Zone ventilation controller (VAV zone master) · BACnet points list
OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 BACnet points list
Updated 12 November 2026
The OJ GreenZone ZoneMaster coordinates up to 25 ZoneModules (room VAV, valve and sensor controllers) and the air handling unit for demand-controlled ventilation. Its EDE lists AHU and section values, then a fixed block of about 59 objects for each of ZoneModules 1-25: room and supply temperatures, CO2/VOC and RH, VAV flows and damper positions, valve outputs, setpoints and alarm bitmaps.
This page lists 1544 BACnet objects for the OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 — 607 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.
- Manufacturer
- OJ Electronics
- Model
- OJ GreenZone ZoneMaster, SW 3.47
- Equipment
- Zone ventilation controller (VAV zone master)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 1544 (607 writable)
- Transport
- —
- Firmware
- SW 3.47
- Default device instance
- 22020
- Also known as
- OJ-ZoneMaster, ZoneMaster, OJ Green Zone, GreenZone, OJ ZoneControl, 67851
Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.
BMS integration notes: OJ Electronics OJ GreenZone ZoneMaster, SW 3.47
To drive the system from the BMS, set BV 110 to take digital inputs from the BMS, then use BV 103 (start), BV 105 / BV 106 (max / min air) and BV 104 (fire). Read AI 111 and AI 104 for operation and AHU status, each ZoneModule's room temperature and alarm bitmaps, and AI 109 for the section alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 103 | DIN Start (BMS) | Start command from the BMS | Write |
| BV 110 | Enable Digital Input Values from BMS | Use BMS values instead of the digital inputs | Write |
| BV 105 | DIN Max Air (BMS) | Max air command from the BMS | Write |
| BV 106 | DIN Min Air (BMS) | Min air command from the BMS | Write |
| BV 112 | Clear All Alarms (BMS) | Clear all alarms | Write |
| AI 111 | ZoneMaster Operation Mode | Current operating mode of the zone system | Read |
| AI 104 | AHU status | Status of the air handling unit | Read |
| AI 1009 | ZoneModule 1 Room Temperature Actual Value | ZoneModule 1 room temperature | Read |
| AI 109 | Section Master Alarm Status | Section master alarm status | Read |
Enable & remote start
Going by the object names, BV 110 (Enable Digital Input Values from BMS) has to be on before the BMS input values BV 103-109 (start, fire, max/min air, summer night cooling) are used. The EDE has no further explanation.
Network setup
- The EDE gives device instance 22020 and device name OJ-ZoneMaster.
Watch out for
- The EDE is a full map for 25 ZoneModules; only the installed ones carry data.
- Alarm bitmaps (AI xx25-xx28 per zone) must be split into bits.
OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 100 | AHU Supply Fan Setpoint | Read | |||
| AI | 101 | AHU Extract Fan Setpoint | Read | |||
| AI | 102 | AHU Supply Air Temp Setpoint | Read | |||
| AI | 103 | AHU Cooling Pump Setpoint | Read | |||
| AImin | 104 | AHU status | Read | |||
| AI | 105 | AHU Supply Fan Alarm Status | Read | |||
| AI | 106 | AHU Extract Fan Alarm Status | Read | |||
| AI | 107 | Combined Cooling Water Temp Value | Read | |||
| AI | 108 | Combined Outdoor Temp Value | Read | |||
| AImin | 109 | Section Master Alarm Status | Read | |||
| AI | 110 | Section ZoneModule Alarm Status | Read | |||
| AImin | 111 | ZoneMaster Operation Mode | Read | |||
| AI | 112 | Actual Summer/Winter Compensation | Read | |||
| AI | 300 | Number Of Zonemodules | Read | |||
| AI | 301 | Section Supply Damper Max Position | Read | |||
| AI | 302 | Section Extract Damper Max Position | Read | |||
| AI | 303 | Section Heat Valve Max Position | Read | |||
| AI | 304 | Section Cool Valve Max Position | Read | |||
| AI | 305 | Section Minimum Temperature Setpoint | Read | |||
| AI | 306 | Section Cooling Requirement | Read | |||
| AI | 1000 | ZoneModule 1 Status | Read | |||
| AI | 1001 | ZoneModule 1 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1002 | ZoneModule 1 VAV Supply 1 Actual Flow | Read | |||
| AI | 1003 | ZoneModule 1 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1004 | ZoneModule 1 VAV Supply 2 Actual Flow | Read | |||
| AI | 1005 | ZoneModule 1 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1006 | ZoneModule 1 VAV Extract Actual Flow | Read | |||
| AI | 1007 | ZoneModule 1 Heating Valve Setpoint % | Read | |||
| AI | 1008 | ZoneModule 1 Cooling Valve Setpoint % | Read | |||
| AImin | 1009 | ZoneModule 1 Room Temperature Actual Value | Read | |||
| AI | 1010 | ZoneModule 1 Supply Temperature Actual Value | Read | |||
| AI | 1011 | ZoneModule 1 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1012 | ZoneModule 1 CO2/VOC Actual Value | Read | |||
| AI | 1013 | ZoneModule 1 RH Actual Value | Read | |||
| AI | 1014 | ZoneModule 1 Room Temperature Actual Setpoint | Read | |||
| AI | 1015 | ZoneModule 1 Room Panel Air Mode | Read | |||
| AI | 1016 | ZoneModule 1 Heating Valve Actual Flow | Read | |||
| AI | 1017 | ZoneModule 1 Cooling Valve Actual Flow | Read | |||
| AI | 1018 | ZoneModule 1 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1019 | ZoneModule 1 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1020 | ZoneModule 1 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1021 | ZoneModule 1 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1022 | ZoneModule 1 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1023 | ZoneModule 1 Ext Aout1 Output | Read | |||
| AI | 1024 | ZoneModule 1 Ext Aout2 Output | Read | |||
| AI | 1025 | ZoneModule 1 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1026 | ZoneModule 1 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1027 | ZoneModule 1 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1028 | ZoneModule 1 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1029 | ZoneModule 1 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1030 | ZoneModule 1 VAV Extract 2 Actual Flow | Read | |||
| AI | 1031 | ZoneModule 1 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1100 | ZoneModule 2 Status | Read | |||
| AI | 1101 | ZoneModule 2 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1102 | ZoneModule 2 VAV Supply 1 Actual Flow | Read | |||
| AI | 1103 | ZoneModule 2 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1104 | ZoneModule 2 VAV Supply 2 Actual Flow | Read | |||
| AI | 1105 | ZoneModule 2 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1106 | ZoneModule 2 VAV Extract Actual Flow | Read | |||
| AI | 1107 | ZoneModule 2 Heating Valve Setpoint % | Read | |||
| AI | 1108 | ZoneModule 2 Cooling Valve Setpoint % | Read | |||
| AI | 1109 | ZoneModule 2 Room Temperature Actual Value | Read | |||
| AI | 1110 | ZoneModule 2 Supply Temperature Actual Value | Read | |||
| AI | 1111 | ZoneModule 2 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1112 | ZoneModule 2 CO2/VOC Actual Value | Read | |||
| AI | 1113 | ZoneModule 2 RH Actual Value | Read | |||
| AI | 1114 | ZoneModule 2 Room Temperature Actual Setpoint | Read | |||
| AI | 1115 | ZoneModule 2 Room Panel Air Mode | Read | |||
| AI | 1116 | ZoneModule 2 Heating Valve Actual Flow | Read | |||
| AI | 1117 | ZoneModule 2 Cooling Valve Actual Flow | Read | |||
| AI | 1118 | ZoneModule 2 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1119 | ZoneModule 2 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1120 | ZoneModule 2 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1121 | ZoneModule 2 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1122 | ZoneModule 2 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1123 | ZoneModule 2 Ext Aout1 Output | Read | |||
| AI | 1124 | ZoneModule 2 Ext Aout2 Output | Read | |||
| AI | 1125 | ZoneModule 2 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1126 | ZoneModule 2 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1127 | ZoneModule 2 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1128 | ZoneModule 2 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1129 | ZoneModule 2 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1130 | ZoneModule 2 VAV Extract 2 Actual Flow | Read | |||
| AI | 1131 | ZoneModule 2 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1200 | ZoneModule 3 Status | Read | |||
| AI | 1201 | ZoneModule 3 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1202 | ZoneModule 3 VAV Supply 1 Actual Flow | Read | |||
| AI | 1203 | ZoneModule 3 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1204 | ZoneModule 3 VAV Supply 2 Actual Flow | Read | |||
| AI | 1205 | ZoneModule 3 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1206 | ZoneModule 3 VAV Extract Actual Flow | Read | |||
| AI | 1207 | ZoneModule 3 Heating Valve Setpoint % | Read | |||
| AI | 1208 | ZoneModule 3 Cooling Valve Setpoint % | Read | |||
| AI | 1209 | ZoneModule 3 Room Temperature Actual Value | Read | |||
| AI | 1210 | ZoneModule 3 Supply Temperature Actual Value | Read | |||
| AI | 1211 | ZoneModule 3 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1212 | ZoneModule 3 CO2/VOC Actual Value | Read | |||
| AI | 1213 | ZoneModule 3 RH Actual Value | Read | |||
| AI | 1214 | ZoneModule 3 Room Temperature Actual Setpoint | Read | |||
| AI | 1215 | ZoneModule 3 Room Panel Air Mode | Read | |||
| AI | 1216 | ZoneModule 3 Heating Valve Actual Flow | Read | |||
| AI | 1217 | ZoneModule 3 Cooling Valve Actual Flow | Read | |||
| AI | 1218 | ZoneModule 3 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1219 | ZoneModule 3 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1220 | ZoneModule 3 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1221 | ZoneModule 3 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1222 | ZoneModule 3 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1223 | ZoneModule 3 Ext Aout1 Output | Read | |||
| AI | 1224 | ZoneModule 3 Ext Aout2 Output | Read | |||
| AI | 1225 | ZoneModule 3 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1226 | ZoneModule 3 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1227 | ZoneModule 3 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1228 | ZoneModule 3 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1229 | ZoneModule 3 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1230 | ZoneModule 3 VAV Extract 2 Actual Flow | Read | |||
| AI | 1231 | ZoneModule 3 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1300 | ZoneModule 4 Status | Read | |||
| AI | 1301 | ZoneModule 4 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1302 | ZoneModule 4 VAV Supply 1 Actual Flow | Read | |||
| AI | 1303 | ZoneModule 4 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1304 | ZoneModule 4 VAV Supply 2 Actual Flow | Read | |||
| AI | 1305 | ZoneModule 4 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1306 | ZoneModule 4 VAV Extract Actual Flow | Read | |||
| AI | 1307 | ZoneModule 4 Heating Valve Setpoint % | Read | |||
| AI | 1308 | ZoneModule 4 Cooling Valve Setpoint % | Read | |||
| AI | 1309 | ZoneModule 4 Room Temperature Actual Value | Read | |||
| AI | 1310 | ZoneModule 4 Supply Temperature Actual Value | Read | |||
| AI | 1311 | ZoneModule 4 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1312 | ZoneModule 4 CO2/VOC Actual Value | Read | |||
| AI | 1313 | ZoneModule 4 RH Actual Value | Read | |||
| AI | 1314 | ZoneModule 4 Room Temperature Actual Setpoint | Read | |||
| AI | 1315 | ZoneModule 4 Room Panel Air Mode | Read | |||
| AI | 1316 | ZoneModule 4 Heating Valve Actual Flow | Read | |||
| AI | 1317 | ZoneModule 4 Cooling Valve Actual Flow | Read | |||
| AI | 1318 | ZoneModule 4 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1319 | ZoneModule 4 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1320 | ZoneModule 4 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1321 | ZoneModule 4 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1322 | ZoneModule 4 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1323 | ZoneModule 4 Ext Aout1 Output | Read | |||
| AI | 1324 | ZoneModule 4 Ext Aout2 Output | Read | |||
| AI | 1325 | ZoneModule 4 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1326 | ZoneModule 4 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1327 | ZoneModule 4 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1328 | ZoneModule 4 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1329 | ZoneModule 4 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1330 | ZoneModule 4 VAV Extract 2 Actual Flow | Read | |||
| AI | 1331 | ZoneModule 4 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1400 | ZoneModule 5 Status | Read | |||
| AI | 1401 | ZoneModule 5 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1402 | ZoneModule 5 VAV Supply 1 Actual Flow | Read | |||
| AI | 1403 | ZoneModule 5 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1404 | ZoneModule 5 VAV Supply 2 Actual Flow | Read | |||
| AI | 1405 | ZoneModule 5 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1406 | ZoneModule 5 VAV Extract Actual Flow | Read | |||
| AI | 1407 | ZoneModule 5 Heating Valve Setpoint % | Read | |||
| AI | 1408 | ZoneModule 5 Cooling Valve Setpoint % | Read | |||
| AI | 1409 | ZoneModule 5 Room Temperature Actual Value | Read | |||
| AI | 1410 | ZoneModule 5 Supply Temperature Actual Value | Read | |||
| AI | 1411 | ZoneModule 5 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1412 | ZoneModule 5 CO2/VOC Actual Value | Read | |||
| AI | 1413 | ZoneModule 5 RH Actual Value | Read | |||
| AI | 1414 | ZoneModule 5 Room Temperature Actual Setpoint | Read | |||
| AI | 1415 | ZoneModule 5 Room Panel Air Mode | Read | |||
| AI | 1416 | ZoneModule 5 Heating Valve Actual Flow | Read | |||
| AI | 1417 | ZoneModule 5 Cooling Valve Actual Flow | Read | |||
| AI | 1418 | ZoneModule 5 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1419 | ZoneModule 5 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1420 | ZoneModule 5 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1421 | ZoneModule 5 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1422 | ZoneModule 5 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1423 | ZoneModule 5 Ext Aout1 Output | Read | |||
| AI | 1424 | ZoneModule 5 Ext Aout2 Output | Read | |||
| AI | 1425 | ZoneModule 5 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1426 | ZoneModule 5 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1427 | ZoneModule 5 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1428 | ZoneModule 5 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1429 | ZoneModule 5 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1430 | ZoneModule 5 VAV Extract 2 Actual Flow | Read | |||
| AI | 1431 | ZoneModule 5 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1500 | ZoneModule 6 Status | Read | |||
| AI | 1501 | ZoneModule 6 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1502 | ZoneModule 6 VAV Supply 1 Actual Flow | Read | |||
| AI | 1503 | ZoneModule 6 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1504 | ZoneModule 6 VAV Supply 2 Actual Flow | Read | |||
| AI | 1505 | ZoneModule 6 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1506 | ZoneModule 6 VAV Extract Actual Flow | Read | |||
| AI | 1507 | ZoneModule 6 Heating Valve Setpoint % | Read | |||
| AI | 1508 | ZoneModule 6 Cooling Valve Setpoint % | Read | |||
| AI | 1509 | ZoneModule 6 Room Temperature Actual Value | Read | |||
