.
Network setup
- BACnet IP only; the device is a B-ASC. Swegon also publishes a BACnet PICS and an EDE file for GOLD.
- Device instance and IP settings are not given in this document.
Watch out for
- Setpoints are split by low and high speed (e.g. AV 0/1 SA airflow, AV 8/9 SA duct pressure); write the one for the active speed.
- BV 42-73 start pressure-sensor zero calibration or set it to manual mode; do not write them from routine BMS logic.
- Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is installed.
- The time channel status objects (AV 130, 135, ... 165) use 0-10 for low speed days and 16-26 for high speed days.
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | SA Airflow | Range 0-20000l/s | l/s | Read | |
| AI | 1 | SA Airflow regulator | Present supply airflow regulator setpoint. Range 0-20000l/s | l/s | Read | |
| AI | 2 | EA Airflow | Present extract airflow. Range 0-20000l/s | l/s | Read | |
| AI | 3 | EA Airflow regulator | Present extract airflow regulator setpoint. Range 0-20000l/s | l/s | Read | |
| AI | 4 | SA Duct pressure | Present supply air duct pressure. Range 0-2000Pa | Pa | Read | |
| AI | 5 | SA Duct pressure regulator | Present supply air duct pressure regulator setpoint. Range 0-2000Pa | Pa | Read | |
| AI | 6 | EA Duct pressure | Present extract air duct pressure. Range 0-2000Pa | Pa | Read | |
| AI | 7 | EA Duct pressure regulator | Present extract air duct pressure regulator setpoint. Range 0-2000Pa | Pa | Read | |
| AI | 8 | SA VAV demand/boost input | Range 0-100.00% | % | Read | |
| AI | 9 | SA VAV demand regulator | Present supply air VAV demand regulator setpoint. Range 0-100.00% | % | Read | |
| AI | 10 | EA VAV demand/boost input | Range 0-100.00% | % | Read | |
| AI | 11 | EA VAV demand regulator | Present supply air VAV demand regulator setpoint. Range 0-100.00% | % | Read | |
| AI | 12 | SA Fan level | Present running level for the supply air fan. Range 0-100.00% | % | Read | |
| AI | 13 | EA Fan level | Present running level for the extract air fan. Range 0-100.00% | % | Read | |
| AI | 14 | SA Fan power | Range 0-32700W (from PV 6.04) | W | Read | |
| AI | 15 | EA Fan power | Range 0-32700W (from PV 6.04) | W | Read | |
| AI | 16 | SFP | SFP supply air + extract air. Range 0.0-9.9 | Read | ||
| AI | 17 | SA Frequency | Present frequency level for the supply air fan. Range 0-100.00Hz | Hz | Read | |
| AI | 18 | EA Frequency | Present frequency level for the extract air fan. Range 0-100.00Hz | Hz | Read | |
| AI | 19 | SA Voltage | Present voltage level for the supply air fan. Range 0-500V | V | Read | |
| AI | 20 | EA Voltage | Present voltage level for the extract air fan. Range 0-500V | V | Read | |
| AI | 21 | SA Current | Range 0-32.700A (from PV 6.04) | A | Read | |
| AI | 22 | EA Current | Range 0-32.700A (from PV 6.04) | A | Read | |
| AI | 23 | SA Airflow pressure | Present airflow pressure in the supply air fan inlet. Range 0-2000Pa | Pa | Read | |
| AI | 24 | EA Airflow pressure | Present airflow pressure inthe extract airfan inlet. Range 0-2000Pa | Pa | Read | |
| AI | 25 | SA Temp regulator | Present supply air temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 26 | EA Temp regulator | Present extract air temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AImin | 27 | SA Temperature | Present supply air temperature. Range -55.00-125.00°C | °C | Read | |
| AImin | 28 | EA/Room temperature | Present extract air/room temperature in the unit. Range -55.00-125.00°C | °C | Read | |
| AImin | 29 | Outdoor temperature | Present outdoor air temperature in the unit. Range -55.00-125.00°C | °C | Read | |
| AI | 30 | EA/Room temperature external | Present room temperature external from the unit. Range -55.00-125.00°C | °C | Read | |
| AI | 31 | Outdoor temperature external | Present outdoor air temperature external from the unit. Range -55.00-125.00°C | °C | Read | |
| AI | 32 | Anti frost temperature | Range -55.00-125.00°C | °C | Read | |
| AI | 33 | Temperature sensor 3 | Present temperature for temp sensor no.3. Range -55.00-125.00°C | °C | Read | |
| AI | 34 | Temperature sensor 4 | Present temperature for temp sensor no.4. Range -55.00-125.00°C | °C | Read | |
| AI | 35 | Rotary heat exchanger level | Present operation level from rotary heat exchanger. Range 0-100.00% | % | Read | |
| AI | 36 | Reheat level | Present level of reheat. Range 0-100.00% | % | Read | |
| AI | 37 | SA Down regulation level | Present level of supply airflow down regulation. Range 0-100.00% | % | Read | |
| AI | 38 | Extra regulation sequence level | Present level of the extra regulation sequence. Range 0-100.00% | % | Read | |
| AI | 39 | Cooling level | Present level of cooling. Range 0-100.00% | % | Read | |
| AI | 40 | Heating boost level | Present level of heating boost. Range 0-100.00% | % | Read | |
| AI | 41 | Cooling boost level | Present level of cooling boost. Range 0-100.00% | % | Read | |
| AI | 42 | HX pressure level | Present pressure drop for the rotary heat exchanger. Range 0-2000Pa | Pa | Read | |
| AI | 43 | HX pressure alarm limit | Range 0-2000Pa | Pa | Read | |
| AI | 44 | HX temperature | Range 0-100.00°C | °C | Read | |
| AI | 45 | Effect reduction level | Range 0-100.00% | % | Read | |
| AI | 46 | Anti frost temp setpoint/operation | Range 10.00-16.00°C | °C | Read | |
| AI | 47 | Anti frost temp setpoint/stop | Range 15.00-40.00°C | °C | Read | |
| AI | 48 | Anti frost temp alarm limit | Range 5.00-30.00°C | °C | Read | |
| AI | 49 | Supply air filter pressure level | Present supply air filter pressure drop. Range 0-2000Pa | Pa | Read | |
| AI | 50 | Supply air filter pressure alarm limit. | Present supply air filter pressure alarm limit. Range 0-2000Pa | Pa | Read | |
| AI | 51 | Supply air filter pressure level, new | Supply air filter pressure saved from calibration. Range 0-2000Pa | Pa | Read | |
| AI | 52 | Extract air filter pressure level | Present extract air filter pressure drop. Range 0-2000Pa | Pa | Read | |
| AI | 53 | Extract air filter pressure alarm limit. | Present extract air filter pressure alarm limit. Range 0-2000Pa | Pa | Read | |
| AI | 54 | Extract air filter pressure level, new | Extract air filter pressure saved from calibration. Range 0-2000Pa | Pa | Read | |
| AI | 55 | Temperature displacement | Present temperature displacement from input signal. Range -5.00 - 5.00°C | °C | Read | |
| AI | 56 | Coil type | Range 0-20 | Read | ||
| AI | 57 | Cool step time | Present time between cool step shift. Range 0-600s | s | Read | |
| AI | 58 | Cool relay 1 restart time | Present time between two starts of cool relay 1. Range 0-900s | s | Read | |
| AI | 59 | Cool relay 2 restart time | Present time between two starts of cool relay 2. Range 0-900s | s | Read | |
| AI | 60 | Program version, HMI | Present program version for the hand terminal. Range 0-10.00 | Read | ||
| AI | 61 | Program version, HMl-slave | Present program version for the extra hand terminal. Range 0-10.00 | Read | ||
| AI | 62 | Program version, main controller. | Present program version for the main control unit. Range 0-10.00 | Read | ||
| AI | 63 | Program version, SA FC-1. | Range 0-10.00 | Read | ||
| AI | 64 | Program version, SA FC-2. | Range 0-10.00 | Read | ||
| AI | 65 | Program version, EA FC-1. | Range 0-10.00 | Read | ||
| AI | 66 | Program version, EA FC-2. | Range 0-10.00 | Read | ||
| AI | 67 | Program version, HX control unit | Range 0-10.00 | Read | ||
| AI | 68 | Weekday | Range 0-6 | Read | ||
| AI | 69 | Extended low speed op. Hours | Present time for extended low speed operation. Range 0-23 | Read | ||
| AI | 70 | Extended low speed op. Minutes | Present time for extended low speed operation. Range 0-59 | Read | ||
| AI | 71 | Extended high speed op. Hours | Present time for extended high speed operation. Range 0-23 | Read | ||
| AI | 72 | Extended high speed op. Minutes | Present time for extended high speed operation. Range 0-59 | Read | ||
| AI | 73 | SA Fan operation time | Range 0-9999 | Read | ||
| AI | 74 | EA Fan operation time | Range 0-9999 | Read | ||
| AI | 75 | Cool operation time | Range 0-9999 | Read | ||
| AI | 76 | Heat exchange operation time | Range 0-9999 | Read | ||
| AI | 77 | Reheat operation time | Range 0-9999 | Read | ||
| AI | 78 | Present tripped alarm | Present tripped alarm number with highest priority. Range 0-200 | Read | ||
| AI | 79 | Active not tripped alarm no.1 | Present active alarm in delay. Range 0-200 | Read | ||
| AI | 80 | Active not tripped alarm no.2 | Present active alarm in delay. Range 0-200 | Read | ||
| AI | 81 | Active not tripped alarm no.3 | Present active alarm in delay. Range 0-200 | Read | ||
| AI | 82 | SA Fan size | Present supply air fan size. Range 04 - 120 | Read | ||
| AI | 83 | EA Fan size | Present extract air fan size. Range 04 - 120 | Read | ||
| AImin | 84 | Operation mode 1 | Range 0-18 | Read | 0=Manual stop, 1=Ext. stop, 2=Com. stop 1, 3=Manual high speed, 4=Summer night cooling, 5=Int. night heat, 6=Manual low speed, 7=Ext. high speed, 8=Com. high speed, 9=Year channel stop, 10=Year channel high speed, 11=Year channel low speed, 12=Time channel high speed, 13=Ext. low speed, 14=Com. low speed, 15=Time channel low speed, 16=Time channel stop, 17=Low speed=stop, 18=Com. stop 2. (New in PV 5.00) | |
| AI | 85 | Operation mode 2 | Range 0 - 22 | Read | 0=, 1=Cold air recovery, 2=Cooling boost, 3=SA down regulation, 4=HX defrosting, 5=Anti frost func. active, 6=Effect reduction, 7=Startup, 8=Zero calibration, 9=Extended low speed, 10=Extended high speed, 11=Air adjustment, 12=Cooling off, 13=Purging R.HX, 14=Extended R.HX. op, 15=Filter calibration, 16=R.HX. calibration, 17=Morning boost, 18=Heating boost, 19=Alarm, 20=CoolDX pressure reduction. (PV 2.00), 21=Startup extract air fan (New in 4.00), 22=Fan heat retention (New in PV 5.00) | |
| AI | 86 | Operation mode, manual | Present manual operation set on the unit's hand terminal. Range 0-3 | Read | 0=Stop, 1=Auto operation, 2=Manual low speed, 3=Manual high speed | |
| AI | 87 | Copy of Input Status 1-16. | Range 0-65535 | Read | ||
| AI | 88 | Copy of Input Status 17-32. | Range 0-65535 | Read | ||
| AI | 89 | Copy of Input Status 33-48. | Range 0-65535 | Read | ||
| AI | 90 | Heat exchanger regulator | Present level of heat exchanger regulator RX/CX/PX. Range 0-100.00% | % | Read | |
| AI | 91 | Extract air-humidity | Present level of extract air-humidity. Range 0-100.00% | % | Read | |
| AI | 92 | Extract air-humidity temperature | Present temperature inside extract air-humidity sensor. Range -55.00-125.00°C | °C | Read | |
| AI | 93 | Extract air-dewpoint | Calculated extract air-dewpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 94 | AYC chilled water temperature | Present AYC chilled water temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 95 | AYC chilled water temperature regulator | Present AYC chilled water temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 96 | AYC chilled water output | Present level of AYC chilled water valve output. Range 0-100.00% | % | Read | |
| AI | 97 | Supply air-dewpoint regulator | Present supply air-dewpoint regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 98 | Supply air-humidity | Present level of supply air-humidity. Range 0-100.00% | % | Read | |
| AI | 99 | Supply air-humidity temperature | Present temperature inside supply air-humidity sensor. Range -55.00-125.00°C | °C | Read | |
| AI | 100 | Supply air-dewpoint | Calculated supply air-dewpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 101 | C.HX. Temperature | Present temperature of coil heat exchanger. Range -55.00-125.00°C | °C | Read | |
| AI | 102 | P.HX. Temperature 1 | Present temperature 1 of plate heat exchanger. Range -55.00-125.00°C | °C | Read | |
| AI | 103 | P.HX. Temperature 2 | Present temperature 2 of plate heat exchanger. Range -55.00-125.00°C | °C | Read | |
| AI | 104 | P/C.HX. Humidity | Present level of air-humidity in plate/coil heat exchanger. Range 0-100.00% | % | Read | |
| AI | 105 | R.HX. Efficiency | Calculated level of rotary heat exchanger efficiency. Range 0-100.00% | % | Read | |
| AI | 106 | C.HX. Valve output | Present level of coil heat exchanger valve output. Range 0-100.00% | % | Read | |
| AI | 107 | P.HX bypass output | Present level of plate heat exchanger bypass output. Range 0-100.00% | % | Read | |
| AI | 108 | Supply air pre-filter pressure level | Present supply air pre-filter pressure drop. Range 0-2000Pa | Pa | Read | |
| AI | 109 | Supply air pre-filter pressure alarm limit. | Present supply air pre-filter pressure alarm limit. Range 0-2000Pa | Pa | Read | |
| AI | 110 | Supply air pre-filter pressure level, new | Supply air pre-filter pressure saved from calibration. Range 0-2000Pa | Pa | Read | |
| AI | 111 | Extract air pre-filter pressure level | Present extract air pre-filter pressure drop. Range 0-2000Pa | Pa | Read | |
| AI | 112 | Extract air pre-filter pressure alarm limit. | Present extract air pre-filter pressure alarm limit. Range 0-2000Pa | Pa | Read | |
| AI | 113 | Extract air pre-filter pressure level, new | Extract air pre-filter pressure saved from calibration. Range 0-2000Pa | Pa | Read | |
| AI | 114 | Xzone reheat level | Present level of Xzone reheat. Range 0-100.00% | % | Read | |
| AI | 115 | Xzone anti frost temperature | Range -55.00-125.00°C | °C | Read | |
| AI | 116 | Xzone cooling level | Present level of Xzone cooling. Range 0-100.00% | % | Read | |
| AI | 117 | Xzone cool step time | Present time between Xzone cool step shift. Range 0-600s | s | Read | |
| AI | 118 | Xzone cool relay 1 restart time | Present time between two starts of Xzone cool relay 1. Range 0-900s | s | Read | |
| AI | 119 | Xzone cool relay 2 restart time | Present time between two starts of Xzone cool relay 2. Range 0-900s | s | Read | |
