Air handling unit controller · BACnet points list

OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet points list

Updated 12 November 2026

Short answer

The OJ Air Plus is an air handling unit controller with a native BACnet server. Its EDE file lists close to a thousand objects: Analog Inputs for measured temperatures, pressures, flows and outputs; Analog Values for setpoints and configuration; Binary Inputs for status and alarm flags; Binary Values for function switches and BMS commands. Many objects only matter when the matching function or module is fitted.

This page lists 979 BACnet objects for the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 — 282 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.

Manufacturer
OJ Electronics
Model
OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
979 (282 writable)
Transport
—
Firmware
SW 1.09
Default device instance
15530
Also known as
OJ Air Plus, OJ-Air Plus, AirPlus, EXcon-Plus, EXcon Plus, 670203
Source document
OJ Air Plus EDE file 670203_EDE_AirPlus_SW109 · 670203 · rev. 19/02/2026
Download CSV 979 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.

BMS integration notes: OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09

Integration in brief

Read the unit state from AI 0 and BI 0, the temperatures and flows from the AI block, and the two alarm relays (BI 30 A-alarm, BI 31 B-alarm). BMS run modes go through AV 108, which only works after the physical operation input is activated; BV 0 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 108BMS-modes only avalable after activation of pysical input 'OperBMS run mode; needs the physical operation inputWrite
AV 134TempSet for actual RegMode [1/100C]Temperature setpoint for the active control modeWrite
BV 0Alarm reset signal (AutoReturn to zero)Alarm reset (returns to 0 by itself)Write
AI 0Actual operating mode 000-099 Unit stopped 100-199: Unit in lowActual operating mode codeRead
BI 0Operation ON/OFFOperation on/off statusRead
AI 16Current SupplyTemp [1/100C]Supply air temperature, 1/100 °CRead
AI 5Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the uActual supply airflowRead
BI 30Alarm relay 1 (A-alarm)A-alarm relay (critical alarm)Read
BI 31Alarm relay 2 (B-alarm)B-alarm relay (non-critical alarm)Read

Enable & remote start

AV 108 sets the BMS run mode, but only after the physical operation input is activated (per the object name).

Sensors & values from the BMS

Outdoor and room temperature can come from the BMS: write AV 102 / AV 103 and switch them in with BV 15 / BV 16.