| AI | 1510 | ZoneModule 6 Supply Temperature Actual Value | Read | |||
| AI | 1511 | ZoneModule 6 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1512 | ZoneModule 6 CO2/VOC Actual Value | Read | |||
| AI | 1513 | ZoneModule 6 RH Actual Value | Read | |||
| AI | 1514 | ZoneModule 6 Room Temperature Actual Setpoint | Read | |||
| AI | 1515 | ZoneModule 6 Room Panel Air Mode | Read | |||
| AI | 1516 | ZoneModule 6 Heating Valve Actual Flow | Read | |||
| AI | 1517 | ZoneModule 6 Cooling Valve Actual Flow | Read | |||
| AI | 1518 | ZoneModule 6 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1519 | ZoneModule 6 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1520 | ZoneModule 6 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1521 | ZoneModule 6 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1522 | ZoneModule 6 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1523 | ZoneModule 6 Ext Aout1 Output | Read | |||
| AI | 1524 | ZoneModule 6 Ext Aout2 Output | Read | |||
| AI | 1525 | ZoneModule 6 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1526 | ZoneModule 6 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1527 | ZoneModule 6 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1528 | ZoneModule 6 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1529 | ZoneModule 6 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1530 | ZoneModule 6 VAV Extract 2 Actual Flow | Read | |||
| AI | 1531 | ZoneModule 6 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1600 | ZoneModule 7 Status | Read | |||
| AI | 1601 | ZoneModule 7 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1602 | ZoneModule 7 VAV Supply 1 Actual Flow | Read | |||
| AI | 1603 | ZoneModule 7 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1604 | ZoneModule 7 VAV Supply 2 Actual Flow | Read | |||
| AI | 1605 | ZoneModule 7 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1606 | ZoneModule 7 VAV Extract Actual Flow | Read | |||
| AI | 1607 | ZoneModule 7 Heating Valve Setpoint % | Read | |||
| AI | 1608 | ZoneModule 7 Cooling Valve Setpoint % | Read | |||
| AI | 1609 | ZoneModule 7 Room Temperature Actual Value | Read | |||
| AI | 1610 | ZoneModule 7 Supply Temperature Actual Value | Read | |||
| AI | 1611 | ZoneModule 7 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1612 | ZoneModule 7 CO2/VOC Actual Value | Read | |||
| AI | 1613 | ZoneModule 7 RH Actual Value | Read | |||
| AI | 1614 | ZoneModule 7 Room Temperature Actual Setpoint | Read | |||
| AI | 1615 | ZoneModule 7 Room Panel Air Mode | Read | |||
| AI | 1616 | ZoneModule 7 Heating Valve Actual Flow | Read | |||
| AI | 1617 | ZoneModule 7 Cooling Valve Actual Flow | Read | |||
| AI | 1618 | ZoneModule 7 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1619 | ZoneModule 7 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1620 | ZoneModule 7 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1621 | ZoneModule 7 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1622 | ZoneModule 7 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1623 | ZoneModule 7 Ext Aout1 Output | Read | |||
| AI | 1624 | ZoneModule 7 Ext Aout2 Output | Read | |||
| AI | 1625 | ZoneModule 7 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1626 | ZoneModule 7 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1627 | ZoneModule 7 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1628 | ZoneModule 7 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1629 | ZoneModule 7 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1630 | ZoneModule 7 VAV Extract 2 Actual Flow | Read | |||
| AI | 1631 | ZoneModule 7 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1700 | ZoneModule 8 Status | Read | |||
| AI | 1701 | ZoneModule 8 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1702 | ZoneModule 8 VAV Supply 1 Actual Flow | Read | |||
| AI | 1703 | ZoneModule 8 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1704 | ZoneModule 8 VAV Supply 2 Actual Flow | Read | |||
| AI | 1705 | ZoneModule 8 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1706 | ZoneModule 8 VAV Extract Actual Flow | Read | |||
| AI | 1707 | ZoneModule 8 Heating Valve Setpoint % | Read | |||
| AI | 1708 | ZoneModule 8 Cooling Valve Setpoint % | Read | |||
| AI | 1709 | ZoneModule 8 Room Temperature Actual Value | Read | |||
| AI | 1710 | ZoneModule 8 Supply Temperature Actual Value | Read | |||
| AI | 1711 | ZoneModule 8 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1712 | ZoneModule 8 CO2/VOC Actual Value | Read | |||
| AI | 1713 | ZoneModule 8 RH Actual Value | Read | |||
| AI | 1714 | ZoneModule 8 Room Temperature Actual Setpoint | Read | |||
| AI | 1715 | ZoneModule 8 Room Panel Air Mode | Read | |||
| AI | 1716 | ZoneModule 8 Heating Valve Actual Flow | Read | |||
| AI | 1717 | ZoneModule 8 Cooling Valve Actual Flow | Read | |||
| AI | 1718 | ZoneModule 8 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1719 | ZoneModule 8 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1720 | ZoneModule 8 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1721 | ZoneModule 8 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1722 | ZoneModule 8 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1723 | ZoneModule 8 Ext Aout1 Output | Read | |||
| AI | 1724 | ZoneModule 8 Ext Aout2 Output | Read | |||
| AI | 1725 | ZoneModule 8 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1726 | ZoneModule 8 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1727 | ZoneModule 8 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1728 | ZoneModule 8 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1729 | ZoneModule 8 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1730 | ZoneModule 8 VAV Extract 2 Actual Flow | Read | |||
| AI | 1731 | ZoneModule 8 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1800 | ZoneModule 9 Status | Read | |||
| AI | 1801 | ZoneModule 9 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1802 | ZoneModule 9 VAV Supply 1 Actual Flow | Read | |||
| AI | 1803 | ZoneModule 9 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1804 | ZoneModule 9 VAV Supply 2 Actual Flow | Read | |||
| AI | 1805 | ZoneModule 9 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1806 | ZoneModule 9 VAV Extract Actual Flow | Read | |||
| AI | 1807 | ZoneModule 9 Heating Valve Setpoint % | Read | |||
| AI | 1808 | ZoneModule 9 Cooling Valve Setpoint % | Read | |||
| AI | 1809 | ZoneModule 9 Room Temperature Actual Value | Read | |||
| AI | 1810 | ZoneModule 9 Supply Temperature Actual Value | Read | |||
| AI | 1811 | ZoneModule 9 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1812 | ZoneModule 9 CO2/VOC Actual Value | Read | |||
| AI | 1813 | ZoneModule 9 RH Actual Value | Read | |||
| AI | 1814 | ZoneModule 9 Room Temperature Actual Setpoint | Read | |||
| AI | 1815 | ZoneModule 9 Room Panel Air Mode | Read | |||
| AI | 1816 | ZoneModule 9 Heating Valve Actual Flow | Read | |||
| AI | 1817 | ZoneModule 9 Cooling Valve Actual Flow | Read | |||
| AI | 1818 | ZoneModule 9 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1819 | ZoneModule 9 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1820 | ZoneModule 9 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1821 | ZoneModule 9 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1822 | ZoneModule 9 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1823 | ZoneModule 9 Ext Aout1 Output | Read | |||
| AI | 1824 | ZoneModule 9 Ext Aout2 Output | Read | |||
| AI | 1825 | ZoneModule 9 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1826 | ZoneModule 9 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1827 | ZoneModule 9 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1828 | ZoneModule 9 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1829 | ZoneModule 9 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1830 | ZoneModule 9 VAV Extract 2 Actual Flow | Read | |||
| AI | 1831 | ZoneModule 9 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 1900 | ZoneModule 10 Status | Read | |||
| AI | 1901 | ZoneModule 10 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 1902 | ZoneModule 10 VAV Supply 1 Actual Flow | Read | |||
| AI | 1903 | ZoneModule 10 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 1904 | ZoneModule 10 VAV Supply 2 Actual Flow | Read | |||
| AI | 1905 | ZoneModule 10 VAV Extract Actuator Setpoint % | Read | |||
| AI | 1906 | ZoneModule 10 VAV Extract Actual Flow | Read | |||
| AI | 1907 | ZoneModule 10 Heating Valve Setpoint % | Read | |||
| AI | 1908 | ZoneModule 10 Cooling Valve Setpoint % | Read | |||
| AI | 1909 | ZoneModule 10 Room Temperature Actual Value | Read | |||
| AI | 1910 | ZoneModule 10 Supply Temperature Actual Value | Read | |||
| AI | 1911 | ZoneModule 10 Remote Setpoint Offset Actual Value | Read | |||
| AI | 1912 | ZoneModule 10 CO2/VOC Actual Value | Read | |||
| AI | 1913 | ZoneModule 10 RH Actual Value | Read | |||
| AI | 1914 | ZoneModule 10 Room Temperature Actual Setpoint | Read | |||
| AI | 1915 | ZoneModule 10 Room Panel Air Mode | Read | |||
| AI | 1916 | ZoneModule 10 Heating Valve Actual Flow | Read | |||
| AI | 1917 | ZoneModule 10 Cooling Valve Actual Flow | Read | |||
| AI | 1918 | ZoneModule 10 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 1919 | ZoneModule 10 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 1920 | ZoneModule 10 VAV Extract Actual Damper pos. % | Read | |||
| AI | 1921 | ZoneModule 10 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 1922 | ZoneModule 10 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 1923 | ZoneModule 10 Ext Aout1 Output | Read | |||
| AI | 1924 | ZoneModule 10 Ext Aout2 Output | Read | |||
| AI | 1925 | ZoneModule 10 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 1926 | ZoneModule 10 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 1927 | ZoneModule 10 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 1928 | ZoneModule 10 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 1929 | ZoneModule 10 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 1930 | ZoneModule 10 VAV Extract 2 Actual Flow | Read | |||
| AI | 1931 | ZoneModule 10 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2000 | ZoneModule 11 Status | Read | |||
| AI | 2001 | ZoneModule 11 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2002 | ZoneModule 11 VAV Supply 1 Actual Flow | Read | |||
| AI | 2003 | ZoneModule 11 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2004 | ZoneModule 11 VAV Supply 2 Actual Flow | Read | |||
| AI | 2005 | ZoneModule 11 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2006 | ZoneModule 11 VAV Extract Actual Flow | Read | |||
| AI | 2007 | ZoneModule 11 Heating Valve Setpoint % | Read | |||
| AI | 2008 | ZoneModule 11 Cooling Valve Setpoint % | Read | |||
| AI | 2009 | ZoneModule 11 Room Temperature Actual Value | Read | |||
| AI | 2010 | ZoneModule 11 Supply Temperature Actual Value | Read | |||
| AI | 2011 | ZoneModule 11 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2012 | ZoneModule 11 CO2/VOC Actual Value | Read | |||
| AI | 2013 | ZoneModule 11 RH Actual Value | Read | |||
| AI | 2014 | ZoneModule 11 Room Temperature Actual Setpoint | Read | |||
| AI | 2015 | ZoneModule 11 Room Panel Air Mode | Read | |||
| AI | 2016 | ZoneModule 11 Heating Valve Actual Flow | Read | |||
| AI | 2017 | ZoneModule 11 Cooling Valve Actual Flow | Read | |||
| AI | 2018 | ZoneModule 11 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2019 | ZoneModule 11 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2020 | ZoneModule 11 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2021 | ZoneModule 11 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2022 | ZoneModule 11 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2023 | ZoneModule 11 Ext Aout1 Output | Read | |||
| AI | 2024 | ZoneModule 11 Ext Aout2 Output | Read | |||
| AI | 2025 | ZoneModule 11 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2026 | ZoneModule 11 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2027 | ZoneModule 11 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2028 | ZoneModule 11 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2029 | ZoneModule 11 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2030 | ZoneModule 11 VAV Extract 2 Actual Flow | Read | |||
| AI | 2031 | ZoneModule 11 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2100 | ZoneModule 12 Status | Read | |||
| AI | 2101 | ZoneModule 12 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2102 | ZoneModule 12 VAV Supply 1 Actual Flow | Read | |||
| AI | 2103 | ZoneModule 12 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2104 | ZoneModule 12 VAV Supply 2 Actual Flow | Read | |||
| AI | 2105 | ZoneModule 12 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2106 | ZoneModule 12 VAV Extract Actual Flow | Read | |||
| AI | 2107 | ZoneModule 12 Heating Valve Setpoint % | Read | |||
| AI | 2108 | ZoneModule 12 Cooling Valve Setpoint % | Read | |||
| AI | 2109 | ZoneModule 12 Room Temperature Actual Value | Read | |||
| AI | 2110 | ZoneModule 12 Supply Temperature Actual Value | Read | |||
| AI | 2111 | ZoneModule 12 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2112 | ZoneModule 12 CO2/VOC Actual Value | Read | |||
| AI | 2113 | ZoneModule 12 RH Actual Value | Read | |||
| AI | 2114 | ZoneModule 12 Room Temperature Actual Setpoint | Read | |||
| AI | 2115 | ZoneModule 12 Room Panel Air Mode | Read | |||
| AI | 2116 | ZoneModule 12 Heating Valve Actual Flow | Read | |||
| AI | 2117 | ZoneModule 12 Cooling Valve Actual Flow | Read | |||
| AI | 2118 | ZoneModule 12 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2119 | ZoneModule 12 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2120 | ZoneModule 12 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2121 | ZoneModule 12 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2122 | ZoneModule 12 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2123 | ZoneModule 12 Ext Aout1 Output | Read | |||
| AI | 2124 | ZoneModule 12 Ext Aout2 Output | Read | |||
| AI | 2125 | ZoneModule 12 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2126 | ZoneModule 12 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2127 | ZoneModule 12 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2128 | ZoneModule 12 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2129 | ZoneModule 12 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2130 | ZoneModule 12 VAV Extract 2 Actual Flow | Read | |||
| AI | 2131 | ZoneModule 12 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2200 | ZoneModule 13 Status | Read | |||
| AI | 2201 | ZoneModule 13 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2202 | ZoneModule 13 VAV Supply 1 Actual Flow | Read | |||
| AI | 2203 | ZoneModule 13 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2204 | ZoneModule 13 VAV Supply 2 Actual Flow | Read | |||
| AI | 2205 | ZoneModule 13 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2206 | ZoneModule 13 VAV Extract Actual Flow | Read | |||
| AI | 2207 | ZoneModule 13 Heating Valve Setpoint % | Read | |||
| AI | 2208 | ZoneModule 13 Cooling Valve Setpoint % | Read | |||
| AI | 2209 | ZoneModule 13 Room Temperature Actual Value | Read | |||
| AI | 2210 | ZoneModule 13 Supply Temperature Actual Value | Read | |||