| AI | 120 | Xzone SA Temp regulator | Present Xzone supply air temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 121 | Xzone EA Temp regulator | Present Xzone extract air temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 122 | Xzone SA Temperature | Present Xzone supply air temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 123 | Xzone EA/Room temperature | Present Xzone extract air/room temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 124 | Pre-heating air temperature | Present pre-heating air temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 125 | Pre-heating level | Present level of pre-heating. Range 0-100.00% | % | Read | |
| AI | 126 | Pre-heating anti frost temperature | Present anti frost temperature for water pre-heating coils. Range -55.00-125.00°C | °C | Read | |
| AI | 127 | ReCO2 CO2 input | Present input signal for ReCO2 CO2. Range 0-100.00% | % | Read | |
| AI | 128 | ReCO2 internal damper output | Present output signal for ReCO2 internal damper. Range 0-100.00% | % | Read | |
| AI | 129 | ReCO2 external damper output | Present output signal for ReCO2 external damper. Range 0-100.00% | % | Read | |
| AI | 130 | ReCO2 outdoor airflow | Present ReCO2 outdoor airflow. Range 0-20000l/s | l/s | Read | |
| AI | 131 | ReCO2 outdoor airflow regulator | Present ReCO2 outdoor airflow regulator setpoint. Range 0-20000l/s | l/s | Read | |
| AI | 132 | ReCO2 outdoor airflow pressure | Present ReCO2 outdoor airflow pressure. Range 0-2000Pa | Pa | Read | |
| AI | 133 | Preheat operation time | Range 0-9999 | Read | ||
| AI | 134 | Xzone cool operation time | Range 0-9999 | Read | ||
| AI | 135 | Xzone reheat operation time | Range 0-9999 | Read | ||
| AI | 136 | Supply air-D temperature | Range -55.00-125.00°C | °C | Read | |
| AI | 137 | Extract air-D temperature | Present extract air-D temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 138 | AYC heat temperature | Present AYC heat temperature. Range -55.00-125.00°C | °C | Read | |
| AI | 139 | AYC heat temp regulator | Present AYC heat temperature regulator setpoint. Range -55.00-125.00°C | °C | Read | |
| AI | 140 | AYC heat valve output | Present level of AYc heat valve output. Range 0-100.00% | % | Read | |
| AI | 141 | Min/Max/Average Sens1Temp | Present Min/Max/Average sensor 1 temperature. Range -55.00-125.00°C (from PV 5.15) | °C | Read | |
| AI | 142 | Min/Max/Average Sens2Temp | Present Min/Max/Average sensor 2 temperature. Range -55.00-125.00°C (from PV 5.15) | °C | Read | |
| AI | 143 | Min/Max/Average Sens3Temp | Present Min/Max/Average sensor 3 temperature. Range -55.00-125.00°C (from PV 5.15) | °C | Read | |
| AI | 144 | Min/Max/Average Sens4Temp | Present Min/Max/Average sensor 4 temperature. Range -55.00-125.00°C (from PV 5.15) | °C | Read | |
| AI | 145 | Miru 1 Airflow | Present Miru 1 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 146 | Miru 1 Airflow regulator | Present Miru 1 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 147 | Miru 1 Pressure | Present Miru 1 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 148 | Miru 1 Pressure regulator | Present Miru 1 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 149 | Miru 1 Outdoor temperature | Present Miru 1 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 150 | Miru 1 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 151 | Miru 1 Fan level | Present running level for the Miru 1 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 152 | Miru 1 Fan power | Present power consumption level for the Miru 1 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 153 | Miru 1 SFP | SFP value for Miru 1 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 154 | Miru 1 KWH | KWH value for Miru 1 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 155 | Miru 1 MWH | MWH value for Miru 1 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 156 | Miru 2 Airflow | Present Miru 2 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 157 | Miru 2 Airflow regulator | Present Miru 2 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 158 | Miru 2 Pressure | Present Miru 2 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 159 | Miru 2 Pressure regulator | Present Miru 2 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 160 | Miru 2 Outdoor temperature | Present Miru 2 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 161 | Miru 2 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 162 | Miru 2 Fan level | Present running level for the Miru 2 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 163 | Miru 2 Fan power | Present power consumption level for the Miru 2 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 164 | Miru 2 SFP | SFP value for Miru 2 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 165 | Miru 2 KWH | KWH value for Miru 2 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 166 | Miru 2 MWH | MWH value for Miru 2 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 167 | Miru 3 Airflow | Present Miru 3 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 168 | Miru 3 Airflow regulator | Present Miru 3 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 169 | Miru 3 Pressure | Present Miru 3 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 170 | Miru 3 Pressure regulator | Present Miru 3 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 171 | Miru 3 Outdoor temperature | Present Miru 3 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 172 | Miru 3 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 173 | Miru 3 Fan level | Present running level for the Miru 3 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 174 | Miru 3 Fan power | Present power consumption level for the Miru 3 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 175 | Miru 3 SFP | SFP value for Miru 3 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 176 | Miru 3 KWH | KWH value for Miru 3 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 177 | Miru 3 MWH | MWH value for Miru 3 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 178 | Miru 4 Airflow | Present Miru 4 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 179 | Miru 4 Airflow regulator | Present Miru 4 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 180 | Miru 4 Pressure | Present Miru 4 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 181 | Miru 4 Pressure regulator | Present Miru 4 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 182 | Miru 4 Outdoor temperature | Present Miru 4 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 183 | Miru 4 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 184 | Miru 4 Fan level | Present running level for the Miru 4 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 185 | Miru 4 Fan power | Present power consumption level for the Miru 4 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 186 | Miru 4 SFP | SFP value for Miru 4 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 187 | Miru 4 KWH | KWH value for Miru 4 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 188 | Miru 4 MWH | MWH value for Miru 4air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 189 | Miru 5 Airflow | Present Miru 5 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 190 | Miru 5 Airflow regulator | Present Miru 5 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 191 | Miru 5 Pressure | Present Miru 5 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 192 | Miru 5 Pressure regulator | Present Miru 5 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 193 | Miru 5 Outdoor temperature | Present Miru 5 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 194 | Miru 5 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 195 | Miru 5 Fan level | Present running level for the Miru 5 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 196 | Miru 5 Fan power | Present power consumption level for the Miru 5 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 197 | Miru 5 SFP | SFP value for Miru 5 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 198 | Miru 5 KWH | KWH value for Miru 5 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 199 | Miru 5 MWH | MWH value for Miru 5 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 200 | Miru 6 Airflow | Present Miru 6 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 201 | Miru 6 Airflow regulator | Present Miru 6 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 202 | Miru 6 Pressure | Present Miru 6 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 203 | Miru 6 Pressure regulator | Present Miru 6 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 204 | Miru 6 Outdoor temperature | Present Miru 6 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 205 | Miru 6 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 206 | Miru 6 Fan level | Present running level for the Miru 6 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 207 | Miru 6 Fan power | Present power consumption level for the Miru 6 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 208 | Miru 6 SFP | SFP value for Miru 6 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 209 | Miru 6 KWH | KWH value for Miru 6 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 210 | Miru 6 MWH | MWH value for Miru 6 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 211 | Miru 7 Airflow | Present Miru 7 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 212 | Miru 7 Airflow regulator | Present Miru 7 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 213 | Miru 7 Pressure | Present Miru 7 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 214 | Miru 7 Pressure regulator | Present Miru 7 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 215 | Miru 7 Outdoor temperature | Present Miru 7 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 216 | Miru 7 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 217 | Miru 7 Fan level | Present running level for the Miru 7 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 218 | Miru 7 Fan power | Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 219 | Miru 7 SFP | SFP value for Miru 7 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 220 | Miru 7 KWH | KWH value for Miru 7 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 221 | Miru 7 MWH | MWH value for Miru 7 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 222 | Miru 8 Airflow | Present Miru 8 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 223 | Miru 8 Airflow regulator | Present Miru 8 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 224 | Miru 8 Pressure | Present Miru 8 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 225 | Miru 8 Pressure regulator | Present Miru 8 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 226 | Miru 8 Outdoor temperature | Present Miru 8 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 227 | Miru 8 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 228 | Miru 8 Fan level | Present running level for the Miru 8 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 229 | Miru 8 Fan power | Present power consumption level for the Miru 8 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 230 | Miru 8 SFP | SFP value for Miru 8 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 231 | Miru 8 KWH | KWH value for Miru 8 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 232 | Miru 8 MWH | MWH value for Miru 8 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 233 | Miru 9 Airflow | Present Miru 9 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 234 | Miru 9 Airflow regulator | Present Miru 9 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 235 | Miru 9 Pressure | Present Miru 9 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 236 | Miru 9 Pressure regulator | Present Miru 9 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 237 | Miru 9 Outdoor temperature | Present Miru 9 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 238 | Miru 9 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 239 | Miru 9 Fan level | Present running level for the Miru 9 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 240 | Miru 9 Fan power | Present power consumption level forthe Miru 9 airfan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 241 | Miru 9 SFP | SFP value for Miru 9 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 242 | Miru 9 KWH | KWH value for Miru 9 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 243 | Miru 9 MWH | MWH value for Miru 9 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 244 | Miru 10 Airflow | Present Miru 10 airflow. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 245 | Miru 10 Airflow regulator | Present Miru 10 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04) | l/s | Read | |
| AI | 246 | Miru 10 Pressure | Present Miru 10 air duct pressure. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 247 | Miru 10 Pressure regulator | Present Miru 10 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04) | Pa | Read | |
| AI | 248 | Miru 10 Outdoor temperature | Present Miru 10 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04) | °C | Read | |
| AI | 249 | Miru 10 Operation time | Range 0-9999 (from PV 6.04) | Read | ||
| AI | 250 | Miru 10 Fan level | Present running level for the Miru 10 air fan. Range 0-100.00% (from PV 6.04) | % | Read | |
| AI | 251 | Miru 10 Fan power | Present power consumption level for the Miru 10 air fan. Range 0-6000W (from PV 6.04) | W | Read | |
| AI | 252 | Miru 10 SFP | SFP value for Miru 10 air fan. Range 0.00-5.00 (from PV 6.04) | Read | ||
| AI | 253 | Miru 10 KWH | KWH value for Miru 10 air fan. Range 0-999KWH (from PV 6.04) | kWh | Read | |
| AI | 254 | Miru 10 MWH | MWH value for Miru 10 air fan. Range 0-32000MWH (from PV 6.04) | MWh | Read | |
