Air handling unit controller · BACnet points list
OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet points list
Updated 12 November 2026
The OJ Air Plus is an air handling unit controller with a native BACnet server. Its EDE file lists close to a thousand objects: Analog Inputs for measured temperatures, pressures, flows and outputs; Analog Values for setpoints and configuration; Binary Inputs for status and alarm flags; Binary Values for function switches and BMS commands. Many objects only matter when the matching function or module is fitted.
This page lists 979 BACnet objects for the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 — 282 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.
- Manufacturer
- OJ Electronics
- Model
- OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 979 (282 writable)
- Transport
- —
- Firmware
- SW 1.09
- Default device instance
- 15530
- Also known as
- OJ Air Plus, OJ-Air Plus, AirPlus, EXcon-Plus, EXcon Plus, 670203
Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.
BMS integration notes: OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
Read the unit state from AI 0 and BI 0, the temperatures and flows from the AI block, and the two alarm relays (BI 30 A-alarm, BI 31 B-alarm). BMS run modes go through AV 108, which only works after the physical operation input is activated; BV 0 resets alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 108 | BMS-modes only avalable after activation of pysical input 'Oper | BMS run mode; needs the physical operation input | Write |
| AV 134 | TempSet for actual RegMode [1/100C] | Temperature setpoint for the active control mode | Write |
| BV 0 | Alarm reset signal (AutoReturn to zero) | Alarm reset (returns to 0 by itself) | Write |
| AI 0 | Actual operating mode 000-099 Unit stopped 100-199: Unit in low | Actual operating mode code | Read |
| BI 0 | Operation ON/OFF | Operation on/off status | Read |
| AI 16 | Current SupplyTemp [1/100C] | Supply air temperature, 1/100 °C | Read |
| AI 5 | Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u | Actual supply airflow | Read |
| BI 30 | Alarm relay 1 (A-alarm) | A-alarm relay (critical alarm) | Read |
| BI 31 | Alarm relay 2 (B-alarm) | B-alarm relay (non-critical alarm) | Read |
Enable & remote start
AV 108 sets the BMS run mode, but only after the physical operation input is activated (per the object name).
Sensors & values from the BMS
Outdoor and room temperature can come from the BMS: write AV 102 / AV 103 and switch them in with BV 15 / BV 16.
Network setup
- The EDE gives device instance 15530 and device name EXcon-Plus.
Watch out for
- Most temperatures and percentages are in hundredths.
- Object names are long texts cut at about 63 characters; map by type and instance, not by name.
- Outdoor and room temperature from the BMS (AV 102, AV 103) are only used when BV 15 / BV 16 activate them.
OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Actual operating mode 000-099 Unit stopped 100-199: Unit in low | OL_Act_DriftMode | Read | ||
| AI | 1 | SA DuctPressure (Calc from PressSignal) [Pa] | AR_SupDuctPa | Pa | Read | |
| AI | 2 | Regulator SetPoint for DuctPressReg [Pa] SA | AR_SupDuctPaRgSet | Pa | Read | |
| AI | 3 | Extract DuctPressure (Calc from PressSignal) [Pa] | AR_ExtDuctPa | Pa | Read | |
| AI | 4 | Regulator SetPoint for DuctPressReg [Pa] EA | AR_ExtDuctPaRgSet | Pa | Read | |
| AImin | 5 | Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u | AR_Act_SA_Flow | l/s | Read | |
| AI | 6 | Setpoint for supply flow controller [l/s] or [m3/h] or [CFM] (D | AR_SA_FlowRegSet | l/s | Read | |
| AI | 7 | Actual Extract/Exhaust flow [l/s] or [m3/h] or [CFM] (Depending | AR_Act_EA_Flow | l/s | Read | |
| AI | 8 | Setpoint for Extract/Exhaust flow controller [l/s] or [m3/h]or | AR_EA_FlowRegSet | l/s | Read | |
| AI | 9 | AR_CO2 Sensor ppm Measure [ppm] | AR_CO2_ppmMeas | Read | ||
| AI | 10 | Signal from Fanoptimizer Input SA | FANOpt_SA_Ctrl_Vin | V | Read | |
| AI | 11 | Signal from Fanoptimizer Input EA | FANOpt_EA_Ctrl_Vin | V | Read | |
| AI | 12 | FAN-Opt Supply Signal [1/100%] | FANOpt_SAPrc_An_In | % | Read | |
| AI | 13 | FAN-Opt Extract Signal [1/100%] | FANOpt_EAPrc_An_In | % | Read | |
| AI | 14 | Supply Max Flow [l/s], Aggregate max | AR_SA_MaxFlow_AggSize | l/s | Read | |
| AI | 15 | Extract/Exhaust Max Flow [l/s], Aggregate | AR_EA_MaxFlow_AggSize | l/s | Read | |
| AImin | 16 | Current SupplyTemp [1/100C] | ATMP_SupTemp | °C | Read | |
| AI | 17 | Regulator SupplyTemp-Set [1/100C] | ATMP_SupTempRegSet | °C | Read | |
| AI | 18 | Actual extract temperature [1/100°C] | ATMP_ExtTemp | °C | Read | |
| AI | 19 | Regulator ExtractTemp-Set [1/100C] | ATMP_ExtTempRegSet | °C | Read | |
| AI | 20 | Actual outdoor temperature [1/100°C] | ATMP_Used_OATemp | °C | Read | |
| AI | 21 | Current RoomTemp (External Sens) [1/100C] | ATMP_RoomTemp | °C | Read | |
| AI | 22 | Current ExhaustTemp [1/100C] | ATMP_ExhaustTemp | °C | Read | |
| AI | 23 | TempMeas for actual RegMode [1/100C] | TR_TempRegMeas | °C | Read | |
| AI | 24 | RegVal for actual RegMode [1/100C] | TR_TempRegVal | °C | Read | |
| AI | 25 | Fluid EXC Temp after EXC [1/100C] | BattEXC_Temp | °C | Read | |
| AI | 26 | Current HeatWaterBatt 1 Temp [1/100C] | ATMP_HT1_CoilRT | °C | Read | |
| AI | 27 | Outdoor Filter Pressure (Avr-Meas) [Pa] | FM_SF_OA_ActFiltPress | Pa | Read | |
| AI | 28 | Extract Filter Pressure (Avr-Meas) [Pa] | FM_SF_EA_ActFiltPress | Pa | Read | |
| AI | 29 | Supply Motor signal percent | AR_SA_MotorSet | % | Read | |
| AI | 30 | Extract/Exhaust Motor signal percent | AR_EA_MotorSet | % | Read | |
| AI | 31 | OA Filter pressure for alarm-limit at actual flow [Pa] | Filt_AlrPa_OA | Pa | Read | |
| AI | 32 | EA Filter pressure for alarm-limit at actual flow [Pa] | Filt_AlrPa_EA | Pa | Read | |
| AI | 33 | FlowOutTempComp PercentOut [1/100%] | AR_FlwTmpCmpOut | % | Read | |
| AI | 34 | Sum/Wint-TempComp actual Setpoint offset [1/100C ] | SWTC_ActSetOfs | Read | ||
| AI | 35 | EXC-Regulator HeatPower [1/100 %] | HeatEXCPower | % | Read | |
| AI | 36 | AfterHeat1-Regulator Power [1/100 %] | Heat1Power | % | Read | |
| AI | 37 | Cool Regulator Power [1/100 %], Output | CL_Cool_Power_AO | % | Read | |
| AI | 38 | Actual Cool-Power [1/100%] | CL_Cool_ActPower | % | Read | |
| AI | 39 | Cool Force Flow Power [1/100 %] | CL_Cool_FlwForcePw | % | Read | |
| AI | 40 | Cool Alarm-1 VDC-Signal [1/100 %] | CL_Cool_Vin1Alarm | % | Read | |
| AI | 41 | Cool Alarm-2 VDC-Signal [1/100 %] | CL_Cool_Vin2Alarm | % | Read | |
| AI | 42 | Cool Alarm-3 VDC-Signal [1/100 %] | CL_Cool_Vin3Alarm | % | Read | |
| AI | 43 | Cool Alarm-4 VDC-Signal [1/100 %] | CL_Cool_Vin4Alarm | % | Read | |
| AI | 44 | Actual low pressure sensor 1 [1/100 bar] | CL_LoPress1Bar | Read | ||
| AI | 45 | Actual high pressure sensor 1 [1/100 bar] | CL_HiPress1Bar | Read | ||
| AI | 46 | Actual low pressure sensor 2 [1/100 bar] | CL_LoPress2Bar | Read | ||
| AI | 47 | Actual high pressure sensor 2 [1/100 bar] | CL_HiPress2Bar | Read | ||
| AI | 55 | Extract SFP [Ws/m3 same as J/m3] | AR_ExtSFP | Read | ||
| AI | 56 | Supply SFP [Ws/m3 same as J/m3] | AR_SupSFP | Read | ||
| AI | 66 | RotaryEXC – motor type | DRHX_Type | Read | ||
| AI | 67 | RotaryEXC – software version [1/100] | DRHX_MOC_SW_Ver | Read | ||
| AI | 68 | RotaryEXC – percentage [1/100%] | DRHX_PercentOut | % | Read | |
| AI | 69 | RotaryEXC – speed output [1/10 rpm] | DRHX_RpmOut | Read | ||
| AI | 70 | RotaryEXC - actual output [mA] | DRHX_I_Out | Read | ||
| AI | 71 | RotaryEXC – output power [W] | DRHX_Power | W | Read | |
| AI | 72 | RotaryEXC – days of operation | DRHX_DriftDays | Read | ||
| AI | 73 | RotaryEXC – percentage setpoint [1/100%] | DRHX_PercentSet | % | Read | |
| AI | 74 | Extension module 1 software version [1/100] | IO2_ID1_SW_Ver | Read | ||
| AI | 75 | Extension module 2 software version [1/100] | IO2_ID2_SW_Ver | Read | ||
| AI | 76 | Act weekday Monday..Sunday (1 = Monday) | RTC_WeekDay | Read | ||
| AI | 79 | Stack for active alarm's 0 (0 end of stack) | Alr_ReleasedId | Read | ||
| AI | 80 | Stack for active alarm's 1 (0 end of stack) | Alr_ReleasedId01 | Read | ||
| AI | 81 | Stack for active alarm's 2 (0 end of stack) | Alr_ReleasedId02 | Read | ||
| AI | 82 | Stack for active alarm's 3 (0 end of stack) | Alr_ReleasedId03 | Read | ||
| AI | 83 | Stack for active alarm's 4 (0 end of stack) | Alr_ReleasedId04 | Read | ||
| AI | 84 | Stack for active alarm's 5 (0 end of stack) | Alr_ReleasedId05 | Read | ||
| AI | 85 | Stack for active alarm's 6 (0 end of stack) | Alr_ReleasedId06 | Read | ||
| AI | 86 | Stack for active alarm's 7 (0 end of stack) | Alr_ReleasedId07 | Read | ||
| AI | 87 | Stack for active alarm's 8 (0 end of stack) | Alr_ReleasedId08 | Read | ||
| AI | 88 | Stack for active alarm's 9 (0 end of stack) | Alr_ReleasedId09 | Read | ||
| AI | 89 | Stack for active alarm's 10 (0 end of stack) | Alr_ReleasedId10 | Read | ||
| AI | 90 | Stack for active alarm's 11 (0 end of stack) | Alr_ReleasedId11 | Read | ||
| AI | 91 | Stack for active alarm's 12 (0 end of stack) | Alr_ReleasedId12 | Read | ||
| AI | 92 | Stack for active alarm's 13 (0 end of stack) | Alr_ReleasedId13 | Read | ||
| AI | 93 | Stack for active alarm's 14 (0 end of stack) | Alr_ReleasedId14 | Read | ||
| AI | 94 | Stack for active alarm's 15 (0 end of stack) | Alr_ReleasedId15 | Read | ||
| AI | 95 | Master Software Ver [1/100] | MasterSW_Ver | Read | ||
| AI | 96 | Display Software Ver [1/100] | DisplaySW_Ver | Read | ||
| AI | 97 | Additional TempSensor1 [1/100C] | ATMP_AddOnTSensor1 | °C | Read | |
| AI | 98 | Additional TempSensor2 [1/100C} | ATMP_AddOnTSensor2 | °C | Read | |
| AI | 99 | Additional TempSensor3 [1/100C] | ATMP_AddOnTSensor3 | °C | Read | |
| AI | 100 | Additional TempSensor4 [1/100C] | ATMP_AddOnTSensor4 | °C | Read | |
| AI | 103 | AfterHeat2-Regulator Power [1/100 %] | HW_EL_HT2_Power | % | Read | |
| AI | 104 | Heatpower Preheater [1/100%] | PH_HeatPower | % | Read | |
| AI | 105 | Current Pre-HeatWaterBattTemp [1/100C] Coil/Return | ATMP_PH_CoilRT | °C | Read | |
| AI | 108 | Heat exchanger efficiency [1/100%] | EXCActualEff | % | Read | |
| AI | 109 | Voltage level, HWB1 Out2 | HW12_VDCOut | V | Read | |
| AI | 110 | Measured pressure loss over heat pump outdoor coil. | HP_CoilPaMeas | Pa | Read | |
| AI | 111 | ModCO2, State 1-L/H, 2-H/L,0-nothing | MODREC_AltFlowAct | Read | ||
| AI | 112 | Recirce closedown timer | UPS_RecClosTimer | s | Read | |
| AI | 113 | CombiBattery VDC-Signal out for AfterHeat/Cool [1/1000 V] | CombiVDC_Out | V | Read | |
| AI | 114 | CombiBattery Power for Heat [1/100%] | CombiHeatPow | % | Read | |
| AI | 115 | CombiBattery Power for Cool [1/100%] | CombiCoolPow | % | Read | |
| AI | 118 | Current external OutDoorTemp [1/100C] | ATMP_ExtOA_SensTemp | °C | Read | |
| AI | 119 | Temperature after pre-heating coil [1/100 °C] | ATMP_PHeatTempAir | °C | Read | |
| AI | 120 | Cold water supply temperature for cooling coil [1/100 °C] | ATMP_CW1_Inlet | °C | Read | |
| AI | 121 | Damper position outdoor damper [1/100 %] | AR_REC_FreshAirDis | % | Read | |
| AI | 122 | Damper position recirculation [1/100 %] | AR_REC_DampPrcDis | % | Read | |
| AI | 123 | Output voltage cooling valve2 (only combi coil) | CL_CoolVDC_Out2 | V | Read | |
| AI | 124 | OA filter restime before filtershift alarm activated | FM_SF_OA_Timer_Rest_d | Read | ||
| AI | 125 | EA filter restime before filtershift alarm activated | FM_SF_EA_Timer_Rest_d | Read | ||
| AI | 126 | Combi HT-WaterBattTemp [1/100C] Coil/Return | ATMP_CMB_CoilRT | °C | Read | |
| AI | 127 | Rel. Humidity Extract air | AR_RelHumExtract | %RH | Read | |
| AI | 128 | Rel. Humidity Supply air | AR_RelHumSupply | %RH | Read | |
| AI | 129 | Rel. Humidity Mixed air | AR_RelHumMixed | %RH | Read | |
| AI | 130 | Extract Filter2 Pressure (Avr-Meas) [Pa] | FM_SF_EA2_ActFiltPress | Pa | Read | |
| AI | 131 | Supply Filter Pressure (Avr-Meas) [Pa] | FM_SF_SA_ActFiltPress | Pa | Read | |
| AI | 132 | Number of Detected ZoneModules | ZM_Count | Read | ||
| AI | 133 | ZoneControl Operation Mode | ZM_OpMode | Read | ||
| AI | 134 | ZoneModule 1 - Status | ZM1_Status | Read | ||
| AI | 135 | ZoneModule 1 - VAV Supply 1 Actuator Setpoint | ZM1_Sup1Set | Read | ||
| AI | 136 | ZoneModule 1 - VAV Supply 1 Actuator Flow | ZM1_Sup1Flow | Read | ||
| AI | 137 | ZoneModule 1 - VAV Supply 2 Actuator Setpoint | ZM1_Sup2Set | Read | ||
| AI | 138 | ZoneModule 1 - VAV Supply 2 Actuator Flow | ZM1_Sup2Flow | Read | ||
| AI | 139 | ZoneModule 1 - VAV Extract 1 Actuator Setpoint | ZM1_Ext1Set | Read | ||
| AI | 140 | ZoneModule 1 - VAV Extract 1 Actuator Flow | ZM1_Ext1Flow | Read | ||
| AI | 141 | ZoneModule 1 - VAV Heating Actuator Setpoint | ZM1_HeatSet | Read | ||
| AI | 142 | ZoneModule 1 - VAV Heating Actuator Flow | ZM1_HeatFlow | Read | ||
| AI | 143 | ZoneModule 1 - VAV Cooling Actuator Setpoint | ZM1_CoolSet | Read | ||
| AI | 144 | ZoneModule 1 - VAV Cooling Actuator Flow | ZM1_CoolFlow | Read | ||
| AI | 145 | ZoneModule 1 - Room Temperature Value | ZM1_RoomTemp | °C | Read | |
| AI | 146 | ZoneModule 1 - Supply Temperature Value | ZM1_SupTemp | °C | Read | |
| AI | 147 | ZoneModule 1 - Remote Setpoint Offset | ZM1_SetOffset | °C | Read | |
| AI | 148 | ZoneModule 1 - CO2/VOC Value | ZM1_CO2VOC | Read | ||
| AI | 149 | ZoneModule 1 - RH Value | ZM1_RH | %RH | Read | |
| AI | 150 | ZoneModule 2 - Status | ZM2_Status | Read | ||
| AI | 151 | ZoneModule 2 - VAV Supply 1 Actuator Setpoint | ZM2_Sup1Set | Read | ||
| AI | 152 | ZoneModule 2 - VAV Supply 1 Actuator Flow | ZM2_Sup1Flow | Read | ||
| AI | 153 | ZoneModule 2 - VAV Supply 2 Actuator Setpoint | ZM2_Sup2Set | Read | ||
| AI | 154 | ZoneModule 2 - VAV Supply 2 Actuator Flow | ZM2_Sup2Flow | Read | ||
| AI | 155 | ZoneModule 2 - VAV Extract 1 Actuator Setpoint | ZM2_Ext1Set | Read | ||
| AI | 156 | ZoneModule 2 - VAV Extract 1 Actuator Flow | ZM2_Ext1Flow | Read | ||
| AI | 157 | ZoneModule 2 - VAV Heating Actuator Setpoint | ZM2_HeatSet | Read | ||
| AI | 158 | ZoneModule 2 - VAV Heating Actuator Flow | ZM2_HeatFlow | Read | ||
| AI | 159 | ZoneModule 2 - VAV Cooling Actuator Setpoint | ZM2_CoolSet | Read | ||
| AI | 160 | ZoneModule 2 - VAV Cooling Actuator Flow | ZM2_CoolFlow | Read | ||
| AI | 161 | ZoneModule 2 - Room Temperature Value | ZM2_RoomTemp | °C | Read | |
| AI | 162 | ZoneModule 2 - Supply Temperature Value | ZM2_SupTemp | °C | Read | |
| AI | 163 | ZoneModule 2 - Remote Setpoint Offset | ZM2_SetOffset | °C | Read | |
| AI | 164 | ZoneModule 2 - CO2/VOC Value | ZM2_CO2VOC | Read | ||
| AI | 165 | ZoneModule 2 - RH Value | ZM2_RH | %RH | Read | |
| AI | 166 | ZoneModule 3 - Status | ZM3_Status | Read | ||
| AI | 167 | ZoneModule 3 - VAV Supply 1 Actuator Setpoint | ZM3_Sup1Set | Read | ||
| AI | 168 | ZoneModule 3 - VAV Supply 1 Actuator Flow | ZM3_Sup1Flow | Read | ||
| AI | 169 | ZoneModule 3 - VAV Supply 2 Actuator Setpoint | ZM3_Sup2Set | Read | ||
| AI | 170 | ZoneModule 3 - VAV Supply 2 Actuator Flow | ZM3_Sup2Flow | Read | ||
| AI | 171 | ZoneModule 3 - VAV Extract 1 Actuator Setpoint | ZM3_Ext1Set | Read | ||
| AI | 172 | ZoneModule 3 - VAV Extract 1 Actuator Flow | ZM3_Ext1Flow | Read | ||
| AI | 173 | ZoneModule 3 - VAV Heating Actuator Setpoint | ZM3_HeatSet | Read | ||
| AI | 174 | ZoneModule 3 - VAV Heating Actuator Flow | ZM3_HeatFlow | Read | ||
| AI | 175 | ZoneModule 3 - VAV Cooling Actuator Setpoint | ZM3_CoolSet | Read | ||
| AI | 176 | ZoneModule 3 - VAV Cooling Actuator Flow | ZM3_CoolFlow | Read | ||
| AI | 177 | ZoneModule 3 - Room Temperature Value | ZM3_RoomTemp | °C | Read | |
| AI | 178 | ZoneModule 3 - Supply Temperature Value | ZM3_SupTemp | °C | Read | |
| AI | 179 | ZoneModule 3 - Remote Setpoint Offset | ZM3_SetOffset | °C | Read | |
| AI | 180 | ZoneModule 3 - CO2/VOC Value | ZM3_CO2VOC | Read | ||
| AI | 181 | ZoneModule 3 - RH Value | ZM3_RH | %RH | Read | |
| AI | 182 | ZoneModule 4 - Status | ZM4_Status | Read | ||
| AI | 183 | ZoneModule 4 - VAV Supply 1 Actuator Setpoint | ZM4_Sup1Set | Read | ||
| AI | 184 | ZoneModule 4 - VAV Supply 1 Actuator Flow | ZM4_Sup1Flow | Read | ||
| AI | 185 | ZoneModule 4 - VAV Supply 2 Actuator Setpoint | ZM4_Sup2Set | Read | ||
| AI | 186 | ZoneModule 4 - VAV Supply 2 Actuator Flow | ZM4_Sup2Flow | Read | ||