Network setup

Watch out for

OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

979 of 979 shown
Type
Access
Show
OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet Points List
DescriptionStates
AImin0Actual operating mode 000-099 Unit stopped 100-199: Unit in lowOL_Act_DriftModeRead
AI1SA DuctPressure (Calc from PressSignal) [Pa]AR_SupDuctPaPaRead
AI2Regulator SetPoint for DuctPressReg [Pa] SAAR_SupDuctPaRgSetPaRead
AI3Extract DuctPressure (Calc from PressSignal) [Pa]AR_ExtDuctPaPaRead
AI4Regulator SetPoint for DuctPressReg [Pa] EAAR_ExtDuctPaRgSetPaRead
AImin5Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the uAR_Act_SA_Flowl/sRead
AI6Setpoint for supply flow controller [l/s] or [m3/h] or [CFM] (DAR_SA_FlowRegSetl/sRead
AI7Actual Extract/Exhaust flow [l/s] or [m3/h] or [CFM] (DependingAR_Act_EA_Flowl/sRead
AI8Setpoint for Extract/Exhaust flow controller [l/s] or [m3/h]orAR_EA_FlowRegSetl/sRead
AI9AR_CO2 Sensor ppm Measure [ppm]AR_CO2_ppmMeasRead
AI10Signal from Fanoptimizer Input SAFANOpt_SA_Ctrl_VinVRead
AI11Signal from Fanoptimizer Input EAFANOpt_EA_Ctrl_VinVRead
AI12FAN-Opt Supply Signal [1/100%]FANOpt_SAPrc_An_In%Read
AI13FAN-Opt Extract Signal [1/100%]FANOpt_EAPrc_An_In%Read
AI14Supply Max Flow [l/s], Aggregate maxAR_SA_MaxFlow_AggSizel/sRead
AI15Extract/Exhaust Max Flow [l/s], AggregateAR_EA_MaxFlow_AggSizel/sRead
AImin16Current SupplyTemp [1/100C]ATMP_SupTemp°CRead
AI17Regulator SupplyTemp-Set [1/100C]ATMP_SupTempRegSet°CRead
AI18Actual extract temperature [1/100°C]ATMP_ExtTemp°CRead
AI19Regulator ExtractTemp-Set [1/100C]ATMP_ExtTempRegSet°CRead
AI20Actual outdoor temperature [1/100°C]ATMP_Used_OATemp°CRead
AI21Current RoomTemp (External Sens) [1/100C]ATMP_RoomTemp°CRead
AI22Current ExhaustTemp [1/100C]ATMP_ExhaustTemp°CRead
AI23TempMeas for actual RegMode [1/100C]TR_TempRegMeas°CRead
AI24RegVal for actual RegMode [1/100C]TR_TempRegVal°CRead
AI25Fluid EXC Temp after EXC [1/100C]BattEXC_Temp°CRead
AI26Current HeatWaterBatt 1 Temp [1/100C]ATMP_HT1_CoilRT°CRead
AI27Outdoor Filter Pressure (Avr-Meas) [Pa]FM_SF_OA_ActFiltPressPaRead
AI28Extract Filter Pressure (Avr-Meas) [Pa]FM_SF_EA_ActFiltPressPaRead
AI29Supply Motor signal percentAR_SA_MotorSet%Read
AI30Extract/Exhaust Motor signal percentAR_EA_MotorSet%Read
AI31OA Filter pressure for alarm-limit at actual flow [Pa]Filt_AlrPa_OAPaRead
AI32EA Filter pressure for alarm-limit at actual flow [Pa]Filt_AlrPa_EAPaRead
AI33FlowOutTempComp PercentOut [1/100%]AR_FlwTmpCmpOut%Read
AI34Sum/Wint-TempComp actual Setpoint offset [1/100C ]SWTC_ActSetOfsRead
AI35EXC-Regulator HeatPower [1/100 %]HeatEXCPower%Read
AI36AfterHeat1-Regulator Power [1/100 %]Heat1Power%Read
AI37Cool Regulator Power [1/100 %], OutputCL_Cool_Power_AO%Read
AI38Actual Cool-Power [1/100%]CL_Cool_ActPower%Read
AI39Cool Force Flow Power [1/100 %]CL_Cool_FlwForcePw%Read
AI40Cool Alarm-1 VDC-Signal [1/100 %]CL_Cool_Vin1Alarm%Read
AI41Cool Alarm-2 VDC-Signal [1/100 %]CL_Cool_Vin2Alarm%Read
AI42Cool Alarm-3 VDC-Signal [1/100 %]CL_Cool_Vin3Alarm%Read
AI43Cool Alarm-4 VDC-Signal [1/100 %]CL_Cool_Vin4Alarm%Read
AI44Actual low pressure sensor 1 [1/100 bar]CL_LoPress1BarRead
AI45Actual high pressure sensor 1 [1/100 bar]CL_HiPress1BarRead
AI46Actual low pressure sensor 2 [1/100 bar]CL_LoPress2BarRead
AI47Actual high pressure sensor 2 [1/100 bar]CL_HiPress2BarRead
AI55Extract SFP [Ws/m3 same as J/m3]AR_ExtSFPRead
AI56Supply SFP [Ws/m3 same as J/m3]AR_SupSFPRead
AI66RotaryEXC – motor typeDRHX_TypeRead
AI67RotaryEXC – software version [1/100]DRHX_MOC_SW_VerRead
AI68RotaryEXC – percentage [1/100%]DRHX_PercentOut%Read
AI69RotaryEXC – speed output [1/10 rpm]DRHX_RpmOutRead
AI70RotaryEXC - actual output [mA]DRHX_I_OutRead
AI71RotaryEXC – output power [W]DRHX_PowerWRead
AI72RotaryEXC – days of operationDRHX_DriftDaysRead
AI73RotaryEXC – percentage setpoint [1/100%]DRHX_PercentSet%Read
AI74Extension module 1 software version [1/100]IO2_ID1_SW_VerRead
AI75Extension module 2 software version [1/100]IO2_ID2_SW_VerRead
AI76Act weekday Monday..Sunday (1 = Monday)RTC_WeekDayRead
AI79Stack for active alarm's 0 (0 end of stack)Alr_ReleasedIdRead
AI80Stack for active alarm's 1 (0 end of stack)Alr_ReleasedId01Read
AI81Stack for active alarm's 2 (0 end of stack)Alr_ReleasedId02Read
AI82Stack for active alarm's 3 (0 end of stack)Alr_ReleasedId03Read
AI83Stack for active alarm's 4 (0 end of stack)Alr_ReleasedId04Read
AI84Stack for active alarm's 5 (0 end of stack)Alr_ReleasedId05Read
AI85Stack for active alarm's 6 (0 end of stack)Alr_ReleasedId06Read
AI86Stack for active alarm's 7 (0 end of stack)Alr_ReleasedId07Read
AI87Stack for active alarm's 8 (0 end of stack)Alr_ReleasedId08Read
AI88Stack for active alarm's 9 (0 end of stack)Alr_ReleasedId09Read
AI89Stack for active alarm's 10 (0 end of stack)Alr_ReleasedId10Read
AI90Stack for active alarm's 11 (0 end of stack)Alr_ReleasedId11Read
AI91Stack for active alarm's 12 (0 end of stack)Alr_ReleasedId12Read
AI92Stack for active alarm's 13 (0 end of stack)Alr_ReleasedId13Read
AI93Stack for active alarm's 14 (0 end of stack)Alr_ReleasedId14Read
AI94Stack for active alarm's 15 (0 end of stack)Alr_ReleasedId15Read
AI95Master Software Ver [1/100]MasterSW_VerRead
AI96Display Software Ver [1/100]DisplaySW_VerRead
AI97Additional TempSensor1 [1/100C]ATMP_AddOnTSensor1°CRead
AI98Additional TempSensor2 [1/100C}ATMP_AddOnTSensor2°CRead
AI99Additional TempSensor3 [1/100C]ATMP_AddOnTSensor3°CRead
AI100Additional TempSensor4 [1/100C]ATMP_AddOnTSensor4°CRead
AI103AfterHeat2-Regulator Power [1/100 %]HW_EL_HT2_Power%Read
AI104Heatpower Preheater [1/100%]PH_HeatPower%Read
AI105Current Pre-HeatWaterBattTemp [1/100C] Coil/ReturnATMP_PH_CoilRT°CRead
AI108Heat exchanger efficiency [1/100%]EXCActualEff%Read
AI109Voltage level, HWB1 Out2HW12_VDCOutVRead
AI110Measured pressure loss over heat pump outdoor coil.HP_CoilPaMeasPaRead
AI111ModCO2, State 1-L/H, 2-H/L,0-nothingMODREC_AltFlowActRead
AI112Recirce closedown timerUPS_RecClosTimersRead
AI113CombiBattery VDC-Signal out for AfterHeat/Cool [1/1000 V]CombiVDC_OutVRead
AI114CombiBattery Power for Heat [1/100%]CombiHeatPow%Read
AI115CombiBattery Power for Cool [1/100%]CombiCoolPow%Read
AI118Current external OutDoorTemp [1/100C]ATMP_ExtOA_SensTemp°CRead
AI119Temperature after pre-heating coil [1/100 °C]ATMP_PHeatTempAir°CRead
AI120Cold water supply temperature for cooling coil [1/100 °C]ATMP_CW1_Inlet°CRead
AI121Damper position outdoor damper [1/100 %]AR_REC_FreshAirDis%Read
AI122Damper position recirculation [1/100 %]AR_REC_DampPrcDis%Read
AI123Output voltage cooling valve2 (only combi coil)CL_CoolVDC_Out2VRead
AI124OA filter restime before filtershift alarm activatedFM_SF_OA_Timer_Rest_dRead
AI125EA filter restime before filtershift alarm activatedFM_SF_EA_Timer_Rest_dRead
AI126Combi HT-WaterBattTemp [1/100C] Coil/ReturnATMP_CMB_CoilRT°CRead
AI127Rel. Humidity Extract airAR_RelHumExtract%RHRead
AI128Rel. Humidity Supply airAR_RelHumSupply%RHRead
AI129Rel. Humidity Mixed airAR_RelHumMixed%RHRead
AI130Extract Filter2 Pressure (Avr-Meas) [Pa]FM_SF_EA2_ActFiltPressPaRead
AI131Supply Filter Pressure (Avr-Meas) [Pa]FM_SF_SA_ActFiltPressPaRead
AI132Number of Detected ZoneModulesZM_CountRead
AI133ZoneControl Operation ModeZM_OpModeRead
AI134ZoneModule 1 - StatusZM1_StatusRead
AI135ZoneModule 1 - VAV Supply 1 Actuator SetpointZM1_Sup1SetRead
AI136ZoneModule 1 - VAV Supply 1 Actuator FlowZM1_Sup1FlowRead
AI137ZoneModule 1 - VAV Supply 2 Actuator SetpointZM1_Sup2SetRead
AI138ZoneModule 1 - VAV Supply 2 Actuator FlowZM1_Sup2FlowRead
AI139ZoneModule 1 - VAV Extract 1 Actuator SetpointZM1_Ext1SetRead
AI140ZoneModule 1 - VAV Extract 1 Actuator FlowZM1_Ext1FlowRead
AI141ZoneModule 1 - VAV Heating Actuator SetpointZM1_HeatSetRead
AI142ZoneModule 1 - VAV Heating Actuator FlowZM1_HeatFlowRead
AI143ZoneModule 1 - VAV Cooling Actuator SetpointZM1_CoolSetRead
AI144ZoneModule 1 - VAV Cooling Actuator FlowZM1_CoolFlowRead
AI145ZoneModule 1 - Room Temperature ValueZM1_RoomTemp°CRead
AI146ZoneModule 1 - Supply Temperature ValueZM1_SupTemp°CRead
AI147ZoneModule 1 - Remote Setpoint OffsetZM1_SetOffset°CRead
AI148ZoneModule 1 - CO2/VOC ValueZM1_CO2VOCRead
AI149ZoneModule 1 - RH ValueZM1_RH%RHRead
AI150ZoneModule 2 - StatusZM2_StatusRead
AI151ZoneModule 2 - VAV Supply 1 Actuator SetpointZM2_Sup1SetRead
AI152ZoneModule 2 - VAV Supply 1 Actuator FlowZM2_Sup1FlowRead
AI153ZoneModule 2 - VAV Supply 2 Actuator SetpointZM2_Sup2SetRead
AI154ZoneModule 2 - VAV Supply 2 Actuator FlowZM2_Sup2FlowRead
AI155ZoneModule 2 - VAV Extract 1 Actuator SetpointZM2_Ext1SetRead
AI156ZoneModule 2 - VAV Extract 1 Actuator FlowZM2_Ext1FlowRead
AI157ZoneModule 2 - VAV Heating Actuator SetpointZM2_HeatSetRead
AI158ZoneModule 2 - VAV Heating Actuator FlowZM2_HeatFlowRead
AI159ZoneModule 2 - VAV Cooling Actuator SetpointZM2_CoolSetRead
AI160ZoneModule 2 - VAV Cooling Actuator FlowZM2_CoolFlowRead
AI161ZoneModule 2 - Room Temperature ValueZM2_RoomTemp°CRead
AI162ZoneModule 2 - Supply Temperature ValueZM2_SupTemp°CRead
AI163ZoneModule 2 - Remote Setpoint OffsetZM2_SetOffset°CRead
AI164ZoneModule 2 - CO2/VOC ValueZM2_CO2VOCRead
AI165ZoneModule 2 - RH ValueZM2_RH%RHRead
AI166ZoneModule 3 - StatusZM3_StatusRead
AI167ZoneModule 3 - VAV Supply 1 Actuator SetpointZM3_Sup1SetRead
AI168ZoneModule 3 - VAV Supply 1 Actuator FlowZM3_Sup1FlowRead
AI169ZoneModule 3 - VAV Supply 2 Actuator SetpointZM3_Sup2SetRead
AI170ZoneModule 3 - VAV Supply 2 Actuator FlowZM3_Sup2FlowRead
AI171ZoneModule 3 - VAV Extract 1 Actuator SetpointZM3_Ext1SetRead
AI172ZoneModule 3 - VAV Extract 1 Actuator FlowZM3_Ext1FlowRead
AI173ZoneModule 3 - VAV Heating Actuator SetpointZM3_HeatSetRead
AI174ZoneModule 3 - VAV Heating Actuator FlowZM3_HeatFlowRead
AI175ZoneModule 3 - VAV Cooling Actuator SetpointZM3_CoolSetRead
AI176ZoneModule 3 - VAV Cooling Actuator FlowZM3_CoolFlowRead
AI177ZoneModule 3 - Room Temperature ValueZM3_RoomTemp°CRead
AI178ZoneModule 3 - Supply Temperature ValueZM3_SupTemp°CRead
AI179ZoneModule 3 - Remote Setpoint OffsetZM3_SetOffset°CRead
AI180ZoneModule 3 - CO2/VOC ValueZM3_CO2VOCRead
AI181ZoneModule 3 - RH ValueZM3_RH%RHRead
AI182ZoneModule 4 - StatusZM4_StatusRead
AI183ZoneModule 4 - VAV Supply 1 Actuator SetpointZM4_Sup1SetRead
AI184ZoneModule 4 - VAV Supply 1 Actuator FlowZM4_Sup1FlowRead
AI185ZoneModule 4 - VAV Supply 2 Actuator SetpointZM4_Sup2SetRead
AI186ZoneModule 4 - VAV Supply 2 Actuator FlowZM4_Sup2FlowRead
AI187ZoneModule 4 - VAV Extract 1 Actuator SetpointZM4_Ext1SetRead
AI188ZoneModule 4 - VAV Extract 1 Actuator FlowZM4_Ext1FlowRead