| AI | 255 | BB Operation mode | Present Blue Box operation mode. Range 0-2 (from PV 6.05) | Read | 0=Stop, 1=Heat, 2=Cool | |
| AI | 256 | BB Cool temp regulator | Present Blue Box cool temperature regulator setpoint. Range -40.0-176.0°C (from PV 6.05) | °C | Read | |
| AI | 257 | BB Heat temp regulator | Present Blue Box heat temperature regulator setpoint. Range -40.0-176.0°C (from PV 6.05) | °C | Read | |
| AI | 258 | BB Supply water temperature | Present Blue Box supply water temperature. Range -20.0-80.0°C (from PV 6.05) | °C | Read | |
| AI | 259 | BB Return water temperature | Present Blue Box return water temperature. Range -40.0-176.0°C (from PV 6.05) | °C | Read | |
| AI | 260 | BB Supply pre-coil temperature | Present Blue Box pre-coil water temperature. Range -20.0-80.0°C (from PV 6.05) | °C | Read | |
| AI | 261 | Extended ext. reg. seq. frost temp | Present extended extra regulation sequence frost temperature. Range -55.00-125.00°C (from PV 6.07) | °C | Read | |
| AI | 262 | Extended ext. reg. seq. Output | Present extended extra regulation sequence output. Range 0-100.00% (from PV 6.07) | % | Read | |
| AI | 263 | Steam humid output | Present steam humidification output. Range 0-100.00% (from PV 6.07) | % | Read | |
| AI | 264 | End-filter pressure level | Range 0-2000Pa (from PV 6.07) | Pa | Read | |
| AI | 265 | End-filter pressure level, new | Supply air end-filter pressure saved from calibration. Range 0-2000Pa (from PV 6.07) | Pa | Read | |
| AI | 266 | End-filter pressure alarm limit | Present supply air end-filter pressure alarm limit. Range 0-2000Pa (from PV 6.07) | Pa | Read | |
| AV | 0 | SA Low speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 1 | SA High speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 2 | SA Max speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 3 | SA Min speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 4 | EA Low speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 5 | EA High speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 6 | EA Max speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 7 | EA Min speed airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 8 | SA Low speed pressure setpoint | Range 0-750Pa | Pa | Write | |
| AV | 9 | SA High speed pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 10 | SA Max speed output signal | Range 10.00-100.00% | % | Write | |
| AV | 11 | SA Max speed pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 12 | EA Low speed pressure setpoint | Range 0-750Pa | Pa | Write | |
| AV | 13 | EA High speed pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 14 | EA Max speed output signal | Range 10.00-100.00% | % | Write | |
| AV | 15 | EA Max speed pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 16 | SA Low speed demand setpoint | Range 0-100.00% | % | Write | |
| AV | 17 | SA High speed demand setpoint | Range 0-100.00% | % | Write | |
| AV | 18 | EA Low speed demand setpoint | Range 0-100.00% | % | Write | |
| AV | 19 | EA High speed demand setpoint | Range 0-100.00% | % | Write | |
| AV | 20 | SA Airflow regulation zone | Range 1.00 - 10.00 | Write | ||
| AV | 21 | SA Airflow C-factor | Supply airflow regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 22 | EA Airflow regulation zone | Range 1.00 - 10.00 | Write | ||
| AV | 23 | EA Airflow C-factor | Extract airflow regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 24 | SA Pressure regulation zone | Range 1.00 - 10.00 | Write | ||
| AV | 25 | SA Pressure C-factor | Supply air pressure regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 26 | EA Pressure regulation zone | Range 1.00 - 10.00 | Write | ||
| AV | 27 | EA Pressure C-factor | Extract air pressure regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 28 | SA Demand P-band. | Supply air demand regulator P-band setting. Range 1.00 - 100.00 | Write | ||
| AV | 29 | SA Demand C-factor | Supply air demand regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 30 | EA Demand P-band. | Extract air demand regulator P-band setting. Range 1.00 - 100.00 | Write | ||
| AV | 31 | EA Demand C-factor | Extract air demand regulator affection setting. Range 0.005 - 2.500 | Write | ||
| AV | 32 | ERS 1 Diff | Range 1.00 - 7.00°C | °C | Write | |
| AV | 33 | ERS 1 Breakpoint | Breakpoint setting according to the diagram for ERs 1. Range 12.00 - 26.00°C | °C | Write | |
| AV | 34 | ERS 2 Breakpoint X1 | Breakpoint X1 setting according to the diagram for ERs 2. Range 10.00-38.00°C | °C | Write | |
| AV | 35 | ERS 2 Breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ERs 2. Range 10.00-40.00°C | °C | Write | |
| AV | 36 | ERS 2 Breakpoint X2 | Breakpoint X2 setting according to the diagram for ERS 2. Range 11.00-39.00°C | °C | Write | |
| AV | 37 | ERS 2 Breakpoint Y2 | Range 10.00-40.00°C | °C | Write | |
| AV | 38 | ERS 2 Breakpoint X3 | Breakpoint X3setting according to the diagram forERS2. Range 12.00-40.00°C | °C | Write | |
| AV | 39 | ERS 2 Breakpoint Y3 | Range 10.00-40.00°C | °C | Write | |
| AVmin | 40 | SA Temperature setpoint | Range 10.00-40.00°C | °C | Write | |
| AVmin | 41 | EA/Room Temperature setpoint | Range 10.00-40.00°C | °C | Write | |
| AV | 42 | SA Min temp setpoint | Range 8.00-20.00°C | °C | Write | |
| AV | 43 | SA Max temp setpoint | Range 16.00-50.00°C | °C | Write | |
| AV | 44 | SA Temperature P-band | Supply air temperature regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 45 | EA/Room Temperature P-band | Range 1.00 - 40.00 | Write | ||
| AV | 46 | SA HX. Reg C-factor | Supply air heat exchange regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 47 | EA/Room HX. Reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 48 | SA Heat Reg C-factor | Supply air reheat regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 49 | EA/Room Heat Reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 50 | SA Extra Reg heat C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 51 | SA Extra Reg cool C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 52 | EA Extra Reg heat C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 53 | EA Extra Reg cool C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 54 | SA Down regulation Reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 56 | SA Cool reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 57 | EA/Room Cool reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 58 | SA Cooling boost C-factor | Range 0.000-2.500 | Write | ||
| AV | 59 | EA/Room Cooling boost reg C-factor | Range 0.000 - 2.500 | Write | ||
| AV | 60 | HX Pressure alarm set. | Range 30-100Pa | Pa | Write | |
| AV | 61 | P/C.HX. defrost P-band | Plate/coil heat exchange defrost P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 62 | P/C.HX. defrost C-factor | Plate/coil heat exchange defrost C-factor setting. Range 0.000 - 2.500 | Write | ||
| AV | 63 | Cooling off set. | Cooling off airflow setting in % of max. airflow. Range 10 - 50% | % | Write | |
| AV | 64 | SA Down regulation neutral zone | Range 0.00-10.00°C | °C | Write | |
| AV | 65 | Cool Outdoor temp limit.1 | Outdoor temperature limit setting for cooling stage 1. Range 0.00-25.00°C | °C | Write | |
| AV | 66 | Cool Outdoor temp limit.2 | Outdoor temperature limit setting for cooling stage 2. Range 0.00-25.00°C | °C | Write | |
| AV | 67 | Cool Outdoor temp limit.3 | Outdoor temperature limit setting for cooling stage 3. Range 0.00-25.00°C | °C | Write | |
| AV | 68 | Temperature reg. Neutral zone | Range 0.50-10.00°C | °C | Write | |
| AV | 69 | SA Cool min air flow | Supply air min. air flow setting for cooling. Range 0-20000l/s | l/s | Write | |
| AV | 70 | EA Cool min air flow | Extract air min. air flow setting for cooling. Range 0-20000l/s | l/s | Write | |
| AV | 71 | Heating boost start limit | Heating boost start temperature limit. Range 0.00-40.00°C | °C | Write | |
| AV | 72 | Cooling boost start limit | Cooling boost (comfort) start temperature limit. Range 0.00-40.00°C | °C | Write | |
| AV | 73 | SA Filter alarm limit | Supply air filter pressure alarm limit setting. Range 50-300Pa | Pa | Write | |
| AV | 74 | EA Filter alarm limit | Extract air filter pressure alarm limit setting. Range 50-300Pa | Pa | Write | |
| AV | 75 | Int. Night heat room start temp | Range 5.00-25.00°C | °C | Write | |
| AV | 76 | Int. Night heat room stop temp | Range 5.00-25.00°C | °C | Write | |
| AV | 77 | Int. Night heat SA temp setpoint | Range 5.00-40.00°C | °C | Write | |
| AV | 78 | Int. Night heat SA airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 79 | Int. Night heat EA airflow setpoint | Range 0-20000l/s | l/s | Write | |
| AV | 80 | Summer night cool EA start temp | Range 17.00-27.00°C | °C | Write | |
| AV | 81 | Summer night cool EA stop temp | Range 12.00-22.00°C | °C | Write | |
| AV | 82 | Summer night cool outdoortemp limit | Range 5.00-15.00°C | °C | Write | |
| AV | 83 | Summer night cool SA temp setpoint | Range 10.00-20.00°C | °C | Write | |
| AV | 84 | Outdoor temp comp. Winter X1. | Endpoint of winter compensation. Range -30.00-(-10.00)°C | °C | Write | |
| AV | 85 | Outdoor temp comp. Winter X2. | Startpoint of winter compensation. Range -10.00-15.00°C | °C | Write | |
| AV | 86 | Outdoor temp comp. Winter Y1. | Level of winter compensation at X1. Range 0.00-10.00°C | °C | Write | |
| AV | 87 | Outdoor temp comp. Summer X3. | Startpoint of summer compensation. Range 15.00-25.00°C | °C | Write | |
| AV | 88 | Outdoor temp comp. Summer X4. | Endpoint of summer compensation. Range 25.00-40.00°C | °C | Write | |
| AV | 89 | Outdoor temp comp. Summer Y2. | Level of summer compensation at X4. Range -10.00-10.00°C | °C | Write | |
| AV | 90 | Outdoor airflow comp. Winter X1. | Endpoint of winter compensation. Range 30.00-(-10.00)°C | °C | Write | |
| AV | 91 | Outdoor airflow comp. Winter X2. | Startpoint of winter compensation. Range -10.00-15.00°C | °C | Write | |
| AV | 92 | Outdoor airflow comp. Winter Y1. | Level of airflow compensation at X1. Range 0-50.00% | % | Write | |
| AV | 93 | Extra Reg. Sequence max output | Range 0-100.00% | % | Write | |
| AV | 94 | EA/Room min temp alarm limit | Setting for min extract air /room temp alarm no.40. Range 8.00-20.00°C | °C | Write | |
| AV | 95 | SA Deviation alarm limit | Range 2.00-15.00°C | °C | Write | |
| AV | 97 | SA Fan regulation mode | Setting of regulation type for the supply air fan. Range 0-3 | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan | |
| AV | 98 | EA Fan regulation mode | Setting of regulation type for the extract air fan. Range 0-3 | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan | |
| AV | 99 | ERS Step | Setting of curve when temperature is above breakpoint. Range 1-4 | Write | ||
| AV | 100 | Temperature regulation mode. | Setting of temperature regulation type. Range 0-3 | Write | 0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg | |
| AV | 101 | Cooling off period | Time setting for cooling off electrical heating coil. Range 60-900s | s | Write | |
| AV | 102 | Cool step time set | Time setting between cool step shift. Range 0 - 600s | s | Write | |
| AV | 103 | Cool restart time | Setting of time between two starts of the cool relays. Range 60 - 900s | s | Write | |
| AV | 104 | Cool regulation mode | Setting of cool regulation type. Range 0-6 | Write | 0=Controlled 0-10V, 1=Controlled 10-0V, 2=On/Off 1-step, 3=On/Off 2-steps, 4=On/Off 3-steps binary, 5=CoolDX economy (PV 2.00), 6=CoolDX comfort (PV 3.00) | |
| AV | 105 | Heating boost regulation mode. | Setting for heating boost function. Range 0-1 | Write | 0=Inactive, 1=Active | |
| AV | 106 | Cooling boost regulation mode. | Setting of cooling boost regulation type. Range 0-5 | Write | 0=Inactive, 1=Comfort, 2=Economy, 3=Sequence, 4=Comfort+economy (New in PV 5.00), 5=Economy+sequence (New in PV 5.00) | |
| AV | 107 | Filter calibration mode | Setting for required filter calibration. Range 0-5 | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter, 4=HX, 5=ReCO2 (New in PV 5.00) | |
| AV | 108 | Air adjustment time, minutes | Setting for amount of minutes to air adjustment function. Range 0 - 1727 | Write | ||
| AV | 109 | Air adjustment time, hours | Range 0 - 28 | Write | ||
| AV | 110 | Hand terminal language | Range 0 - 18 | Write | 0=Svenska, 1=Norsk, 2=Dansk, 3=Suomi, 4=English, 5=Français, 6=Deutsch, 7=Polski, 8=Český, 9=Italiano, 10=Español, 11=Português, 12=Русский, 13=Eesti, 14=Latviesu, 15=Lietiviu, 16=Nederlands, 17=Magyar (New in PV 5.00), 18=Türkçe (New in PV 5.01) | |
| AV | 111 | Summer night cool start, hour | Setting for start time of summer night cooling function. Range 0-23 | Write | ||
| AV | 112 | Summer night cool start, minute | Setting for start time of summer night cooling function. Range 0-59 | Write | ||
| AV | 113 | Summer night cool stop, hour | Setting for stop time of summer night cooling function. Range 0-23 | Write | ||
| AV | 114 | Summer night cool stop, minute | Setting for stop time of summer night cooling function. Range 0-59 | Write | ||
| AV | 115 | Extra regulation sequence cool mode | Setting of extra regulation sequence cool type. Range 0-2 | Write | 0=Inactive, 1=Comfort, 2=Economy | |
| AV | 116 | Extra regulation sequence heat mode | Setting of extra regulation sequence heat type. Range 0-2 | Write | 0=Inactive, 1=Comfort, 2=Economy | |
| AV | 117 | Morning boost time, hours | Setting of morning boost time before normal operation. Range 0-23 | Write | ||
| AV | 118 | Morning boost time, minutes | Setting of morning boost time before normal operation. Range 0-59 | Write | ||
| AV | 119 | Startup time | Range 0 - 600s | s | Write | |
| AV | 120 | Start delay SA fan. | Setting of start delay time for the supply air fan. Range 0 - 600s | s | Write | |
| AV | 121 | Start delay EA fan. | Range 0 - 600s | s | Write | |
