Air handling unit controller · BACnet points list

Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet points list

Updated 6 November 2026

Short answer

GOLD generation C/D air handlers have a BACnet IP driver built into the unit controller (program version 6.08), acting as a B-ASC; no gateway is needed. The list covers fan airflows, pressures, levels and power, temperatures and regulator setpoints, heat exchanger and coil data, accessory functions (Xzone, ReCO2, AYC, MIRU, Blue Box, steam humidifier), time and year channels, one binary input per alarm and info number, and calibration commands. The BMS starts, stops and selects speed through one analog value.

This page lists 852 BACnet objects for the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP — 531 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.

Manufacturer
Swegon
Model
GOLD generation C/D (RX/PX/CX/SD) BACnet IP
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
852 (531 writable)
Transport
BACnet IP
Firmware
Program version 6.08 or later
Also known as
GOLD C, GOLD D, GOLD RX, GOLD PX, GOLD CX, GOLD SD, GOLD version D, GB.BACnet480.121017, BACnet480
Source document
BACnet IP GOLD RX/PX/CX/SD, Generation C/D (program version 6.08) · GB.BACnet480.121017
Download CSV 852 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.

BMS integration notes: Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP

Integration in brief

Command the unit with AV 174 Communication operation mode (0 = Auto lets the time channels run it; 1-4 force stop or low/high speed) and read back AI 84 Operation mode 1 plus the low/high speed BIs. Adjust the main temperature setpoints (AV 40 supply, AV 41 extract/room) and the low/high speed airflow or pressure setpoints, and monitor BI 5/BI 6 for A/B alarms with BV 0 to reset. Page 3 of the guide lists these as the key points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 174Communication operation modeBMS stop / low / high speed command (0 = Auto)Write
AV 40SA Temperature setpointSupply air temperature setpointWrite
AV 41EA/Room Temperature setpointExtract/room temperature setpointWrite
BV 0Alarm resetResets alarmsWrite
AI 84Operation mode 1Actual operating mode and what stopped the unitRead
AI 27SA TemperatureSupply air temperatureRead
AI 28EA/Room temperatureExtract/room temperatureRead
AI 29Outdoor temperatureOutdoor air temp measured by the unit, °CRead
BI 5A-alarm.Any A-class alarmRead
BI 6B-alarm.Any B-class alarmRead

Enable & remote start

AV 174 Communication operation mode: 0=Auto (normal stop when the time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (PV 5.00 or later; intermittent night heat and morning boost still work). AI 84 Operation mode 1 shows whether the unit is stopped or running from the hand terminal, an external input, communication or a time/year channel.

Sensors & values from the BMS

Room temperature can come from the BMS: set AV 200 EA/Room temperature external func. to 2 (Communication) and write AV 201. Outdoor temperature works the same with AV 202 = 2 and AV 203. AV 204 sets the timeout for these communicated temperatures.