| AI | 187 | ZoneModule 4 - VAV Extract 1 Actuator Setpoint | ZM4_Ext1Set | Read | ||
| AI | 188 | ZoneModule 4 - VAV Extract 1 Actuator Flow | ZM4_Ext1Flow | Read | ||
| AI | 189 | ZoneModule 4 - VAV Heating Actuator Setpoint | ZM4_HeatSet | Read | ||
| AI | 190 | ZoneModule 4 - VAV Heating Actuator Flow | ZM4_HeatFlow | Read | ||
| AI | 191 | ZoneModule 4 - VAV Cooling Actuator Setpoint | ZM4_CoolSet | Read | ||
| AI | 192 | ZoneModule 4 - VAV Cooling Actuator Flow | ZM4_CoolFlow | Read | ||
| AI | 193 | ZoneModule 4 - Room Temperature Value | ZM4_RoomTemp | °C | Read | |
| AI | 194 | ZoneModule 4 - Supply Temperature Value | ZM4_SupTemp | °C | Read | |
| AI | 195 | ZoneModule 4 - Remote Setpoint Offset | ZM4_SetOffset | °C | Read | |
| AI | 196 | ZoneModule 4 - CO2/VOC Value | ZM4_CO2VOC | Read | ||
| AI | 197 | ZoneModule 4 - RH Value | ZM4_RH | %RH | Read | |
| AI | 198 | CVM Phase L1 to neutral (N) voltage [V] | CVMVoltageL1 | V | Read | |
| AI | 199 | CVM Current L1 value [mA] | CVMCurrentL1 | Read | ||
| AI | 200 | CVM Active power L1 [W] | CVMActPowerL1 | W | Read | |
| AI | 201 | CVM Phase L2 to neutral (N) voltage [V] | CVMVoltageL2 | V | Read | |
| AI | 202 | CVM Current value [mA] L2 | CVMCurrentL2 | Read | ||
| AI | 203 | CVM Active power [W] L2 | CVMActPowerL2 | W | Read | |
| AI | 204 | CVM Phase L3 to neutral (N) voltage [V] | CVMVoltageL3 | V | Read | |
| AI | 205 | CVM Current value L3 [mA] | CVMCurrentL3 | Read | ||
| AI | 206 | CVM Active power L3 [W] | CVMActPowerL3 | W | Read | |
| AI | 207 | CVM Active power three phases [W] | CVMActPowerIII | W | Read | |
| AI | 208 | CVM Frequency value [Hz] | CVMFrequency | Hz | Read | |
| AI | 209 | CVM Phase-phase Voltage L1 to L2 [V] | CVMVoltageL1L2 | V | Read | |
| AI | 210 | CVM Phase-phase Voltage L2 to L3 [V] | CVMVoltageL2L3 | V | Read | |
| AI | 211 | CVM Phase-phase Voltage L3 to L1 [V] | CVMVoltageL3L1 | V | Read | |
| AI | 212 | CCVM Cool Phase L1 to neutral (N) voltage [V] | CCVMVoltageL1 | V | Read | |
| AI | 213 | CCVM Cool Current L1 value [mA] | CCVMCurrentL1 | Read | ||
| AI | 214 | CCVM Cool Active power L1 [kW] | CCVMActPowerL1 | W | Read | |
| AI | 215 | CCVM Cool Phase L2 to neutral (N) voltage [V] | CCVMVoltageL2 | V | Read | |
| AI | 216 | CCVM Cool Current L2 value [mA] | CCVMCurrentL2 | Read | ||
| AI | 217 | CCVM Cool Active power L2 [kW] | CCVMActPowerL2 | W | Read | |
| AI | 218 | CCVM Cool Phase L3 to neutral (N) voltage [V] | CCVMVoltageL3 | V | Read | |
| AI | 219 | CCVM Cool Current L3 value [mA] | CCVMCurrentL3 | Read | ||
| AI | 220 | CCVM Cool Active power L3 [kW] | CCVMActPowerL3 | W | Read | |
| AI | 221 | CCVM Cool Active power three phases [W] (Low Byte) | CCVMActPowrIII | W | Read | |
| AI | 222 | CCVM Cool Frequency value [Hz] | CCVMFrequency | Hz | Read | |
| AI | 223 | CCVM Cool Phase-phase Voltage L1 to L2 [V] | CCVMVoltagL1L2 | V | Read | |
| AI | 224 | CCVM Cool Phase-phase Voltage L2 to L3 [V] | CCVMVoltagL2L3 | V | Read | |
| AI | 225 | CCVM Cool Phase-phase Voltage L3 to L1 [V] | CCVMVoltagL3L1 | V | Read | |
| AI | 226 | Actual used Power (kW) Elektrik Heat Battery 1 | El_HT1_ActPower | W | Read | |
| AI | 227 | Actual used Power (kW) Elektrik Heat Battery 2 | El_HT2_ActPower | W | Read | |
| AI | 230 | CVM Active energy three phases [kWh] | CVMActEnergIII | Read | ||
| AI | 231 | CCVM Cool Active energy three phases [kWh] | CCVMActEnerIII | Read | ||
| AI | 232 | Current EfficiencyTemp [1/100C] | ATMP_EfficiencyTemp | °C | Read | |
| AI | 233 | Internal OutDoorTemp [1/100C] | ATMP_OA_SensTemp | °C | Read | |
| AI | 234 | Current SupplyTemp2 [1/100C] | ATMP_SupplyTemp2 | °C | Read | |
| AI | 235 | CVM Current value L1 high byte [mA] | CVMCurrentL1H | Read | ||
| AI | 236 | CVM Active power L1 high byte [W] | CVMActPowerL1H | W | Read | |
| AI | 237 | CVM Current value L2 high byte [mA] | CVMCurrentL2H | Read | ||
| AI | 238 | CVM Active power L2 high byte [W] | CVMActPowerL2H | W | Read | |
| AI | 239 | CVM Current value L3 high byte [mA] | CVMCurrentL3H | Read | ||
| AI | 240 | CVM Active power L3 high byte [W] | CVMActPowerL3H | W | Read | |
| AI | 241 | CVM Active power three phases high byte [W] | CVMActPoweIIIH | W | Read | |
| AI | 242 | CVM Active energy three phases high byte [Wh] | CVMActEnerIIIH | Read | ||
| AI | 243 | CCVM Current 1 value high byte [mA] | CCVMCurrentL1H | Read | ||
| AI | 244 | CCVM Active power 1 high byte [W] | CCVMActPoweL1H | W | Read | |
| AI | 245 | CCVM Current 2 value high byte [mA] | CCVMCurrentL2H | Read | ||
| AI | 246 | CCVM Active power 2 high byte [W] | CCVMActPoweL2H | W | Read | |
| AI | 247 | CCVM Current 3 value high byte [mA] | CCVMCurrentL3H | Read | ||
| AI | 248 | CCVM Active 3 power high byte [W] | CCVMActPoweL3H | W | Read | |
| AI | 249 | CCVM Active power three phases high byte [W] | CCVMActPowIIIH | W | Read | |
| AI | 250 | CCVM Active energy three phases high byte [Wh] | CCVMActEnrIIIH | Read | ||
| AI | 251 | Supply SFPII [Ws/m3 same as J/m3] | AR_SupSFPII | Read | ||
| AI | 252 | Extract SFPII -2 [Ws/m3 same as J/m3] | AR_ExtSFPII | Read | ||
| AI | 253 | Combined SFP [Ws/m3 same as J/m3] High | AHU_FullSFPHigh | Read | ||
| AI | 254 | Combined SFP [Ws/m3 same as J/m3] Low | AHU_FullSFPLow | Read | ||
| AI | 256 | Actual % rel. Huminity Mixed air | Humid_ActRHMix | %RH | Read | |
| AI | 263 | Rel. Humidity Outdoor air | AR_RelHumOutdoor | %RH | Read | |
| AI | 264 | Rel. Humidity Exhaust air | AR_RelHumExhaust | %RH | Read | |
| AI | 265 | Current Temperature OutdoorTempSensor 6040 (External Sens) [1/1 | TTH_ID5_Temp_Average | °C | Read | |
| AI | 266 | Average Outdoorflow-pressure [Pa] | Filt_DynFlowAvr_SA | Pa | Read | |
| AI | 267 | Average Extract/Exhaustflow-pressure [Pa] | Filt_DynFlowAvr_EA | Pa | Read | |
| AI | 268 | Average OA-Filter-pressure [Pa] DYNAMICMODE | Filt_AlrLimDynPa_OA | Pa | Read | |
| AI | 269 | Average EA-Filter-pressure [Pa] DYNAMICMODE | Filt_AlrLimDynPa_EA | Pa | Read | |
| AI | 270 | Current air temperature just before the outdoor coil of the hea | ATMP_HP_OutdCoilTmp | °C | Read | |
| AI | 271 | Average SA-Filter-pressure [Pa] DYNAMICMODE | Filt_AlrLimDynPa_SA | Pa | Read | |
| AI | 272 | Average EA2-Filter-pressure [Pa] DYNAMICMODE | Filt_AlrLimDynPa_EA2 | Pa | Read | |
| AI | 273 | SummerNight Time with Heat Demand [sec] | SNC_Heat_On_Time | s | Read | |
| AI | 274 | Timer for DX-Cool RE-1 ON-Periode [sec] | DX_OnTimerRE1 | s | Read | |
| AI | 275 | Timer for DX-Cool RE-2 ON-Periode [sec] | DX_OnTimerRE2 | s | Read | |
| AI | 276 | Timer for DX-Cool RE-3 ON-Periode [sec] | DX_OnTimerRE3 | s | Read | |
| AI | 277 | Timer for DX-Cool RE-4 ON-Periode [sec] | DX_OnTimerRE4 | s | Read | |
| AI | 278 | Counter for DX-Cool RE-1 starts per hour | DX_RestartCnt1 | Read | ||
| AI | 279 | Current Heat2 WaterBatt Temp [1/100C] Coil/Return | ATMP_HT2_CoilRT | °C | Read | |
| AI | 280 | Counter for DX-Cool RE-3 starts per hour | DX_RestartCnt3 | Read | ||
| AI | 281 | Counter for DX-Cool RE-4 starts per hour | DX_RestartCnt4 | Read | ||
| AI | 282 | Timer for DX-Cool K1 Restart-Periode | DX_RestartTim1 | s | Read | |
| AI | 283 | Timer for DX-Cool K2 Restart-Periode | DX_RestartTim2 | s | Read | |
| AI | 284 | Timer for DX-Cool K3 Restart-Periode | DX_RestartTim3 | s | Read | |
| AI | 285 | Timer for DX-Cool K14Restart-Periode | DX_RestartTim4 | s | Read | |
| AI | 286 | Filter actual alarmstatus for OA-filter [1/100%] | Filt_PrcStat_OA | % | Read | |
| AI | 287 | Filter actual alarmstatus for EA-filter [1/100%] | Filt_PrcStat_EA | % | Read | |
| AI | 288 | OA Filter pressure for new-filter at actual flow [Pa] | Filt_TabValPa_OA | Pa | Read | |
| AI | 289 | EA Filter pressure for new-filter at actual flow [Pa] | Filt_TabValPa_EA | Pa | Read | |
| AI | 290 | Condenser Valve Power | ROHCondPower | % | Read | |
| AI | 291 | Voltage level, to condenser valve | ROHCondOutVDC | V | Read | |
| AI | 292 | Shunt Valve Power | ROHShuntPower | % | Read | |
| AI | 293 | Voltage level, to shunt valve | ROHShuntOutVDC | V | Read | |
| AI | 294 | Output to SteamHuminifier [1/1000 V] | Humid_OutVDC | V | Read | |
| AI | 295 | Timer delayed heat 2 | Ht2DelayTimer | s | Read | |
| AI | 296 | Average press Rotary EXC Flow Measure, Extract channel | REXCPressAvg | Pa | Read | |
| AI | 297 | HeatPump power used when heating is demanded. Otherwise CoolPow | HP_HeatPower | % | Read | |
| AI | 298 | Supply air fan 2 Type | SA2_Slave_Size | Read | ||
| AI | 299 | Supply air fan 2 Software Ver [1/100] | SA2_Slave_MOC_SW_Ver | Read | ||
| AI | 300 | Supply air fan 2 Boot Software / HW Ver [1/100] | SA2_Slave_AOC_SW_Ver | Read | ||
| AI | 301 | Supply air fan 2 procent output [1/100%] | SA2_Slave_PercentOut | % | Read | |
| AI | 302 | Supply air fan 2 actual RPM [RPM] | SA2_Slave_RPM_Out | Read | ||
| AI | 303 | Supply air fan 2 actual current output [1/100mA] | SA2_Slave_I_Out | A | Read | |
| AI | 304 | Supply air fan 2 actual power input [Watt] | SA2_Slave_Power_In | W | Read | |
| AI | 305 | Supply air fan 2 actual running time [minutes] | SA2_Slave_DriftMinute | min | Read | |
| AI | 306 | Supply air fan 2 actual running time [days] | SA2_Slave_DriftDays | Read | ||
| AI | 307 | Supply air fan 2 Percent to Fan | SA2_Slave_PercentSet | % | Read | |
| AI | 308 | Extract air fan 2 Type | EA2_Slave_Size | Read | ||
| AI | 309 | Extract air fan 2 Software Ver [1/100] | EA2_Slave_MOC_SW_Ver | Read | ||
| AI | 310 | Extract air fan 2 Boot Software / HW Ver [1/100] | EA2_Slave_AOC_SW_Ver | Read | ||
| AI | 311 | Extract air fan 2 procent output [1/100%] | EA2_Slave_PercentOut | % | Read | |
| AI | 312 | Extract air fan 2 actual RPM [RPM] | EA2_Slave_RPM_Out | Read | ||
| AI | 313 | Extract air fan 2 actual current output [1/100mA] | EA2_Slave_I_Out | A | Read | |
| AI | 314 | Extract air fan 2 actual power input [Watt] | EA2_Slave_Power_In | W | Read | |
| AI | 315 | Extract air fan 2 actual running time [minutes] | EA2_Slave_DriftMinute | min | Read | |
| AI | 316 | Extract air fan 2 actual running time [days] | EA2_Slave_DriftDays | Read | ||
| AI | 317 | Extract air fan 2 Percent to Fan | EA2_Slave_PercentSet | % | Read | |
| AI | 318 | Supply air fan Type | SA_Master_Size | Read | ||
| AI | 319 | Supply air fan Software Ver [1/100] | SA_Master_MOC_SW_Ver | Read | ||
| AI | 320 | Supply air fan Boot Software Ver [1/100] | SA_Master_AOC_SW_Ver | Read | ||
| AI | 321 | Supply air fan procent ouput [1/100%] | SA_Master_PercentOut | % | Read | |
| AI | 322 | Supply air fan actual RPM [RPM] | SA_Master_RPM_Out | Read | ||
| AI | 323 | Supply air fan actual current output [1/100mA] | SA_Master_I_Out | A | Read | |
| AI | 324 | Supply air fan actual running time [minutes] | SA_Master_DriftMinute | min | Read | |
| AI | 325 | Supply air fan actual running time [days] | SA_Master_DriftDays | Read | ||
| AI | 326 | Supply air fan Percent to Fan | SA_Master_PercentSet | % | Read | |
| AI | 327 | Extract air fan Boot Software Ver [1/100] | EA_Master_AOC_SW_Ver | Read | ||
| AI | 328 | Extract air fan procent ouput [1/100%] | EA_Master_PercentOut | % | Read | |
| AI | 329 | Extract air fan actual RPM [RPM] | EA_Master_RPM_Out | Read | ||
| AI | 330 | Extract air fan actual current output [1/100mA] | EA_Master_I_Out | A | Read | |
| AI | 331 | Extract air fan actual running time [minutes] | EA_Master_DriftMinute | min | Read | |
| AI | 332 | Extract air fan actual running time [days] | EA_Master_DriftDays | Read | ||
| AI | 333 | Extract air fan Percent to Fan | EA_Master_PercentSet | % | Read | |
| AI | 334 | Extract air fan Type | EA_Master_Size | Read | ||
| AI | 335 | Extract air fan Software Ver [1/100] | EA_Master_MOC_SW_Ver | Read | ||
| AI | 336 | SA filter restime before filtershift alarm activated | FM_SF_SA_Timer_Rest_d | Read | ||
| AI | 337 | EA filter 2 restime before filtershift alarm activated | FM_SF_EA2_Timer_Rest_d | Read | ||
| AI | 338 | Extract air temperature after Heatpump value [1/100C] | ATMP_HP_ExtAirTemp | °C | Read | |
| AI | 339 | Daikin:Suction air temperature | DaikSucTmpSet | °C | Read | |
| AI | 341 | Drives Compressor Drive Type | DC_Compressor_DriveType | Read | ||
| AI | 342 | Drives Compressor AOC SW version | DC_Compressor_AOCSWVer | Read | ||
| AI | 343 | Drives Compressor MOC SW version | DC_Compressor_MOCSWVer | Read | ||
| AI | 344 | Drives Compressor PrcOut | DC_Compressor_PercentOut | % | Read | |
| AI | 345 | Drives Compressor RPMOut | DC_Compressor_RPM_Out | Read | ||
| AI | 346 | Drives Compressor Power In (filtered) | DC_Compressor_Power_In | W | Read | |
| AI | 347 | Drives Compressor Operation Day | DC_Compressor_DriftDays | Read | ||
| AI | 348 | Cross-EXC pressure average, depent on flow | EXC_FlwAvr | Pa | Read | |
| AI | 351 | Consumed kWh High Note!: Values are calculated as (High byte) | CVMConActEner3PhkWHH | Read | ||
| AI | 352 | Consumed kWh Low Note!: Values are calculated as (High byte) x | CVMConActEner3PhkWH | Read | ||
| AI | 353 | Consumed Wh High Note!: Values are calculated as (High byte) x | CVMConActEner3PhWHH | Read | ||
| AI | 354 | Consumed Wh Low Note!: Values are calculated as (High byte) x | CVMConActEner3PhWH | Read | ||
| AI | 355 | Consumed [kWh] High. Note: Values are calculated as (High byte) | CCVMConActEner3PhkWHH | Read | ||
| AI | 356 | Consumed [kWh] Low. Note: Values are calculated as (High byte) | CCVMConActEner3PhkWH | Read | ||
| AI | 357 | Consumed [Wh] High. Note: Values are calculated as (High byte) | CCVMConActEner3PhWHH | Read | ||
| AI | 358 | Consumed [Wh] Low. Note: Values are calculated as (High byte) x | CCVMConActEner3PhWH | Read | ||
| AI | 365 | Supply air fan actual power input [Watt] | SA_Master_Power_In | W | Read | |
| AI | 366 | Extract air fan actual power input [Watt] | EA_Master_Power_In | W | Read | |
| AI | 390 | Display temperature, not in regulation PH Inlet | ATMP_PH_Inlet | °C | Read | |
| AI | 391 | Display temperature, not in regulation HT1 Inlet | ATMP_HT1_Inlet | °C | Read | |
| AI | 392 | Display temperature, not in regulation HT2 Inlet | ATMP_HT2_Inlet | °C | Read | |
| AI | 393 | Display temperature, not in regulation Cmb HT Inlet | ATMP_CMB_Inlet | °C | Read | |
| AI | 450 | Outdoor-Damper setpoint in percent | BDInletSetPrc | % | Read | |
| AI | 451 | Outdoor-Damper actual position in percent | BDInletRelPos | % | Read | |
| AI | 452 | Exhaust-Damper setpoint in percent | BDExhauSetPrc | % | Read | |
| AI | 453 | Exhaust-Damper actual position in percent | BDExhauRelPos | % | Read | |
| AI | 454 | Exhaust-Backup-Damper setpoint in percent | BDExhBakSetPrc | % | Read | |
| AI | 455 | Exhaust-Backup-Damper actual position in percent | BDExhBakRelPos | % | Read | |
| AI | 456 | Recirculation-Damper setpoint in percent | BDRecSetPrc | % | Read | |
| AI | 457 | Recirculation-Damper actual position in percent | BDRecRelPos | % | Read | |
| AI | 458 | CrossByPass-Damper setpoint in percent | BDByPasSetPrc | % | Read | |
| AI | 459 | CrossByPass-Damper actual position in percent | BDByPasRelPos | % | Read | |
| AI | 460 | Drying-Damper setpoint in percent | BDDryinSetPrc | % | Read | |
| AI | 461 | Drying-Damper actual position in percent | BDDryinRelPos | % | Read | |
| AI | 462 | Supply-Damper setpoint in percent | BDSASetPrc | % | Read | |
| AI | 463 | Supply-Damper actual position in percent | BDSARelPos | % | Read | |
| AI | 464 | Supply-Backup-Damper setpoint in percent | BDSupBakSetPrc | % | Read | |
| AI | 465 | Supply-Backup-Damper actual position in percent | BDSupBakRelPos | % | Read | |
| AI | 466 | SmokeEvac-Damper setpoint in percent | BDSmokeSetPrc | % | Read | |
| AI | 467 | SmokeEvac-Damper actual position in percent | BDSmokeRelPos | % | Read | |
| AI | 468 | SmokeByPass-Damper setpoint in percent | BDSMBPSetPrc | % | Read | |
| AI | 469 | SmokeByPass-Damper actual position in percent | BDSMBPRelPos | % | Read | |
| AI | 470 | Heater 1 Setpoint in percent | BVHeat1SetPrc | % | Read | |
| AI | 471 | Heater 1 Valve actual position in percent | BVHeat1RelPos | % | Read | |
| AI | 472 | Cooler Setpoint in percent | BVCoolSetPrc | % | Read | |
| AI | 473 | Cooler Valve actual position in percent | BVCoolRelPos | % | Read | |
| AI | 474 | Heater 2 Setpoint in percent | BVHeat2SetPrc | % | Read | |
| AI | 475 | Heater 2 Valve actual position in percent | BVHeat2RelPos | % | Read | |
| AI | 476 | FluidExchanger Setpoint in percent | BVFlExcSetPrc | % | Read | |