| AI | 2211 | ZoneModule 13 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2212 | ZoneModule 13 CO2/VOC Actual Value | Read | |||
| AI | 2213 | ZoneModule 13 RH Actual Value | Read | |||
| AI | 2214 | ZoneModule 13 Room Temperature Actual Setpoint | Read | |||
| AI | 2215 | ZoneModule 13 Room Panel Air Mode | Read | |||
| AI | 2216 | ZoneModule 13 Heating Valve Actual Flow | Read | |||
| AI | 2217 | ZoneModule 13 Cooling Valve Actual Flow | Read | |||
| AI | 2218 | ZoneModule 13 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2219 | ZoneModule 13 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2220 | ZoneModule 13 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2221 | ZoneModule 13 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2222 | ZoneModule 13 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2223 | ZoneModule 13 Ext Aout1 Output | Read | |||
| AI | 2224 | ZoneModule 13 Ext Aout2 Output | Read | |||
| AI | 2225 | ZoneModule 13 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2226 | ZoneModule 13 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2227 | ZoneModule 13 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2228 | ZoneModule 13 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2229 | ZoneModule 13 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2230 | ZoneModule 13 VAV Extract 2 Actual Flow | Read | |||
| AI | 2231 | ZoneModule 13 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2300 | ZoneModule 14 Status | Read | |||
| AI | 2301 | ZoneModule 14 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2302 | ZoneModule 14 VAV Supply 1 Actual Flow | Read | |||
| AI | 2303 | ZoneModule 14 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2304 | ZoneModule 14 VAV Supply 2 Actual Flow | Read | |||
| AI | 2305 | ZoneModule 14 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2306 | ZoneModule 14 VAV Extract Actual Flow | Read | |||
| AI | 2307 | ZoneModule 14 Heating Valve Setpoint % | Read | |||
| AI | 2308 | ZoneModule 14 Cooling Valve Setpoint % | Read | |||
| AI | 2309 | ZoneModule 14 Room Temperature Actual Value | Read | |||
| AI | 2310 | ZoneModule 14 Supply Temperature Actual Value | Read | |||
| AI | 2311 | ZoneModule 14 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2312 | ZoneModule 14 CO2/VOC Actual Value | Read | |||
| AI | 2313 | ZoneModule 14 RH Actual Value | Read | |||
| AI | 2314 | ZoneModule 14 Room Temperature Actual Setpoint | Read | |||
| AI | 2315 | ZoneModule 14 Room Panel Air Mode | Read | |||
| AI | 2316 | ZoneModule 14 Heating Valve Actual Flow | Read | |||
| AI | 2317 | ZoneModule 14 Cooling Valve Actual Flow | Read | |||
| AI | 2318 | ZoneModule 14 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2319 | ZoneModule 14 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2320 | ZoneModule 14 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2321 | ZoneModule 14 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2322 | ZoneModule 14 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2323 | ZoneModule 14 Ext Aout1 Output | Read | |||
| AI | 2324 | ZoneModule 14 Ext Aout2 Output | Read | |||
| AI | 2325 | ZoneModule 14 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2326 | ZoneModule 14 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2327 | ZoneModule 14 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2328 | ZoneModule 14 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2329 | ZoneModule 14 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2330 | ZoneModule 14 VAV Extract 2 Actual Flow | Read | |||
| AI | 2331 | ZoneModule 14 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2400 | ZoneModule 15 Status | Read | |||
| AI | 2401 | ZoneModule 15 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2402 | ZoneModule 15 VAV Supply 1 Actual Flow | Read | |||
| AI | 2403 | ZoneModule 15 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2404 | ZoneModule 15 VAV Supply 2 Actual Flow | Read | |||
| AI | 2405 | ZoneModule 15 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2406 | ZoneModule 15 VAV Extract Actual Flow | Read | |||
| AI | 2407 | ZoneModule 15 Heating Valve Setpoint % | Read | |||
| AI | 2408 | ZoneModule 15 Cooling Valve Setpoint % | Read | |||
| AI | 2409 | ZoneModule 15 Room Temperature Actual Value | Read | |||
| AI | 2410 | ZoneModule 15 Supply Temperature Actual Value | Read | |||
| AI | 2411 | ZoneModule 15 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2412 | ZoneModule 15 CO2/VOC Actual Value | Read | |||
| AI | 2413 | ZoneModule 15 RH Actual Value | Read | |||
| AI | 2414 | ZoneModule 15 Room Temperature Actual Setpoint | Read | |||
| AI | 2415 | ZoneModule 15 Room Panel Air Mode | Read | |||
| AI | 2416 | ZoneModule 15 Heating Valve Actual Flow | Read | |||
| AI | 2417 | ZoneModule 15 Cooling Valve Actual Flow | Read | |||
| AI | 2418 | ZoneModule 15 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2419 | ZoneModule 15 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2420 | ZoneModule 15 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2421 | ZoneModule 15 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2422 | ZoneModule 15 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2423 | ZoneModule 15 Ext Aout1 Output | Read | |||
| AI | 2424 | ZoneModule 15 Ext Aout2 Output | Read | |||
| AI | 2425 | ZoneModule 15 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2426 | ZoneModule 15 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2427 | ZoneModule 15 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2428 | ZoneModule 15 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2429 | ZoneModule 15 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2430 | ZoneModule 15 VAV Extract 2 Actual Flow | Read | |||
| AI | 2431 | ZoneModule 15 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2500 | ZoneModule 16 Status | Read | |||
| AI | 2501 | ZoneModule 16 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2502 | ZoneModule 16 VAV Supply 1 Actual Flow | Read | |||
| AI | 2503 | ZoneModule 16 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2504 | ZoneModule 16 VAV Supply 2 Actual Flow | Read | |||
| AI | 2505 | ZoneModule 16 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2506 | ZoneModule 16 VAV Extract Actual Flow | Read | |||
| AI | 2507 | ZoneModule 16 Heating Valve Setpoint % | Read | |||
| AI | 2508 | ZoneModule 16 Cooling Valve Setpoint % | Read | |||
| AI | 2509 | ZoneModule 16 Room Temperature Actual Value | Read | |||
| AI | 2510 | ZoneModule 16 Supply Temperature Actual Value | Read | |||
| AI | 2511 | ZoneModule 16 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2512 | ZoneModule 16 CO2/VOC Actual Value | Read | |||
| AI | 2513 | ZoneModule 16 RH Actual Value | Read | |||
| AI | 2514 | ZoneModule 16 Room Temperature Actual Setpoint | Read | |||
| AI | 2515 | ZoneModule 16 Room Panel Air Mode | Read | |||
| AI | 2516 | ZoneModule 16 Heating Valve Actual Flow | Read | |||
| AI | 2517 | ZoneModule 16 Cooling Valve Actual Flow | Read | |||
| AI | 2518 | ZoneModule 16 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2519 | ZoneModule 16 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2520 | ZoneModule 16 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2521 | ZoneModule 16 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2522 | ZoneModule 16 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2523 | ZoneModule 16 Ext Aout1 Output | Read | |||
| AI | 2524 | ZoneModule 16 Ext Aout2 Output | Read | |||
| AI | 2525 | ZoneModule 16 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2526 | ZoneModule 16 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2527 | ZoneModule 16 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2528 | ZoneModule 16 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2529 | ZoneModule 16 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2530 | ZoneModule 16 VAV Extract 2 Actual Flow | Read | |||
| AI | 2531 | ZoneModule 16 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2600 | ZoneModule 17 Status | Read | |||
| AI | 2601 | ZoneModule 17 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2602 | ZoneModule 17 VAV Supply 1 Actual Flow | Read | |||
| AI | 2603 | ZoneModule 17 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2604 | ZoneModule 17 VAV Supply 2 Actual Flow | Read | |||
| AI | 2605 | ZoneModule 17 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2606 | ZoneModule 17 VAV Extract Actual Flow | Read | |||
| AI | 2607 | ZoneModule 17 Heating Valve Setpoint % | Read | |||
| AI | 2608 | ZoneModule 17 Cooling Valve Setpoint % | Read | |||
| AI | 2609 | ZoneModule 17 Room Temperature Actual Value | Read | |||
| AI | 2610 | ZoneModule 17 Supply Temperature Actual Value | Read | |||
| AI | 2611 | ZoneModule 17 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2612 | ZoneModule 17 CO2/VOC Actual Value | Read | |||
| AI | 2613 | ZoneModule 17 RH Actual Value | Read | |||
| AI | 2614 | ZoneModule 17 Room Temperature Actual Setpoint | Read | |||
| AI | 2615 | ZoneModule 17 Room Panel Air Mode | Read | |||
| AI | 2616 | ZoneModule 17 Heating Valve Actual Flow | Read | |||
| AI | 2617 | ZoneModule 17 Cooling Valve Actual Flow | Read | |||
| AI | 2618 | ZoneModule 17 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2619 | ZoneModule 17 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2620 | ZoneModule 17 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2621 | ZoneModule 17 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2622 | ZoneModule 17 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2623 | ZoneModule 17 Ext Aout1 Output | Read | |||
| AI | 2624 | ZoneModule 17 Ext Aout2 Output | Read | |||
| AI | 2625 | ZoneModule 17 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2626 | ZoneModule 17 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2627 | ZoneModule 17 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2628 | ZoneModule 17 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2629 | ZoneModule 17 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2630 | ZoneModule 17 VAV Extract 2 Actual Flow | Read | |||
| AI | 2631 | ZoneModule 17 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2700 | ZoneModule 18 Status | Read | |||
| AI | 2701 | ZoneModule 18 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2702 | ZoneModule 18 VAV Supply 1 Actual Flow | Read | |||
| AI | 2703 | ZoneModule 18 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2704 | ZoneModule 18 VAV Supply 2 Actual Flow | Read | |||
| AI | 2705 | ZoneModule 18 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2706 | ZoneModule 18 VAV Extract Actual Flow | Read | |||
| AI | 2707 | ZoneModule 18 Heating Valve Setpoint % | Read | |||
| AI | 2708 | ZoneModule 18 Cooling Valve Setpoint % | Read | |||
| AI | 2709 | ZoneModule 18 Room Temperature Actual Value | Read | |||
| AI | 2710 | ZoneModule 18 Supply Temperature Actual Value | Read | |||
| AI | 2711 | ZoneModule 18 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2712 | ZoneModule 18 CO2/VOC Actual Value | Read | |||
| AI | 2713 | ZoneModule 18 RH Actual Value | Read | |||
| AI | 2714 | ZoneModule 18 Room Temperature Actual Setpoint | Read | |||
| AI | 2715 | ZoneModule 18 Room Panel Air Mode | Read | |||
| AI | 2716 | ZoneModule 18 Heating Valve Actual Flow | Read | |||
| AI | 2717 | ZoneModule 18 Cooling Valve Actual Flow | Read | |||
| AI | 2718 | ZoneModule 18 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2719 | ZoneModule 18 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2720 | ZoneModule 18 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2721 | ZoneModule 18 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2722 | ZoneModule 18 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2723 | ZoneModule 18 Ext Aout1 Output | Read | |||
| AI | 2724 | ZoneModule 18 Ext Aout2 Output | Read | |||
| AI | 2725 | ZoneModule 18 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2726 | ZoneModule 18 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2727 | ZoneModule 18 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2728 | ZoneModule 18 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2729 | ZoneModule 18 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2730 | ZoneModule 18 VAV Extract 2 Actual Flow | Read | |||
| AI | 2731 | ZoneModule 18 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2800 | ZoneModule 19 Status | Read | |||
| AI | 2801 | ZoneModule 19 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2802 | ZoneModule 19 VAV Supply 1 Actual Flow | Read | |||
| AI | 2803 | ZoneModule 19 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2804 | ZoneModule 19 VAV Supply 2 Actual Flow | Read | |||
| AI | 2805 | ZoneModule 19 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2806 | ZoneModule 19 VAV Extract Actual Flow | Read | |||
| AI | 2807 | ZoneModule 19 Heating Valve Setpoint % | Read | |||
| AI | 2808 | ZoneModule 19 Cooling Valve Setpoint % | Read | |||
| AI | 2809 | ZoneModule 19 Room Temperature Actual Value | Read | |||
| AI | 2810 | ZoneModule 19 Supply Temperature Actual Value | Read | |||
| AI | 2811 | ZoneModule 19 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2812 | ZoneModule 19 CO2/VOC Actual Value | Read | |||
| AI | 2813 | ZoneModule 19 RH Actual Value | Read | |||
| AI | 2814 | ZoneModule 19 Room Temperature Actual Setpoint | Read | |||
| AI | 2815 | ZoneModule 19 Room Panel Air Mode | Read | |||
| AI | 2816 | ZoneModule 19 Heating Valve Actual Flow | Read | |||
| AI | 2817 | ZoneModule 19 Cooling Valve Actual Flow | Read | |||
| AI | 2818 | ZoneModule 19 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2819 | ZoneModule 19 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2820 | ZoneModule 19 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2821 | ZoneModule 19 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2822 | ZoneModule 19 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2823 | ZoneModule 19 Ext Aout1 Output | Read | |||
| AI | 2824 | ZoneModule 19 Ext Aout2 Output | Read | |||
| AI | 2825 | ZoneModule 19 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2826 | ZoneModule 19 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2827 | ZoneModule 19 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2828 | ZoneModule 19 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2829 | ZoneModule 19 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2830 | ZoneModule 19 VAV Extract 2 Actual Flow | Read | |||
| AI | 2831 | ZoneModule 19 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 2900 | ZoneModule 20 Status | Read | |||
| AI | 2901 | ZoneModule 20 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 2902 | ZoneModule 20 VAV Supply 1 Actual Flow | Read | |||
| AI | 2903 | ZoneModule 20 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 2904 | ZoneModule 20 VAV Supply 2 Actual Flow | Read | |||
| AI | 2905 | ZoneModule 20 VAV Extract Actuator Setpoint % | Read | |||
| AI | 2906 | ZoneModule 20 VAV Extract Actual Flow | Read | |||
| AI | 2907 | ZoneModule 20 Heating Valve Setpoint % | Read | |||
| AI | 2908 | ZoneModule 20 Cooling Valve Setpoint % | Read | |||
| AI | 2909 | ZoneModule 20 Room Temperature Actual Value | Read | |||
| AI | 2910 | ZoneModule 20 Supply Temperature Actual Value | Read | |||