Network setup

Watch out for

Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

852 of 852 shown
Type
Other
Access
Show
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet Points List
DescriptionStates
AI0SA AirflowRange 0-20000l/sl/sRead
AI1SA Airflow regulatorPresent supply airflow regulator setpoint. Range 0-20000l/sl/sRead
AI2EA AirflowPresent extract airflow. Range 0-20000l/sl/sRead
AI3EA Airflow regulatorPresent extract airflow regulator setpoint. Range 0-20000l/sl/sRead
AI4SA Duct pressurePresent supply air duct pressure. Range 0-2000PaPaRead
AI5SA Duct pressure regulatorPresent supply air duct pressure regulator setpoint. Range 0-2000PaPaRead
AI6EA Duct pressurePresent extract air duct pressure. Range 0-2000PaPaRead
AI7EA Duct pressure regulatorPresent extract air duct pressure regulator setpoint. Range 0-2000PaPaRead
AI8SA VAV demand/boost inputRange 0-100.00%%Read
AI9SA VAV demand regulatorPresent supply air VAV demand regulator setpoint. Range 0-100.00%%Read
AI10EA VAV demand/boost inputRange 0-100.00%%Read
AI11EA VAV demand regulatorPresent supply air VAV demand regulator setpoint. Range 0-100.00%%Read
AI12SA Fan levelPresent running level for the supply air fan. Range 0-100.00%%Read
AI13EA Fan levelPresent running level for the extract air fan. Range 0-100.00%%Read
AI14SA Fan powerRange 0-32700W (from PV 6.04)WRead
AI15EA Fan powerRange 0-32700W (from PV 6.04)WRead
AI16SFPSFP supply air + extract air. Range 0.0-9.9Read
AI17SA FrequencyPresent frequency level for the supply air fan. Range 0-100.00HzHzRead
AI18EA FrequencyPresent frequency level for the extract air fan. Range 0-100.00HzHzRead
AI19SA VoltagePresent voltage level for the supply air fan. Range 0-500VVRead
AI20EA VoltagePresent voltage level for the extract air fan. Range 0-500VVRead
AI21SA CurrentRange 0-32.700A (from PV 6.04)ARead
AI22EA CurrentRange 0-32.700A (from PV 6.04)ARead
AI23SA Airflow pressurePresent airflow pressure in the supply air fan inlet. Range 0-2000PaPaRead
AI24EA Airflow pressurePresent airflow pressure inthe extract airfan inlet. Range 0-2000PaPaRead
AI25SA Temp regulatorPresent supply air temperature regulator setpoint. Range -55.00-125.00°C°CRead
AI26EA Temp regulatorPresent extract air temperature regulator setpoint. Range -55.00-125.00°C°CRead
AImin27SA TemperaturePresent supply air temperature. Range -55.00-125.00°C°CRead
AImin28EA/Room temperaturePresent extract air/room temperature in the unit. Range -55.00-125.00°C°CRead
AImin29Outdoor temperaturePresent outdoor air temperature in the unit. Range -55.00-125.00°C°CRead
AI30EA/Room temperature externalPresent room temperature external from the unit. Range -55.00-125.00°C°CRead
AI31Outdoor temperature externalPresent outdoor air temperature external from the unit. Range -55.00-125.00°C°CRead
AI32Anti frost temperatureRange -55.00-125.00°C°CRead
AI33Temperature sensor 3Present temperature for temp sensor no.3. Range -55.00-125.00°C°CRead
AI34Temperature sensor 4Present temperature for temp sensor no.4. Range -55.00-125.00°C°CRead
AI35Rotary heat exchanger levelPresent operation level from rotary heat exchanger. Range 0-100.00%%Read
AI36Reheat levelPresent level of reheat. Range 0-100.00%%Read
AI37SA Down regulation levelPresent level of supply airflow down regulation. Range 0-100.00%%Read
AI38Extra regulation sequence levelPresent level of the extra regulation sequence. Range 0-100.00%%Read
AI39Cooling levelPresent level of cooling. Range 0-100.00%%Read
AI40Heating boost levelPresent level of heating boost. Range 0-100.00%%Read
AI41Cooling boost levelPresent level of cooling boost. Range 0-100.00%%Read
AI42HX pressure levelPresent pressure drop for the rotary heat exchanger. Range 0-2000PaPaRead
AI43HX pressure alarm limitRange 0-2000PaPaRead
AI44HX temperatureRange 0-100.00°C°CRead
AI45Effect reduction levelRange 0-100.00%%Read
AI46Anti frost temp setpoint/operationRange 10.00-16.00°C°CRead
AI47Anti frost temp setpoint/stopRange 15.00-40.00°C°CRead
AI48Anti frost temp alarm limitRange 5.00-30.00°C°CRead
AI49Supply air filter pressure levelPresent supply air filter pressure drop. Range 0-2000PaPaRead
AI50Supply air filter pressure alarm limit.Present supply air filter pressure alarm limit. Range 0-2000PaPaRead
AI51Supply air filter pressure level, newSupply air filter pressure saved from calibration. Range 0-2000PaPaRead
AI52Extract air filter pressure levelPresent extract air filter pressure drop. Range 0-2000PaPaRead
AI53Extract air filter pressure alarm limit.Present extract air filter pressure alarm limit. Range 0-2000PaPaRead
AI54Extract air filter pressure level, newExtract air filter pressure saved from calibration. Range 0-2000PaPaRead
AI55Temperature displacementPresent temperature displacement from input signal. Range -5.00 - 5.00°C°CRead
AI56Coil typeRange 0-20Read
AI57Cool step timePresent time between cool step shift. Range 0-600ssRead
AI58Cool relay 1 restart timePresent time between two starts of cool relay 1. Range 0-900ssRead
AI59Cool relay 2 restart timePresent time between two starts of cool relay 2. Range 0-900ssRead
AI60Program version, HMIPresent program version for the hand terminal. Range 0-10.00Read
AI61Program version, HMl-slavePresent program version for the extra hand terminal. Range 0-10.00Read
AI62Program version, main controller.Present program version for the main control unit. Range 0-10.00Read
AI63Program version, SA FC-1.Range 0-10.00Read
AI64Program version, SA FC-2.Range 0-10.00Read
AI65Program version, EA FC-1.Range 0-10.00Read
AI66Program version, EA FC-2.Range 0-10.00Read
AI67Program version, HX control unitRange 0-10.00Read
AI68WeekdayRange 0-6Read
AI69Extended low speed op. HoursPresent time for extended low speed operation. Range 0-23Read
AI70Extended low speed op. MinutesPresent time for extended low speed operation. Range 0-59Read
AI71Extended high speed op. HoursPresent time for extended high speed operation. Range 0-23Read
AI72Extended high speed op. MinutesPresent time for extended high speed operation. Range 0-59Read
AI73SA Fan operation timeRange 0-9999Read
AI74EA Fan operation timeRange 0-9999Read
AI75Cool operation timeRange 0-9999Read
AI76Heat exchange operation timeRange 0-9999Read
AI77Reheat operation timeRange 0-9999Read
AI78Present tripped alarmPresent tripped alarm number with highest priority. Range 0-200Read
AI79Active not tripped alarm no.1Present active alarm in delay. Range 0-200Read
AI80Active not tripped alarm no.2Present active alarm in delay. Range 0-200Read
AI81Active not tripped alarm no.3Present active alarm in delay. Range 0-200Read
AI82SA Fan sizePresent supply air fan size. Range 04 - 120Read
AI83EA Fan sizePresent extract air fan size. Range 04 - 120Read
AImin84Operation mode 1Range 0-18Read0=Manual stop, 1=Ext. stop, 2=Com. stop 1, 3=Manual high speed, 4=Summer night cooling, 5=Int. night heat, 6=Manual low speed, 7=Ext. high speed, 8=Com. high speed, 9=Year channel stop, 10=Year channel high speed, 11=Year channel low speed, 12=Time channel high speed, 13=Ext. low speed, 14=Com. low speed, 15=Time channel low speed, 16=Time channel stop, 17=Low speed=stop, 18=Com. stop 2. (New in PV 5.00)
AI85Operation mode 2Range 0 - 22Read0=, 1=Cold air recovery, 2=Cooling boost, 3=SA down regulation, 4=HX defrosting, 5=Anti frost func. active, 6=Effect reduction, 7=Startup, 8=Zero calibration, 9=Extended low speed, 10=Extended high speed, 11=Air adjustment, 12=Cooling off, 13=Purging R.HX, 14=Extended R.HX. op, 15=Filter calibration, 16=R.HX. calibration, 17=Morning boost, 18=Heating boost, 19=Alarm, 20=CoolDX pressure reduction. (PV 2.00), 21=Startup extract air fan (New in 4.00), 22=Fan heat retention (New in PV 5.00)
AI86Operation mode, manualPresent manual operation set on the unit's hand terminal. Range 0-3Read0=Stop, 1=Auto operation, 2=Manual low speed, 3=Manual high speed
AI87Copy of Input Status 1-16.Range 0-65535Read
AI88Copy of Input Status 17-32.Range 0-65535Read
AI89Copy of Input Status 33-48.Range 0-65535Read
AI90Heat exchanger regulatorPresent level of heat exchanger regulator RX/CX/PX. Range 0-100.00%%Read
AI91Extract air-humidityPresent level of extract air-humidity. Range 0-100.00%%Read
AI92Extract air-humidity temperaturePresent temperature inside extract air-humidity sensor. Range -55.00-125.00°C°CRead
AI93Extract air-dewpointCalculated extract air-dewpoint. Range -55.00-125.00°C°CRead
AI94AYC chilled water temperaturePresent AYC chilled water temperature. Range -55.00-125.00°C°CRead
AI95AYC chilled water temperature regulatorPresent AYC chilled water temperature regulator setpoint. Range -55.00-125.00°C°CRead
AI96AYC chilled water outputPresent level of AYC chilled water valve output. Range 0-100.00%%Read
AI97Supply air-dewpoint regulatorPresent supply air-dewpoint regulator setpoint. Range -55.00-125.00°C°CRead
AI98Supply air-humidityPresent level of supply air-humidity. Range 0-100.00%%Read
AI99Supply air-humidity temperaturePresent temperature inside supply air-humidity sensor. Range -55.00-125.00°C°CRead
AI100Supply air-dewpointCalculated supply air-dewpoint. Range -55.00-125.00°C°CRead
AI101C.HX. TemperaturePresent temperature of coil heat exchanger. Range -55.00-125.00°C°CRead
AI102P.HX. Temperature 1Present temperature 1 of plate heat exchanger. Range -55.00-125.00°C°CRead
AI103P.HX. Temperature 2Present temperature 2 of plate heat exchanger. Range -55.00-125.00°C°CRead
AI104P/C.HX. HumidityPresent level of air-humidity in plate/coil heat exchanger. Range 0-100.00%%Read
AI105R.HX. EfficiencyCalculated level of rotary heat exchanger efficiency. Range 0-100.00%%Read
AI106C.HX. Valve outputPresent level of coil heat exchanger valve output. Range 0-100.00%%Read
AI107P.HX bypass outputPresent level of plate heat exchanger bypass output. Range 0-100.00%%Read
AI108Supply air pre-filter pressure levelPresent supply air pre-filter pressure drop. Range 0-2000PaPaRead
AI109Supply air pre-filter pressure alarm limit.Present supply air pre-filter pressure alarm limit. Range 0-2000PaPaRead
AI110Supply air pre-filter pressure level, newSupply air pre-filter pressure saved from calibration. Range 0-2000PaPaRead
AI111Extract air pre-filter pressure levelPresent extract air pre-filter pressure drop. Range 0-2000PaPaRead
AI112Extract air pre-filter pressure alarm limit.Present extract air pre-filter pressure alarm limit. Range 0-2000PaPaRead
AI113Extract air pre-filter pressure level, newExtract air pre-filter pressure saved from calibration. Range 0-2000PaPaRead
AI114Xzone reheat levelPresent level of Xzone reheat. Range 0-100.00%%Read
AI115Xzone anti frost temperatureRange -55.00-125.00°C°CRead
AI116Xzone cooling levelPresent level of Xzone cooling. Range 0-100.00%%Read
AI117Xzone cool step timePresent time between Xzone cool step shift. Range 0-600ssRead
AI118Xzone cool relay 1 restart timePresent time between two starts of Xzone cool relay 1. Range 0-900ssRead
AI119Xzone cool relay 2 restart timePresent time between two starts of Xzone cool relay 2. Range 0-900ssRead
AI120Xzone SA Temp regulatorPresent Xzone supply air temperature regulator setpoint. Range -55.00-125.00°C°CRead
AI121Xzone EA Temp regulatorPresent Xzone extract air temperature regulator setpoint. Range -55.00-125.00°C°CRead
AI122Xzone SA TemperaturePresent Xzone supply air temperature. Range -55.00-125.00°C°CRead
AI123Xzone EA/Room temperaturePresent Xzone extract air/room temperature. Range -55.00-125.00°C°CRead
AI124Pre-heating air temperaturePresent pre-heating air temperature. Range -55.00-125.00°C°CRead
