 "manufacturer": "Swegon",
 "manufacturer_slug": "swegon",
 "model": "GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48",
 "model_slug": "gold-e-f-bacnet-ip-pv248",
 "aliases": [
  "GOLD F",
  "GOLD version F",
  "GOLD E",
  "GOLD RX",
  "GOLD PX",
  "GOLD CX",
  "GOLD SD",
  "IQlogic",
  "GOLD_E_F_BACnet_251202"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "Swegon GOLD air handling units of generations E and F (RX, PX, CX and SD versions) with program version 2.48.",
 "summary": "The built-in IQlogic controller in Swegon GOLD E/F air handlers is a native BACnet IP device (B-AAC) with no gateway. This PV 2.48 object list has about 2,160 objects, roughly 700 more than the 2015 generation-E list: fan airflow and pressure, temperatures and regulation levels, heat-exchanger and coil data, accessory functions, energy counters, one binary input per alarm, plus calendars, a schedule and notification classes. The unit is started, stopped and speed-selected from the BMS through one multistate value.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "GOLD PV 2.48 (EDE reference file 2.48, 2025-12-02)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Built from the EDE file in Swegon's GOLD E/F BACnet zip and checked against the PDF/xlsx object list in the same zip (GOLD_E_F_BACnet_251202). Access W = marked settable in the EDE. AI 181 is in the PDF but missing from the EDE and was added from the PDF; BI 1536 and BV 3230 are in the EDE only.",
  "One object list covers all RX, PX, CX and SD versions and every accessory; many objects only apply when the related function is fitted.",
  "The zip also has a variant of the list without the External override objects (instances 3000 and up) for units where that function is not wanted.",
  "Most alarms are individual BIs named 'Alarm <group>:<number> ...'; BI 13 and BI 14 summarize A- and B-class alarms.",
  "Where the EDE and PDF names differ, the EDE (device) name is used: the PDF calls AI 739-746 'Pulse counter input n kWh/MWh' and AV 519 'SMART Link OA temp limit'."
 ],
 "integration": {
  "summary": "Command the unit with MV 793 Communication operation level (Auto lets the internal time channel run it; the other states force stop, low or high speed) and read back MI 592 Operation level. Write the main temperature setpoints (AV 132 supply, AV 135 extract/room), read the supply, extract and outdoor temperatures, and watch BI 13/14 for A/B alarms with BV 1 to reset.",
  "minimum_points": [
   {
    "ref": "MV 793",
    "name": "Communication operation level",
    "why": "BMS start/stop and speed command"
   },
   {
    "ref": "AV 132",
    "name": "SA temperature set point",
    "why": "Supply air temperature setpoint"
   },
   {
    "ref": "AV 135",
    "name": "EA/Room temperature set point",
    "why": "Extract/room temperature setpoint"
   },
   {
    "ref": "BV 1",
    "name": "Alarm reset",
    "why": "Resets all active alarms"
   },
   {
    "ref": "MI 592",
    "name": "Operation level",
    "why": "Actual operating state and who stopped the unit"
   },
   {
    "ref": "AI 64",
    "name": "SA Temperature",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 66",
    "name": "EA Temperature",
    "why": "Extract air temperature"
   },
   {
    "ref": "AI 73",
    "name": "Outdoor temperature",
    "why": "Outdoor air temp measured by the unit, °C"
   },
   {
    "ref": "BI 13",
    "name": "A-alarm active",
    "why": "Any A-class alarm"
   },
   {
    "ref": "BI 14",
    "name": "B-alarm active",
    "why": "Any B-class alarm"
   }
  ],
  "enable": "MV 793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI 592 shows whether a stop or speed came from communication, the hand terminal, a digital input, the time channel or an alarm.",
  "heartbeat": null,
  "remote_sensors": "Room temperature can come from the BMS: enable BV 167 'External room temp from BMS function' and write AV 168; outdoor temperature likewise via BV 177 and AV 178. Each has an alarm-time AV in minutes (AV 169, AV 179). Xzone has its own BMS room temperature (BV 379, AV 380, AV 381).",
  "setup": [
   "BACnet IP only; the device is a B-AAC with intrinsic alarming through notification classes.",
   "The EDE gives device instance 0 as the reference value; set the real device instance and IP settings on the unit."
  ],
  "gotchas": [
   "Setpoints are split by low and high speed (e.g. AV 3/5 SA airflow, AV 19/21 SA duct pressure); write the one for the active speed.",
   "Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is fitted.",
   "External override objects (instances 3000 and up) take over fans and heat exchanger for a set time; leave them alone unless that function is planned."
  ]
 },
 "source": {
  "title": "BACnet IP GOLD RX/PX/CX/SD, Generation E/F (with EDE, PICS and state/unit files)",
  "doc_number": "GOLD_E_F_BACnet_251202 (Swegon doc 9307)",
  "revision_date": "2025-12-02",
  "url": "https://www.swegon.com/globalassets/digizuite/9307-en-gold_e_bacnet_pv110_other_en.zip"
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Component name",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "SA Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "SA Air flow regulator",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "EA Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "EA Air flow regulator",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "SA Duct pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "SA Duct pressure regulator",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "EA Duct pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "EA Duct pressure regulator",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Demand input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Demand regulator",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "SA Air flow pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "EA Air flow pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Demand CO2 regulator",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Demand VOC regulator",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "SA Pre-filter pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "SA Pre-filter pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "EA Pre-filter pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "EA Pre-filter pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "SA AHU filter pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "SA AHU filter pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "EA AHU filter pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "EA AHU filter pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "SA End-filter pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "SA End-filter pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "SA Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "EA Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "SA Fan speed",
   "description": "",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "EA Fan speed",
   "description": "",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "SA Voltage",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "EA Voltage",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "SA Fan current",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "EA Fan current",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "SA Fan power",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "EA Fan power",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "SA Fan kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "EA Fan kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "SA Fan MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "EA Fan MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "SA Fan operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "EA Fan operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "SA Fan min air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "EA Fan min air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "SA Fan max air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "EA Fan max air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "SA Temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "SA-D Temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "EA Temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "EA-D Temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "EA Regulation temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "EA Temperature PX/CX",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "EA Temperature SD",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "Outdoor temperature COOL DX",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "Outdoor temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "Outdoor regulation temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "External outdoor temperature 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "External outdoor temperature 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "External outdoor temperature 3",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "External outdoor temperature 4",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "EA Duct temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "Room temperature 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "Room temperature 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "Room temperature 3",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "Room temperature 4",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "SA Temp regulator",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "EA Temp regulator",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Cool exchanger regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "Heat exchanger regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "Extra regulation sequence 1 heat regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "Extra regulation sequence 1 heat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "Reheat regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "Reheat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "ReCO2 heat level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "Down regulation level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Heating boost level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Extra regulation sequence 1 cool regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Extra regulation sequence 1 cool output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Cool regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Cool output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "ReCO2 cool level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Cooling boost level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "RHX operation level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "RHX/PHX/CHX efficiency",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "RHX defrost pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "RHX defrost pressure alarm limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "RHX carry over control pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "RHX operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "PX exchanger bypass 4A output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "PX exchanger bypass 4A feedback",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "PX defrost pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 117,
   "name": "PHX-3D Bypass output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "PHX-3D Bypass input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "PHX-3D Bypass temperature 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "PHX-3D Bypass temperature 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "PX exchanger damper 1 output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "PHX-2 Damper 1 input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "PX exchanger damper 2 output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "PHX-2 Damper 2 input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "PX exchanger bypass output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "PX exchanger bypass feedback",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "CHX-1 Valve output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "CHX-1 Valve input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "CHX-1 Return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "PHX/CHX operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "PHX-1D Bypass output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "PHX-1D Bypass input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "CHX-2 Return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "CHX-2 Extract coil pressure level",
   "description": "",
   "units": "mbar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "PHX/CHX Humidity level",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "CHX-2 Valve output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 138,
   "name": "CHX-2 Valve input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "CHX-2 Pump output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "Extra regulation sequence 1 anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "Extra regulation sequence 2 anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "Extra regulation sequence 1 temperature guard",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "Extra regulation sequence 2 temperature guard",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "Extra regulation sequence 1 input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "Extra regulation sequence 1 heat operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "Extra regulation sequence 1 cool operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "Extra regulation sequence 2 input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "Extra regulation sequence 2 heat operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "Extra regulation sequence 2 cool operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "Re-heat anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "Re-heat input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "Re-heat operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "Cool water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "Cool input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "Cool operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "Xzone SA temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 175,
   "name": "Xzone EA temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 176,
   "name": "Xzone EA regulation temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 177,
   "name": "Xzone Room temperature 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 178,
   "name": "Xzone Room temperature 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 179,
   "name": "Xzone Room temperature 3",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "Xzone Room temperature 4",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "Xzone Room temperature min/max/average",
   "description": "Min, max or average of room sensors 1-4, per configuration",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 186,
   "name": "Xzone SA Temp regulator",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 187,
   "name": "Xzone EA Temp regulator",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "Xzone re-heat regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "Xzone cool regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 199,
   "name": "Xzone heat, anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 200,
   "name": "Xzone heat/cool temperature guard",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "Xzone heat, output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "Xzone heat, input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "Xzone heat, operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "Xzone cool, water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 211,
   "name": "Xzone cool temperature guard",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "Xzone cool, output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 215,
   "name": "Xzone cool, input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 216,
   "name": "Xzone cool, operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "Pre-heat temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 221,
   "name": "Pre-heat temp regulator set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 222,
   "name": "Pre-heat temp regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 225,
   "name": "Pre-heat anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 228,
   "name": "Pre-heat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 229,
   "name": "Pre-heat input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "Pre-heat operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 233,
   "name": "ReCO2 recirculation damper output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 234,
   "name": "ReCO2 recirculation damper input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 235,
   "name": "ReCO2 outdoor damper output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 236,
   "name": "ReCO2 outdoor damper input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 237,
   "name": "ReCO2 outdoor air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 238,
   "name": "ReCO2 outdoor air flow regulator set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "SA humidity level",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 245,
   "name": "SA humidity temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 246,
   "name": "SA dew point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 247,
   "name": "EA humidity level",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 248,
   "name": "EA humidity temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 249,
   "name": "EA dew point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Dehumidifying SA dew point regulator set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Dehumidifying output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "Humidifying SA regulator set point",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 255,
   "name": "Humidifying output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 260,
   "name": "Exhaust air humidity",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 261,
   "name": "Exhaust air temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 262,
   "name": "Outdoor air humidity",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 263,
   "name": "Outdoor air temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 264,
   "name": "Room air humidity",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 265,
   "name": "Room air temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 266,
   "name": "VOC level",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 267,
   "name": "CO2 level",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 271,
   "name": "COOL DX, unit power size",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 274,
   "name": "COOL DX, compressor 1 low pressure level",
   "description": "",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 275,
   "name": "COOL DX, compressor 1 high pressure level",
   "description": "",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 276,
   "name": "COOL DX, compressor 2 low pressure level",
   "description": "",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 277,
   "name": "COOL DX, compressor 2 high pressure level",
   "description": "",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 281,
   "name": "Exhaust heat temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 282,
   "name": "Exhaust heat temp regulator set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 283,
   "name": "Exhaust heat temp regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 285,
   "name": "Exhaust heat anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 286,
   "name": "Exhaust heat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 287,
   "name": "Exhaust heat input level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 288,
   "name": "Exhaust heat operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "SMART Link, WB outlet water 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "SMART Link, WB outlet water 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 291,
   "name": "SMART Link, WB outlet water 3",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 292,
   "name": "SMART Link, WB outlet water 4",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 293,
   "name": "SMART Link, WB outlet water average",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 294,
   "name": "SMART Link, WB reference water",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 297,
   "name": "SMART Link WB, heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 298,
   "name": "SMART Link WB, chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "SMART Link WB, Min heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "SMART Link WB, Max heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "SMART Link WB, Min chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "SMART Link WB, Max chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 327,
   "name": "SMART Link, DX unit 1 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 328,
   "name": "SMART Link, DX unit 1 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 329,
   "name": "SMART Link, DX unit 1 operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 338,
   "name": "SMART Link, DX unit 2 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 339,
   "name": "SMART Link, DX unit 2 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 340,
   "name": "SMART Link, DX unit 2 operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 349,
   "name": "SMART Link, DX unit 3 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 350,
   "name": "SMART Link, DX unit 3 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 351,
   "name": "SMART Link, DX unit 3 operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 360,
   "name": "SMART Link, DX unit 4 power level set point",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 361,
   "name": "SMART Link, DX unit 4 power level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 362,
   "name": "SMART Link, DX unit 4 operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 374,
   "name": "AYC Heat, heated water",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 375,
   "name": "AYC Heated water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 376,
   "name": "AYC Heat, valve output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 377,
   "name": "AYC Heat, valve input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 378,
   "name": "AYC Heat, operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 379,
   "name": "AYC Heated water heat demand",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 387,
   "name": "AYC Cool, chilled water",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 388,
   "name": "AYC Chilled water set point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 389,
   "name": "AYC Cool, valve output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 390,
   "name": "AYC Cool, valve input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 391,
   "name": "AYC Cool, operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 392,
   "name": "AYC Chilled water cool demand",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 400,
   "name": "MIRU Control 1 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 401,
   "name": "MIRU Control 1 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 402,
   "name": "MIRU Control 1 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 403,
   "name": "MIRU Control 1 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 404,
   "name": "MIRU Control 1 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 405,
   "name": "MIRU Control 1 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 406,
   "name": "MIRU Control 1 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 407,
   "name": "MIRU Control 1 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 408,
   "name": "MIRU Control 1 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 409,
   "name": "MIRU Control 1 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 410,
   "name": "MIRU Control 1 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 411,
   "name": "MIRU Control 1 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 412,
   "name": "MIRU Control 1 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 417,
   "name": "MIRU Control 2 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 418,
   "name": "MIRU Control 2 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 419,
   "name": "MIRU Control 2 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 420,
   "name": "MIRU Control 2 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 421,
   "name": "MIRU Control 2 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 422,
   "name": "MIRU Control 2 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 423,
   "name": "MIRU Control 2 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 424,
   "name": "MIRU Control 2 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 425,
   "name": "MIRU Control 2 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 426,
   "name": "MIRU Control 2 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 427,
   "name": "MIRU Control 2 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 428,
   "name": "MIRU Control 2 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 429,
   "name": "MIRU Control 2 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 434,
   "name": "MIRU Control 3 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 435,
   "name": "MIRU Control 3 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 436,
   "name": "MIRU Control 3 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 437,
   "name": "MIRU Control 3 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 438,
   "name": "MIRU Control 3 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 439,
   "name": "MIRU Control 3 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 440,
   "name": "MIRU Control 3 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 441,
   "name": "MIRU Control 3 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 442,
   "name": "MIRU Control 3 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 443,