| AV | 122 | Air flow unit | Range 0 -2 | Write | 0=l/s, 1=m3/s, 2=m3/h | |
| AV | 124 | Year | Setting for the unit's internal clock. Range 2000-2099 | Write | ||
| AV | 125 | Month | Setting for the unit's internal clock. Range 1-12 | Write | ||
| AV | 126 | Date | Setting for the unit's internal clock. Range 0-31 | Write | ||
| AV | 127 | Hour | Setting for the unit's internal clock. Range 0-23 | Write | ||
| AV | 128 | Minute | Setting for the unit's internal clock. Range 0-59 | Write | ||
| AV | 129 | Second | Setting for the unit's internal clock. Range 0-59 | Write | ||
| AV | 130 | Time channel 1 status | Range 0-10,16-26 | Write | 0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday, 16=Inactive, 17=Monday, 18=Tuesday, 19=Wednesday, 20=Thursday, 21=Friday, 22=Saturday, 23=Sunday, 24=Monday..Friday, 25=Monday..Sunday, 26=Saturday..Sunday | |
| AV | 131 | Time channel 1 start hour | Range 0-23 | Write | ||
| AV | 132 | Time channel 1 start minute | Range 0-59 | Write | ||
| AV | 133 | Time channel 1 stop hour | Range 0-23 | Write | ||
| AV | 134 | Time channel 1 stop minute | Range 0-59 | Write | ||
| AV | 135 | Time channel 2 status | Range 0-10,16-26 | Write | ||
| AV | 136 | Time channel 2 start hour | Range 0-23 | Write | ||
| AV | 137 | Time channel 2 start minute | Range 0-59 | Write | ||
| AV | 138 | Time channel 2 stop hour | Range 0-23 | Write | ||
| AV | 139 | Time channel 2 stop minute | Range 0-59 | Write | ||
| AV | 140 | Time channel 3 status | Range 0-10,16-26 | Write | ||
| AV | 141 | Time channel 3 start hour | Range 0-23 | Write | ||
| AV | 142 | Time channel 3 start minute | Range 0-59 | Write | ||
| AV | 143 | Time channel 3 stop hour | Range 0-23 | Write | ||
| AV | 144 | Time channel 3 stop minute | Range 0-59 | Write | ||
| AV | 145 | Time channel 4 status | Range 0-10,16-26 | Write | ||
| AV | 146 | Time channel 4 start hour | Range 0-23 | Write | ||
| AV | 147 | Time channel 4 start minute | Range 0-59 | Write | ||
| AV | 148 | Time channel 4 stop hour | Range 0-23 | Write | ||
| AV | 149 | Time channel 4 stop minute | Range 0-59 | Write | ||
| AV | 150 | Time channel 5 status | Range 0-10,16-26 | Write | ||
| AV | 151 | Time channel 5 start hour | Range 0-23 | Write | ||
| AV | 152 | Time channel 5 start minute | Range 0-59 | Write | ||
| AV | 153 | Time channel 5 stop hour | Range 0-23 | Write | ||
| AV | 154 | Time channel 5 stop minute | Range 0-59 | Write | ||
| AV | 155 | Time channel 6 status | Range 0-10,16-26 | Write | ||
| AV | 156 | Time channel 6 start hour | Range 0-23 | Write | ||
| AV | 157 | Time channel 6 start minute | Range 0-59 | Write | ||
| AV | 158 | Time channel 6 stop hour | Range 0-23 | Write | ||
| AV | 159 | Time channel 6 stop minute | Range 0-59 | Write | ||
| AV | 160 | Time channel 7 status | Range 0-10,16-26 | Write | ||
| AV | 161 | Time channel 7 start hour | Range 0-23 | Write | ||
| AV | 162 | Time channel 7 start minute | Range 0-59 | Write | ||
| AV | 163 | Time channel 7 stop hour | Range 0-23 | Write | ||
| AV | 164 | Time channel 7 stop minute | Range 0-59 | Write | ||
| AV | 165 | Time channel 8 status | Range 0-10,16-26 | Write | ||
| AV | 166 | Time channel 8 start hour | Range 0-23 | Write | ||
| AV | 167 | Time channel 8 start minute | Range 0-59 | Write | ||
| AV | 168 | Time channel 8 stop hour | Range 0-23 | Write | ||
| AV | 169 | Time channel 8 stop minute | Range 0-59 | Write | ||
| AV | 170 | Extended low speed op. Hours set | Setting for extended low speed operation. Range 0-23 | Write | ||
| AV | 171 | Extended low speed op. Minutes set | Setting for extended low speed operation. Range 0-59 | Write | ||
| AV | 172 | Extended high speed op. Hours set | Setting for extended high speed operation. Range 0-23 | Write | ||
| AV | 173 | Extended high speed op. Minutes set | Setting for extended high speed operation. Range 0-59 | Write | ||
| AVmin | 174 | Communication operation mode | Setting of unit operation mode from communication. Range 0-4 | Write | 0=Auto operation (normal stop when time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (New in PV 5.00) | |
| AV | 175 | Service period alarm. | Setting for delay time in months before service alarm. Range 0-99 | Write | ||
| AV | 176 | External alarm 1 delay | Setting of delay time for external alarm no 1. Range 1 - 600s | s | Write | |
| AV | 177 | External alarm 2 delay | Setting of delay time for external alarm no 2. Range 1 - 600s | s | Write | |
| AV | 178 | Int. Night heat SA pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 179 | Int. Night heat EA pressure setpoint | Range 20-750Pa | Pa | Write | |
| AV | 180 | Copy of Coil Status 1-16 | Range 0-65535 | Write | ||
| AV | 181 | Copy of Coil Status 17-32 | Range 0-65535 | Write | ||
| AV | 182 | Copy of Coil Status 33-48 | Range 0-65535 | Write | ||
| AV | 183 | Heat relay periodic func. | Setting of periodic operation. Range 0-3 | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 184 | Cool relay 1 periodic func. | Setting of periodic operation. Range 0-3 | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 185 | Cool relay 2 periodic func. | Setting of periodic operation. Range 0-3 | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 186 | Slave control C-factor | Slave regulator affection setting. Range 0.5 - 2.0 | Write | ||
| AV | 187 | SA dehumid P-band | SA dehumid regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 188 | SA dehumid C-factor | SA dehumid regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 189 | Dewpoint reg. P-band | Dewpoint regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 190 | Dewpoint reg. C-factor | Dewpoint regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 191 | AYC chilled water temperature set | Setting of AYC chilled water temperature setpoint. Range 5.00-30.00°C | °C | Write | |
| AV | 192 | Dewpoint neutral zone | Dewpoint neutral zone setting. Range 0.00-5.00°C | °C | Write | |
| AV | 193 | Comp. airflow | Setting of comp. airflow. Range 0-30.00% | % | Write | |
| AV | 194 | Supply air-humidity_set | Setting of supply air-humidity. Range 10.00-90.00% | % | Write | |
| AV | 195 | Water heating periodic op. time | Setting of periodic op. time (minute). Range 0-60min | min | Write | |
| AV | 196 | Water heating interval | Setting of water heating interval time (hour). Range 0-168h | h | Write | |
| AV | 197 | Cool periodic op. time | Setting of periodic op. time (minute). Range 0-60min | min | Write | |
| AV | 198 | Cool interval | Setting of cool interval time (hour). Range 0-168h | h | Write | |
| AV | 199 | P/C.HX. bypass adj. | Setting of plate/coil heat exchange bypass adjustment. Range -5.00-5.00°C | °C | Write | |
| AV | 200 | EA/Room temperature external func. | Setting of EA/Room temperature (external) function. Range 0-3 (from PV 5.15) | Write | 0=Inactive, 1=Input signal on terminal 40..41, 2=Communication (AV 201), 3=Min/Max/Average (PV 5.15) | |
| AV | 201 | EA/Room temperature com. | Setting of EA/Room temperature via communication. Range -55.00-125.00°C | °C | Write | |
| AV | 202 | Outdoor temperature external func. | Setting of outdoor temperature (external) function. Range 0-2 | Write | 0=Inactive, 1=Input signal on terminal 38..39, 2=Communication (AV 203) | |
| AV | 203 | Outdoor temperature com. | Setting of outdoor temperature via communication. Range -55.00-125.00°C | °C | Write | |
| AV | 204 | Timeout temperature com. | Range 0-9999min | min | Write | |
| AV | 205 | Flow at fire function. | Setting for activating the air fan operation at fire function. Range 0-3 | Write | 0=Inactive, 1=SA, 2=EA, 3=SA+EA | |
| AV | 206 | Air fan down regulation func. | Setting for activating the air fan down regulation function. Range 0-2 | Write | 0=Inactive, 1=SA, 2=SA+EA | |
| AV | 207 | SA speed at fire. | Setting of supply air speed at fire. Range 50.00-100.00% | % | Write | |
| AV | 208 | EA speed at fire. | Setting of extract air speed at fire. Range 50.00-100.00% | % | Write | |
| AV | 209 | Temperature alarm setpoint. | Temperature alarm function setting (no.80). Range -25.00-25.00°C | °C | Write | |
| AV | 210 | Temperature alarm time. | Setting of delay time for temperature alarm (no.80). Range 1-999s | s | Write | |
| AV | 211 | Supply air min P-band. | Supply air min regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 212 | Supply air min C-factor. | Supply air min regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 213 | Supply air max P-band. | Supply air max regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 214 | Supply air max C-factor. | Supply air max regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 215 | Year channel 1 function. | Range 0-3 | Write | 0=Inactive, 1=Stop, 2=Low speed, 3=High speed | |
| AV | 216 | Year channel 1 start year. | Range 2000 - 2099 | Write | ||
| AV | 217 | Year channel 1 start month. | Range 1 - 12 | Write | ||
| AV | 218 | Year channel 1 start date. | Range 1-31 | Write | ||
| AV | 219 | Year channel 1 start hour. | Range 0- 23 | Write | ||
| AV | 220 | Year channel 1 start minute. | Range 0- 59 | Write | ||
| AV | 221 | Year channel 1 stop year. | Range 2000-2099 | Write | ||
| AV | 222 | Year channel 1 stop month. | Range 1-12 | Write | ||
| AV | 223 | Year channel 1 stop date. | Range 1- 31 | Write | ||
| AV | 224 | Year channel 1 stop hour. | Range 0-23 | Write | ||
| AV | 225 | Year channel 1 stop minute. | Range 0-59 | Write | ||
| AV | 226 | Year channel 2 function. | Range 0-3 | Write | ||
| AV | 227 | Year channel 2 start year. | Range 2000 - 2099 | Write | ||
| AV | 228 | Year channel 2 start month. | Range 1- 12 | Write | ||
| AV | 229 | Year channel 2 start date. | Range 1- 31 | Write | ||
| AV | 230 | Year channel 2 start hour. | Range 0-23 | Write | ||
| AV | 231 | Year channel 2 start minute. | Range 0 - 59 | Write | ||
| AV | 232 | Year channel 2 stop year. | Range 2000 - 2099 | Write | ||
| AV | 233 | Year channel 2 stop month. | Range 1 - 12 | Write | ||
| AV | 234 | Year channel 2 stop date. | Range 1- 31 | Write | ||
| AV | 235 | Year channel 2 stop hour. | Range 0 - 23 | Write | ||
| AV | 236 | Year channel 2 stop minute. | Range 0- 59 | Write | ||
| AV | 237 | Year channel 3 function. | Range 0-3 | Write | ||
| AV | 238 | Year channel 3 start year. | Range 2000 - 2099 | Write | ||
| AV | 239 | Year channel 3 start month. | Range 1 - 12 | Write | ||
| AV | 240 | Year channel 3 start date. | Range 1 - 31 | Write | ||
| AV | 241 | Year channel 3 start hour. | Range 0 - 23 | Write | ||
| AV | 242 | Year channel 3 start minute. | Range 0-59 | Write | ||
| AV | 243 | Year channel 3 stop year. | Range 2000 - 2099 | Write | ||
| AV | 244 | Year channel 3 stop month. | Range 1 - 12 | Write | ||
| AV | 245 | Year channel 3 stop date. | Range 1- 31 | Write | ||
| AV | 246 | Year channel 3 stop hour. | Range 0 - 23 | Write | ||
| AV | 247 | Year channel 3 stop minute. | Range 0 - 59 | Write | ||
| AV | 248 | Year channel 4 function. | Range 0-3 | Write | ||
| AV | 249 | Year channel 4 start year. | Range 2000 - 2099 | Write | ||
| AV | 250 | Year channel 4 start month. | Range 1- 12 | Write | ||
| AV | 251 | Year channel 4 start date. | Range 1- 31 | Write | ||
| AV | 252 | Year channel 4 start hour. | Range 0 - 23 | Write | ||
| AV | 253 | Year channel 4 start minute. | Range 0 - 59 | Write | ||
| AV | 254 | Year channel 4 stop year. | Range 2000 - 2099 | Write | ||
| AV | 255 | Year channel 4 stop month. | Range 1 - 12 | Write | ||
| AV | 256 | Year channel 4 stop date. | Range 1 - 31 | Write | ||
| AV | 257 | Year channel 4 stop hour. | Range 0 - 23 | Write | ||
| AV | 258 | Year channel 4 stop minute. | Range 0 - 59 | Write | ||
| AV | 259 | Year channel 5 function. | Range 0-3 | Write | ||
| AV | 260 | Year channel 5 start year. | Range 2000 - 2099 | Write | ||
| AV | 261 | Year channel 5 start month. | Range 1 - 12 | Write | ||
| AV | 262 | Year channel 5 start date. | Range 1- 31 | Write | ||
| AV | 263 | Year channel 6 start hour. | Year channel 5 start hour (the guide prints 'channel 6' here). Range 0-23 | Write | ||
| AV | 264 | Year channel 5 start minute. | Range 0- 59 | Write | ||
| AV | 265 | Year channel 5 stop year. | Range 2000 - 2099 | Write | ||
| AV | 266 | Year channel 5 stop month. | Range 1 - 12 | Write | ||
| AV | 267 | Year channel 5 stop date. | Range 1- 31 | Write | ||
| AV | 268 | Year channel 5 stop hour. | Range 0 - 23 | Write | ||
| AV | 269 | Year channel 5 stop minute. | Range 0 - 59 | Write | ||
| AV | 270 | Year channel 6 function. | Range 0-3 | Write | ||
| AV | 271 | Year channel 6 start year. | Range 2000 - 2099 | Write | ||
| AV | 272 | Year channel 6 start month. | Range 1 - 12 | Write | ||
| AV | 273 | Year channel 6 start date. | Range 1- 31 | Write | ||
| AV | 274 | Year channel 6 start hour. | Range 0- 23 | Write | ||
| AV | 275 | Year channel 6 start minute. | Range 0-59 | Write | ||
| AV | 276 | Year channel 6 stop year. | Range 2000 -2099 | Write | ||
| AV | 277 | Year channel 6 stop month. | Range 1- 12 | Write | ||
| AV | 278 | Year channel 6 stop date. | Range 1- 31 | Write | ||
| AV | 279 | Year channel 6 stop hour. | Range 0- 23 | Write | ||
| AV | 280 | Year channel 6 stop minute. | Range 0-59 | Write | ||
| AV | 281 | Year channel 7 function. | Range 0-3 | Write | ||
| AV | 282 | Year channel 7 start year. | Range 2000 - 2099 | Write | ||
| AV | 283 | Year channel 7 start month. | Range 1- 12 | Write | ||
| AV | 284 | Year channel 7 start date. | Range 1- 31 | Write | ||
| AV | 285 | Year channel 7 start hour. | Range 0 - 23 | Write | ||
| AV | 286 | Year channel 7 start minute. | Range 0 - 59 | Write | ||
| AV | 287 | Year channel 7 stop year. | Range 2000 - 2099 | Write | ||
| AV | 288 | Year channel 7 stop month. | Range 1 - 12 | Write | ||
| AV | 289 | Year channel 7 stop date. | Range 1- 31 | Write | ||