AI125Pre-heating levelPresent level of pre-heating. Range 0-100.00%%Read
AI126Pre-heating anti frost temperaturePresent anti frost temperature for water pre-heating coils. Range -55.00-125.00°C°CRead
AI127ReCO2 CO2 inputPresent input signal for ReCO2 CO2. Range 0-100.00%%Read
AI128ReCO2 internal damper outputPresent output signal for ReCO2 internal damper. Range 0-100.00%%Read
AI129ReCO2 external damper outputPresent output signal for ReCO2 external damper. Range 0-100.00%%Read
AI130ReCO2 outdoor airflowPresent ReCO2 outdoor airflow. Range 0-20000l/sl/sRead
AI131ReCO2 outdoor airflow regulatorPresent ReCO2 outdoor airflow regulator setpoint. Range 0-20000l/sl/sRead
AI132ReCO2 outdoor airflow pressurePresent ReCO2 outdoor airflow pressure. Range 0-2000PaPaRead
AI133Preheat operation timeRange 0-9999Read
AI134Xzone cool operation timeRange 0-9999Read
AI135Xzone reheat operation timeRange 0-9999Read
AI136Supply air-D temperatureRange -55.00-125.00°C°CRead
AI137Extract air-D temperaturePresent extract air-D temperature. Range -55.00-125.00°C°CRead
AI138AYC heat temperaturePresent AYC heat temperature. Range -55.00-125.00°C°CRead
AI139AYC heat temp regulatorPresent AYC heat temperature regulator setpoint. Range -55.00-125.00°C°CRead
AI140AYC heat valve outputPresent level of AYc heat valve output. Range 0-100.00%%Read
AI141Min/Max/Average Sens1TempPresent Min/Max/Average sensor 1 temperature. Range -55.00-125.00°C (from PV 5.15)°CRead
AI142Min/Max/Average Sens2TempPresent Min/Max/Average sensor 2 temperature. Range -55.00-125.00°C (from PV 5.15)°CRead
AI143Min/Max/Average Sens3TempPresent Min/Max/Average sensor 3 temperature. Range -55.00-125.00°C (from PV 5.15)°CRead
AI144Min/Max/Average Sens4TempPresent Min/Max/Average sensor 4 temperature. Range -55.00-125.00°C (from PV 5.15)°CRead
AI145Miru 1 AirflowPresent Miru 1 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI146Miru 1 Airflow regulatorPresent Miru 1 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI147Miru 1 PressurePresent Miru 1 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI148Miru 1 Pressure regulatorPresent Miru 1 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI149Miru 1 Outdoor temperaturePresent Miru 1 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI150Miru 1 Operation timeRange 0-9999 (from PV 6.04)Read
AI151Miru 1 Fan levelPresent running level for the Miru 1 air fan. Range 0-100.00% (from PV 6.04)%Read
AI152Miru 1 Fan powerPresent power consumption level for the Miru 1 air fan. Range 0-6000W (from PV 6.04)WRead
AI153Miru 1 SFPSFP value for Miru 1 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI154Miru 1 KWHKWH value for Miru 1 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI155Miru 1 MWHMWH value for Miru 1 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI156Miru 2 AirflowPresent Miru 2 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI157Miru 2 Airflow regulatorPresent Miru 2 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI158Miru 2 PressurePresent Miru 2 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI159Miru 2 Pressure regulatorPresent Miru 2 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI160Miru 2 Outdoor temperaturePresent Miru 2 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI161Miru 2 Operation timeRange 0-9999 (from PV 6.04)Read
AI162Miru 2 Fan levelPresent running level for the Miru 2 air fan. Range 0-100.00% (from PV 6.04)%Read
AI163Miru 2 Fan powerPresent power consumption level for the Miru 2 air fan. Range 0-6000W (from PV 6.04)WRead
AI164Miru 2 SFPSFP value for Miru 2 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI165Miru 2 KWHKWH value for Miru 2 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI166Miru 2 MWHMWH value for Miru 2 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI167Miru 3 AirflowPresent Miru 3 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI168Miru 3 Airflow regulatorPresent Miru 3 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI169Miru 3 PressurePresent Miru 3 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI170Miru 3 Pressure regulatorPresent Miru 3 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI171Miru 3 Outdoor temperaturePresent Miru 3 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI172Miru 3 Operation timeRange 0-9999 (from PV 6.04)Read
AI173Miru 3 Fan levelPresent running level for the Miru 3 air fan. Range 0-100.00% (from PV 6.04)%Read
AI174Miru 3 Fan powerPresent power consumption level for the Miru 3 air fan. Range 0-6000W (from PV 6.04)WRead
AI175Miru 3 SFPSFP value for Miru 3 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI176Miru 3 KWHKWH value for Miru 3 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI177Miru 3 MWHMWH value for Miru 3 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI178Miru 4 AirflowPresent Miru 4 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI179Miru 4 Airflow regulatorPresent Miru 4 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI180Miru 4 PressurePresent Miru 4 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI181Miru 4 Pressure regulatorPresent Miru 4 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI182Miru 4 Outdoor temperaturePresent Miru 4 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI183Miru 4 Operation timeRange 0-9999 (from PV 6.04)Read
AI184Miru 4 Fan levelPresent running level for the Miru 4 air fan. Range 0-100.00% (from PV 6.04)%Read
AI185Miru 4 Fan powerPresent power consumption level for the Miru 4 air fan. Range 0-6000W (from PV 6.04)WRead
AI186Miru 4 SFPSFP value for Miru 4 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI187Miru 4 KWHKWH value for Miru 4 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI188Miru 4 MWHMWH value for Miru 4air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI189Miru 5 AirflowPresent Miru 5 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI190Miru 5 Airflow regulatorPresent Miru 5 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI191Miru 5 PressurePresent Miru 5 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI192Miru 5 Pressure regulatorPresent Miru 5 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI193Miru 5 Outdoor temperaturePresent Miru 5 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI194Miru 5 Operation timeRange 0-9999 (from PV 6.04)Read
AI195Miru 5 Fan levelPresent running level for the Miru 5 air fan. Range 0-100.00% (from PV 6.04)%Read
AI196Miru 5 Fan powerPresent power consumption level for the Miru 5 air fan. Range 0-6000W (from PV 6.04)WRead
AI197Miru 5 SFPSFP value for Miru 5 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI198Miru 5 KWHKWH value for Miru 5 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI199Miru 5 MWHMWH value for Miru 5 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI200Miru 6 AirflowPresent Miru 6 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI201Miru 6 Airflow regulatorPresent Miru 6 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI202Miru 6 PressurePresent Miru 6 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI203Miru 6 Pressure regulatorPresent Miru 6 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI204Miru 6 Outdoor temperaturePresent Miru 6 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI205Miru 6 Operation timeRange 0-9999 (from PV 6.04)Read
AI206Miru 6 Fan levelPresent running level for the Miru 6 air fan. Range 0-100.00% (from PV 6.04)%Read
AI207Miru 6 Fan powerPresent power consumption level for the Miru 6 air fan. Range 0-6000W (from PV 6.04)WRead
AI208Miru 6 SFPSFP value for Miru 6 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI209Miru 6 KWHKWH value for Miru 6 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI210Miru 6 MWHMWH value for Miru 6 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI211Miru 7 AirflowPresent Miru 7 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI212Miru 7 Airflow regulatorPresent Miru 7 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI213Miru 7 PressurePresent Miru 7 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI214Miru 7 Pressure regulatorPresent Miru 7 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI215Miru 7 Outdoor temperaturePresent Miru 7 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI216Miru 7 Operation timeRange 0-9999 (from PV 6.04)Read
AI217Miru 7 Fan levelPresent running level for the Miru 7 air fan. Range 0-100.00% (from PV 6.04)%Read
AI218Miru 7 Fan powerRange 0-6000W (from PV 6.04)WRead
AI219Miru 7 SFPSFP value for Miru 7 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI220Miru 7 KWHKWH value for Miru 7 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI221Miru 7 MWHMWH value for Miru 7 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI222Miru 8 AirflowPresent Miru 8 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI223Miru 8 Airflow regulatorPresent Miru 8 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI224Miru 8 PressurePresent Miru 8 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI225Miru 8 Pressure regulatorPresent Miru 8 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI226Miru 8 Outdoor temperaturePresent Miru 8 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI227Miru 8 Operation timeRange 0-9999 (from PV 6.04)Read
AI228Miru 8 Fan levelPresent running level for the Miru 8 air fan. Range 0-100.00% (from PV 6.04)%Read
AI229Miru 8 Fan powerPresent power consumption level for the Miru 8 air fan. Range 0-6000W (from PV 6.04)WRead
AI230Miru 8 SFPSFP value for Miru 8 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI231Miru 8 KWHKWH value for Miru 8 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI232Miru 8 MWHMWH value for Miru 8 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI233Miru 9 AirflowPresent Miru 9 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI234Miru 9 Airflow regulatorPresent Miru 9 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI235Miru 9 PressurePresent Miru 9 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI236Miru 9 Pressure regulatorPresent Miru 9 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI237Miru 9 Outdoor temperaturePresent Miru 9 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI238Miru 9 Operation timeRange 0-9999 (from PV 6.04)Read
AI239Miru 9 Fan levelPresent running level for the Miru 9 air fan. Range 0-100.00% (from PV 6.04)%Read
AI240Miru 9 Fan powerPresent power consumption level forthe Miru 9 airfan. Range 0-6000W (from PV 6.04)WRead
AI241Miru 9 SFPSFP value for Miru 9 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI242Miru 9 KWHKWH value for Miru 9 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI243Miru 9 MWHMWH value for Miru 9 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI244Miru 10 AirflowPresent Miru 10 airflow. Range 0-10000l/s (from PV 6.04)l/sRead
AI245Miru 10 Airflow regulatorPresent Miru 10 airflow regulator setpoint. Range 0-10000l/s (from PV 6.04)l/sRead
AI246Miru 10 PressurePresent Miru 10 air duct pressure. Range 0-750Pa (from PV 6.04)PaRead
AI247Miru 10 Pressure regulatorPresent Miru 10 air duct pressure regulator setpoint. Range 0-750Pa (from PV 6.04)PaRead
AI248Miru 10 Outdoor temperaturePresent Miru 10 outdoor air temperature. Range -55.00-95.00°C (from PV 6.04)°CRead
AI249Miru 10 Operation timeRange 0-9999 (from PV 6.04)Read
AI250Miru 10 Fan levelPresent running level for the Miru 10 air fan. Range 0-100.00% (from PV 6.04)%Read