| AI | 477 | FluidExchanger Valve actual position in percent | BVFlExcRelPos | % | Read | |
| AI | 478 | Preheater Setpoint in percent | BVPrHeatSetPrc | % | Read | |
| AI | 479 | Preheater Valve actual position in percent | BVPrHeatRelPos | % | Read | |
| AI | 480 | CombiCoil Setpoint in percent | BVCombSetPrc | % | Read | |
| AI | 481 | CombiCoil Valve actual position in percent | BVCombRelPos | % | Read | |
| AI | 482 | Opt7 Setpoint in percent | BVOpt7SetPrc | % | Read | |
| AI | 483 | Opt7 Valve actual position in percent | BVOpt7RelPos | % | Read | |
| AI | 484 | Extract-Damper setpoint in percent | BDExtSetPrc | % | Read | |
| AI | 485 | Extract-Damper actual position in percent | BDExtRelPos | % | Read | |
| AV | 1 | Manual Operation Mode [GUI] | OL_Manual_Modes | Write | ||
| AV | 2 | Fan Regulation Mode | AR_MtrRegMode | Write | ||
| AV | 14 | Offset for Sup/Ext Motor Slave and CO2 Reg [1/100%] | AR_MtrRegOffset | % | Write | |
| AV | 19 | AR_CO2 Regulator MinFlow [l/s] | AR_CO2_MinFlow | l/s | Write | |
| AV | 20 | AR_CO2 Regulator MaxFlow [l/s] | AR_CO2_MaxFlow | l/s | Write | |
| AV | 21 | AR_CO2 Regulator SupFlow Offset [1/100%] | AR_CO2_SupFlwOffs | % | Write | |
| AV | 22 | AR_CO2 ppm AlarmLimet Set [ppm] | AR_CO2_AlrLimit | Write | ||
| AV | 23 | AR_CO2 Regulator P-Band [ppm] | AR_CO2_PB | Write | ||
| AV | 24 | AR_CO2 Regulator I-Time [sec] | AR_CO2_I_Time | s | Write | |
| AV | 25 | FAN-Opt Supply Regulator MinFlow [l/s] | FANOpt_SA_MinFlow | l/s | Write | |
| AV | 26 | FAN-Opt Supply Regulator MaxFlow [l/s] | FANOpt_SA_MaxFlow | l/s | Write | |
| AV | 27 | FAN-Opt Extract Regulator MinFlow [l/s] | FANOpt_EA_MinFlow | l/s | Write | |
| AV | 28 | FAN-Opt Extract Regulator MaxFlow [l/s] | FANOpt_EA_MaxFlow | l/s | Write | |
| AV | 29 | FAN-Opt Regulator ExtFlow Offset [1/100%] | FANOpt_EA_FlwOffs | % | Write | |
| AV | 30 | Supply Motor Reg I-Time Set [Sec] | AR_SupMtr_I_Time | s | Write | |
| AV | 31 | Extract Motor Reg I-Time Set [Sec] | AR_ExtMtr_I_Time | s | Write | |
| AV | 32 | User Supply Motor Percent Set at Fire [%] | AH_SA_FlowFireSet | % | Write | |
| AV | 33 | User Extract Motor Percent Set at Fire [%] | AH_EA_FlowFireSet | % | Write | |
| AV | 34 | HiSpeed AfterRun TimeOut Set [min] | OL_HS_AfterRun_SetTimer | min | Write | |
| AV | 35 | FlowOutTempComp PercentSet [1/100%] | AR_FlwTmpCmpSet | % | Write | |
| AV | 36 | FlowOutTempComp StartTempSet [1/100C] | AR_FlwTmpCmpStart | °C | Write | |
| AV | 37 | FlowOutTempComp StopTempSet [1/100C] | AR_FlwTmpCmpStop | °C | Write | |
| AV | 38 | Actual year | RTC_Year_Uset | Write | ||
| AV | 39 | Actual month | RTC_Month_Uset | Write | ||
| AV | 40 | Actual date | RTC_Date_Uset | Write | ||
| AV | 41 | Actual hour | RTC_Hour_Uset | h | Write | |
| AV | 42 | Actual minutes | RTC_Minute_Uset | min | Write | |
| AV | 43 | Actual seconds | RTC_Second_Uset | s | Write | |
| AV | 44 | Extended Drift Start Day (0-Mon..6-Sun) | ExtDrfStartDay | Write | ||
| AV | 45 | Extended Drift Start Minute (Hour*60+Min) | ExtDrfStartMin | min | Write | |
| AV | 46 | Extended Drift Stop Day (0-Mon..6-Sun) | ExtDrfStopDay | Write | ||
| AV | 47 | Extended Drift Stop Minute (Hour*60+Min) | ExtDrfStopMin | min | Write | |
| AV | 50 | Supply LoSpeed DuctPressure Set [Pa] | AR_SA_DuctPaLoSet | Pa | Write | |
| AV | 51 | Supply MediumSpeed DuctPressure Set [Pa] | AR_SA_DuctPaMedSet | Pa | Write | |
| AV | 52 | Supply HiSpeed DuctPressure Set [Pa] | AR_SA_DuctPaHiSet | Pa | Write | |
| AV | 53 | Extract/Exhaust LoSpeed DuctPressure Set [Pa] | AR_EA_DuctPaLoSet | Pa | Write | |
| AV | 54 | Extract/Exhaust MediumSpeed DuctPressure Set [Pa] | AR_EA_DuctPaMedSet | Pa | Write | |
| AV | 55 | Extract/Exhaust HiSpeed DuctPressure Set [Pa] | AR_EA_DuctPaHiSet | Pa | Write | |
| AV | 56 | User Supply Flow-LoSpeedSet [l/s] | AR_SA_LoSpeedFlowSet | l/s | Write | |
| AV | 57 | User Supply Flow-MedSpeedSet [l/s] | AR_SA_MedSpeedFlowSet | l/s | Write | |
| AV | 58 | User Supply Flow-HiSpeedSet [l/s] | AR_SA_HiSpeedFlowSet | l/s | Write | |
| AV | 59 | User Extract/Exhaust Flow-LoSpeedSet [l/s] | AR_EA_LoSpeedFlowSet | l/s | Write | |
| AV | 60 | User Extract/Exhaust Flow-MedSpeedSet [l/s] | AR_EA_MedSpeedFlowSet | l/s | Write | |
| AV | 61 | User Extract/Exhaust Flow-HiSpeedSet [l/s] | AR_EA_HiSpeedFlowSet | l/s | Write | |
| AV | 62 | Supply Motor Lowspeed [1/100%], FFS | AR_SA_FixLoPrcSet | % | Write | |
| AV | 63 | Supply Motor Mediumspeed [1/100%], FFS | AR_SA_FixMedPrcSet | % | Write | |
| AV | 64 | Supply Motor Highspeed [1/100%], FFS | AR_SA_FixHiPrcSet | % | Write | |
| AV | 65 | Extract/Exhaust Motor Lowspeed [1/100%], FFS | AR_EA_FixLoPrcSet | % | Write | |
| AV | 66 | Extract/Exhaust Motor Mediumspeed [1/100%], FFS | AR_EA_FixMedPrcSet | % | Write | |
| AV | 67 | Extract/Exhaust Motor Highspeed [1/100%], FFS | AR_EA_FixHiPrcSet | % | Write | |
| AV | 68 | AR_CO2 Regulator User SetPoint for Lo timer Periode (HI AR_CO2 | AR_CO2_UsetLP | Write | ||
| AV | 69 | AR_CO2 Regulator User SetPoint for Medium timer Periode(Med AR_ | AR_CO2_UsetMP | Write | ||
| AV | 70 | AR_CO2 Regulator User SetPoint for Hi timer Periode(LO AR_CO2 V | AR_CO2_UsetHP | Write | ||
| AV | 71 | Extract/Exhaust Min Flow for DuctReg [l/s] | AR_EA_DuctMinFlowSet | l/s | Write | |
| AV | 72 | Extract/Exhaust Max Flow for DuctReg [l/s] | AR_EA_DuctMaxFlowSet | l/s | Write | |
| AV | 73 | Supply Min Flow for DuctReg [l/s] | AR_SA_DuctMinFlowSet | l/s | Write | |
| AV | 74 | Supply Max Flow for DuctReg [l/s] | AR_SA_DuctMaxFlowSet | l/s | Write | |
| AV | 75 | TempDiff2 between Set/Meas Alarm Limit SA [1/100C] | SupTempDif2Alr | Write | ||
| AV | 76 | TempDiff between Set/Meas Alarm Limit SA [1/100C] | SupTempDiffAlr | Write | ||
| AV | 77 | P-Band for Supply TempReg heating [1/100C] | SupTempHeatPB | Write | ||
| AV | 78 | SA I-Time for Reg on Heat2 Out [sec] | TR_SupTempHeat2IT | s | Write | |
| AV | 79 | SA I-Time for supply tempReg Heat pump while heating [sec] | TR_SupTempHP_IT | s | Write | |
| AV | 82 | Huminifier Supply Setpoint [1/100%] RH | Humid_SupSet | %RH | Write | |
| AV | 102 | Current external Modbus OutDoorTemp [1/100C] | STMP_MBT_OutDoor | °C | Write | |
| AV | 103 | Current external Modbus RoomTemp [1/100C] | STMP_MBT_Room1 | °C | Write | |
| AV | 104 | Customer set of alarmlimit modbus outdoorsensor min | TR_AlrLimOA_MBT_Min | °C | Write | |
| AV | 105 | Customer set of alarmlimit modbus outdoorsensor max | TR_AlrLimOA_MBT_Max | °C | Write | |
| AV | 106 | Customer set of alarmlimit modbus roomsensor min | TR_AlrLimRoomMin | °C | Write | |
| AV | 107 | Customer set of alarmlimit modbus roomsensor max | TR_AlrLimRoomMax | °C | Write | |
| AVmin | 108 | BMS-modes only avalable after activation of pysical input 'Oper | OL_BMS_Ctrl_Modes | Write | ||
| AV | 133 | Temp-Regulationmode0-Sup, 1-Ext, 2-Room, 3-Sup/Ext -Diff | AHU_TempRegMode | Write | ||
| AVmin | 134 | TempSet for actual RegMode [1/100C] | TR_TempRegSet | °C | Write | |
| AV | 135 | Min Allowed SupplyTemp [1/100C] | STMP_SupTempMinSet | °C | Write | |
| AV | 136 | Max Allowed SupplyTemp [1/100C] | STMP_SupTempMaxSet | °C | Write | |
| AV | 137 | TempDiff Set between Extract/Supply TempRegMode = 3 | STMP_SupTempDiffSet | °C | Write | |
| AV | 140 | SA I-Time for Reg on CoolOut [sec] | TR_SupTempCool_IT | s | Write | |
| AV | 141 | SA I-Time for Reg on EXC Out [sec] | TR_SupTempEXC_IT | s | Write | |
| AV | 142 | SA I-Time for Reg on Heat Out [sec] | TR_SupTempHeat_IT | s | Write | |
| AV | 143 | SA I-Time for SupTempReg Flow DownReg Out [sec] | TR_SupTempDnRegIt | s | Write | |
| AV | 144 | TempDiff between Set/Meas Alarm Limit EA [1/100C] | STMP_ExtTempDiffAlr | °C | Write | |
| AV | 145 | P-Band for Extract TempReg heating [1/100C] | ExtTempHeatPB | Write | ||
| AV | 146 | EA I-Time for Reg on CoolOut [sec] | TR_ExtTempCool_It | s | Write | |
| AV | 147 | EA I-Time for Reg on EXC Out [sec] | TR_ExtTempEXC_It | s | Write | |
| AV | 148 | EA I-Time for Reg on Heat Out [sec] | TR_ExtTempHeat_It | s | Write | |
| AV | 149 | EA I-Time for ExtTempReg Flow DownReg Out [sec] | TR_ExtTempDnRegIt | s | Write | |
| AV | 150 | Sum/Wint-TempComp Winter Lo OutDoor TempSet [1/100C] | SWTC_WintX1 | °C | Write | |
| AV | 151 | Sum/Wint-TempComp Winter Hi OutDoor TempSet [1/100C] | SWTC_WintX2 | °C | Write | |
| AV | 152 | Sum/Wint-TempComp Summer Lo OutDoor TempSet [1/100C] | SWTC_SumX1 | °C | Write | |
| AV | 153 | Sum/Wint-TempComp Summer Hi OutDoor TempSet [1/100C] | SWTC_SumX2 | °C | Write | |
| AV | 154 | Sum/Wint-TempComp Winter compensation [1/100C] | SWTCWinComVal | Write | ||
| AV | 155 | Sum/Wint-TempComp Summer compensation [1/100C] | SWTCSumComVal | Write | ||
| AV | 156 | Summer/Winter Mode: 0 - 4 | SW_Mode | Write | ||
| AV | 157 | OutdoorTemp for start WinterMode (SW_Mode = 1) | SW_OutWinterON | °C | Write | |
| AV | 158 | OutdoorTemp for start SummerMode (SW_Mode = 1) | SW_OutSummerON | °C | Write | |
| AV | 159 | Month for Start WinterMode (SW_Mode = 2) | SW_MonthWintON | Write | ||
| AV | 160 | Date for Start WinterMode (SW_Mode = 2) | SW_DateWintON | Write | ||
| AV | 161 | Month for Start SummerMode (SW_Mode = 2) | SW_MonthSumON | Write | ||
| AV | 162 | Date for Start SummerMode (SW_Mode = 2) | SW_DateSumON | Write | ||
| AV | 163 | StartTemp for Nightheat Function [1/100 C] | NH_Recirce_StartTmp | °C | Write | |
| AV | 164 | StopTemp for Nightheat Function [1/100 C] | NH_Recirce_StopTmp | °C | Write | |
| AV | 165 | SupplyTempSet for Internal FireAlr [1/100C] | AH_SA_Temp_InternFireAlr | °C | Write | |
| AV | 166 | ExtractTempSet for Internal FireAlr [1/100C] | AH_EA_Temp_InternFireAlr | °C | Write | |
| AV | 167 | Cool-FlowForce Percent Set [1/100 %] | CL_Cool_FlwForcePc | % | Write | |
| AV | 168 | Min OutDoorTemp for CoolAgg. Active | CL_Cool_OutTmpMin | °C | Write | |
| AV | 169 | Min SupplyTemp for Cool (Used for RoomReg) | CL_Cool_SupMinTmp | °C | Write | |
| AV | 170 | SummerNight Ext/Room Temp Start [1/100C] | SNC_EATempStart | °C | Write | |
| AV | 171 | SummerNight Ext/Room Temp Stop [1/100C] | SNC_EA_TempStop | °C | Write | |
| AV | 172 | SummerNight OutDoor Temp Start [1/100C] | SNC_OA_TempStart | °C | Write | |
| AV | 173 | SummerNight SupTemp Reg Set [1/100C] | SNC_SA_TempSet | °C | Write | |
| AV | 174 | SummerNight StartTime [Min] 20:00 - 02-00, in server checked | SNC_StartTime | min | Write | |
| AV | 175 | SummerNight StopTime [Min] 03:00 - 08:00, in server checked | SNC_StopTime | min | Write | |
| AV | 176 | Min ExhaustTempSet for Cross EXC [1/100C] | CExcDeIceTemp | °C | Write | |
| AV | 177 | P-Band for BypaasReg for Cross EXC [1/100C] | CExcDeIceTempP | Write | ||
| AV | 178 | Fluid EXC PumpFunc: 0 - 3 | BattEXC_PumpFc | Write | ||
| AV | 179 | Fluid EXC PumpStartTemp. Is used | BattEXC_PumpSt | °C | Write | |
| AV | 180 | Fluid EXC TempDiff Alarm Set Alarm | BattEXC_AlrSet | °C | Write | |
| AV | 181 | HWB1 Upstart PowerSet [1/100%] | HW1_UpStartPow | % | Write | |
| AV | 182 | HeatWaterBatt 1 PumpFunc: 0 - 3 | HW1_PumpFunc | Write | ||
| AV | 183 | HeatWaterBatt 1 PumpStartTemp. Is used together with WaterPumpF | HW1_PmpStartTmp | °C | Write | |
| AV | 184 | SetVal for HWB1 AntiFrost Reg when Agg. = Stop [1/100C] | HW1_FrzStopSet | °C | Write | |
| AV | 185 | SetVal for HWB1 AntiFrost Reg when Agg. = Drift [1/100C | HW1_FrzDriftSet | °C | Write | |
| AV | 186 | HW1 P-Band for AntiFrost Reg [1/100C] | HW1FreezePB | Write | ||
| AV | 187 | SetVal for HWB1 AntiFrost TempAlarm [1/100C] | HW1_FrzAlrTpSet | °C | Write | |
| AV | 188 | CoolWater PumpFunc: 0 - 3 | CL_CW_PumpFunc | Write | ||
| AV | 189 | CoolWaterBatt PumpStartTemp. Is used together with WaterPumpFun | CL_CW_PmpStartTmp | °C | Write | |
| AV | 190 | Filter Pressure Alr Limit for OA-Filter (static mode) | Filt_StatAlr_OA | Pa | Write | |
| AV | 191 | Filter Pressure Alr Limit for EA-Filter (static mode) | Filt_StatAlr_EA | Pa | Write | |
| AV | 192 | Filter Pressure Alr Limit for OA-Filter (dynamic mode) | Filt_DynAlrSetPrc_OA | % | Write | |
| AV | 193 | Filter Pressure Alr Limit for EA-Filter (dynamic mode) | Filt_DynAlrSetPrc_EA | % | Write | |
| AV | 194 | Alarm Mail Config: 0 - Mail are not send 1 - Mail on A-Alarm 2 | Alr_MailSetup | Write | ||
| AV | 195 | UserRE Function: 0 B-Alarm 1 Lo Speed indicator 2 Hi Speed indi | AHU_UserAlr_RE_Func | Write | ||
| AV | 196 | HWB2 Upstart PowerSet [1/100%] | HW2UpStartPow | % | Write | |
| AV | 197 | HWB 2 PumpFunc: 0 - 3 | HW2PumpFunc | Write | ||
| AV | 198 | HWB 2 PumpFunc start Temperature | HW2PmpStartTmp | °C | Write | |
| AV | 199 | SetVal for HWB2 AntiFrost Reg when Agg. = Stop [1/100C] | HW2FrzStopSet | °C | Write | |
| AV | 200 | SetVal for HWB2 AntiFrost Reg when Agg. = Drift [1/100C] | HW2FrzDriftSet | °C | Write | |
| AV | 201 | HW2 P-Band for AntiFrost Reg [1/100C] | HW2FreezePB | Write | ||
| AV | 202 | SetVal for HWB2 AntiFrost TempAlarm [1/100C] | HW2FrzAlrTpSet | °C | Write | |
| AV | 203 | Setpoint Preheater | PH_HeatSet | °C | Write | |
| AV | 204 | PreHeater SetVal for AntiFrost TempAlarm [1/100C] | PH_MinAlrFrz | °C | Write | |
| AV | 205 | PreHeater SetVal for AntiFrost Reg when Agg. = Stop [1/100C] Pr | PH_StandbyTmp | °C | Write | |
| AV | 206 | Preheater Heatpower Percent under startup [1/100%] | PH_StartPrc | % | Write | |
| AV | 207 | Pre-heating coil P-band for frost protection control [1/100°C] | PHeatFrzPB | Write | ||
| AV | 208 | Preheat PumpStart OutDoorTemp. Is used together with | STMP_PHPmpStTmpH | °C | Write | |
| AV | 209 | SetVal for Preheat AntiFrost Reg when Agg. = Drift [1/100C] Hea | STMP_PHFrzDrSetH | °C | Write | |
| AV | 210 | Mode for PumpFunc: 0 - 3 | PH_PumpMode | Write | ||
| AV | 211 | Min OutDoorTemp for CoolAgg. Relay 1 Active | DXOutTempMin1 | °C | Write | |
| AV | 212 | Min OutDoorTemp for CoolAgg. Relay 2 Active | DXOutTempMin2 | °C | Write | |
| AV | 213 | Min OutDoorTemp for CoolAgg. Relay 3 Active | DXOutTempMin3 | °C | Write | |
| AV | 214 | Min OutDoorTemp for CoolAgg. Relay 4 Active | DXOutTempMin4 | °C | Write | |
| AV | 215 | Min air temp at outdoor coil for HeatPump operate Relay1 | STMP_HP_MinOpTemp1 | °C | Write | |
| AV | 216 | Min air temp at outdoor coil for HeatPump operate Relay2 | STMP_HP_MinOpTemp2 | °C | Write | |
| AV | 217 | Min air temp at outdoor coil for HeatPump operate Relay3 | STMP_HP_MinOpTemp3 | °C | Write | |
| AV | 218 | Min air temp at outdoor coil for HeatPump operate Relay4 | STMP_HP_MinOpTemp4 | °C | Write | |
| AV | 219 | Fluid EXC SetVal for AntiFrost Reg when Agg. = Stop [1/100C] | BattEXCFrzStop | °C | Write | |
| AV | 220 | Fluid EXC SetVal for AntiFrost Reg when Agg. = Drift [1/100C] | BattEXCFrzDrf | °C | Write | |
| AV | 221 | Fluid EXC P-Band for AntiFrost Reg [1/100C] | BattEXCFrzePB | Write | ||
| AV | 222 | Fluid EXCSetVal for AntiFrost TempAlarm [1/100C] | BattEXCFrzASet | °C | Write | |
| AV | 223 | Extern Signal Greenzone, Supply | FANOpt_SA_GZ_An_In | % | Write | |
| AV | 224 | Extern Signal Greenzone, Extract | FANOpt_EA_GZ_An_In | % | Write | |
| AV | 225 | HeatWater VDC out function(Out 12): 0->0-10V, 1->2-10V | HW12_VDCOutFunc | Write | ||
| AV | 226 | Pressure percent over calibration | REXDeIcePerc | % | Write | |
| AV | 227 | Stop temperature freshair cooling | STMP_NO_FAirCoolBlk | °C | Write | |
| AV | 228 | Stop cooling over roomtemperature | CL_NO_CStopRTemp | °C | Write | |
| AV | 229 | Heat2 limiting type 1Room, 2 Outdoor | Ht2LimitTyp | Write | ||
| AV | 230 | Startdifference temperature | HT2StLimRTemp | Write | ||
| AV | 231 | Stepsize limiting roomtemp | Ht2StLimRPer | % | Write | |
| AV | 232 | DownCounter for HeatStart allowed [sec] | Ht2StLimOTemp | °C | Write | |
| AV | 233 | Offset in % of Flow if Heat2 is on | Ht2FlowOffset | % | Write | |
| AV | 234 | Timeset delayed Heat 2 | HT2_SetDelayStartTime | s | Write | |
| AV | 235 | Set Change Airflow Recirce | TR_RecFlowShift | Write | ||
| AV | 236 | Temperature for start with open damper | STMP_RecClosDAStart | °C | Write | |
| AV | 237 | Timeset for CO2 DX-Cooling-Aggregate from 0 ..100% | ROHRiseT100 | s | Write | |
| AV | 238 | SA SummerNight Motor percent Set | SNC_SupCoolFlw | l/s | Write | |
| AV | 239 | EA SummerNight Motor Flow Set | SNC_ExtCoolFlw | l/s | Write | |
| AV | 240 | SA SummerNight Motor Flow Set | SNC_SupCoolPa | Pa | Write | |
| AV | 241 | EA SummerNight Motor Press Set | SNC_ExtCoolPa | Pa | Write | |