| AV | 290 | Year channel 7 stop hour. | Range 0 - 23 | Write | ||
| AV | 291 | Year channel 7 stop minute. | Range 0 - 59 | Write | ||
| AV | 292 | Year channel 8 function. | Range 0-3 | Write | ||
| AV | 293 | Year channel 8 start year. | Range 2000 - 2099 | Write | ||
| AV | 294 | Year channel 8 start month. | Range 1 - 12 | Write | ||
| AV | 295 | Year channel 8 start date. | Range 1 - 31 | Write | ||
| AV | 296 | Year channel 8 start hour. | Range 0 - 23 | Write | ||
| AV | 297 | Year channel 8 start minute. | Range 0- 59 | Write | ||
| AV | 298 | Year channel 8 stop year. | Range 2000 - 2099 | Write | ||
| AV | 299 | Year channel 8 stop month. | Range 1- 12 | Write | ||
| AV | 300 | Year channel 8 stop date. | Range 1- 31 | Write | ||
| AV | 301 | Year channel 8 stop hour. | Range 0 - 23 | Write | ||
| AV | 302 | Year channel 8 stop minute. | Range 0 - 59 | Write | ||
| AV | 303 | Filter select. | Setting for filter select function. Range 0-3 | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 304 | Pre-filter select. | Setting for pre-filter select function. Range 0-3 | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 305 | SA pre-filter alarm limit. | Supply air pre-filter pressure alarm limit setting. Range 50-300Pa | Pa | Write | |
| AV | 306 | EA pre-filter alarm limit. | Extract air pre-filter pressure alarm limit setting. Range 50-300Pa | Pa | Write | |
| AV | 307 | Pre-filter calibration mode. | Setting for required filter calibration. Range 0-3 | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter | |
| AV | 308 | Xzone reheat function. | Setting for Xzone reheat function. Range 0-4 | Write | 0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP | |
| AV | 309 | Xzone cooling function. | Setting for Xzone cooling function. Range 0-5 | Write | 0=Inactive, 1=0-10V, 2=10-0V, 3=On/off 1, 4=On/off 2, 5=On/off 3 | |
| AV | 310 | Xzone temperature reg. Neutral zone. | Range 0.50-10.00°C | °C | Write | |
| AV | 311 | Xzone temperature regulation mode. | Setting of Xzone temperature regulation type. Range 0-3 | Write | 0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg | |
| AV | 312 | Xzone ERS Step. | Setting of Xzone curve when temperature is above breakpoint. Range 1-4 | Write | ||
| AV | 313 | Xzone ERS 1 Diff. | Range 1.00 - 7.00°C | °C | Write | |
| AV | 314 | Xzone ERS 1 Breakpoint. | Breakpoint setting according to the diagram for Xzone ERs 1. Range 12.00 - 26.00°C | °C | Write | |
| AV | 315 | Xzone ERS 2 Breakpoint X1. | Breakpoint X1 setting according to the diagram for Xzone ERS 2. Range 10.00-38.00°C | °C | Write | |
| AV | 316 | Xzone ERS 2 Breakpoint Y1. | Breakpoint Y1 setting according to the diagram for Xzone ERS 2. Range 10.00-40.00°C | °C | Write | |
| AV | 317 | Xzone ERS 2 Breakpoint X2. | Breakpoint X2 setting according to the diagram for Xzone ERS 2. Range 11.00-39.00°C | °C | Write | |
| AV | 318 | Xzone ERS 2 Breakpoint Y2. | Range 10.00-40.00°C | °C | Write | |
| AV | 319 | Xzone ERS 2 Breakpoint X3. | Breakpoint X3 setting according to the diagram for Xzone ERS 2. Range 12.00-40.00°C | °C | Write | |
| AV | 320 | Xzone ERS 2 Breakpoint Y3. | Breakpoint Y3 setting according to the diagram for Xzone ERS 2. Range 10.00-40.00°C | °C | Write | |
| AV | 321 | Xzone SA Temperature setpoint. | Range 10.00-40.00°C | °C | Write | |
| AV | 322 | Xzone EA/Room Temperature setpoint. | Range 10.00-40.00°C | °C | Write | |
| AV | 323 | Xzone SA Min temp setpoint. | Range 8.00-20.00°C | °C | Write | |
| AV | 324 | Xzone SA Max temp setpoint | Range 16.00-50.00°C | °C | Write | |
| AV | 325 | Pre-heating function. | Setting of pre-heating function. Range 0-4 | Write | 0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP | |
| AV | 326 | Pre-heating setpoint. | Setting of pre-heating temperature setpoint. Range -30.00-30.00°C | °C | Write | |
| AV | 327 | Xzone P-band. | Xzone regulator P-band setting. Range 1.00-40.00 | Write | ||
| AV | 328 | Xzone SA reheat C-factor. | Xzone supply air reheat regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 329 | Xzone SA cooling C-factor. | Xzone supply air cooling regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 330 | Xzone EA reheat C-factor. | Xzone extract air reheat regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 331 | Xzone EA cooling C-factor. | Xzone extract air cooling regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 332 | Xzone SA min P-band. | Xzone supply air min regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 333 | Xzone SA min C-factor. | Xzone supply air min regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 334 | Xzone SA max P-band. | Xzone supply air max regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 335 | Xzone SA max C-factor. | Xzone supply air min regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 336 | Preheat P-band. | Preheat regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 337 | Preheat C-factor. | Preheat regulator affection setting. Range 0.000 - 2.500 | Write | ||
| AV | 338 | ReCO2 CO2 function. | Setting of ReCO2 CO2 function. Range 0-2 | Write | 0=Inactive, 1=CO2, 2=CO2+flow | |
| AV | 339 | ReCO2 CO2 setpoint. | Setting of ReCO2 CO2 setpoint. Range 0-100.00% | % | Write | |
| AV | 340 | ReCO2 cooling function. | Setting of ReCO2 cooling function. Range 0-2 | Write | 0=Inactive, 1=Comfort, 2=Economy | |
| AV | 341 | ReCO2 heating function. | Setting of ReCO2 heating function. Range 0-2 | Write | 0=Inactive, 1=Comfort, 2=Economy | |
| AV | 342 | ReCO2 min outdoor air. | Setting of ReCO2 min outdoor air. Range 0-20000l/s | l/s | Write | |
| AV | 343 | ReCO2 min exhaust air. | Setting of ReCO2 min exhaust air. Range 0-20000l/s | l/s | Write | |
| AV | 344 | ReCO2 CO2 P-band. | ReCO2 CO2 regulator P-band setting. Range 1.00 - 100.00 | Write | ||
| AV | 345 | ReCO2 CO2 C-factor. | ReCO2 CO2 regulator affection setting. Range 0.000 - 5.000 | Write | ||
| AV | 346 | ReCO2 CO2 flow C-factor. | ReCO2 flow regulator affection setting. Range 0.000 - 5.000 | Write | ||
| AV | 347 | ReCO2 heating C-factor. | ReCO2 heating regulator affection setting. Range 0.000 - 5.000 | Write | ||
| AV | 348 | ReCO2 cooling C-factor. | ReCO2 cooling regulator affection setting. Range 0.000 - 5.000 | Write | ||
| AV | 349 | AYC function. | Setting of AYC function. Range 0-3 | Write | 0=Inactive, 1=Cool, 2=Heat, 3=Cool+heat | |
| AV | 350 | AYC heat temp set. | Setting of AYC heated water temperature setpoint. Range 10.00-80.00°C | °C | Write | |
| AV | 351 | AYC night comp. channel. | Setting of AYC night compensation channel. Range 1-2 | Write | 1=Channel 1, 2=Channel 2 | |
| AV | 352 | AYC channel start hour. | Setting of AYC channel start time (hour). Range 0-23h | h | Write | |
| AV | 353 | AYC channel start minute. | Setting of AYC channel start time (minute). Range 0-59min | min | Write | |
| AV | 354 | AYC channel stop hour. | Setting of AYC channel stop time (hour). Range 0-23h | h | Write | |
| AV | 355 | AYC channel stop minute. | Setting of AYC channel stop time (minute). Range 0-59min | min | Write | |
| AV | 356 | AYC channel period. | Setting of AYc channel period. Range 0-10 | Write | 0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday | |
| AV | 357 | AYC heat P-band. | AYC heat regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 358 | AYC heat C-factor. | AYC heat regulator affection setting. Range 0.000-2.500 | Write | ||
| AV | 359 | AYC cool P-band. | AYC cool regulator P-band setting. Range 1.00 - 40.00 | Write | ||
| AV | 360 | AYC cool C-factor. | AYC cool regulator affection setting. Range 0.000-2.500 | Write | ||
| AV | 361 | AYC heat out comp. X1. | Range -40.00-40.00°C | °C | Write | |
| AV | 362 | AYC heat out comp. Y1. | Range 10.00-80.00°C | °C | Write | |
| AV | 363 | AYC heat out comp. X2. | Range -40.00-40.00°C | °C | Write | |
| AV | 364 | AYC heat out comp. Y2. | Range 10.00-80.00°C | °C | Write | |
| AV | 365 | AYC heat out comp. X3. | Range -40.00-40.00°C | °C | Write | |
| AV | 366 | AYC heat out comp. Y3. | Range 10.00-80.00°C | °C | Write | |
| AV | 367 | AYC heat room comp. temp limit. | Range 0.00-40.00°C | °C | Write | |
| AV | 368 | AYC heat room comp P-band. | Range 1.00-10.00°C | °C | Write | |
| AV | 369 | AYC heat night comp temp. | Range -10.00-10.00°C | °C | Write | |
| AV | 370 | AYC heat pump on temp. | Range -40.00-40.00°C | °C | Write | |
| AV | 371 | AYC heat pump off temp. | Range -40.00-40.00°C | °C | Write | |
| AV | 372 | AYC heat pump alarm. | Setting for selecting the AYC heated water pump alarm function. Range 0-3 | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 373 | AYC heat per op function. | Range 0-3 | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 374 | AYC heat per op time. | Range 0-60min | min | Write | |
| AV | 375 | AYC heat per op interval. | Range 0-168h | h | Write | |
| AV | 376 | AYC cool out comp. X1. | Range -40.00-40.00°C | °C | Write | |
| AV | 377 | AYC cool out comp. Y1. | Range 10.00-80.00°C | °C | Write | |
| AV | 378 | AYC cool out comp. X2. | Range -40.00-40.00°C | °C | Write | |
| AV | 379 | AYC cool out comp. Y2. | Range 10.00-80.00°C | °C | Write | |
| AV | 380 | AYC cool out comp. X3. | Range -40.00-40.00°C | °C | Write | |
| AV | 381 | AYC cool out comp. Y3. | Range 10.00-80.00°C | °C | Write | |
| AV | 382 | AYC cool room comp. temp limit. | Range 0.00-40.00°C | °C | Write | |
| AV | 383 | AYC cool room comp. P-band. | Range 1.00-10.00°C | °C | Write | |
| AV | 384 | AYC cool night comp temp. | Range -10.00-10.00°C | °C | Write | |
| AV | 385 | AYC cool pump on temp. | Range -40.00-40.00°C | °C | Write | |
| AV | 386 | AYC cool pump off temp. | Range -40.00-40.00°C | °C | Write | |
| AV | 387 | AYC cool pump alarm. | Setting for selecting the AYC chilled water pump alarm function. Range 0-3 | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 388 | AYC cool per op function. | Range 0-3 | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 389 | AYC cool per op time. | Range 0-60min | min | Write | |
| AV | 390 | AYC cool per op interval. | Range 0-168h | h | Write | |
| AV | 391 | IO-mod 3 output 1 function. | Setting of I/O-module no. 3 relay 1 output. Range 0- 10 | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| AV | 392 | IO-mod 3 output 2 function. | Setting of I/O-module no. 3 relay 2 output. Range 0 - 10 | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| AV | 393 | Humid reg. func. | Setting for selecting humidifying function. Range 0-3 (from PV 6.07) | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=Steam (New in PV 6.07) | |
| AV | 394 | Humid reg. Start. | Humidifying start limit setting. Range 10.00-90.00% (from PV 5.10) | % | Write | |
| AV | 395 | Humid reg. Stop. | Humidifying stop limit setting. Range 15.00-95.00% (from PV 5.10) | % | Write | |
| AV | 396 | Min/Max/Average SensNumber | Range 1-4 (from PV 5.15) | Write | ||
| AV | 397 | Min/Max/Average SensFunction | Setting for selecting sensor function. Range 0-2 (from PV 5.15) | Write | 0=Min, 1=Max, 2=Average | |
| AV | 398 | Miru 1 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 399 | Miru 1 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 400 | Miru 1 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 401 | Miru 1 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 402 | Miru 2 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 403 | Miru 2 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 404 | Miru 2 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 405 | Miru 2 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 406 | Miru 3 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 407 | Miru 3 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 408 | Miru 3 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 409 | Miru 3 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 410 | Miru 4 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 411 | Miru 4 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 412 | Miru 4 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 413 | Miru 4 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 414 | Miru 5 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 415 | Miru 5 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 416 | Miru 5 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 417 | Miru 5 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 418 | Miru 6 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 419 | Miru 6 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 420 | Miru 6 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 421 | Miru 6 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 422 | Miru 7 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 423 | Miru 7 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 424 | Miru 7 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 425 | Miru 7 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 426 | Miru 8 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 427 | Miru 8 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 428 | Miru 8 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 429 | Miru 8 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 430 | Miru 9 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 431 | Miru 9 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 432 | Miru 9 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 433 | Miru 9 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 434 | Miru 10 Low speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 435 | Miru 10 High speed airflow setpoint | Range 0-10000l/s (from PV 6.04) | l/s | Write | |
| AV | 436 | Miru 10 Low speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 437 | Miru 10 High speed pressure setpoint | Range 0-750Pa (from PV 6.04) | Pa | Write | |