   "name": "MIRU Control 3 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 444,
   "name": "MIRU Control 3 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 445,
   "name": "MIRU Control 3 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 446,
   "name": "MIRU Control 3 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 451,
   "name": "MIRU Control 4 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 452,
   "name": "MIRU Control 4 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 453,
   "name": "MIRU Control 4 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 454,
   "name": "MIRU Control 4 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 455,
   "name": "MIRU Control 4 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 456,
   "name": "MIRU Control 4 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 457,
   "name": "MIRU Control 4 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 458,
   "name": "MIRU Control 4 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 459,
   "name": "MIRU Control 4 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 460,
   "name": "MIRU Control 4 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 461,
   "name": "MIRU Control 4 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 462,
   "name": "MIRU Control 4 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 463,
   "name": "MIRU Control 4 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 468,
   "name": "MIRU Control 5 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 469,
   "name": "MIRU Control 5 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 470,
   "name": "MIRU Control 5 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 471,
   "name": "MIRU Control 5 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 472,
   "name": "MIRU Control 5 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 473,
   "name": "MIRU Control 5 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 474,
   "name": "MIRU Control 5 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 475,
   "name": "MIRU Control 5 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 476,
   "name": "MIRU Control 5 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 477,
   "name": "MIRU Control 5 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 478,
   "name": "MIRU Control 5 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 479,
   "name": "MIRU Control 5 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 480,
   "name": "MIRU Control 5 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 485,
   "name": "MIRU Control 6 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 486,
   "name": "MIRU Control 6 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 487,
   "name": "MIRU Control 6 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 488,
   "name": "MIRU Control 6 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 489,
   "name": "MIRU Control 6 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 490,
   "name": "MIRU Control 6 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 491,
   "name": "MIRU Control 6 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 492,
   "name": "MIRU Control 6 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 493,
   "name": "MIRU Control 6 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 494,
   "name": "MIRU Control 6 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 495,
   "name": "MIRU Control 6 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 496,
   "name": "MIRU Control 6 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 497,
   "name": "MIRU Control 6 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 502,
   "name": "MIRU Control 7 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 503,
   "name": "MIRU Control 7 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 504,
   "name": "MIRU Control 7 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 505,
   "name": "MIRU Control 7 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 506,
   "name": "MIRU Control 7 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 507,
   "name": "MIRU Control 7 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 508,
   "name": "MIRU Control 7 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 509,
   "name": "MIRU Control 7 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 510,
   "name": "MIRU Control 7 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 511,
   "name": "MIRU Control 7 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 512,
   "name": "MIRU Control 7 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 513,
   "name": "MIRU Control 7 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 514,
   "name": "MIRU Control 7 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 519,
   "name": "MIRU Control 8 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 520,
   "name": "MIRU Control 8 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 521,
   "name": "MIRU Control 8 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 522,
   "name": "MIRU Control 8 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 523,
   "name": "MIRU Control 8 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 524,
   "name": "MIRU Control 8 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 525,
   "name": "MIRU Control 8 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 526,
   "name": "MIRU Control 8 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 527,
   "name": "MIRU Control 8 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 528,
   "name": "MIRU Control 8 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 529,
   "name": "MIRU Control 8 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 530,
   "name": "MIRU Control 8 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 531,
   "name": "MIRU Control 8 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 536,
   "name": "MIRU Control 9 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 537,
   "name": "MIRU Control 9 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 538,
   "name": "MIRU Control 9 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 539,
   "name": "MIRU Control 9 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 540,
   "name": "MIRU Control 9 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 541,
   "name": "MIRU Control 9 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 542,
   "name": "MIRU Control 9 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 543,
   "name": "MIRU Control 9 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 544,
   "name": "MIRU Control 9 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 545,
   "name": "MIRU Control 9 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 546,
   "name": "MIRU Control 9 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 547,
   "name": "MIRU Control 9 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 548,
   "name": "MIRU Control 9 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 553,
   "name": "MIRU Control 10 Min air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 554,
   "name": "MIRU Control 10 Max air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 555,
   "name": "MIRU Control 10 Air flow",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 556,
   "name": "MIRU Control 10 Air flow set point",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 557,
   "name": "MIRU Control 10 Pressure",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 558,
   "name": "MIRU Control 10 Pressure set point",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 559,
   "name": "MIRU Control 10 External temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 560,
   "name": "MIRU Control 10 Operation time",
   "description": "",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 561,
   "name": "MIRU Control 10 Fan level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 562,
   "name": "MIRU Control 10 Fan power",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 563,
   "name": "MIRU Control 10 SFP",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 564,
   "name": "MIRU Control 10 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 565,
   "name": "MIRU Control 10 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 570,
   "name": "IQlogic software version",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 604,
   "name": "Triggered alarm #1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 605,
   "name": "Triggered alarm #2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 606,
   "name": "Triggered alarm #3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 607,
   "name": "Triggered alarm #4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 608,
   "name": "Triggered alarm #5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 609,
   "name": "Triggered alarm #6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 610,
   "name": "Triggered alarm #7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 611,
   "name": "Triggered alarm #8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 612,
   "name": "Triggered alarm #9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 613,
   "name": "Triggered alarm #10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 614,
   "name": "Triggered alarm group #1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 615,
   "name": "Triggered alarm group #2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 616,
   "name": "Triggered alarm group #3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 617,
   "name": "Triggered alarm group #4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 618,
   "name": "Triggered alarm group #5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 619,
   "name": "Triggered alarm group #6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 620,
   "name": "Triggered alarm group #7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 621,
   "name": "Triggered alarm group #8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 622,
   "name": "Triggered alarm group #9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 623,
   "name": "Triggered alarm group #10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 661,
   "name": "Prolonged low speed remaining hours",
   "description": "",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 662,
   "name": "Prolonged low speed remaining seconds",
   "description": "",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 663,
   "name": "Prolonged high speed remaining hours",
   "description": "",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 664,
   "name": "Prolonged high speed remaining seconds",
   "description": "",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 697,
   "name": "Exhaust heat heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 698,
   "name": "Exhaust heat heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 699,
   "name": "Exhaust heat frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 700,
   "name": "Extra regulation sequence 2 heat regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 701,
   "name": "Extra regulation sequence 2 heat output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 702,
   "name": "Extra regulation sequence 2 cool regulator level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 703,
   "name": "Extra regulation sequence 2 cool output level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 704,
   "name": "Re-heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 705,
   "name": "Re-heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 706,
   "name": "Re-heat frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 707,
   "name": "Pre-heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 708,
   "name": "Pre-heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 709,
   "name": "Pre-heat frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 710,
   "name": "Xzone heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 711,
   "name": "Xzone heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 712,
   "name": "Xzone frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 713,
   "name": "Extra regulation sequence 1 heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 714,
   "name": "Extra regulation sequence 1 heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 715,
   "name": "Extra regulation sequence 1 frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 716,
   "name": "Extra regulation sequence 2 heat retention at stop",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 717,
   "name": "Extra regulation sequence 2 heat retention at operation",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 718,
   "name": "Extra regulation sequence 2 frost protection alarm limit",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 719,
   "name": "Heat exchange motor power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 720,
   "name": "Heat exchange motor power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 721,
   "name": "Heat exchange motor energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 722,
   "name": "Heat exchange motor energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 723,
   "name": "Heat power recovery W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 724,
   "name": "Heat power recovery kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 725,
   "name": "Heat power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 726,
   "name": "Heat power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 727,
   "name": "Cool power recovery W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 728,
   "name": "Cool power recovery kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 729,
   "name": "Cool power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 730,
   "name": "Cool power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 731,
   "name": "Heat energy recovery kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 732,
   "name": "Heat energy recovery MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 733,
   "name": "Cool energy recovery kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 734,
   "name": "Cool energy recovery MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 735,
   "name": "Heat energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 736,
   "name": "Heat energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 737,
   "name": "Cool energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 738,
   "name": "Cool energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 739,
   "name": "Energy input 1 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 740,
   "name": "Energy input 1 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 741,
   "name": "Energy input 2 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 742,
   "name": "Energy input 2 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 743,
   "name": "Energy input 3 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 744,
   "name": "Energy input 3 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 745,
   "name": "Energy input 4 kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 746,
   "name": "Energy input 4 MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 747,
   "name": "Re-heat water coil power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 748,
   "name": "Re-heat water coil power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 749,
   "name": "Re-heat water coil energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 750,
   "name": "Re-heat water coil energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 751,
   "name": "Cool water coil power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 752,
   "name": "Cool water coil power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 753,
   "name": "Cool water coil energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 754,
   "name": "Cool water coil energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 755,
   "name": "Xzone heat water coil power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 756,
   "name": "Xzone heat water coil power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 757,
   "name": "Xzone heat water coil energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 758,
   "name": "Xzone heat water coil energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 759,
   "name": "Xzone cool water coil power consumption W",
   "description": "",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 760,
   "name": "Xzone cool water coil power consumption kW",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 761,
   "name": "Xzone cool water coil energy consumption kWh",
   "description": "",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 762,
   "name": "Xzone cool water coil energy consumption MWh",
   "description": "",
   "units": "MWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 763,
   "name": "Re-heat liquid flow level",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 764,
   "name": "Cool liquid flow level",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 765,
   "name": "Xzone heat liquid flow level",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 766,
   "name": "Xzone cool liquid flow level",
   "description": "",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 780,
   "name": "Re-heat return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 781,
   "name": "Re-heat flow water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 782,
   "name": "Cool return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 783,
   "name": "Cool flow water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 784,
   "name": "Xzone heat return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 785,
   "name": "Xzone heat flow water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 786,
   "name": "Xzone cool return water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 787,
   "name": "Xzone cool flow water temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 800,
   "name": "External operation I/O-module 3, analogue input 1",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 801,
   "name": "External operation I/O-module 3, analogue input 2",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 804,
   "name": "External operation I/O-module 3, analogue output 1",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 805,
   "name": "External operation I/O-module 3, analogue output 2",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 806,
   "name": "External operation I/O-module 6, analogue input 1",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 807,
   "name": "External operation I/O-module 6, analogue input 2",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 810,
   "name": "External operation I/O-module 6, analogue output 1",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 811,
   "name": "External operation I/O-module 6, analogue output 2",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 812,
   "name": "External operation I/O-module A, analogue input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 813,
   "name": "External operation I/O-module A, temp sensor 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 814,
   "name": "External operation I/O-module A, temp sensor 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 815,
   "name": "External operation I/O-module B, analogue input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 816,
   "name": "External operation I/O-module B, temp sensor 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 817,
   "name": "External operation I/O-module B, temp sensor 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 818,
   "name": "External operation I/O-module C, analogue input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 819,
   "name": "External operation I/O-module C, temp sensor 1",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 820,
   "name": "External operation I/O-module C, temp sensor 2",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1405,
   "name": "H/C recirculation defrost damper output",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1406,
   "name": "H/C recirculation defrost damper input",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1409,
   "name": "H/C heat anti frost temp/overheat input",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1413,
   "name": "H/C operation level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1414,
   "name": "H/C heat defrost level",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1415,
   "name": "H/C defrost pressure level",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1416,
   "name": "H/C defrost pressure start limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1417,
   "name": "H/C defrost pressure end limit",
   "description": "",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1418,
   "name": "H/C superheat temp",
   "description": "",
   "units": "K",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1419,
   "name": "H/C discharge temp",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1420,
   "name": "H/C suction temp",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1421,
   "name": "H/C condensation temp",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1422,
   "name": "H/C evaporation temp",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1423,
   "name": "H/C high pressure",
   "description": "",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1424,
   "name": "H/C low pressure",
   "description": "",
   "units": "bar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3002,
   "name": "External override, remaining time",
   "description": "",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Extract air start up",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "SA low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "EA low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "SA high speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "EA high speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "SA max speed air flow set point boost",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "EA max speed air flow set point boost",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "SA regulation zone",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "EA regulation zone",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SA regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "EA regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "SA low speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "EA low speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "SA high speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "EA high speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "SA max speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "EA max speed pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "SA max speed output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "EA max speed output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "SA pressure regulation zone",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "EA pressure regulation zone",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "SA pressure I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "EA pressure I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Demand low speed CO2 set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Demand high speed CO2 set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Demand low speed VOC set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Demand high speed VOC set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Demand low speed set point",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Demand high speed set point",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SA min speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "EA min speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SA max speed air flow set point demand",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "EA max speed air flow set point demand",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Demand P-band",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Demand I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Demand CO2 P-band",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Demand VOC P-band",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Slave offset factor",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "SA slave offset air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "EA slave offset air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Outdoor temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Outdoor temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Outdoor temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Outdoor temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Outdoor temp compensation Y1 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Outdoor temp compensation Y2 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Outdoor temp compensation Y3 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "Outdoor temp compensation Y4 SA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Outdoor temp compensation Y1 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Outdoor temp compensation Y2 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Outdoor temp compensation Y3 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Outdoor temp compensation Y4 EA air flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Outdoor temp compensation Y1 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Outdoor temp compensation Y2 SA  pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "Outdoor temp compensation Y3 SA  pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Outdoor temp compensation Y4 SA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "Outdoor temp compensation Y1 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Outdoor temp compensation Y2 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Outdoor temp compensation Y3 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Outdoor temp compensation Y4 EA pressure",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "Down regulation neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "Down regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "Down regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "SA fan speed at fire alarm 1",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "EA fan speed at fire alarm 1",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "SA