AI251Miru 10 Fan powerPresent power consumption level for the Miru 10 air fan. Range 0-6000W (from PV 6.04)WRead
AI252Miru 10 SFPSFP value for Miru 10 air fan. Range 0.00-5.00 (from PV 6.04)Read
AI253Miru 10 KWHKWH value for Miru 10 air fan. Range 0-999KWH (from PV 6.04)kWhRead
AI254Miru 10 MWHMWH value for Miru 10 air fan. Range 0-32000MWH (from PV 6.04)MWhRead
AI255BB Operation modePresent Blue Box operation mode. Range 0-2 (from PV 6.05)Read0=Stop, 1=Heat, 2=Cool
AI256BB Cool temp regulatorPresent Blue Box cool temperature regulator setpoint. Range -40.0-176.0°C (from PV 6.05)°CRead
AI257BB Heat temp regulatorPresent Blue Box heat temperature regulator setpoint. Range -40.0-176.0°C (from PV 6.05)°CRead
AI258BB Supply water temperaturePresent Blue Box supply water temperature. Range -20.0-80.0°C (from PV 6.05)°CRead
AI259BB Return water temperaturePresent Blue Box return water temperature. Range -40.0-176.0°C (from PV 6.05)°CRead
AI260BB Supply pre-coil temperaturePresent Blue Box pre-coil water temperature. Range -20.0-80.0°C (from PV 6.05)°CRead
AI261Extended ext. reg. seq. frost tempPresent extended extra regulation sequence frost temperature. Range -55.00-125.00°C (from PV 6.07)°CRead
AI262Extended ext. reg. seq. OutputPresent extended extra regulation sequence output. Range 0-100.00% (from PV 6.07)%Read
AI263Steam humid outputPresent steam humidification output. Range 0-100.00% (from PV 6.07)%Read
AI264End-filter pressure levelRange 0-2000Pa (from PV 6.07)PaRead
AI265End-filter pressure level, newSupply air end-filter pressure saved from calibration. Range 0-2000Pa (from PV 6.07)PaRead
AI266End-filter pressure alarm limitPresent supply air end-filter pressure alarm limit. Range 0-2000Pa (from PV 6.07)PaRead
AV0SA Low speed airflow setpointRange 0-20000l/sl/sWrite
AV1SA High speed airflow setpointRange 0-20000l/sl/sWrite
AV2SA Max speed airflow setpointRange 0-20000l/sl/sWrite
AV3SA Min speed airflow setpointRange 0-20000l/sl/sWrite
AV4EA Low speed airflow setpointRange 0-20000l/sl/sWrite
AV5EA High speed airflow setpointRange 0-20000l/sl/sWrite
AV6EA Max speed airflow setpointRange 0-20000l/sl/sWrite
AV7EA Min speed airflow setpointRange 0-20000l/sl/sWrite
AV8SA Low speed pressure setpointRange 0-750PaPaWrite
AV9SA High speed pressure setpointRange 20-750PaPaWrite
AV10SA Max speed output signalRange 10.00-100.00%%Write
AV11SA Max speed pressure setpointRange 20-750PaPaWrite
AV12EA Low speed pressure setpointRange 0-750PaPaWrite
AV13EA High speed pressure setpointRange 20-750PaPaWrite
AV14EA Max speed output signalRange 10.00-100.00%%Write
AV15EA Max speed pressure setpointRange 20-750PaPaWrite
AV16SA Low speed demand setpointRange 0-100.00%%Write
AV17SA High speed demand setpointRange 0-100.00%%Write
AV18EA Low speed demand setpointRange 0-100.00%%Write
AV19EA High speed demand setpointRange 0-100.00%%Write
AV20SA Airflow regulation zoneRange 1.00 - 10.00Write
AV21SA Airflow C-factorSupply airflow regulator affection setting. Range 0.005 - 2.500Write
AV22EA Airflow regulation zoneRange 1.00 - 10.00Write
AV23EA Airflow C-factorExtract airflow regulator affection setting. Range 0.005 - 2.500Write
AV24SA Pressure regulation zoneRange 1.00 - 10.00Write
AV25SA Pressure C-factorSupply air pressure regulator affection setting. Range 0.005 - 2.500Write
AV26EA Pressure regulation zoneRange 1.00 - 10.00Write
AV27EA Pressure C-factorExtract air pressure regulator affection setting. Range 0.005 - 2.500Write
AV28SA Demand P-band.Supply air demand regulator P-band setting. Range 1.00 - 100.00Write
AV29SA Demand C-factorSupply air demand regulator affection setting. Range 0.005 - 2.500Write
AV30EA Demand P-band.Extract air demand regulator P-band setting. Range 1.00 - 100.00Write
AV31EA Demand C-factorExtract air demand regulator affection setting. Range 0.005 - 2.500Write
AV32ERS 1 DiffRange 1.00 - 7.00°C°CWrite
AV33ERS 1 BreakpointBreakpoint setting according to the diagram for ERs 1. Range 12.00 - 26.00°C°CWrite
AV34ERS 2 Breakpoint X1Breakpoint X1 setting according to the diagram for ERs 2. Range 10.00-38.00°C°CWrite
AV35ERS 2 Breakpoint Y1Breakpoint Y1 setting according to the diagram for ERs 2. Range 10.00-40.00°C°CWrite
AV36ERS 2 Breakpoint X2Breakpoint X2 setting according to the diagram for ERS 2. Range 11.00-39.00°C°CWrite
AV37ERS 2 Breakpoint Y2Range 10.00-40.00°C°CWrite
AV38ERS 2 Breakpoint X3Breakpoint X3setting according to the diagram forERS2. Range 12.00-40.00°C°CWrite
AV39ERS 2 Breakpoint Y3Range 10.00-40.00°C°CWrite
AVmin40SA Temperature setpointRange 10.00-40.00°C°CWrite
AVmin41EA/Room Temperature setpointRange 10.00-40.00°C°CWrite
AV42SA Min temp setpointRange 8.00-20.00°C°CWrite
AV43SA Max temp setpointRange 16.00-50.00°C°CWrite
AV44SA Temperature P-bandSupply air temperature regulator P-band setting. Range 1.00 - 40.00Write
AV45EA/Room Temperature P-bandRange 1.00 - 40.00Write
AV46SA HX. Reg C-factorSupply air heat exchange regulator affection setting. Range 0.000 - 2.500Write
AV47EA/Room HX. Reg C-factorRange 0.000 - 2.500Write
AV48SA Heat Reg C-factorSupply air reheat regulator affection setting. Range 0.000 - 2.500Write
AV49EA/Room Heat Reg C-factorRange 0.000 - 2.500Write
AV50SA Extra Reg heat C-factorRange 0.000 - 2.500Write
AV51SA Extra Reg cool C-factorRange 0.000 - 2.500Write
AV52EA Extra Reg heat C-factorRange 0.000 - 2.500Write
AV53EA Extra Reg cool C-factorRange 0.000 - 2.500Write
AV54SA Down regulation Reg C-factorRange 0.000 - 2.500Write
AV56SA Cool reg C-factorRange 0.000 - 2.500Write
AV57EA/Room Cool reg C-factorRange 0.000 - 2.500Write
AV58SA Cooling boost C-factorRange 0.000-2.500Write
AV59EA/Room Cooling boost reg C-factorRange 0.000 - 2.500Write
AV60HX Pressure alarm set.Range 30-100PaPaWrite
AV61P/C.HX. defrost P-bandPlate/coil heat exchange defrost P-band setting. Range 1.00 - 40.00Write
AV62P/C.HX. defrost C-factorPlate/coil heat exchange defrost C-factor setting. Range 0.000 - 2.500Write
AV63Cooling off set.Cooling off airflow setting in % of max. airflow. Range 10 - 50%%Write
AV64SA Down regulation neutral zoneRange 0.00-10.00°C°CWrite
AV65Cool Outdoor temp limit.1Outdoor temperature limit setting for cooling stage 1. Range 0.00-25.00°C°CWrite
AV66Cool Outdoor temp limit.2Outdoor temperature limit setting for cooling stage 2. Range 0.00-25.00°C°CWrite
AV67Cool Outdoor temp limit.3Outdoor temperature limit setting for cooling stage 3. Range 0.00-25.00°C°CWrite
AV68Temperature reg. Neutral zoneRange 0.50-10.00°C°CWrite
AV69SA Cool min air flowSupply air min. air flow setting for cooling. Range 0-20000l/sl/sWrite
AV70EA Cool min air flowExtract air min. air flow setting for cooling. Range 0-20000l/sl/sWrite
AV71Heating boost start limitHeating boost start temperature limit. Range 0.00-40.00°C°CWrite
AV72Cooling boost start limitCooling boost (comfort) start temperature limit. Range 0.00-40.00°C°CWrite
AV73SA Filter alarm limitSupply air filter pressure alarm limit setting. Range 50-300PaPaWrite
AV74EA Filter alarm limitExtract air filter pressure alarm limit setting. Range 50-300PaPaWrite
AV75Int. Night heat room start tempRange 5.00-25.00°C°CWrite
AV76Int. Night heat room stop tempRange 5.00-25.00°C°CWrite
AV77Int. Night heat SA temp setpointRange 5.00-40.00°C°CWrite
AV78Int. Night heat SA airflow setpointRange 0-20000l/sl/sWrite
AV79Int. Night heat EA airflow setpointRange 0-20000l/sl/sWrite
AV80Summer night cool EA start tempRange 17.00-27.00°C°CWrite
AV81Summer night cool EA stop tempRange 12.00-22.00°C°CWrite
AV82Summer night cool outdoortemp limitRange 5.00-15.00°C°CWrite
AV83Summer night cool SA temp setpointRange 10.00-20.00°C°CWrite
AV84Outdoor temp comp. Winter X1.Endpoint of winter compensation. Range -30.00-(-10.00)°C°CWrite
AV85Outdoor temp comp. Winter X2.Startpoint of winter compensation. Range -10.00-15.00°C°CWrite
AV86Outdoor temp comp. Winter Y1.Level of winter compensation at X1. Range 0.00-10.00°C°CWrite
AV87Outdoor temp comp. Summer X3.Startpoint of summer compensation. Range 15.00-25.00°C°CWrite
AV88Outdoor temp comp. Summer X4.Endpoint of summer compensation. Range 25.00-40.00°C°CWrite
AV89Outdoor temp comp. Summer Y2.Level of summer compensation at X4. Range -10.00-10.00°C°CWrite
AV90Outdoor airflow comp. Winter X1.Endpoint of winter compensation. Range 30.00-(-10.00)°C°CWrite
AV91Outdoor airflow comp. Winter X2.Startpoint of winter compensation. Range -10.00-15.00°C°CWrite
AV92Outdoor airflow comp. Winter Y1.Level of airflow compensation at X1. Range 0-50.00%%Write
AV93Extra Reg. Sequence max outputRange 0-100.00%%Write
AV94EA/Room min temp alarm limitSetting for min extract air /room temp alarm no.40. Range 8.00-20.00°C°CWrite
AV95SA Deviation alarm limitRange 2.00-15.00°C°CWrite
AV97SA Fan regulation modeSetting of regulation type for the supply air fan. Range 0-3Write0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan
AV98EA Fan regulation modeSetting of regulation type for the extract air fan. Range 0-3Write0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan
AV99ERS StepSetting of curve when temperature is above breakpoint. Range 1-4Write
AV100Temperature regulation mode.Setting of temperature regulation type. Range 0-3Write0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg
AV101Cooling off periodTime setting for cooling off electrical heating coil. Range 60-900ssWrite
AV102Cool step time setTime setting between cool step shift. Range 0 - 600ssWrite
AV103Cool restart timeSetting of time between two starts of the cool relays. Range 60 - 900ssWrite
AV104Cool regulation modeSetting of cool regulation type. Range 0-6Write0=Controlled 0-10V, 1=Controlled 10-0V, 2=On/Off 1-step, 3=On/Off 2-steps, 4=On/Off 3-steps binary, 5=CoolDX economy (PV 2.00), 6=CoolDX comfort (PV 3.00)
AV105Heating boost regulation mode.Setting for heating boost function. Range 0-1Write0=Inactive, 1=Active
AV106Cooling boost regulation mode.Setting of cooling boost regulation type. Range 0-5Write0=Inactive, 1=Comfort, 2=Economy, 3=Sequence, 4=Comfort+economy (New in PV 5.00), 5=Economy+sequence (New in PV 5.00)
AV107Filter calibration modeSetting for required filter calibration. Range 0-5Write0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter, 4=HX, 5=ReCO2 (New in PV 5.00)
AV108Air adjustment time, minutesSetting for amount of minutes to air adjustment function. Range 0 - 1727Write
AV109Air adjustment time, hoursRange 0 - 28Write
AV110Hand terminal languageRange 0 - 18Write0=Svenska, 1=Norsk, 2=Dansk, 3=Suomi, 4=English, 5=Français, 6=Deutsch, 7=Polski, 8=Český, 9=Italiano, 10=Español, 11=Português, 12=Русский, 13=Eesti, 14=Latviesu, 15=Lietiviu, 16=Nederlands, 17=Magyar (New in PV 5.00), 18=Türkçe (New in PV 5.01)
AV111Summer night cool start, hourSetting for start time of summer night cooling function. Range 0-23Write
AV112Summer night cool start, minuteSetting for start time of summer night cooling function. Range 0-59Write
AV113Summer night cool stop, hourSetting for stop time of summer night cooling function. Range 0-23Write
AV114Summer night cool stop, minuteSetting for stop time of summer night cooling function. Range 0-59Write
AV115Extra regulation sequence cool modeSetting of extra regulation sequence cool type. Range 0-2Write0=Inactive, 1=Comfort, 2=Economy
AV116Extra regulation sequence heat modeSetting of extra regulation sequence heat type. Range 0-2Write0=Inactive, 1=Comfort, 2=Economy
AV117Morning boost time, hoursSetting of morning boost time before normal operation. Range 0-23Write
AV118Morning boost time, minutesSetting of morning boost time before normal operation. Range 0-59Write