| AV | 438 | BB Cool temp setpoint | Blue Box cooling temperature setpoint. Range -20.0-80.0°C (from PV 6.05) | °C | Write | |
| AV | 439 | BB Heat temp setpoint | Blue Box heating temperature setpoint. Range 10.0-80.0°C (from PV 6.05) | °C | Write | |
| AV | 440 | BB Unit type | Blue Box unit type. Range 0-3 (from PV 6.05) | Write | 0=None, 1=Heat pump, 2=Chiller, 3=Reversible | |
| AV | 441 | BB Optimize upper valve limit | Blue Box optimize function upper valve limit. Range 70.00-100.00% (from PV 6.05) | % | Write | |
| AV | 442 | BB Optimize lower valve limit | Blue Box optimize function lower valve limit. Range 5.00-90.00% (from PV 6.05) | % | Write | |
| AV | 443 | BB Optimize delay | Blue Box optimize function delay time. Range 30-32000s (from PV 6.05) | s | Write | |
| AV | 444 | BB Cool optimize up | Blue Box cooling optimize function up. Range 0.1-6.0°C (from PV 6.05) | °C | Write | |
| AV | 445 | BB Cool optimize down | Blue Box cooling optimize function down. Range 0.1-6.0°C (from PV 6.05) | °C | Write | |
| AV | 446 | BB Heat optimize up | Blue Box heating optimize function up. Range 0.1-6.0°C (from PV 6.05) | °C | Write | |
| AV | 447 | BB Heat optimize down | Blue Box heating optimize function down. Range 0.1-6.0°C (from PV 6.05) | °C | Write | |
| AV | 448 | BB Cool optimize diff temperature | Blue Box cooling optimize function differential temperature. Range 1.0-10.0°C (from PV 6.05) | °C | Write | |
| AV | 449 | BB Heat optimize diff temperature | Blue Box heating optimize function differential temperature. Range 1.0-10.0°C (from PV 6.05) | °C | Write | |
| AV | 450 | BB AQUA Link function | Blue Box AQUA Link function. Range 0-3 (from PV 6.05) | Write | 0=Inactive, 1=Heat, 2=Cool, 3=Heat + Cool | |
| AV | 451 | BB AQUA Link cool pump alarm function | Blue Box AQUA Link cool pump alarm function. Range 0-3 (from PV 6.05) | Write | 0=Inactive, 1=Open, 2=Close, 3=Contactor | |
| AV | 452 | BB AQUA Link heat pump alarm function | Blue Box AQUA Link heat pump alarm function. Range 0-3 (from PV 6.05) | Write | 0=Inactive, 1=Open, 2=Close, 3=Contactor | |
| AV | 453 | Extended ext. reg. seq. reheat function | Extended extra regulation sequence reheat function. Range 0-4 (from PV 6.07) | Write | 0=Inactive, 1=El. P/P, 2=El. 0-10V, 3=Water FP, 4=Water | |
| AV | 454 | Season heat mode setpoint | Season heat mode type setpoint. Range 0-2 (from PV 6.07) | Write | 0=Digital Input NO, 1=Digital Input NC, 2=Manual | |
| AV | 455 | Season heat function | Season heating function. Range 0-1 (from PV 6.07) | Write | 0=Inactive, 1=Active | |
| AV | 456 | Steam humid extract air setpoint | Steam humidification extract air setpoint. Range 0-100.00% (from PV 6.07) | % | Write | |
| AV | 457 | Steam humid supply air max limit | Steam humidification supply air max limit. Range 0-100.00% (from PV 6.07) | % | Write | |
| AV | 458 | Steam humid extract air P-band | Steam humidification extract air P-band. Range 1-60.00% (from PV 6.07) | % | Write | |
| AV | 459 | Steam humid extract air C-factor | Steam humidification extract air C-factor. Range 0-3.000 (from PV 6.07) | Write | ||
| AV | 460 | Steam humid supply air max P-band | Steam humidification supply air max P-band. Range 1-60.00% (from PV 6.07) | % | Write | |
| AV | 461 | Steam humid supply air max C-factor | Steam humidification supply air max C-factor. Range 0-3.000 (from PV 6.07) | Write | ||
| AV | 462 | End-filter alarm limit | Supply air end-filter pressure alarm limit setting. Range 10-1000Pa (from PV 6.07) | Pa | Write | |
| AV | 463 | End-filter select | Supply air end-filter function. Range 0-1 (from PV 6.07) | Write | 0=Inactive, 1=Active | |
| AV | 464 | End-filter calibration | Supply air end-filter calibration. Range 0-1 (from PV 6.07) | Write | 0=Inactive, 1=Active | |
| BI | 0 | Heat output | Status for relay output. | Read | ||
| BI | 1 | Cool output 1 | Status for relay output. | Read | ||
| BI | 2 | Cool output 2 | Status for relay output. | Read | ||
| BI | 3 | Low speed output | Status for relay output. | Read | ||
| BI | 4 | High speed output | Status for relay output. | Read | ||
| BImin | 5 | A-alarm. | Status for relay output. | Read | ||
| BImin | 6 | B-alarm. | Status for relay output. | Read | ||
| BI | 7 | Operation output | Status for relay output. | Read | ||
| BI | 8 | Damper output | Status for relay output. | Read | ||
| BI | 9 | External low speed input | Status for digital input. | Read | ||
| BI | 10 | External high speed input | Status for digital input. | Read | ||
| BI | 11 | External alarm 1 input | Status for digital input. | Read | ||
| BI | 12 | External alarm 2 input | Status for digital input. | Read | ||
| BI | 13 | External fire alarm input. | Status for digital input. | Read | ||
| BI | 14 | External stop input | Status for digital input. | Read | ||
| BI | 15 | DIP Switch 1 | Status for dip switch setting. | Read | ||
| BI | 16 | DIP Switch 2 | Status for dip switch setting. | Read | ||
| BI | 17 | DIP Switch 3 | Status for dip switch setting | Read | ||
| BI | 18 | DIP Switch 4 | Status for dip switch setting. | Read | ||
| BI | 19 | DIP Switch 5 | Status for dip switch setting | Read | ||
| BI | 20 | DIP Switch 6 | Status for dip switch setting. | Read | ||
| BI | 21 | AYC heat pump output | Status for AYC heat pump output. | Read | ||
| BI | 22 | AYC cool pump output | Status for AYC cool pump output. | Read | ||
| BI | 23 | C.HX. pump output | Status for coil heat exchanger pump output. | Read | ||
| BI | 24 | R.HX rotation monitor | Status from the rotation detector. | Read | ||
| BI | 25 | Xzone heat output | Status for relay output. | Read | ||
| BI | 26 | Xzone cool output 1 | Status for relay output. | Read | ||
| BI | 27 | Xzone cool output 2 | Status for relay output. | Read | ||
| BI | 28 | Pre-heat output | Status for relay output. | Read | ||
| BI | 29 | IO-mod 3 output 1 | Status for I/O-module no. 3 relay 1 output. | Read | ||
| BI | 30 | IO-mod 3 output 2 | Status for I/O-module no. 3 relay 2 output. | Read | ||
| BI | 31 | IO-mod 4 output 1 | Status for I/O-module no. 4 relay 1 output. (from PV 5.10) | Read | ||
| BI | 32 | Miru 1 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 33 | Miru 2 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 34 | Miru 3 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 35 | Miru 4 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 36 | Miru 5 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 37 | Miru 6 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 38 | Miru 7 Alarm | Status of group alarm from Miru fan (from PV 6.04) | Read | ||
| BI | 39 | Miru 8 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 40 | Miru 9 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 41 | Miru 10 Alarm | Status of group alarm from Miru fan. (from PV 6.04) | Read | ||
| BI | 42 | Extended ext. reg. seq. Pump | Status of extended extra regulation sequence pump output. (from PV 6.07) | Read | ||
| BI | 43 | Season heating mode | Status of season heating mode. (from PV 6.07) | Read | ||
| BI | 48 | Alarm number 1 | Status if alarm number 1 is active. | Read | ||
| BI | 49 | Alarm number 2 | Status if alarm number 2 is active | Read | ||
| BI | 50 | Alarm number 3 | Status if alarm number 3 is active | Read | ||
| BI | 247 | Alarm number 200 | Status if alarm number 200 is active. | Read | ||
| BI | 248 | Info number 1 | Status if info number 1 is active | Read | ||
| BI | 249 | Info number 2 | Status if info number 2 is active | Read | ||
| BI | 250 | Info number 3 | Status if info number 3 is active. | Read | ||
| BI | 347 | Info number 100 | Status if info number 100 is active. | Read | ||
| BVmin | 0 | Alarm reset | Resets tripped alarms. | Write | ||
| BV | 1 | SA Boosting func. | Setting for activating the boost function for the supply air fan | Write | ||
| BV | 2 | EA Boosting func. | Setting for activating the boost function for the extract air fan. | Write | ||
| BV | 3 | R.HX. Defrost func. | Write | |||
| BV | 7 | Cool operation mode | Setting for cooling between off and auto operation. | Write | ||
| BV | 8 | Int. Night heat func. | Setting for activating the intermittent night heat function. | Write | ||
| BV | 9 | Damper func. | Write | |||
| BV | 10 | Summer night cooling | Setting for activating the summer night cool function. | Write | ||
| BV | 11 | Temp displacement | Write | |||
| BV | 12 | Outdoor temp compensation | Write | |||
| BV | 13 | Outdoor airflow compensation | Setting for activating the outdoor airflow compensation function. | Write | ||
| BV | 14 | Auto. Summer/winter switch | Write | |||
| BV | 15 | Switch clock func. | Setting for switch clock function type. | Write | 0=Stop - low speed - high speed, 1=Low speed - high speed | |
| BV | 16 | Internal fire alarm func. | Setting for activating the internal fire alarm function. | Write | ||
| BV | 18 | External alarm 1 active at closure | Setting for external alarm number 1 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 19 | External alarm 2 active at closure | Setting for external alarm number 2 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 21 | Dewpoint reg. func. | Setting for activating the dewpoint regulator function. | Write | ||
| BV | 22 | Dehumid reg. func. | Setting for activating the dehumid regulator function. | Write | ||
| BV | 23 | External fire alarm func. | Setting for external fire resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 24 | External alarm 1 func. | Setting for external alarm 1 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 25 | External alarm 2 func. | Setting for external alarm 2 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 26 | Temperature alarm func. | Write | |||
| BV | 27 | Int. Night heat output func. | Write | 0=IQnomic, 1=IQnomic+ | ||
| BV | 28 | AYC heat out comp. func. | Write | 0=Inactive, 1=Active | ||
| BV | 29 | AYC heat room comp. func. | Setting for selecting the AYC room comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 30 | AYC heat room comp. night block func. | Write | 0=Inactive, 1=Active | ||
| BV | 31 | AYC heat night comp. func. | Setting for selecting the AYC night comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 32 | AYC heat valve signal func. | Write | 0=Inactive, 1=Active | ||
| BV | 33 | AYC cool out comp. func. | Write | 0=Inactive, 1=Active | ||
| BV | 34 | AYC cool room comp. func. | Setting for selecting the AYC room comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 35 | AYC cool room comp. night block func. | Write | 0=Inactive, 1=Active | ||
| BV | 36 | AYC cool night comp. func. | Setting for selecting the AYC night comp. chilled water function | Write | 0=Inactive, 1=Active | |
| BV | 37 | AYC cool valve signal func. | Write | 0=Inactive, 1=Active | ||
| BV | 38 | BB func. | Setting for selecting the Blue Box function. (from PV 6.05) | Write | 0=Inactive, 1=Active | |
| BV | 39 | BB optimize temp. func. | Setting for selecting the Blue Box optimize temperature function. (from PV 6.05) | Write | 0=Inactive, 1=Active | |
| BV | 40 | Season heat mode | Setting for selecting season heating mode. (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 41 | Steam humid alarm input | Setting for selecting steam humidification alarm input. (from PV 6.08) | Write | 0=NO(Alarm at open input), 1=NC(Alarm at closed input) | |
| BV | 42 | ReCO2 zero cal. | Setting for selecting zero calibration of ReCO2 pressure sensor. (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 43 | EA flow zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 44 | SA flow zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 45 | SA filt zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 46 | EA filt zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 47 | SA duct zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 48 | EA duct zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 49 | R.HX zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 50 | SA pre-filt zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 51 | EA pre-filt zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 52 | SA end-filt zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 53 | NU B zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 54 | NU C zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 55 | NU D zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 56 | NU E zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 57 | NU F zero cal. | (from PV 6.08) | Write | 0=Inactive, 1=Active | |
| BV | 58 | ReCO2 man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 59 | EA flow man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 60 | SA flow man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 61 | SA filt man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 62 | EA filt man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 63 | SA duct man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 64 | EA duct man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 65 | R.HX man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 66 | SA pre-filt man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 67 | EA pre-filt man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 68 | SA end-filt man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 69 | NU B man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 70 | NU C man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 71 | NU D man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 72 | NU E man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| BV | 73 | NU F man mode zero cal. | (from PV 6.08) | Write | 0=Auto, 1=Manual | |
| NC | 0 | NC 00 A-Alarm | (from PV 5.15) | Read | ||
| NC | 1 | NC 00 B-Alarm | (from PV 5.15) | Read |
No points match these filters.