| AI | 2911 | ZoneModule 20 Remote Setpoint Offset Actual Value | Read | |||
| AI | 2912 | ZoneModule 20 CO2/VOC Actual Value | Read | |||
| AI | 2913 | ZoneModule 20 RH Actual Value | Read | |||
| AI | 2914 | ZoneModule 20 Room Temperature Actual Setpoint | Read | |||
| AI | 2915 | ZoneModule 20 Room Panel Air Mode | Read | |||
| AI | 2916 | ZoneModule 20 Heating Valve Actual Flow | Read | |||
| AI | 2917 | ZoneModule 20 Cooling Valve Actual Flow | Read | |||
| AI | 2918 | ZoneModule 20 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 2919 | ZoneModule 20 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 2920 | ZoneModule 20 VAV Extract Actual Damper pos. % | Read | |||
| AI | 2921 | ZoneModule 20 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 2922 | ZoneModule 20 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 2923 | ZoneModule 20 Ext Aout1 Output | Read | |||
| AI | 2924 | ZoneModule 20 Ext Aout2 Output | Read | |||
| AI | 2925 | ZoneModule 20 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 2926 | ZoneModule 20 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 2927 | ZoneModule 20 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 2928 | ZoneModule 20 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 2929 | ZoneModule 20 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 2930 | ZoneModule 20 VAV Extract 2 Actual Flow | Read | |||
| AI | 2931 | ZoneModule 20 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3000 | ZoneModule 21 Status | Read | |||
| AI | 3001 | ZoneModule 21 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 3002 | ZoneModule 21 VAV Supply 1 Actual Flow | Read | |||
| AI | 3003 | ZoneModule 21 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 3004 | ZoneModule 21 VAV Supply 2 Actual Flow | Read | |||
| AI | 3005 | ZoneModule 21 VAV Extract Actuator Setpoint % | Read | |||
| AI | 3006 | ZoneModule 21 VAV Extract Actual Flow | Read | |||
| AI | 3007 | ZoneModule 21 Heating Valve Setpoint % | Read | |||
| AI | 3008 | ZoneModule 21 Cooling Valve Setpoint % | Read | |||
| AI | 3009 | ZoneModule 21 Room Temperature Actual Value | Read | |||
| AI | 3010 | ZoneModule 21 Supply Temperature Actual Value | Read | |||
| AI | 3011 | ZoneModule 21 Remote Setpoint Offset Actual Value | Read | |||
| AI | 3012 | ZoneModule 21 CO2/VOC Actual Value | Read | |||
| AI | 3013 | ZoneModule 21 RH Actual Value | Read | |||
| AI | 3014 | ZoneModule 21 Room Temperature Actual Setpoint | Read | |||
| AI | 3015 | ZoneModule 21 Room Panel Air Mode | Read | |||
| AI | 3016 | ZoneModule 21 Heating Valve Actual Flow | Read | |||
| AI | 3017 | ZoneModule 21 Cooling Valve Actual Flow | Read | |||
| AI | 3018 | ZoneModule 21 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 3019 | ZoneModule 21 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 3020 | ZoneModule 21 VAV Extract Actual Damper pos. % | Read | |||
| AI | 3021 | ZoneModule 21 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 3022 | ZoneModule 21 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 3023 | ZoneModule 21 Ext Aout1 Output | Read | |||
| AI | 3024 | ZoneModule 21 Ext Aout2 Output | Read | |||
| AI | 3025 | ZoneModule 21 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 3026 | ZoneModule 21 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 3027 | ZoneModule 21 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 3028 | ZoneModule 21 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 3029 | ZoneModule 21 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 3030 | ZoneModule 21 VAV Extract 2 Actual Flow | Read | |||
| AI | 3031 | ZoneModule 21 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3100 | ZoneModule 22 Status | Read | |||
| AI | 3101 | ZoneModule 22 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 3102 | ZoneModule 22 VAV Supply 1 Actual Flow | Read | |||
| AI | 3103 | ZoneModule 22 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 3104 | ZoneModule 22 VAV Supply 2 Actual Flow | Read | |||
| AI | 3105 | ZoneModule 22 VAV Extract Actuator Setpoint % | Read | |||
| AI | 3106 | ZoneModule 22 VAV Extract Actual Flow | Read | |||
| AI | 3107 | ZoneModule 22 Heating Valve Setpoint % | Read | |||
| AI | 3108 | ZoneModule 22 Cooling Valve Setpoint % | Read | |||
| AI | 3109 | ZoneModule 22 Room Temperature Actual Value | Read | |||
| AI | 3110 | ZoneModule 22 Supply Temperature Actual Value | Read | |||
| AI | 3111 | ZoneModule 22 Remote Setpoint Offset Actual Value | Read | |||
| AI | 3112 | ZoneModule 22 CO2/VOC Actual Value | Read | |||
| AI | 3113 | ZoneModule 22 RH Actual Value | Read | |||
| AI | 3114 | ZoneModule 22 Room Temperature Actual Setpoint | Read | |||
| AI | 3115 | ZoneModule 22 Room Panel Air Mode | Read | |||
| AI | 3116 | ZoneModule 22 Heating Valve Actual Flow | Read | |||
| AI | 3117 | ZoneModule 22 Cooling Valve Actual Flow | Read | |||
| AI | 3118 | ZoneModule 22 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 3119 | ZoneModule 22 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 3120 | ZoneModule 22 VAV Extract Actual Damper pos. % | Read | |||
| AI | 3121 | ZoneModule 22 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 3122 | ZoneModule 22 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 3123 | ZoneModule 22 Ext Aout1 Output | Read | |||
| AI | 3124 | ZoneModule 22 Ext Aout2 Output | Read | |||
| AI | 3125 | ZoneModule 22 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 3126 | ZoneModule 22 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 3127 | ZoneModule 22 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 3128 | ZoneModule 22 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 3129 | ZoneModule 22 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 3130 | ZoneModule 22 VAV Extract 2 Actual Flow | Read | |||
| AI | 3131 | ZoneModule 22 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3200 | ZoneModule 23 Status | Read | |||
| AI | 3201 | ZoneModule 23 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 3202 | ZoneModule 23 VAV Supply 1 Actual Flow | Read | |||
| AI | 3203 | ZoneModule 23 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 3204 | ZoneModule 23 VAV Supply 2 Actual Flow | Read | |||
| AI | 3205 | ZoneModule 23 VAV Extract Actuator Setpoint % | Read | |||
| AI | 3206 | ZoneModule 23 VAV Extract Actual Flow | Read | |||
| AI | 3207 | ZoneModule 23 Heating Valve Setpoint % | Read | |||
| AI | 3208 | ZoneModule 23 Cooling Valve Setpoint % | Read | |||
| AI | 3209 | ZoneModule 23 Room Temperature Actual Value | Read | |||
| AI | 3210 | ZoneModule 23 Supply Temperature Actual Value | Read | |||
| AI | 3211 | ZoneModule 23 Remote Setpoint Offset Actual Value | Read | |||
| AI | 3212 | ZoneModule 23 CO2/VOC Actual Value | Read | |||
| AI | 3213 | ZoneModule 23 RH Actual Value | Read | |||
| AI | 3214 | ZoneModule 23 Room Temperature Actual Setpoint | Read | |||
| AI | 3215 | ZoneModule 23 Room Panel Air Mode | Read | |||
| AI | 3216 | ZoneModule 23 Heating Valve Actual Flow | Read | |||
| AI | 3217 | ZoneModule 23 Cooling Valve Actual Flow | Read | |||
| AI | 3218 | ZoneModule 23 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 3219 | ZoneModule 23 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 3220 | ZoneModule 23 VAV Extract Actual Damper pos. % | Read | |||
| AI | 3221 | ZoneModule 23 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 3222 | ZoneModule 23 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 3223 | ZoneModule 23 Ext Aout1 Output | Read | |||
| AI | 3224 | ZoneModule 23 Ext Aout2 Output | Read | |||
| AI | 3225 | ZoneModule 23 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 3226 | ZoneModule 23 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 3227 | ZoneModule 23 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 3228 | ZoneModule 23 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 3229 | ZoneModule 23 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 3230 | ZoneModule 23 VAV Extract 2 Actual Flow | Read | |||
| AI | 3231 | ZoneModule 23 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3300 | ZoneModule 24 Status | Read | |||
| AI | 3301 | ZoneModule 24 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 3302 | ZoneModule 24 VAV Supply 1 Actual Flow | Read | |||
| AI | 3303 | ZoneModule 24 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 3304 | ZoneModule 24 VAV Supply 2 Actual Flow | Read | |||
| AI | 3305 | ZoneModule 24 VAV Extract Actuator Setpoint % | Read | |||
| AI | 3306 | ZoneModule 24 VAV Extract Actual Flow | Read | |||
| AI | 3307 | ZoneModule 24 Heating Valve Setpoint % | Read | |||
| AI | 3308 | ZoneModule 24 Cooling Valve Setpoint % | Read | |||
| AI | 3309 | ZoneModule 24 Room Temperature Actual Value | Read | |||
| AI | 3310 | ZoneModule 24 Supply Temperature Actual Value | Read | |||
| AI | 3311 | ZoneModule 24 Remote Setpoint Offset Actual Value | Read | |||
| AI | 3312 | ZoneModule 24 CO2/VOC Actual Value | Read | |||
| AI | 3313 | ZoneModule 24 RH Actual Value | Read | |||
| AI | 3314 | ZoneModule 24 Room Temperature Actual Setpoint | Read | |||
| AI | 3315 | ZoneModule 24 Room Panel Air Mode | Read | |||
| AI | 3316 | ZoneModule 24 Heating Valve Actual Flow | Read | |||
| AI | 3317 | ZoneModule 24 Cooling Valve Actual Flow | Read | |||
| AI | 3318 | ZoneModule 24 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 3319 | ZoneModule 24 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 3320 | ZoneModule 24 VAV Extract Actual Damper pos. % | Read | |||
| AI | 3321 | ZoneModule 24 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 3322 | ZoneModule 24 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 3323 | ZoneModule 24 Ext Aout1 Output | Read | |||
| AI | 3324 | ZoneModule 24 Ext Aout2 Output | Read | |||
| AI | 3325 | ZoneModule 24 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 3326 | ZoneModule 24 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 3327 | ZoneModule 24 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 3328 | ZoneModule 24 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 3329 | ZoneModule 24 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 3330 | ZoneModule 24 VAV Extract 2 Actual Flow | Read | |||
| AI | 3331 | ZoneModule 24 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3400 | ZoneModule 25 Status | Read | |||
| AI | 3401 | ZoneModule 25 VAV Supply 1 Actuator Setpoint % | Read | |||
| AI | 3402 | ZoneModule 25 VAV Supply 1 Actual Flow | Read | |||
| AI | 3403 | ZoneModule 25 VAV Supply 2 Actuator Setpoint % | Read | |||
| AI | 3404 | ZoneModule 25 VAV Supply 2 Actual Flow | Read | |||
| AI | 3405 | ZoneModule 25 VAV Extract Actuator Setpoint % | Read | |||
| AI | 3406 | ZoneModule 25 VAV Extract Actual Flow | Read | |||
| AI | 3407 | ZoneModule 25 Heating Valve Setpoint % | Read | |||
| AI | 3408 | ZoneModule 25 Cooling Valve Setpoint % | Read | |||
| AI | 3409 | ZoneModule 25 Room Temperature Actual Value | Read | |||
| AI | 3410 | ZoneModule 25 Supply Temperature Actual Value | Read | |||
| AI | 3411 | ZoneModule 25 Remote Setpoint Offset Actual Value | Read | |||
| AI | 3412 | ZoneModule 25 CO2/VOC Actual Value | Read | |||
| AI | 3413 | ZoneModule 25 RH Actual Value | Read | |||
| AI | 3414 | ZoneModule 25 Room Temperature Actual Setpoint | Read | |||
| AI | 3415 | ZoneModule 25 Room Panel Air Mode | Read | |||
| AI | 3416 | ZoneModule 25 Heating Valve Actual Flow | Read | |||
| AI | 3417 | ZoneModule 25 Cooling Valve Actual Flow | Read | |||
| AI | 3418 | ZoneModule 25 VAV Supply 1 Actual Damper pos. % | Read | |||
| AI | 3419 | ZoneModule 25 VAV Supply 2 Actual Damper pos. % | Read | |||
| AI | 3420 | ZoneModule 25 VAV Extract Actual Damper pos. % | Read | |||
| AI | 3421 | ZoneModule 25 EL Heater 1 Temp. Sensor Value | Read | |||
| AI | 3422 | ZoneModule 25 EL Heater 2 Temp. Sensor Value | Read | |||
| AI | 3423 | ZoneModule 25 Ext Aout1 Output | Read | |||
| AI | 3424 | ZoneModule 25 Ext Aout2 Output | Read | |||
| AI | 3425 | ZoneModule 25 ZoneModule Alarm Bitmap 1 | Read | |||
| AI | 3426 | ZoneModule 25 ZoneModule Alarm Bitmap 2 | Read | |||
| AI | 3427 | ZoneModule 25 ZoneModule Alarm Bitmap 3 | Read | |||
| AI | 3428 | ZoneModule 25 ZoneModule Alarm Bitmap 4 | Read | |||
| AI | 3429 | ZoneModule 25 VAV Extract 2 Actuator Setpoint % | Read | |||
| AI | 3430 | ZoneModule 25 VAV Extract 2 Actual Flow | Read | |||
| AI | 3431 | ZoneModule 25 VAV Extract 2 Actual Damper pos. % | Read | |||
| AI | 3500 | Number Of Zonemasters | Read | |||
| AI | 3501 | ZoneMaster Chain ID | Read | |||
| AI | 4000 | ZoneMaster 1 ZoneMaster Local Alarm Status | Read | |||
| AI | 4100 | ZoneMaster 2 ZoneMaster Local Alarm Status | Read | |||
| AI | 4200 | ZoneMaster 3 ZoneMaster Local Alarm Status | Read | |||
| AI | 4300 | ZoneMaster 4 ZoneMaster Local Alarm Status | Read | |||
| AI | 4400 | ZoneMaster 5 ZoneMaster Local Alarm Status | Read | |||
| AV | 0 | System Time Year | Write | |||
| AV | 1 | System Time Month | Write | |||
| AV | 2 | System Time Date | Write | |||
| AV | 3 | System Time Hour | Write | |||
| AV | 4 | System Time Minute | Write | |||
| AV | 5 | System Time Second | Write | |||
| AV | 100 | AHU Min Supply Fan Speed | Write | |||
| AV | 101 | AHU Max Supply Fan Speed | Write | |||
| AV | 102 | AHU Min Extract Fan Speed | Write | |||
| AV | 103 | AHU Max Extract Fan Speed | Write | |||
| AV | 104 | Minimum Supply Air Temperature | Write | |||
| AV | 105 | Highest Allowed Cooling Water Temp | Write | |||
| AV | 106 | Lowest Allowed Heating Water Temp | Write | |||
| AV | 107 | Winter Start Temperature | Write | |||
| AV | 108 | Winter Max Temperature | Write | |||
| AV | 109 | Winter Temp Diff | Write | |||
| AV | 110 | Summer Start Temperature | Write | |||
| AV | 111 | Summer Max Temperature | Write | |||
| AV | 112 | Summer Temp Diff | Write | |||
| AV | 113 | Max Supply Pressure | Write | |||
| AV | 114 | Max Extract Pressure | Write | |||
| AV | 1001 | ZoneModule 1 Room Temperature Setpoint | Write | |||
| AV | 1002 | ZoneModule 1 Minimum Supply Temperature | Write | |||
| AV | 1003 | ZoneModule 1 Maximum Supply Temperature | Write | |||
| AV | 1004 | ZoneModule 1 Room CO2 Setpoint | Write | |||
| AV | 1005 | ZoneModule 1 Room RH Setpoint | Write | |||
| AV | 1006 | ZoneModule 1 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1007 | ZoneModule 1 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1008 | ZoneModule 1 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1009 | ZoneModule 1 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1010 | ZoneModule 1 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1011 | ZoneModule 1 VAV Extract Min. Air Flow | Write | |||
| AV | 1012 | ZoneModule 1 VAV Extract Max. Air Flow | Write | |||
| AV | 1013 | ZoneModule 1 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1014 | ZoneModule 1 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1015 | ZoneModule 1 VAV Extract Nominal Air Flow | Write | |||
| AV | 1016 | ZoneModule 1 Room Panel Low Air Flow | Write | |||
| AV | 1017 | ZoneModule 1 Room Panel High Air Flow | Write | |||
| AV | 1018 | ZoneModule 1 Room Panel Override Timeout | Write | |||
| AV | 1019 | ZoneModule 1 Heat Valve Max. Flow | Write | |||
| AV | 1020 | ZoneModule 1 Cool Valve Max. Flow | Write | |||