fan speed at fire alarm 2",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "EA fan speed at fire alarm 2",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "SA fan speed at internal fire alarm",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "EA fan speed at internal fire alarm",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "SA pre-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "EA pre-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "SA AHU-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "EA AHU-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "SA end-filter alarm limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "Seasonal controlled temperature regulation active",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "Seasonal controlled temperature regulation inactive",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "ERS 1 step",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "ERS 1 diff",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "ERS 1 breakpoint",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "ERS 2 breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "ERS 2 breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "ERS 2 breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "ERS 2 breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "ERS 2 breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "ERS 2 breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "ERS 2 breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "ERS 2 breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "SA temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "EA/Room temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "SA min temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "SA max temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "EA regultaion P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "EA regultaion I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "ORS breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "ORS breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "ORS breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "ORS breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "ORS breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "ORS breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "ORS breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "ORS breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "ORE breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "ORE breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "ORE breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "ORE breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "ORE breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "ORE breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "ORE breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "ORE breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "External room temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "External room temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "External OA temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "External OA temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "RHX defrost start limit",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "RHX min exhaust air temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "RHX min exhaust air temp P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "RHX min exhaust air temp I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "PHX periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "PHX periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "PHX supply air temp set point displacement",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "CHX periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "CHX periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "PHX/CHX Bypass defrost limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "PHX/CHX Bypass defrost P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "PHX/CHX Bypass defrost I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "Heat exchange temperature regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "Heat exchange temperature regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "Cool exchange temperature regulation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "Cool exchange temperature regulation I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "Re-heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "Re-heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Re-heat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "Re-heat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "Extra regulation sequence 1 heat max output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "Extra regulation sequence 1 cool max output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "Extra regulation sequence 1 heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "Extra regulation sequence 1 heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "Extra regulation sequence 1 cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "Extra regulation sequence 1 cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 247,
   "name": "Extra regulation 1 periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "Extra regulation 1 periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 252,
   "name": "Extra regulation 1 temperature protection temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 253,
   "name": "Extra regulation 1 temperature protection alarm delay",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 258,
   "name": "Cool step1 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 259,
   "name": "Cool step2 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 260,
   "name": "Cool step3 min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 262,
   "name": "Cool SA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 263,
   "name": "Cool EA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 264,
   "name": "Cool outdoor temp limit 1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "Cool outdoor temp limit 2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "Cool outdoor temp limit 3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "Cool 0-10V min supply air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "Cool 0-10V min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "Cool restart time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "Cool step up delay time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "Cool stand still time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "Cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "Cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "Cool periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "Cool periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "Cool step1 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "Cool step2 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "Cool step3 min extract air flow limit",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "Summer night cool start time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "Summer night cool start time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "Summer night cool stop time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "Summer night cool stop time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "Summer night cool OA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "Summer night cool EA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "Summer night cool EA temp stop limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "Summer night cool SA temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 293,
   "name": "Summer night cool SA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 294,
   "name": "Summer night cool EA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "Intermittent night heat SA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "Intermittent night heat SA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 299,
   "name": "Intermittent night heat EA temp start limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "Intermittent night heat EA temp stop limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "Intermittent night heat SA temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "Intermittent night heat EA flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 304,
   "name": "Intermittent night heat EA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 306,
   "name": "Morning boost start time (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 307,
   "name": "Morning boost start time (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 308,
   "name": "Morning boost air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 309,
   "name": "Morning boost duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "Summer night cool SA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "Summer night cool EA duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "Cooling boost comfort start limit",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "Cooling boost comfort regulation speed",
   "description": "",
   "units": "%/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "Cooling boost economy P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "Cooling boost economy I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "Heating boost comfort start limit",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "Heating boost comfort regulation speed",
   "description": "",
   "units": "%/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 331,
   "name": "Xzone ERS 1 step",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 332,
   "name": "Xzone ERS 1 diff",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 333,
   "name": "Xzone ERS 1 breakpoint",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 336,
   "name": "Xzone ERS 2 breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 337,
   "name": "Xzone ERS 2 breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 338,
   "name": "Xzone ERS 2 breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 339,
   "name": "Xzone ERS 2 breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 340,
   "name": "Xzone ERS 2 breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 341,
   "name": "Xzone ERS 2 breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 342,
   "name": "Xzone ERS 2 breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 343,
   "name": "Xzone ERS 2 breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 346,
   "name": "Xzone SA temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 349,
   "name": "Xzone EA/Room temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 350,
   "name": "Xzone SA min temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 351,
   "name": "Xzone SA max temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 352,
   "name": "Xzone EA regultaion P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 353,
   "name": "Xzone EA regultaion I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 354,
   "name": "Xzone ORS breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 355,
   "name": "Xzone ORS breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 356,
   "name": "Xzone ORS breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 357,
   "name": "Xzone ORS breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 358,
   "name": "Xzone ORS breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 359,
   "name": "Xzone ORS breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 360,
   "name": "Xzone ORS breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 361,
   "name": "Xzone ORS breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 364,
   "name": "Xzone ORE breakpoint X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 365,
   "name": "Xzone ORE breakpoint X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 366,
   "name": "Xzone ORE breakpoint X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 367,
   "name": "Xzone ORE breakpoint X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 368,
   "name": "Xzone ORE breakpoint Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 369,
   "name": "Xzone ORE breakpoint Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 370,
   "name": "Xzone ORE breakpoint Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 371,
   "name": "Xzone ORE breakpoint Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 380,
   "name": "Xzone external room temp from BMS",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 381,
   "name": "Xzone external room temp from BMS alarm time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 384,
   "name": "Xzone reheat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 385,
   "name": "Xzone reheat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 388,
   "name": "Xzone reheat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 389,
   "name": "Xzone reheat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "Xzone Cool SA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 397,
   "name": "Xzone Cool EA neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "Xzone Cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "Xzone Cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 403,
   "name": "Xzone Cool periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 404,
   "name": "Xzone Cool periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "Pre-heat temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "Pre-heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "Pre-heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 416,
   "name": "Pre-heat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 417,
   "name": "Pre-heat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 426,
   "name": "ReCO2-CO2 set point",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 427,
   "name": "ReCO2 min. outdoor air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 428,
   "name": "ReCO2 min. exhaust air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 429,
   "name": "ReCO2-CO2 P-band",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 430,
   "name": "ReCO2-CO2 I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 431,
   "name": "ReCO2-CO2 air flow boost reg. P-band",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 432,
   "name": "ReCO2-CO2 air flow boost reg. I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 433,
   "name": "ReCO2 heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 434,
   "name": "ReCO2 heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 435,
   "name": "ReCO2 cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 436,
   "name": "ReCO2 cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 437,
   "name": "ReCO2-CO2 ppm set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 438,
   "name": "ReCO2-CO2 ppm P-band",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 439,
   "name": "ReCO2-VOC ppm set point",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 440,
   "name": "ReCO2-VOC ppm P-band",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 443,
   "name": "Humidifying on/off start level",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "Humidifying on/off stop level",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 448,
   "name": "Humidifying 0-10V set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 449,
   "name": "Humidifying 0-10V SA max set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 450,
   "name": "Humidifying 0-10V SA P-band",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 451,
   "name": "Humidifying 0-10V SA I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 452,
   "name": "Humidifying 0-10V EA P-band",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 453,
   "name": "Humidifying 0-10V EA I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 458,
   "name": "Dehumidifying SA set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 460,
   "name": "Dehumidifying EA set point",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 470,
   "name": "COOL DX Low pressure stop limit",
   "description": "",
   "units": "kPa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 471,
   "name": "COOL DX High pressure stop limit",
   "description": "",
   "units": "kPa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 472,
   "name": "COOL DX Restart time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 474,
   "name": "Exhaust heat temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 475,
   "name": "Exhaust heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 476,
   "name": "Exhaust heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 479,
   "name": "Exhaust heat periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 480,
   "name": "Exhaust heat periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 482,
   "name": "SMART Link WB Heat temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 483,
   "name": "SMART Link WB Heat temperature heat zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 484,
   "name": "SMART Link WB Cool temperature set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 485,
   "name": "SMART Link WB Cool temperature heat zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 491,
   "name": "SMART Link WB Optimize valve upper limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 492,
   "name": "SMART Link WB Optimize valve lower limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 493,
   "name": "SMART Link WB Optimize time delay",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 494,
   "name": "SMART Link WB Optimize heat regulation speed",
   "description": "",
   "units": "K/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 495,
   "name": "SMART Link WB Optimize cool regulation speed",
   "description": "",
   "units": "K/min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 510,
   "name": "SMART Link DX Amount of units",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 519,
   "name": "SMART Link OA operation limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 524,
   "name": "AYC Heated water temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 526,
   "name": "AYC Heated water OA temp for start of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 527,
   "name": "AYC Heated water OA temp for stop of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 532,
   "name": "AYC Heated water periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 533,
   "name": "AYC Heated water periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "AYC Heated water OA temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "AYC Heated water OA temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 539,
   "name": "AYC Heated water OA temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540,
   "name": "AYC Heated water OA temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 541,
   "name": "AYC Heated water OA temp compensation Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 542,
   "name": "AYC Heated water OA temp compensation Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 543,
   "name": "AYC Heated water OA temp compensation Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 544,
   "name": "AYC Heated water OA temp compensation Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 549,
   "name": "AYC Heated water room temp compensation temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 550,
   "name": "AYC Heated water room temp compensation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 554,
   "name": "AYC Heated water night temp compensation temp",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 556,
   "name": "AYC Heated water night temp compensation start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 557,
   "name": "AYC Heated water night temp compensation start time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 558,
   "name": "AYC Heated water night temp compensation stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 559,
   "name": "AYC Heated water night temp compensation stop time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 563,
   "name": "AYC Heated water night temp compensation start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 564,
   "name": "AYC Heated water night temp compensation start time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 565,
   "name": "AYC Heated water night temp compensation stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 566,
   "name": "AYC Heated water night temp compensation stop time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 569,
   "name": "AYC Heated water P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 570,
   "name": "AYC Heated water I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 572,
   "name": "AYC Chilled water temp set point",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 575,
   "name": "AYC Chilled water OA temp for start of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 576,
   "name": "AYC Chilled water OA temp for stop of pump",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 581,
   "name": "AYC Chilled water periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582,
   "name": "AYC Chilled water periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 586,
   "name": "AYC Chilled water OA temp compensation X1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 587,
   "name": "AYC Chilled water OA temp compensation X2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 588,
   "name": "AYC Chilled water OA temp compensation X3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 589,
   "name": "AYC Chilled water OA temp compensation X4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 590,
   "name": "AYC Chilled water OA temp compensation Y1",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 591,
   "name": "AYC Chilled water OA temp compensation Y2",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 592,
   "name": "AYC Chilled water OA temp compensation Y3",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 593,
   "name": "AYC Chilled water OA temp compensation Y4",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 598,
   "name": "AYC Chilledwater room temp compensation temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 599,
   "name": "AYC Chilled water room temp compensation P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 603,
   "name": "AYC Chilled water night temp compensation temp",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 605,
   "name": "AYC Chilled water night temp compensation start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 606,
   "name": "AYC Chilled water night temp compensation start time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 607,
   "name": "AYC Chilled water night temp compensation stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 608,
   "name": "AYC Chilled water night temp compensation stop time 1 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 612,
   "name": "AYC Chilled water night temp compensation start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 613,
   "name": "AYC Chilled water night temp compensation start time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 614,
   "name": "AYC Chilledwater night temp compensation stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 615,
   "name": "AYC Chilled water night temp compensation stop time 2 (minutes)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 619,
   "name": "AYC Chilled water dew point compensation neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 620,
   "name": "AYC Chilled water dew point compensation regulation speed",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 623,
   "name": "AYC Chilled water P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 624,
   "name": "AYC Chilled water I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 638,
   "name": "Optimize SA pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 639,
   "name": "Optimize EA pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 672,
   "name": "MIRU Control 1 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 673,
   "name": "MIRU Control 1 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 674,
   "name": "MIRU Control 1 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 675,
   "name": "MIRU Control 1 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 676,
   "name": "MIRU Control 1 offset factor for slave controlled air flow",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 677,
   "name": "MIRU Control 1 fixed flow offset for slave controlled SA flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 680,
   "name": "MIRU Control 2 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 681,
   "name": "MIRU Control 2 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 682,
   "name": "MIRU Control 2 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 683,
   "name": "MIRU Control 2 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 684,
   "name": "MIRU Control 2 offset factor for slave controlled air flow",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 685,
   "name": "MIRU Control 2 fixed flow offset for slave controlled SA flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 688,
   "name": "MIRU Control 3 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 689,
   "name": "MIRU Control 3 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 690,
   "name": "MIRU Control 3 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 691,
   "name": "MIRU Control 3 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 692,
   "name": "MIRU Control 3 offset factor for slave controlled air flow",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 693,
   "name": "MIRU Control 3 fixed flow offset for slave controlled SA flow",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 696,
   "name": "MIRU Control 4 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 697,
   "name": "MIRU Control 4 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 698,
   "name": "MIRU Control 4 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 699,
   "name": "MIRU Control 4 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 704,
   "name": "MIRU Control 5 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 705,
   "name": "MIRU Control 5 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 706,