Object ID lookup: Swegon GOLD generation C/D point IDs by name
AI0SA AirflowAI1SA Airflow regulatorAI2EA AirflowAI3EA Airflow regulatorAI4SA Duct pressureAI5SA Duct pressure regulatorAI6EA Duct pressureAI7EA Duct pressure regulatorAI8SA VAV demand/boost inputAI9SA VAV demand regulatorAI10EA VAV demand/boost inputAI11EA VAV demand regulatorAI12SA Fan levelAI13EA Fan levelAI14SA Fan powerAI15EA Fan powerAI16SFPAI17SA FrequencyAI18EA FrequencyAI19SA VoltageAI20EA VoltageAI21SA CurrentAI22EA CurrentAI23SA Airflow pressureAI24EA Airflow pressureAI25SA Temp regulatorAI26EA Temp regulatorAI27SA TemperatureAI28EA/Room temperatureAI29Outdoor temperatureAI30EA/Room temperature externalAI31Outdoor temperature externalAI32Anti frost temperatureAI33Temperature sensor 3AI34Temperature sensor 4AI35Rotary heat exchanger levelAI36Reheat levelAI37SA Down regulation levelAI38Extra regulation sequence levelAI39Cooling levelAI40Heating boost levelAI41Cooling boost levelAI42HX pressure levelAI43HX pressure alarm limitAI44HX temperatureAI45Effect reduction levelAI46Anti frost temp setpoint/operationAI47Anti frost temp setpoint/stopAI48Anti frost temp alarm limitAI49Supply air filter pressure levelAI50Supply air filter pressure alarm limit.AI51Supply air filter pressure level, newAI52Extract air filter pressure levelAI53Extract air filter pressure alarm limit.AI54Extract air filter pressure level, newAI55Temperature displacementAI56Coil typeAI57Cool step timeAI58Cool relay 1 restart timeAI59Cool relay 2 restart timeAI60Program version, HMIAI61Program version, HMl-slaveAI62Program version, main controller.AI63Program version, SA FC-1.AI64Program version, SA FC-2.AI65Program version, EA FC-1.AI66Program version, EA FC-2.AI67Program version, HX control unitAI68WeekdayAI69Extended low speed op. HoursAI70Extended low speed op. MinutesAI71Extended high speed op. HoursAI72Extended high speed op. MinutesAI73SA Fan operation timeAI74EA Fan operation timeAI75Cool operation timeAI76Heat exchange operation timeAI77Reheat operation timeAI78Present tripped alarmAI79Active not tripped alarm no.1AI80Active not tripped alarm no.2AI81Active not tripped alarm no.3AI82SA Fan sizeAI83EA Fan sizeAI84Operation mode 1AI85Operation mode 2AI86Operation mode, manualAI87Copy of Input Status 1-16.AI88Copy of Input Status 17-32.AI89Copy of Input Status 33-48.AI90Heat exchanger regulatorAI91Extract air-humidityAI92Extract air-humidity temperatureAI93Extract air-dewpointAI94AYC chilled water temperatureAI95AYC chilled water temperature regulatorAI96AYC chilled water outputAI97Supply air-dewpoint regulatorAI98Supply air-humidityAI99Supply air-humidity temperatureAI100Supply air-dewpointAI101C.HX. TemperatureAI102P.HX. Temperature 1AI103P.HX. Temperature 2AI104P/C.HX. HumidityAI105R.HX. EfficiencyAI106C.HX. Valve outputAI107P.HX bypass outputAI108Supply air pre-filter pressure levelAI109Supply air pre-filter pressure alarm limit.AI110Supply air pre-filter pressure level, newAI111Extract air pre-filter pressure levelAI112Extract air pre-filter pressure alarm limit.AI113Extract air pre-filter pressure level, newAI114Xzone reheat levelAI115Xzone anti frost temperatureAI116Xzone cooling levelAI117Xzone cool step timeAI118Xzone cool relay 1 restart timeAI119Xzone cool relay 2 restart timeAI120Xzone SA Temp regulatorAI121Xzone EA Temp regulatorAI122Xzone SA TemperatureAI123Xzone EA/Room temperatureAI124Pre-heating air temperatureAI125Pre-heating levelAI126Pre-heating anti frost temperatureAI127ReCO2 CO2 inputAI128ReCO2 internal damper outputAI129ReCO2 external damper outputAI130ReCO2 outdoor airflowAI131ReCO2 outdoor airflow regulatorAI132ReCO2 outdoor airflow pressureAI133Preheat operation timeAI134Xzone cool operation timeAI135Xzone reheat operation timeAI136Supply air-D temperatureAI137Extract air-D temperatureAI138AYC heat temperatureAI139AYC heat temp regulatorAI140AYC heat valve outputAI141Min/Max/Average Sens1TempAI142Min/Max/Average Sens2TempAI143Min/Max/Average Sens3TempAI144Min/Max/Average Sens4TempAI145Miru 1 AirflowAI146Miru 1 Airflow regulatorAI147Miru 1 PressureAI148Miru 1 Pressure regulatorAI149Miru 1 Outdoor temperatureAI150Miru 1 Operation timeAI151Miru 1 Fan levelAI152Miru 1 Fan powerAI153Miru 1 SFPAI154Miru 1 KWHAI155Miru 1 MWHAI156Miru 2 AirflowAI157Miru 2 Airflow regulatorAI158Miru 2 PressureAI159Miru 2 Pressure regulatorAI160Miru 2 Outdoor temperatureAI161Miru 2 Operation timeAI162Miru 2 Fan levelAI163Miru 2 Fan powerAI164Miru 2 SFPAI165Miru 2 KWHAI166Miru 2 MWHAI167Miru 3 AirflowAI168Miru 3 Airflow regulatorAI169Miru 3 PressureAI170Miru 3 Pressure regulatorAI171Miru 3 Outdoor temperatureAI172Miru 3 Operation timeAI173Miru 3 Fan levelAI174Miru 3 Fan powerAI175Miru 3 SFPAI176Miru 3 KWHAI177Miru 3 MWHAI178Miru 4 AirflowAI179Miru 4 Airflow regulatorAI180Miru 4 PressureAI181Miru 4 Pressure regulatorAI182Miru 4 Outdoor temperatureAI183Miru 4 Operation timeAI184Miru 4 Fan levelAI185Miru 4 Fan powerAI186Miru 4 SFPAI187Miru 4 KWHAI188Miru 4 MWHAI189Miru 5 AirflowAI190Miru 5 Airflow regulatorAI191Miru 5 PressureAI192Miru 5 Pressure regulatorAI193Miru 5 Outdoor temperatureAI194Miru 5 Operation timeAI195Miru 5 Fan levelAI196Miru 5 Fan powerAI197Miru 5 SFPAI198Miru 5 KWHAI199Miru 5 MWHAI200Miru 6 AirflowAI201Miru 6 Airflow regulatorAI202Miru 6 PressureAI203Miru 6 Pressure regulatorAI204Miru 6 Outdoor temperatureAI205Miru 6 Operation timeAI206Miru 6 Fan levelAI207Miru 6 Fan powerAI208Miru 6 SFPAI209Miru 6 KWHAI210Miru 6 MWHAI211Miru 7 AirflowAI212Miru 7 Airflow regulatorAI213Miru 7 PressureAI214Miru 7 Pressure regulatorAI215Miru 7 Outdoor temperatureAI216Miru 7 Operation timeAI217Miru 7 Fan levelAI218Miru 7 Fan powerAI219Miru 7 SFPAI220Miru 7 KWHAI221Miru 7 MWHAI222Miru 8 AirflowAI223Miru 8 Airflow regulatorAI224Miru 8 PressureAI225Miru 8 Pressure regulatorAI226Miru 8 Outdoor temperatureAI227Miru 8 Operation timeAI228Miru 8 Fan levelAI229Miru 8 Fan powerAI230Miru 8 SFPAI231Miru 8 KWHAI232Miru 8 MWHAI233Miru 9 AirflowAI234Miru 9 Airflow regulatorAI235Miru 9 PressureAI236Miru 9 Pressure regulatorAI237Miru 9 Outdoor temperatureAI238Miru 9 Operation timeAI239Miru 9 Fan levelAI240Miru 9 Fan powerAI241Miru 9 SFPAI242Miru 9 KWHAI243Miru 9 MWHAI244Miru 10 AirflowAI245Miru 10 Airflow regulatorAI246Miru 10 PressureAI247Miru 10 Pressure regulatorAI248Miru 10 Outdoor temperatureAI249Miru 10 Operation timeAI250Miru 10 Fan levelAI251Miru 10 Fan powerAI252Miru 10 SFPAI253Miru 10 KWHAI254Miru 10 MWHAI255BB Operation modeAI256BB Cool temp regulatorAI257BB Heat temp regulatorAI258BB Supply water temperatureAI259BB Return water temperatureAI260BB Supply pre-coil temperatureAI261Extended ext. reg. seq. frost tempAI262Extended ext. reg. seq. OutputAI263Steam humid outputAI264End-filter pressure levelAI265End-filter pressure level, newAI266End-filter pressure alarm limitAV0SA Low speed airflow setpointAV1SA High speed airflow setpointAV2SA Max speed airflow setpointAV3SA Min speed airflow setpointAV4EA Low speed airflow setpointAV5EA High speed airflow setpointAV6EA Max speed airflow setpointAV7EA Min speed airflow setpointAV8SA Low speed pressure setpointAV9SA High speed pressure setpointAV10SA Max speed output signalAV11SA Max speed pressure setpointAV12EA Low speed pressure setpointAV13EA High speed pressure setpointAV14EA Max speed output signalAV15EA Max speed pressure setpointAV16SA Low speed demand setpointAV17SA High speed demand setpointAV18EA Low speed demand setpointAV19EA High speed demand setpointAV20SA Airflow regulation zoneAV21SA Airflow C-factorAV22EA Airflow regulation zoneAV23EA Airflow C-factorAV24SA Pressure regulation zoneAV25SA Pressure C-factorAV26EA Pressure regulation zoneAV27EA Pressure C-factorAV28SA Demand P-band.AV29SA Demand C-factorAV30EA Demand P-band.AV31EA Demand C-factorAV32ERS 1 DiffAV33ERS 1 BreakpointAV34ERS 2 Breakpoint X1AV35ERS 2 Breakpoint Y1AV36ERS 2 Breakpoint X2AV37ERS 2 Breakpoint Y2AV38ERS 2 Breakpoint X3AV39ERS 2 Breakpoint Y3AV40SA Temperature setpointAV41EA/Room Temperature setpointAV42SA Min temp setpointAV43SA Max temp setpointAV44SA Temperature P-bandAV45EA/Room Temperature P-bandAV46SA HX. Reg C-factorAV47EA/Room HX. Reg C-factorAV48SA Heat Reg C-factorAV49EA/Room Heat Reg C-factorAV50SA Extra Reg heat C-factorAV51SA Extra Reg cool C-factorAV52EA Extra Reg heat C-factorAV53EA Extra Reg cool C-factorAV54SA Down regulation Reg C-factorAV56SA Cool reg C-factorAV57EA/Room Cool reg C-factorAV58SA Cooling boost C-factorAV59EA/Room Cooling boost reg C-factorAV60HX Pressure alarm set.AV61P/C.HX. defrost P-bandAV62P/C.HX. defrost C-factorAV63Cooling off set.AV64SA Down regulation neutral zoneAV65Cool Outdoor temp limit.1AV66Cool Outdoor temp limit.2AV67Cool Outdoor temp limit.3AV68Temperature reg. Neutral zoneAV69SA Cool min air flowAV70EA Cool min air flowAV71Heating boost start limitAV72Cooling boost start limitAV73SA Filter alarm limitAV74EA Filter alarm limitAV75Int. Night heat room start tempAV76Int. Night heat room stop tempAV77Int. Night heat SA temp setpointAV78Int. Night heat SA airflow setpointAV79Int. Night heat EA airflow setpointAV80Summer night cool EA start tempAV81Summer night cool EA stop tempAV82Summer night cool outdoortemp limitAV83Summer night cool SA temp setpointAV84Outdoor temp comp. Winter X1.AV85Outdoor temp comp. Winter X2.AV86Outdoor temp comp. Winter Y1.AV87Outdoor temp comp. Summer X3.AV88Outdoor temp comp. Summer X4.AV89Outdoor temp comp. Summer Y2.AV90Outdoor airflow comp. Winter X1.AV91Outdoor airflow comp. Winter X2.AV92Outdoor airflow comp. Winter Y1.AV93Extra Reg. Sequence max outputAV94EA/Room min temp alarm limitAV95SA Deviation alarm limitAV97SA Fan regulation modeAV98EA Fan regulation modeAV99ERS StepAV100Temperature regulation mode.AV101Cooling off periodAV102Cool step time setAV103Cool restart timeAV104Cool regulation modeAV105Heating boost regulation mode.AV106Cooling boost regulation mode.AV107Filter calibration modeAV108Air adjustment time, minutesAV109Air adjustment time, hoursAV110Hand terminal languageAV111Summer night cool start, hourAV112Summer night cool start, minuteAV113Summer night cool stop, hourAV114Summer night cool stop, minuteAV115Extra regulation sequence cool modeAV116Extra regulation sequence heat modeAV117Morning boost time, hoursAV118Morning boost time, minutesAV119Startup timeAV120Start delay SA fan.AV121Start delay EA fan.AV122Air flow unitAV124YearAV125MonthAV126DateAV127HourAV128MinuteAV129SecondAV130Time channel 1 statusAV131Time channel 1 start hourAV132Time channel 1 start minuteAV133Time channel 1 stop hourAV134Time channel 1 stop minuteAV135Time channel 2 statusAV136Time channel 2 start hourAV137Time channel 2 start minuteAV138Time channel 2 stop hourAV139Time channel 2 stop minuteAV140Time channel 3 statusAV141Time channel 3 start hourAV142Time channel 3 start minuteAV143Time channel 3 stop hourAV144Time channel 3 stop minuteAV145Time channel 4 statusAV146Time channel 4 start hourAV147Time channel 4 start minuteAV148Time channel 4 stop hourAV149Time channel 4 stop minuteAV150Time channel 5 statusAV151Time channel 5 start hourAV152Time channel 5 start minuteAV153Time channel 5 stop hourAV154Time channel 5 stop minuteAV155Time channel 6 statusAV156Time channel 6 start hourAV157Time channel 6 start minuteAV158Time channel 6 stop hourAV159Time channel 6 stop minuteAV160Time channel 7 statusAV161Time channel 7 start hourAV162Time channel 7 start minuteAV163Time channel 7 stop hourAV164Time channel 7 stop minuteAV165Time channel 8 statusAV166Time channel 8 start hourAV167Time channel 8 start minuteAV168Time channel 8 stop hourAV169Time channel 8 stop minuteAV170Extended low speed op. Hours setAV171Extended low speed op. Minutes setAV172Extended high speed op. Hours setAV173Extended high speed op. Minutes setAV174Communication operation modeAV175Service period alarm.AV176External alarm 1 delayAV177External alarm 2 delayAV178Int. Night heat SA pressure setpointAV179Int. Night heat EA pressure setpointAV180Copy of Coil Status 1-16AV181Copy of Coil Status 17-32AV182Copy of Coil Status 33-48AV183Heat relay periodic func.AV184Cool relay 1 periodic func.AV185Cool relay 2 periodic func.AV186Slave control C-factorAV187SA dehumid P-bandAV188SA dehumid C-factorAV189Dewpoint reg. P-bandAV190Dewpoint reg. C-factorAV191AYC chilled water temperature setAV192Dewpoint neutral zoneAV193Comp. airflowAV194Supply air-humidity_setAV195Water heating periodic op. timeAV196Water heating intervalAV197Cool periodic op. timeAV198Cool intervalAV199P/C.HX. bypass adj.AV200EA/Room temperature external func.AV201EA/Room temperature com.AV202Outdoor temperature external func.AV203Outdoor temperature com.AV204Timeout temperature com.AV205Flow at fire function.AV206Air fan down regulation func.AV207SA speed at fire.AV208EA speed at fire.AV209Temperature alarm setpoint.AV210Temperature alarm time.AV211Supply air min P-band.AV212Supply air min C-factor.AV213Supply air max P-band.AV214Supply air max C-factor.AV215Year channel 1 function.AV216Year channel 1 start year.AV217Year channel 1 start month.AV218Year channel 1 start date.AV219Year channel 1 start hour.AV220Year channel 1 start minute.AV221Year channel 1 stop year.AV222Year channel 1 stop month.AV223Year channel 1 stop date.AV224Year channel 1 stop hour.AV225Year channel 1 stop minute.AV226Year channel 2 function.AV227Year channel 2 start year.AV228Year channel 2 start month.AV229Year channel 2 start date.AV230Year channel 2 start hour.AV231Year channel 2 start minute.AV232Year channel 2 stop year.AV233Year channel 2 stop month.AV234Year channel 2 stop date.AV235Year channel 2 stop hour.AV236Year channel 2 stop minute.AV237Year channel 3 function.AV238Year channel 3 start year.AV239Year channel 3 start month.AV240Year channel 3 start date.AV241Year channel 3 start hour.AV242Year channel 3 start minute.AV243Year channel 3 stop year.AV244Year channel 3 stop month.AV245Year channel 3 stop date.AV246Year channel 3 stop hour.AV247Year channel 3 stop minute.AV248Year channel 4 function.AV249Year channel 4 start year.AV250Year channel 4 start month.AV251Year channel 4 start date.AV252Year channel 4 start hour.AV253Year channel 4 start minute.AV254Year channel 4 stop year.AV255Year channel 4 stop