AI189ZoneModule 4 - VAV Heating Actuator SetpointZM4_HeatSetRead
AI190ZoneModule 4 - VAV Heating Actuator FlowZM4_HeatFlowRead
AI191ZoneModule 4 - VAV Cooling Actuator SetpointZM4_CoolSetRead
AI192ZoneModule 4 - VAV Cooling Actuator FlowZM4_CoolFlowRead
AI193ZoneModule 4 - Room Temperature ValueZM4_RoomTemp°CRead
AI194ZoneModule 4 - Supply Temperature ValueZM4_SupTemp°CRead
AI195ZoneModule 4 - Remote Setpoint OffsetZM4_SetOffset°CRead
AI196ZoneModule 4 - CO2/VOC ValueZM4_CO2VOCRead
AI197ZoneModule 4 - RH ValueZM4_RH%RHRead
AI198CVM Phase L1 to neutral (N) voltage [V]CVMVoltageL1VRead
AI199CVM Current L1 value [mA]CVMCurrentL1Read
AI200CVM Active power L1 [W]CVMActPowerL1WRead
AI201CVM Phase L2 to neutral (N) voltage [V]CVMVoltageL2VRead
AI202CVM Current value [mA] L2CVMCurrentL2Read
AI203CVM Active power [W] L2CVMActPowerL2WRead
AI204CVM Phase L3 to neutral (N) voltage [V]CVMVoltageL3VRead
AI205CVM Current value L3 [mA]CVMCurrentL3Read
AI206CVM Active power L3 [W]CVMActPowerL3WRead
AI207CVM Active power three phases [W]CVMActPowerIIIWRead
AI208CVM Frequency value [Hz]CVMFrequencyHzRead
AI209CVM Phase-phase Voltage L1 to L2 [V]CVMVoltageL1L2VRead
AI210CVM Phase-phase Voltage L2 to L3 [V]CVMVoltageL2L3VRead
AI211CVM Phase-phase Voltage L3 to L1 [V]CVMVoltageL3L1VRead
AI212CCVM Cool Phase L1 to neutral (N) voltage [V]CCVMVoltageL1VRead
AI213CCVM Cool Current L1 value [mA]CCVMCurrentL1Read
AI214CCVM Cool Active power L1 [kW]CCVMActPowerL1WRead
AI215CCVM Cool Phase L2 to neutral (N) voltage [V]CCVMVoltageL2VRead
AI216CCVM Cool Current L2 value [mA]CCVMCurrentL2Read
AI217CCVM Cool Active power L2 [kW]CCVMActPowerL2WRead
AI218CCVM Cool Phase L3 to neutral (N) voltage [V]CCVMVoltageL3VRead
AI219CCVM Cool Current L3 value [mA]CCVMCurrentL3Read
AI220CCVM Cool Active power L3 [kW]CCVMActPowerL3WRead
AI221CCVM Cool Active power three phases [W] (Low Byte)CCVMActPowrIIIWRead
AI222CCVM Cool Frequency value [Hz]CCVMFrequencyHzRead
AI223CCVM Cool Phase-phase Voltage L1 to L2 [V]CCVMVoltagL1L2VRead
AI224CCVM Cool Phase-phase Voltage L2 to L3 [V]CCVMVoltagL2L3VRead
AI225CCVM Cool Phase-phase Voltage L3 to L1 [V]CCVMVoltagL3L1VRead
AI226Actual used Power (kW) Elektrik Heat Battery 1El_HT1_ActPowerWRead
AI227Actual used Power (kW) Elektrik Heat Battery 2El_HT2_ActPowerWRead
AI230CVM Active energy three phases [kWh]CVMActEnergIIIRead
AI231CCVM Cool Active energy three phases [kWh]CCVMActEnerIIIRead
AI232Current EfficiencyTemp [1/100C]ATMP_EfficiencyTemp°CRead
AI233Internal OutDoorTemp [1/100C]ATMP_OA_SensTemp°CRead
AI234Current SupplyTemp2 [1/100C]ATMP_SupplyTemp2°CRead
AI235CVM Current value L1 high byte [mA]CVMCurrentL1HRead
AI236CVM Active power L1 high byte [W]CVMActPowerL1HWRead
AI237CVM Current value L2 high byte [mA]CVMCurrentL2HRead
AI238CVM Active power L2 high byte [W]CVMActPowerL2HWRead
AI239CVM Current value L3 high byte [mA]CVMCurrentL3HRead
AI240CVM Active power L3 high byte [W]CVMActPowerL3HWRead
AI241CVM Active power three phases high byte [W]CVMActPoweIIIHWRead
AI242CVM Active energy three phases high byte [Wh]CVMActEnerIIIHRead
AI243CCVM Current 1 value high byte [mA]CCVMCurrentL1HRead
AI244CCVM Active power 1 high byte [W]CCVMActPoweL1HWRead
AI245CCVM Current 2 value high byte [mA]CCVMCurrentL2HRead
AI246CCVM Active power 2 high byte [W]CCVMActPoweL2HWRead
AI247CCVM Current 3 value high byte [mA]CCVMCurrentL3HRead
AI248CCVM Active 3 power high byte [W]CCVMActPoweL3HWRead
AI249CCVM Active power three phases high byte [W]CCVMActPowIIIHWRead
AI250CCVM Active energy three phases high byte [Wh]CCVMActEnrIIIHRead
AI251Supply SFPII [Ws/m3 same as J/m3]AR_SupSFPIIRead
AI252Extract SFPII -2 [Ws/m3 same as J/m3]AR_ExtSFPIIRead
AI253Combined SFP [Ws/m3 same as J/m3] HighAHU_FullSFPHighRead
AI254Combined SFP [Ws/m3 same as J/m3] LowAHU_FullSFPLowRead
AI256Actual % rel. Huminity Mixed airHumid_ActRHMix%RHRead
AI263Rel. Humidity Outdoor airAR_RelHumOutdoor%RHRead
AI264Rel. Humidity Exhaust airAR_RelHumExhaust%RHRead
AI265Current Temperature OutdoorTempSensor 6040 (External Sens) [1/1TTH_ID5_Temp_Average°CRead
AI266Average Outdoorflow-pressure [Pa]Filt_DynFlowAvr_SAPaRead
AI267Average Extract/Exhaustflow-pressure [Pa]Filt_DynFlowAvr_EAPaRead
AI268Average OA-Filter-pressure [Pa] DYNAMICMODEFilt_AlrLimDynPa_OAPaRead
AI269Average EA-Filter-pressure [Pa] DYNAMICMODEFilt_AlrLimDynPa_EAPaRead
AI270Current air temperature just before the outdoor coil of the heaATMP_HP_OutdCoilTmp°CRead
AI271Average SA-Filter-pressure [Pa] DYNAMICMODEFilt_AlrLimDynPa_SAPaRead
AI272Average EA2-Filter-pressure [Pa] DYNAMICMODEFilt_AlrLimDynPa_EA2PaRead
AI273SummerNight Time with Heat Demand [sec]SNC_Heat_On_TimesRead
AI274Timer for DX-Cool RE-1 ON-Periode [sec]DX_OnTimerRE1sRead
AI275Timer for DX-Cool RE-2 ON-Periode [sec]DX_OnTimerRE2sRead
AI276Timer for DX-Cool RE-3 ON-Periode [sec]DX_OnTimerRE3sRead
AI277Timer for DX-Cool RE-4 ON-Periode [sec]DX_OnTimerRE4sRead
AI278Counter for DX-Cool RE-1 starts per hourDX_RestartCnt1Read
AI279Current Heat2 WaterBatt Temp [1/100C] Coil/ReturnATMP_HT2_CoilRT°CRead
AI280Counter for DX-Cool RE-3 starts per hourDX_RestartCnt3Read
AI281Counter for DX-Cool RE-4 starts per hourDX_RestartCnt4Read
AI282Timer for DX-Cool K1 Restart-PeriodeDX_RestartTim1sRead
AI283Timer for DX-Cool K2 Restart-PeriodeDX_RestartTim2sRead
AI284Timer for DX-Cool K3 Restart-PeriodeDX_RestartTim3sRead
AI285Timer for DX-Cool K14Restart-PeriodeDX_RestartTim4sRead
AI286Filter actual alarmstatus for OA-filter [1/100%]Filt_PrcStat_OA%Read
AI287Filter actual alarmstatus for EA-filter [1/100%]Filt_PrcStat_EA%Read
AI288OA Filter pressure for new-filter at actual flow [Pa]Filt_TabValPa_OAPaRead
AI289EA Filter pressure for new-filter at actual flow [Pa]Filt_TabValPa_EAPaRead
AI290Condenser Valve PowerROHCondPower%Read
AI291Voltage level, to condenser valveROHCondOutVDCVRead
AI292Shunt Valve PowerROHShuntPower%Read
AI293Voltage level, to shunt valveROHShuntOutVDCVRead
AI294Output to SteamHuminifier [1/1000 V]Humid_OutVDCVRead
AI295Timer delayed heat 2Ht2DelayTimersRead
AI296Average press Rotary EXC Flow Measure, Extract channelREXCPressAvgPaRead
AI297HeatPump power used when heating is demanded. Otherwise CoolPowHP_HeatPower%Read
AI298Supply air fan 2 TypeSA2_Slave_SizeRead
AI299Supply air fan 2 Software Ver [1/100]SA2_Slave_MOC_SW_VerRead
AI300Supply air fan 2 Boot Software / HW Ver [1/100]SA2_Slave_AOC_SW_VerRead
AI301Supply air fan 2 procent output [1/100%]SA2_Slave_PercentOut%Read
AI302Supply air fan 2 actual RPM [RPM]SA2_Slave_RPM_OutRead
AI303Supply air fan 2 actual current output [1/100mA]SA2_Slave_I_OutARead
AI304Supply air fan 2 actual power input [Watt]SA2_Slave_Power_InWRead
AI305Supply air fan 2 actual running time [minutes]SA2_Slave_DriftMinuteminRead
AI306Supply air fan 2 actual running time [days]SA2_Slave_DriftDaysRead
AI307Supply air fan 2 Percent to FanSA2_Slave_PercentSet%Read
AI308Extract air fan 2 TypeEA2_Slave_SizeRead
AI309Extract air fan 2 Software Ver [1/100]EA2_Slave_MOC_SW_VerRead
AI310Extract air fan 2 Boot Software / HW Ver [1/100]EA2_Slave_AOC_SW_VerRead
AI311Extract air fan 2 procent output [1/100%]EA2_Slave_PercentOut%Read
AI312Extract air fan 2 actual RPM [RPM]EA2_Slave_RPM_OutRead
AI313Extract air fan 2 actual current output [1/100mA]EA2_Slave_I_OutARead
AI314Extract air fan 2 actual power input [Watt]EA2_Slave_Power_InWRead
AI315Extract air fan 2 actual running time [minutes]EA2_Slave_DriftMinuteminRead
AI316Extract air fan 2 actual running time [days]EA2_Slave_DriftDaysRead
AI317Extract air fan 2 Percent to FanEA2_Slave_PercentSet%Read
AI318Supply air fan TypeSA_Master_SizeRead
AI319Supply air fan Software Ver [1/100]SA_Master_MOC_SW_VerRead
AI320Supply air fan Boot Software Ver [1/100]SA_Master_AOC_SW_VerRead
AI321Supply air fan procent ouput [1/100%]SA_Master_PercentOut%Read
AI322Supply air fan actual RPM [RPM]SA_Master_RPM_OutRead
AI323Supply air fan actual current output [1/100mA]SA_Master_I_OutARead
AI324Supply air fan actual running time [minutes]SA_Master_DriftMinuteminRead
AI325Supply air fan actual running time [days]SA_Master_DriftDaysRead
AI326Supply air fan Percent to FanSA_Master_PercentSet%Read
AI327Extract air fan Boot Software Ver [1/100]EA_Master_AOC_SW_VerRead
AI328Extract air fan procent ouput [1/100%]EA_Master_PercentOut%Read
AI329Extract air fan actual RPM [RPM]EA_Master_RPM_OutRead
AI330Extract air fan actual current output [1/100mA]EA_Master_I_OutARead
AI331Extract air fan actual running time [minutes]EA_Master_DriftMinuteminRead
AI332Extract air fan actual running time [days]EA_Master_DriftDaysRead
AI333Extract air fan Percent to FanEA_Master_PercentSet%Read
AI334Extract air fan TypeEA_Master_SizeRead
AI335Extract air fan Software Ver [1/100]EA_Master_MOC_SW_VerRead
AI336SA filter restime before filtershift alarm activatedFM_SF_SA_Timer_Rest_dRead
AI337EA filter 2 restime before filtershift alarm activatedFM_SF_EA2_Timer_Rest_dRead
AI338Extract air temperature after Heatpump value [1/100C]ATMP_HP_ExtAirTemp°CRead
AI339Daikin:Suction air temperatureDaikSucTmpSet°CRead
AI341Drives Compressor Drive TypeDC_Compressor_DriveTypeRead
AI342Drives Compressor AOC SW versionDC_Compressor_AOCSWVerRead
AI343Drives Compressor MOC SW versionDC_Compressor_MOCSWVerRead
AI344Drives Compressor PrcOutDC_Compressor_PercentOut%Read
AI345Drives Compressor RPMOutDC_Compressor_RPM_OutRead
AI346Drives Compressor Power In (filtered)DC_Compressor_Power_InWRead
AI347Drives Compressor Operation DayDC_Compressor_DriftDaysRead
AI348Cross-EXC pressure average, depent on flowEXC_FlwAvrPaRead
AI351Consumed kWh High Note!: Values are calculated as (High byte)CVMConActEner3PhkWHHRead
AI352Consumed kWh Low Note!: Values are calculated as (High byte) xCVMConActEner3PhkWHRead
AI353Consumed Wh High Note!: Values are calculated as (High byte) xCVMConActEner3PhWHHRead
AI354Consumed Wh Low Note!: Values are calculated as (High byte) xCVMConActEner3PhWHRead
AI355Consumed [kWh] High. Note: Values are calculated as (High byte)CCVMConActEner3PhkWHHRead
AI356Consumed [kWh] Low. Note: Values are calculated as (High byte)CCVMConActEner3PhkWHRead
AI357Consumed [Wh] High. Note: Values are calculated as (High byte)CCVMConActEner3PhWHHRead
AI358Consumed [Wh] Low. Note: Values are calculated as (High byte) xCCVMConActEner3PhWHRead
AI365Supply air fan actual power input [Watt]SA_Master_Power_InWRead
AI366Extract air fan actual power input [Watt]EA_Master_Power_InWRead
AI390Display temperature, not in regulation PH InletATMP_PH_Inlet°CRead