| AV | 1022 | ZoneModule 1 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1023 | ZoneModule 1 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1024 | ZoneModule 1 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1101 | ZoneModule 2 Room Temperature Setpoint | Write | |||
| AV | 1102 | ZoneModule 2 Minimum Supply Temperature | Write | |||
| AV | 1103 | ZoneModule 2 Maximum Supply Temperature | Write | |||
| AV | 1104 | ZoneModule 2 Room CO2 Setpoint | Write | |||
| AV | 1105 | ZoneModule 2 Room RH Setpoint | Write | |||
| AV | 1106 | ZoneModule 2 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1107 | ZoneModule 2 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1108 | ZoneModule 2 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1109 | ZoneModule 2 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1110 | ZoneModule 2 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1111 | ZoneModule 2 VAV Extract Min. Air Flow | Write | |||
| AV | 1112 | ZoneModule 2 VAV Extract Max. Air Flow | Write | |||
| AV | 1113 | ZoneModule 2 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1114 | ZoneModule 2 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1115 | ZoneModule 2 VAV Extract Nominal Air Flow | Write | |||
| AV | 1116 | ZoneModule 2 Room Panel Low Air Flow | Write | |||
| AV | 1117 | ZoneModule 2 Room Panel High Air Flow | Write | |||
| AV | 1118 | ZoneModule 2 Room Panel Override Timeout | Write | |||
| AV | 1119 | ZoneModule 2 Heat Valve Max. Flow | Write | |||
| AV | 1120 | ZoneModule 2 Cool Valve Max. Flow | Write | |||
| AV | 1122 | ZoneModule 2 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1123 | ZoneModule 2 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1124 | ZoneModule 2 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1201 | ZoneModule 3 Room Temperature Setpoint | Write | |||
| AV | 1202 | ZoneModule 3 Minimum Supply Temperature | Write | |||
| AV | 1203 | ZoneModule 3 Maximum Supply Temperature | Write | |||
| AV | 1204 | ZoneModule 3 Room CO2 Setpoint | Write | |||
| AV | 1205 | ZoneModule 3 Room RH Setpoint | Write | |||
| AV | 1206 | ZoneModule 3 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1207 | ZoneModule 3 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1208 | ZoneModule 3 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1209 | ZoneModule 3 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1210 | ZoneModule 3 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1211 | ZoneModule 3 VAV Extract Min. Air Flow | Write | |||
| AV | 1212 | ZoneModule 3 VAV Extract Max. Air Flow | Write | |||
| AV | 1213 | ZoneModule 3 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1214 | ZoneModule 3 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1215 | ZoneModule 3 VAV Extract Nominal Air Flow | Write | |||
| AV | 1216 | ZoneModule 3 Room Panel Low Air Flow | Write | |||
| AV | 1217 | ZoneModule 3 Room Panel High Air Flow | Write | |||
| AV | 1218 | ZoneModule 3 Room Panel Override Timeout | Write | |||
| AV | 1219 | ZoneModule 3 Heat Valve Max. Flow | Write | |||
| AV | 1220 | ZoneModule 3 Cool Valve Max. Flow | Write | |||
| AV | 1222 | ZoneModule 3 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1223 | ZoneModule 3 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1224 | ZoneModule 3 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1301 | ZoneModule 4 Room Temperature Setpoint | Write | |||
| AV | 1302 | ZoneModule 4 Minimum Supply Temperature | Write | |||
| AV | 1303 | ZoneModule 4 Maximum Supply Temperature | Write | |||
| AV | 1304 | ZoneModule 4 Room CO2 Setpoint | Write | |||
| AV | 1305 | ZoneModule 4 Room RH Setpoint | Write | |||
| AV | 1306 | ZoneModule 4 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1307 | ZoneModule 4 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1308 | ZoneModule 4 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1309 | ZoneModule 4 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1310 | ZoneModule 4 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1311 | ZoneModule 4 VAV Extract Min. Air Flow | Write | |||
| AV | 1312 | ZoneModule 4 VAV Extract Max. Air Flow | Write | |||
| AV | 1313 | ZoneModule 4 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1314 | ZoneModule 4 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1315 | ZoneModule 4 VAV Extract Nominal Air Flow | Write | |||
| AV | 1316 | ZoneModule 4 Room Panel Low Air Flow | Write | |||
| AV | 1317 | ZoneModule 4 Room Panel High Air Flow | Write | |||
| AV | 1318 | ZoneModule 4 Room Panel Override Timeout | Write | |||
| AV | 1319 | ZoneModule 4 Heat Valve Max. Flow | Write | |||
| AV | 1320 | ZoneModule 4 Cool Valve Max. Flow | Write | |||
| AV | 1322 | ZoneModule 4 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1323 | ZoneModule 4 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1324 | ZoneModule 4 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1401 | ZoneModule 5 Room Temperature Setpoint | Write | |||
| AV | 1402 | ZoneModule 5 Minimum Supply Temperature | Write | |||
| AV | 1403 | ZoneModule 5 Maximum Supply Temperature | Write | |||
| AV | 1404 | ZoneModule 5 Room CO2 Setpoint | Write | |||
| AV | 1405 | ZoneModule 5 Room RH Setpoint | Write | |||
| AV | 1406 | ZoneModule 5 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1407 | ZoneModule 5 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1408 | ZoneModule 5 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1409 | ZoneModule 5 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1410 | ZoneModule 5 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1411 | ZoneModule 5 VAV Extract Min. Air Flow | Write | |||
| AV | 1412 | ZoneModule 5 VAV Extract Max. Air Flow | Write | |||
| AV | 1413 | ZoneModule 5 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1414 | ZoneModule 5 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1415 | ZoneModule 5 VAV Extract Nominal Air Flow | Write | |||
| AV | 1416 | ZoneModule 5 Room Panel Low Air Flow | Write | |||
| AV | 1417 | ZoneModule 5 Room Panel High Air Flow | Write | |||
| AV | 1418 | ZoneModule 5 Room Panel Override Timeout | Write | |||
| AV | 1419 | ZoneModule 5 Heat Valve Max. Flow | Write | |||
| AV | 1420 | ZoneModule 5 Cool Valve Max. Flow | Write | |||
| AV | 1422 | ZoneModule 5 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1423 | ZoneModule 5 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1424 | ZoneModule 5 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1501 | ZoneModule 6 Room Temperature Setpoint | Write | |||
| AV | 1502 | ZoneModule 6 Minimum Supply Temperature | Write | |||
| AV | 1503 | ZoneModule 6 Maximum Supply Temperature | Write | |||
| AV | 1504 | ZoneModule 6 Room CO2 Setpoint | Write | |||
| AV | 1505 | ZoneModule 6 Room RH Setpoint | Write | |||
| AV | 1506 | ZoneModule 6 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1507 | ZoneModule 6 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1508 | ZoneModule 6 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1509 | ZoneModule 6 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1510 | ZoneModule 6 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1511 | ZoneModule 6 VAV Extract Min. Air Flow | Write | |||
| AV | 1512 | ZoneModule 6 VAV Extract Max. Air Flow | Write | |||
| AV | 1513 | ZoneModule 6 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1514 | ZoneModule 6 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1515 | ZoneModule 6 VAV Extract Nominal Air Flow | Write | |||
| AV | 1516 | ZoneModule 6 Room Panel Low Air Flow | Write | |||
| AV | 1517 | ZoneModule 6 Room Panel High Air Flow | Write | |||
| AV | 1518 | ZoneModule 6 Room Panel Override Timeout | Write | |||
| AV | 1519 | ZoneModule 6 Heat Valve Max. Flow | Write | |||
| AV | 1520 | ZoneModule 6 Cool Valve Max. Flow | Write | |||
| AV | 1522 | ZoneModule 6 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1523 | ZoneModule 6 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1524 | ZoneModule 6 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1601 | ZoneModule 7 Room Temperature Setpoint | Write | |||
| AV | 1602 | ZoneModule 7 Minimum Supply Temperature | Write | |||
| AV | 1603 | ZoneModule 7 Maximum Supply Temperature | Write | |||
| AV | 1604 | ZoneModule 7 Room CO2 Setpoint | Write | |||
| AV | 1605 | ZoneModule 7 Room RH Setpoint | Write | |||
| AV | 1606 | ZoneModule 7 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1607 | ZoneModule 7 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1608 | ZoneModule 7 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1609 | ZoneModule 7 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1610 | ZoneModule 7 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1611 | ZoneModule 7 VAV Extract Min. Air Flow | Write | |||
| AV | 1612 | ZoneModule 7 VAV Extract Max. Air Flow | Write | |||
| AV | 1613 | ZoneModule 7 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1614 | ZoneModule 7 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1615 | ZoneModule 7 VAV Extract Nominal Air Flow | Write | |||
| AV | 1616 | ZoneModule 7 Room Panel Low Air Flow | Write | |||
| AV | 1617 | ZoneModule 7 Room Panel High Air Flow | Write | |||
| AV | 1618 | ZoneModule 7 Room Panel Override Timeout | Write | |||
| AV | 1619 | ZoneModule 7 Heat Valve Max. Flow | Write | |||
| AV | 1620 | ZoneModule 7 Cool Valve Max. Flow | Write | |||
| AV | 1622 | ZoneModule 7 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1623 | ZoneModule 7 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1624 | ZoneModule 7 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1701 | ZoneModule 8 Room Temperature Setpoint | Write | |||
| AV | 1702 | ZoneModule 8 Minimum Supply Temperature | Write | |||
| AV | 1703 | ZoneModule 8 Maximum Supply Temperature | Write | |||
| AV | 1704 | ZoneModule 8 Room CO2 Setpoint | Write | |||
| AV | 1705 | ZoneModule 8 Room RH Setpoint | Write | |||
| AV | 1706 | ZoneModule 8 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1707 | ZoneModule 8 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1708 | ZoneModule 8 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1709 | ZoneModule 8 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1710 | ZoneModule 8 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1711 | ZoneModule 8 VAV Extract Min. Air Flow | Write | |||
| AV | 1712 | ZoneModule 8 VAV Extract Max. Air Flow | Write | |||
| AV | 1713 | ZoneModule 8 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1714 | ZoneModule 8 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1715 | ZoneModule 8 VAV Extract Nominal Air Flow | Write | |||
| AV | 1716 | ZoneModule 8 Room Panel Low Air Flow | Write | |||
| AV | 1717 | ZoneModule 8 Room Panel High Air Flow | Write | |||
| AV | 1718 | ZoneModule 8 Room Panel Override Timeout | Write | |||
| AV | 1719 | ZoneModule 8 Heat Valve Max. Flow | Write | |||
| AV | 1720 | ZoneModule 8 Cool Valve Max. Flow | Write | |||
| AV | 1722 | ZoneModule 8 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1723 | ZoneModule 8 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1724 | ZoneModule 8 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1801 | ZoneModule 9 Room Temperature Setpoint | Write | |||
| AV | 1802 | ZoneModule 9 Minimum Supply Temperature | Write | |||
| AV | 1803 | ZoneModule 9 Maximum Supply Temperature | Write | |||
| AV | 1804 | ZoneModule 9 Room CO2 Setpoint | Write | |||
| AV | 1805 | ZoneModule 9 Room RH Setpoint | Write | |||
| AV | 1806 | ZoneModule 9 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1807 | ZoneModule 9 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1808 | ZoneModule 9 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1809 | ZoneModule 9 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1810 | ZoneModule 9 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1811 | ZoneModule 9 VAV Extract Min. Air Flow | Write | |||
| AV | 1812 | ZoneModule 9 VAV Extract Max. Air Flow | Write | |||
| AV | 1813 | ZoneModule 9 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1814 | ZoneModule 9 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1815 | ZoneModule 9 VAV Extract Nominal Air Flow | Write | |||
| AV | 1816 | ZoneModule 9 Room Panel Low Air Flow | Write | |||
| AV | 1817 | ZoneModule 9 Room Panel High Air Flow | Write | |||
| AV | 1818 | ZoneModule 9 Room Panel Override Timeout | Write | |||
| AV | 1819 | ZoneModule 9 Heat Valve Max. Flow | Write | |||
| AV | 1820 | ZoneModule 9 Cool Valve Max. Flow | Write | |||
| AV | 1822 | ZoneModule 9 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1823 | ZoneModule 9 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1824 | ZoneModule 9 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 1901 | ZoneModule 10 Room Temperature Setpoint | Write | |||
| AV | 1902 | ZoneModule 10 Minimum Supply Temperature | Write | |||
| AV | 1903 | ZoneModule 10 Maximum Supply Temperature | Write | |||
| AV | 1904 | ZoneModule 10 Room CO2 Setpoint | Write | |||
| AV | 1905 | ZoneModule 10 Room RH Setpoint | Write | |||
| AV | 1906 | ZoneModule 10 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 1907 | ZoneModule 10 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 1908 | ZoneModule 10 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 1909 | ZoneModule 10 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 1910 | ZoneModule 10 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 1911 | ZoneModule 10 VAV Extract Min. Air Flow | Write | |||
| AV | 1912 | ZoneModule 10 VAV Extract Max. Air Flow | Write | |||
| AV | 1913 | ZoneModule 10 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 1914 | ZoneModule 10 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 1915 | ZoneModule 10 VAV Extract Nominal Air Flow | Write | |||
| AV | 1916 | ZoneModule 10 Room Panel Low Air Flow | Write | |||
| AV | 1917 | ZoneModule 10 Room Panel High Air Flow | Write | |||
| AV | 1918 | ZoneModule 10 Room Panel Override Timeout | Write | |||
| AV | 1919 | ZoneModule 10 Heat Valve Max. Flow | Write | |||
| AV | 1920 | ZoneModule 10 Cool Valve Max. Flow | Write | |||
| AV | 1922 | ZoneModule 10 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 1923 | ZoneModule 10 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 1924 | ZoneModule 10 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2001 | ZoneModule 11 Room Temperature Setpoint | Write | |||
| AV | 2002 | ZoneModule 11 Minimum Supply Temperature | Write | |||
| AV | 2003 | ZoneModule 11 Maximum Supply Temperature | Write | |||
| AV | 2004 | ZoneModule 11 Room CO2 Setpoint | Write | |||
| AV | 2005 | ZoneModule 11 Room RH Setpoint | Write | |||
| AV | 2006 | ZoneModule 11 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2007 | ZoneModule 11 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2008 | ZoneModule 11 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2009 | ZoneModule 11 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2010 | ZoneModule 11 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2011 | ZoneModule 11 VAV Extract Min. Air Flow | Write | |||
| AV | 2012 | ZoneModule 11 VAV Extract Max. Air Flow | Write | |||
| AV | 2013 | ZoneModule 11 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2014 | ZoneModule 11 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2015 | ZoneModule 11 VAV Extract Nominal Air Flow | Write | |||