month.AV256Year channel 4 stop date.AV257Year channel 4 stop hour.AV258Year channel 4 stop minute.AV259Year channel 5 function.AV260Year channel 5 start year.AV261Year channel 5 start month.AV262Year channel 5 start date.AV263Year channel 6 start hour.AV264Year channel 5 start minute.AV265Year channel 5 stop year.AV266Year channel 5 stop month.AV267Year channel 5 stop date.AV268Year channel 5 stop hour.AV269Year channel 5 stop minute.AV270Year channel 6 function.AV271Year channel 6 start year.AV272Year channel 6 start month.AV273Year channel 6 start date.AV274Year channel 6 start hour.AV275Year channel 6 start minute.AV276Year channel 6 stop year.AV277Year channel 6 stop month.AV278Year channel 6 stop date.AV279Year channel 6 stop hour.AV280Year channel 6 stop minute.AV281Year channel 7 function.AV282Year channel 7 start year.AV283Year channel 7 start month.AV284Year channel 7 start date.AV285Year channel 7 start hour.AV286Year channel 7 start minute.AV287Year channel 7 stop year.AV288Year channel 7 stop month.AV289Year channel 7 stop date.AV290Year channel 7 stop hour.AV291Year channel 7 stop minute.AV292Year channel 8 function.AV293Year channel 8 start year.AV294Year channel 8 start month.AV295Year channel 8 start date.AV296Year channel 8 start hour.AV297Year channel 8 start minute.AV298Year channel 8 stop year.AV299Year channel 8 stop month.AV300Year channel 8 stop date.AV301Year channel 8 stop hour.AV302Year channel 8 stop minute.AV303Filter select.AV304Pre-filter select.AV305SA pre-filter alarm limit.AV306EA pre-filter alarm limit.AV307Pre-filter calibration mode.AV308Xzone reheat function.AV309Xzone cooling function.AV310Xzone temperature reg. Neutral zone.AV311Xzone temperature regulation mode.AV312Xzone ERS Step.AV313Xzone ERS 1 Diff.AV314Xzone ERS 1 Breakpoint.AV315Xzone ERS 2 Breakpoint X1.AV316Xzone ERS 2 Breakpoint Y1.AV317Xzone ERS 2 Breakpoint X2.AV318Xzone ERS 2 Breakpoint Y2.AV319Xzone ERS 2 Breakpoint X3.AV320Xzone ERS 2 Breakpoint Y3.AV321Xzone SA Temperature setpoint.AV322Xzone EA/Room Temperature setpoint.AV323Xzone SA Min temp setpoint.AV324Xzone SA Max temp setpointAV325Pre-heating function.AV326Pre-heating setpoint.AV327Xzone P-band.AV328Xzone SA reheat C-factor.AV329Xzone SA cooling C-factor.AV330Xzone EA reheat C-factor.AV331Xzone EA cooling C-factor.AV332Xzone SA min P-band.AV333Xzone SA min C-factor.AV334Xzone SA max P-band.AV335Xzone SA max C-factor.AV336Preheat P-band.AV337Preheat C-factor.AV338ReCO2 CO2 function.AV339ReCO2 CO2 setpoint.AV340ReCO2 cooling function.AV341ReCO2 heating function.AV342ReCO2 min outdoor air.AV343ReCO2 min exhaust air.AV344ReCO2 CO2 P-band.AV345ReCO2 CO2 C-factor.AV346ReCO2 CO2 flow C-factor.AV347ReCO2 heating C-factor.AV348ReCO2 cooling C-factor.AV349AYC function.AV350AYC heat temp set.AV351AYC night comp. channel.AV352AYC channel start hour.AV353AYC channel start minute.AV354AYC channel stop hour.AV355AYC channel stop minute.AV356AYC channel period.AV357AYC heat P-band.AV358AYC heat C-factor.AV359AYC cool P-band.AV360AYC cool C-factor.AV361AYC heat out comp. X1.AV362AYC heat out comp. Y1.AV363AYC heat out comp. X2.AV364AYC heat out comp. Y2.AV365AYC heat out comp. X3.AV366AYC heat out comp. Y3.AV367AYC heat room comp. temp limit.AV368AYC heat room comp P-band.AV369AYC heat night comp temp.AV370AYC heat pump on temp.AV371AYC heat pump off temp.AV372AYC heat pump alarm.AV373AYC heat per op function.AV374AYC heat per op time.AV375AYC heat per op interval.AV376AYC cool out comp. X1.AV377AYC cool out comp. Y1.AV378AYC cool out comp. X2.AV379AYC cool out comp. Y2.AV380AYC cool out comp. X3.AV381AYC cool out comp. Y3.AV382AYC cool room comp. temp limit.AV383AYC cool room comp. P-band.AV384AYC cool night comp temp.AV385AYC cool pump on temp.AV386AYC cool pump off temp.AV387AYC cool pump alarm.AV388AYC cool per op function.AV389AYC cool per op time.AV390AYC cool per op interval.AV391IO-mod 3 output 1 function.AV392IO-mod 3 output 2 function.AV393Humid reg. func.AV394Humid reg. Start.AV395Humid reg. Stop.AV396Min/Max/Average SensNumberAV397Min/Max/Average SensFunctionAV398Miru 1 Low speed airflow setpointAV399Miru 1 High speed airflow setpointAV400Miru 1 Low speed pressure setpointAV401Miru 1 High speed pressure setpointAV402Miru 2 Low speed airflow setpointAV403Miru 2 High speed airflow setpointAV404Miru 2 Low speed pressure setpointAV405Miru 2 High speed pressure setpointAV406Miru 3 Low speed airflow setpointAV407Miru 3 High speed airflow setpointAV408Miru 3 Low speed pressure setpointAV409Miru 3 High speed pressure setpointAV410Miru 4 Low speed airflow setpointAV411Miru 4 High speed airflow setpointAV412Miru 4 Low speed pressure setpointAV413Miru 4 High speed pressure setpointAV414Miru 5 Low speed airflow setpointAV415Miru 5 High speed airflow setpointAV416Miru 5 Low speed pressure setpointAV417Miru 5 High speed pressure setpointAV418Miru 6 Low speed airflow setpointAV419Miru 6 High speed airflow setpointAV420Miru 6 Low speed pressure setpointAV421Miru 6 High speed pressure setpointAV422Miru 7 Low speed airflow setpointAV423Miru 7 High speed airflow setpointAV424Miru 7 Low speed pressure setpointAV425Miru 7 High speed pressure setpointAV426Miru 8 Low speed airflow setpointAV427Miru 8 High speed airflow setpointAV428Miru 8 Low speed pressure setpointAV429Miru 8 High speed pressure setpointAV430Miru 9 Low speed airflow setpointAV431Miru 9 High speed airflow setpointAV432Miru 9 Low speed pressure setpointAV433Miru 9 High speed pressure setpointAV434Miru 10 Low speed airflow setpointAV435Miru 10 High speed airflow setpointAV436Miru 10 Low speed pressure setpointAV437Miru 10 High speed pressure setpointAV438BB Cool temp setpointAV439BB Heat temp setpointAV440BB Unit typeAV441BB Optimize upper valve limitAV442BB Optimize lower valve limitAV443BB Optimize delayAV444BB Cool optimize upAV445BB Cool optimize downAV446BB Heat optimize upAV447BB Heat optimize downAV448BB Cool optimize diff temperatureAV449BB Heat optimize diff temperatureAV450BB AQUA Link functionAV451BB AQUA Link cool pump alarm functionAV452BB AQUA Link heat pump alarm functionAV453Extended ext. reg. seq. reheat functionAV454Season heat mode setpointAV455Season heat functionAV456Steam humid extract air setpointAV457Steam humid supply air max limitAV458Steam humid extract air P-bandAV459Steam humid extract air C-factorAV460Steam humid supply air max P-bandAV461Steam humid supply air max C-factorAV462End-filter alarm limitAV463End-filter selectAV464End-filter calibrationBI0Heat outputBI1Cool output 1BI2Cool output 2BI3Low speed outputBI4High speed outputBI5A-alarm.BI6B-alarm.BI7Operation outputBI8Damper outputBI9External low speed inputBI10External high speed inputBI11External alarm 1 inputBI12External alarm 2 inputBI13External fire alarm input.BI14External stop inputBI15DIP Switch 1BI16DIP Switch 2BI17DIP Switch 3BI18DIP Switch 4BI19DIP Switch 5BI20DIP Switch 6BI21AYC heat pump outputBI22AYC cool pump outputBI23C.HX. pump outputBI24R.HX rotation monitorBI25Xzone heat outputBI26Xzone cool output 1BI27Xzone cool output 2BI28Pre-heat outputBI29IO-mod 3 output 1BI30IO-mod 3 output 2BI31IO-mod 4 output 1BI32Miru 1 AlarmBI33Miru 2 AlarmBI34Miru 3 AlarmBI35Miru 4 AlarmBI36Miru 5 AlarmBI37Miru 6 AlarmBI38Miru 7 AlarmBI39Miru 8 AlarmBI40Miru 9 AlarmBI41Miru 10 AlarmBI42Extended ext. reg. seq. PumpBI43Season heating modeBI48Alarm number 1BI49Alarm number 2BI50Alarm number 3BI247Alarm number 200BI248Info number 1BI249Info number 2BI250Info number 3BI347Info number 100BV0Alarm resetBV1SA Boosting func.BV2EA Boosting func.BV3R.HX. Defrost func.BV7Cool operation modeBV8Int. Night heat func.BV9Damper func.BV10Summer night coolingBV11Temp displacementBV12Outdoor temp compensationBV13Outdoor airflow compensationBV14Auto. Summer/winter switchBV15Switch clock func.BV16Internal fire alarm func.BV18External alarm 1 active at closureBV19External alarm 2 active at closureBV21Dewpoint reg. func.BV22Dehumid reg. func.BV23External fire alarm func.BV24External alarm 1 func.BV25External alarm 2 func.BV26Temperature alarm func.BV27Int. Night heat output func.BV28AYC heat out comp. func.BV29AYC heat room comp. func.BV30AYC heat room comp. night block func.BV31AYC heat night comp. func.BV32AYC heat valve signal func.BV33AYC cool out comp. func.BV34AYC cool room comp. func.BV35AYC cool room comp. night block func.BV36AYC cool night comp. func.BV37AYC cool valve signal func.BV38BB func.BV39BB optimize temp. func.BV40Season heat modeBV41Steam humid alarm inputBV42ReCO2 zero cal.BV43EA flow zero cal.BV44SA flow zero cal.BV45SA filt zero cal.BV46EA filt zero cal.BV47SA duct zero cal.BV48EA duct zero cal.BV49R.HX zero cal.BV50SA pre-filt zero cal.BV51EA pre-filt zero cal.BV52SA end-filt zero cal.BV53NU B zero cal.BV54NU C zero cal.BV55NU D zero cal.BV56NU E zero cal.BV57NU F zero cal.BV58ReCO2 man mode zero cal.BV59EA flow man mode zero cal.BV60SA flow man mode zero cal.BV61SA filt man mode zero cal.BV62EA filt man mode zero cal.BV63SA duct man mode zero cal.BV64EA duct man mode zero cal.BV65R.HX man mode zero cal.BV66SA pre-filt man mode zero cal.BV67EA pre-filt man mode zero cal.BV68SA end-filt man mode zero cal.BV69NU B man mode zero cal.BV70NU C man mode zero cal.BV71NU D man mode zero cal.BV72NU E man mode zero cal.BV73NU F man mode zero cal.NC0NC 00 A-AlarmNC1NC 00 B-Alarm
Integration notes
- Taken from GB.BACnet480.121017 (pp3-49). Only the first page of each object section has a text layer; the rest are images, read by OCR and checked against zoomed page renders. Instances missing from the OCR were filled from the printed sequence and the pages were checked by eye where they jumped.
- Access follows the section headings: Analog Inputs and Binary Inputs read-only, Analog Values and Binary Values read/write.
- The guide prints only the first and last objects of two long ranges: BI 48-50 and BI 247 (Alarm number 1-3 and 200) and BI 248-250 and BI 347 (Info number 1-3 and 100). Going by those rows, Alarm number n is BI 47+n and Info number n is BI 247+n; only the printed rows are listed here.
- Instances not printed in the guide (AV 55, AV 96, AV 123, BI 44-47, BV 4-6, BV 17, BV 20) are left out.
- The Misc column marks the program version that added an object (PV 5.10 to 6.08); it is shown in the description as "from PV x". Descriptions keep the printed Min/Max range.
- This is an older generation than the GOLD E list (different instance numbers); Compact / GOLD LP units have their own list.
- AV 263 is printed as 'Year channel 6 start hour.' although it sits in the channel 5 block; the name is kept as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation C/D (RX/PX/CX/SD) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP
How many BACnet points does the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP have?
This list has 852 BACnet objects: 267 analog inputs, 462 analog values, 52 binary inputs, 69 binary values, 2 notification classs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet points are writable?
531 of the 852 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet documentation?
The source is BACnet IP GOLD RX/PX/CX/SD, Generation C/D (program version 6.08) (GB.BACnet480.121017), published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-d-2010-2013/communication/_en/bacnet480.6.08.pdf.
What are the minimum BACnet points to integrate the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?
Start with AV 174 Communication operation mode (BMS stop / low / high speed command (0 = Auto)); AV 40 SA Temperature setpoint (Supply air temperature setpoint); AV 41 EA/Room Temperature setpoint (Extract/room temperature setpoint); BV 0 Alarm reset (Resets alarms); AI 84 Operation mode 1 (Actual operating mode and what stopped the unit); AI 27 SA Temperature (Supply air temperature); AI 28 EA/Room temperature (Extract/room temperature); AI 29 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 5 A-alarm. (Any A-class alarm); BI 6 B-alarm. (Any B-class alarm).
How do I enable BMS control of the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?
AV 174 Communication operation mode: 0=Auto (normal stop when the time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (PV 5.00 or later; intermittent night heat and morning boost still work). AI 84 Operation mode 1 shows whether the unit is stopped or running from the hand terminal, an external input, communication or a time/year channel.
Can the BMS supply sensor values to the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?
Room temperature can come from the BMS: set AV 200 EA/Room temperature external func. to 2 (Communication) and write AV 201. Outdoor temperature works the same with AV 202 = 2 and AV 203. AV 204 sets the timeout for these communicated temperatures.
How do I check these points on the real GOLD generation C/D (RX/PX/CX/SD) BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
- Air handling unit controller
Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
Swegon COMPACT and GOLD LP air handling units with controller program version 2.01 or later.
Also known as: COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480 - Air handling unit controller
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation E (RX, PX, CX and SD versions) running program version 1.10 or later.
Also known as: GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316 - Air handling unit controller
Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
Swegon GOLD air handling units of generations E and F (RX, PX, CX and SD versions) with program version 2.48.
Also known as: GOLD F, GOLD version F, GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_F_BACnet_251202 - Other equipment (demand-controlled ventilation system controller)
Swegon SuperWISE (generation 1) BACnet IP - system objects
Swegon SuperWISE (first generation) system controllers for WISE demand-controlled ventilation, program version 1.25.
Also known as: SuperWISE, Super WISE, WISE gen 1, GB.BACnetSuper WISE.140603, SuperWISE_BACnet_list_ver_1.3
Source: BACnet IP GOLD RX/PX/CX/SD, Generation C/D (program version 6.08) · GB.BACnet480.121017. Object names, instances and units are reproduced as published; descriptions are our own.