AV119Startup timeRange 0 - 600ssWrite
AV120Start delay SA fan.Setting of start delay time for the supply air fan. Range 0 - 600ssWrite
AV121Start delay EA fan.Range 0 - 600ssWrite
AV122Air flow unitRange 0 -2Write0=l/s, 1=m3/s, 2=m3/h
AV124YearSetting for the unit's internal clock. Range 2000-2099Write
AV125MonthSetting for the unit's internal clock. Range 1-12Write
AV126DateSetting for the unit's internal clock. Range 0-31Write
AV127HourSetting for the unit's internal clock. Range 0-23Write
AV128MinuteSetting for the unit's internal clock. Range 0-59Write
AV129SecondSetting for the unit's internal clock. Range 0-59Write
AV130Time channel 1 statusRange 0-10,16-26Write0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday, 16=Inactive, 17=Monday, 18=Tuesday, 19=Wednesday, 20=Thursday, 21=Friday, 22=Saturday, 23=Sunday, 24=Monday..Friday, 25=Monday..Sunday, 26=Saturday..Sunday
AV131Time channel 1 start hourRange 0-23Write
AV132Time channel 1 start minuteRange 0-59Write
AV133Time channel 1 stop hourRange 0-23Write
AV134Time channel 1 stop minuteRange 0-59Write
AV135Time channel 2 statusRange 0-10,16-26Write
AV136Time channel 2 start hourRange 0-23Write
AV137Time channel 2 start minuteRange 0-59Write
AV138Time channel 2 stop hourRange 0-23Write
AV139Time channel 2 stop minuteRange 0-59Write
AV140Time channel 3 statusRange 0-10,16-26Write
AV141Time channel 3 start hourRange 0-23Write
AV142Time channel 3 start minuteRange 0-59Write
AV143Time channel 3 stop hourRange 0-23Write
AV144Time channel 3 stop minuteRange 0-59Write
AV145Time channel 4 statusRange 0-10,16-26Write
AV146Time channel 4 start hourRange 0-23Write
AV147Time channel 4 start minuteRange 0-59Write
AV148Time channel 4 stop hourRange 0-23Write
AV149Time channel 4 stop minuteRange 0-59Write
AV150Time channel 5 statusRange 0-10,16-26Write
AV151Time channel 5 start hourRange 0-23Write
AV152Time channel 5 start minuteRange 0-59Write
AV153Time channel 5 stop hourRange 0-23Write
AV154Time channel 5 stop minuteRange 0-59Write
AV155Time channel 6 statusRange 0-10,16-26Write
AV156Time channel 6 start hourRange 0-23Write
AV157Time channel 6 start minuteRange 0-59Write
AV158Time channel 6 stop hourRange 0-23Write
AV159Time channel 6 stop minuteRange 0-59Write
AV160Time channel 7 statusRange 0-10,16-26Write
AV161Time channel 7 start hourRange 0-23Write
AV162Time channel 7 start minuteRange 0-59Write
AV163Time channel 7 stop hourRange 0-23Write
AV164Time channel 7 stop minuteRange 0-59Write
AV165Time channel 8 statusRange 0-10,16-26Write
AV166Time channel 8 start hourRange 0-23Write
AV167Time channel 8 start minuteRange 0-59Write
AV168Time channel 8 stop hourRange 0-23Write
AV169Time channel 8 stop minuteRange 0-59Write
AV170Extended low speed op. Hours setSetting for extended low speed operation. Range 0-23Write
AV171Extended low speed op. Minutes setSetting for extended low speed operation. Range 0-59Write
AV172Extended high speed op. Hours setSetting for extended high speed operation. Range 0-23Write
AV173Extended high speed op. Minutes setSetting for extended high speed operation. Range 0-59Write
AVmin174Communication operation modeSetting of unit operation mode from communication. Range 0-4Write0=Auto operation (normal stop when time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (New in PV 5.00)
AV175Service period alarm.Setting for delay time in months before service alarm. Range 0-99Write
AV176External alarm 1 delaySetting of delay time for external alarm no 1. Range 1 - 600ssWrite
AV177External alarm 2 delaySetting of delay time for external alarm no 2. Range 1 - 600ssWrite
AV178Int. Night heat SA pressure setpointRange 20-750PaPaWrite
AV179Int. Night heat EA pressure setpointRange 20-750PaPaWrite
AV180Copy of Coil Status 1-16Range 0-65535Write
AV181Copy of Coil Status 17-32Range 0-65535Write
AV182Copy of Coil Status 33-48Range 0-65535Write
AV183Heat relay periodic func.Setting of periodic operation. Range 0-3Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV184Cool relay 1 periodic func.Setting of periodic operation. Range 0-3Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV185Cool relay 2 periodic func.Setting of periodic operation. Range 0-3Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02)
AV186Slave control C-factorSlave regulator affection setting. Range 0.5 - 2.0Write
AV187SA dehumid P-bandSA dehumid regulator P-band setting. Range 1.00 - 40.00Write
AV188SA dehumid C-factorSA dehumid regulator affection setting. Range 0.000 - 2.500Write
AV189Dewpoint reg. P-bandDewpoint regulator P-band setting. Range 1.00 - 40.00Write
AV190Dewpoint reg. C-factorDewpoint regulator affection setting. Range 0.000 - 2.500Write
AV191AYC chilled water temperature setSetting of AYC chilled water temperature setpoint. Range 5.00-30.00°C°CWrite
AV192Dewpoint neutral zoneDewpoint neutral zone setting. Range 0.00-5.00°C°CWrite
AV193Comp. airflowSetting of comp. airflow. Range 0-30.00%%Write
AV194Supply air-humidity_setSetting of supply air-humidity. Range 10.00-90.00%%Write
AV195Water heating periodic op. timeSetting of periodic op. time (minute). Range 0-60minminWrite
AV196Water heating intervalSetting of water heating interval time (hour). Range 0-168hhWrite
AV197Cool periodic op. timeSetting of periodic op. time (minute). Range 0-60minminWrite
AV198Cool intervalSetting of cool interval time (hour). Range 0-168hhWrite
AV199P/C.HX. bypass adj.Setting of plate/coil heat exchange bypass adjustment. Range -5.00-5.00°C°CWrite
AV200EA/Room temperature external func.Setting of EA/Room temperature (external) function. Range 0-3 (from PV 5.15)Write0=Inactive, 1=Input signal on terminal 40..41, 2=Communication (AV 201), 3=Min/Max/Average (PV 5.15)
AV201EA/Room temperature com.Setting of EA/Room temperature via communication. Range -55.00-125.00°C°CWrite
AV202Outdoor temperature external func.Setting of outdoor temperature (external) function. Range 0-2Write0=Inactive, 1=Input signal on terminal 38..39, 2=Communication (AV 203)
AV203Outdoor temperature com.Setting of outdoor temperature via communication. Range -55.00-125.00°C°CWrite
AV204Timeout temperature com.Range 0-9999minminWrite
AV205Flow at fire function.Setting for activating the air fan operation at fire function. Range 0-3Write0=Inactive, 1=SA, 2=EA, 3=SA+EA
AV206Air fan down regulation func.Setting for activating the air fan down regulation function. Range 0-2Write0=Inactive, 1=SA, 2=SA+EA
AV207SA speed at fire.Setting of supply air speed at fire. Range 50.00-100.00%%Write
AV208EA speed at fire.Setting of extract air speed at fire. Range 50.00-100.00%%Write
AV209Temperature alarm setpoint.Temperature alarm function setting (no.80). Range -25.00-25.00°C°CWrite
AV210Temperature alarm time.Setting of delay time for temperature alarm (no.80). Range 1-999ssWrite
AV211Supply air min P-band.Supply air min regulator P-band setting. Range 1.00 - 40.00Write
AV212Supply air min C-factor.Supply air min regulator affection setting. Range 0.000 - 2.500Write
AV213Supply air max P-band.Supply air max regulator P-band setting. Range 1.00 - 40.00Write
AV214Supply air max C-factor.Supply air max regulator affection setting. Range 0.000 - 2.500Write
AV215Year channel 1 function.Range 0-3Write0=Inactive, 1=Stop, 2=Low speed, 3=High speed
AV216Year channel 1 start year.Range 2000 - 2099Write
AV217Year channel 1 start month.Range 1 - 12Write
AV218Year channel 1 start date.Range 1-31Write
AV219Year channel 1 start hour.Range 0- 23Write
AV220Year channel 1 start minute.Range 0- 59Write
AV221Year channel 1 stop year.Range 2000-2099Write
AV222Year channel 1 stop month.Range 1-12Write
AV223Year channel 1 stop date.Range 1- 31Write
AV224Year channel 1 stop hour.Range 0-23Write
AV225Year channel 1 stop minute.Range 0-59Write
AV226Year channel 2 function.Range 0-3Write
AV227Year channel 2 start year.Range 2000 - 2099Write
AV228Year channel 2 start month.Range 1- 12Write
AV229Year channel 2 start date.Range 1- 31Write
AV230Year channel 2 start hour.Range 0-23Write
AV231Year channel 2 start minute.Range 0 - 59Write
AV232Year channel 2 stop year.Range 2000 - 2099Write
AV233Year channel 2 stop month.Range 1 - 12Write
AV234Year channel 2 stop date.Range 1- 31Write
AV235Year channel 2 stop hour.Range 0 - 23Write
AV236Year channel 2 stop minute.Range 0- 59Write
AV237Year channel 3 function.Range 0-3Write
AV238Year channel 3 start year.Range 2000 - 2099Write
AV239Year channel 3 start month.Range 1 - 12Write
AV240Year channel 3 start date.Range 1 - 31Write
AV241Year channel 3 start hour.Range 0 - 23Write
AV242Year channel 3 start minute.Range 0-59Write
AV243Year channel 3 stop year.Range 2000 - 2099Write
AV244Year channel 3 stop month.Range 1 - 12Write
AV245Year channel 3 stop date.Range 1- 31Write
AV246Year channel 3 stop hour.Range 0 - 23Write
AV247Year channel 3 stop minute.Range 0 - 59Write
AV248Year channel 4 function.Range 0-3Write
AV249Year channel 4 start year.Range 2000 - 2099Write
AV250Year channel 4 start month.Range 1- 12Write
AV251Year channel 4 start date.Range 1- 31Write
AV252Year channel 4 start hour.Range 0 - 23Write
AV253Year channel 4 start minute.Range 0 - 59Write
AV254Year channel 4 stop year.Range 2000 - 2099Write
AV255Year channel 4 stop month.Range 1 - 12Write
AV256Year channel 4 stop date.Range 1 - 31Write
AV257Year channel 4 stop hour.Range 0 - 23Write
AV258Year channel 4 stop minute.Range 0 - 59Write
AV259Year channel 5 function.Range 0-3Write
AV260Year channel 5 start year.Range 2000 - 2099Write
AV261Year channel 5 start month.Range 1 - 12Write
AV262Year channel 5 start date.Range 1- 31Write
AV263Year channel 6 start hour.Year channel 5 start hour (the guide prints 'channel 6' here). Range 0-23Write
AV264Year channel 5 start minute.Range 0- 59Write
AV265Year channel 5 stop year.Range 2000 - 2099Write
AV266Year channel 5 stop month.Range 1 - 12Write
AV267Year channel 5 stop date.Range 1- 31Write
AV268Year channel 5 stop hour.Range 0 - 23Write
AV269Year channel 5 stop minute.Range 0 - 59Write
AV270Year channel 6 function.Range 0-3Write
AV271Year channel 6 start year.Range 2000 - 2099Write
AV272Year channel 6 start month.Range 1 - 12Write
AV273Year channel 6 start date.Range 1- 31Write
AV274Year channel 6 start hour.Range 0- 23Write
AV275Year channel 6 start minute.Range 0-59Write
AV276Year channel 6 stop year.Range 2000 -2099Write
AV277Year channel 6 stop month.Range 1- 12Write
AV278Year channel 6 stop date.Range 1- 31Write
AV279Year channel 6 stop hour.Range 0- 23Write
AV280Year channel 6 stop minute.Range 0-59Write
AV281Year channel 7 function.Range 0-3Write
AV282Year channel 7 start year.Range 2000 - 2099Write
AV283Year channel 7 start month.Range 1- 12Write
AV284Year channel 7 start date.Range 1- 31Write
AV285Year channel 7 start hour.Range 0 - 23Write
AV286Year channel 7 start minute.Range 0 - 59Write
AV287Year channel 7 stop year.Range 2000 - 2099Write
AV288Year channel 7 stop month.Range 1 - 12Write
AV289Year channel 7 stop date.Range 1- 31Write
AV290Year channel 7 stop hour.Range 0 - 23Write
AV291Year channel 7 stop minute.Range 0 - 59Write
AV292Year channel 8 function.Range 0-3Write
AV293Year channel 8 start year.Range 2000 - 2099Write
AV294Year channel 8 start month.Range 1 - 12Write
AV295Year channel 8 start date.Range 1 - 31Write
AV296Year channel 8 start hour.Range 0 - 23Write
AV297Year channel 8 start minute.Range 0- 59Write
AV298Year channel 8 stop year.Range 2000 - 2099Write
AV299Year channel 8 stop month.Range 1- 12Write
AV300Year channel 8 stop date.Range 1- 31Write