| AV | 2016 | ZoneModule 11 Room Panel Low Air Flow | Write | |||
| AV | 2017 | ZoneModule 11 Room Panel High Air Flow | Write | |||
| AV | 2018 | ZoneModule 11 Room Panel Override Timeout | Write | |||
| AV | 2019 | ZoneModule 11 Heat Valve Max. Flow | Write | |||
| AV | 2020 | ZoneModule 11 Cool Valve Max. Flow | Write | |||
| AV | 2022 | ZoneModule 11 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2023 | ZoneModule 11 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2024 | ZoneModule 11 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2101 | ZoneModule 12 Room Temperature Setpoint | Write | |||
| AV | 2102 | ZoneModule 12 Minimum Supply Temperature | Write | |||
| AV | 2103 | ZoneModule 12 Maximum Supply Temperature | Write | |||
| AV | 2104 | ZoneModule 12 Room CO2 Setpoint | Write | |||
| AV | 2105 | ZoneModule 12 Room RH Setpoint | Write | |||
| AV | 2106 | ZoneModule 12 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2107 | ZoneModule 12 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2108 | ZoneModule 12 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2109 | ZoneModule 12 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2110 | ZoneModule 12 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2111 | ZoneModule 12 VAV Extract Min. Air Flow | Write | |||
| AV | 2112 | ZoneModule 12 VAV Extract Max. Air Flow | Write | |||
| AV | 2113 | ZoneModule 12 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2114 | ZoneModule 12 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2115 | ZoneModule 12 VAV Extract Nominal Air Flow | Write | |||
| AV | 2116 | ZoneModule 12 Room Panel Low Air Flow | Write | |||
| AV | 2117 | ZoneModule 12 Room Panel High Air Flow | Write | |||
| AV | 2118 | ZoneModule 12 Room Panel Override Timeout | Write | |||
| AV | 2119 | ZoneModule 12 Heat Valve Max. Flow | Write | |||
| AV | 2120 | ZoneModule 12 Cool Valve Max. Flow | Write | |||
| AV | 2122 | ZoneModule 12 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2123 | ZoneModule 12 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2124 | ZoneModule 12 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2201 | ZoneModule 13 Room Temperature Setpoint | Write | |||
| AV | 2202 | ZoneModule 13 Minimum Supply Temperature | Write | |||
| AV | 2203 | ZoneModule 13 Maximum Supply Temperature | Write | |||
| AV | 2204 | ZoneModule 13 Room CO2 Setpoint | Write | |||
| AV | 2205 | ZoneModule 13 Room RH Setpoint | Write | |||
| AV | 2206 | ZoneModule 13 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2207 | ZoneModule 13 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2208 | ZoneModule 13 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2209 | ZoneModule 13 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2210 | ZoneModule 13 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2211 | ZoneModule 13 VAV Extract Min. Air Flow | Write | |||
| AV | 2212 | ZoneModule 13 VAV Extract Max. Air Flow | Write | |||
| AV | 2213 | ZoneModule 13 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2214 | ZoneModule 13 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2215 | ZoneModule 13 VAV Extract Nominal Air Flow | Write | |||
| AV | 2216 | ZoneModule 13 Room Panel Low Air Flow | Write | |||
| AV | 2217 | ZoneModule 13 Room Panel High Air Flow | Write | |||
| AV | 2218 | ZoneModule 13 Room Panel Override Timeout | Write | |||
| AV | 2219 | ZoneModule 13 Heat Valve Max. Flow | Write | |||
| AV | 2220 | ZoneModule 13 Cool Valve Max. Flow | Write | |||
| AV | 2222 | ZoneModule 13 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2223 | ZoneModule 13 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2224 | ZoneModule 13 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2301 | ZoneModule 14 Room Temperature Setpoint | Write | |||
| AV | 2302 | ZoneModule 14 Minimum Supply Temperature | Write | |||
| AV | 2303 | ZoneModule 14 Maximum Supply Temperature | Write | |||
| AV | 2304 | ZoneModule 14 Room CO2 Setpoint | Write | |||
| AV | 2305 | ZoneModule 14 Room RH Setpoint | Write | |||
| AV | 2306 | ZoneModule 14 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2307 | ZoneModule 14 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2308 | ZoneModule 14 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2309 | ZoneModule 14 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2310 | ZoneModule 14 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2311 | ZoneModule 14 VAV Extract Min. Air Flow | Write | |||
| AV | 2312 | ZoneModule 14 VAV Extract Max. Air Flow | Write | |||
| AV | 2313 | ZoneModule 14 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2314 | ZoneModule 14 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2315 | ZoneModule 14 VAV Extract Nominal Air Flow | Write | |||
| AV | 2316 | ZoneModule 14 Room Panel Low Air Flow | Write | |||
| AV | 2317 | ZoneModule 14 Room Panel High Air Flow | Write | |||
| AV | 2318 | ZoneModule 14 Room Panel Override Timeout | Write | |||
| AV | 2319 | ZoneModule 14 Heat Valve Max. Flow | Write | |||
| AV | 2320 | ZoneModule 14 Cool Valve Max. Flow | Write | |||
| AV | 2322 | ZoneModule 14 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2323 | ZoneModule 14 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2324 | ZoneModule 14 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2401 | ZoneModule 15 Room Temperature Setpoint | Write | |||
| AV | 2402 | ZoneModule 15 Minimum Supply Temperature | Write | |||
| AV | 2403 | ZoneModule 15 Maximum Supply Temperature | Write | |||
| AV | 2404 | ZoneModule 15 Room CO2 Setpoint | Write | |||
| AV | 2405 | ZoneModule 15 Room RH Setpoint | Write | |||
| AV | 2406 | ZoneModule 15 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2407 | ZoneModule 15 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2408 | ZoneModule 15 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2409 | ZoneModule 15 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2410 | ZoneModule 15 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2411 | ZoneModule 15 VAV Extract Min. Air Flow | Write | |||
| AV | 2412 | ZoneModule 15 VAV Extract Max. Air Flow | Write | |||
| AV | 2413 | ZoneModule 15 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2414 | ZoneModule 15 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2415 | ZoneModule 15 VAV Extract Nominal Air Flow | Write | |||
| AV | 2416 | ZoneModule 15 Room Panel Low Air Flow | Write | |||
| AV | 2417 | ZoneModule 15 Room Panel High Air Flow | Write | |||
| AV | 2418 | ZoneModule 15 Room Panel Override Timeout | Write | |||
| AV | 2419 | ZoneModule 15 Heat Valve Max. Flow | Write | |||
| AV | 2420 | ZoneModule 15 Cool Valve Max. Flow | Write | |||
| AV | 2422 | ZoneModule 15 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2423 | ZoneModule 15 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2424 | ZoneModule 15 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2501 | ZoneModule 16 Room Temperature Setpoint | Write | |||
| AV | 2502 | ZoneModule 16 Minimum Supply Temperature | Write | |||
| AV | 2503 | ZoneModule 16 Maximum Supply Temperature | Write | |||
| AV | 2504 | ZoneModule 16 Room CO2 Setpoint | Write | |||
| AV | 2505 | ZoneModule 16 Room RH Setpoint | Write | |||
| AV | 2506 | ZoneModule 16 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2507 | ZoneModule 16 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2508 | ZoneModule 16 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2509 | ZoneModule 16 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2510 | ZoneModule 16 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2511 | ZoneModule 16 VAV Extract Min. Air Flow | Write | |||
| AV | 2512 | ZoneModule 16 VAV Extract Max. Air Flow | Write | |||
| AV | 2513 | ZoneModule 16 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2514 | ZoneModule 16 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2515 | ZoneModule 16 VAV Extract Nominal Air Flow | Write | |||
| AV | 2516 | ZoneModule 16 Room Panel Low Air Flow | Write | |||
| AV | 2517 | ZoneModule 16 Room Panel High Air Flow | Write | |||
| AV | 2518 | ZoneModule 16 Room Panel Override Timeout | Write | |||
| AV | 2519 | ZoneModule 16 Heat Valve Max. Flow | Write | |||
| AV | 2520 | ZoneModule 16 Cool Valve Max. Flow | Write | |||
| AV | 2522 | ZoneModule 16 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2523 | ZoneModule 16 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2524 | ZoneModule 16 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2601 | ZoneModule 17 Room Temperature Setpoint | Write | |||
| AV | 2602 | ZoneModule 17 Minimum Supply Temperature | Write | |||
| AV | 2603 | ZoneModule 17 Maximum Supply Temperature | Write | |||
| AV | 2604 | ZoneModule 17 Room CO2 Setpoint | Write | |||
| AV | 2605 | ZoneModule 17 Room RH Setpoint | Write | |||
| AV | 2606 | ZoneModule 17 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2607 | ZoneModule 17 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2608 | ZoneModule 17 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2609 | ZoneModule 17 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2610 | ZoneModule 17 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2611 | ZoneModule 17 VAV Extract Min. Air Flow | Write | |||
| AV | 2612 | ZoneModule 17 VAV Extract Max. Air Flow | Write | |||
| AV | 2613 | ZoneModule 17 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2614 | ZoneModule 17 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2615 | ZoneModule 17 VAV Extract Nominal Air Flow | Write | |||
| AV | 2616 | ZoneModule 17 Room Panel Low Air Flow | Write | |||
| AV | 2617 | ZoneModule 17 Room Panel High Air Flow | Write | |||
| AV | 2618 | ZoneModule 17 Room Panel Override Timeout | Write | |||
| AV | 2619 | ZoneModule 17 Heat Valve Max. Flow | Write | |||
| AV | 2620 | ZoneModule 17 Cool Valve Max. Flow | Write | |||
| AV | 2622 | ZoneModule 17 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2623 | ZoneModule 17 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2624 | ZoneModule 17 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2701 | ZoneModule 18 Room Temperature Setpoint | Write | |||
| AV | 2702 | ZoneModule 18 Minimum Supply Temperature | Write | |||
| AV | 2703 | ZoneModule 18 Maximum Supply Temperature | Write | |||
| AV | 2704 | ZoneModule 18 Room CO2 Setpoint | Write | |||
| AV | 2705 | ZoneModule 18 Room RH Setpoint | Write | |||
| AV | 2706 | ZoneModule 18 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2707 | ZoneModule 18 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2708 | ZoneModule 18 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2709 | ZoneModule 18 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2710 | ZoneModule 18 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2711 | ZoneModule 18 VAV Extract Min. Air Flow | Write | |||
| AV | 2712 | ZoneModule 18 VAV Extract Max. Air Flow | Write | |||
| AV | 2713 | ZoneModule 18 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2714 | ZoneModule 18 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2715 | ZoneModule 18 VAV Extract Nominal Air Flow | Write | |||
| AV | 2716 | ZoneModule 18 Room Panel Low Air Flow | Write | |||
| AV | 2717 | ZoneModule 18 Room Panel High Air Flow | Write | |||
| AV | 2718 | ZoneModule 18 Room Panel Override Timeout | Write | |||
| AV | 2719 | ZoneModule 18 Heat Valve Max. Flow | Write | |||
| AV | 2720 | ZoneModule 18 Cool Valve Max. Flow | Write | |||
| AV | 2722 | ZoneModule 18 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2723 | ZoneModule 18 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2724 | ZoneModule 18 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2801 | ZoneModule 19 Room Temperature Setpoint | Write | |||
| AV | 2802 | ZoneModule 19 Minimum Supply Temperature | Write | |||
| AV | 2803 | ZoneModule 19 Maximum Supply Temperature | Write | |||
| AV | 2804 | ZoneModule 19 Room CO2 Setpoint | Write | |||
| AV | 2805 | ZoneModule 19 Room RH Setpoint | Write | |||
| AV | 2806 | ZoneModule 19 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2807 | ZoneModule 19 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2808 | ZoneModule 19 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2809 | ZoneModule 19 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2810 | ZoneModule 19 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2811 | ZoneModule 19 VAV Extract Min. Air Flow | Write | |||
| AV | 2812 | ZoneModule 19 VAV Extract Max. Air Flow | Write | |||
| AV | 2813 | ZoneModule 19 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2814 | ZoneModule 19 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2815 | ZoneModule 19 VAV Extract Nominal Air Flow | Write | |||
| AV | 2816 | ZoneModule 19 Room Panel Low Air Flow | Write | |||
| AV | 2817 | ZoneModule 19 Room Panel High Air Flow | Write | |||
| AV | 2818 | ZoneModule 19 Room Panel Override Timeout | Write | |||
| AV | 2819 | ZoneModule 19 Heat Valve Max. Flow | Write | |||
| AV | 2820 | ZoneModule 19 Cool Valve Max. Flow | Write | |||
| AV | 2822 | ZoneModule 19 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2823 | ZoneModule 19 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2824 | ZoneModule 19 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 2901 | ZoneModule 20 Room Temperature Setpoint | Write | |||
| AV | 2902 | ZoneModule 20 Minimum Supply Temperature | Write | |||
| AV | 2903 | ZoneModule 20 Maximum Supply Temperature | Write | |||
| AV | 2904 | ZoneModule 20 Room CO2 Setpoint | Write | |||
| AV | 2905 | ZoneModule 20 Room RH Setpoint | Write | |||
| AV | 2906 | ZoneModule 20 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 2907 | ZoneModule 20 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 2908 | ZoneModule 20 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 2909 | ZoneModule 20 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 2910 | ZoneModule 20 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 2911 | ZoneModule 20 VAV Extract Min. Air Flow | Write | |||
| AV | 2912 | ZoneModule 20 VAV Extract Max. Air Flow | Write | |||
| AV | 2913 | ZoneModule 20 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 2914 | ZoneModule 20 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 2915 | ZoneModule 20 VAV Extract Nominal Air Flow | Write | |||
| AV | 2916 | ZoneModule 20 Room Panel Low Air Flow | Write | |||
| AV | 2917 | ZoneModule 20 Room Panel High Air Flow | Write | |||
| AV | 2918 | ZoneModule 20 Room Panel Override Timeout | Write | |||
| AV | 2919 | ZoneModule 20 Heat Valve Max. Flow | Write | |||
| AV | 2920 | ZoneModule 20 Cool Valve Max. Flow | Write | |||
| AV | 2922 | ZoneModule 20 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 2923 | ZoneModule 20 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 2924 | ZoneModule 20 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 3001 | ZoneModule 21 Room Temperature Setpoint | Write | |||
| AV | 3002 | ZoneModule 21 Minimum Supply Temperature | Write | |||
| AV | 3003 | ZoneModule 21 Maximum Supply Temperature | Write | |||
| AV | 3004 | ZoneModule 21 Room CO2 Setpoint | Write | |||
| AV | 3005 | ZoneModule 21 Room RH Setpoint | Write | |||