| AV | 242 | SA SummerNight Motor Press Set | SNC_SupCoolPrc | % | Write | |
| AV | 243 | EA SummerNight Motor percent Set | SNC_ExtCoolPrc | % | Write | |
| AV | 244 | SummerNight Motor percent Set | SNC_SlvOffsPrc | % | Write | |
| AV | 248 | AR_CO2 Max Value Mod Rec/Rema1000 Mode | AR_CO2_MaxModRec | Write | ||
| AV | 249 | AR_CO2 Min Value Mod Rec/Rema1000 Mode | AR_CO2_MinModRec | Write | ||
| AV | 250 | Setpoint % Humidity Extract RH, Dehumidity | DehumSet_RH | %RH | Write | |
| AV | 257 | Min FreshAir part in percent | AR_REC_MinFreshAir | % | Write | |
| AV | 258 | Filter Pressure Alr Limit for SA-Filter (static mode) | Filt_StaAlr_SA | Pa | Write | |
| AV | 259 | Filter Pressure Alr Limit for EA-Filter2 (static mode) | Filt_StaAlr_EA2 | Pa | Write | |
| AV | 260 | Filter Pressure Alr Limit for SA-Filter (dynamic mode) | Filt_DynAlrSetPrc_SA | % | Write | |
| AV | 261 | Filter Pressure Alr Limit for EA-Filter2 (dynamic mode) | Filt_DynAlrSetPrc_EA2 | % | Write | |
| AV | 262 | ZoneModule 1 - Room Temperature Setpoint | ZM1_RoomTmpSet | °C | Write | |
| AV | 263 | ZoneModule 1 - Minimum Supply Temperature | ZM1_MinSupTemp | °C | Write | |
| AV | 264 | ZoneModule 1 - Maximum Supply Temperature | ZM1_MaxSupTemp | °C | Write | |
| AV | 265 | ZoneModule 1 - Room CO2 Setpoint | ZM1_CO2Set | Write | ||
| AV | 266 | ZoneModule 1 - Room RH Setpoint | ZM1_RHSet | %RH | Write | |
| AV | 267 | ZoneModule 1 - VAV Supply PIR Min Air Flow | ZM1_PIRMinFlow | l/s | Write | |
| AV | 268 | ZoneModule 2 - Room Temperature Setpoint | ZM2_RoomTmpSet | °C | Write | |
| AV | 269 | ZoneModule 2 - Minimum Supply Temperature | ZM2_MinSupTemp | °C | Write | |
| AV | 270 | ZoneModule 2 - Maximum Supply Temperature | ZM2_MaxSupTemp | °C | Write | |
| AV | 271 | ZoneModule 2 - Room CO2 Setpoint | ZM2_CO2Set | Write | ||
| AV | 272 | ZoneModule 2 - Room RH Setpoint | ZM2_RHSet | %RH | Write | |
| AV | 273 | ZoneModule 2 - VAV Supply PIR Min Air Flow | ZM2_PIRMinFlow | l/s | Write | |
| AV | 274 | ZoneModule 3 - Room Temperature Setpoint | ZM3_RoomTmpSet | °C | Write | |
| AV | 275 | ZoneModule 3 - Minimum Supply Temperature | ZM3_MinSupTemp | °C | Write | |
| AV | 276 | ZoneModule 3 - Maximum Supply Temperature | ZM3_MaxSupTemp | °C | Write | |
| AV | 277 | ZoneModule 3 - Room CO2 Setpoint | ZM3_CO2Set | Write | ||
| AV | 278 | ZoneModule 3 - Room RH Setpoint | ZM3_RHSet | %RH | Write | |
| AV | 279 | ZoneModule 3 - VAV Supply PIR Min Air Flow | ZM3_PIRMinFlow | l/s | Write | |
| AV | 280 | ZoneModule 4 - Room Temperature Setpoint | ZM4_RoomTmpSet | °C | Write | |
| AV | 281 | ZoneModule 4 - Minimum Supply Temperature | ZM4_MinSupTemp | °C | Write | |
| AV | 282 | ZoneModule 4 - Maximum Supply Temperature | ZM4_MaxSupTemp | °C | Write | |
| AV | 283 | ZoneModule 4 - Room CO2 Setpoint | ZM4_CO2Set | Write | ||
| AV | 284 | ZoneModule 4 - Room RH Setpoint | ZM4_RHSet | %RH | Write | |
| AV | 285 | ZoneModule 4 - VAV Supply PIR Min Air Flow | ZM4_PIRMinFlow | l/s | Write | |
| AV | 286 | CombiHeatWaterBatt Upstart PowerSet [1/100%] | CombiUpStPow | % | Write | |
| AV | 287 | CombiWaterBatt PumpFunc: 0 - 3 | CombiPumpFunc | Write | ||
| AV | 288 | CombiBatt PumpStartTemp. Is used together with WaterPumpFunc = | STMP_CombiPmpStTmpH | °C | Write | |
| AV | 289 | Combi PumpFunc=3 then pump only starts when heatingpower exceed | CombiPmpStPrc | % | Write | |
| AV | 290 | SetVal for CombiBatt AntiFrost Reg when Agg. = Stop [1/100C] He | STMP_CombFrzStopSet | °C | Write | |
| AV | 291 | SetVal for CombiBatt AntiFrost Reg when Agg. = Drift [1/100C] H | STMP_CombFrzDrSetH | °C | Write | |
| AV | 292 | Combi P-Band for AntiFrost Reg [1/100C] | CombiFrzPB | Write | ||
| AV | 293 | SetVal for CombiBatt AntiFrost TempAlarm [1/100C] | STMP_CombiFrzAlHSet | °C | Write | |
| AV | 294 | Max % CoolPower for Dehumidity without DewPointSensor | DewCoolPower | % | Write | |
| AV | 295 | StartTemp for Nightheat Function ROH under 5 deg [1/100 C] | NH_Recirce_StartTmp2 | °C | Write | |
| AV | 296 | StopTemp for Recirc heat Function ROH under 5 deg [1/100 C] | NH_Recirce_StopTmp2 | °C | Write | |
| AV | 297 | SwitchTemp for Nightheat Function ROH [1/100 C] | NH_Recirce_SwitchTmp2 | °C | Write | |
| AV | 304 | Mod. recirce max FreshAir part, Damper position | AR_REC_MaxFreshAir | % | Write | |
| AV | 305 | Risetime 0..100%, in sec | HW1_RiseT100 | s | Write | |
| AV | 306 | Night lowering temperatur correction | STMP_NightSetBack | Write | ||
| AV | 307 | Alarmlevel in percent, if dusty | ALR_REXLevelPrcDus | % | Write | |
| AV | 308 | Alarmlevel in percent if froozen | ALR_REXLevelPrcFrz | % | Write | |
| AV | 309 | Fluid EXC PumpFunc=3 then pump only starts when EXCpower exceed | BattEXCPmpStPr | % | Write | |
| AV | 310 | Cool PumpFunc=3 pump only starts when Coolpower exceeds this se | CL_CW_PumpStartPr | % | Write | |
| AV | 311 | HWB 2 PumpFunc=3 then pump only starts when heatingpower exceed | HW2PmpStartPrc | % | Write | |
| AV | 312 | When PumpFunc=3 then pump only starts when heatingpower exceeds | HW1_PmpStartPrc | % | Write | |
| AV | 313 | Pressure to start deicing of cross Exc. [Pa] | CEXC_DeIcePress | Pa | Write | |
| AV | 314 | Time for deicing cross exc. when pressure monitored. | CExcDeIceTime | s | Write | |
| AV | 315 | LoPressSens-1 AlarmLimit [1/100 Bar] | CL_LoPress1Alr | Write | ||
| AV | 316 | HiPressSens-1 AlarmLimit [1/100 Bar] | CL_HiPress1Alr | Write | ||
| AV | 317 | LoPressSens-2 AlarmLimit [1/100 Bar] | CL_LoPress2Alr | Write | ||
| AV | 318 | HiPressSens-2 AlarmLimit [1/100 Bar] | CL_HiPress2Alr | Write | ||
| AV | 319 | Heat 2 limited over this Temperatur | ROHOutdBlkTmp | °C | Write | |
| AV | 320 | AR_CO2 Regulator Fan Min % Setpoint [1/100%] | AR_CO2_MinPerc | % | Write | |
| AV | 321 | AR_CO2 Regulator Fan Max % Setpoint [1/100%] | AR_CO2_MaxPerc | % | Write | |
| AV | 322 | Temperature Offiset Slider from Web [1/100C] | TR_TempRegOffset | Write | ||
| AV | 323 | Drives Compressor Setpoint/PrcSet | DC_Compressor_PercentSet | % | Write | |
| AV | 324 | IOC Digital input Heatpump Frost / Lubrication | IOC_DI_FP_Oil_HPT_Uset | Write | ||
| BImin | 0 | Operation ON/OFF | Operation | Read | ||
| BI | 1 | External stop | ExtStop | Read | ||
| BI | 2 | External HiSpeed | ExtHiSpeed | Read | ||
| BI | 3 | Extended low speed –> Active | ExtDrfLoSpeed | Read | ||
| BI | 4 | Extended high speed –> Active | ExtDrfHiSpeed | Read | ||
| BI | 5 | Power to electric heating coil reduced due to low flow | El_HT1_BattPowerRed | Read | ||
| BI | 6 | Summer night cooling is active | SNC_Drift | Read | ||
| BI | 7 | Reset parameters for summer night cooling new calculation is in | SNC_Reset | Read | ||
| BI | 8 | Winter temperature compensation is active | SWTC_WintComp | Read | ||
| BI | 9 | Summer temperature compensation is active | SWTC_SumComp | Read | ||
| BI | 10 | Summer/winter actual status OFF –> winter operation ('0') ON | SW_Status | Read | ||
| BI | 11 | Recirculation status ('1' = Open damper) | MODREC_Status | Read | ||
| BI | 12 | Exercising heat exchanger –> Active | EXC_Exercise | Read | ||
| BI | 13 | Signal to cross-flow exchanger reduced (frost protection) | CExcIceProtect | Read | ||
| BI | 14 | Supply duct pressure controller reduced to min. Flow | AR_SA_DuctMinFlow | Read | ||
| BI | 15 | Supply duct pressure controller increased to max. Flow | AR_SA_DuctMaxFlow | Read | ||
| BI | 16 | Extract/Exhaust duct pressure controller reduced to min. Flow | AR_EA_DuctMinFlow | Read | ||
| BI | 17 | Extract/Exhaust duct pressure controller increased to max. Flow | AR_EA_DuctMaxFlow | Read | ||
| BI | 18 | Cooling recovery –> status | CoolRecovery | Read | ||
| BI | 19 | Circulation pump on heating coil: Frost protection –> Active | HW1_FrostReg | Read | ||
| BI | 20 | Circulation pump on heating coil: Pump exercising –> Active | HW1_PumpExer | Read | ||
| BI | 21 | CoolWaterCoil PumpExercise active | CL_CW_PumpExer | Read | ||
| BI | 22 | Signal to heating coil reduced (insufficient flow) –> Active | Heat_FlwDnReg | Read | ||
| BI | 23 | 1-when min. supply temperature control is active.Only active wh | TempRegMinSup | Read | ||
| BI | 24 | 1-when max. supply temperature control is active.Only active wh | TempRegMaxSup | Read | ||
| BI | 25 | Circulation pump on heat recovery coil: Pump exercising –> Ac | BattEXC_Exer | Read | ||
| BI | 26 | Heating relay 1 | Heat_RE1_DO1 | Read | ||
| BI | 27 | Cool Relay 1 | Cool_RE1 | Read | ||
| BI | 28 | Circulation pump on Fluid EXC coil: Pump –> Running | BattEXC_PumpRE | Read | ||
| BI | 29 | At least one active alarm | AlrActive | Read | ||
| BImin | 30 | Alarm relay 1 (A-alarm) | Alr_RE1 | Read | ||
| BImin | 31 | Alarm relay 2 (B-alarm) | Alr_RE2 | Read | ||
| BI | 32 | Fire alarm signal (room sensor) | Alr_ExtFireSignal | Read | ||
| BI | 33 | Smoke Alarm Signal (Sensor in duct) | Alr_ExtSmokeSignal | Read | ||
| BI | 35 | Filter alarm for outdoor filter (pressure drop above set limit) | Filt_Alarm_OA | Read | ||
| BI | 36 | Filter alarm for extract filter (pressure drop above set limit) | Filt_Alarm_EA | Read | ||
| BI | 37 | Supply temperature sensor – sensor fault | SupTempSensErr | Read | ||
| BI | 38 | Extract temperature sensor – sensor fault | ExtTempSensErr | Read | ||
| BI | 39 | Outdoor temperature sensor – sensor fault | OutDoorSensErr | Read | ||
| BI | 40 | Room temperature sensor – sensor fault | RoomSensErr | Read | ||
| BI | 41 | Exhaust temperature sensor – sensor fault | ExhaustSensErr | Read | ||
| BI | 42 | Heating coil temperature sensor – sensor fault | HW1_SensErr | Read | ||
| BI | 43 | Fluid EXC temperature sensor – sensor fault | BattEXC_SensEr | Read | ||
| BI | 44 | Heating coil frost alarm | HW1_FrostAlr | Read | ||
| BI | 45 | Cooling shared alarm | CL_Cool_SumAlarm | Read | ||
| BI | 46 | Cooling digital alarm 1 input | CL_Cool_DI1_Alarm | Read | ||
| BI | 47 | Cooling digital alarm 2 input | CL_Cool_DI2_Alarm | Read | ||
| BI | 48 | Cooling digital alarm 3 input | CL_Cool_DI3_Alarm | Read | ||
| BI | 49 | Cooling digital alarm 4 input | CL_Cool_DI4_Alarm | Read | ||
| BI | 50 | Supply motor ON/OFF | AR_SA_SupMotorON | Read | ||
| BI | 51 | Supply Motor Alarm | SupMotorAlarm | Read | ||
| BI | 57 | Supply air fan ripple alarm | Alr_SA_Controler_Ripple | Read | ||
| BI | 59 | Extract/Exhaust motor ON/OFF | AR_EA_EA_MotorON | Read | ||
| BI | 60 | Extract Motor Alarm | ExtMotorAlarm | Read | ||
| BI | 66 | Extract/exhaust air fan 2 Ripple Alarm | Alr_EA2_Controler_Ripple | Read | ||
| BI | 68 | Rotary heat exchanger – motor control ON/OFF | DRHX_DriftON | Read | ||
| BI | 69 | Rotary heat exchanger – reset signal | DRHX_AlrReset | Read | ||
| BI | 70 | Rotary heat exchanger – rotation direction | DRHX_CCW_Rotation | Read | ||
| BI | 71 | Rotary heat exchanger rotation alarm | DRHX_RotorAlr | Read | ||
| BI | 72 | Rotary heat exchanger low voltage alarm | DRHX_V_LowAlr | Read | ||
| BI | 73 | Rotary heat exchanger hihg voltage alarm | DRHX_V_HighAlr | Read | ||
| BI | 74 | Rotary heat exchanger high current | DRHX_I_HighAlr | Read | ||
| BI | 75 | Rotary heat exchanger temperature alarm | DRHX_TempAlr | Read | ||
| BI | 76 | Rotary heat exchanger rotation signal | DRHX_RotorSignal | Read | ||
| BI | 77 | Rotary heat exchanger torque overload | DRHX_Blocked | Read | ||
| BI | 78 | Status Brandstop input | ExtBrandStop | Read | ||
| BI | 79 | Add on sensor 1 - Sensor fault | AddOnTSens1Err | Read | ||
| BI | 80 | Add on sensor 2 - Sensor fault | AddOnTSens2Err | Read | ||
| BI | 81 | Add on sensor 3 - Sensor fault | AddOnTSens3Err | Read | ||
| BI | 82 | Add on sensor 4 - Sensor fault | AddOnTSens4Err | Read | ||
| BI | 83 | Alarm frost thermostat alarm (digital input) | Alr_Frost_OA_Luftsensor | Read | ||
| BI | 84 | Heating coil 2 - Frost control active | HW2FrostReg | Read | ||
| BI | 85 | Heating coil 2 - Circulation pump, pump exercising active | HW2PumpExer | Read | ||
| BI | 86 | Heating coil 2 - Return sensor - Sensor fault | HW2SensErr | Read | ||
| BI | 87 | Heating coil 2 - Frost alarm | HW2FrostAlr | Read | ||
| BI | 88 | Pre-heating coil - Frost alarm | PH_FreezeAlarm | Read | ||
| BI | 89 | Pre-heating coil - Frost protection active | PH_FrostRegAct | Read | ||
| BI | 90 | Pre-heater Pump exercise active | PH_PumpExer | Read | ||
| BI | 91 | Preheater - heat relay 1 | PH_HeatRelay | Read | ||
| BI | 92 | Pre-heating coil - Overheating fault | PH_Overheat | Read | ||
| BI | 93 | Pre-heating coil - Output reduction, low air volume | PH_PowReduce | Read | ||
| BI | 94 | Returnwater sensor error | PH_HWBSensErr | Read | ||
| BI | 95 | Alarm - Heat recovery efficiency below alarm limit | Alr_EXCEffToLow | Read | ||
| BI | 96 | Alarm Atv Comm Supply | Alr_AtvSA_Comm | Read | ||
| BI | 97 | Alarm Atv Comm Extract | Alr_AtvEA_Comm | Read | ||
| BI | 98 | Alarm Atv FC Supply | Alr_AtvSAMotorAlarm | Read | ||
| BI | 99 | Alarm Atv FC Extract | Alr_AtvEAMotorAlarm | Read | ||
| BI | 100 | Frost alarm fluid-coupled coil (CoilEXC) | Alr_FrostBatt_EXC | Read | ||
| BI | 101 | Contact error DeIcer El-Battery | Alr_DeIceContact | Read | ||
| BI | 102 | DeIcer overheatingsalarm El-Battery | Alr_DeIceOverheat | Read | ||
| BI | 103 | DeIcer power reduction alarm El-Battery | Alr_DeIceReduced | Read | ||
| BI | 104 | Alarm - pressure transmitter not calibrated (Ice guard rotor he | Alr_NoREXCali | Read | ||
| BI | 105 | Alarm - pressure transmitter not configured (Ice guard rotor he | Alr_SensREXNConf | Read | ||
| BI | 106 | Coolrecovery over damper active ('1' = Open damper) | NO_CRecovStat | Read | ||
| BI | 107 | Cooling stopped by room temperature | NO_CStopRTStat | Read | ||
| BI | 108 | Signal for the 4-way-valve in HeatPump | HP_CoolingActv | Read | ||
| BI | 109 | Status bit: De-icing of heatpump | HP_De_icingAct | Read | ||
| BI | 110 | Alarm - rotor heat exchanger blocked by ice (high pressure over | Alr_RotEXCFrozen | Read | ||
| BI | 111 | Alarm - rotor heat exchanger blocked by dirt (high pressure ove | Alr_RotEXCDusty | Read | ||
| BI | 112 | Flow is change heat2 active | HT2FlowChgAct | Read | ||
| BI | 113 | Status of delaytimer Heat 2 | HT2DelayStatus | Read | ||
| BI | 114 | Limit of heat 2 is avoid | HT2DelLimBlkNo | Read | ||
| BI | 115 | Blocking Heat2 in recirkulation mode = Aktivated | HT2RecBlkAct | Read | ||
| BI | 116 | Status of low flow under 100% recirculation | NH_LowRecFlowStat | Read | ||
| BI | 117 | Closed damper running active | RecClosDmpAct | Read | ||
| BI | 118 | Max. raise-/fall-time is activated | HW1_RiseFallActiv | Read | ||
| BI | 119 | Supply air fan 2 high current limit | Alr_SA2_Contr_HiIOAlr | Read | ||
| BI | 120 | Supply air fan 2 voltage low alarm | Alr_SA2_Contr_LoVIn | Read | ||
| BI | 121 | Supply air fan 2 voltage high alarm | Alr_SA2_Contr_HiVIn | Read | ||
| BI | 122 | Supply air fan 2 high current limit alarm | Alr_SA2_Control_I_MaxAlr | Read | ||
| BI | 123 | Supply air fan 2 temperature alarm | Alr_SA2_Contr_HiTemp | Read | ||
| BI | 124 | Supply air fan 2 alarm for phase error | Alr_SA2_Contr_PhaseErr | Read | ||
| BI | 125 | Supply air fan 2 Direction error | Alr_SA2_Contr_Rot_DirErr | Read | ||
| BI | 126 | Supply air fan 2 alarm for blocked rotor | Alr_SA2_Controler_RotBlk | Read | ||
| BI | 128 | Extract/exhaust air fan 2 voltage low alarm | Alr_EA2_Contr_LoVIn | Read | ||
| BI | 129 | Extract/exhaust air fan 2 voltage high alarm | Alr_EA2_Contr_HiVIn | Read | ||
| BI | 130 | Extract/exhaust air fan 2 high current limit alarm | Alr_EA2_Control_I_MaxAlr | Read | ||
| BI | 131 | Extract/exhaust air fan 2 temperature alarm | Alr_EA2_Contr_HiTemp | Read | ||
| BI | 132 | Extract/exhaust air fan 2 alarm for phase error | Alr_EA2_Contr_PhaseErr | Read | ||
| BI | 133 | Extract/exhaust air fan 2 Direction error | Alr_EA2_Contr_Rot_DirErr | Read | ||
| BI | 134 | Extract/exhaust air fan 2 alarm for blocked rotor | Alr_EA2_Controler_RotBlk | Read | ||
| BI | 135 | Alarm SA2 Controler Comm Alarm | Alr_SA2Controler_Com | Read | ||
| BI | 136 | Alarm EA2 Controler Comm Alarm | Alr_EA2Controler_Com | Read | ||
| BI | 137 | Supply air fan high current limit | Alr_SA_ControlerI_MaxAlr | Read | ||
| BI | 138 | Supply air fan voltage low alarm | Alr_SA_Contr_LoVIn | Read | ||
| BI | 139 | Supply air fan voltage high alarm | Alr_SA_Contr_HiVIn | Read | ||
| BI | 140 | Supply air fan high current limit alarm | Alr_SA_Contr_HiIOAlr | Read | ||