   "name": "MIRU Control 5 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 707,
   "name": "MIRU Control 5 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 712,
   "name": "MIRU Control 6 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 713,
   "name": "MIRU Control 6 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 714,
   "name": "MIRU Control 6 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 715,
   "name": "MIRU Control 6 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 720,
   "name": "MIRU Control 7 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 721,
   "name": "MIRU Control 7 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 722,
   "name": "MIRU Control 7 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 723,
   "name": "MIRU Control 7 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 728,
   "name": "MIRU Control 8 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 729,
   "name": "MIRU Control 8 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 730,
   "name": "MIRU Control 8 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 731,
   "name": "MIRU Control 8 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 736,
   "name": "MIRU Control 9 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 737,
   "name": "MIRU Control 9 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 738,
   "name": "MIRU Control 9 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 739,
   "name": "MIRU Control 9 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 744,
   "name": "MIRU Control 10 Low speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 745,
   "name": "MIRU Control 10 High speed duct pressure set point",
   "description": "",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 746,
   "name": "MIRU Control 10 Low speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 747,
   "name": "MIRU Control 10 High speed air flow set point",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 752,
   "name": "Delta temperature alarm limit",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 753,
   "name": "Efficiency alarm limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 754,
   "name": "Extra regulation sequence 1 heat neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 755,
   "name": "Extra regulation sequence 2 heat neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 756,
   "name": "ReCO2 heat neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 757,
   "name": "H/C heat neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 758,
   "name": "Re-heat neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 759,
   "name": "Extra regulation sequence 1 cool neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 760,
   "name": "Extra regulation sequence 2 cool neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 761,
   "name": "ReCO2 cool neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 762,
   "name": "H/C cool neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 763,
   "name": "Cool neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 764,
   "name": "Cooling boost neutral zone",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 776,
   "name": "Night temp compensation temp",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 778,
   "name": "Night temp compensation start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 779,
   "name": "Night temp compensation start time 1 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 780,
   "name": "Night temp compensation stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 781,
   "name": "Night temp compensation stop time 1 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 783,
   "name": "Night temp compensation start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 784,
   "name": "Night temp compensation start time 2 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 785,
   "name": "Night temp compensation stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 786,
   "name": "Night temp compensation stop time 2 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 800,
   "name": "External operation I/O-module A, analogue output",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 801,
   "name": "External operation I/O-module B, analogue output",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 802,
   "name": "External operation I/O-module C, analogue output",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 818,
   "name": "Extra regulation sequence 2 heat max output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 819,
   "name": "Extra regulation sequence 2 cool max output signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 820,
   "name": "Extra regulation sequence 2 heat P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 821,
   "name": "Extra regulation sequence 2 heat I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 822,
   "name": "Extra regulation sequence 2 cool P-band",
   "description": "",
   "units": "K",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 823,
   "name": "Extra regulation sequence 2 cool I-time",
   "description": "",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 826,
   "name": "Extra regulation 2 periodic operation interval",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 827,
   "name": "Extra regulation 2 periodic operation time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 830,
   "name": "Seasonal controlled supply air",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 831,
   "name": "Seasonal controlled extract air/room temp",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 832,
   "name": "Seasonal controlled supply air min temp",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 833,
   "name": "Seasonal controlled supply air max temp",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 852,
   "name": "H/C outdoor temperature limit heating",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 853,
   "name": "H/C outdoor temperature limit cooling",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 854,
   "name": "H/C air flow limit supply air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 855,
   "name": "H/C air flow limit extract air",
   "description": "",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 891,
   "name": "Humidifying start time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 892,
   "name": "Humidifying start time 1 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 893,
   "name": "Humidifying stop time 1 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 894,
   "name": "Humidifying stop time 1 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 896,
   "name": "Humidifying start time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 897,
   "name": "Humidifying start time 2 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 898,
   "name": "Humidifying stop time 2 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 899,
   "name": "Humidifying stop time 2 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 901,
   "name": "Humidifying start time 3 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 902,
   "name": "Humidifying start time 3 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 903,
   "name": "Humidifying stop time 3 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 904,
   "name": "Humidifying stop time 3 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 906,
   "name": "Humidifying start time 4 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 907,
   "name": "Humidifying start time 4 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 908,
   "name": "Humidifying stop time 4 (hour)",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 909,
   "name": "Humidifying stop time 4 (minute)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 910,
   "name": "Humidifying start time",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 911,
   "name": "Humidifying stop time",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 912,
   "name": "Humidifying time",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1268,
   "name": "Prolonged low speed hours",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1269,
   "name": "Prolonged low speed minutes",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1270,
   "name": "Prolonged high speed hours",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1271,
   "name": "Prolonged high speed minutes",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3000,
   "name": "External override code 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3001,
   "name": "External override code 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3002,
   "name": "External override, duration",
   "description": "",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3010,
   "name": "External override value, Supply air fan level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3011,
   "name": "External override value, Extract air fan level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3020,
   "name": "External override value, RX HX level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3030,
   "name": "External override value, PX HX damper 3A",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3031,
   "name": "External override value, PX HX damper 1A",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3032,
   "name": "External override value, PX HX bypass 2A",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3033,
   "name": "External override value, PX HX bypass 4A",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3040,
   "name": "External override value, CX HX valve",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3041,
   "name": "External override value, CX HX pump level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3050,
   "name": "External override value, Pre-heat level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3060,
   "name": "External override value, Reheat level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3070,
   "name": "External override value, Xzone heat level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3080,
   "name": "External override value, Extra reg. 1 level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3090,
   "name": "External override value, Extra reg. 2 level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3100,
   "name": "External override value, Cool level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3110,
   "name": "External override value, Xzone cool level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3130,
   "name": "External override value, HC comp. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3131,
   "name": "External override value, HC defrost recirc. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3132,
   "name": "External override value, HC defrost el. heat level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3150,
   "name": "External override value, SMART Link DX 1 comp. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3151,
   "name": "External override value, SMART Link DX 2 comp. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3152,
   "name": "External override value, SMART Link DX 3 comp. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3153,
   "name": "External override value, SMART Link DX 4 comp. level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3170,
   "name": "External override value, Humidifying level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3180,
   "name": "External override value, ReCO2 recirculation damper",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3181,
   "name": "External override value, ReCO2 outdoor damper",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3190,
   "name": "External override value, AYC heat valve level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3191,
   "name": "External override value, AYC cool valve level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3220,
   "name": "External override value, Miru 1 fan level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3221,
   "name": "External override value, Miru 2 fan level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3222,
   "name": "External override value, Miru 3 fan level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3230,
   "name": "External override value, Exhaust heat level",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Operation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Damper operation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Low speed operation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "High speed operation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Intermittent night heat active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Morning boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Heating boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Cooling boost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Summer night cool active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "A-alarm active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "B-alarm active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "HX operation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "HX cool recovery active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "HX defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "RHX speed monitor signal",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "CHX pump output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "CHX pump input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "Seasonal controlled temperature regulation indication",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "Season heat, extra regulation sequence allowed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Season heat, re-heat allowed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Extra regulation sequence 1, output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "Extra regulation sequence 1, power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Extra regulation sequence 1, anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "Extra regulation sequence 1 combi coil input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Extra regulation sequence 1 combi coil output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Re-heat output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "Re-heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "Re-heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Cool output 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Cool output 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "Extra regulation sequence 2 combi coil input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "Extra regulation sequence 2 combi coil output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "Extra regulation sequence 2, output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "Extra regulation sequence 2, power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "Extra regulation sequence 2, anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "Pre-heat output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "Pre-heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "Pre-heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "Xzone heat output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "Xzone heat power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "Xzone heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "Xzone cool output 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "Xzone cool output 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 65,
   "name": "Xzone combi coil module A input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "Xzone combi coil module A output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 67,
   "name": "Xzone combi coil module B input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "Xzone combi coil module B output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "Exhaust heat pump output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "Exhaust heat heating power reduction active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "Exhaust heat anti-frost regulation active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 99,
   "name": "AYC heat pump output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "AYC heat pump input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "AYC cool pump output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "AYC cool pump input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "COOL DX compressor 1 output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "COOL DX compressor 1 input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 115,
   "name": "COOL DX compressor 2 output",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 116,
   "name": "COOL DX compressor 2 input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 199,
   "name": "Wireless AP active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 200,
   "name": "External operation I/O-module 3, digital input 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "External operation I/O-module 3, digital input 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "External operation I/O-module 3, digital output 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 203,
   "name": "External operation I/O-module 3, digital output 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "External operation I/O-module 6, digital input 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 205,
   "name": "External operation I/O-module 6, digital input 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 206,
   "name": "External operation I/O-module 6, digital output 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 207,
   "name": "External operation I/O-module 6, digital output 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 208,
   "name": "External operation I/O-module A, digital input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 209,
   "name": "External operation I/O-module B, digital input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 210,
   "name": "External operation I/O-module C, digital input",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 319,
   "name": "SMART Link, WB operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 323,
   "name": "SMART Link, DX unit 1 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 324,
   "name": "SMART Link, DX unit 1 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 325,
   "name": "SMART Link, DX unit 1 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 326,
   "name": "SMART Link, DX unit 1 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 334,
   "name": "SMART Link, DX unit 2 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 335,
   "name": "SMART Link, DX unit 2 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 336,
   "name": "SMART Link, DX unit 2 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 337,
   "name": "SMART Link, DX unit 2 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 345,
   "name": "SMART Link, DX unit 3 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 346,
   "name": "SMART Link, DX unit 3 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 347,
   "name": "SMART Link, DX unit 3 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 348,
   "name": "SMART Link, DX unit 3 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 356,
   "name": "SMART Link, DX unit 4 operation",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 357,
   "name": "SMART Link, DX unit 4 cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 358,
   "name": "SMART Link, DX unit 4 defrost request",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 359,
   "name": "SMART Link, DX unit 4 defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 367,
   "name": "SMART Link, DX Defrost airflow increase status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 501,
   "name": "Alarm 1:1 External fire alarm no. 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 502,
   "name": "Alarm 1:2 External fire alarm no. 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 503,
   "name": "Alarm 1:3 Internal fire alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 516,
   "name": "Alarm 2:1 External alarm no. 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 517,
   "name": "Alarm 2:2 External alarm no. 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 531,
   "name": "Alarm 3:1 Pre-heat I/O-module no. 9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 532,
   "name": "Alarm 3:2 Pre-heat electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 533,
   "name": "Alarm 3:3 Pre-heat frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 534,
   "name": "Alarm 3:4 Pre-heat frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 535,
   "name": "Alarm 3:5 Pre-heat temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 536,
   "name": "Alarm 3:6 Pre-heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 537,
   "name": "Alarm 3:7 Pre-heat temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 538,
   "name": "Alarm 3:8 Pre-heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 546,
   "name": "Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 547,
   "name": "Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 548,
   "name": "Alarm 4:3 Extra reg. sequence 1 frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 549,
   "name": "Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 550,
   "name": "Alarm 4:5 Extra reg. sequence 1 valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 551,
   "name": "Alarm 4:6 Extra reg. sequence 1 alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 552,
   "name": "Alarm 4:7 Extra reg. sequence 1 temperature protection from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 553,
   "name": "Alarm 4:8 Extra reg. sequence 1 combi coil temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 554,
   "name": "Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 555,
   "name": "Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 556,
   "name": "Alarm 4:11 Extra reg. sequence 2 frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 557,
   "name": "Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 558,
   "name": "Alarm 4:13 Extra reg. sequence 2 valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 559,
   "name": "Alarm 4:14 Extra reg. sequence 2 alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 560,
   "name": "Alarm 4:15 Extra reg. sequence 2 combi coil temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 561,
   "name": "Alarm 5:1 Re-heat electrical heater over heat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 562,
   "name": "Alarm 5:2 Re-heat frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 563,
   "name": "Alarm 5:3 Re-heat frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 564,
   "name": "Alarm 5:4 Re-heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 565,
   "name": "Alarm 5:5 Re-heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 576,
   "name": "Alarm 6:1 Xzone I/O-module no. A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 577,
   "name": "Alarm 6:2 Xzone electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 578,
   "name": "Alarm 6:3 Xzone frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 579,
   "name": "Alarm 6:4 Xzone frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 580,
   "name": "Alarm 6:5 Xzone supply air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 581,
   "name": "Alarm 6:6 Xzone heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 582,
   "name": "Alarm 6:7 Xzone supply air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 583,
   "name": "Alarm 6:8 Xzone supply air temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 584,
   "name": "Alarm 6:9 Xzone heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 585,
   "name": "Alarm 6:10 Xzone combi coil module A temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 586,
   "name": "Alarm 6:11 Xzone temperature protection I/O-module no. 9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 591,
   "name": "Alarm 7:1 Xzone I/O-module no. B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 592,
   "name": "Alarm 7:2 Xzone extract air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 593,
   "name": "Alarm 7:3 Xzone cool valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 594,
   "name": "Alarm 7:4 Xzone extract air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 595,
   "name": "Alarm 7:5 Xzone cool alarm input 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 596,
   "name": "Alarm 7:6 Xzone cool alarm input 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 597,
   "name": "Alarm 7:7 Xzone combi coil module B temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 610,
   "name": "Alarm 8:5 Cool valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 611,
   "name": "Alarm 8:6 Cool alarm input 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 612,
   "name": "Alarm 8:7 Cool alarm input 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 621,
   "name": "Alarm 9:1 Exhaust heat I/O-module no. 4 com error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 622,
   "name": "Alarm 9:2 Exhaust heat electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 623,
   "name": "Alarm 9:3 Exhaust heat frost protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 624,
   "name": "Alarm 9:4 Exhaust heat frost protection temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 625,
   "name": "Alarm 9:5 Exhaust heat temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 626,
   "name": "Alarm 9:6 Exhaust heat valve monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 627,
   "name": "Alarm 9:7 Exhaust heat temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 628,
   "name": "Alarm 9:8 Exhaust heat alarm input tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 636,
   "name": "Alarm 10:1 Supply air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 637,
   "name": "Alarm 10:2 Supply air temperature sensor for density compensation defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 638,
   "name": "Alarm 10:3 Extract air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 639,
   "name": "Alarm 10:4 Extract air temperature sensor for density compensation defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 640,
   "name": "Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 641,
   "name": "Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 642,