| AV | 3006 | ZoneModule 21 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 3007 | ZoneModule 21 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 3008 | ZoneModule 21 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 3009 | ZoneModule 21 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 3010 | ZoneModule 21 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 3011 | ZoneModule 21 VAV Extract Min. Air Flow | Write | |||
| AV | 3012 | ZoneModule 21 VAV Extract Max. Air Flow | Write | |||
| AV | 3013 | ZoneModule 21 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 3014 | ZoneModule 21 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 3015 | ZoneModule 21 VAV Extract Nominal Air Flow | Write | |||
| AV | 3016 | ZoneModule 21 Room Panel Low Air Flow | Write | |||
| AV | 3017 | ZoneModule 21 Room Panel High Air Flow | Write | |||
| AV | 3018 | ZoneModule 21 Room Panel Override Timeout | Write | |||
| AV | 3019 | ZoneModule 21 Heat Valve Max. Flow | Write | |||
| AV | 3020 | ZoneModule 21 Cool Valve Max. Flow | Write | |||
| AV | 3022 | ZoneModule 21 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 3023 | ZoneModule 21 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 3024 | ZoneModule 21 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 3101 | ZoneModule 22 Room Temperature Setpoint | Write | |||
| AV | 3102 | ZoneModule 22 Minimum Supply Temperature | Write | |||
| AV | 3103 | ZoneModule 22 Maximum Supply Temperature | Write | |||
| AV | 3104 | ZoneModule 22 Room CO2 Setpoint | Write | |||
| AV | 3105 | ZoneModule 22 Room RH Setpoint | Write | |||
| AV | 3106 | ZoneModule 22 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 3107 | ZoneModule 22 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 3108 | ZoneModule 22 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 3109 | ZoneModule 22 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 3110 | ZoneModule 22 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 3111 | ZoneModule 22 VAV Extract Min. Air Flow | Write | |||
| AV | 3112 | ZoneModule 22 VAV Extract Max. Air Flow | Write | |||
| AV | 3113 | ZoneModule 22 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 3114 | ZoneModule 22 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 3115 | ZoneModule 22 VAV Extract Nominal Air Flow | Write | |||
| AV | 3116 | ZoneModule 22 Room Panel Low Air Flow | Write | |||
| AV | 3117 | ZoneModule 22 Room Panel High Air Flow | Write | |||
| AV | 3118 | ZoneModule 22 Room Panel Override Timeout | Write | |||
| AV | 3119 | ZoneModule 22 Heat Valve Max. Flow | Write | |||
| AV | 3120 | ZoneModule 22 Cool Valve Max. Flow | Write | |||
| AV | 3122 | ZoneModule 22 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 3123 | ZoneModule 22 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 3124 | ZoneModule 22 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 3201 | ZoneModule 23 Room Temperature Setpoint | Write | |||
| AV | 3202 | ZoneModule 23 Minimum Supply Temperature | Write | |||
| AV | 3203 | ZoneModule 23 Maximum Supply Temperature | Write | |||
| AV | 3204 | ZoneModule 23 Room CO2 Setpoint | Write | |||
| AV | 3205 | ZoneModule 23 Room RH Setpoint | Write | |||
| AV | 3206 | ZoneModule 23 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 3207 | ZoneModule 23 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 3208 | ZoneModule 23 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 3209 | ZoneModule 23 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 3210 | ZoneModule 23 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 3211 | ZoneModule 23 VAV Extract Min. Air Flow | Write | |||
| AV | 3212 | ZoneModule 23 VAV Extract Max. Air Flow | Write | |||
| AV | 3213 | ZoneModule 23 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 3214 | ZoneModule 23 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 3215 | ZoneModule 23 VAV Extract Nominal Air Flow | Write | |||
| AV | 3216 | ZoneModule 23 Room Panel Low Air Flow | Write | |||
| AV | 3217 | ZoneModule 23 Room Panel High Air Flow | Write | |||
| AV | 3218 | ZoneModule 23 Room Panel Override Timeout | Write | |||
| AV | 3219 | ZoneModule 23 Heat Valve Max. Flow | Write | |||
| AV | 3220 | ZoneModule 23 Cool Valve Max. Flow | Write | |||
| AV | 3222 | ZoneModule 23 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 3223 | ZoneModule 23 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 3224 | ZoneModule 23 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 3301 | ZoneModule 24 Room Temperature Setpoint | Write | |||
| AV | 3302 | ZoneModule 24 Minimum Supply Temperature | Write | |||
| AV | 3303 | ZoneModule 24 Maximum Supply Temperature | Write | |||
| AV | 3304 | ZoneModule 24 Room CO2 Setpoint | Write | |||
| AV | 3305 | ZoneModule 24 Room RH Setpoint | Write | |||
| AV | 3306 | ZoneModule 24 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 3307 | ZoneModule 24 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 3308 | ZoneModule 24 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 3309 | ZoneModule 24 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 3310 | ZoneModule 24 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 3311 | ZoneModule 24 VAV Extract Min. Air Flow | Write | |||
| AV | 3312 | ZoneModule 24 VAV Extract Max. Air Flow | Write | |||
| AV | 3313 | ZoneModule 24 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 3314 | ZoneModule 24 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 3315 | ZoneModule 24 VAV Extract Nominal Air Flow | Write | |||
| AV | 3316 | ZoneModule 24 Room Panel Low Air Flow | Write | |||
| AV | 3317 | ZoneModule 24 Room Panel High Air Flow | Write | |||
| AV | 3318 | ZoneModule 24 Room Panel Override Timeout | Write | |||
| AV | 3319 | ZoneModule 24 Heat Valve Max. Flow | Write | |||
| AV | 3320 | ZoneModule 24 Cool Valve Max. Flow | Write | |||
| AV | 3322 | ZoneModule 24 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 3323 | ZoneModule 24 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 3324 | ZoneModule 24 VAV Extract 2 Max. Air Flow | Write | |||
| AV | 3401 | ZoneModule 25 Room Temperature Setpoint | Write | |||
| AV | 3402 | ZoneModule 25 Minimum Supply Temperature | Write | |||
| AV | 3403 | ZoneModule 25 Maximum Supply Temperature | Write | |||
| AV | 3404 | ZoneModule 25 Room CO2 Setpoint | Write | |||
| AV | 3405 | ZoneModule 25 Room RH Setpoint | Write | |||
| AV | 3406 | ZoneModule 25 VAV Supply PIR Min. Air Flow | Write | |||
| AV | 3407 | ZoneModule 25 VAV Supply 1 Min. Air Flow | Write | |||
| AV | 3408 | ZoneModule 25 VAV Supply 1 Max. Air Flow | Write | |||
| AV | 3409 | ZoneModule 25 VAV Supply 2 Min. Air Flow | Write | |||
| AV | 3410 | ZoneModule 25 VAV Supply 2 Max. Air Flow | Write | |||
| AV | 3411 | ZoneModule 25 VAV Extract Min. Air Flow | Write | |||
| AV | 3412 | ZoneModule 25 VAV Extract Max. Air Flow | Write | |||
| AV | 3413 | ZoneModule 25 VAV Supply 1 Nominal Air Flow | Write | |||
| AV | 3414 | ZoneModule 25 VAV Supply 2 Nominal Air Flow | Write | |||
| AV | 3415 | ZoneModule 25 VAV Extract Nominal Air Flow | Write | |||
| AV | 3416 | ZoneModule 25 Room Panel Low Air Flow | Write | |||
| AV | 3417 | ZoneModule 25 Room Panel High Air Flow | Write | |||
| AV | 3418 | ZoneModule 25 Room Panel Override Timeout | Write | |||
| AV | 3419 | ZoneModule 25 Heat Valve Max. Flow | Write | |||
| AV | 3420 | ZoneModule 25 Cool Valve Max. Flow | Write | |||
| AV | 3422 | ZoneModule 25 VAV Extract 2 Nominal Air Flow | Write | |||
| AV | 3423 | ZoneModule 25 VAV Extract 2 Min. Air Flow | Write | |||
| AV | 3424 | ZoneModule 25 VAV Extract 2 Max. Air Flow | Write | |||
| BI | 100 | AHU Heating Pump State | Read | |||
| BI | 101 | Combined DIN Supply Fan Alarm | Read | |||
| BI | 102 | Combined DIN Extract Fan Alarm | Read | |||
| BI | 103 | Combined DIN Start | Read | |||
| BI | 104 | Combined DIN Fire | Read | |||
| BI | 105 | Combined DIN Max Air | Read | |||
| BI | 106 | Combined DIN Min Air | Read | |||
| BI | 107 | Combined DIN Summer Night Cooling | Read | |||
| BI | 300 | Section PIR Status | Read | |||
| BI | 301 | Section Frost Protection Status | Read | |||
| BI | 1000 | ZoneModule 1 Window/Frost Value | Read | |||
| BI | 1001 | ZoneModule 1 PIR Active Flag | Read | |||
| BI | 1002 | ZoneModule 1 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1003 | ZoneModule 1 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1100 | ZoneModule 2 Window/Frost Value | Read | |||
| BI | 1101 | ZoneModule 2 PIR Active Flag | Read | |||
| BI | 1102 | ZoneModule 2 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1103 | ZoneModule 2 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1200 | ZoneModule 3 Window/Frost Value | Read | |||
| BI | 1201 | ZoneModule 3 PIR Active Flag | Read | |||
| BI | 1202 | ZoneModule 3 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1203 | ZoneModule 3 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1300 | ZoneModule 4 Window/Frost Value | Read | |||
| BI | 1301 | ZoneModule 4 PIR Active Flag | Read | |||
| BI | 1302 | ZoneModule 4 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1303 | ZoneModule 4 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1400 | ZoneModule 5 Window/Frost Value | Read | |||
| BI | 1401 | ZoneModule 5 PIR Active Flag | Read | |||
| BI | 1402 | ZoneModule 5 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1403 | ZoneModule 5 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1500 | ZoneModule 6 Window/Frost Value | Read | |||
| BI | 1501 | ZoneModule 6 PIR Active Flag | Read | |||
| BI | 1502 | ZoneModule 6 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1503 | ZoneModule 6 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1600 | ZoneModule 7 Window/Frost Value | Read | |||
| BI | 1601 | ZoneModule 7 PIR Active Flag | Read | |||
| BI | 1602 | ZoneModule 7 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1603 | ZoneModule 7 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1700 | ZoneModule 8 Window/Frost Value | Read | |||
| BI | 1701 | ZoneModule 8 PIR Active Flag | Read | |||
| BI | 1702 | ZoneModule 8 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1703 | ZoneModule 8 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1800 | ZoneModule 9 Window/Frost Value | Read | |||
| BI | 1801 | ZoneModule 9 PIR Active Flag | Read | |||
| BI | 1802 | ZoneModule 9 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1803 | ZoneModule 9 Supply Temp Sensor Short Circuit Fla | Read | |||
| BI | 1900 | ZoneModule 10 Window/Frost Value | Read | |||
| BI | 1901 | ZoneModule 10 PIR Active Flag | Read | |||
| BI | 1902 | ZoneModule 10 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 1903 | ZoneModule 10 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2000 | ZoneModule 11 Window/Frost Value | Read | |||
| BI | 2001 | ZoneModule 11 PIR Active Flag | Read | |||
| BI | 2002 | ZoneModule 11 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2003 | ZoneModule 11 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2100 | ZoneModule 12 Window/Frost Value | Read | |||
| BI | 2101 | ZoneModule 12 PIR Active Flag | Read | |||
| BI | 2102 | ZoneModule 12 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2103 | ZoneModule 12 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2200 | ZoneModule 13 Window/Frost Value | Read | |||
| BI | 2201 | ZoneModule 13 PIR Active Flag | Read | |||
| BI | 2202 | ZoneModule 13 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2203 | ZoneModule 13 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2300 | ZoneModule 14 Window/Frost Value | Read | |||
| BI | 2301 | ZoneModule 14 PIR Active Flag | Read | |||
| BI | 2302 | ZoneModule 14 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2303 | ZoneModule 14 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2400 | ZoneModule 15 Window/Frost Value | Read | |||
| BI | 2401 | ZoneModule 15 PIR Active Flag | Read | |||
| BI | 2402 | ZoneModule 15 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2403 | ZoneModule 15 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2500 | ZoneModule 16 Window/Frost Value | Read | |||
| BI | 2501 | ZoneModule 16 PIR Active Flag | Read | |||
| BI | 2502 | ZoneModule 16 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2503 | ZoneModule 16 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2600 | ZoneModule 17 Window/Frost Value | Read | |||
| BI | 2601 | ZoneModule 17 PIR Active Flag | Read | |||
| BI | 2602 | ZoneModule 17 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2603 | ZoneModule 17 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2700 | ZoneModule 18 Window/Frost Value | Read | |||
| BI | 2701 | ZoneModule 18 PIR Active Flag | Read | |||
| BI | 2702 | ZoneModule 18 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2703 | ZoneModule 18 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2800 | ZoneModule 19 Window/Frost Value | Read | |||
| BI | 2801 | ZoneModule 19 PIR Active Flag | Read | |||
| BI | 2802 | ZoneModule 19 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2803 | ZoneModule 19 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 2900 | ZoneModule 20 Window/Frost Value | Read | |||
| BI | 2901 | ZoneModule 20 PIR Active Flag | Read | |||
| BI | 2902 | ZoneModule 20 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 2903 | ZoneModule 20 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 3000 | ZoneModule 21 Window/Frost Value | Read | |||
| BI | 3001 | ZoneModule 21 PIR Active Flag | Read | |||
| BI | 3002 | ZoneModule 21 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 3003 | ZoneModule 21 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 3100 | ZoneModule 22 Window/Frost Value | Read | |||
| BI | 3101 | ZoneModule 22 PIR Active Flag | Read | |||
| BI | 3102 | ZoneModule 22 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 3103 | ZoneModule 22 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 3200 | ZoneModule 23 Window/Frost Value | Read | |||
| BI | 3201 | ZoneModule 23 PIR Active Flag | Read | |||
| BI | 3202 | ZoneModule 23 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 3203 | ZoneModule 23 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 3300 | ZoneModule 24 Window/Frost Value | Read | |||
| BI | 3301 | ZoneModule 24 PIR Active Flag | Read | |||
| BI | 3302 | ZoneModule 24 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 3303 | ZoneModule 24 Supply Temp Sensor Short Circuit Fl | Read | |||
| BI | 3400 | ZoneModule 25 Window/Frost Value | Read | |||
| BI | 3401 | ZoneModule 25 PIR Active Flag | Read | |||
| BI | 3402 | ZoneModule 25 Room Temp Sensor Short Circuit Flag | Read | |||
| BI | 3403 | ZoneModule 25 Supply Temp Sensor Short Circuit Fl | Read | |||
| BV | 100 | Summer/Winter Compensation Enable | Write | |||
| BVmin | 103 | DIN Start (BMS) | Write | |||
| BV | 104 | DIN Fire (BMS) | Write | |||
| BVmin | 105 | DIN Max Air (BMS) | Write | |||
| BVmin | 106 | DIN Min Air (BMS) | Write | |||
| BV | 107 | DIN Combi-Heat Available (BMS) | Write | |||
| BV | 108 | DIN Combi-Cool Available (BMS) | Write | |||
| BV | 109 | DIN Summer Night Cooling (BMS) | Write | |||
| BVmin | 110 | Enable Digital Input Values from BMS | Write | |||
| BV | 111 | Week Schedule Enabled in Zones | Write | |||
| BVmin | 112 | Clear All Alarms (BMS) | Write |
No points match these filters.