AI391Display temperature, not in regulation HT1 InletATMP_HT1_Inlet°CRead
AI392Display temperature, not in regulation HT2 InletATMP_HT2_Inlet°CRead
AI393Display temperature, not in regulation Cmb HT InletATMP_CMB_Inlet°CRead
AI450Outdoor-Damper setpoint in percentBDInletSetPrc%Read
AI451Outdoor-Damper actual position in percentBDInletRelPos%Read
AI452Exhaust-Damper setpoint in percentBDExhauSetPrc%Read
AI453Exhaust-Damper actual position in percentBDExhauRelPos%Read
AI454Exhaust-Backup-Damper setpoint in percentBDExhBakSetPrc%Read
AI455Exhaust-Backup-Damper actual position in percentBDExhBakRelPos%Read
AI456Recirculation-Damper setpoint in percentBDRecSetPrc%Read
AI457Recirculation-Damper actual position in percentBDRecRelPos%Read
AI458CrossByPass-Damper setpoint in percentBDByPasSetPrc%Read
AI459CrossByPass-Damper actual position in percentBDByPasRelPos%Read
AI460Drying-Damper setpoint in percentBDDryinSetPrc%Read
AI461Drying-Damper actual position in percentBDDryinRelPos%Read
AI462Supply-Damper setpoint in percentBDSASetPrc%Read
AI463Supply-Damper actual position in percentBDSARelPos%Read
AI464Supply-Backup-Damper setpoint in percentBDSupBakSetPrc%Read
AI465Supply-Backup-Damper actual position in percentBDSupBakRelPos%Read
AI466SmokeEvac-Damper setpoint in percentBDSmokeSetPrc%Read
AI467SmokeEvac-Damper actual position in percentBDSmokeRelPos%Read
AI468SmokeByPass-Damper setpoint in percentBDSMBPSetPrc%Read
AI469SmokeByPass-Damper actual position in percentBDSMBPRelPos%Read
AI470Heater 1 Setpoint in percentBVHeat1SetPrc%Read
AI471Heater 1 Valve actual position in percentBVHeat1RelPos%Read
AI472Cooler Setpoint in percentBVCoolSetPrc%Read
AI473Cooler Valve actual position in percentBVCoolRelPos%Read
AI474Heater 2 Setpoint in percentBVHeat2SetPrc%Read
AI475Heater 2 Valve actual position in percentBVHeat2RelPos%Read
AI476FluidExchanger Setpoint in percentBVFlExcSetPrc%Read
AI477FluidExchanger Valve actual position in percentBVFlExcRelPos%Read
AI478Preheater Setpoint in percentBVPrHeatSetPrc%Read
AI479Preheater Valve actual position in percentBVPrHeatRelPos%Read
AI480CombiCoil Setpoint in percentBVCombSetPrc%Read
AI481CombiCoil Valve actual position in percentBVCombRelPos%Read
AI482Opt7 Setpoint in percentBVOpt7SetPrc%Read
AI483Opt7 Valve actual position in percentBVOpt7RelPos%Read
AI484Extract-Damper setpoint in percentBDExtSetPrc%Read
AI485Extract-Damper actual position in percentBDExtRelPos%Read
AV1Manual Operation Mode [GUI]OL_Manual_ModesWrite
AV2Fan Regulation ModeAR_MtrRegModeWrite
AV14Offset for Sup/Ext Motor Slave and CO2 Reg [1/100%]AR_MtrRegOffset%Write
AV19AR_CO2 Regulator MinFlow [l/s]AR_CO2_MinFlowl/sWrite
AV20AR_CO2 Regulator MaxFlow [l/s]AR_CO2_MaxFlowl/sWrite
AV21AR_CO2 Regulator SupFlow Offset [1/100%]AR_CO2_SupFlwOffs%Write
AV22AR_CO2 ppm AlarmLimet Set [ppm]AR_CO2_AlrLimitWrite
AV23AR_CO2 Regulator P-Band [ppm]AR_CO2_PBWrite
AV24AR_CO2 Regulator I-Time [sec]AR_CO2_I_TimesWrite
AV25FAN-Opt Supply Regulator MinFlow [l/s]FANOpt_SA_MinFlowl/sWrite
AV26FAN-Opt Supply Regulator MaxFlow [l/s]FANOpt_SA_MaxFlowl/sWrite
AV27FAN-Opt Extract Regulator MinFlow [l/s]FANOpt_EA_MinFlowl/sWrite
AV28FAN-Opt Extract Regulator MaxFlow [l/s]FANOpt_EA_MaxFlowl/sWrite
AV29FAN-Opt Regulator ExtFlow Offset [1/100%]FANOpt_EA_FlwOffs%Write
AV30Supply Motor Reg I-Time Set [Sec]AR_SupMtr_I_TimesWrite
AV31Extract Motor Reg I-Time Set [Sec]AR_ExtMtr_I_TimesWrite
AV32User Supply Motor Percent Set at Fire [%]AH_SA_FlowFireSet%Write
AV33User Extract Motor Percent Set at Fire [%]AH_EA_FlowFireSet%Write
AV34HiSpeed AfterRun TimeOut Set [min]OL_HS_AfterRun_SetTimerminWrite
AV35FlowOutTempComp PercentSet [1/100%]AR_FlwTmpCmpSet%Write
AV36FlowOutTempComp StartTempSet [1/100C]AR_FlwTmpCmpStart°CWrite
AV37FlowOutTempComp StopTempSet [1/100C]AR_FlwTmpCmpStop°CWrite
AV38Actual yearRTC_Year_UsetWrite
AV39Actual monthRTC_Month_UsetWrite
AV40Actual dateRTC_Date_UsetWrite
AV41Actual hourRTC_Hour_UsethWrite
AV42Actual minutesRTC_Minute_UsetminWrite
AV43Actual secondsRTC_Second_UsetsWrite
AV44Extended Drift Start Day (0-Mon..6-Sun)ExtDrfStartDayWrite
AV45Extended Drift Start Minute (Hour*60+Min)ExtDrfStartMinminWrite
AV46Extended Drift Stop Day (0-Mon..6-Sun)ExtDrfStopDayWrite
AV47Extended Drift Stop Minute (Hour*60+Min)ExtDrfStopMinminWrite
AV50Supply LoSpeed DuctPressure Set [Pa]AR_SA_DuctPaLoSetPaWrite
AV51Supply MediumSpeed DuctPressure Set [Pa]AR_SA_DuctPaMedSetPaWrite
AV52Supply HiSpeed DuctPressure Set [Pa]AR_SA_DuctPaHiSetPaWrite
AV53Extract/Exhaust LoSpeed DuctPressure Set [Pa]AR_EA_DuctPaLoSetPaWrite
AV54Extract/Exhaust MediumSpeed DuctPressure Set [Pa]AR_EA_DuctPaMedSetPaWrite
AV55Extract/Exhaust HiSpeed DuctPressure Set [Pa]AR_EA_DuctPaHiSetPaWrite
AV56User Supply Flow-LoSpeedSet [l/s]AR_SA_LoSpeedFlowSetl/sWrite
AV57User Supply Flow-MedSpeedSet [l/s]AR_SA_MedSpeedFlowSetl/sWrite
AV58User Supply Flow-HiSpeedSet [l/s]AR_SA_HiSpeedFlowSetl/sWrite
AV59User Extract/Exhaust Flow-LoSpeedSet [l/s]AR_EA_LoSpeedFlowSetl/sWrite
AV60User Extract/Exhaust Flow-MedSpeedSet [l/s]AR_EA_MedSpeedFlowSetl/sWrite
AV61User Extract/Exhaust Flow-HiSpeedSet [l/s]AR_EA_HiSpeedFlowSetl/sWrite
AV62Supply Motor Lowspeed [1/100%], FFSAR_SA_FixLoPrcSet%Write
AV63Supply Motor Mediumspeed [1/100%], FFSAR_SA_FixMedPrcSet%Write
AV64Supply Motor Highspeed [1/100%], FFSAR_SA_FixHiPrcSet%Write
AV65Extract/Exhaust Motor Lowspeed [1/100%], FFSAR_EA_FixLoPrcSet%Write
AV66Extract/Exhaust Motor Mediumspeed [1/100%], FFSAR_EA_FixMedPrcSet%Write
AV67Extract/Exhaust Motor Highspeed [1/100%], FFSAR_EA_FixHiPrcSet%Write
AV68AR_CO2 Regulator User SetPoint for Lo timer Periode (HI AR_CO2AR_CO2_UsetLPWrite
AV69AR_CO2 Regulator User SetPoint for Medium timer Periode(Med AR_AR_CO2_UsetMPWrite
AV70AR_CO2 Regulator User SetPoint for Hi timer Periode(LO AR_CO2 VAR_CO2_UsetHPWrite
AV71Extract/Exhaust Min Flow for DuctReg [l/s]AR_EA_DuctMinFlowSetl/sWrite
AV72Extract/Exhaust Max Flow for DuctReg [l/s]AR_EA_DuctMaxFlowSetl/sWrite
AV73Supply Min Flow for DuctReg [l/s]AR_SA_DuctMinFlowSetl/sWrite
AV74Supply Max Flow for DuctReg [l/s]AR_SA_DuctMaxFlowSetl/sWrite
AV75TempDiff2 between Set/Meas Alarm Limit SA [1/100C]SupTempDif2AlrWrite
AV76TempDiff between Set/Meas Alarm Limit SA [1/100C]SupTempDiffAlrWrite
AV77P-Band for Supply TempReg heating [1/100C]SupTempHeatPBWrite
AV78SA I-Time for Reg on Heat2 Out [sec]TR_SupTempHeat2ITsWrite
AV79SA I-Time for supply tempReg Heat pump while heating [sec]TR_SupTempHP_ITsWrite
AV82Huminifier Supply Setpoint [1/100%] RHHumid_SupSet%RHWrite
AV102Current external Modbus OutDoorTemp [1/100C]STMP_MBT_OutDoor°CWrite
AV103Current external Modbus RoomTemp [1/100C]STMP_MBT_Room1°CWrite
AV104Customer set of alarmlimit modbus outdoorsensor minTR_AlrLimOA_MBT_Min°CWrite
AV105Customer set of alarmlimit modbus outdoorsensor maxTR_AlrLimOA_MBT_Max°CWrite
AV106Customer set of alarmlimit modbus roomsensor minTR_AlrLimRoomMin°CWrite
AV107Customer set of alarmlimit modbus roomsensor maxTR_AlrLimRoomMax°CWrite
AVmin108BMS-modes only avalable after activation of pysical input 'OperOL_BMS_Ctrl_ModesWrite
AV133Temp-Regulationmode0-Sup, 1-Ext, 2-Room, 3-Sup/Ext -DiffAHU_TempRegModeWrite
AVmin134TempSet for actual RegMode [1/100C]TR_TempRegSet°CWrite
AV135Min Allowed SupplyTemp [1/100C]STMP_SupTempMinSet°CWrite
AV136Max Allowed SupplyTemp [1/100C]STMP_SupTempMaxSet°CWrite
AV137TempDiff Set between Extract/Supply TempRegMode = 3STMP_SupTempDiffSet°CWrite
AV140SA I-Time for Reg on CoolOut [sec]TR_SupTempCool_ITsWrite
AV141SA I-Time for Reg on EXC Out [sec]TR_SupTempEXC_ITsWrite
AV142SA I-Time for Reg on Heat Out [sec]TR_SupTempHeat_ITsWrite
AV143SA I-Time for SupTempReg Flow DownReg Out [sec]TR_SupTempDnRegItsWrite
AV144TempDiff between Set/Meas Alarm Limit EA [1/100C]STMP_ExtTempDiffAlr°CWrite
AV145P-Band for Extract TempReg heating [1/100C]ExtTempHeatPBWrite
AV146EA I-Time for Reg on CoolOut [sec]TR_ExtTempCool_ItsWrite
AV147EA I-Time for Reg on EXC Out [sec]TR_ExtTempEXC_ItsWrite
AV148EA I-Time for Reg on Heat Out [sec]TR_ExtTempHeat_ItsWrite
AV149EA I-Time for ExtTempReg Flow DownReg Out [sec]TR_ExtTempDnRegItsWrite
AV150Sum/Wint-TempComp Winter Lo OutDoor TempSet [1/100C]SWTC_WintX1°CWrite
AV151Sum/Wint-TempComp Winter Hi OutDoor TempSet [1/100C]SWTC_WintX2°CWrite
AV152Sum/Wint-TempComp Summer Lo OutDoor TempSet [1/100C]SWTC_SumX1°CWrite
AV153Sum/Wint-TempComp Summer Hi OutDoor TempSet [1/100C]SWTC_SumX2°CWrite
AV154Sum/Wint-TempComp Winter compensation [1/100C]SWTCWinComValWrite
AV155Sum/Wint-TempComp Summer compensation [1/100C]SWTCSumComValWrite
AV156Summer/Winter Mode: 0 - 4SW_ModeWrite
AV157OutdoorTemp for start WinterMode (SW_Mode = 1)SW_OutWinterON°CWrite
AV158OutdoorTemp for start SummerMode (SW_Mode = 1)SW_OutSummerON°CWrite
AV159Month for Start WinterMode (SW_Mode = 2)SW_MonthWintONWrite
AV160Date for Start WinterMode (SW_Mode = 2)SW_DateWintONWrite
AV161Month for Start SummerMode (SW_Mode = 2)SW_MonthSumONWrite
AV162Date for Start SummerMode (SW_Mode = 2)SW_DateSumONWrite
AV163StartTemp for Nightheat Function [1/100 C]NH_Recirce_StartTmp°CWrite
AV164StopTemp for Nightheat Function [1/100 C]NH_Recirce_StopTmp°CWrite
AV165SupplyTempSet for Internal FireAlr [1/100C]AH_SA_Temp_InternFireAlr°CWrite
AV166ExtractTempSet for Internal FireAlr [1/100C]AH_EA_Temp_InternFireAlr°CWrite
AV167Cool-FlowForce Percent Set [1/100 %]CL_Cool_FlwForcePc%Write
AV168Min OutDoorTemp for CoolAgg. ActiveCL_Cool_OutTmpMin°CWrite
AV169Min SupplyTemp for Cool (Used for RoomReg)CL_Cool_SupMinTmp°CWrite
AV170SummerNight Ext/Room Temp Start [1/100C]SNC_EATempStart°CWrite
AV171SummerNight Ext/Room Temp Stop [1/100C]SNC_EA_TempStop°CWrite
AV172SummerNight OutDoor Temp Start [1/100C]SNC_OA_TempStart°CWrite
AV173SummerNight SupTemp Reg Set [1/100C]SNC_SA_TempSet°CWrite
AV174SummerNight StartTime [Min] 20:00 - 02-00, in server checkedSNC_StartTimeminWrite
AV175SummerNight StopTime [Min] 03:00 - 08:00, in server checkedSNC_StopTimeminWrite
AV176Min ExhaustTempSet for Cross EXC [1/100C]CExcDeIceTemp°CWrite
AV177P-Band for BypaasReg for Cross EXC [1/100C]CExcDeIceTempPWrite
AV178Fluid EXC PumpFunc: 0 - 3BattEXC_PumpFcWrite
AV179Fluid EXC PumpStartTemp. Is usedBattEXC_PumpSt°CWrite
AV180Fluid EXC TempDiff Alarm Set AlarmBattEXC_AlrSet°CWrite
AV181HWB1 Upstart PowerSet [1/100%]HW1_UpStartPow%Write
AV182HeatWaterBatt 1 PumpFunc: 0 - 3HW1_PumpFuncWrite
AV183HeatWaterBatt 1 PumpStartTemp. Is used together with WaterPumpFHW1_PmpStartTmp°CWrite
AV184SetVal for HWB1 AntiFrost Reg when Agg. = Stop [1/100C]HW1_FrzStopSet°CWrite