   "name": "Alarm 10:7 Extract air duct temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 645,
   "name": "Alarm 10:10 Outdoor air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 651,
   "name": "Alarm 11:1 Room temperature sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 652,
   "name": "Alarm 11:2 Room temperature sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 653,
   "name": "Alarm 11:3 Room temperature sensor no. 3 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 654,
   "name": "Alarm 11:4 Room temperature sensor no. 4 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 655,
   "name": "Alarm 11:5 Xzone room temperature sensor no. 5 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 656,
   "name": "Alarm 11:6 Xzone room temperature sensor no. 6 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 657,
   "name": "Alarm 11:7 Xzone room temperature sensor no. 7 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 658,
   "name": "Alarm 11:8 Xzone room temperature sensor no. 8 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 659,
   "name": "Alarm 11:9 Outdoor temperature sensor no. A defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 660,
   "name": "Alarm 11:10 Outdoor temperature sensor no. B defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 661,
   "name": "Alarm 11:11 Outdoor temperature sensor no. C defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 662,
   "name": "Alarm 11:12 Outdoor temperature sensor no. D defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 663,
   "name": "Alarm 11:13 Room temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 664,
   "name": "Alarm 11:14 Xzone room temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 665,
   "name": "Alarm 11:15 Outdoor temperature from com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 666,
   "name": "Alarm 12:1 Supply air temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 667,
   "name": "Alarm 12:2 Supply air temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 671,
   "name": "Alarm 12:6 Extract air temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 676,
   "name": "Alarm 12:11 Temperature guard below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 678,
   "name": "Alarm 12:13 Heat exchange efficiency below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 681,
   "name": "Alarm 13:1 Humidification I/O-module no. 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 682,
   "name": "Alarm 13:2 Supply air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 683,
   "name": "Alarm 13:3 Extract air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 684,
   "name": "Alarm 13:4 Exhaust air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 685,
   "name": "Alarm 13:5 Outdoor air humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 686,
   "name": "Alarm 13:6 Room humidity sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 689,
   "name": "Alarm 13:9 Humidifier alarm output tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 691,
   "name": "Alarm 13:11 VOC sensor com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 692,
   "name": "Alarm 13:12 VOC sensor internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 693,
   "name": "Alarm 13:13 VOC sensor internal error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 694,
   "name": "Alarm 13:14 VOC sensor level below/above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 696,
   "name": "Alarm 14:1 Re-heat liquid flow measurement I/O-module no. 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 697,
   "name": "Alarm 14:2 Re-heat liquid flow measurement temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 698,
   "name": "Alarm 14:3 Re-heat liquid flow measurement temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 699,
   "name": "Alarm 14:4 Re-heat liquid flow measurement valve leakage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 700,
   "name": "Alarm 14:5 Re-heat liquid flow measurement flow sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 703,
   "name": "Alarm 14:8 Cool liquid flow measurement I/O-module no. 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 704,
   "name": "Alarm 14:9 Cool liquid flow measurement temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 705,
   "name": "Alarm 14:10 Cool liquid flow measurement temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 706,
   "name": "Alarm 14:11 Cool liquid flow measurement valve leakage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 707,
   "name": "Alarm 14:12 Cool liquid flow measurement flow sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 711,
   "name": "Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 712,
   "name": "Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 713,
   "name": "Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 714,
   "name": "Alarm 15:4 Plate heat exchanger damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 716,
   "name": "Alarm 15:6 Plate heat exchanger bypass damper 4A monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 717,
   "name": "Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 718,
   "name": "Alarm 15:8 Plate heat exchanger bypass damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 719,
   "name": "Alarm 15:9 Plate heat exchanger damper no. 1 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 720,
   "name": "Alarm 15:10 Plate heat exchanger damper no. 2 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 721,
   "name": "Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 722,
   "name": "Alarm 15:12 Plate heat exchanger bypass damper monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 723,
   "name": "Alarm 15:13 Plate counter flow heat exchanger defrost pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 724,
   "name": "Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 725,
   "name": "Alarm 15:15 Plate heat exchanger defrost pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 726,
   "name": "Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 727,
   "name": "Alarm 16:2 Coil heat exchanger temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 728,
   "name": "Alarm 16:3 Coil heat exchanger valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 729,
   "name": "Alarm 16:4 Coil heat exchanger pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 730,
   "name": "Alarm 16:5 Coil heat exchanger I/O-module no. C communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 731,
   "name": "Alarm 16:6 Coil heat exchanger pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 732,
   "name": "Alarm 16:7 Coil heat exchanger low pressure brine circuit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 733,
   "name": "Alarm 16:8 Coil heat exchanger pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 741,
   "name": "Alarm 17:1 Rotary heat exchanger motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 742,
   "name": "Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 743,
   "name": "Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 744,
   "name": "Alarm 17:4 Rotary heat exchanger speed monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 745,
   "name": "Alarm 17:5 Rotary heat exchanger motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 746,
   "name": "Alarm 17:6 Rotary heat exchanger motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 747,
   "name": "Alarm 17:7 Rotary heat exchanger motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 748,
   "name": "Alarm 17:8 Rotary heat exchanger motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 749,
   "name": "Alarm 17:9 Rotary heat exchanger motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 750,
   "name": "Alarm 17:10 Rotary heat exchanger motor controller internal error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 751,
   "name": "Alarm 17:11 Rotary heat exchanger motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 752,
   "name": "Alarm 17:12 Rotary heat exchanger motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 753,
   "name": "Alarm 17:13 Rotary heat exchanger motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 754,
   "name": "Alarm 17:14 Rotary heat exchanger motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 755,
   "name": "Alarm 17:15 Rotary heat exchanger I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 756,
   "name": "Alarm 18:1 AYC I/O-module no. 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 757,
   "name": "Alarm 18:2 AYC heat temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 758,
   "name": "Alarm 18:3 AYC heat valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 759,
   "name": "Alarm 18:4 AYC heat pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 760,
   "name": "Alarm 18:5 AYC heat temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 761,
   "name": "Alarm 18:6 AYC heat temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 764,
   "name": "Alarm 18:9 AYC cool temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 765,
   "name": "Alarm 18:10 AYC cool valve monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 766,
   "name": "Alarm 18:11 AYC cool pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 767,
   "name": "Alarm 18:12 AYC cool temperature below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 768,
   "name": "Alarm 18:13 AYC cool temperature above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 771,
   "name": "Alarm 19:1 Rotary heat exchanger AQC pressure sensor no. E com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 772,
   "name": "Alarm 19:2 Rotary heat exchanger AQC pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 773,
   "name": "Alarm 19:3 Rotary heat exchanger AQC damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 801,
   "name": "Alarm 21:1 COOL DX I/O-module no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 802,
   "name": "Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 803,
   "name": "Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 804,
   "name": "Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 805,
   "name": "Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 806,
   "name": "Alarm 21:6 COOL DX compressor no. 1 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 807,
   "name": "Alarm 21:7 COOL DX compressor no. 1 restart error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 808,
   "name": "Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 809,
   "name": "Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 810,
   "name": "Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 811,
   "name": "Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 812,
   "name": "Alarm 21:12 COOL DX compressor no. 2 monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 813,
   "name": "Alarm 21:13 COOL DX compressor no. 2 restart error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 814,
   "name": "Alarm 21:14 COOL DX outdoor air temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 815,
   "name": "Alarm 21:15 COOL DX phase sequence error or supply voltage missing",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 816,
   "name": "Alarm 22:1 Xzone heat liquid flow measurement I/O-module no. D com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 817,
   "name": "Alarm 22:2 Xzone heat liquid flow measurement temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 818,
   "name": "Alarm 22:3 Xzone heat liquid flow measurement temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 819,
   "name": "Alarm 22:4 Xzone heat liquid flow measurement valve leakage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 820,
   "name": "Alarm 22:5 Xzone heat liquid flow measurement flow sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 823,
   "name": "Alarm 22:8 Xzone cool liquid flow measurement I/O-module no. E com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 824,
   "name": "Alarm 22:9 Xzone cool liquid flow measurement temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 825,
   "name": "Alarm 22:10 Xzone cool liquid flow measurement temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 826,
   "name": "Alarm 22:11 Xzone cool liquid flow measurement valve leakage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 827,
   "name": "Alarm 22:12 Xzone cool liquid flow measurement flow sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 831,
   "name": "Alarm 23:1 SMART Link com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 832,
   "name": "Alarm 23:2 SMART Link alarm level 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 833,
   "name": "Alarm 23:3 SMART Link alarm level 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 834,
   "name": "Alarm 23:4 SMART Link alarm level 3 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 840,
   "name": "Alarm 23:10 AQUA Link I/O-module no. 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 841,
   "name": "Alarm 23:11 AQUA Link pump monitor tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 846,
   "name": "Alarm 24:1 SMART Link no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 847,
   "name": "Alarm 24:2 SMART Link no. 1 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 849,
   "name": "Alarm 24:4 SMART Link no. 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 850,
   "name": "Alarm 24:5 SMART Link no. 2 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 852,
   "name": "Alarm 24:7 SMART Link no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 853,
   "name": "Alarm 24:8 SMART Link no. 3 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 855,
   "name": "Alarm 24:10 SMART Link no. 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 856,
   "name": "Alarm 24:11 SMART Link no. 4 alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 858,
   "name": "Alarm 24:13 SMART Link supply air flow below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 861,
   "name": "Alarm 25:1 SMART Link+ cooling circuit A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 862,
   "name": "Alarm 25:2 SMART Link+ cooling circuit B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 863,
   "name": "Alarm 25:3 SMART Link+ heating circuit A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 864,
   "name": "Alarm 25:4 SMART Link+ heating circuit B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 876,
   "name": "Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 877,
   "name": "Alarm 26:2 Pre-filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 882,
   "name": "Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 883,
   "name": "Alarm 26:8 Pre-filter extract air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 891,
   "name": "Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 892,
   "name": "Alarm 27:2 AHU filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 897,
   "name": "Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 898,
   "name": "Alarm 27:8 AHU filter extract air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 906,
   "name": "Alarm 28:1 End filter supply air pressure sensor no. A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 907,
   "name": "Alarm 28:2 End filter supply air dirty",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 921,
   "name": "Alarm 29:1 Energy monitoring pulse counter com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 936,
   "name": "Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 937,
   "name": "Alarm 30:2 Air flow measurement supply air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 938,
   "name": "Alarm 30:3 Air flow measurement supply air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 941,
   "name": "Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 942,
   "name": "Alarm 30:7 Air flow measurement extract air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 943,
   "name": "Alarm 30:8 Air flow measurement extract air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 946,
   "name": "Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 951,
   "name": "Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 952,
   "name": "Alarm 31:2 Pressure regulation supply air pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 953,
   "name": "Alarm 31:3 Pressure regulation supply air pressure above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 956,
   "name": "Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 957,
   "name": "Alarm 31:7 Pressure regulation extract air press. below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 958,
   "name": "Alarm 31:8 Pressure regulation extract air press. above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 966,
   "name": "Alarm 32:1 ReCO2 I/O-module no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 967,
   "name": "Alarm 32:2 ReCO2 pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 968,
   "name": "Alarm 32:3 ReCO2 recirculation damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 969,
   "name": "Alarm 32:4 ReCO2 outdoor air damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 981,
   "name": "Alarm 33:1 Service period above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 995,
   "name": "Alarm 33:15 Lock function tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 996,
   "name": "Alarm 34:1 External control I/O-module no. 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 997,
   "name": "Alarm 34:2 External control I/O-module no. 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1011,
   "name": "Alarm 35:1 Booster diffusers I/O-module no. 8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1026,
   "name": "Alarm 36:1 External BMS control I/O-module no. A communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1027,
   "name": "Alarm 36:2 External BMS control I/O-module no. A temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1028,
   "name": "Alarm 36:3 External BMS control I/O-module no. A temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1031,
   "name": "Alarm 36:6 External BMS control I/O-module no. B communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1032,
   "name": "Alarm 36:7 External BMS control I/O-module no. B temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1033,
   "name": "Alarm 36:8 External BMS control I/O-module no. B temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1036,
   "name": "Alarm 36:11 External BMS control I/O-module no. C communication error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1037,
   "name": "Alarm 36:12 External BMS control I/O-module no. C temp. sensor no. 1 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1038,
   "name": "Alarm 36:13 External BMS control I/O-module no. C temp. sensor no. 2 defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1041,
   "name": "Alarm 37:1 Multilogic com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1056,
   "name": "Alarm 38:1 MIRU 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1057,
   "name": "Alarm 38:2 MIRU 1 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1058,
   "name": "Alarm 38:3 MIRU 1 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1059,
   "name": "Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1060,
   "name": "Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1061,
   "name": "Alarm 38:6 MIRU 1 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1062,
   "name": "Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1063,
   "name": "Alarm 38:8 MIRU 1 air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1064,
   "name": "Alarm 38:9 MIRU 1 air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1065,
   "name": "Alarm 38:10 MIRU 1 pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1066,
   "name": "Alarm 38:11 MIRU 1 pressure above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1071,
   "name": "Alarm 39:1 MIRU 2 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1072,
   "name": "Alarm 39:2 MIRU 2 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1073,
   "name": "Alarm 39:3 MIRU 2 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1074,
   "name": "Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1075,
   "name": "Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1076,
   "name": "Alarm 39:6 MIRU 2 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1077,
   "name": "Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1078,
   "name": "Alarm 39:8 MIRU 2 air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1079,
   "name": "Alarm 39:9 MIRU 2 air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1080,
   "name": "Alarm 39:10 MIRU 2 pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1081,
   "name": "Alarm 39:11 MIRU 2 pressure above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1086,
   "name": "Alarm 40:1 MIRU 3 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1087,
   "name": "Alarm 40:2 MIRU 3 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1088,
   "name": "Alarm 40:3 MIRU 3 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1089,
   "name": "Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1090,
   "name": "Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1091,
   "name": "Alarm 40:6 MIRU 3 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1092,
   "name": "Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1093,
   "name": "Alarm 40:8 MIRU 3 air flow below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1094,
   "name": "Alarm 40:9 MIRU 3 air flow above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1095,
   "name": "Alarm 40:10 MIRU 3 pressure below set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1096,
   "name": "Alarm 40:11 MIRU 3 pressure above set point alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1101,
   "name": "Alarm 41:1 MIRU 4 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1102,
   "name": "Alarm 41:2 MIRU 4 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1103,
   "name": "Alarm 41:3 MIRU 4 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1104,
   "name": "Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1105,
   "name": "Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1106,
   "name": "Alarm 41:6 MIRU 4 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1107,
   "name": "Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1116,
   "name": "Alarm 42:1 MIRU 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1117,
   "name": "Alarm 42:2 MIRU 5 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1118,
   "name": "Alarm 42:3 MIRU 5 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1119,
   "name": "Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1120,
   "name": "Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1121,
   "name": "Alarm 42:6 MIRU 5 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1122,
   "name": "Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1131,
   "name": "Alarm 43:1 MIRU 6 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1132,
   "name": "Alarm 43:2 MIRU 6 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1133,
   "name": "Alarm 43:3 MIRU 6 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1134,
   "name": "Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1135,
   "name": "Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1136,
   "name": "Alarm 43:6 MIRU 6 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1137,
   "name": "Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1146,
   "name": "Alarm 44:1 MIRU 7 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1147,
   "name": "Alarm 44:2 MIRU 7 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1148,
   "name": "Alarm 44:3 MIRU 7 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1149,
   "name": "Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1150,
   "name": "Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1151,
   "name": "Alarm 44:6 MIRU 7 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1152,
   "name": "Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1161,
   "name": "Alarm 45:1 MIRU 8 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1162,
   "name": "Alarm 45:2 MIRU 8 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1163,
   "name": "Alarm 45:3 MIRU 8 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1164,
   "name": "Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1165,
   "name": "Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1166,
   "name": "Alarm 45:6 MIRU 8 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1167,
   "name": "Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1176,
   "name": "Alarm 46:1 MIRU 9 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1177,
   "name": "Alarm 46:2 MIRU 9 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1178,
   "name": "Alarm 46:3 MIRU 9 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1179,
   "name": "Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1180,
   "name": "Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1181,
   "name": "Alarm 46:6 MIRU 9 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1182,
   "name": "Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1191,
   "name": "Alarm 47:1 MIRU 10 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1192,
   "name": "Alarm 47:2 MIRU 10 motor controller alarm tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1193,
   "name": "Alarm 47:3 MIRU 10 motor controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1194,
   "name": "Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1195,
   "name": "Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1196,
   "name": "Alarm 47:6 MIRU 10 temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1197,
   "name": "Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1221,
   "name": "Alarm 49:1 Supply air fan no. 1A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1222,
   "name": "Alarm 49:2 Supply air fan no. 1A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1223,
   "name": "Alarm 49:3 Supply air fan no. 1A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1224,
   "name": "Alarm 49:4 Supply air fan no. 1A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1225,
   "name": "Alarm 49:5 Supply air fan no. 1A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1226,
   "name": "Alarm 49:6 Supply air fan no. 1A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1227,
   "name": "Alarm 49:7 Supply air fan no. 1A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1228,
   "name": "Alarm 49:8 Supply air fan no. 1A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1229,