| BI | 141 | Supply air fan temperature alarm | Alr_SA_Contr_HiTemp | Read | ||
| BI | 142 | Supply air fan alarm for phase error | Alr_SA_Contr_PhaseErr | Read | ||
| BI | 143 | Supply air fan Direction error | Alr_SA_Contr_Rot_DirErr | Read | ||
| BI | 144 | Supply air fan alarm for blocked rotor | Alr_SA_Controler_RotBlk | Read | ||
| BI | 145 | Extract/exhaust air fan high current limit | Alr_EA_ControlerI_MaxAlr | Read | ||
| BI | 146 | Extract/exhaust air fan voltage low alarm | Alr_EA_Contr_LoVIn | Read | ||
| BI | 147 | Extract/exhaust air fan voltage high alarm | Alr_EA_Contr_HiVIn | Read | ||
| BI | 148 | Extract/exhaust air fan high current limit alarm | Alr_EA_Contr_HiIOAlr | Read | ||
| BI | 149 | Extract/exhaust air fan temperature alarm | Alr_EA_Contr_HiTemp | Read | ||
| BI | 150 | Extract/exhaust air fan alarm for phase error | Alr_EA_Contr_PhaseErr | Read | ||
| BI | 151 | Extract/exhaust air fan Direction error | Alr_EA_Contr_Rot_DirErr | Read | ||
| BI | 152 | Extract/exhaust air fan alarm for blocked rotor | Alr_EA_Controler_RotBlk | Read | ||
| BI | 153 | OJ-DV Supply Comm Alarm | Alr_SA_Controler_Comm | Read | ||
| BI | 154 | OJ-DV Extract Comm Alarm | Alr_EA_Controler_Comm | Read | ||
| BI | 155 | TTH-6202 communication error | Alr_TTH6202Com | Read | ||
| BI | 156 | Communication Alarm Belimo Smoke Damper | Alr_BDSmokeCom_Error | Read | ||
| BI | 157 | Position Alarm Belimo Smoke Damper | Alr_BDSmokePos_Error | Read | ||
| BI | 158 | Extention IO-Modul no 1 - communication error | Alr_Ext_Modul1_Comm | Read | ||
| BI | 159 | Extention IO-Modul no 2 - communication error | Alr_Ext_Modul2_Comm | Read | ||
| BI | 160 | Extention IO-Modul no 3 - communication error | Alr_Ext_Modul3_Comm | Read | ||
| BI | 161 | Extention IO-Modul no 4 - communication error | Alr_Ext_Modul4_Comm | Read | ||
| BI | 162 | Extention IO-Modul no 5 - communication error | Alr_Ext_Modul5_Comm | Read | ||
| BI | 163 | Extention IO-Modul no 6 - communication error | Alr_Ext_Modul6_Comm | Read | ||
| BI | 164 | Extention IO-Modul no 7 - communication error | Alr_Ext_Modul7_Comm | Read | ||
| BI | 165 | Extention IO-Modul no 8 - communication error | Alr_Ext_Modul8_Comm | Read | ||
| BI | 166 | Supplysensor 2 alarm | Alr_SupAirTemp2 | Read | ||
| BI | 167 | Addon sensor 1 - Sensor error | Alr_AddOnSens1 | Read | ||
| BI | 168 | Addon sensor 2 - Sensor error | Alr_AddOnSens2 | Read | ||
| BI | 169 | Addon sensor 3 - Sensor error | Alr_AddOnSens3 | Read | ||
| BI | 170 | Addon sensor 4 - Sensor error | Alr_AddOnSens4 | Read | ||
| BI | 171 | SupMotor Alarm | Alr_SA_Controler | Read | ||
| BI | 172 | ExtMotor Alarm | Alr_EA_Controler | Read | ||
| BI | 173 | Combi coil; Cooling relay no. 2 aktive | Cmb2CoolRel | Read | ||
| BI | 174 | Flag for Rise-Falltime active DX-CO2-Cooling | ROHRiFaActiv | Read | ||
| BI | 176 | Preheater - heat relay 3 | PH_HeatRelay3 | Read | ||
| BI | 177 | State of extern start input | ExternInput_StartState | Read | ||
| BI | 178 | Supply air fan EEprom error | Alr_SA_Contr_EE_Error | Read | ||
| BI | 179 | Supply air fan 2 EEprom error | Alr_SA2_Contr_EE_Error | Read | ||
| BI | 180 | Extract/exhaust air fan EEprom error | Alr_EA_Contr_EE_Error | Read | ||
| BI | 181 | Extract/exhaust air fan 2 EEprom error | Alr_EA2_Contr_EE_Error | Read | ||
| BI | 182 | Sensor alarm TTH6040 no Com | Alr_TTH6040Com | Read | ||
| BI | 183 | Low oil level cooling compressor | Alr_LowOilDXHP | Read | ||
| BI | 184 | Common-Alarm circulationpumps | Alr_Common_HWPump | Read | ||
| BI | 185 | Common-Alarm Supplyfan | Alr_Common_SupFan | Read | ||
| BI | 186 | Common-Alarm Extractfan | Alr_Common_ExtFan | Read | ||
| BI | 187 | Common-Alarm Supply duct/flow | Alr_Common_SupFlDu | Read | ||
| BI | 188 | Common-Alarm Extract duct/flow | Alr_Common_ExtFlDu | Read | ||
| BI | 189 | Common-Alarm Exchanger | Alr_Common_EXC | Read | ||
| BI | 190 | Common-Alarm antifreeze | Alr_Common_Freeze | Read | ||
| BI | 191 | Common-Alarm El-Batteries | Alr_Common_ElHeat | Read | ||
| BI | 192 | Common-Alarm Temperatures low/high | Alr_Common_Temp | Read | ||
| BI | 193 | Common-Alarm Supply Filter | Alr_Common_SFilt | Read | ||
| BI | 194 | Common-Alarm Extract Filter | Alr_Common_EFilt | Read | ||
| BI | 195 | Common-Alarm Temperaturesensors | Alr_Common_TmpSens | Read | ||
| BI | 196 | Common-Alarm Cooling | Alr_Common_Cool | Read | ||
| BI | 197 | Common-Alarm Dampers Belimo | Alr_Common_BDamp | Read | ||
| BI | 198 | Common-Alarm Internals / SysModBus | Alr_Common_Intern | Read | ||
| BI | 199 | Value in Control Reg BMS Ctrl | BMS_InpRegState | Read | ||
| BI | 200 | State of extern lowspeed input | ExternInput_LowSpeed | Read | ||
| BI | 201 | BMS-Sensor Room Out of Range | Alr_BMS_Room_TS_OOR | Read | ||
| BI | 202 | BMS-Sensor Outdoor Out of Range | Alr_BMS_OA_TS_OOR | Read | ||
| BI | 203 | Fire mann stop | Alr_FireManStop | Read | ||
| BI | 204 | Smoke evacuation activated | Alr_SmokEvacAct | Read | ||
| BI | 205 | Smoke evacuation fan alarm | Alr_SmokEvaFan | Read | ||
| BI | 206 | Output for supply air damper aktive | DO_OA_BigDamp_Relay | Read | ||
| BI | 207 | Big Damper relay Supply | DO_SA_BigDamp_Relay | Read | ||
| BI | 208 | Recirce DamperSignal | AR_DA_REC_DO | Read | ||
| BI | 209 | External OutDoorTemp -Sensor Error | ExOutDSensErr | Read | ||
| BI | 210 | PreHeatWaterBatt Sensor Alarm | Alr_PreheatAirSens | Read | ||
| BI | 211 | Cooling water supply temperature - sensor error | CL_CW_TSensErr | Read | ||
| BI | 212 | Heat Relay 21 (ExtMod-Reserve) | Heat_RE21_DO21 | Read | ||
| BI | 213 | Heat Relay 22 (ExtMod-Reserve) | Heat_RE22_DO22 | Read | ||
| BI | 214 | Heat Relay 23 (ExtMod-Reserve) | Heat_RE23_DO23 | Read | ||
| BI | 215 | Heat Relay 24 (ExtMod-Reserve) | Heat_RE24_DO24 | Read | ||
| BI | 216 | Heat Relay 25 (ExtMod-Reserve) | Heat_RE25_DO25 | Read | ||
| BI | 217 | Heating relay26 (ExtMod-Reserve) | Heat_RE26_DO26 | Read | ||
| BI | 218 | Pump relay combi coil activated | Combi_PumpRE_DO | Read | ||
| BI | 219 | Electric coil: High temperature alarm signal | EL1_OverHtBac | Read | ||
| BI | 220 | Electric coil: Relay stuck | Alr_HT1_EL_Coil_Contact | Read | ||
| BI | 221 | Electric coil 2: High temperature alarm signal | EL2_OverHtBac | Read | ||
| BI | 222 | Electric coil 2: Relay stuck | Alr_HT2_EL_Coil_Contact | Read | ||
| BI | 223 | Alarm - Time is out for filter change supply air filter | Alr_OAFilt_TimerAlrOn | Read | ||
| BI | 224 | Alarm - Time is out for filter change extract air filter | Alr_EAFilt_TimerAlrOn | Read | ||
| BI | 225 | Extended medium speed –> Active | ExtDrfMeSpeed | Read | ||
| BI | 226 | Preheater - heat relay 2 | PH_HeatRelay2 | Read | ||
| BI | 229 | Supply air fan, Power limit | Alr_SA_Contr_PowLim | Read | ||
| BI | 230 | Extract/exhaust air fan, Power limit | Alr_EA_Contr_PowLim | Read | ||
| BI | 233 | Supply air fan2 Ripple Alarm | Alr_SA2_Controler_Ripple | Read | ||
| BI | 234 | Extract/exhaust air fan, Intern Stop | Alr_EA_Controler_IStop | Read | ||
| BI | 235 | Supply air fan2 Intern Stop | Alr_SA2_Controler_IStop | Read | ||
| BI | 236 | Extract/exhaust air fan 2, Intern Stop | Alr_EA2_Controler_IStop | Read | ||
| BI | 237 | CombiBattery heat usable | CmbHeatState | Read | ||
| BI | 238 | CombiBattery cool usable | CmbCoolState | Read | ||
| BI | 239 | ElPrehheat Overheat State | Pre_OverHtBac | Read | ||
| BI | 240 | Contact error Preheater El-Battery | Alr_Preheat_Contact | Read | ||
| BI | 244 | Extract/exhaust air fan 2 high current limit | Alr_EA2_Contr_HiIOAlr | Read | ||
| BI | 245 | B-Alr SupFan is stopped | Alr_SA_FanStop | Read | ||
| BI | 246 | Smoke Evac Damper not in position | Alr_SMEvacDmpNotInPos | Read | ||
| BI | 247 | Smoke Bypass Damper not in position | Alr_SMBPassDmpNotInPos | Read | ||
| BI | 248 | Communication Alarm DPTH1 | Alr_DPTH_1Com | Read | ||
| BI | 249 | Communication Alarm DPTH2 | Alr_DPTH_2Com | Read | ||
| BI | 250 | Communication Alarm DPTH3 | Alr_DPTH_3Com | Read | ||
| BI | 251 | Communication Alarm DPTH4 | Alr_DPTH_4Com | Read | ||
| BI | 252 | Communication Alarm DPTH5 | Alr_DPTH_5Com | Read | ||
| BI | 253 | Filter Alarm for SA-Filter (pressure above Limit) | Filt_Alarm_SA | Read | ||
| BI | 254 | Filter Alarm for EA2-Filter (pressure above Limit) | Filt_Alarm_EA2 | Read | ||
| BI | 255 | Alarm from Supplyfilter timer | Alr_SAFilt_TimerAlrOn | Read | ||
| BI | 256 | Alarm from Extractfilter2 timer | Alr_EAFilt2_TimerAlrOn | Read | ||
| BI | 257 | ZoneControl PIR Active | ZM_PIR | Read | ||
| BI | 258 | ZoneModule 1 - WindowFrost Value | ZM1_WinFrost | Read | ||
| BI | 259 | ZoneModule 1 - PIR Active | ZM1_PIR | Read | ||
| BI | 260 | ZoneModule 1 - Room Temp Sensor Error | ZM1_RoomTmpErr | Read | ||
| BI | 261 | ZoneModule 1 - Supply Temp Sensor Error | ZM1_SupTempErr | Read | ||
| BI | 262 | ZoneModule 2 - WindowFrost Value | ZM2_WinFrost | Read | ||
| BI | 263 | ZoneModule 2 - PIR Active | ZM2_PIR | Read | ||
| BI | 264 | ZoneModule 2 - Room Temp Sensor Error | ZM2_RoomTmpErr | Read | ||
| BI | 265 | ZoneModule 2 - Supply Temp Sensor Error | ZM2_SupTempErr | Read | ||
| BI | 266 | ZoneModule 3 - WindowFrost Value | ZM3_WinFrost | Read | ||
| BI | 267 | ZoneModule 3 - PIR Active | ZM3_PIR | Read | ||
| BI | 268 | ZoneModule 3 - Room Temp Sensor Error | ZM3_RoomTmpErr | Read | ||
| BI | 269 | ZoneModule 3 - Supply Temp Sensor Error | ZM3_SupTempErr | Read | ||
| BI | 270 | ZoneModule 4 - WindowFrost Value | ZM4_WinFrost | Read | ||
| BI | 271 | ZoneModule 4 - PIR Active | ZM4_PIR | Read | ||
| BI | 272 | ZoneModule 4 - Room Temp Sensor Error | ZM4_RoomTmpErr | Read | ||
| BI | 273 | ZoneModule 4 - Supply Temp Sensor Error | ZM4_SupTempErr | Read | ||
| BI | 274 | Cool Relay 2 | Cool_RE2 | Read | ||
| BI | 275 | Cool Relay 3 | Cool_RE3 | Read | ||
| BI | 276 | Cool Relay 4 | Cool_RE4 | Read | ||
| BI | 277 | Alarm smoke evacuation damper is activated ('1' = Open damper) | Alr_FireEvaDmp | Read | ||
| BI | 278 | Heat Relay 2 (ExtMod-Reserve) | Heat_RE2_DO2 | Read | ||
| BI | 279 | Combi coil - Return sensor - Sensor fault | CombiTSenErr | Read | ||
| BI | 280 | Combi coil - Frost alarm | CombiFrostAlrH | Read | ||
| BI | 281 | Combi coil - Frost protection active | CombiFrostReg | Read | ||
| BI | 282 | Combi coil - Circulation pump, pump exercising active | CombiPumpExer | Read | ||
| BI | 283 | Combi coil; Cooling relay aktive | CombiCoolRel | Read | ||
| BI | 284 | Combi coil; Heating relay aktive | CombiHeatRel | Read | ||
| BI | 286 | Supply Fan wall Alarm (B) | Alr_SA_FanWallAlr | Read | ||
| BI | 287 | Extract Fan wall Alarm (B) | Alr_EA_FanWallAlr | Read | ||
| BI | 288 | Extract digital damper output signal ('1' = Open damper) | DO_EA_Damper_Signal | Read | ||
| BI | 289 | Exhaust digital damper output signal ('1' = Open damper) | DO_EXH_Damper_Signal | Read | ||
| BI | 290 | Exhaust backup digital damper output signal ('1' = Open damper) | DO_EXHBa_Damper_Signal | Read | ||
| BI | 291 | Supply backup digital damper output signal ('1' = Open damper) | DO_SABa_Damper_Signal | Read | ||
| BI | 292 | SupBackupMotor Alarm | AlrSupBMtr | Read | ||
| BI | 293 | ExhBackupMotor Alarm | AlrExhBMtr | Read | ||
| BI | 294 | Sensor alarm TTH6040 OutDoor no Com (port A) | TTH_6040OA_PortA_Com | Read | ||
| BI | 295 | Supply Backup Motor Alarm | SupBMotorAlarm | Read | ||
| BI | 296 | Exhaust Backup Motor Alarm | ExhBMotorAlarm | Read | ||
| BI | 297 | Reduction of cross-flow exchanger due to de-icing; deicing star | CExcDeIcing | Read | ||
| BI | 298 | Electric coil 2 - Output reduction active due to low flow | El_HT2_BatPowerRed | Read | ||
| BI | 299 | Extract/exhaust air fan Ripplealarm | Alr_EA_Controler_Ripple | Read | ||
| BI | 300 | Supply air fan, Intern Stop | Alr_SA_Controler_IStop | Read | ||
| BI | 301 | Preheater Frost Alarm Cooling | PH_FrzAlrCool | Read | ||
| BI | 302 | Status frost thermostat alarm (digital input) | AR_DI_State_LuftAlr | Read | ||
| BI | 303 | Humidifier alarm status | HumidAlrInp | Read | ||
| BI | 304 | Freshair cooling is stopped | NO_CStopStat | Read | ||
| BI | 305 | Communication CVM Mini Meter | Alr_CommCVMMini | Read | ||
| BI | 306 | Communication CVM Mini Cool Meter | Alr_CommCVMCool | Read | ||
| BI | 307 | A-Alr Comm Error HMI_20T | Alr_ComHMI_20T | Read | ||
| BI | 308 | Alarm, Fire damper not closed | AlrFireDmpNCls | Read | ||
| BI | 309 | Alarm, Fire damper not opened | AlrFireDmpNOpn | Read | ||
| BI | 310 | Fire damper test is ongoing | FireDmpTstActv | Read | ||
| BI | 311 | Extract air temperature after Heatpump, sensor error | HP_TSExtAirErr | Read | ||
| BI | 312 | Start of AHU is blocked, if mounted and open | AggBlKAlr | Read | ||
| BI | 313 | Firethermostat alarm via El-Heater input | FireEHtCoilAlr | Read | ||
| BI | 314 | Firethermostat alarm via El-Pre-Heater input | FireEPrHeatAlr | Read | ||
| BI | 315 | Daikin EVKit communications Alarm | AlrCommDaikin | Read | ||
| BI | 316 | Daikin 'warning' bits from register 30003 | AlrDaikinWrn | Read | ||
| BI | 317 | Daikin 'alarm' bits from register 30003 | AlrDaikinAlr | Read | ||
| BI | 318 | Daikin 'error' bits from register 30003 | AlrDaikinErr | Read | ||
| BI | 320 | Drives Compressor communication alarm | Alr_DrCmpComAlr | Read | ||
| BI | 321 | Drives Compressor high current alarm | Alr_DrCmp_IHgh | Read | ||
| BI | 322 | Drives Compressor low voltage alarm | Alr_DrCmpLwVlt | Read | ||
| BI | 323 | Drives Compressor high voltage alarm | Alr_DrCmpHghVlt | Read | ||
| BI | 324 | Drives Compressor high temperature alarm | Alr_DrCmpHiTmp | Read | ||
| BI | 325 | Drives Compressor compressor alarm | Alr_DrCmpInpPhAlr | Read | ||
| BI | 326 | Drives Compressor rotor blocked | Alr_DrCmpRtrBlkAlr | Read | ||
| BI | 327 | Drives Compressor current limit alarm | Alr_DrCmpILimitAlr | Read | ||
| BI | 328 | Drives Compressor voltage limit alarm | Alr_DrCmpVLimitAlr | Read | ||
| BI | 329 | Drives Compressor rotor direction alarm | Alr_DrCmpRtrDirAlr | Read | ||
| BI | 330 | Drives Compressor Eeprom error | Alr_DrCmpEEPROM | Read | ||
| BI | 331 | Drives Compressor internal Stop | Alr_DrCmpIntrnStp | Read | ||
| BI | 332 | Drives Compressor Earth fault alarm | Alr_DrCmpEarthFlt | Read | ||
| BI | 333 | Drives Compressor Motor phase alarm | Alr_DrCmpPhaseErr | Read | ||
| BI | 334 | Drives Compressot MOC communication err | Alr_DrCmpComErrMOC | Read | ||
| BI | 335 | Drives Compressor 24V overload alarm | Alr_DrCmp24VOvrlad | Read | ||
| BI | 336 | Drives Compressor internal bootloader alarm | Alr_DrCmpMOCinBoot | Read | ||
| BI | 337 | Drives Compressor internal com alarm | Alr_DrCmpComErrIOM | Read | ||
| BI | 338 | Drives Compressor Motor overheat alarm | Alr_DrCmpOverheat | Read | ||
| BI | 339 | Drives Compressor Start up alarm | Alr_DrCmpErStrtup | Read | ||
| BI | 340 | Drives Compressor Pressure relax alarm | Alr_DrCmpPrssRlx | Read | ||
| BI | 341 | Drives Compressor Max start alarm | Alr_DrCmpMaxStarts | Read | ||
| BI | 342 | Drives Compressor Min run time alarm | Alr_DrCmpMinRntime | Read | ||
| BI | 343 | Drives Compressor Overloaded | Alr_DrCmp_Overload | Read | ||
| BI | 348 | Heat pump deicing not correct | Alr_HP_Deice_Incorrect | Read | ||
| BI | 349 | Heat pump water temp alarm | Alr_HP_WaterTemp | Read | ||
| BI | 350 | State of the Heat pump Oil/Defrost input | HP_Stat_Lub | Read | ||
| BI | 352 | Alarm Counterflow EXC Deicing is active for too long time | Alr_CF_Timerunout_On | Read | ||
| BI | 353 | Filter calibration completed OA (valid filter data)ONLY IF 'DYN | FiltCaliDone_OA | Read | ||
| BI | 354 | Filter calibration completed SA (valid filter data)ONLY IF 'DYN | FiltCaliDone_SA | Read | ||
| BI | 355 | Filter calibration completed EA1 (valid filter data)ONLY IF 'DY | FiltCaliDone_EA1 | Read | ||
| BI | 356 | Filter calibration completed EA2 (valid filter data)ONLY IF 'DY | FiltCaliDone_EA2 | Read | ||
| BI | 357 | Pre-heating coil - Return sensor - Sensor fault | PH_TempSensErr | Read | ||
| BI | 358 | Drive Compressor Existflag | EXISTS_DV_Compressor | Read | ||
| BVmin | 0 | Alarm reset signal (AutoReturn to zero) | Alr_Reset_Uset | Write | ||
| BV | 1 | Cooling recovery: ON/OFF | AHU_CoolRecovFunc | Write | ||
| BV | 2 | Summer night cooling: ON/OFF | SNC_Func | Write | ||
| BV | 3 | Summer/winter temp. compensation: ON/OFF | SWTC_Func | Write | ||
| BV | 4 | Flow/outdoor temperature compensation: ON/OFF | AR_FlwTmpCmpFunc | Write | ||
