- OJ-DV / OJ-DV GEN II ventilation drive
EC/PM fan motor frequency drive · BACnet points list
OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive BACnet points list
Updated 12 November 2026
The OJ-DV fan drive has BACnet MS/TP on its RS-485 terminals and RJ12 ports. A short list of Binary Values gives run, alarm reset, fire mode and the alarm and warning flags; Integer Values carry the speed setpoint, speed limits, ramps and running data. BACnet MS/TP has to be switched on first, through the OJ PC tool or Modbus.
This page lists 53 BACnet objects for the OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.
- Manufacturer
- OJ Electronics
- Model
- OJ-DV / OJ-DV GEN II ventilation drive
- Equipment
- EC/PM fan motor frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 53 (10 writable)
- Transport
- BACnet MS/TP
- Firmware
- AOC 2.50 or later
- Also known as
- OJ-DV, OJ DV, OJ-DV GEN II, DV GEN II, OJ Drives DV, 670092, 67855
Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.
BMS integration notes: OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive
Enable BACnet MS/TP on the drive, then write the speed setpoint to IV 0 and set BV 0 to run. Read IV 8 and IV 7 for actual speed and output, and the BV alarm flags for faults; BV 1 resets alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Motor ON/OFF | Run command (1 = on); clears on any error | Write |
| IV 0 | Prc Set | Speed setpoint, 0-10000 = 0-100.00 % | Write |
| BV 1 | Reset Alarms | Alarm reset (1 = reset) | Write |
| IV 8 | RPM Out | Motor speed, rpm | Read |
| IV 7 | Prc Out | Output level, x0.01 % | Read |
| IV 12 | Power In (Filtered) | Input power, W | Read |
| BV 15 | Internal Stop | Internal stop alarm | Read |
| BV 10 | Rotor Blocked | Rotor blocked alarm | Read |
Enable & remote start
BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the motor.
Network setup
- Out of the box the drive talks Modbus (address 54, 38400 baud, no parity, 1 stop bit); BACnet MS/TP is switched on from the OJ PC tool (Alternative device communications) or through Modbus coils.
- MS/TP settings: baud 9600-115200, MAC 0-127, Max Master 1-127, device instance 0-4194302 (Modbus holding registers).
- OJ publishes an EDE file for the object list on its product page.
Watch out for
- BV 0 drops back to 0 on any error, so the BMS has to set it again after the fault is cleared.
- Do not write BV 4 = 0: it turns BACnet MS/TP off until it is re-enabled through Modbus.
- IV 0 reflects the actual setpoint when analog control is active.
OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Motor ON/OFF | Run command; drive clears it on any error | Write | 1=ON | |
| BVmin | 1 | Reset Alarms | Alarm reset; returns to 0 after the reset | Write | 1=Reset | |
| BV | 2 | Fire Mode | Fire mode active | Write | 1=Active | |
| BV | 3 | Motor Output OFF | Keep motor output off | Write | 1=Keep motor output off | |
| BV | 4 | BACnet Enable | 0 turns BACnet MS/TP off (recover via Modbus) | Write | 1=BACnet active | |
| BV | 5 | V LO Alarm | Read | 1=Alarm | ||
| BV | 6 | V HI Alarm | Read | 1=Alarm | ||
| BV | 7 | I HI Alarm | Read | 1=Alarm | ||
| BV | 8 | Temperature High | Read | 1=Warning | ||
| BV | 9 | Input Phase Error | Read | 1=Warning | ||
| BVmin | 10 | Rotor Blocked | Read | 1=Alarm | ||
| BV | 11 | Current Limit | Read | 1=Warning | ||
| BV | 12 | Voltage Limit | Read | 1=Warning | ||
| BV | 13 | Rotor Direction | Read | 1=Alarm | ||
| BV | 14 | EEPROME error | Read | 1=Warning | ||
| BVmin | 15 | Internal Stop | Read | 1=Alarm (Stop) | ||
| BV | 16 | Earth Fault | Read | 1=Alarm | ||
| BV | 17 | Motor Phase Error | Read | 1=Alarm | ||
| BV | 18 | Communication Error MOC | Read | 1=Alarm | ||
| BV | 19 | Ext 24 V Supply overload | Read | 1=Overload | ||
| BV | 20 | MOC in Bootloader | Read | 1=Alarm | ||
| BV | 21 | Communication Error IOM | Read | 1=Warning | ||
| BV | 22 | Motor Overheat IOM | Read | 1=Alarm | ||
| BV | 23 | STO Fault | Read | 1=Alarm | ||
| BV | 24 | STO test failed | Read | 1=Self test failed | ||
| IVmin | 0 | Prc Set | Speed setpoint, 0-100.00 %; value x0.01 | % | Write | |
| IV | 1 | min RPM | Minimum motor speed | rpm | Write | |
| IV | 2 | max RPM | Maximum motor speed | rpm | Write | |
| IV | 3 | Up Ramp Time | Acceleration ramp time | s | Write | |
| IV | 4 | Down Ramp Time | Deceleration ramp time | s | Write | |
| IV | 5 | AOC SW Version | value x0.01 | Read | ||
| IV | 6 | MOC SW Version | value x0.01 | Read | ||
| IVmin | 7 | Prc Out | Output level; value x0.01 | % | Read | |
| IVmin | 8 | RPM Out | Motor speed | rpm | Read | |
| IV | 9 | Intern Temp | value x0.01 | °C | Read | |
| IV | 10 | V IN_RMS | V | Read | ||
| IV | 11 | I Out | mA | Read | ||
| IVmin | 12 | Power In (Filtered) | W | Read | ||
| IV | 13 | Operation Minutes | min | Read | ||
| IV | 14 | Operations Days | days | Read | ||
| IV | 15 | Extern Set | External (analog) setpoint input | V | Read | |
| IV | 16 | V DC Bus (Peak) | V | Read | ||
| IV | 17 | V motor (Peak) | V | Read | ||
| IV | 18 | Power Consumption Wh | Wh | Read | ||
| IV | 19 | Power Consumption kWh | kWh | Read | ||
| IV | 20 | Power Consumption MWh | MWh | Read | ||
| IV | 21 | BACnet Software version | value x0.01 | Read | ||
| IV | 22 | Vin L1 - GND (RMS) | V | Read | ||
| IV | 23 | Vin L2 - GND (RMS) | V | Read | ||
| IV | 24 | Vin L3 - GND (RMS) | V | Read | ||
| IV | 25 | Vibration_SUM_RMS | 2 mg | Read | ||
| IV | 26 | AOC Thermist.Temp | value x0.01 | °C | Read | |
| IV | 27 | CurrentTimeLow1 | s | Read |
No points match these filters.