AV185SetVal for HWB1 AntiFrost Reg when Agg. = Drift [1/100CHW1_FrzDriftSet°CWrite
AV186HW1 P-Band for AntiFrost Reg [1/100C]HW1FreezePBWrite
AV187SetVal for HWB1 AntiFrost TempAlarm [1/100C]HW1_FrzAlrTpSet°CWrite
AV188CoolWater PumpFunc: 0 - 3CL_CW_PumpFuncWrite
AV189CoolWaterBatt PumpStartTemp. Is used together with WaterPumpFunCL_CW_PmpStartTmp°CWrite
AV190Filter Pressure Alr Limit for OA-Filter (static mode)Filt_StatAlr_OAPaWrite
AV191Filter Pressure Alr Limit for EA-Filter (static mode)Filt_StatAlr_EAPaWrite
AV192Filter Pressure Alr Limit for OA-Filter (dynamic mode)Filt_DynAlrSetPrc_OA%Write
AV193Filter Pressure Alr Limit for EA-Filter (dynamic mode)Filt_DynAlrSetPrc_EA%Write
AV194Alarm Mail Config: 0 - Mail are not send 1 - Mail on A-Alarm 2Alr_MailSetupWrite
AV195UserRE Function: 0 B-Alarm 1 Lo Speed indicator 2 Hi Speed indiAHU_UserAlr_RE_FuncWrite
AV196HWB2 Upstart PowerSet [1/100%]HW2UpStartPow%Write
AV197HWB 2 PumpFunc: 0 - 3HW2PumpFuncWrite
AV198HWB 2 PumpFunc start TemperatureHW2PmpStartTmp°CWrite
AV199SetVal for HWB2 AntiFrost Reg when Agg. = Stop [1/100C]HW2FrzStopSet°CWrite
AV200SetVal for HWB2 AntiFrost Reg when Agg. = Drift [1/100C]HW2FrzDriftSet°CWrite
AV201HW2 P-Band for AntiFrost Reg [1/100C]HW2FreezePBWrite
AV202SetVal for HWB2 AntiFrost TempAlarm [1/100C]HW2FrzAlrTpSet°CWrite
AV203Setpoint PreheaterPH_HeatSet°CWrite
AV204PreHeater SetVal for AntiFrost TempAlarm [1/100C]PH_MinAlrFrz°CWrite
AV205PreHeater SetVal for AntiFrost Reg when Agg. = Stop [1/100C] PrPH_StandbyTmp°CWrite
AV206Preheater Heatpower Percent under startup [1/100%]PH_StartPrc%Write
AV207Pre-heating coil P-band for frost protection control [1/100°C]PHeatFrzPBWrite
AV208Preheat PumpStart OutDoorTemp. Is used together withSTMP_PHPmpStTmpH°CWrite
AV209SetVal for Preheat AntiFrost Reg when Agg. = Drift [1/100C] HeaSTMP_PHFrzDrSetH°CWrite
AV210Mode for PumpFunc: 0 - 3PH_PumpModeWrite
AV211Min OutDoorTemp for CoolAgg. Relay 1 ActiveDXOutTempMin1°CWrite
AV212Min OutDoorTemp for CoolAgg. Relay 2 ActiveDXOutTempMin2°CWrite
AV213Min OutDoorTemp for CoolAgg. Relay 3 ActiveDXOutTempMin3°CWrite
AV214Min OutDoorTemp for CoolAgg. Relay 4 ActiveDXOutTempMin4°CWrite
AV215Min air temp at outdoor coil for HeatPump operate Relay1STMP_HP_MinOpTemp1°CWrite
AV216Min air temp at outdoor coil for HeatPump operate Relay2STMP_HP_MinOpTemp2°CWrite
AV217Min air temp at outdoor coil for HeatPump operate Relay3STMP_HP_MinOpTemp3°CWrite
AV218Min air temp at outdoor coil for HeatPump operate Relay4STMP_HP_MinOpTemp4°CWrite
AV219Fluid EXC SetVal for AntiFrost Reg when Agg. = Stop [1/100C]BattEXCFrzStop°CWrite
AV220Fluid EXC SetVal for AntiFrost Reg when Agg. = Drift [1/100C]BattEXCFrzDrf°CWrite
AV221Fluid EXC P-Band for AntiFrost Reg [1/100C]BattEXCFrzePBWrite
AV222Fluid EXCSetVal for AntiFrost TempAlarm [1/100C]BattEXCFrzASet°CWrite
AV223Extern Signal Greenzone, SupplyFANOpt_SA_GZ_An_In%Write
AV224Extern Signal Greenzone, ExtractFANOpt_EA_GZ_An_In%Write
AV225HeatWater VDC out function(Out 12): 0->0-10V, 1->2-10VHW12_VDCOutFuncWrite
AV226Pressure percent over calibrationREXDeIcePerc%Write
AV227Stop temperature freshair coolingSTMP_NO_FAirCoolBlk°CWrite
AV228Stop cooling over roomtemperatureCL_NO_CStopRTemp°CWrite
AV229Heat2 limiting type 1Room, 2 OutdoorHt2LimitTypWrite
AV230Startdifference temperatureHT2StLimRTempWrite
AV231Stepsize limiting roomtempHt2StLimRPer%Write
AV232DownCounter for HeatStart allowed [sec]Ht2StLimOTemp°CWrite
AV233Offset in % of Flow if Heat2 is onHt2FlowOffset%Write
AV234Timeset delayed Heat 2HT2_SetDelayStartTimesWrite
AV235Set Change Airflow RecirceTR_RecFlowShiftWrite
AV236Temperature for start with open damperSTMP_RecClosDAStart°CWrite
AV237Timeset for CO2 DX-Cooling-Aggregate from 0 ..100%ROHRiseT100sWrite
AV238SA SummerNight Motor percent SetSNC_SupCoolFlwl/sWrite
AV239EA SummerNight Motor Flow SetSNC_ExtCoolFlwl/sWrite
AV240SA SummerNight Motor Flow SetSNC_SupCoolPaPaWrite
AV241EA SummerNight Motor Press SetSNC_ExtCoolPaPaWrite
AV242SA SummerNight Motor Press SetSNC_SupCoolPrc%Write
AV243EA SummerNight Motor percent SetSNC_ExtCoolPrc%Write
AV244SummerNight Motor percent SetSNC_SlvOffsPrc%Write
AV248AR_CO2 Max Value Mod Rec/Rema1000 ModeAR_CO2_MaxModRecWrite
AV249AR_CO2 Min Value Mod Rec/Rema1000 ModeAR_CO2_MinModRecWrite
AV250Setpoint % Humidity Extract RH, DehumidityDehumSet_RH%RHWrite
AV257Min FreshAir part in percentAR_REC_MinFreshAir%Write
AV258Filter Pressure Alr Limit for SA-Filter (static mode)Filt_StaAlr_SAPaWrite
AV259Filter Pressure Alr Limit for EA-Filter2 (static mode)Filt_StaAlr_EA2PaWrite
AV260Filter Pressure Alr Limit for SA-Filter (dynamic mode)Filt_DynAlrSetPrc_SA%Write
AV261Filter Pressure Alr Limit for EA-Filter2 (dynamic mode)Filt_DynAlrSetPrc_EA2%Write
AV262ZoneModule 1 - Room Temperature SetpointZM1_RoomTmpSet°CWrite
AV263ZoneModule 1 - Minimum Supply TemperatureZM1_MinSupTemp°CWrite
AV264ZoneModule 1 - Maximum Supply TemperatureZM1_MaxSupTemp°CWrite
AV265ZoneModule 1 - Room CO2 SetpointZM1_CO2SetWrite
AV266ZoneModule 1 - Room RH SetpointZM1_RHSet%RHWrite
AV267ZoneModule 1 - VAV Supply PIR Min Air FlowZM1_PIRMinFlowl/sWrite
AV268ZoneModule 2 - Room Temperature SetpointZM2_RoomTmpSet°CWrite
AV269ZoneModule 2 - Minimum Supply TemperatureZM2_MinSupTemp°CWrite
AV270ZoneModule 2 - Maximum Supply TemperatureZM2_MaxSupTemp°CWrite
AV271ZoneModule 2 - Room CO2 SetpointZM2_CO2SetWrite
AV272ZoneModule 2 - Room RH SetpointZM2_RHSet%RHWrite
AV273ZoneModule 2 - VAV Supply PIR Min Air FlowZM2_PIRMinFlowl/sWrite
AV274ZoneModule 3 - Room Temperature SetpointZM3_RoomTmpSet°CWrite
AV275ZoneModule 3 - Minimum Supply TemperatureZM3_MinSupTemp°CWrite
AV276ZoneModule 3 - Maximum Supply TemperatureZM3_MaxSupTemp°CWrite
AV277ZoneModule 3 - Room CO2 SetpointZM3_CO2SetWrite
AV278ZoneModule 3 - Room RH SetpointZM3_RHSet%RHWrite
AV279ZoneModule 3 - VAV Supply PIR Min Air FlowZM3_PIRMinFlowl/sWrite
AV280ZoneModule 4 - Room Temperature SetpointZM4_RoomTmpSet°CWrite
AV281ZoneModule 4 - Minimum Supply TemperatureZM4_MinSupTemp°CWrite
AV282ZoneModule 4 - Maximum Supply TemperatureZM4_MaxSupTemp°CWrite
AV283ZoneModule 4 - Room CO2 SetpointZM4_CO2SetWrite
AV284ZoneModule 4 - Room RH SetpointZM4_RHSet%RHWrite
AV285ZoneModule 4 - VAV Supply PIR Min Air FlowZM4_PIRMinFlowl/sWrite
AV286CombiHeatWaterBatt Upstart PowerSet [1/100%]CombiUpStPow%Write
AV287CombiWaterBatt PumpFunc: 0 - 3CombiPumpFuncWrite
AV288CombiBatt PumpStartTemp. Is used together with WaterPumpFunc =STMP_CombiPmpStTmpH°CWrite
AV289Combi PumpFunc=3 then pump only starts when heatingpower exceedCombiPmpStPrc%Write
AV290SetVal for CombiBatt AntiFrost Reg when Agg. = Stop [1/100C] HeSTMP_CombFrzStopSet°CWrite
AV291SetVal for CombiBatt AntiFrost Reg when Agg. = Drift [1/100C] HSTMP_CombFrzDrSetH°CWrite
AV292Combi P-Band for AntiFrost Reg [1/100C]CombiFrzPBWrite
AV293SetVal for CombiBatt AntiFrost TempAlarm [1/100C]STMP_CombiFrzAlHSet°CWrite
AV294Max % CoolPower for Dehumidity without DewPointSensorDewCoolPower%Write
AV295StartTemp for Nightheat Function ROH under 5 deg [1/100 C]NH_Recirce_StartTmp2°CWrite
AV296StopTemp for Recirc heat Function ROH under 5 deg [1/100 C]NH_Recirce_StopTmp2°CWrite
AV297SwitchTemp for Nightheat Function ROH [1/100 C]NH_Recirce_SwitchTmp2°CWrite
AV304Mod. recirce max FreshAir part, Damper positionAR_REC_MaxFreshAir%Write
AV305Risetime 0..100%, in secHW1_RiseT100sWrite
AV306Night lowering temperatur correctionSTMP_NightSetBackWrite
AV307Alarmlevel in percent, if dustyALR_REXLevelPrcDus%Write
AV308Alarmlevel in percent if froozenALR_REXLevelPrcFrz%Write
AV309Fluid EXC PumpFunc=3 then pump only starts when EXCpower exceedBattEXCPmpStPr%Write
AV310Cool PumpFunc=3 pump only starts when Coolpower exceeds this seCL_CW_PumpStartPr%Write
AV311HWB 2 PumpFunc=3 then pump only starts when heatingpower exceedHW2PmpStartPrc%Write
AV312When PumpFunc=3 then pump only starts when heatingpower exceedsHW1_PmpStartPrc%Write
AV313Pressure to start deicing of cross Exc. [Pa]CEXC_DeIcePressPaWrite
AV314Time for deicing cross exc. when pressure monitored.CExcDeIceTimesWrite
AV315LoPressSens-1 AlarmLimit [1/100 Bar]CL_LoPress1AlrWrite
AV316HiPressSens-1 AlarmLimit [1/100 Bar]CL_HiPress1AlrWrite
AV317LoPressSens-2 AlarmLimit [1/100 Bar]CL_LoPress2AlrWrite
AV318HiPressSens-2 AlarmLimit [1/100 Bar]CL_HiPress2AlrWrite
AV319Heat 2 limited over this TemperaturROHOutdBlkTmp°CWrite
AV320AR_CO2 Regulator Fan Min % Setpoint [1/100%]AR_CO2_MinPerc%Write
AV321AR_CO2 Regulator Fan Max % Setpoint [1/100%]AR_CO2_MaxPerc%Write
AV322Temperature Offiset Slider from Web [1/100C]TR_TempRegOffsetWrite
AV323Drives Compressor Setpoint/PrcSetDC_Compressor_PercentSet%Write
AV324IOC Digital input Heatpump Frost / LubricationIOC_DI_FP_Oil_HPT_UsetWrite
BImin0Operation ON/OFFOperationRead
BI1External stopExtStopRead
BI2External HiSpeedExtHiSpeedRead
BI3Extended low speed –> ActiveExtDrfLoSpeedRead
BI4Extended high speed –> ActiveExtDrfHiSpeedRead
BI5Power to electric heating coil reduced due to low flowEl_HT1_BattPowerRedRead
BI6Summer night cooling is activeSNC_DriftRead
BI7Reset parameters for summer night cooling new calculation is inSNC_ResetRead
BI8Winter temperature compensation is activeSWTC_WintCompRead
BI9Summer temperature compensation is activeSWTC_SumCompRead
BI10Summer/winter actual status OFF –> winter operation ('0') ONSW_StatusRead
BI11Recirculation status ('1' = Open damper)MODREC_StatusRead
BI12Exercising heat exchanger –> ActiveEXC_ExerciseRead
BI13Signal to cross-flow exchanger reduced (frost protection)CExcIceProtectRead
BI14Supply duct pressure controller reduced to min. FlowAR_SA_DuctMinFlowRead
BI15Supply duct pressure controller increased to max. FlowAR_SA_DuctMaxFlowRead
BI16Extract/Exhaust duct pressure controller reduced to min. FlowAR_EA_DuctMinFlowRead
BI17Extract/Exhaust duct pressure controller increased to max. FlowAR_EA_DuctMaxFlowRead
BI18Cooling recovery –> statusCoolRecoveryRead
BI19Circulation pump on heating coil: Frost protection –> ActiveHW1_FrostRegRead
BI20Circulation pump on heating coil: Pump exercising –> ActiveHW1_PumpExerRead
BI21CoolWaterCoil PumpExercise activeCL_CW_PumpExerRead
BI22Signal to heating coil reduced (insufficient flow) –> ActiveHeat_FlwDnRegRead
BI231-when min. supply temperature control is active.Only active whTempRegMinSupRead
BI241-when max. supply temperature control is active.Only active whTempRegMaxSupRead
BI25Circulation pump on heat recovery coil: Pump exercising –> AcBattEXC_ExerRead
BI26Heating relay 1Heat_RE1_DO1Read
BI27Cool Relay 1Cool_RE1Read