| BV | 5 | Recirculation: ON/OFF ('1' = Open damper) | NH_REC_Func_On | Write | ||
| BV | 6 | Forced flow with cooling demand: ON/OFF | CL_Cool_FlwForceFc | Write | ||
| BV | 7 | Automatic summer/winter time: ON/OFF | SWTC_SumFunc | Write | ||
| BV | 8 | Input for forced high speed | ExtDrfHiPeriod | Write | ||
| BV | 9 | Run-on time for forced high speed active | ExtDrfPeriodON | Write | ||
| BV | 10 | Start manual zero calibration (can be used together with automa | AHU_ManZeroCali | Write | ||
| BV | 11 | Automatic zero calibration: ON/OFF | AHU_AutoZeroCali | Write | ||
| BV | 12 | Dynamic filter alarm: ON/OFF OFF static limit on dynamic limit | FiltDynAlrFunc | Write | ||
| BV | 13 | Start filter calibration. Is automatically reset to zero (OFF) | FM_FiltCalibrate_Start | Write | ||
| BV | 15 | Activate outdoor temperature from BMS | TR_MBT_OA_Act | Write | ||
| BV | 16 | Activate room temperature from BMS | TR_MBT_Room1Activ | Write | ||
| BV | 17 | Hot water supply is available for the combi coil | CmbEnHeatMB | Write | ||
| BV | 18 | Cold water supply is available for the combi coil | CmbEnCoolMB | Write | ||
| BV | 19 | Force recirc via Ext. Modbus ('1' = Open damper) | ExtMB_ForceRecirc | Write | ||
| BV | 20 | Enable Modbus Force recirc signal | ExtMBEnbl_ForceRec | Write | ||
| BV | 21 | Enable combi coil for control via external Modbus [1=Modbus/0=D | CmbEnCtrlMB | Write | ||
| BV | 22 | Filter (OA) Dynamic Alarm function ON/OFF OFF -> Static Limit O | Filt_DynAlrFunc_OA | Write | ||
| BV | 23 | Filter (SA) Dynamic Alarm function ON/OFF OFF -> Static Limit O | Filt_DynAlrFunc_SA | Write | ||
| BV | 24 | Filter (EX) Dynamic Alarm function ON/OFF OFF -> Static Limit O | Filt_DynAlrFunc_EA1 | Write | ||
| BV | 25 | Filter (EX2) Dynamic Alarm function ON/OFF OFF -> Static Limit | Filt_DynAlrFunc_EA2 | Write | ||
| BV | 26 | Rotary heatexchanger, turn ratation direction to counter clock | EXC_CCV | Write | ||
| BV | 27 | Summer Night Cooling activated in low speed | SNC_FuncLoSpeed | Write | ||
| BV | 28 | External high speed start signal | ExtHighSpdSet | Write | ||
| BV | 29 | Drive Compressor Mountflag | MNT_DV_Compressor | Write | ||
| BV | 30 | Input for forced medium speed | ExtDrfMePeriod | Write | ||
| BV | 31 | Limit the first step between min / max SA-BattFlow El-Heater 1 | EL_HT1_LimitStep_1Uset | Write | ||
| BV | 32 | Limit the first step between min / max SA-BattFlow El-Heater 2 | EL_HT2_LimitStep_1Uset | Write | ||
| BV | 33 | Limit the first step between min / max SA-BattFlow El- Preheate | PH_EL_LimitStep_1Uset | Write | ||
| CAL | 0 | Calendar #1 | Calendar #1 | Write | ||
| CAL | 1 | Calendar #2 | Calendar #2 | Write | ||
| CAL | 2 | Calendar #3 | Calendar #3 | Write | ||
| NC | 0 | NC 00 A-Alarm | Notification Class 00 A-Alarm | Read | ||
| NC | 1 | NC 01 B-Alarm | Notification Class 01 B-Alarm | Read | ||
| SCH | 0 | Schedule #1 | Schedule #1 | Write |
No points match these filters.
Object ID lookup: OJ Electronics OJ Air Plus AHU controller, SW 1.09 point IDs by name
AI0Actual operating mode 000-099 Unit stopped 100-199: Unit in lowAI1SA DuctPressure (Calc from PressSignal) [Pa]AI2Regulator SetPoint for DuctPressReg [Pa] SAAI3Extract DuctPressure (Calc from PressSignal) [Pa]AI4Regulator SetPoint for DuctPressReg [Pa] EAAI5Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the uAI6Setpoint for supply flow controller [l/s] or [m3/h] or [CFM] (DAI7Actual Extract/Exhaust flow [l/s] or [m3/h] or [CFM] (DependingAI8Setpoint for Extract/Exhaust flow controller [l/s] or [m3/h]orAI9AR_CO2 Sensor ppm Measure [ppm]AI10Signal from Fanoptimizer Input SAAI11Signal from Fanoptimizer Input EAAI12FAN-Opt Supply Signal [1/100%]AI13FAN-Opt Extract Signal [1/100%]AI14Supply Max Flow [l/s], Aggregate maxAI15Extract/Exhaust Max Flow [l/s], AggregateAI16Current SupplyTemp [1/100C]AI17Regulator SupplyTemp-Set [1/100C]AI18Actual extract temperature [1/100°C]AI19Regulator ExtractTemp-Set [1/100C]AI20Actual outdoor temperature [1/100°C]AI21Current RoomTemp (External Sens) [1/100C]AI22Current ExhaustTemp [1/100C]AI23TempMeas for actual RegMode [1/100C]AI24RegVal for actual RegMode [1/100C]AI25Fluid EXC Temp after EXC [1/100C]AI26Current HeatWaterBatt 1 Temp [1/100C]AI27Outdoor Filter Pressure (Avr-Meas) [Pa]AI28Extract Filter Pressure (Avr-Meas) [Pa]AI29Supply Motor signal percentAI30Extract/Exhaust Motor signal percentAI31OA Filter pressure for alarm-limit at actual flow [Pa]AI32EA Filter pressure for alarm-limit at actual flow [Pa]AI33FlowOutTempComp PercentOut [1/100%]AI34Sum/Wint-TempComp actual Setpoint offset [1/100C ]AI35EXC-Regulator HeatPower [1/100 %]AI36AfterHeat1-Regulator Power [1/100 %]AI37Cool Regulator Power [1/100 %], OutputAI38Actual Cool-Power [1/100%]AI39Cool Force Flow Power [1/100 %]AI40Cool Alarm-1 VDC-Signal [1/100 %]AI41Cool Alarm-2 VDC-Signal [1/100 %]AI42Cool Alarm-3 VDC-Signal [1/100 %]AI43Cool Alarm-4 VDC-Signal [1/100 %]AI44Actual low pressure sensor 1 [1/100 bar]AI45Actual high pressure sensor 1 [1/100 bar]AI46Actual low pressure sensor 2 [1/100 bar]AI47Actual high pressure sensor 2 [1/100 bar]AI55Extract SFP [Ws/m3 same as J/m3]AI56Supply SFP [Ws/m3 same as J/m3]AI66RotaryEXC – motor typeAI67RotaryEXC – software version [1/100]AI68RotaryEXC – percentage [1/100%]AI69RotaryEXC – speed output [1/10 rpm]AI70RotaryEXC - actual output [mA]AI71RotaryEXC – output power [W]AI72RotaryEXC – days of operationAI73RotaryEXC – percentage setpoint [1/100%]AI74Extension module 1 software version [1/100]AI75Extension module 2 software version [1/100]AI76Act weekday Monday..Sunday (1 = Monday)AI79Stack for active alarm's 0 (0 end of stack)AI80Stack for active alarm's 1 (0 end of stack)AI81Stack for active alarm's 2 (0 end of stack)AI82Stack for active alarm's 3 (0 end of stack)AI83Stack for active alarm's 4 (0 end of stack)AI84Stack for active alarm's 5 (0 end of stack)AI85Stack for active alarm's 6 (0 end of stack)AI86Stack for active alarm's 7 (0 end of stack)AI87Stack for active alarm's 8 (0 end of stack)AI88Stack for active alarm's 9 (0 end of stack)AI89Stack for active alarm's 10 (0 end of stack)AI90Stack for active alarm's 11 (0 end of stack)AI91Stack for active alarm's 12 (0 end of stack)AI92Stack for active alarm's 13 (0 end of stack)AI93Stack for active alarm's 14 (0 end of stack)AI94Stack for active alarm's 15 (0 end of stack)AI95Master Software Ver [1/100]AI96Display Software Ver [1/100]AI97Additional TempSensor1 [1/100C]AI98Additional TempSensor2 [1/100C}AI99Additional TempSensor3 [1/100C]AI100Additional TempSensor4 [1/100C]AI103AfterHeat2-Regulator Power [1/100 %]AI104Heatpower Preheater [1/100%]AI105Current Pre-HeatWaterBattTemp [1/100C] Coil/ReturnAI108Heat exchanger efficiency [1/100%]AI109Voltage level, HWB1 Out2AI110Measured pressure loss over heat pump outdoor coil.AI111ModCO2, State 1-L/H, 2-H/L,0-nothingAI112Recirce closedown timerAI113CombiBattery VDC-Signal out for AfterHeat/Cool [1/1000 V]AI114CombiBattery Power for Heat [1/100%]AI115CombiBattery Power for Cool [1/100%]AI118Current external OutDoorTemp [1/100C]AI119Temperature after pre-heating coil [1/100 °C]AI120Cold water supply temperature for cooling coil [1/100 °C]AI121Damper position outdoor damper [1/100 %]AI122Damper position recirculation [1/100 %]AI123Output voltage cooling valve2 (only combi coil)AI124OA filter restime before filtershift alarm activatedAI125EA filter restime before filtershift alarm activatedAI126Combi HT-WaterBattTemp [1/100C] Coil/ReturnAI127Rel. Humidity Extract airAI128Rel. Humidity Supply airAI129Rel. Humidity Mixed airAI130Extract Filter2 Pressure (Avr-Meas) [Pa]AI131Supply Filter Pressure (Avr-Meas) [Pa]AI132Number of Detected ZoneModulesAI133ZoneControl Operation ModeAI134ZoneModule 1 - StatusAI135ZoneModule 1 - VAV Supply 1 Actuator SetpointAI136ZoneModule 1 - VAV Supply 1 Actuator FlowAI137ZoneModule 1 - VAV Supply 2 Actuator SetpointAI138ZoneModule 1 - VAV Supply 2 Actuator FlowAI139ZoneModule 1 - VAV Extract 1 Actuator SetpointAI140ZoneModule 1 - VAV Extract 1 Actuator FlowAI141ZoneModule 1 - VAV Heating Actuator SetpointAI142ZoneModule 1 - VAV Heating Actuator FlowAI143ZoneModule 1 - VAV Cooling Actuator SetpointAI144ZoneModule 1 - VAV Cooling Actuator FlowAI145ZoneModule 1 - Room Temperature ValueAI146ZoneModule 1 - Supply Temperature ValueAI147ZoneModule 1 - Remote Setpoint OffsetAI148ZoneModule 1 - CO2/VOC ValueAI149ZoneModule 1 - RH ValueAI150ZoneModule 2 - StatusAI151ZoneModule 2 - VAV Supply 1 Actuator SetpointAI152ZoneModule 2 - VAV Supply 1 Actuator FlowAI153ZoneModule 2 - VAV Supply 2 Actuator SetpointAI154ZoneModule 2 - VAV Supply 2 Actuator FlowAI155ZoneModule 2 - VAV Extract 1 Actuator SetpointAI156ZoneModule 2 - VAV Extract 1 Actuator FlowAI157ZoneModule 2 - VAV Heating Actuator SetpointAI158ZoneModule 2 - VAV Heating Actuator FlowAI159ZoneModule 2 - VAV Cooling Actuator SetpointAI160ZoneModule 2 - VAV Cooling Actuator FlowAI161ZoneModule 2 - Room Temperature ValueAI162ZoneModule 2 - Supply Temperature ValueAI163ZoneModule 2 - Remote Setpoint OffsetAI164ZoneModule 2 - CO2/VOC ValueAI165ZoneModule 2 - RH ValueAI166ZoneModule 3 - StatusAI167ZoneModule 3 - VAV Supply 1 Actuator SetpointAI168ZoneModule 3 - VAV Supply 1 Actuator FlowAI169ZoneModule 3 - VAV Supply 2 Actuator SetpointAI170ZoneModule 3 - VAV Supply 2 Actuator FlowAI171ZoneModule 3 - VAV Extract 1 Actuator SetpointAI172ZoneModule 3 - VAV Extract 1 Actuator FlowAI173ZoneModule 3 - VAV Heating Actuator SetpointAI174ZoneModule 3 - VAV Heating Actuator FlowAI175ZoneModule 3 - VAV Cooling Actuator SetpointAI176ZoneModule 3 - VAV Cooling Actuator FlowAI177ZoneModule 3 - Room Temperature ValueAI178ZoneModule 3 - Supply Temperature ValueAI179ZoneModule 3 - Remote Setpoint OffsetAI180ZoneModule 3 - CO2/VOC ValueAI181ZoneModule 3 - RH ValueAI182ZoneModule 4 - StatusAI183ZoneModule 4 - VAV Supply 1 Actuator SetpointAI184ZoneModule 4 - VAV Supply 1 Actuator FlowAI185ZoneModule 4 - VAV Supply 2 Actuator SetpointAI186ZoneModule 4 - VAV Supply 2 Actuator FlowAI187ZoneModule 4 - VAV Extract 1 Actuator SetpointAI188ZoneModule 4 - VAV Extract 1 Actuator FlowAI189ZoneModule 4 - VAV Heating Actuator SetpointAI190ZoneModule 4 - VAV Heating Actuator FlowAI191ZoneModule 4 - VAV Cooling Actuator SetpointAI192ZoneModule 4 - VAV Cooling Actuator FlowAI193ZoneModule 4 - Room Temperature ValueAI194ZoneModule 4 - Supply Temperature ValueAI195ZoneModule 4 - Remote Setpoint OffsetAI196ZoneModule 4 - CO2/VOC ValueAI197ZoneModule 4 - RH ValueAI198CVM Phase L1 to neutral (N) voltage [V]AI199CVM Current L1 value [mA]AI200CVM Active power L1 [W]AI201CVM Phase L2 to neutral (N) voltage [V]AI202CVM Current value [mA] L2AI203CVM Active power [W] L2AI204CVM Phase L3 to neutral (N) voltage [V]AI205CVM Current value L3 [mA]AI206CVM Active power L3 [W]AI207CVM Active power three phases [W]AI208CVM Frequency value [Hz]AI209CVM Phase-phase Voltage L1 to L2 [V]AI210CVM Phase-phase Voltage L2 to L3 [V]AI211CVM Phase-phase Voltage L3 to L1 [V]AI212CCVM Cool Phase L1 to neutral (N) voltage [V]AI213CCVM Cool Current L1 value [mA]AI214CCVM Cool Active power L1 [kW]AI215CCVM Cool Phase L2 to neutral (N) voltage [V]AI216CCVM Cool Current L2 value [mA]AI217CCVM Cool Active power L2 [kW]AI218CCVM Cool Phase L3 to neutral (N) voltage [V]AI219CCVM Cool Current L3 value [mA]AI220CCVM Cool Active power L3 [kW]AI221CCVM Cool Active power three phases [W] (Low Byte)AI222CCVM Cool Frequency value [Hz]AI223CCVM Cool Phase-phase Voltage L1 to L2 [V]AI224CCVM Cool Phase-phase Voltage L2 to L3 [V]AI225CCVM Cool Phase-phase Voltage L3 to L1 [V]AI226Actual used Power (kW) Elektrik Heat Battery 1AI227Actual used Power (kW) Elektrik Heat Battery 2AI230CVM Active energy three phases [kWh]AI231CCVM Cool Active energy three phases [kWh]AI232Current EfficiencyTemp [1/100C]AI233Internal OutDoorTemp [1/100C]AI234Current SupplyTemp2 [1/100C]AI235CVM Current value L1 high byte [mA]AI236CVM Active power L1 high byte [W]AI237CVM Current value L2 high byte [mA]AI238CVM Active power L2 high byte [W]AI239CVM Current value L3 high byte [mA]AI240CVM Active power L3 high byte [W]AI241CVM Active power three phases high byte [W]AI242CVM Active energy three phases high byte [Wh]AI243CCVM Current 1 value high byte [mA]AI244CCVM Active power 1 high byte [W]AI245CCVM Current 2 value high byte [mA]AI246CCVM Active power 2 high byte [W]AI247CCVM Current 3 value high byte [mA]AI248CCVM Active 3 power high byte [W]AI249CCVM Active power three phases high byte [W]AI250CCVM Active energy three phases high byte [Wh]AI251Supply SFPII [Ws/m3 same as J/m3]AI252Extract SFPII -2 [Ws/m3 same as J/m3]AI253Combined SFP [Ws/m3 same as J/m3] HighAI254Combined SFP [Ws/m3 same as J/m3] LowAI256Actual % rel. Huminity Mixed airAI263Rel. Humidity Outdoor airAI264Rel. Humidity Exhaust airAI265Current Temperature OutdoorTempSensor 6040 (External Sens) [1/1AI266Average Outdoorflow-pressure [Pa]AI267Average Extract/Exhaustflow-pressure [Pa]AI268Average OA-Filter-pressure [Pa] DYNAMICMODEAI269Average EA-Filter-pressure [Pa] DYNAMICMODEAI270Current air temperature just before the outdoor coil of the heaAI271Average SA-Filter-pressure [Pa] DYNAMICMODEAI272Average EA2-Filter-pressure [Pa] DYNAMICMODEAI273SummerNight Time with Heat Demand [sec]AI274Timer for DX-Cool RE-1 ON-Periode [sec]AI275Timer for DX-Cool RE-2 ON-Periode [sec]AI276Timer for DX-Cool RE-3 ON-Periode [sec]AI277Timer for DX-Cool RE-4 ON-Periode [sec]AI278Counter for DX-Cool RE-1 starts per hourAI279Current Heat2 WaterBatt Temp [1/100C] Coil/ReturnAI280Counter for DX-Cool RE-3 starts per hourAI281Counter for DX-Cool RE-4 starts per hourAI282Timer for DX-Cool K1 Restart-PeriodeAI283Timer for DX-Cool K2 Restart-PeriodeAI284Timer for DX-Cool K3 Restart-PeriodeAI285Timer for DX-Cool K14Restart-PeriodeAI286Filter actual alarmstatus for OA-filter [1/100%]AI287Filter actual alarmstatus for EA-filter [1/100%]AI288OA Filter pressure for new-filter at actual flow [Pa]AI289EA Filter pressure for new-filter at actual flow [Pa]AI290Condenser Valve PowerAI291Voltage level, to condenser valveAI292Shunt Valve PowerAI293Voltage level, to shunt valveAI294Output to SteamHuminifier [1/1000 V]AI295Timer delayed heat 2AI296Average press Rotary EXC Flow Measure, Extract channelAI297HeatPump power used when heating is demanded. Otherwise CoolPowAI298Supply air fan 2 TypeAI299Supply air fan 2 Software Ver [1/100]AI300Supply air fan 2 Boot Software / HW Ver [1/100]AI301Supply air fan 2 procent output [1/100%]AI302Supply air fan 2 actual RPM [RPM]AI303Supply air fan 2 actual current output [1/100mA]AI304Supply air fan 2 actual power input [Watt]AI305Supply air fan 2 actual running time [minutes]AI306Supply air fan 2 actual running time [days]AI307Supply air fan 2 Percent to FanAI308Extract air fan 2 TypeAI309Extract air fan 2 Software Ver [1/100]AI310Extract air fan 2 Boot Software / HW Ver [1/100]AI311Extract air fan 2 procent output [1/100%]AI312Extract air fan 2 actual RPM [RPM]AI313Extract air fan 2 actual current output [1/100mA]AI314Extract air fan 2 actual power input [Watt]AI315Extract air fan 2 actual running time [minutes]AI316Extract air fan 2 actual running time [days]AI317Extract air fan 2 Percent to FanAI318Supply air fan TypeAI319Supply air fan Software Ver [1/100]AI320Supply air fan Boot Software Ver [1/100]AI321Supply air fan procent ouput [1/100%]AI322Supply air fan actual RPM [RPM]AI323Supply air fan actual current output [1/100mA]AI324Supply air fan actual running time [minutes]AI325Supply air fan actual running time [days]AI326Supply air fan Percent to FanAI327Extract air fan Boot Software Ver [1/100]AI328Extract air fan procent ouput [1/100%]AI329Extract air fan actual RPM [RPM]AI330Extract air fan actual current output [1/100mA]AI331Extract air fan actual running time [minutes]AI332Extract air fan actual running time [days]AI333Extract air fan Percent to FanAI334Extract air fan TypeAI335Extract air fan Software Ver [1/100]AI336SA filter restime before filtershift alarm activatedAI337EA filter 2 restime before filtershift alarm activatedAI338Extract air temperature after Heatpump value [1/100C]AI339Daikin:Suction air temperatureAI341Drives Compressor Drive TypeAI342Drives Compressor AOC SW versionAI343Drives Compressor MOC SW versionAI344Drives Compressor PrcOutAI345Drives Compressor RPMOutAI346Drives Compressor Power In (filtered)AI347Drives Compressor Operation