Object ID lookup: OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive point IDs by name
BV0Motor ON/OFFBV1Reset AlarmsBV2Fire ModeBV3Motor Output OFFBV4BACnet EnableBV5V LO AlarmBV6V HI AlarmBV7I HI AlarmBV8Temperature HighBV9Input Phase ErrorBV10Rotor BlockedBV11Current LimitBV12Voltage LimitBV13Rotor DirectionBV14EEPROME errorBV15Internal StopBV16Earth FaultBV17Motor Phase ErrorBV18Communication Error MOCBV19Ext 24 V Supply overloadBV20MOC in BootloaderBV21Communication Error IOMBV22Motor Overheat IOMBV23STO FaultBV24STO test failedIV0Prc SetIV1min RPMIV2max RPMIV3Up Ramp TimeIV4Down Ramp TimeIV5AOC SW VersionIV6MOC SW VersionIV7Prc OutIV8RPM OutIV9Intern TempIV10V IN_RMSIV11I OutIV12Power In (Filtered)IV13Operation MinutesIV14Operations DaysIV15Extern SetIV16V DC Bus (Peak)IV17V motor (Peak)IV18Power Consumption WhIV19Power Consumption kWhIV20Power Consumption MWhIV21BACnet Software versionIV22Vin L1 - GND (RMS)IV23Vin L2 - GND (RMS)IV24Vin L3 - GND (RMS)IV25Vibration_SUM_RMSIV26AOC Thermist.TempIV27CurrentTimeLow1
Integration notes
- Integer Value objects (IV) carry scaled whole numbers; values marked x0.01 have two implied decimals (IV 0 = 10000 means 100.00 %).
- The first-generation OJ-DV note (67855 10/20) lists BV 0-22 and IV 0-20 with the same names; BV 23-24 (STO) and IV 21-27 come from the GEN II note only.
- The GEN II table also prints a CurrentTimeHigh1 row with no object ID; it is left out here.
- Writing 0 to BV 4 turns BACnet MS/TP off; it comes back only through Modbus or protocol auto-detect.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ-DV / OJ-DV GEN II ventilation drive and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive
How many BACnet points does the OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive have?
This list has 53 BACnet objects: 25 binary values, 28 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive BACnet points are writable?
10 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive BACnet documentation?
The source is DV GEN II BACnet application note (OJ DV BACnet MS/TP protocol) (670092), revision 05/24, published free by OJ Electronics at https://ojelectronics.com/drives/wp-admin/admin-ajax.php?action=productdownload&media_id=63476983&filename=670092-05-24-DV+GEN+II+BACNET+APPLICATION+NOTE_GB_Web.pdf&view=true.
What are the minimum BACnet points to integrate the OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive?
Start with BV 0 Motor ON/OFF (Run command (1 = on); clears on any error); IV 0 Prc Set (Speed setpoint, 0-10000 = 0-100.00 %); BV 1 Reset Alarms (Alarm reset (1 = reset)); IV 8 RPM Out (Motor speed, rpm); IV 7 Prc Out (Output level, x0.01 %); IV 12 Power In (Filtered) (Input power, W); BV 15 Internal Stop (Internal stop alarm); BV 10 Rotor Blocked (Rotor blocked alarm).
How do I enable BMS control of the OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive?
BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the motor.
How do I check these points on the real OJ-DV / OJ-DV GEN II ventilation drive?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More OJ Electronics BACnet points lists
- Air handling unit controller
OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
OJ Electronics OJ Air Plus air handling unit controllers (device name EXcon-Plus) with software 1.09.
Also known as: OJ Air Plus, OJ-Air Plus, AirPlus, EXcon-Plus, EXcon Plus, 670203 - Zone ventilation controller (VAV zone master)
OJ Electronics OJ GreenZone ZoneMaster, SW 3.47
OJ Electronics GreenZone ZoneMaster demand-controlled ventilation masters with software 3.47, including their ZoneModules.
Also known as: OJ-ZoneMaster, ZoneMaster, OJ Green Zone, GreenZone, OJ ZoneControl, 67851 - Compressor frequency drive
OJ Electronics OJ-DC compressor drive
OJ Electronics OJ-DC drives for compressors in air handling units, heat pumps and chillers.
Also known as: OJ-DC, OJ DC, OJ Drives DC, 67958B - Rotary heat exchanger drive (energy recovery wheel)
OJ Electronics OJ-DRHX rotary heat exchanger drive
OJ Electronics OJ-DRHX drives for rotary heat exchanger wheels in air handling units.
Also known as: OJ-DRHX, OJ DRHX, DRHX, 67854
Source: DV GEN II BACnet application note (OJ DV BACnet MS/TP protocol) · 670092 · rev. 05/24. Object names, instances and units are reproduced as published; descriptions are our own.