   "name": "Alarm 49:9 Supply air fan no. 1A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1230,
   "name": "Alarm 49:10 Supply air fan no. 1A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1231,
   "name": "Alarm 49:11 Supply air fan no. 1A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1236,
   "name": "Alarm 50:1 Supply air fan no. 2A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1237,
   "name": "Alarm 50:2 Supply air fan no. 2A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1238,
   "name": "Alarm 50:3 Supply air fan no. 2A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1239,
   "name": "Alarm 50:4 Supply air fan no. 2A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1240,
   "name": "Alarm 50:5 Supply air fan no. 2A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1241,
   "name": "Alarm 50:6 Supply air fan no. 2A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1242,
   "name": "Alarm 50:7 Supply air fan no. 2A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1243,
   "name": "Alarm 50:8 Supply air fan no. 2A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1244,
   "name": "Alarm 50:9 Supply air fan no. 2A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1245,
   "name": "Alarm 50:10 Supply air fan no. 2A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1246,
   "name": "Alarm 50:11 Supply air fan no. 2A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1251,
   "name": "Alarm 51:1 Supply air fan no. 3A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1252,
   "name": "Alarm 51:2 Supply air fan no. 3A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1253,
   "name": "Alarm 51:3 Supply air fan no. 3A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1254,
   "name": "Alarm 51:4 Supply air fan no. 3A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1255,
   "name": "Alarm 51:5 Supply air fan no. 3A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1256,
   "name": "Alarm 51:6 Supply air fan no. 3A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1257,
   "name": "Alarm 51:7 Supply air fan no. 3A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1258,
   "name": "Alarm 51:8 Supply air fan no. 3A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1259,
   "name": "Alarm 51:9 Supply air fan no. 3A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1260,
   "name": "Alarm 51:10 Supply air fan no. 3A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1261,
   "name": "Alarm 51:11 Supply air fan no. 3A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1266,
   "name": "Alarm 52:1 Supply air fan no. 1B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1267,
   "name": "Alarm 52:2 Supply air fan no. 1B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1268,
   "name": "Alarm 52:3 Supply air fan no. 1B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1269,
   "name": "Alarm 52:4 Supply air fan no. 1B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1270,
   "name": "Alarm 52:5 Supply air fan no. 1B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1271,
   "name": "Alarm 52:6 Supply air fan no. 1B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1272,
   "name": "Alarm 52:7 Supply air fan no. 1B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1273,
   "name": "Alarm 52:8 Supply air fan no. 1B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1274,
   "name": "Alarm 52:9 Supply air fan no. 1B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1275,
   "name": "Alarm 52:10 Supply air fan no. 1B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1281,
   "name": "Alarm 53:1 Supply air fan no. 2B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1282,
   "name": "Alarm 53:2 Supply air fan no. 2B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1283,
   "name": "Alarm 53:3 Supply air fan no. 2B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1284,
   "name": "Alarm 53:4 Supply air fan no. 2B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1285,
   "name": "Alarm 53:5 Supply air fan no. 2B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1286,
   "name": "Alarm 53:6 Supply air fan no. 2B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1287,
   "name": "Alarm 53:7 Supply air fan no. 2B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1288,
   "name": "Alarm 53:8 Supply air fan no. 2B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1289,
   "name": "Alarm 53:9 Supply air fan no. 2B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1290,
   "name": "Alarm 53:10 Supply air fan no. 2B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1296,
   "name": "Alarm 54:1 Supply air fan no. 3B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1297,
   "name": "Alarm 54:2 Supply air fan no. 3B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1298,
   "name": "Alarm 54:3 Supply air fan no. 3B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1299,
   "name": "Alarm 54:4 Supply air fan no. 3B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1300,
   "name": "Alarm 54:5 Supply air fan no. 3B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1301,
   "name": "Alarm 54:6 Supply air fan no. 3B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1302,
   "name": "Alarm 54:7 Supply air fan no. 3B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1303,
   "name": "Alarm 54:8 Supply air fan no. 3B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1304,
   "name": "Alarm 54:9 Supply air fan no. 3B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1305,
   "name": "Alarm 54:10 Supply air fan no. 3B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1311,
   "name": "Alarm 55:1 Extract air fan no. 1A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1312,
   "name": "Alarm 55:2 Extract air fan no. 1A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1313,
   "name": "Alarm 55:3 Extract air fan no. 1A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1314,
   "name": "Alarm 55:4 Extract air fan no. 1A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1315,
   "name": "Alarm 55:5 Extract air fan no. 1A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1316,
   "name": "Alarm 55:6 Extract air fan no. 1A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1317,
   "name": "Alarm 55:7 Extract air fan no. 1A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1318,
   "name": "Alarm 55:8 Extract air fan no. 1A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1319,
   "name": "Alarm 55:9 Extract air fan no. 1A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1320,
   "name": "Alarm 55:10 Extract air fan no. 1A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1321,
   "name": "Alarm 55:11 Extract air fan no. 1A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1326,
   "name": "Alarm 56:1 Extract air fan no. 2A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1327,
   "name": "Alarm 56:2 Extract air fan no. 2A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1328,
   "name": "Alarm 56:3 Extract air fan no. 2A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1329,
   "name": "Alarm 56:4 Extract air fan no. 2A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1330,
   "name": "Alarm 56:5 Extract air fan no. 2A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1331,
   "name": "Alarm 56:6 Extract air fan no. 2A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1332,
   "name": "Alarm 56:7 Extract air fan no. 2A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1333,
   "name": "Alarm 56:8 Extract air fan no. 2A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1334,
   "name": "Alarm 56:9 Extract air fan no. 2A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1335,
   "name": "Alarm 56:10 Extract air fan no. 2A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1336,
   "name": "Alarm 56:11 Extract air fan no. 2A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1341,
   "name": "Alarm 57:1 Extract air fan no. 3A com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1342,
   "name": "Alarm 57:2 Extract air fan no. 3A motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1343,
   "name": "Alarm 57:3 Extract air fan no. 3A motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1344,
   "name": "Alarm 57:4 Extract air fan no. 3A motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1345,
   "name": "Alarm 57:5 Extract air fan no. 3A motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1346,
   "name": "Alarm 57:6 Extract air fan no. 3A motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1347,
   "name": "Alarm 57:7 Extract air fan no. 3A motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1348,
   "name": "Alarm 57:8 Extract air fan no. 3A motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1349,
   "name": "Alarm 57:9 Extract air fan no. 3A motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1350,
   "name": "Alarm 57:10 Extract air fan no. 3A motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1351,
   "name": "Alarm 57:11 Extract air fan no. 3A motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1356,
   "name": "Alarm 58:1 Extract air fan no. 1B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1357,
   "name": "Alarm 58:2 Extract air fan no. 1B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1358,
   "name": "Alarm 58:3 Extract air fan no. 1B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1359,
   "name": "Alarm 58:4 Extract air fan no. 1B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1360,
   "name": "Alarm 58:5 Extract air fan no. 1B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1361,
   "name": "Alarm 58:6 Extract air fan no. 1B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1362,
   "name": "Alarm 58:7 Extract air fan no. 1B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1363,
   "name": "Alarm 58:8 Extract air fan no. 1B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1364,
   "name": "Alarm 58:9 Extract air fan no. 1B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1365,
   "name": "Alarm 58:10 Extract air fan no. 1B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1371,
   "name": "Alarm 59:1 Extract air fan no. 2B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1372,
   "name": "Alarm 59:2 Extract air fan no. 2B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1373,
   "name": "Alarm 59:3 Extract air fan no. 2B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1374,
   "name": "Alarm 59:4 Extract air fan no. 2B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1375,
   "name": "Alarm 59:5 Extract air fan no. 2B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1376,
   "name": "Alarm 59:6 Extract air fan no. 2B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1377,
   "name": "Alarm 59:7 Extract air fan no. 2B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1378,
   "name": "Alarm 59:8 Extract air fan no. 2B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1379,
   "name": "Alarm 59:9 Extract air fan no. 2B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1380,
   "name": "Alarm 59:10 Extract air fan no. 2B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1386,
   "name": "Alarm 60:1 Extract air fan no. 3B com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1387,
   "name": "Alarm 60:2 Extract air fan no. 3B motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1388,
   "name": "Alarm 60:3 Extract air fan no. 3B motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1389,
   "name": "Alarm 60:4 Extract air fan no. 3B motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1390,
   "name": "Alarm 60:5 Extract air fan no. 3B motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1391,
   "name": "Alarm 60:6 Extract air fan no. 3B motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1392,
   "name": "Alarm 60:7 Extract air fan no. 3B motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1393,
   "name": "Alarm 60:8 Extract air fan no. 3B motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1394,
   "name": "Alarm 60:9 Extract air fan no. 3B motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1395,
   "name": "Alarm 60:10 Extract air fan no. 3B motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1401,
   "name": "Alarm 61:1 Supply air fan no. 1A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1406,
   "name": "Alarm 61:6 Supply air fan no. 2A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1411,
   "name": "Alarm 61:11 Supply air fan no. 3A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1416,
   "name": "Alarm 62:1 Extract air fan no. 1A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1421,
   "name": "Alarm 62:6 Extract air fan no. 2A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1426,
   "name": "Alarm 62:11 Extract air fan no. 3A I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1431,
   "name": "Alarm 63:1 MIRU 1 I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1436,
   "name": "Alarm 63:6 MIRU 2 I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1441,
   "name": "Alarm 63:11 MIRU 3 I/O-module com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1446,
   "name": "Alarm 64:1 Supply air fan no. 1A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1448,
   "name": "Alarm 64:3 Supply air fan no. 1A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1450,
   "name": "Alarm 64:5 Supply air fan no. 1A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1451,
   "name": "Alarm 64:6 Supply air fan no. 2A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1453,
   "name": "Alarm 64:8 Supply air fan no. 2A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1455,
   "name": "Alarm 64:10 Supply air fan no. 2A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1456,
   "name": "Alarm 64:11 Supply air fan no. 3A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1458,
   "name": "Alarm 64:13 Supply air fan no. 3A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1460,
   "name": "Alarm 64:15 Supply air fan no. 3A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1461,
   "name": "Alarm 65:1 Extract air fan no. 1A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1463,
   "name": "Alarm 65:3 Extract air fan no. 1A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1465,
   "name": "Alarm 65:5 Extract air fan no. 1A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1466,
   "name": "Alarm 65:6 Extract air fan no. 2A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1468,
   "name": "Alarm 65:8 Extract air fan no. 2A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1470,
   "name": "Alarm 65:10 Extract air fan no. 2A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1471,
   "name": "Alarm 65:11 Extract air fan no. 3A common A-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1473,
   "name": "Alarm 65:13 Extract air fan no. 3A common B-alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1475,
   "name": "Alarm 65:15 Extract air fan no. 3A common warning",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1536,
   "name": "Alarm 70:1 H/C controls com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1537,
   "name": "Alarm 70:2 H/C controls internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1538,
   "name": "Alarm 70:3 H/C controls clock circuit defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1540,
   "name": "Alarm 70:5 H/C defrost pressure sensor no. D com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1541,
   "name": "Alarm 70:6 H/C defrost I/O-module no. 5 com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1542,
   "name": "Alarm 70:7 H/C defrost recirculation damper monitoring tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1543,
   "name": "Alarm 70:8 H/C defrost electrical heater overheat protection tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1544,
   "name": "Alarm 70:9 H/C defrost time above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1546,
   "name": "Alarm 70:11 H/C defrost interval above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1547,
   "name": "Alarm 70:12 H/C wrong phase sequence",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1551,
   "name": "Alarm 71:1 H/C compressor motor control com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1552,
   "name": "Alarm 71:2 H/C compressor motor control start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1553,
   "name": "Alarm 71:3 H/C compressor motor controller over or under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1554,
   "name": "Alarm 71:4 H/C compressor out of operation range",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1559,
   "name": "Alarm 71:9 H/C expansion valve controller com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1566,
   "name": "Alarm 72:1 H/C high pressure switch tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1567,
   "name": "Alarm 72:2 H/C high pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1568,
   "name": "Alarm 72:3 H/C thermal switch compressor no. 1 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1569,
   "name": "Alarm 72:4 H/C discharge temperature above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1570,
   "name": "Alarm 72:5 H/C discharge temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1571,
   "name": "Alarm 72:6 H/C high pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1572,
   "name": "Alarm 72:7 H/C low pressure sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1573,
   "name": "Alarm 72:8 H/C suction temperature sensor defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1574,
   "name": "Alarm 72:9 H/C pressure difference below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1575,
   "name": "Alarm 72:10 H/C maintenance and compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1576,
   "name": "Alarm 72:11 H/C superheat temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1577,
   "name": "Alarm 72:12 H/C unloading of low pressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1578,
   "name": "Alarm 72:13 H/C unloading of high pressure",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1579,
   "name": "Alarm 72:14 H/C low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1580,
   "name": "Alarm 72:15 H/C thermal switch compressor no. 2 tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1642,
   "name": "Alarm 77:2 MIRU 1 motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1643,
   "name": "Alarm 77:3 MIRU 1 motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1644,
   "name": "Alarm 77:4 MIRU 1 motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1645,
   "name": "Alarm 77:5 MIRU 1 motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1646,
   "name": "Alarm 77:6 MIRU 1 motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1647,
   "name": "Alarm 77:7 MIRU 1 motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1648,
   "name": "Alarm 77:8 MIRU 1 motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1649,
   "name": "Alarm 77:9 MIRU 1 motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1650,
   "name": "Alarm 77:10 MIRU 1 motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1651,
   "name": "Alarm 77:11 MIRU 1 motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1657,
   "name": "Alarm 78:2 MIRU 2 motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1658,
   "name": "Alarm 78:3 MIRU 2 motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1659,
   "name": "Alarm 78:4 MIRU 2 motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1660,
   "name": "Alarm 78:5 MIRU 2 motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1661,
   "name": "Alarm 78:6 MIRU 2 motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1662,
   "name": "Alarm 78:7 MIRU 2 motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1663,
   "name": "Alarm 78:8 MIRU 2 motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1664,
   "name": "Alarm 78:9 MIRU 2 motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1665,
   "name": "Alarm 78:10 MIRU 2 motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1666,
   "name": "Alarm 78:11 MIRU 2 motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1672,
   "name": "Alarm 79:2 MIRU 3 motor controller over current",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1673,
   "name": "Alarm 79:3 MIRU 3 motor controller under voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1674,
   "name": "Alarm 79:4 MIRU 3 motor controller over voltage",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1675,
   "name": "Alarm 79:5 MIRU 3 motor controller over temperature",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1676,
   "name": "Alarm 79:6 MIRU 3 motor controller start error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1677,
   "name": "Alarm 79:7 MIRU 3 motor controller ripple error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1678,
   "name": "Alarm 79:8 MIRU 3 motor controller phase error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1679,
   "name": "Alarm 79:9 MIRU 3 motor controller internal memory error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1680,
   "name": "Alarm 79:10 MIRU 3 motor controller current reduction",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1681,
   "name": "Alarm 79:11 MIRU 3 motor controller internal com. error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1702,
   "name": "Alarm 81:2 SMART Link no. 1 supply air flow below defrost alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1703,
   "name": "Alarm 81:3 SMART Link no. 1 High pressure switch tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1704,
   "name": "Alarm 81:4 SMART Link no. 1 High pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1705,
   "name": "Alarm 81:5 SMART Link no. 1 Low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1706,
   "name": "Alarm 81:6 SMART Link no. 1 Evaporation temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1707,
   "name": "Alarm 81:7 SMART Link no. 1 Inverter group alarm (Power+)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1708,
   "name": "Alarm 81:8 SMART Link no. 1 Envelope alarm.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1709,
   "name": "Alarm 81:9 SMART Link no. 1 Starting up of faulty compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1710,
   "name": "Alarm 81:10 SMART Link no. 1 Discharge temperature above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1711,
   "name": "Alarm 81:11 SMART Link no. 1 Pressure difference below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1717,
   "name": "Alarm 82:2 SMART Link no. 2 supply air flow below defrost alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1718,
   "name": "Alarm 82:3 SMART Link no. 2 High pressure switch tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1719,
   "name": "Alarm 82:4 SMART Link no. 2 High pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1720,
   "name": "Alarm 82:5 SMART Link no. 2 Low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1721,
   "name": "Alarm 82:6 SMART Link no. 2 Evaporation temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1722,
   "name": "Alarm 82:7 SMART Link no. 2 Inverter group alarm (Power+)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1723,
   "name": "Alarm 82:8 SMART Link no. 2 Envelope alarm.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1724,
   "name": "Alarm 82:9 SMART Link no. 2 Starting up of faulty compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1725,
   "name": "Alarm 82:10 SMART Link no. 2 Discharge temperature above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1726,
   "name": "Alarm 82:11 SMART Link no. 2 Pressure difference below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1732,
   "name": "Alarm 83:2 SMART Link no. 3 supply air flow below defrost alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1733,
   "name": "Alarm 83:3 SMART Link no. 3 High pressure switch tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1734,
   "name": "Alarm 83:4 SMART Link no. 3 High pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1735,
   "name": "Alarm 83:5 SMART Link no. 3 Low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1736,
   "name": "Alarm 83:6 SMART Link no. 3 Evaporation temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1737,
   "name": "Alarm 83:7 SMART Link no. 3 Inverter group alarm (Power+)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1738,
   "name": "Alarm 83:8 SMART Link no. 3 Envelope alarm.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1739,
   "name": "Alarm 83:9 SMART Link no. 3 Starting up of faulty compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1740,
   "name": "Alarm 83:10 SMART Link no. 3 Discharge temperature above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1741,
   "name": "Alarm 83:11 SMART Link no. 3 Pressure difference below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1747,
   "name": "Alarm 84:2 SMART Link no. 4 supply air flow below defrost alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1748,
   "name": "Alarm 84:3 SMART Link no. 4 High pressure switch tripped",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1749,
   "name": "Alarm 84:4 SMART Link no. 4 High pressure above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1750,
   "name": "Alarm 84:5 SMART Link no. 4 Low pressure below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1751,
   "name": "Alarm 84:6 SMART Link no. 4 Evaporation temperature below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1752,
   "name": "Alarm 84:7 SMART Link no. 4 Inverter group alarm (Power+)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1753,
   "name": "Alarm 84:8 SMART Link no. 4 Envelope alarm.",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1754,
   "name": "Alarm 84:9 SMART Link no. 4 Starting up of faulty compressor",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1755,
   "name": "Alarm 84:10 SMART Link no. 4 Discharge temperature above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1756,
   "name": "Alarm 84:11 SMART Link no. 4 Pressure difference below alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1911,
   "name": "Info 95:1 Supply air pre filter calibration performed at low air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1912,
   "name": "Info 95:2 Extract air pre filter calibration performed at low air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1913,
   "name": "Info 95:3 Supply air AHU filter calibration performed at low air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1914,