BI28Circulation pump on Fluid EXC coil: Pump –> RunningBattEXC_PumpRERead
BI29At least one active alarmAlrActiveRead
BImin30Alarm relay 1 (A-alarm)Alr_RE1Read
BImin31Alarm relay 2 (B-alarm)Alr_RE2Read
BI32Fire alarm signal (room sensor)Alr_ExtFireSignalRead
BI33Smoke Alarm Signal (Sensor in duct)Alr_ExtSmokeSignalRead
BI35Filter alarm for outdoor filter (pressure drop above set limit)Filt_Alarm_OARead
BI36Filter alarm for extract filter (pressure drop above set limit)Filt_Alarm_EARead
BI37Supply temperature sensor – sensor faultSupTempSensErrRead
BI38Extract temperature sensor – sensor faultExtTempSensErrRead
BI39Outdoor temperature sensor – sensor faultOutDoorSensErrRead
BI40Room temperature sensor – sensor faultRoomSensErrRead
BI41Exhaust temperature sensor – sensor faultExhaustSensErrRead
BI42Heating coil temperature sensor – sensor faultHW1_SensErrRead
BI43Fluid EXC temperature sensor – sensor faultBattEXC_SensErRead
BI44Heating coil frost alarmHW1_FrostAlrRead
BI45Cooling shared alarmCL_Cool_SumAlarmRead
BI46Cooling digital alarm 1 inputCL_Cool_DI1_AlarmRead
BI47Cooling digital alarm 2 inputCL_Cool_DI2_AlarmRead
BI48Cooling digital alarm 3 inputCL_Cool_DI3_AlarmRead
BI49Cooling digital alarm 4 inputCL_Cool_DI4_AlarmRead
BI50Supply motor ON/OFFAR_SA_SupMotorONRead
BI51Supply Motor AlarmSupMotorAlarmRead
BI57Supply air fan ripple alarmAlr_SA_Controler_RippleRead
BI59Extract/Exhaust motor ON/OFFAR_EA_EA_MotorONRead
BI60Extract Motor AlarmExtMotorAlarmRead
BI66Extract/exhaust air fan 2 Ripple AlarmAlr_EA2_Controler_RippleRead
BI68Rotary heat exchanger – motor control ON/OFFDRHX_DriftONRead
BI69Rotary heat exchanger – reset signalDRHX_AlrResetRead
BI70Rotary heat exchanger – rotation directionDRHX_CCW_RotationRead
BI71Rotary heat exchanger rotation alarmDRHX_RotorAlrRead
BI72Rotary heat exchanger low voltage alarmDRHX_V_LowAlrRead
BI73Rotary heat exchanger hihg voltage alarmDRHX_V_HighAlrRead
BI74Rotary heat exchanger high currentDRHX_I_HighAlrRead
BI75Rotary heat exchanger temperature alarmDRHX_TempAlrRead
BI76Rotary heat exchanger rotation signalDRHX_RotorSignalRead
BI77Rotary heat exchanger torque overloadDRHX_BlockedRead
BI78Status Brandstop inputExtBrandStopRead
BI79Add on sensor 1 - Sensor faultAddOnTSens1ErrRead
BI80Add on sensor 2 - Sensor faultAddOnTSens2ErrRead
BI81Add on sensor 3 - Sensor faultAddOnTSens3ErrRead
BI82Add on sensor 4 - Sensor faultAddOnTSens4ErrRead
BI83Alarm frost thermostat alarm (digital input)Alr_Frost_OA_LuftsensorRead
BI84Heating coil 2 - Frost control activeHW2FrostRegRead
BI85Heating coil 2 - Circulation pump, pump exercising activeHW2PumpExerRead
BI86Heating coil 2 - Return sensor - Sensor faultHW2SensErrRead
BI87Heating coil 2 - Frost alarmHW2FrostAlrRead
BI88Pre-heating coil - Frost alarmPH_FreezeAlarmRead
BI89Pre-heating coil - Frost protection activePH_FrostRegActRead
BI90Pre-heater Pump exercise activePH_PumpExerRead
BI91Preheater - heat relay 1PH_HeatRelayRead
BI92Pre-heating coil - Overheating faultPH_OverheatRead
BI93Pre-heating coil - Output reduction, low air volumePH_PowReduceRead
BI94Returnwater sensor errorPH_HWBSensErrRead
BI95Alarm - Heat recovery efficiency below alarm limitAlr_EXCEffToLowRead
BI96Alarm Atv Comm SupplyAlr_AtvSA_CommRead
BI97Alarm Atv Comm ExtractAlr_AtvEA_CommRead
BI98Alarm Atv FC SupplyAlr_AtvSAMotorAlarmRead
BI99Alarm Atv FC ExtractAlr_AtvEAMotorAlarmRead
BI100Frost alarm fluid-coupled coil (CoilEXC)Alr_FrostBatt_EXCRead
BI101Contact error DeIcer El-BatteryAlr_DeIceContactRead
BI102DeIcer overheatingsalarm El-BatteryAlr_DeIceOverheatRead
BI103DeIcer power reduction alarm El-BatteryAlr_DeIceReducedRead
BI104Alarm - pressure transmitter not calibrated (Ice guard rotor heAlr_NoREXCaliRead
BI105Alarm - pressure transmitter not configured (Ice guard rotor heAlr_SensREXNConfRead
BI106Coolrecovery over damper active ('1' = Open damper)NO_CRecovStatRead
BI107Cooling stopped by room temperatureNO_CStopRTStatRead
BI108Signal for the 4-way-valve in HeatPumpHP_CoolingActvRead
BI109Status bit: De-icing of heatpumpHP_De_icingActRead
BI110Alarm - rotor heat exchanger blocked by ice (high pressure overAlr_RotEXCFrozenRead
BI111Alarm - rotor heat exchanger blocked by dirt (high pressure oveAlr_RotEXCDustyRead
BI112Flow is change heat2 activeHT2FlowChgActRead
BI113Status of delaytimer Heat 2HT2DelayStatusRead
BI114Limit of heat 2 is avoidHT2DelLimBlkNoRead
BI115Blocking Heat2 in recirkulation mode = AktivatedHT2RecBlkActRead
BI116Status of low flow under 100% recirculationNH_LowRecFlowStatRead
BI117Closed damper running activeRecClosDmpActRead
BI118Max. raise-/fall-time is activatedHW1_RiseFallActivRead
BI119Supply air fan 2 high current limitAlr_SA2_Contr_HiIOAlrRead
BI120Supply air fan 2 voltage low alarmAlr_SA2_Contr_LoVInRead
BI121Supply air fan 2 voltage high alarmAlr_SA2_Contr_HiVInRead
BI122Supply air fan 2 high current limit alarmAlr_SA2_Control_I_MaxAlrRead
BI123Supply air fan 2 temperature alarmAlr_SA2_Contr_HiTempRead
BI124Supply air fan 2 alarm for phase errorAlr_SA2_Contr_PhaseErrRead
BI125Supply air fan 2 Direction errorAlr_SA2_Contr_Rot_DirErrRead
BI126Supply air fan 2 alarm for blocked rotorAlr_SA2_Controler_RotBlkRead
BI128Extract/exhaust air fan 2 voltage low alarmAlr_EA2_Contr_LoVInRead
BI129Extract/exhaust air fan 2 voltage high alarmAlr_EA2_Contr_HiVInRead
BI130Extract/exhaust air fan 2 high current limit alarmAlr_EA2_Control_I_MaxAlrRead
BI131Extract/exhaust air fan 2 temperature alarmAlr_EA2_Contr_HiTempRead
BI132Extract/exhaust air fan 2 alarm for phase errorAlr_EA2_Contr_PhaseErrRead
BI133Extract/exhaust air fan 2 Direction errorAlr_EA2_Contr_Rot_DirErrRead
BI134Extract/exhaust air fan 2 alarm for blocked rotorAlr_EA2_Controler_RotBlkRead
BI135Alarm SA2 Controler Comm AlarmAlr_SA2Controler_ComRead
BI136Alarm EA2 Controler Comm AlarmAlr_EA2Controler_ComRead
BI137Supply air fan high current limitAlr_SA_ControlerI_MaxAlrRead
BI138Supply air fan voltage low alarmAlr_SA_Contr_LoVInRead
BI139Supply air fan voltage high alarmAlr_SA_Contr_HiVInRead
BI140Supply air fan high current limit alarmAlr_SA_Contr_HiIOAlrRead
BI141Supply air fan temperature alarmAlr_SA_Contr_HiTempRead
BI142Supply air fan alarm for phase errorAlr_SA_Contr_PhaseErrRead
BI143Supply air fan Direction errorAlr_SA_Contr_Rot_DirErrRead
BI144Supply air fan alarm for blocked rotorAlr_SA_Controler_RotBlkRead
BI145Extract/exhaust air fan high current limitAlr_EA_ControlerI_MaxAlrRead
BI146Extract/exhaust air fan voltage low alarmAlr_EA_Contr_LoVInRead
BI147Extract/exhaust air fan voltage high alarmAlr_EA_Contr_HiVInRead
BI148Extract/exhaust air fan high current limit alarmAlr_EA_Contr_HiIOAlrRead
BI149Extract/exhaust air fan temperature alarmAlr_EA_Contr_HiTempRead
BI150Extract/exhaust air fan alarm for phase errorAlr_EA_Contr_PhaseErrRead
BI151Extract/exhaust air fan Direction errorAlr_EA_Contr_Rot_DirErrRead
BI152Extract/exhaust air fan alarm for blocked rotorAlr_EA_Controler_RotBlkRead
BI153OJ-DV Supply Comm AlarmAlr_SA_Controler_CommRead
BI154OJ-DV Extract Comm AlarmAlr_EA_Controler_CommRead
BI155TTH-6202 communication errorAlr_TTH6202ComRead
BI156Communication Alarm Belimo Smoke DamperAlr_BDSmokeCom_ErrorRead
BI157Position Alarm Belimo Smoke DamperAlr_BDSmokePos_ErrorRead
BI158Extention IO-Modul no 1 - communication errorAlr_Ext_Modul1_CommRead
BI159Extention IO-Modul no 2 - communication errorAlr_Ext_Modul2_CommRead
BI160Extention IO-Modul no 3 - communication errorAlr_Ext_Modul3_CommRead
BI161Extention IO-Modul no 4 - communication errorAlr_Ext_Modul4_CommRead
BI162Extention IO-Modul no 5 - communication errorAlr_Ext_Modul5_CommRead
BI163Extention IO-Modul no 6 - communication errorAlr_Ext_Modul6_CommRead
BI164Extention IO-Modul no 7 - communication errorAlr_Ext_Modul7_CommRead
BI165Extention IO-Modul no 8 - communication errorAlr_Ext_Modul8_CommRead
BI166Supplysensor 2 alarmAlr_SupAirTemp2Read
BI167Addon sensor 1 - Sensor errorAlr_AddOnSens1Read
BI168Addon sensor 2 - Sensor errorAlr_AddOnSens2Read
BI169Addon sensor 3 - Sensor errorAlr_AddOnSens3Read
BI170Addon sensor 4 - Sensor errorAlr_AddOnSens4Read
BI171SupMotor AlarmAlr_SA_ControlerRead
BI172ExtMotor AlarmAlr_EA_ControlerRead
BI173Combi coil; Cooling relay no. 2 aktiveCmb2CoolRelRead
BI174Flag for Rise-Falltime active DX-CO2-CoolingROHRiFaActivRead
BI176Preheater - heat relay 3PH_HeatRelay3Read
BI177State of extern start inputExternInput_StartStateRead
BI178Supply air fan EEprom errorAlr_SA_Contr_EE_ErrorRead
BI179Supply air fan 2 EEprom errorAlr_SA2_Contr_EE_ErrorRead
BI180Extract/exhaust air fan EEprom errorAlr_EA_Contr_EE_ErrorRead
BI181Extract/exhaust air fan 2 EEprom errorAlr_EA2_Contr_EE_ErrorRead
BI182Sensor alarm TTH6040 no ComAlr_TTH6040ComRead
BI183Low oil level cooling compressorAlr_LowOilDXHPRead
BI184Common-Alarm circulationpumpsAlr_Common_HWPumpRead
BI185Common-Alarm SupplyfanAlr_Common_SupFanRead
BI186Common-Alarm ExtractfanAlr_Common_ExtFanRead
BI187Common-Alarm Supply duct/flowAlr_Common_SupFlDuRead
BI188Common-Alarm Extract duct/flowAlr_Common_ExtFlDuRead
BI189Common-Alarm ExchangerAlr_Common_EXCRead
BI190Common-Alarm antifreezeAlr_Common_FreezeRead
BI191Common-Alarm El-BatteriesAlr_Common_ElHeatRead
BI192Common-Alarm Temperatures low/highAlr_Common_TempRead
BI193Common-Alarm Supply FilterAlr_Common_SFiltRead
BI194Common-Alarm Extract FilterAlr_Common_EFiltRead
BI195Common-Alarm TemperaturesensorsAlr_Common_TmpSensRead
BI196Common-Alarm CoolingAlr_Common_CoolRead
BI197Common-Alarm Dampers BelimoAlr_Common_BDampRead
BI198Common-Alarm Internals / SysModBusAlr_Common_InternRead
BI199Value in Control Reg BMS CtrlBMS_InpRegStateRead
BI200State of extern lowspeed inputExternInput_LowSpeedRead
BI201BMS-Sensor Room Out of RangeAlr_BMS_Room_TS_OORRead
BI202BMS-Sensor Outdoor Out of RangeAlr_BMS_OA_TS_OORRead
BI203Fire mann stopAlr_FireManStopRead
BI204Smoke evacuation activatedAlr_SmokEvacActRead
BI205Smoke evacuation fan alarmAlr_SmokEvaFanRead
BI206Output for supply air damper aktiveDO_OA_BigDamp_RelayRead
BI207Big Damper relay SupplyDO_SA_BigDamp_RelayRead
BI208Recirce DamperSignalAR_DA_REC_DORead
BI209External OutDoorTemp -Sensor ErrorExOutDSensErrRead
BI210PreHeatWaterBatt Sensor AlarmAlr_PreheatAirSensRead
BI211Cooling water supply temperature - sensor errorCL_CW_TSensErrRead
BI212Heat Relay 21 (ExtMod-Reserve)Heat_RE21_DO21Read
BI213Heat Relay 22 (ExtMod-Reserve)Heat_RE22_DO22Read
BI214Heat Relay 23 (ExtMod-Reserve)Heat_RE23_DO23Read
BI215Heat Relay 24 (ExtMod-Reserve)Heat_RE24_DO24Read