AV301Year channel 8 stop hour.Range 0 - 23Write
AV302Year channel 8 stop minute.Range 0 - 59Write
AV303Filter select.Setting for filter select function. Range 0-3Write0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA
AV304Pre-filter select.Setting for pre-filter select function. Range 0-3Write0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA
AV305SA pre-filter alarm limit.Supply air pre-filter pressure alarm limit setting. Range 50-300PaPaWrite
AV306EA pre-filter alarm limit.Extract air pre-filter pressure alarm limit setting. Range 50-300PaPaWrite
AV307Pre-filter calibration mode.Setting for required filter calibration. Range 0-3Write0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter
AV308Xzone reheat function.Setting for Xzone reheat function. Range 0-4Write0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP
AV309Xzone cooling function.Setting for Xzone cooling function. Range 0-5Write0=Inactive, 1=0-10V, 2=10-0V, 3=On/off 1, 4=On/off 2, 5=On/off 3
AV310Xzone temperature reg. Neutral zone.Range 0.50-10.00°C°CWrite
AV311Xzone temperature regulation mode.Setting of Xzone temperature regulation type. Range 0-3Write0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg
AV312Xzone ERS Step.Setting of Xzone curve when temperature is above breakpoint. Range 1-4Write
AV313Xzone ERS 1 Diff.Range 1.00 - 7.00°C°CWrite
AV314Xzone ERS 1 Breakpoint.Breakpoint setting according to the diagram for Xzone ERs 1. Range 12.00 - 26.00°C°CWrite
AV315Xzone ERS 2 Breakpoint X1.Breakpoint X1 setting according to the diagram for Xzone ERS 2. Range 10.00-38.00°C°CWrite
AV316Xzone ERS 2 Breakpoint Y1.Breakpoint Y1 setting according to the diagram for Xzone ERS 2. Range 10.00-40.00°C°CWrite
AV317Xzone ERS 2 Breakpoint X2.Breakpoint X2 setting according to the diagram for Xzone ERS 2. Range 11.00-39.00°C°CWrite
AV318Xzone ERS 2 Breakpoint Y2.Range 10.00-40.00°C°CWrite
AV319Xzone ERS 2 Breakpoint X3.Breakpoint X3 setting according to the diagram for Xzone ERS 2. Range 12.00-40.00°C°CWrite
AV320Xzone ERS 2 Breakpoint Y3.Breakpoint Y3 setting according to the diagram for Xzone ERS 2. Range 10.00-40.00°C°CWrite
AV321Xzone SA Temperature setpoint.Range 10.00-40.00°C°CWrite
AV322Xzone EA/Room Temperature setpoint.Range 10.00-40.00°C°CWrite
AV323Xzone SA Min temp setpoint.Range 8.00-20.00°C°CWrite
AV324Xzone SA Max temp setpointRange 16.00-50.00°C°CWrite
AV325Pre-heating function.Setting of pre-heating function. Range 0-4Write0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP
AV326Pre-heating setpoint.Setting of pre-heating temperature setpoint. Range -30.00-30.00°C°CWrite
AV327Xzone P-band.Xzone regulator P-band setting. Range 1.00-40.00Write
AV328Xzone SA reheat C-factor.Xzone supply air reheat regulator affection setting. Range 0.000 - 2.500Write
AV329Xzone SA cooling C-factor.Xzone supply air cooling regulator affection setting. Range 0.000 - 2.500Write
AV330Xzone EA reheat C-factor.Xzone extract air reheat regulator affection setting. Range 0.000 - 2.500Write
AV331Xzone EA cooling C-factor.Xzone extract air cooling regulator affection setting. Range 0.000 - 2.500Write
AV332Xzone SA min P-band.Xzone supply air min regulator P-band setting. Range 1.00 - 40.00Write
AV333Xzone SA min C-factor.Xzone supply air min regulator affection setting. Range 0.000 - 2.500Write
AV334Xzone SA max P-band.Xzone supply air max regulator P-band setting. Range 1.00 - 40.00Write
AV335Xzone SA max C-factor.Xzone supply air min regulator affection setting. Range 0.000 - 2.500Write
AV336Preheat P-band.Preheat regulator P-band setting. Range 1.00 - 40.00Write
AV337Preheat C-factor.Preheat regulator affection setting. Range 0.000 - 2.500Write
AV338ReCO2 CO2 function.Setting of ReCO2 CO2 function. Range 0-2Write0=Inactive, 1=CO2, 2=CO2+flow
AV339ReCO2 CO2 setpoint.Setting of ReCO2 CO2 setpoint. Range 0-100.00%%Write
AV340ReCO2 cooling function.Setting of ReCO2 cooling function. Range 0-2Write0=Inactive, 1=Comfort, 2=Economy
AV341ReCO2 heating function.Setting of ReCO2 heating function. Range 0-2Write0=Inactive, 1=Comfort, 2=Economy
AV342ReCO2 min outdoor air.Setting of ReCO2 min outdoor air. Range 0-20000l/sl/sWrite
AV343ReCO2 min exhaust air.Setting of ReCO2 min exhaust air. Range 0-20000l/sl/sWrite
AV344ReCO2 CO2 P-band.ReCO2 CO2 regulator P-band setting. Range 1.00 - 100.00Write
AV345ReCO2 CO2 C-factor.ReCO2 CO2 regulator affection setting. Range 0.000 - 5.000Write
AV346ReCO2 CO2 flow C-factor.ReCO2 flow regulator affection setting. Range 0.000 - 5.000Write
AV347ReCO2 heating C-factor.ReCO2 heating regulator affection setting. Range 0.000 - 5.000Write
AV348ReCO2 cooling C-factor.ReCO2 cooling regulator affection setting. Range 0.000 - 5.000Write
AV349AYC function.Setting of AYC function. Range 0-3Write0=Inactive, 1=Cool, 2=Heat, 3=Cool+heat
AV350AYC heat temp set.Setting of AYC heated water temperature setpoint. Range 10.00-80.00°C°CWrite
AV351AYC night comp. channel.Setting of AYC night compensation channel. Range 1-2Write1=Channel 1, 2=Channel 2
AV352AYC channel start hour.Setting of AYC channel start time (hour). Range 0-23hhWrite
AV353AYC channel start minute.Setting of AYC channel start time (minute). Range 0-59minminWrite
AV354AYC channel stop hour.Setting of AYC channel stop time (hour). Range 0-23hhWrite
AV355AYC channel stop minute.Setting of AYC channel stop time (minute). Range 0-59minminWrite
AV356AYC channel period.Setting of AYc channel period. Range 0-10Write0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday
AV357AYC heat P-band.AYC heat regulator P-band setting. Range 1.00 - 40.00Write
AV358AYC heat C-factor.AYC heat regulator affection setting. Range 0.000-2.500Write
AV359AYC cool P-band.AYC cool regulator P-band setting. Range 1.00 - 40.00Write
AV360AYC cool C-factor.AYC cool regulator affection setting. Range 0.000-2.500Write
AV361AYC heat out comp. X1.Range -40.00-40.00°C°CWrite
AV362AYC heat out comp. Y1.Range 10.00-80.00°C°CWrite
AV363AYC heat out comp. X2.Range -40.00-40.00°C°CWrite
AV364AYC heat out comp. Y2.Range 10.00-80.00°C°CWrite
AV365AYC heat out comp. X3.Range -40.00-40.00°C°CWrite
AV366AYC heat out comp. Y3.Range 10.00-80.00°C°CWrite
AV367AYC heat room comp. temp limit.Range 0.00-40.00°C°CWrite
AV368AYC heat room comp P-band.Range 1.00-10.00°C°CWrite
AV369AYC heat night comp temp.Range -10.00-10.00°C°CWrite
AV370AYC heat pump on temp.Range -40.00-40.00°C°CWrite
AV371AYC heat pump off temp.Range -40.00-40.00°C°CWrite
AV372AYC heat pump alarm.Setting for selecting the AYC heated water pump alarm function. Range 0-3Write0=Inactive, 1=Open, 2=Closed, 3=Contactor
AV373AYC heat per op function.Range 0-3Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve
AV374AYC heat per op time.Range 0-60minminWrite
AV375AYC heat per op interval.Range 0-168hhWrite
AV376AYC cool out comp. X1.Range -40.00-40.00°C°CWrite
AV377AYC cool out comp. Y1.Range 10.00-80.00°C°CWrite
AV378AYC cool out comp. X2.Range -40.00-40.00°C°CWrite
AV379AYC cool out comp. Y2.Range 10.00-80.00°C°CWrite
AV380AYC cool out comp. X3.Range -40.00-40.00°C°CWrite
AV381AYC cool out comp. Y3.Range 10.00-80.00°C°CWrite
AV382AYC cool room comp. temp limit.Range 0.00-40.00°C°CWrite
AV383AYC cool room comp. P-band.Range 1.00-10.00°C°CWrite
AV384AYC cool night comp temp.Range -10.00-10.00°C°CWrite
AV385AYC cool pump on temp.Range -40.00-40.00°C°CWrite
AV386AYC cool pump off temp.Range -40.00-40.00°C°CWrite
AV387AYC cool pump alarm.Setting for selecting the AYC chilled water pump alarm function. Range 0-3Write0=Inactive, 1=Open, 2=Closed, 3=Contactor
AV388AYC cool per op function.Range 0-3Write0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve
AV389AYC cool per op time.Range 0-60minminWrite
AV390AYC cool per op interval.Range 0-168hhWrite
AV391IO-mod 3 output 1 function.Setting of I/O-module no. 3 relay 1 output. Range 0- 10Write0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost
AV392IO-mod 3 output 2 function.Setting of I/O-module no. 3 relay 2 output. Range 0 - 10Write0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost
AV393Humid reg. func.Setting for selecting humidifying function. Range 0-3 (from PV 6.07)Write0=Inactive, 1=Supply air, 2=Extract air, 3=Steam (New in PV 6.07)
AV394Humid reg. Start.Humidifying start limit setting. Range 10.00-90.00% (from PV 5.10)%Write
AV395Humid reg. Stop.Humidifying stop limit setting. Range 15.00-95.00% (from PV 5.10)%Write
AV396Min/Max/Average SensNumberRange 1-4 (from PV 5.15)Write
AV397Min/Max/Average SensFunctionSetting for selecting sensor function. Range 0-2 (from PV 5.15)Write0=Min, 1=Max, 2=Average
AV398Miru 1 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV399Miru 1 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV400Miru 1 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV401Miru 1 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV402Miru 2 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV403Miru 2 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV404Miru 2 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV405Miru 2 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV406Miru 3 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV407Miru 3 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV408Miru 3 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV409Miru 3 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV410Miru 4 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV411Miru 4 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV412Miru 4 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV413Miru 4 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV414Miru 5 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV415Miru 5 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV416Miru 5 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV417Miru 5 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV418Miru 6 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV419Miru 6 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV420Miru 6 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV421Miru 6 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV422Miru 7 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV423Miru 7 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV424Miru 7 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV425Miru 7 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV426Miru 8 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV427Miru 8 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV428Miru 8 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV429Miru 8 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV430Miru 9 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV431Miru 9 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV432Miru 9 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV433Miru 9 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV434Miru 10 Low speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV435Miru 10 High speed airflow setpointRange 0-10000l/s (from PV 6.04)l/sWrite
AV436Miru 10 Low speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV437Miru 10 High speed pressure setpointRange 0-750Pa (from PV 6.04)PaWrite
AV438BB Cool temp setpointBlue Box cooling temperature setpoint. Range -20.0-80.0°C (from PV 6.05)°CWrite
AV439BB Heat temp setpointBlue Box heating temperature setpoint. Range 10.0-80.0°C (from PV 6.05)°CWrite
AV440BB Unit typeBlue Box unit type. Range 0-3 (from PV 6.05)Write0=None, 1=Heat pump, 2=Chiller, 3=Reversible