DayAI348Cross-EXC pressure average, depent on flowAI351Consumed kWh High Note!: Values are calculated as (High byte)AI352Consumed kWh Low Note!: Values are calculated as (High byte) xAI353Consumed Wh High Note!: Values are calculated as (High byte) xAI354Consumed Wh Low Note!: Values are calculated as (High byte) xAI355Consumed [kWh] High. Note: Values are calculated as (High byte)AI356Consumed [kWh] Low. Note: Values are calculated as (High byte)AI357Consumed [Wh] High. Note: Values are calculated as (High byte)AI358Consumed [Wh] Low. Note: Values are calculated as (High byte) xAI365Supply air fan actual power input [Watt]AI366Extract air fan actual power input [Watt]AI390Display temperature, not in regulation PH InletAI391Display temperature, not in regulation HT1 InletAI392Display temperature, not in regulation HT2 InletAI393Display temperature, not in regulation Cmb HT InletAI450Outdoor-Damper setpoint in percentAI451Outdoor-Damper actual position in percentAI452Exhaust-Damper setpoint in percentAI453Exhaust-Damper actual position in percentAI454Exhaust-Backup-Damper setpoint in percentAI455Exhaust-Backup-Damper actual position in percentAI456Recirculation-Damper setpoint in percentAI457Recirculation-Damper actual position in percentAI458CrossByPass-Damper setpoint in percentAI459CrossByPass-Damper actual position in percentAI460Drying-Damper setpoint in percentAI461Drying-Damper actual position in percentAI462Supply-Damper setpoint in percentAI463Supply-Damper actual position in percentAI464Supply-Backup-Damper setpoint in percentAI465Supply-Backup-Damper actual position in percentAI466SmokeEvac-Damper setpoint in percentAI467SmokeEvac-Damper actual position in percentAI468SmokeByPass-Damper setpoint in percentAI469SmokeByPass-Damper actual position in percentAI470Heater 1 Setpoint in percentAI471Heater 1 Valve actual position in percentAI472Cooler Setpoint in percentAI473Cooler Valve actual position in percentAI474Heater 2 Setpoint in percentAI475Heater 2 Valve actual position in percentAI476FluidExchanger Setpoint in percentAI477FluidExchanger Valve actual position in percentAI478Preheater Setpoint in percentAI479Preheater Valve actual position in percentAI480CombiCoil Setpoint in percentAI481CombiCoil Valve actual position in percentAI482Opt7 Setpoint in percentAI483Opt7 Valve actual position in percentAI484Extract-Damper setpoint in percentAI485Extract-Damper actual position in percentAV1Manual Operation Mode [GUI]AV2Fan Regulation ModeAV14Offset for Sup/Ext Motor Slave and CO2 Reg [1/100%]AV19AR_CO2 Regulator MinFlow [l/s]AV20AR_CO2 Regulator MaxFlow [l/s]AV21AR_CO2 Regulator SupFlow Offset [1/100%]AV22AR_CO2 ppm AlarmLimet Set [ppm]AV23AR_CO2 Regulator P-Band [ppm]AV24AR_CO2 Regulator I-Time [sec]AV25FAN-Opt Supply Regulator MinFlow [l/s]AV26FAN-Opt Supply Regulator MaxFlow [l/s]AV27FAN-Opt Extract Regulator MinFlow [l/s]AV28FAN-Opt Extract Regulator MaxFlow [l/s]AV29FAN-Opt Regulator ExtFlow Offset [1/100%]AV30Supply Motor Reg I-Time Set [Sec]AV31Extract Motor Reg I-Time Set [Sec]AV32User Supply Motor Percent Set at Fire [%]AV33User Extract Motor Percent Set at Fire [%]AV34HiSpeed AfterRun TimeOut Set [min]AV35FlowOutTempComp PercentSet [1/100%]AV36FlowOutTempComp StartTempSet [1/100C]AV37FlowOutTempComp StopTempSet [1/100C]AV38Actual yearAV39Actual monthAV40Actual dateAV41Actual hourAV42Actual minutesAV43Actual secondsAV44Extended Drift Start Day (0-Mon..6-Sun)AV45Extended Drift Start Minute (Hour*60+Min)AV46Extended Drift Stop Day (0-Mon..6-Sun)AV47Extended Drift Stop Minute (Hour*60+Min)AV50Supply LoSpeed DuctPressure Set [Pa]AV51Supply MediumSpeed DuctPressure Set [Pa]AV52Supply HiSpeed DuctPressure Set [Pa]AV53Extract/Exhaust LoSpeed DuctPressure Set [Pa]AV54Extract/Exhaust MediumSpeed DuctPressure Set [Pa]AV55Extract/Exhaust HiSpeed DuctPressure Set [Pa]AV56User Supply Flow-LoSpeedSet [l/s]AV57User Supply Flow-MedSpeedSet [l/s]AV58User Supply Flow-HiSpeedSet [l/s]AV59User Extract/Exhaust Flow-LoSpeedSet [l/s]AV60User Extract/Exhaust Flow-MedSpeedSet [l/s]AV61User Extract/Exhaust Flow-HiSpeedSet [l/s]AV62Supply Motor Lowspeed [1/100%], FFSAV63Supply Motor Mediumspeed [1/100%], FFSAV64Supply Motor Highspeed [1/100%], FFSAV65Extract/Exhaust Motor Lowspeed [1/100%], FFSAV66Extract/Exhaust Motor Mediumspeed [1/100%], FFSAV67Extract/Exhaust Motor Highspeed [1/100%], FFSAV68AR_CO2 Regulator User SetPoint for Lo timer Periode (HI AR_CO2AV69AR_CO2 Regulator User SetPoint for Medium timer Periode(Med AR_AV70AR_CO2 Regulator User SetPoint for Hi timer Periode(LO AR_CO2 VAV71Extract/Exhaust Min Flow for DuctReg [l/s]AV72Extract/Exhaust Max Flow for DuctReg [l/s]AV73Supply Min Flow for DuctReg [l/s]AV74Supply Max Flow for DuctReg [l/s]AV75TempDiff2 between Set/Meas Alarm Limit SA [1/100C]AV76TempDiff between Set/Meas Alarm Limit SA [1/100C]AV77P-Band for Supply TempReg heating [1/100C]AV78SA I-Time for Reg on Heat2 Out [sec]AV79SA I-Time for supply tempReg Heat pump while heating [sec]AV82Huminifier Supply Setpoint [1/100%] RHAV102Current external Modbus OutDoorTemp [1/100C]AV103Current external Modbus RoomTemp [1/100C]AV104Customer set of alarmlimit modbus outdoorsensor minAV105Customer set of alarmlimit modbus outdoorsensor maxAV106Customer set of alarmlimit modbus roomsensor minAV107Customer set of alarmlimit modbus roomsensor maxAV108BMS-modes only avalable after activation of pysical input 'OperAV133Temp-Regulationmode0-Sup, 1-Ext, 2-Room, 3-Sup/Ext -DiffAV134TempSet for actual RegMode [1/100C]AV135Min Allowed SupplyTemp [1/100C]AV136Max Allowed SupplyTemp [1/100C]AV137TempDiff Set between Extract/Supply TempRegMode = 3AV140SA I-Time for Reg on CoolOut [sec]AV141SA I-Time for Reg on EXC Out [sec]AV142SA I-Time for Reg on Heat Out [sec]AV143SA I-Time for SupTempReg Flow DownReg Out [sec]AV144TempDiff between Set/Meas Alarm Limit EA [1/100C]AV145P-Band for Extract TempReg heating [1/100C]AV146EA I-Time for Reg on CoolOut [sec]AV147EA I-Time for Reg on EXC Out [sec]AV148EA I-Time for Reg on Heat Out [sec]AV149EA I-Time for ExtTempReg Flow DownReg Out [sec]AV150Sum/Wint-TempComp Winter Lo OutDoor TempSet [1/100C]AV151Sum/Wint-TempComp Winter Hi OutDoor TempSet [1/100C]AV152Sum/Wint-TempComp Summer Lo OutDoor TempSet [1/100C]AV153Sum/Wint-TempComp Summer Hi OutDoor TempSet [1/100C]AV154Sum/Wint-TempComp Winter compensation [1/100C]AV155Sum/Wint-TempComp Summer compensation [1/100C]AV156Summer/Winter Mode: 0 - 4AV157OutdoorTemp for start WinterMode (SW_Mode = 1)AV158OutdoorTemp for start SummerMode (SW_Mode = 1)AV159Month for Start WinterMode (SW_Mode = 2)AV160Date for Start WinterMode (SW_Mode = 2)AV161Month for Start SummerMode (SW_Mode = 2)AV162Date for Start SummerMode (SW_Mode = 2)AV163StartTemp for Nightheat Function [1/100 C]AV164StopTemp for Nightheat Function [1/100 C]AV165SupplyTempSet for Internal FireAlr [1/100C]AV166ExtractTempSet for Internal FireAlr [1/100C]AV167Cool-FlowForce Percent Set [1/100 %]AV168Min OutDoorTemp for CoolAgg. ActiveAV169Min SupplyTemp for Cool (Used for RoomReg)AV170SummerNight Ext/Room Temp Start [1/100C]AV171SummerNight Ext/Room Temp Stop [1/100C]AV172SummerNight OutDoor Temp Start [1/100C]AV173SummerNight SupTemp Reg Set [1/100C]AV174SummerNight StartTime [Min] 20:00 - 02-00, in server checkedAV175SummerNight StopTime [Min] 03:00 - 08:00, in server checkedAV176Min ExhaustTempSet for Cross EXC [1/100C]AV177P-Band for BypaasReg for Cross EXC [1/100C]AV178Fluid EXC PumpFunc: 0 - 3AV179Fluid EXC PumpStartTemp. Is usedAV180Fluid EXC TempDiff Alarm Set AlarmAV181HWB1 Upstart PowerSet [1/100%]AV182HeatWaterBatt 1 PumpFunc: 0 - 3AV183HeatWaterBatt 1 PumpStartTemp. Is used together with WaterPumpFAV184SetVal for HWB1 AntiFrost Reg when Agg. = Stop [1/100C]AV185SetVal for HWB1 AntiFrost Reg when Agg. = Drift [1/100CAV186HW1 P-Band for AntiFrost Reg [1/100C]AV187SetVal for HWB1 AntiFrost TempAlarm [1/100C]AV188CoolWater PumpFunc: 0 - 3AV189CoolWaterBatt PumpStartTemp. Is used together with WaterPumpFunAV190Filter Pressure Alr Limit for OA-Filter (static mode)AV191Filter Pressure Alr Limit for EA-Filter (static mode)AV192Filter Pressure Alr Limit for OA-Filter (dynamic mode)AV193Filter Pressure Alr Limit for EA-Filter (dynamic mode)AV194Alarm Mail Config: 0 - Mail are not send 1 - Mail on A-Alarm 2AV195UserRE Function: 0 B-Alarm 1 Lo Speed indicator 2 Hi Speed indiAV196HWB2 Upstart PowerSet [1/100%]AV197HWB 2 PumpFunc: 0 - 3AV198HWB 2 PumpFunc start TemperatureAV199SetVal for HWB2 AntiFrost Reg when Agg. = Stop [1/100C]AV200SetVal for HWB2 AntiFrost Reg when Agg. = Drift [1/100C]AV201HW2 P-Band for AntiFrost Reg [1/100C]AV202SetVal for HWB2 AntiFrost TempAlarm [1/100C]AV203Setpoint PreheaterAV204PreHeater SetVal for AntiFrost TempAlarm [1/100C]AV205PreHeater SetVal for AntiFrost Reg when Agg. = Stop [1/100C] PrAV206Preheater Heatpower Percent under startup [1/100%]AV207Pre-heating coil P-band for frost protection control [1/100°C]AV208Preheat PumpStart OutDoorTemp. Is used together withAV209SetVal for Preheat AntiFrost Reg when Agg. = Drift [1/100C] HeaAV210Mode for PumpFunc: 0 - 3AV211Min OutDoorTemp for CoolAgg. Relay 1 ActiveAV212Min OutDoorTemp for CoolAgg. Relay 2 ActiveAV213Min OutDoorTemp for CoolAgg. Relay 3 ActiveAV214Min OutDoorTemp for CoolAgg. Relay 4 ActiveAV215Min air temp at outdoor coil for HeatPump operate Relay1AV216Min air temp at outdoor coil for HeatPump operate Relay2AV217Min air temp at outdoor coil for HeatPump operate Relay3AV218Min air temp at outdoor coil for HeatPump operate Relay4AV219Fluid EXC SetVal for AntiFrost Reg when Agg. = Stop [1/100C]AV220Fluid EXC SetVal for AntiFrost Reg when Agg. = Drift [1/100C]AV221Fluid EXC P-Band for AntiFrost Reg [1/100C]AV222Fluid EXCSetVal for AntiFrost TempAlarm [1/100C]AV223Extern Signal Greenzone, SupplyAV224Extern Signal Greenzone, ExtractAV225HeatWater VDC out function(Out 12): 0->0-10V, 1->2-10VAV226Pressure percent over calibrationAV227Stop temperature freshair coolingAV228Stop cooling over roomtemperatureAV229Heat2 limiting type 1Room, 2 OutdoorAV230Startdifference temperatureAV231Stepsize limiting roomtempAV232DownCounter for HeatStart allowed [sec]AV233Offset in % of Flow if Heat2 is onAV234Timeset delayed Heat 2AV235Set Change Airflow RecirceAV236Temperature for start with open damperAV237Timeset for CO2 DX-Cooling-Aggregate from 0 ..100%AV238SA SummerNight Motor percent SetAV239EA SummerNight Motor Flow SetAV240SA SummerNight Motor Flow SetAV241EA SummerNight Motor Press SetAV242SA SummerNight Motor Press SetAV243EA SummerNight Motor percent SetAV244SummerNight Motor percent SetAV248AR_CO2 Max Value Mod Rec/Rema1000 ModeAV249AR_CO2 Min Value Mod Rec/Rema1000 ModeAV250Setpoint % Humidity Extract RH, DehumidityAV257Min FreshAir part in percentAV258Filter Pressure Alr Limit for SA-Filter (static mode)AV259Filter Pressure Alr Limit for EA-Filter2 (static mode)AV260Filter Pressure Alr Limit for SA-Filter (dynamic mode)AV261Filter Pressure Alr Limit for EA-Filter2 (dynamic mode)AV262ZoneModule 1 - Room Temperature SetpointAV263ZoneModule 1 - Minimum Supply TemperatureAV264ZoneModule 1 - Maximum Supply TemperatureAV265ZoneModule 1 - Room CO2 SetpointAV266ZoneModule 1 - Room RH SetpointAV267ZoneModule 1 - VAV Supply PIR Min Air FlowAV268ZoneModule 2 - Room Temperature SetpointAV269ZoneModule 2 - Minimum Supply TemperatureAV270ZoneModule 2 - Maximum Supply TemperatureAV271ZoneModule 2 - Room CO2 SetpointAV272ZoneModule 2 - Room RH SetpointAV273ZoneModule 2 - VAV Supply PIR Min Air FlowAV274ZoneModule 3 - Room Temperature SetpointAV275ZoneModule 3 - Minimum Supply TemperatureAV276ZoneModule 3 - Maximum Supply TemperatureAV277ZoneModule 3 - Room CO2 SetpointAV278ZoneModule 3 - Room RH SetpointAV279ZoneModule 3 - VAV Supply PIR Min Air FlowAV280ZoneModule 4 - Room Temperature SetpointAV281ZoneModule 4 - Minimum Supply TemperatureAV282ZoneModule 4 - Maximum Supply TemperatureAV283ZoneModule 4 - Room CO2 SetpointAV284ZoneModule 4 - Room RH SetpointAV285ZoneModule 4 - VAV Supply PIR Min Air FlowAV286CombiHeatWaterBatt Upstart PowerSet [1/100%]AV287CombiWaterBatt PumpFunc: 0 - 3AV288CombiBatt PumpStartTemp. Is used together with WaterPumpFunc =AV289Combi PumpFunc=3 then pump only starts when heatingpower exceedAV290SetVal for CombiBatt AntiFrost Reg when Agg. = Stop [1/100C] HeAV291SetVal for CombiBatt AntiFrost Reg when Agg. = Drift [1/100C] HAV292Combi P-Band for AntiFrost Reg [1/100C]AV293SetVal for CombiBatt AntiFrost TempAlarm [1/100C]AV294Max % CoolPower for Dehumidity without DewPointSensorAV295StartTemp for Nightheat Function ROH under 5 deg [1/100 C]AV296StopTemp for Recirc heat Function ROH under 5 deg [1/100 C]AV297SwitchTemp for Nightheat Function ROH [1/100 C]AV304Mod. recirce max FreshAir part, Damper positionAV305Risetime 0..100%, in secAV306Night lowering temperatur correctionAV307Alarmlevel in percent, if dustyAV308Alarmlevel in percent if froozenAV309Fluid EXC PumpFunc=3 then pump only starts when EXCpower exceedAV310Cool PumpFunc=3 pump only starts when Coolpower exceeds this seAV311HWB 2 PumpFunc=3 then pump only starts when heatingpower exceedAV312When PumpFunc=3 then pump only starts when heatingpower exceedsAV313Pressure to start deicing of cross Exc. [Pa]AV314Time for deicing cross exc. when pressure monitored.AV315LoPressSens-1 AlarmLimit [1/100 Bar]AV316HiPressSens-1 AlarmLimit [1/100 Bar]AV317LoPressSens-2 AlarmLimit [1/100 Bar]AV318HiPressSens-2 AlarmLimit [1/100 Bar]AV319Heat 2 limited over this TemperaturAV320AR_CO2 Regulator Fan Min % Setpoint [1/100%]AV321AR_CO2 Regulator Fan Max % Setpoint [1/100%]AV322Temperature Offiset Slider from Web [1/100C]AV323Drives Compressor Setpoint/PrcSetAV324IOC Digital input Heatpump Frost / LubricationBI0Operation ON/OFFBI1External stopBI2External HiSpeedBI3Extended low speed –> ActiveBI4Extended high speed –> ActiveBI5Power to electric heating coil reduced due to low flowBI6Summer night cooling is activeBI7Reset parameters for summer night cooling new calculation is inBI8Winter temperature compensation is activeBI9Summer temperature compensation is activeBI10Summer/winter actual status OFF –> winter operation ('0') ONBI11Recirculation status ('1' = Open damper)BI12Exercising heat exchanger –> ActiveBI13Signal to cross-flow exchanger reduced (frost protection)BI14Supply duct pressure controller reduced to min. FlowBI15Supply duct pressure controller increased to max. FlowBI16Extract/Exhaust duct pressure controller reduced to min. FlowBI17Extract/Exhaust duct pressure controller increased to max. FlowBI18Cooling recovery –> statusBI19Circulation pump on heating coil: Frost protection –> ActiveBI20Circulation pump on heating coil: Pump exercising –> ActiveBI21CoolWaterCoil PumpExercise activeBI22Signal to heating coil reduced (insufficient flow) –> ActiveBI231-when min. supply temperature control is active.Only active whBI241-when max. supply temperature control is active.Only active whBI25Circulation pump on heat recovery coil: Pump exercising –> AcBI26Heating relay 1BI27Cool Relay 1BI28Circulation pump on Fluid EXC coil: Pump –> RunningBI29At least one active alarmBI30Alarm relay 1 (A-alarm)BI31Alarm relay 2 (B-alarm)BI32Fire alarm signal (room sensor)BI33Smoke Alarm Signal (Sensor in duct)BI35Filter alarm for outdoor filter (pressure drop above set limit)BI36Filter alarm for extract filter (pressure drop above set limit)BI37Supply temperature sensor – sensor faultBI38Extract temperature sensor – sensor faultBI39Outdoor temperature sensor – sensor faultBI40Room temperature sensor – sensor faultBI41Exhaust temperature sensor – sensor faultBI42Heating coil temperature sensor – sensor faultBI43Fluid EXC temperature sensor – sensor faultBI44Heating coil frost alarmBI45Cooling shared alarmBI46Cooling digital alarm 1 inputBI47Cooling digital alarm 2 inputBI48Cooling digital alarm 3 inputBI49Cooling digital alarm 4 inputBI50Supply motor ON/OFFBI51Supply Motor AlarmBI57Supply air fan ripple alarmBI59Extract/Exhaust motor ON/OFFBI60Extract Motor AlarmBI66Extract/exhaust air fan 2 Ripple AlarmBI68Rotary heat exchanger – motor control ON/OFFBI69Rotary heat exchanger – reset signalBI70Rotary heat exchanger – rotation directionBI71Rotary heat exchanger rotation alarmBI72Rotary heat exchanger low voltage alarmBI73Rotary heat exchanger hihg voltage alarmBI74Rotary heat exchanger high currentBI75Rotary heat exchanger temperature alarmBI76Rotary heat exchanger rotation signalBI77Rotary