BI216Heat Relay 25 (ExtMod-Reserve)Heat_RE25_DO25Read
BI217Heating relay26 (ExtMod-Reserve)Heat_RE26_DO26Read
BI218Pump relay combi coil activatedCombi_PumpRE_DORead
BI219Electric coil: High temperature alarm signalEL1_OverHtBacRead
BI220Electric coil: Relay stuckAlr_HT1_EL_Coil_ContactRead
BI221Electric coil 2: High temperature alarm signalEL2_OverHtBacRead
BI222Electric coil 2: Relay stuckAlr_HT2_EL_Coil_ContactRead
BI223Alarm - Time is out for filter change supply air filterAlr_OAFilt_TimerAlrOnRead
BI224Alarm - Time is out for filter change extract air filterAlr_EAFilt_TimerAlrOnRead
BI225Extended medium speed –> ActiveExtDrfMeSpeedRead
BI226Preheater - heat relay 2PH_HeatRelay2Read
BI229Supply air fan, Power limitAlr_SA_Contr_PowLimRead
BI230Extract/exhaust air fan, Power limitAlr_EA_Contr_PowLimRead
BI233Supply air fan2 Ripple AlarmAlr_SA2_Controler_RippleRead
BI234Extract/exhaust air fan, Intern StopAlr_EA_Controler_IStopRead
BI235Supply air fan2 Intern StopAlr_SA2_Controler_IStopRead
BI236Extract/exhaust air fan 2, Intern StopAlr_EA2_Controler_IStopRead
BI237CombiBattery heat usableCmbHeatStateRead
BI238CombiBattery cool usableCmbCoolStateRead
BI239ElPrehheat Overheat StatePre_OverHtBacRead
BI240Contact error Preheater El-BatteryAlr_Preheat_ContactRead
BI244Extract/exhaust air fan 2 high current limitAlr_EA2_Contr_HiIOAlrRead
BI245B-Alr SupFan is stoppedAlr_SA_FanStopRead
BI246Smoke Evac Damper not in positionAlr_SMEvacDmpNotInPosRead
BI247Smoke Bypass Damper not in positionAlr_SMBPassDmpNotInPosRead
BI248Communication Alarm DPTH1Alr_DPTH_1ComRead
BI249Communication Alarm DPTH2Alr_DPTH_2ComRead
BI250Communication Alarm DPTH3Alr_DPTH_3ComRead
BI251Communication Alarm DPTH4Alr_DPTH_4ComRead
BI252Communication Alarm DPTH5Alr_DPTH_5ComRead
BI253Filter Alarm for SA-Filter (pressure above Limit)Filt_Alarm_SARead
BI254Filter Alarm for EA2-Filter (pressure above Limit)Filt_Alarm_EA2Read
BI255Alarm from Supplyfilter timerAlr_SAFilt_TimerAlrOnRead
BI256Alarm from Extractfilter2 timerAlr_EAFilt2_TimerAlrOnRead
BI257ZoneControl PIR ActiveZM_PIRRead
BI258ZoneModule 1 - WindowFrost ValueZM1_WinFrostRead
BI259ZoneModule 1 - PIR ActiveZM1_PIRRead
BI260ZoneModule 1 - Room Temp Sensor ErrorZM1_RoomTmpErrRead
BI261ZoneModule 1 - Supply Temp Sensor ErrorZM1_SupTempErrRead
BI262ZoneModule 2 - WindowFrost ValueZM2_WinFrostRead
BI263ZoneModule 2 - PIR ActiveZM2_PIRRead
BI264ZoneModule 2 - Room Temp Sensor ErrorZM2_RoomTmpErrRead
BI265ZoneModule 2 - Supply Temp Sensor ErrorZM2_SupTempErrRead
BI266ZoneModule 3 - WindowFrost ValueZM3_WinFrostRead
BI267ZoneModule 3 - PIR ActiveZM3_PIRRead
BI268ZoneModule 3 - Room Temp Sensor ErrorZM3_RoomTmpErrRead
BI269ZoneModule 3 - Supply Temp Sensor ErrorZM3_SupTempErrRead
BI270ZoneModule 4 - WindowFrost ValueZM4_WinFrostRead
BI271ZoneModule 4 - PIR ActiveZM4_PIRRead
BI272ZoneModule 4 - Room Temp Sensor ErrorZM4_RoomTmpErrRead
BI273ZoneModule 4 - Supply Temp Sensor ErrorZM4_SupTempErrRead
BI274Cool Relay 2Cool_RE2Read
BI275Cool Relay 3Cool_RE3Read
BI276Cool Relay 4Cool_RE4Read
BI277Alarm smoke evacuation damper is activated ('1' = Open damper)Alr_FireEvaDmpRead
BI278Heat Relay 2 (ExtMod-Reserve)Heat_RE2_DO2Read
BI279Combi coil - Return sensor - Sensor faultCombiTSenErrRead
BI280Combi coil - Frost alarmCombiFrostAlrHRead
BI281Combi coil - Frost protection activeCombiFrostRegRead
BI282Combi coil - Circulation pump, pump exercising activeCombiPumpExerRead
BI283Combi coil; Cooling relay aktiveCombiCoolRelRead
BI284Combi coil; Heating relay aktiveCombiHeatRelRead
BI286Supply Fan wall Alarm (B)Alr_SA_FanWallAlrRead
BI287Extract Fan wall Alarm (B)Alr_EA_FanWallAlrRead
BI288Extract digital damper output signal ('1' = Open damper)DO_EA_Damper_SignalRead
BI289Exhaust digital damper output signal ('1' = Open damper)DO_EXH_Damper_SignalRead
BI290Exhaust backup digital damper output signal ('1' = Open damper)DO_EXHBa_Damper_SignalRead
BI291Supply backup digital damper output signal ('1' = Open damper)DO_SABa_Damper_SignalRead
BI292SupBackupMotor AlarmAlrSupBMtrRead
BI293ExhBackupMotor AlarmAlrExhBMtrRead
BI294Sensor alarm TTH6040 OutDoor no Com (port A)TTH_6040OA_PortA_ComRead
BI295Supply Backup Motor AlarmSupBMotorAlarmRead
BI296Exhaust Backup Motor AlarmExhBMotorAlarmRead
BI297Reduction of cross-flow exchanger due to de-icing; deicing starCExcDeIcingRead
BI298Electric coil 2 - Output reduction active due to low flowEl_HT2_BatPowerRedRead
BI299Extract/exhaust air fan RipplealarmAlr_EA_Controler_RippleRead
BI300Supply air fan, Intern StopAlr_SA_Controler_IStopRead
BI301Preheater Frost Alarm CoolingPH_FrzAlrCoolRead
BI302Status frost thermostat alarm (digital input)AR_DI_State_LuftAlrRead
BI303Humidifier alarm statusHumidAlrInpRead
BI304Freshair cooling is stoppedNO_CStopStatRead
BI305Communication CVM Mini MeterAlr_CommCVMMiniRead
BI306Communication CVM Mini Cool MeterAlr_CommCVMCoolRead
BI307A-Alr Comm Error HMI_20TAlr_ComHMI_20TRead
BI308Alarm, Fire damper not closedAlrFireDmpNClsRead
BI309Alarm, Fire damper not openedAlrFireDmpNOpnRead
BI310Fire damper test is ongoingFireDmpTstActvRead
BI311Extract air temperature after Heatpump, sensor errorHP_TSExtAirErrRead
BI312Start of AHU is blocked, if mounted and openAggBlKAlrRead
BI313Firethermostat alarm via El-Heater inputFireEHtCoilAlrRead
BI314Firethermostat alarm via El-Pre-Heater inputFireEPrHeatAlrRead
BI315Daikin EVKit communications AlarmAlrCommDaikinRead
BI316Daikin 'warning' bits from register 30003AlrDaikinWrnRead
BI317Daikin 'alarm' bits from register 30003AlrDaikinAlrRead
BI318Daikin 'error' bits from register 30003AlrDaikinErrRead
BI320Drives Compressor communication alarmAlr_DrCmpComAlrRead
BI321Drives Compressor high current alarmAlr_DrCmp_IHghRead
BI322Drives Compressor low voltage alarmAlr_DrCmpLwVltRead
BI323Drives Compressor high voltage alarmAlr_DrCmpHghVltRead
BI324Drives Compressor high temperature alarmAlr_DrCmpHiTmpRead
BI325Drives Compressor compressor alarmAlr_DrCmpInpPhAlrRead
BI326Drives Compressor rotor blockedAlr_DrCmpRtrBlkAlrRead
BI327Drives Compressor current limit alarmAlr_DrCmpILimitAlrRead
BI328Drives Compressor voltage limit alarmAlr_DrCmpVLimitAlrRead
BI329Drives Compressor rotor direction alarmAlr_DrCmpRtrDirAlrRead
BI330Drives Compressor Eeprom errorAlr_DrCmpEEPROMRead
BI331Drives Compressor internal StopAlr_DrCmpIntrnStpRead
BI332Drives Compressor Earth fault alarmAlr_DrCmpEarthFltRead
BI333Drives Compressor Motor phase alarmAlr_DrCmpPhaseErrRead
BI334Drives Compressot MOC communication errAlr_DrCmpComErrMOCRead
BI335Drives Compressor 24V overload alarmAlr_DrCmp24VOvrladRead
BI336Drives Compressor internal bootloader alarmAlr_DrCmpMOCinBootRead
BI337Drives Compressor internal com alarmAlr_DrCmpComErrIOMRead
BI338Drives Compressor Motor overheat alarmAlr_DrCmpOverheatRead
BI339Drives Compressor Start up alarmAlr_DrCmpErStrtupRead
BI340Drives Compressor Pressure relax alarmAlr_DrCmpPrssRlxRead
BI341Drives Compressor Max start alarmAlr_DrCmpMaxStartsRead
BI342Drives Compressor Min run time alarmAlr_DrCmpMinRntimeRead
BI343Drives Compressor OverloadedAlr_DrCmp_OverloadRead
BI348Heat pump deicing not correctAlr_HP_Deice_IncorrectRead
BI349Heat pump water temp alarmAlr_HP_WaterTempRead
BI350State of the Heat pump Oil/Defrost inputHP_Stat_LubRead
BI352Alarm Counterflow EXC Deicing is active for too long timeAlr_CF_Timerunout_OnRead
BI353Filter calibration completed OA (valid filter data)ONLY IF 'DYNFiltCaliDone_OARead
BI354Filter calibration completed SA (valid filter data)ONLY IF 'DYNFiltCaliDone_SARead
BI355Filter calibration completed EA1 (valid filter data)ONLY IF 'DYFiltCaliDone_EA1Read
BI356Filter calibration completed EA2 (valid filter data)ONLY IF 'DYFiltCaliDone_EA2Read
BI357Pre-heating coil - Return sensor - Sensor faultPH_TempSensErrRead
BI358Drive Compressor ExistflagEXISTS_DV_CompressorRead
BVmin0Alarm reset signal (AutoReturn to zero)Alr_Reset_UsetWrite
BV1Cooling recovery: ON/OFFAHU_CoolRecovFuncWrite
BV2Summer night cooling: ON/OFFSNC_FuncWrite
BV3Summer/winter temp. compensation: ON/OFFSWTC_FuncWrite
BV4Flow/outdoor temperature compensation: ON/OFFAR_FlwTmpCmpFuncWrite
BV5Recirculation: ON/OFF ('1' = Open damper)NH_REC_Func_OnWrite
BV6Forced flow with cooling demand: ON/OFFCL_Cool_FlwForceFcWrite
BV7Automatic summer/winter time: ON/OFFSWTC_SumFuncWrite
BV8Input for forced high speedExtDrfHiPeriodWrite
BV9Run-on time for forced high speed activeExtDrfPeriodONWrite
BV10Start manual zero calibration (can be used together with automaAHU_ManZeroCaliWrite
BV11Automatic zero calibration: ON/OFFAHU_AutoZeroCaliWrite
BV12Dynamic filter alarm: ON/OFF OFF static limit on dynamic limitFiltDynAlrFuncWrite
BV13Start filter calibration. Is automatically reset to zero (OFF)FM_FiltCalibrate_StartWrite
BV15Activate outdoor temperature from BMSTR_MBT_OA_ActWrite
BV16Activate room temperature from BMSTR_MBT_Room1ActivWrite
BV17Hot water supply is available for the combi coilCmbEnHeatMBWrite
BV18Cold water supply is available for the combi coilCmbEnCoolMBWrite
BV19Force recirc via Ext. Modbus ('1' = Open damper)ExtMB_ForceRecircWrite
BV20Enable Modbus Force recirc signalExtMBEnbl_ForceRecWrite
BV21Enable combi coil for control via external Modbus [1=Modbus/0=DCmbEnCtrlMBWrite
BV22Filter (OA) Dynamic Alarm function ON/OFF OFF -> Static Limit OFilt_DynAlrFunc_OAWrite
BV23Filter (SA) Dynamic Alarm function ON/OFF OFF -> Static Limit OFilt_DynAlrFunc_SAWrite
BV24Filter (EX) Dynamic Alarm function ON/OFF OFF -> Static Limit OFilt_DynAlrFunc_EA1Write
BV25Filter (EX2) Dynamic Alarm function ON/OFF OFF -> Static LimitFilt_DynAlrFunc_EA2Write
BV26Rotary heatexchanger, turn ratation direction to counter clockEXC_CCVWrite
BV27Summer Night Cooling activated in low speedSNC_FuncLoSpeedWrite
BV28External high speed start signalExtHighSpdSetWrite
BV29Drive Compressor MountflagMNT_DV_CompressorWrite
BV30Input for forced medium speedExtDrfMePeriodWrite
BV31Limit the first step between min / max SA-BattFlow El-Heater 1EL_HT1_LimitStep_1UsetWrite
BV32Limit the first step between min / max SA-BattFlow El-Heater 2EL_HT2_LimitStep_1UsetWrite
BV33Limit the first step between min / max SA-BattFlow El- PreheatePH_EL_LimitStep_1UsetWrite
CAL0Calendar #1Calendar #1Write
CAL1Calendar #2Calendar #2Write
CAL2Calendar #3Calendar #3Write
NC0NC 00 A-AlarmNotification Class 00 A-AlarmRead
NC1NC 01 B-AlarmNotification Class 01 B-AlarmRead
SCH0Schedule #1Schedule #1Write
Object ID lookup: OJ Electronics OJ Air Plus AHU controller, SW 1.09 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09