AV441BB Optimize upper valve limitBlue Box optimize function upper valve limit. Range 70.00-100.00% (from PV 6.05)%Write
AV442BB Optimize lower valve limitBlue Box optimize function lower valve limit. Range 5.00-90.00% (from PV 6.05)%Write
AV443BB Optimize delayBlue Box optimize function delay time. Range 30-32000s (from PV 6.05)sWrite
AV444BB Cool optimize upBlue Box cooling optimize function up. Range 0.1-6.0°C (from PV 6.05)°CWrite
AV445BB Cool optimize downBlue Box cooling optimize function down. Range 0.1-6.0°C (from PV 6.05)°CWrite
AV446BB Heat optimize upBlue Box heating optimize function up. Range 0.1-6.0°C (from PV 6.05)°CWrite
AV447BB Heat optimize downBlue Box heating optimize function down. Range 0.1-6.0°C (from PV 6.05)°CWrite
AV448BB Cool optimize diff temperatureBlue Box cooling optimize function differential temperature. Range 1.0-10.0°C (from PV 6.05)°CWrite
AV449BB Heat optimize diff temperatureBlue Box heating optimize function differential temperature. Range 1.0-10.0°C (from PV 6.05)°CWrite
AV450BB AQUA Link functionBlue Box AQUA Link function. Range 0-3 (from PV 6.05)Write0=Inactive, 1=Heat, 2=Cool, 3=Heat + Cool
AV451BB AQUA Link cool pump alarm functionBlue Box AQUA Link cool pump alarm function. Range 0-3 (from PV 6.05)Write0=Inactive, 1=Open, 2=Close, 3=Contactor
AV452BB AQUA Link heat pump alarm functionBlue Box AQUA Link heat pump alarm function. Range 0-3 (from PV 6.05)Write0=Inactive, 1=Open, 2=Close, 3=Contactor
AV453Extended ext. reg. seq. reheat functionExtended extra regulation sequence reheat function. Range 0-4 (from PV 6.07)Write0=Inactive, 1=El. P/P, 2=El. 0-10V, 3=Water FP, 4=Water
AV454Season heat mode setpointSeason heat mode type setpoint. Range 0-2 (from PV 6.07)Write0=Digital Input NO, 1=Digital Input NC, 2=Manual
AV455Season heat functionSeason heating function. Range 0-1 (from PV 6.07)Write0=Inactive, 1=Active
AV456Steam humid extract air setpointSteam humidification extract air setpoint. Range 0-100.00% (from PV 6.07)%Write
AV457Steam humid supply air max limitSteam humidification supply air max limit. Range 0-100.00% (from PV 6.07)%Write
AV458Steam humid extract air P-bandSteam humidification extract air P-band. Range 1-60.00% (from PV 6.07)%Write
AV459Steam humid extract air C-factorSteam humidification extract air C-factor. Range 0-3.000 (from PV 6.07)Write
AV460Steam humid supply air max P-bandSteam humidification supply air max P-band. Range 1-60.00% (from PV 6.07)%Write
AV461Steam humid supply air max C-factorSteam humidification supply air max C-factor. Range 0-3.000 (from PV 6.07)Write
AV462End-filter alarm limitSupply air end-filter pressure alarm limit setting. Range 10-1000Pa (from PV 6.07)PaWrite
AV463End-filter selectSupply air end-filter function. Range 0-1 (from PV 6.07)Write0=Inactive, 1=Active
AV464End-filter calibrationSupply air end-filter calibration. Range 0-1 (from PV 6.07)Write0=Inactive, 1=Active
BI0Heat outputStatus for relay output.Read
BI1Cool output 1Status for relay output.Read
BI2Cool output 2Status for relay output.Read
BI3Low speed outputStatus for relay output.Read
BI4High speed outputStatus for relay output.Read
BImin5A-alarm.Status for relay output.Read
BImin6B-alarm.Status for relay output.Read
BI7Operation outputStatus for relay output.Read
BI8Damper outputStatus for relay output.Read
BI9External low speed inputStatus for digital input.Read
BI10External high speed inputStatus for digital input.Read
BI11External alarm 1 inputStatus for digital input.Read
BI12External alarm 2 inputStatus for digital input.Read
BI13External fire alarm input.Status for digital input.Read
BI14External stop inputStatus for digital input.Read
BI15DIP Switch 1Status for dip switch setting.Read
BI16DIP Switch 2Status for dip switch setting.Read
BI17DIP Switch 3Status for dip switch settingRead
BI18DIP Switch 4Status for dip switch setting.Read
BI19DIP Switch 5Status for dip switch settingRead
BI20DIP Switch 6Status for dip switch setting.Read
BI21AYC heat pump outputStatus for AYC heat pump output.Read
BI22AYC cool pump outputStatus for AYC cool pump output.Read
BI23C.HX. pump outputStatus for coil heat exchanger pump output.Read
BI24R.HX rotation monitorStatus from the rotation detector.Read
BI25Xzone heat outputStatus for relay output.Read
BI26Xzone cool output 1Status for relay output.Read
BI27Xzone cool output 2Status for relay output.Read
BI28Pre-heat outputStatus for relay output.Read
BI29IO-mod 3 output 1Status for I/O-module no. 3 relay 1 output.Read
BI30IO-mod 3 output 2Status for I/O-module no. 3 relay 2 output.Read
BI31IO-mod 4 output 1Status for I/O-module no. 4 relay 1 output. (from PV 5.10)Read
BI32Miru 1 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI33Miru 2 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI34Miru 3 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI35Miru 4 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI36Miru 5 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI37Miru 6 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI38Miru 7 AlarmStatus of group alarm from Miru fan (from PV 6.04)Read
BI39Miru 8 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI40Miru 9 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI41Miru 10 AlarmStatus of group alarm from Miru fan. (from PV 6.04)Read
BI42Extended ext. reg. seq. PumpStatus of extended extra regulation sequence pump output. (from PV 6.07)Read
BI43Season heating modeStatus of season heating mode. (from PV 6.07)Read
BI48Alarm number 1Status if alarm number 1 is active.Read
BI49Alarm number 2Status if alarm number 2 is activeRead
BI50Alarm number 3Status if alarm number 3 is activeRead
BI247Alarm number 200Status if alarm number 200 is active.Read
BI248Info number 1Status if info number 1 is activeRead
BI249Info number 2Status if info number 2 is activeRead
BI250Info number 3Status if info number 3 is active.Read
BI347Info number 100Status if info number 100 is active.Read
BVmin0Alarm resetResets tripped alarms.Write
BV1SA Boosting func.Setting for activating the boost function for the supply air fanWrite
BV2EA Boosting func.Setting for activating the boost function for the extract air fan.Write
BV3R.HX. Defrost func.Write
BV7Cool operation modeSetting for cooling between off and auto operation.Write
BV8Int. Night heat func.Setting for activating the intermittent night heat function.Write
BV9Damper func.Write
BV10Summer night coolingSetting for activating the summer night cool function.Write
BV11Temp displacementWrite
BV12Outdoor temp compensationWrite
BV13Outdoor airflow compensationSetting for activating the outdoor airflow compensation function.Write
BV14Auto. Summer/winter switchWrite
BV15Switch clock func.Setting for switch clock function type.Write0=Stop - low speed - high speed, 1=Low speed - high speed
BV16Internal fire alarm func.Setting for activating the internal fire alarm function.Write
BV18External alarm 1 active at closureSetting for external alarm number 1 condition to be activated.Write0=Alarm at closed input, 1=Alarm at open input
BV19External alarm 2 active at closureSetting for external alarm number 2 condition to be activated.Write0=Alarm at closed input, 1=Alarm at open input
BV21Dewpoint reg. func.Setting for activating the dewpoint regulator function.Write
BV22Dehumid reg. func.Setting for activating the dehumid regulator function.Write
BV23External fire alarm func.Setting for external fire resetting function.Write0=Manual, 1=Automatic
BV24External alarm 1 func.Setting for external alarm 1 resetting function.Write0=Manual, 1=Automatic
BV25External alarm 2 func.Setting for external alarm 2 resetting function.Write0=Manual, 1=Automatic
BV26Temperature alarm func.Write
BV27Int. Night heat output func.Write0=IQnomic, 1=IQnomic+
BV28AYC heat out comp. func.Write0=Inactive, 1=Active
BV29AYC heat room comp. func.Setting for selecting the AYC room comp. heated water function.Write0=Inactive, 1=Active
BV30AYC heat room comp. night block func.Write0=Inactive, 1=Active
BV31AYC heat night comp. func.Setting for selecting the AYC night comp. heated water function.Write0=Inactive, 1=Active
BV32AYC heat valve signal func.Write0=Inactive, 1=Active
BV33AYC cool out comp. func.Write0=Inactive, 1=Active
BV34AYC cool room comp. func.Setting for selecting the AYC room comp. chilled water function.Write0=Inactive, 1=Active
BV35AYC cool room comp. night block func.Write0=Inactive, 1=Active
BV36AYC cool night comp. func.Setting for selecting the AYC night comp. chilled water functionWrite0=Inactive, 1=Active
BV37AYC cool valve signal func.Write0=Inactive, 1=Active
BV38BB func.Setting for selecting the Blue Box function. (from PV 6.05)Write0=Inactive, 1=Active
BV39BB optimize temp. func.Setting for selecting the Blue Box optimize temperature function. (from PV 6.05)Write0=Inactive, 1=Active
BV40Season heat modeSetting for selecting season heating mode. (from PV 6.08)Write0=Inactive, 1=Active
BV41Steam humid alarm inputSetting for selecting steam humidification alarm input. (from PV 6.08)Write0=NO(Alarm at open input), 1=NC(Alarm at closed input)
BV42ReCO2 zero cal.Setting for selecting zero calibration of ReCO2 pressure sensor. (from PV 6.08)Write0=Inactive, 1=Active
BV43EA flow zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV44SA flow zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV45SA filt zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV46EA filt zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV47SA duct zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV48EA duct zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV49R.HX zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV50SA pre-filt zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV51EA pre-filt zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV52SA end-filt zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV53NU B zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV54NU C zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV55NU D zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV56NU E zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV57NU F zero cal.(from PV 6.08)Write0=Inactive, 1=Active
BV58ReCO2 man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV59EA flow man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV60SA flow man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV61SA filt man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV62EA filt man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV63SA duct man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV64EA duct man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV65R.HX man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV66SA pre-filt man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV67EA pre-filt man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV68SA end-filt man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV69NU B man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV70NU C man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV71NU D man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV72NU E man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
BV73NU F man mode zero cal.(from PV 6.08)Write0=Auto, 1=Manual
NC0NC 00 A-Alarm(from PV 5.15)Read
NC1NC 00 B-Alarm(from PV 5.15)Read
Object ID lookup: Swegon GOLD generation C/D point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation C/D (RX/PX/CX/SD) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP

How many BACnet points does the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP have?

This list has 852 BACnet objects: 267 analog inputs, 462 analog values, 52 binary inputs, 69 binary values, 2 notification classs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet points are writable?

531 of the 852 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP BACnet documentation?

The source is BACnet IP GOLD RX/PX/CX/SD, Generation C/D (program version 6.08) (GB.BACnet480.121017), published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-d-2010-2013/communication/_en/bacnet480.6.08.pdf.

What are the minimum BACnet points to integrate the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?

Start with AV 174 Communication operation mode (BMS stop / low / high speed command (0 = Auto)); AV 40 SA Temperature setpoint (Supply air temperature setpoint); AV 41 EA/Room Temperature setpoint (Extract/room temperature setpoint); BV 0 Alarm reset (Resets alarms); AI 84 Operation mode 1 (Actual operating mode and what stopped the unit); AI 27 SA Temperature (Supply air temperature); AI 28 EA/Room temperature (Extract/room temperature); AI 29 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 5 A-alarm. (Any A-class alarm); BI 6 B-alarm. (Any B-class alarm).

How do I enable BMS control of the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?

AV 174 Communication operation mode: 0=Auto (normal stop when the time channels are deactivated), 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 (PV 5.00 or later; intermittent night heat and morning boost still work). AI 84 Operation mode 1 shows whether the unit is stopped or running from the hand terminal, an external input, communication or a time/year channel.

Can the BMS supply sensor values to the Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP?

Room temperature can come from the BMS: set AV 200 EA/Room temperature external func. to 2 (Communication) and write AV 201. Outdoor temperature works the same with AV 202 = 2 and AV 203. AV 204 sets the timeout for these communicated temperatures.

How do I check these points on the real GOLD generation C/D (RX/PX/CX/SD) BACnet IP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Swegon BACnet points lists

Source: BACnet IP GOLD RX/PX/CX/SD, Generation C/D (program version 6.08) · GB.BACnet480.121017. Object names, instances and units are reproduced as published; descriptions are our own.