heat exchanger torque overloadBI78Status Brandstop inputBI79Add on sensor 1 - Sensor faultBI80Add on sensor 2 - Sensor faultBI81Add on sensor 3 - Sensor faultBI82Add on sensor 4 - Sensor faultBI83Alarm frost thermostat alarm (digital input)BI84Heating coil 2 - Frost control activeBI85Heating coil 2 - Circulation pump, pump exercising activeBI86Heating coil 2 - Return sensor - Sensor faultBI87Heating coil 2 - Frost alarmBI88Pre-heating coil - Frost alarmBI89Pre-heating coil - Frost protection activeBI90Pre-heater Pump exercise activeBI91Preheater - heat relay 1BI92Pre-heating coil - Overheating faultBI93Pre-heating coil - Output reduction, low air volumeBI94Returnwater sensor errorBI95Alarm - Heat recovery efficiency below alarm limitBI96Alarm Atv Comm SupplyBI97Alarm Atv Comm ExtractBI98Alarm Atv FC SupplyBI99Alarm Atv FC ExtractBI100Frost alarm fluid-coupled coil (CoilEXC)BI101Contact error DeIcer El-BatteryBI102DeIcer overheatingsalarm El-BatteryBI103DeIcer power reduction alarm El-BatteryBI104Alarm - pressure transmitter not calibrated (Ice guard rotor heBI105Alarm - pressure transmitter not configured (Ice guard rotor heBI106Coolrecovery over damper active ('1' = Open damper)BI107Cooling stopped by room temperatureBI108Signal for the 4-way-valve in HeatPumpBI109Status bit: De-icing of heatpumpBI110Alarm - rotor heat exchanger blocked by ice (high pressure overBI111Alarm - rotor heat exchanger blocked by dirt (high pressure oveBI112Flow is change heat2 activeBI113Status of delaytimer Heat 2BI114Limit of heat 2 is avoidBI115Blocking Heat2 in recirkulation mode = AktivatedBI116Status of low flow under 100% recirculationBI117Closed damper running activeBI118Max. raise-/fall-time is activatedBI119Supply air fan 2 high current limitBI120Supply air fan 2 voltage low alarmBI121Supply air fan 2 voltage high alarmBI122Supply air fan 2 high current limit alarmBI123Supply air fan 2 temperature alarmBI124Supply air fan 2 alarm for phase errorBI125Supply air fan 2 Direction errorBI126Supply air fan 2 alarm for blocked rotorBI128Extract/exhaust air fan 2 voltage low alarmBI129Extract/exhaust air fan 2 voltage high alarmBI130Extract/exhaust air fan 2 high current limit alarmBI131Extract/exhaust air fan 2 temperature alarmBI132Extract/exhaust air fan 2 alarm for phase errorBI133Extract/exhaust air fan 2 Direction errorBI134Extract/exhaust air fan 2 alarm for blocked rotorBI135Alarm SA2 Controler Comm AlarmBI136Alarm EA2 Controler Comm AlarmBI137Supply air fan high current limitBI138Supply air fan voltage low alarmBI139Supply air fan voltage high alarmBI140Supply air fan high current limit alarmBI141Supply air fan temperature alarmBI142Supply air fan alarm for phase errorBI143Supply air fan Direction errorBI144Supply air fan alarm for blocked rotorBI145Extract/exhaust air fan high current limitBI146Extract/exhaust air fan voltage low alarmBI147Extract/exhaust air fan voltage high alarmBI148Extract/exhaust air fan high current limit alarmBI149Extract/exhaust air fan temperature alarmBI150Extract/exhaust air fan alarm for phase errorBI151Extract/exhaust air fan Direction errorBI152Extract/exhaust air fan alarm for blocked rotorBI153OJ-DV Supply Comm AlarmBI154OJ-DV Extract Comm AlarmBI155TTH-6202 communication errorBI156Communication Alarm Belimo Smoke DamperBI157Position Alarm Belimo Smoke DamperBI158Extention IO-Modul no 1 - communication errorBI159Extention IO-Modul no 2 - communication errorBI160Extention IO-Modul no 3 - communication errorBI161Extention IO-Modul no 4 - communication errorBI162Extention IO-Modul no 5 - communication errorBI163Extention IO-Modul no 6 - communication errorBI164Extention IO-Modul no 7 - communication errorBI165Extention IO-Modul no 8 - communication errorBI166Supplysensor 2 alarmBI167Addon sensor 1 - Sensor errorBI168Addon sensor 2 - Sensor errorBI169Addon sensor 3 - Sensor errorBI170Addon sensor 4 - Sensor errorBI171SupMotor AlarmBI172ExtMotor AlarmBI173Combi coil; Cooling relay no. 2 aktiveBI174Flag for Rise-Falltime active DX-CO2-CoolingBI176Preheater - heat relay 3BI177State of extern start inputBI178Supply air fan EEprom errorBI179Supply air fan 2 EEprom errorBI180Extract/exhaust air fan EEprom errorBI181Extract/exhaust air fan 2 EEprom errorBI182Sensor alarm TTH6040 no ComBI183Low oil level cooling compressorBI184Common-Alarm circulationpumpsBI185Common-Alarm SupplyfanBI186Common-Alarm ExtractfanBI187Common-Alarm Supply duct/flowBI188Common-Alarm Extract duct/flowBI189Common-Alarm ExchangerBI190Common-Alarm antifreezeBI191Common-Alarm El-BatteriesBI192Common-Alarm Temperatures low/highBI193Common-Alarm Supply FilterBI194Common-Alarm Extract FilterBI195Common-Alarm TemperaturesensorsBI196Common-Alarm CoolingBI197Common-Alarm Dampers BelimoBI198Common-Alarm Internals / SysModBusBI199Value in Control Reg BMS CtrlBI200State of extern lowspeed inputBI201BMS-Sensor Room Out of RangeBI202BMS-Sensor Outdoor Out of RangeBI203Fire mann stopBI204Smoke evacuation activatedBI205Smoke evacuation fan alarmBI206Output for supply air damper aktiveBI207Big Damper relay SupplyBI208Recirce DamperSignalBI209External OutDoorTemp -Sensor ErrorBI210PreHeatWaterBatt Sensor AlarmBI211Cooling water supply temperature - sensor errorBI212Heat Relay 21 (ExtMod-Reserve)BI213Heat Relay 22 (ExtMod-Reserve)BI214Heat Relay 23 (ExtMod-Reserve)BI215Heat Relay 24 (ExtMod-Reserve)BI216Heat Relay 25 (ExtMod-Reserve)BI217Heating relay26 (ExtMod-Reserve)BI218Pump relay combi coil activatedBI219Electric coil: High temperature alarm signalBI220Electric coil: Relay stuckBI221Electric coil 2: High temperature alarm signalBI222Electric coil 2: Relay stuckBI223Alarm - Time is out for filter change supply air filterBI224Alarm - Time is out for filter change extract air filterBI225Extended medium speed –> ActiveBI226Preheater - heat relay 2BI229Supply air fan, Power limitBI230Extract/exhaust air fan, Power limitBI233Supply air fan2 Ripple AlarmBI234Extract/exhaust air fan, Intern StopBI235Supply air fan2 Intern StopBI236Extract/exhaust air fan 2, Intern StopBI237CombiBattery heat usableBI238CombiBattery cool usableBI239ElPrehheat Overheat StateBI240Contact error Preheater El-BatteryBI244Extract/exhaust air fan 2 high current limitBI245B-Alr SupFan is stoppedBI246Smoke Evac Damper not in positionBI247Smoke Bypass Damper not in positionBI248Communication Alarm DPTH1BI249Communication Alarm DPTH2BI250Communication Alarm DPTH3BI251Communication Alarm DPTH4BI252Communication Alarm DPTH5BI253Filter Alarm for SA-Filter (pressure above Limit)BI254Filter Alarm for EA2-Filter (pressure above Limit)BI255Alarm from Supplyfilter timerBI256Alarm from Extractfilter2 timerBI257ZoneControl PIR ActiveBI258ZoneModule 1 - WindowFrost ValueBI259ZoneModule 1 - PIR ActiveBI260ZoneModule 1 - Room Temp Sensor ErrorBI261ZoneModule 1 - Supply Temp Sensor ErrorBI262ZoneModule 2 - WindowFrost ValueBI263ZoneModule 2 - PIR ActiveBI264ZoneModule 2 - Room Temp Sensor ErrorBI265ZoneModule 2 - Supply Temp Sensor ErrorBI266ZoneModule 3 - WindowFrost ValueBI267ZoneModule 3 - PIR ActiveBI268ZoneModule 3 - Room Temp Sensor ErrorBI269ZoneModule 3 - Supply Temp Sensor ErrorBI270ZoneModule 4 - WindowFrost ValueBI271ZoneModule 4 - PIR ActiveBI272ZoneModule 4 - Room Temp Sensor ErrorBI273ZoneModule 4 - Supply Temp Sensor ErrorBI274Cool Relay 2BI275Cool Relay 3BI276Cool Relay 4BI277Alarm smoke evacuation damper is activated ('1' = Open damper)BI278Heat Relay 2 (ExtMod-Reserve)BI279Combi coil - Return sensor - Sensor faultBI280Combi coil - Frost alarmBI281Combi coil - Frost protection activeBI282Combi coil - Circulation pump, pump exercising activeBI283Combi coil; Cooling relay aktiveBI284Combi coil; Heating relay aktiveBI286Supply Fan wall Alarm (B)BI287Extract Fan wall Alarm (B)BI288Extract digital damper output signal ('1' = Open damper)BI289Exhaust digital damper output signal ('1' = Open damper)BI290Exhaust backup digital damper output signal ('1' = Open damper)BI291Supply backup digital damper output signal ('1' = Open damper)BI292SupBackupMotor AlarmBI293ExhBackupMotor AlarmBI294Sensor alarm TTH6040 OutDoor no Com (port A)BI295Supply Backup Motor AlarmBI296Exhaust Backup Motor AlarmBI297Reduction of cross-flow exchanger due to de-icing; deicing starBI298Electric coil 2 - Output reduction active due to low flowBI299Extract/exhaust air fan RipplealarmBI300Supply air fan, Intern StopBI301Preheater Frost Alarm CoolingBI302Status frost thermostat alarm (digital input)BI303Humidifier alarm statusBI304Freshair cooling is stoppedBI305Communication CVM Mini MeterBI306Communication CVM Mini Cool MeterBI307A-Alr Comm Error HMI_20TBI308Alarm, Fire damper not closedBI309Alarm, Fire damper not openedBI310Fire damper test is ongoingBI311Extract air temperature after Heatpump, sensor errorBI312Start of AHU is blocked, if mounted and openBI313Firethermostat alarm via El-Heater inputBI314Firethermostat alarm via El-Pre-Heater inputBI315Daikin EVKit communications AlarmBI316Daikin 'warning' bits from register 30003BI317Daikin 'alarm' bits from register 30003BI318Daikin 'error' bits from register 30003BI320Drives Compressor communication alarmBI321Drives Compressor high current alarmBI322Drives Compressor low voltage alarmBI323Drives Compressor high voltage alarmBI324Drives Compressor high temperature alarmBI325Drives Compressor compressor alarmBI326Drives Compressor rotor blockedBI327Drives Compressor current limit alarmBI328Drives Compressor voltage limit alarmBI329Drives Compressor rotor direction alarmBI330Drives Compressor Eeprom errorBI331Drives Compressor internal StopBI332Drives Compressor Earth fault alarmBI333Drives Compressor Motor phase alarmBI334Drives Compressot MOC communication errBI335Drives Compressor 24V overload alarmBI336Drives Compressor internal bootloader alarmBI337Drives Compressor internal com alarmBI338Drives Compressor Motor overheat alarmBI339Drives Compressor Start up alarmBI340Drives Compressor Pressure relax alarmBI341Drives Compressor Max start alarmBI342Drives Compressor Min run time alarmBI343Drives Compressor OverloadedBI348Heat pump deicing not correctBI349Heat pump water temp alarmBI350State of the Heat pump Oil/Defrost inputBI352Alarm Counterflow EXC Deicing is active for too long timeBI353Filter calibration completed OA (valid filter data)ONLY IF 'DYNBI354Filter calibration completed SA (valid filter data)ONLY IF 'DYNBI355Filter calibration completed EA1 (valid filter data)ONLY IF 'DYBI356Filter calibration completed EA2 (valid filter data)ONLY IF 'DYBI357Pre-heating coil - Return sensor - Sensor faultBI358Drive Compressor ExistflagBV0Alarm reset signal (AutoReturn to zero)BV1Cooling recovery: ON/OFFBV2Summer night cooling: ON/OFFBV3Summer/winter temp. compensation: ON/OFFBV4Flow/outdoor temperature compensation: ON/OFFBV5Recirculation: ON/OFF ('1' = Open damper)BV6Forced flow with cooling demand: ON/OFFBV7Automatic summer/winter time: ON/OFFBV8Input for forced high speedBV9Run-on time for forced high speed activeBV10Start manual zero calibration (can be used together with automaBV11Automatic zero calibration: ON/OFFBV12Dynamic filter alarm: ON/OFF OFF static limit on dynamic limitBV13Start filter calibration. Is automatically reset to zero (OFF)BV15Activate outdoor temperature from BMSBV16Activate room temperature from BMSBV17Hot water supply is available for the combi coilBV18Cold water supply is available for the combi coilBV19Force recirc via Ext. Modbus ('1' = Open damper)BV20Enable Modbus Force recirc signalBV21Enable combi coil for control via external Modbus [1=Modbus/0=DBV22Filter (OA) Dynamic Alarm function ON/OFF OFF -> Static Limit OBV23Filter (SA) Dynamic Alarm function ON/OFF OFF -> Static Limit OBV24Filter (EX) Dynamic Alarm function ON/OFF OFF -> Static Limit OBV25Filter (EX2) Dynamic Alarm function ON/OFF OFF -> Static LimitBV26Rotary heatexchanger, turn ratation direction to counter clockBV27Summer Night Cooling activated in low speedBV28External high speed start signalBV29Drive Compressor MountflagBV30Input for forced medium speedBV31Limit the first step between min / max SA-BattFlow El-Heater 1BV32Limit the first step between min / max SA-BattFlow El-Heater 2BV33Limit the first step between min / max SA-BattFlow El- PreheateCAL0Calendar #1CAL1Calendar #2CAL2Calendar #3NC0NC 00 A-AlarmNC1NC 01 B-AlarmSCH0Schedule #1
Integration notes
- Built from the EDE export (B.I.G.-EU layout 2.3, 19/02/2026). The EDE has no read/write column, so access is inferred: AV/BV writable, AI/BI read-only.
- Object names are the controller's long texts, cut off at about 63 characters as in the EDE; the description holds the short internal tag.
- Many values are scaled: names marked [1/100C] or [1/100%] carry hundredths (2150 = 21.50).
- Units come from the EDE unit codes; a few names state a different unit in brackets (for example power named [kW] with the code for watts).
- Four object names contain a semicolon in the EDE (BI 173, 283, 284, 297); they are kept whole.
- The EDE does not say which BACnet transport the controller uses; check it on site.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
How many BACnet points does the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 have?
This list has 979 BACnet objects: 365 analog inputs, 245 analog values, 330 binary inputs, 33 binary values, 3 calendars, 2 notification classs, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.
Which OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet points are writable?
282 of the 979 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet documentation?
The source is OJ Air Plus EDE file 670203_EDE_AirPlus_SW109 (670203), revision 19/02/2026, published free by OJ Electronics at https://ojelectronics.com/controllers-sensors/wp-admin/admin-ajax.php?action=productdownload&media_id=70102341&filename=670203_EDE_AirPlus_SW109.csv.
What are the minimum BACnet points to integrate the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?
Start with AV 108 BMS-modes only avalable after activation of pysical input 'Oper (BMS run mode; needs the physical operation input); AV 134 TempSet for actual RegMode [1/100C] (Temperature setpoint for the active control mode); BV 0 Alarm reset signal (AutoReturn to zero) (Alarm reset (returns to 0 by itself)); AI 0 Actual operating mode 000-099 Unit stopped 100-199: Unit in low (Actual operating mode code); BI 0 Operation ON/OFF (Operation on/off status); AI 16 Current SupplyTemp [1/100C] (Supply air temperature, 1/100 °C); AI 5 Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u (Actual supply airflow); BI 30 Alarm relay 1 (A-alarm) (A-alarm relay (critical alarm)); BI 31 Alarm relay 2 (B-alarm) (B-alarm relay (non-critical alarm)).
How do I enable BMS control of the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?
AV 108 sets the BMS run mode, but only after the physical operation input is activated (per the object name).
Can the BMS supply sensor values to the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?
Outdoor and room temperature can come from the BMS: write AV 102 / AV 103 and switch them in with BV 15 / BV 16.
How do I check these points on the real OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More OJ Electronics BACnet points lists
- Zone ventilation controller (VAV zone master)
OJ Electronics OJ GreenZone ZoneMaster, SW 3.47
OJ Electronics GreenZone ZoneMaster demand-controlled ventilation masters with software 3.47, including their ZoneModules.
Also known as: OJ-ZoneMaster, ZoneMaster, OJ Green Zone, GreenZone, OJ ZoneControl, 67851 - Compressor frequency drive
OJ Electronics OJ-DC compressor drive
OJ Electronics OJ-DC drives for compressors in air handling units, heat pumps and chillers.
Also known as: OJ-DC, OJ DC, OJ Drives DC, 67958B - Rotary heat exchanger drive (energy recovery wheel)
OJ Electronics OJ-DRHX rotary heat exchanger drive
OJ Electronics OJ-DRHX drives for rotary heat exchanger wheels in air handling units.
Also known as: OJ-DRHX, OJ DRHX, DRHX, 67854 - EC/PM fan motor frequency drive
OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive
OJ Electronics OJ-DV ventilation drives for EC/PM fan motors, first generation and GEN II.
Also known as: OJ-DV, OJ DV, OJ-DV GEN II, DV GEN II, OJ Drives DV, 670092, 67855
Source: OJ Air Plus EDE file 670203_EDE_AirPlus_SW109 · 670203 · rev. 19/02/2026. Object names, instances and units are reproduced as published; descriptions are our own.