   "name": "Info 95:4 Extract air AHU filter calibration performed at low air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1915,
   "name": "Info 95:5 End filter calibration performed at low air flow",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1924,
   "name": "Info 95:14 Reduced humidity recovery time above alarm limit",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1925,
   "name": "Info 95:15 Supply air humidity level above outdoor air level",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1926,
   "name": "Info 96:1 H/C defrost calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1927,
   "name": "Info 96:2 H/C defrost calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1928,
   "name": "Info 96:3 H/C minimum SA flow limit below factory setting",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1929,
   "name": "Info 96:4 H/C minimum EA flow limit below factory setting",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1930,
   "name": "Info 96:5 H/C OA temp limit for heating below factory setting",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1941,
   "name": "Info 97:1 Cloud connection offline",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1942,
   "name": "Info 97:2 Cloud certificate missing/expired",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1952,
   "name": "Info 97:12 Plate heat exchanger bypass optimization not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1953,
   "name": "Info 97:13 Plate heat exchanger bypass optimization not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1954,
   "name": "Info 97:14 Plate heat exchanger defrost calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1955,
   "name": "Info 97:15 Plate heat exchanger defrost calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1956,
   "name": "Info 98:1 Supply air pre-filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1957,
   "name": "Info 98:2 Supply air pre-filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1958,
   "name": "Info 98:3 Extract air pre-filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1959,
   "name": "Info 98:4 Extract air pre-filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1960,
   "name": "Info 98:5 Supply air air handling unit filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1961,
   "name": "Info 98:6 Supply air air handling unit filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1962,
   "name": "Info 98:7 Extract air air handling unit filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1963,
   "name": "Info 98:8 Extract air air handling unit filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1964,
   "name": "Info 98:9 Supply air end filter calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1965,
   "name": "Info 98:10 Supply air end filter calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1966,
   "name": "Info 98:11 Rotary heat exchanger defrost calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1967,
   "name": "Info 98:12 Rotary heat exchanger defrost calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1968,
   "name": "Info 98:13 ReCO2 calibration not performed",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1969,
   "name": "Info 98:14 ReCO2 calibration not approved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1970,
   "name": "Info 98:15 ReCO2 incorrect setting",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1971,
   "name": "Info 99:1 E-mail error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1975,
   "name": "Info 99:5 FTP error",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1976,
   "name": "Info 99:6 Schedule invalid data auto corrected",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1977,
   "name": "Info 99:7 SD card memory soon full. Oldest log data will soon be deleted",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1978,
   "name": "Info 99:8 SD card memory full. Oldest log data deleted",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1979,
   "name": "Info 99:9 IQlogic CPU2 reboot caused by corrupt SD card remove and replace",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1981,
   "name": "Info 99:11 No external outdoor air temp. sensor connected for heat retention",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1982,
   "name": "Info 99:12 No extract air/room temperature sensor connected",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1984,
   "name": "Info 99:14 Internal serial memory error CPU 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1985,
   "name": "Info 99:15 Clock circuit defective",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2001,
   "name": "Active alarm group 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2002,
   "name": "Active alarm group 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2003,
   "name": "Active alarm group 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2004,
   "name": "Active alarm group 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2005,
   "name": "Active alarm group 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2006,
   "name": "Active alarm group 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2007,
   "name": "Active alarm group 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2008,
   "name": "Active alarm group 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2009,
   "name": "Active alarm group 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2010,
   "name": "Active alarm group 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2011,
   "name": "Active alarm group 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2012,
   "name": "Active alarm group 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2013,
   "name": "Active alarm group 13",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2014,
   "name": "Active alarm group 14",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2015,
   "name": "Active alarm group 15",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2016,
   "name": "Active alarm group 16",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2017,
   "name": "Active alarm group 17",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2018,
   "name": "Active alarm group 18",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2019,
   "name": "Active alarm group 19",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2020,
   "name": "Active alarm group 20",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2021,
   "name": "Active alarm group 21",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2022,
   "name": "Active alarm group 22",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2023,
   "name": "Active alarm group 23",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2024,
   "name": "Active alarm group 24",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2025,
   "name": "Active alarm group 25",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2026,
   "name": "Active alarm group 26",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2027,
   "name": "Active alarm group 27",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2028,
   "name": "Active alarm group 28",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2029,
   "name": "Active alarm group 29",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2030,
   "name": "Active alarm group 30",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2031,
   "name": "Active alarm group 31",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2032,
   "name": "Active alarm group 32",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2033,
   "name": "Active alarm group 33",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2034,
   "name": "Active alarm group 34",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2035,
   "name": "Active alarm group 35",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2036,
   "name": "Active alarm group 36",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2037,
   "name": "Active alarm group 37",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2038,
   "name": "Active alarm group 38",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2039,
   "name": "Active alarm group 39",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2040,
   "name": "Active alarm group 40",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2041,
   "name": "Active alarm group 41",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2042,
   "name": "Active alarm group 42",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2043,
   "name": "Active alarm group 43",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2044,
   "name": "Active alarm group 44",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2045,
   "name": "Active alarm group 45",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2046,
   "name": "Active alarm group 46",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2047,
   "name": "Active alarm group 47",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2048,
   "name": "Active alarm group 48",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2049,
   "name": "Active alarm group 49",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2050,
   "name": "Active alarm group 50",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2051,
   "name": "Active alarm group 51",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2052,
   "name": "Active alarm group 52",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2053,
   "name": "Active alarm group 53",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2054,
   "name": "Active alarm group 54",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2055,
   "name": "Active alarm group 55",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2056,
   "name": "Active alarm group 56",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2057,
   "name": "Active alarm group 57",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2058,
   "name": "Active alarm group 58",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2059,
   "name": "Active alarm group 59",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2060,
   "name": "Active alarm group 60",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2061,
   "name": "Active alarm group 61",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2062,
   "name": "Active alarm group 62",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2063,
   "name": "Active alarm group 63",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2064,
   "name": "Active alarm group 64",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2065,
   "name": "Active alarm group 65",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2066,
   "name": "Active alarm group 66",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2067,
   "name": "Active alarm group 67",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2068,
   "name": "Active alarm group 68",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2069,
   "name": "Active alarm group 69",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2070,
   "name": "Active alarm group 70",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2071,
   "name": "Active alarm group 71",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2072,
   "name": "Active alarm group 72",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2073,
   "name": "Active alarm group 73",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2074,
   "name": "Active alarm group 74",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2075,
   "name": "Active alarm group 75",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2076,
   "name": "Active alarm group 76",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2077,
   "name": "Active alarm group 77",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2078,
   "name": "Active alarm group 78",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2079,
   "name": "Active alarm group 79",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2080,
   "name": "Active alarm group 80",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2081,
   "name": "Active alarm group 81",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2082,
   "name": "Active alarm group 82",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2083,
   "name": "Active alarm group 83",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2084,
   "name": "Active alarm group 84",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2085,
   "name": "Active alarm group 85",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2086,
   "name": "Active alarm group 86",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2087,
   "name": "Active alarm group 87",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2088,
   "name": "Active alarm group 88",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2089,
   "name": "Active alarm group 89",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2090,
   "name": "Active alarm group 90",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2091,
   "name": "Active alarm group 91",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2092,
   "name": "Active alarm group 92",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2093,
   "name": "Active alarm group 93",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2094,
   "name": "Active alarm group 94",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2095,
   "name": "Active alarm group 95",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2096,
   "name": "Active alarm group 96",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2097,
   "name": "Active alarm group 97",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2098,
   "name": "Active alarm group 98",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2099,
   "name": "Active alarm group 99",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2100,
   "name": "Active alarm group 100",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Booster diffusers",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Alarm reset",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Internal fire alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "SA flow pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "EA flow pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "SA duct pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "EA duct pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "ReCO2 pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "RHX defrost pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Carry over control pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "SA filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "EA filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "SA pre-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "EA pre-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "SA end-filter pressure sensor auto zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "PX heat exchange pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "Air quality control pressure sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "HC defrost sensor auto calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "SA flow pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "EA flow pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "SA duct pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "EA duct pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "ReCO2 pressure sensor activate calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "RHX Defrost pressure sensor activate calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "Carry over control pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "SA filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "EA filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "SA pre-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "EA pre-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "SA end-filter pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "PX heat exchange pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "Air quality control pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "HC defrost pressure sensor activate zero calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "External room sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "External room sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "External room sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 165,
   "name": "External room sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 167,
   "name": "External room temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "External OA sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "External OA sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "External OA sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "External OA sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "External OA temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 182,
   "name": "RHX defrost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 183,
   "name": "RHX defrost calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 187,
   "name": "RHX carry over control function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 190,
   "name": "RHX min exhaust air temp function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "PHX periodic operation of bypass damper function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "PX bypass optimize",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "CHX periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "CHX periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 228,
   "name": "Re-heat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 229,
   "name": "Re-heat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 245,
   "name": "Extra regulation 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 246,
   "name": "Extra regulation 1 periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 274,
   "name": "Cool relay 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 275,
   "name": "Cool relay 2 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 276,
   "name": "Cool periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 296,
   "name": "Intermittent night heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 302,
   "name": "Intermittent night heat recirculation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "Morning boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 320,
   "name": "Heating boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 325,
   "name": "Xzone heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 327,
   "name": "Xzone cool function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 374,
   "name": "Xzone external room sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 375,
   "name": "Xzone external room sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 376,
   "name": "Xzone external room sensor 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 377,
   "name": "Xzone external room sensor 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 379,
   "name": "Xzone external room temp from BMS function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 386,
   "name": "Xzone reheat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 387,
   "name": "Xzone reheat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 400,
   "name": "Xzone Cool relay 1 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 401,
   "name": "Xzone Cool relay 2 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "Xzone Cool periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 410,
   "name": "Pre-heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 414,
   "name": "Pre-heat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 415,
   "name": "Pre-heat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 425,
   "name": "ReCO2 Calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 459,
   "name": "Heat exchange active in dehumidifying sequence",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 477,
   "name": "Exhaust heat periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 478,
   "name": "Exhaust heat periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 489,
   "name": "SMART Link WB Cooling Optimize function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 490,
   "name": "SMART Link WB Heating Optimize function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 504,
   "name": "AQUA Link Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 530,
   "name": "AYC Heated water periodic operation of pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 531,
   "name": "AYC Heated water periodic operation of valve",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 536,
   "name": "AYC Heated water OA temp compensation",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 547,
   "name": "AYC Heated water room temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 548,
   "name": "AYC Heated water room temp compensation at night",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 553,
   "name": "AYC Heated water night temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 579,
   "name": "AYC Chilled water periodic operation of pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 580,
   "name": "AYC Chilled water periodic operation of valve",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 585,
   "name": "AYC Chilled water OA temp compensation",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 596,
   "name": "AYC Chilled water room temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 597,
   "name": "AYC Chilled water room temp compensation at night",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 602,
   "name": "AYC Chilled water night temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 618,
   "name": "AYC Chilled water dew point compensation air flow boost",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 637,
   "name": "Optimize function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 775,
   "name": "Night temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 824,
   "name": "Extra regulation 2 periodic operation of pump function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 825,
   "name": "Extra regulation 2 periodic operation of valve function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1000,
   "name": "External operation I/O-module A, function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1001,
   "name": "External operation I/O-module A, temp sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1002,
   "name": "External operation I/O-module A, temp sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1003,
   "name": "External operation I/O-module A, digital output",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1004,
   "name": "External operation I/O-module B, function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1005,
   "name": "External operation I/O-module B, temp sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1006,
   "name": "External operation I/O-module B, temp sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1007,
   "name": "External operation I/O-module B, digital output",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1008,
   "name": "External operation I/O-module C, function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1009,
   "name": "External operation I/O-module C, temp sensor 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1010,
   "name": "External operation I/O-module C, temp sensor 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1011,
   "name": "External operation I/O-module C, digital output",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3000,
   "name": "External override function, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3010,
   "name": "External override value, Supply air fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3011,
   "name": "External override value, Extract air fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3050,
   "name": "External override value, Pre-heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3060,
   "name": "External override value, Reheat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3070,
   "name": "External override value, Xzone heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3080,
   "name": "External override value, Extra reg. 1 relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3081,
   "name": "External override value, Extra reg. 1 relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3090,
   "name": "External override value, Extra reg. 2 relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3091,
   "name": "External override value, Extra reg. 2 relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3100,
   "name": "External override value, Cool relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3101,
   "name": "External override value, Cool relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3110,
   "name": "External override value, Xzone cool relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3111,
   "name": "External override value, Xzone cool relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3120,
   "name": "External override value, COOL DX comp. 1 on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3121,
   "name": "External override value, COOL DX comp. 2 on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3130,
   "name": "External override value, HC, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3131,
   "name": "External override value, HC cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3132,
   "name": "External override value, HC defrost, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3140,
   "name": "External override value, SMART Link WB, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3141,
   "name": "External override value, SMART Link WB, SMART Link WB cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3150,
   "name": "External override value, SMART Link DX 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3151,
   "name": "External override value, SMART Link DX 1 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3152,
   "name": "External override value, SMART Link DX 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3153,
   "name": "External override value, SMART Link DX 2 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3154,
   "name": "External override value, SMART Link DX 3, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3155,
   "name": "External override value, SMART Link DX 3 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3156,