How many BACnet points does the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 have?

This list has 979 BACnet objects: 365 analog inputs, 245 analog values, 330 binary inputs, 33 binary values, 3 calendars, 2 notification classs, 1 schedule. The exact set on a given unit depends on its firmware, installed options and configuration.

Which OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet points are writable?

282 of the 979 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09 BACnet documentation?

The source is OJ Air Plus EDE file 670203_EDE_AirPlus_SW109 (670203), revision 19/02/2026, published free by OJ Electronics at https://ojelectronics.com/controllers-sensors/wp-admin/admin-ajax.php?action=productdownload&media_id=70102341&filename=670203_EDE_AirPlus_SW109.csv.

What are the minimum BACnet points to integrate the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?

Start with AV 108 BMS-modes only avalable after activation of pysical input 'Oper (BMS run mode; needs the physical operation input); AV 134 TempSet for actual RegMode [1/100C] (Temperature setpoint for the active control mode); BV 0 Alarm reset signal (AutoReturn to zero) (Alarm reset (returns to 0 by itself)); AI 0 Actual operating mode 000-099 Unit stopped 100-199: Unit in low (Actual operating mode code); BI 0 Operation ON/OFF (Operation on/off status); AI 16 Current SupplyTemp [1/100C] (Supply air temperature, 1/100 °C); AI 5 Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u (Actual supply airflow); BI 30 Alarm relay 1 (A-alarm) (A-alarm relay (critical alarm)); BI 31 Alarm relay 2 (B-alarm) (B-alarm relay (non-critical alarm)).

How do I enable BMS control of the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?

AV 108 sets the BMS run mode, but only after the physical operation input is activated (per the object name).

Can the BMS supply sensor values to the OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?

Outdoor and room temperature can come from the BMS: write AV 102 / AV 103 and switch them in with BV 15 / BV 16.

How do I check these points on the real OJ Air Plus AHU controller (EXcon-Plus), SW 1.09?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More OJ Electronics BACnet points lists

Source: OJ Air Plus EDE file 670203_EDE_AirPlus_SW109 · 670203 · rev. 19/02/2026. Object names, instances and units are reproduced as published; descriptions are our own.