   "name": "External override value, SMART Link DX 4, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3157,
   "name": "External override value, SMART Link DX 4 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3160,
   "name": "External override value, AQUA Link pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3170,
   "name": "External override value, Humidifying relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3190,
   "name": "External override value, AYC heat pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3191,
   "name": "External override value, AYC cool pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3200,
   "name": "External override value, AHU damper relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3201,
   "name": "External override value, AHU operation relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3210,
   "name": "External override value, Booster heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3211,
   "name": "External override value, Booster cool relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3220,
   "name": "External override value, Miru 1 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3221,
   "name": "External override value, Miru 2 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3222,
   "name": "External override value, Miru 3 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3230,
   "name": "External override value, Exhaust heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4010,
   "name": "External override activate, Supply air fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4011,
   "name": "External override activate, Extract air fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4050,
   "name": "External override activate, Pre-heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4060,
   "name": "External override activate, Reheat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4070,
   "name": "External override activate, Xzone heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4080,
   "name": "External override activate, Extra reg. 1 relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4081,
   "name": "External override activate, Extra reg. 1 relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4090,
   "name": "External override activate, Extra reg. 2 relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4091,
   "name": "External override activate, Extra reg. 2 relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4100,
   "name": "External override activate, Cool relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4101,
   "name": "External override activate, Cool relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4110,
   "name": "External override activate, Xzone cool relay 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4111,
   "name": "External override activate, Xzone cool relay 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4120,
   "name": "External override activate, COOL DX comp. 1 on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4121,
   "name": "External override activate, COOL DX comp. 2 on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4130,
   "name": "External override activate, HC, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4131,
   "name": "External override activate, HC cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4132,
   "name": "External override activate, HC defrost, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4140,
   "name": "External override activate, SMART Link WB, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4141,
   "name": "External override activate, SMART Link WB, SMART Link WB cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4150,
   "name": "External override activate, SMART Link DX 1, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4151,
   "name": "External override activate, SMART Link DX 1 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4152,
   "name": "External override activate, SMART Link DX 2, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4153,
   "name": "External override activate, SMART Link DX 2 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4154,
   "name": "External override activate, SMART Link DX 3, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4155,
   "name": "External override activate, SMART Link DX 3 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4156,
   "name": "External override activate, SMART Link DX 4, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4157,
   "name": "External override activate, SMART Link DX 4 cool/heat, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4160,
   "name": "External override activate, AQUA Link pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4170,
   "name": "External override activate, Humidifying relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4190,
   "name": "External override activate, AYC heat pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4191,
   "name": "External override activate, AYC cool pump, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4200,
   "name": "External override activate, AHU damper relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4201,
   "name": "External override activate, AHU operation relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4210,
   "name": "External override activate, Booster heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4211,
   "name": "External override activate, Booster cool relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4220,
   "name": "External override activate, Miru 1 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4221,
   "name": "External override activate, Miru 2 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4222,
   "name": "External override activate, Miru 3 fan, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4230,
   "name": "External override activate, Exhaust heat relay, on/off",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5010,
   "name": "External override activate, Supply air fan level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5011,
   "name": "External override activate, Extract air fan level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5020,
   "name": "External override activate, RX HX level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5030,
   "name": "External override activate, PX HX damper 3A",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5031,
   "name": "External override activate, PX HX damper 1A",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5032,
   "name": "External override activate, PX HX bypass 2A",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5033,
   "name": "External override activate, PX HX bypass 4A",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5040,
   "name": "External override activate, CX HX valve",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5041,
   "name": "External override activate, CX HX pump level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5050,
   "name": "External override activate, Pre-heat level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5060,
   "name": "External override activate, Reheat level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5070,
   "name": "External override activate, Xzone heat level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5080,
   "name": "External override activate, Extra reg. 1 level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5090,
   "name": "External override activate, Extra reg. 2 level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5100,
   "name": "External override activate, Cool level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5110,
   "name": "External override activate, Xzone cool level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5130,
   "name": "External override activate, HC comp. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5131,
   "name": "External override activate, HC defrost recirc. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5132,
   "name": "External override activate, HC defrost el. heat level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5150,
   "name": "External override activate, SMART Link DX 1 comp. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5151,
   "name": "External override activate, SMART Link DX 2 comp. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5152,
   "name": "External override activate, SMART Link DX 3 comp. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5153,
   "name": "External override activate, SMART Link DX 4 comp. level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5170,
   "name": "External override activate, Humidifying level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5180,
   "name": "External override activate, ReCO2 recirculation damper",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5181,
   "name": "External override activate, ReCO2 outdoor damper",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5190,
   "name": "External override activate, AYC heat valve level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5191,
   "name": "External override activate, AYC cool valve level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5220,
   "name": "External override activate, Miru 1 fan level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5221,
   "name": "External override activate, Miru 2 fan level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5222,
   "name": "External override activate, Miru 3 fan level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5230,
   "name": "External override activate, Exhaust heat level",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 0,
   "name": "Calendar #1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 1,
   "name": "Calendar #2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Application id/AHU Type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Air flow direction",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Fan no.2 as SA, 2=Fan no.1 as SA"
  },
  {
   "type": "MI",
   "instance": 110,
   "name": "PHX bypass type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Center, 2=Side"
  },
  {
   "type": "MI",
   "instance": 114,
   "name": "PHX-2 3D Type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Cross flow, 2=Counter flow"
  },
  {
   "type": "MI",
   "instance": 115,
   "name": "PHX type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=PHX-1 1D HS, 2=PHX-2 3D, 3=PHX-3 1D 1PS"
  },
  {
   "type": "MI",
   "instance": 140,
   "name": "Extra regulation sequence 1 coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 142,
   "name": "Extra regulation sequence 2 coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 152,
   "name": "Re-heat coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 163,
   "name": "Cool coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 198,
   "name": "Xzone heat, coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 209,
   "name": "Xzone cool, coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used"
  },
  {
   "type": "MI",
   "instance": 224,
   "name": "Pre-heat coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 284,
   "name": "Exhaust heat coil type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 320,
   "name": "SMART Link, WB cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MI",
   "instance": 591,
   "name": "AHU Version",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Version 1, 2=Version 2, 3=Version 3, 4=Version 4, 5=Version A, 6=Version B, 7=Version C, 8=Version D, 9=Version E, 10=Version F"
  },
  {
   "type": "MI",
   "instance": 592,
   "name": "Operation level",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation, 15=Morning boost stop, 16=Intermittent night heat stop, 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment"
  },
  {
   "type": "MI",
   "instance": 665,
   "name": "Schedule exception invalid data",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 666,
   "name": "Calendar 1 invalid data",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 667,
   "name": "Calendar 2 invalid data",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 1400,
   "name": "H/C mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 1401,
   "name": "H/C defrost accessory",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Recirculation, 3=Electric heat"
  },
  {
   "type": "MI",
   "instance": 1402,
   "name": "H/C recirculation defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 1403,
   "name": "H/C defrost active",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MI",
   "instance": 1407,
   "name": "H/C heat type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric"
  },
  {
   "type": "MI",
   "instance": 1410,
   "name": "H/C operation mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Stop, 3=Stabilization, 4=Normal operation, 5=Comfort operation, 6=Economy operation, 7=Defrost, 8=Defrost, 9=Oil recovery"
  },
  {
   "type": "MI",
   "instance": 1411,
   "name": "H/C defrost mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Start delay, 3=Initializing, 4=Pre-defrosting, 5=Defrosting, 6=Draining"
  },
  {
   "type": "MI",
   "instance": 1412,
   "name": "H/C heat/cool mode",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Heating, 2=Cooling"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Boost Supply air",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Boost Extract air",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On"
  },
  {
   "type": "NC",
   "instance": 0,
   "name": "NC 00 A-Alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 1,
   "name": "NC 01 B-Alarm",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 3,
   "name": "NC 03 Alarms specified in BACnet",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 10,
   "name": "NC 10 Info message",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 11,
   "name": "NC 11 Events specified in BACnet",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 0,
   "name": "Schedule #1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "SA Fan regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "EA Fan regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Internal fire alarm reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "External fire alarm no. 1 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "External fire alarm no. 2 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "External alarm no. 1 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "External alarm no. 2 reset function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Manual reset, 2=Auto reset"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "External alarm no. 1 input function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Alarm at closed contact, 2=Alarm at open contact"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "External alarm no. 2 input function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Alarm at closed contact, 2=Alarm at open contact"
  },
  {
   "type": "MV",
   "instance": 53,
   "name": "Outdoor temp compensation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed"
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "Down regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=SA and EA"
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "Fans in operation at fire alarm 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 87,
   "name": "Fans in operation at fire alarm 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 90,
   "name": "Fans in operation at internal fire alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "Pre-filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "Pre-filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "AHU filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "AHU filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=SA and EA"
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "SA end filter function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA"
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "SA end filter calibration",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "Seasonal controlled temperature regulation",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "Seasonal controlled temperature regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "Temperature regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE"
  },
  {
   "type": "MV",
   "instance": 166,
   "name": "External room sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 176,
   "name": "External OA sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 188,
   "name": "RHX sorption rotor function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Sorption max at cool, 3=Sorption always max"
  },
  {
   "type": "MV",
   "instance": 189,
   "name": "Rotor type",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=RECOnomic, 2=STE, 3=MPE, 4=MTE"
  },
  {
   "type": "MV",
   "instance": 236,
   "name": "Extra regulation 1 combi coil output indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 237,
   "name": "Extra regulation sequence 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool"
  },
  {
   "type": "MV",
   "instance": 238,
   "name": "Extra regulation sequence 1 output function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=0-10V, 2=10-0V"
  },
  {
   "type": "MV",
   "instance": 249,
   "name": "Extra regulation 1 combi coil external signal indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 250,
   "name": "Extra regulation 1 combi coil external signal value",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 251,
   "name": "Extra regulation 1 temperature protection function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 254,
   "name": "Season heat function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode"
  },
  {
   "type": "MV",
   "instance": 255,
   "name": "Season heat manual setting",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Re-heat, 2=Extra regulation sequence"
  },
  {
   "type": "MV",
   "instance": 261,
   "name": "Cool on/off regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=1 step, 3=2 steps, 4=3 steps"
  },
  {
   "type": "MV",
   "instance": 284,
   "name": "Summer night cool function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Internal, 3=External"
  },
  {
   "type": "MV",
   "instance": 295,
   "name": "Summer night cool from communication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 313,
   "name": "Cooling boost function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence, 7=Sequence and Comfort, 8=Comfort, Economy and Sequence"
  },
  {
   "type": "MV",
   "instance": 329,
   "name": "Xzone temperature regulation mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=ERS-1, 2=ERS-2, 3=SA, 4=EA, 5=ORS, 6=ORE"
  },
  {
   "type": "MV",
   "instance": 378,
   "name": "Xzone external room sensors measurement function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Average, 2=Min, 3=Max"
  },
  {
   "type": "MV",
   "instance": 390,
   "name": "Xzone combi coil module A external signal indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 391,
   "name": "Xzone combi coil module A output indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 392,
   "name": "Xzone combi coil module A external signal value",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 395,
   "name": "Xzone Cool on/off regulation function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=1 step, 3=2 steps, 4=3 steps"
  },
  {
   "type": "MV",
   "instance": 405,
   "name": "Xzone combi coil module B external signal indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 406,
   "name": "Xzone combi coil module B output indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 407,
   "name": "Xzone combi coil module B external signal value",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 423,
   "name": "ReCO2-CO2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=CO2, 3=CO2 and air flow boost"
  },
  {
   "type": "MV",
   "instance": 424,
   "name": "ReCO2 temperature regulation sequence function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool"
  },
  {
   "type": "MV",
   "instance": 441,
   "name": "Humidifying function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=On/Off, 3=0-10V"
  },
  {
   "type": "MV",
   "instance": 442,
   "name": "Humidifying sensor",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=SA, 2=EA, 3=Room"
  },
  {
   "type": "MV",
   "instance": 457,
   "name": "DeHumidifying function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA, 4=Room"
  },
  {
   "type": "MV",
   "instance": 465,
   "name": "VOC sensor function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monitoring only, 3=Monitoring and regulation"
  },
  {
   "type": "MV",
   "instance": 469,
   "name": "COOL DX Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Economy, 3=Comfort, 4=Top"
  },
  {
   "type": "MV",
   "instance": 473,
   "name": "Constant exhaust air temperature function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 481,
   "name": "SMART Link Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible"
  },
  {
   "type": "MV",
   "instance": 505,
   "name": "AQUA Link Pump alarm function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function)"
  },
  {
   "type": "MV",
   "instance": 521,
   "name": "AYC Function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water"
  },
  {
   "type": "MV",
   "instance": 528,
   "name": "AYC Heated water signal monitor function for pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function"
  },
  {
   "type": "MV",
   "instance": 555,
   "name": "AYC Heated water night temp compensation time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 562,
   "name": "AYC Heated water night temp compensation time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 577,
   "name": "AYC Chilled water signal monitor function for pump",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function"
  },
  {
   "type": "MV",
   "instance": 604,
   "name": "AYC Chilled water night temp compensation time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 611,
   "name": "AYC Chilled water night temp compensation time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 660,
   "name": "MIRU Control 1 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 661,
   "name": "MIRU Control 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 662,
   "name": "MIRU Control 3 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 663,
   "name": "MIRU Control 4 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 664,
   "name": "MIRU Control 5 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 665,
   "name": "MIRU Control 6 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 666,
   "name": "MIRU Control 7 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 667,
   "name": "MIRU Control 8 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 668,
   "name": "MIRU Control 9 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 669,
   "name": "MIRU Control 10 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and low / high speed"
  },
  {
   "type": "MV",
   "instance": 671,
   "name": "MIRU Control 1 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 679,
   "name": "MIRU Control 2 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 687,
   "name": "MIRU Control 3 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 695,
   "name": "MIRU Control 4 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 703,
   "name": "MIRU Control 5 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 711,
   "name": "MIRU Control 6 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 719,
   "name": "MIRU Control 7 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 727,
   "name": "MIRU Control 8 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 735,
   "name": "MIRU Control 9 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 743,
   "name": "MIRU Control 10 Balanced air flow function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=SA, 3=EA"
  },
  {
   "type": "MV",
   "instance": 765,
   "name": "Heat neutral zone function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Set point, 2=Start limit"
  },
  {
   "type": "MV",
   "instance": 766,
   "name": "Cool neutral zone function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Set point, 2=Start limit"
  },
  {
   "type": "MV",
   "instance": 777,
   "name": "Night temp compensation time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 782,
   "name": "Night temp compensation time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 793,
   "name": "Communication operation level",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop"
  },
  {
   "type": "MV",
   "instance": 794,
   "name": "Schedule operation level",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop"
  },
  {
   "type": "MV",
   "instance": 816,
   "name": "Extra regulation sequence 2 function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool"
  },
  {
   "type": "MV",
   "instance": 817,
   "name": "Extra regulation sequence 2 output function",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=0-10V, 2=10-0V"
  },
  {
   "type": "MV",
   "instance": 828,
   "name": "Extra regulation 2 combi coil external signal indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 829,
   "name": "Extra regulation 2 combi coil external signal value",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Active"
  },
  {
   "type": "MV",
   "instance": 834,
   "name": "Extra regulation 2 combi coil output indication",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MV",
   "instance": 850,
   "name": "H/C heat mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Standard, 2=Comfort"
  },
  {
   "type": "MV",
   "instance": 851,
   "name": "H/C cool mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Standard, 2=Comfort"
  },
  {
   "type": "MV",
   "instance": 890,
   "name": "Humidifying time 1 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 895,
   "name": "Humidifying time 2 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 900,
   "name": "Humidifying time 3 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  },
  {
   "type": "MV",
   "instance": 905,
   "name": "Humidifying time 4 (days)",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10=Monday to Sunday, 11=Saturday to Sunday"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/swegon/gold-e-f-bacnet-ip-pv248",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}