Object ID lookup: OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 point IDs by name
AI100AHU Supply Fan SetpointAI101AHU Extract Fan SetpointAI102AHU Supply Air Temp SetpointAI103AHU Cooling Pump SetpointAI104AHU statusAI105AHU Supply Fan Alarm StatusAI106AHU Extract Fan Alarm StatusAI107Combined Cooling Water Temp ValueAI108Combined Outdoor Temp ValueAI109Section Master Alarm StatusAI110Section ZoneModule Alarm StatusAI111ZoneMaster Operation ModeAI112Actual Summer/Winter CompensationAI300Number Of ZonemodulesAI301Section Supply Damper Max PositionAI302Section Extract Damper Max PositionAI303Section Heat Valve Max PositionAI304Section Cool Valve Max PositionAI305Section Minimum Temperature SetpointAI306Section Cooling RequirementAI1000ZoneModule 1 StatusAI1001ZoneModule 1 VAV Supply 1 Actuator Setpoint %AI1002ZoneModule 1 VAV Supply 1 Actual FlowAI1003ZoneModule 1 VAV Supply 2 Actuator Setpoint %AI1004ZoneModule 1 VAV Supply 2 Actual FlowAI1005ZoneModule 1 VAV Extract Actuator Setpoint %AI1006ZoneModule 1 VAV Extract Actual FlowAI1007ZoneModule 1 Heating Valve Setpoint %AI1008ZoneModule 1 Cooling Valve Setpoint %AI1009ZoneModule 1 Room Temperature Actual ValueAI1010ZoneModule 1 Supply Temperature Actual ValueAI1011ZoneModule 1 Remote Setpoint Offset Actual ValueAI1012ZoneModule 1 CO2/VOC Actual ValueAI1013ZoneModule 1 RH Actual ValueAI1014ZoneModule 1 Room Temperature Actual SetpointAI1015ZoneModule 1 Room Panel Air ModeAI1016ZoneModule 1 Heating Valve Actual FlowAI1017ZoneModule 1 Cooling Valve Actual FlowAI1018ZoneModule 1 VAV Supply 1 Actual Damper pos. %AI1019ZoneModule 1 VAV Supply 2 Actual Damper pos. %AI1020ZoneModule 1 VAV Extract Actual Damper pos. %AI1021ZoneModule 1 EL Heater 1 Temp. Sensor ValueAI1022ZoneModule 1 EL Heater 2 Temp. Sensor ValueAI1023ZoneModule 1 Ext Aout1 OutputAI1024ZoneModule 1 Ext Aout2 OutputAI1025ZoneModule 1 ZoneModule Alarm Bitmap 1AI1026ZoneModule 1 ZoneModule Alarm Bitmap 2AI1027ZoneModule 1 ZoneModule Alarm Bitmap 3AI1028ZoneModule 1 ZoneModule Alarm Bitmap 4AI1029ZoneModule 1 VAV Extract 2 Actuator Setpoint %AI1030ZoneModule 1 VAV Extract 2 Actual FlowAI1031ZoneModule 1 VAV Extract 2 Actual Damper pos. %AI1100ZoneModule 2 StatusAI1101ZoneModule 2 VAV Supply 1 Actuator Setpoint %AI1102ZoneModule 2 VAV Supply 1 Actual FlowAI1103ZoneModule 2 VAV Supply 2 Actuator Setpoint %AI1104ZoneModule 2 VAV Supply 2 Actual FlowAI1105ZoneModule 2 VAV Extract Actuator Setpoint %AI1106ZoneModule 2 VAV Extract Actual FlowAI1107ZoneModule 2 Heating Valve Setpoint %AI1108ZoneModule 2 Cooling Valve Setpoint %AI1109ZoneModule 2 Room Temperature Actual ValueAI1110ZoneModule 2 Supply Temperature Actual ValueAI1111ZoneModule 2 Remote Setpoint Offset Actual ValueAI1112ZoneModule 2 CO2/VOC Actual ValueAI1113ZoneModule 2 RH Actual ValueAI1114ZoneModule 2 Room Temperature Actual SetpointAI1115ZoneModule 2 Room Panel Air ModeAI1116ZoneModule 2 Heating Valve Actual FlowAI1117ZoneModule 2 Cooling Valve Actual FlowAI1118ZoneModule 2 VAV Supply 1 Actual Damper pos. %AI1119ZoneModule 2 VAV Supply 2 Actual Damper pos. %AI1120ZoneModule 2 VAV Extract Actual Damper pos. %AI1121ZoneModule 2 EL Heater 1 Temp. Sensor ValueAI1122ZoneModule 2 EL Heater 2 Temp. Sensor ValueAI1123ZoneModule 2 Ext Aout1 OutputAI1124ZoneModule 2 Ext Aout2 OutputAI1125ZoneModule 2 ZoneModule Alarm Bitmap 1AI1126ZoneModule 2 ZoneModule Alarm Bitmap 2AI1127ZoneModule 2 ZoneModule Alarm Bitmap 3AI1128ZoneModule 2 ZoneModule Alarm Bitmap 4AI1129ZoneModule 2 VAV Extract 2 Actuator Setpoint %AI1130ZoneModule 2 VAV Extract 2 Actual FlowAI1131ZoneModule 2 VAV Extract 2 Actual Damper pos. %AI1200ZoneModule 3 StatusAI1201ZoneModule 3 VAV Supply 1 Actuator Setpoint %AI1202ZoneModule 3 VAV Supply 1 Actual FlowAI1203ZoneModule 3 VAV Supply 2 Actuator Setpoint %AI1204ZoneModule 3 VAV Supply 2 Actual FlowAI1205ZoneModule 3 VAV Extract Actuator Setpoint %AI1206ZoneModule 3 VAV Extract Actual FlowAI1207ZoneModule 3 Heating Valve Setpoint %AI1208ZoneModule 3 Cooling Valve Setpoint %AI1209ZoneModule 3 Room Temperature Actual ValueAI1210ZoneModule 3 Supply Temperature Actual ValueAI1211ZoneModule 3 Remote Setpoint Offset Actual ValueAI1212ZoneModule 3 CO2/VOC Actual ValueAI1213ZoneModule 3 RH Actual ValueAI1214ZoneModule 3 Room Temperature Actual SetpointAI1215ZoneModule 3 Room Panel Air ModeAI1216ZoneModule 3 Heating Valve Actual FlowAI1217ZoneModule 3 Cooling Valve Actual FlowAI1218ZoneModule 3 VAV Supply 1 Actual Damper pos. %AI1219ZoneModule 3 VAV Supply 2 Actual Damper pos. %AI1220ZoneModule 3 VAV Extract Actual Damper pos. %AI1221ZoneModule 3 EL Heater 1 Temp. Sensor ValueAI1222ZoneModule 3 EL Heater 2 Temp. Sensor ValueAI1223ZoneModule 3 Ext Aout1 OutputAI1224ZoneModule 3 Ext Aout2 OutputAI1225ZoneModule 3 ZoneModule Alarm Bitmap 1AI1226ZoneModule 3 ZoneModule Alarm Bitmap 2AI1227ZoneModule 3 ZoneModule Alarm Bitmap 3AI1228ZoneModule 3 ZoneModule Alarm Bitmap 4AI1229ZoneModule 3 VAV Extract 2 Actuator Setpoint %AI1230ZoneModule 3 VAV Extract 2 Actual FlowAI1231ZoneModule 3 VAV Extract 2 Actual Damper pos. %AI1300ZoneModule 4 StatusAI1301ZoneModule 4 VAV Supply 1 Actuator Setpoint %AI1302ZoneModule 4 VAV Supply 1 Actual FlowAI1303ZoneModule 4 VAV Supply 2 Actuator Setpoint %AI1304ZoneModule 4 VAV Supply 2 Actual FlowAI1305ZoneModule 4 VAV Extract Actuator Setpoint %AI1306ZoneModule 4 VAV Extract Actual FlowAI1307ZoneModule 4 Heating Valve Setpoint %AI1308ZoneModule 4 Cooling Valve Setpoint %AI1309ZoneModule 4 Room Temperature Actual ValueAI1310ZoneModule 4 Supply Temperature Actual ValueAI1311ZoneModule 4 Remote Setpoint Offset Actual ValueAI1312ZoneModule 4 CO2/VOC Actual ValueAI1313ZoneModule 4 RH Actual ValueAI1314ZoneModule 4 Room Temperature Actual SetpointAI1315ZoneModule 4 Room Panel Air ModeAI1316ZoneModule 4 Heating Valve Actual FlowAI1317ZoneModule 4 Cooling Valve Actual FlowAI1318ZoneModule 4 VAV Supply 1 Actual Damper pos. %AI1319ZoneModule 4 VAV Supply 2 Actual Damper pos. %AI1320ZoneModule 4 VAV Extract Actual Damper pos. %AI1321ZoneModule 4 EL Heater 1 Temp. Sensor ValueAI1322ZoneModule 4 EL Heater 2 Temp. Sensor ValueAI1323ZoneModule 4 Ext Aout1 OutputAI1324ZoneModule 4 Ext Aout2 OutputAI1325ZoneModule 4 ZoneModule Alarm Bitmap 1AI1326ZoneModule 4 ZoneModule Alarm Bitmap 2AI1327ZoneModule 4 ZoneModule Alarm Bitmap 3AI1328ZoneModule 4 ZoneModule Alarm Bitmap 4AI1329ZoneModule 4 VAV Extract 2 Actuator Setpoint %AI1330ZoneModule 4 VAV Extract 2 Actual FlowAI1331ZoneModule 4 VAV Extract 2 Actual Damper pos. %AI1400ZoneModule 5 StatusAI1401ZoneModule 5 VAV Supply 1 Actuator Setpoint %AI1402ZoneModule 5 VAV Supply 1 Actual FlowAI1403ZoneModule 5 VAV Supply 2 Actuator Setpoint %AI1404ZoneModule 5 VAV Supply 2 Actual FlowAI1405ZoneModule 5 VAV Extract Actuator Setpoint %AI1406ZoneModule 5 VAV Extract Actual FlowAI1407ZoneModule 5 Heating Valve Setpoint %AI1408ZoneModule 5 Cooling Valve Setpoint %AI1409ZoneModule 5 Room Temperature Actual ValueAI1410ZoneModule 5 Supply Temperature Actual ValueAI1411ZoneModule 5 Remote Setpoint Offset Actual ValueAI1412ZoneModule 5 CO2/VOC Actual ValueAI1413ZoneModule 5 RH Actual ValueAI1414ZoneModule 5 Room Temperature Actual SetpointAI1415ZoneModule 5 Room Panel Air ModeAI1416ZoneModule 5 Heating Valve Actual FlowAI1417ZoneModule 5 Cooling Valve Actual FlowAI1418ZoneModule 5 VAV Supply 1 Actual Damper pos. %AI1419ZoneModule 5 VAV Supply 2 Actual Damper pos. %AI1420ZoneModule 5 VAV Extract Actual Damper pos. %AI1421ZoneModule 5 EL Heater 1 Temp. Sensor ValueAI1422ZoneModule 5 EL Heater 2 Temp. Sensor ValueAI1423ZoneModule 5 Ext Aout1 OutputAI1424ZoneModule 5 Ext Aout2 OutputAI1425ZoneModule 5 ZoneModule Alarm Bitmap 1AI1426ZoneModule 5 ZoneModule Alarm Bitmap 2AI1427ZoneModule 5 ZoneModule Alarm Bitmap 3AI1428ZoneModule 5 ZoneModule Alarm Bitmap 4AI1429ZoneModule 5 VAV Extract 2 Actuator Setpoint %AI1430ZoneModule 5 VAV Extract 2 Actual FlowAI1431ZoneModule 5 VAV Extract 2 Actual Damper pos. %AI1500ZoneModule 6 StatusAI1501ZoneModule 6 VAV Supply 1 Actuator Setpoint %AI1502ZoneModule 6 VAV Supply 1 Actual FlowAI1503ZoneModule 6 VAV Supply 2 Actuator Setpoint %AI1504ZoneModule 6 VAV Supply 2 Actual FlowAI1505ZoneModule 6 VAV Extract Actuator Setpoint %AI1506ZoneModule 6 VAV Extract Actual FlowAI1507ZoneModule 6 Heating Valve Setpoint %AI1508ZoneModule 6 Cooling Valve Setpoint %AI1509ZoneModule 6 Room Temperature Actual ValueAI1510ZoneModule 6 Supply Temperature Actual ValueAI1511ZoneModule 6 Remote Setpoint Offset Actual ValueAI1512ZoneModule 6 CO2/VOC Actual ValueAI1513ZoneModule 6 RH Actual ValueAI1514ZoneModule 6 Room Temperature Actual SetpointAI1515ZoneModule 6 Room Panel Air ModeAI1516ZoneModule 6 Heating Valve Actual FlowAI1517ZoneModule 6 Cooling Valve Actual FlowAI1518ZoneModule 6 VAV Supply 1 Actual Damper pos. %AI1519ZoneModule 6 VAV Supply 2 Actual Damper pos. %AI1520ZoneModule 6 VAV Extract Actual Damper pos. %AI1521ZoneModule 6 EL Heater 1 Temp. Sensor ValueAI1522ZoneModule 6 EL Heater 2 Temp. Sensor ValueAI1523ZoneModule 6 Ext Aout1 OutputAI1524ZoneModule 6 Ext Aout2 OutputAI1525ZoneModule 6 ZoneModule Alarm Bitmap 1AI1526ZoneModule 6 ZoneModule Alarm Bitmap 2AI1527ZoneModule 6 ZoneModule Alarm Bitmap 3AI1528ZoneModule 6 ZoneModule Alarm Bitmap 4AI1529ZoneModule 6 VAV Extract 2 Actuator Setpoint %AI1530ZoneModule 6 VAV Extract 2 Actual FlowAI1531ZoneModule 6 VAV Extract 2 Actual Damper pos. %AI1600ZoneModule 7 StatusAI1601ZoneModule 7 VAV Supply 1 Actuator Setpoint %AI1602ZoneModule 7 VAV Supply 1 Actual FlowAI1603ZoneModule 7 VAV Supply 2 Actuator Setpoint %AI1604ZoneModule 7 VAV Supply 2 Actual FlowAI1605ZoneModule 7 VAV Extract Actuator Setpoint %AI1606ZoneModule 7 VAV Extract Actual FlowAI1607ZoneModule 7 Heating Valve Setpoint %AI1608ZoneModule 7 Cooling Valve Setpoint %AI1609ZoneModule 7 Room Temperature Actual ValueAI1610ZoneModule 7 Supply Temperature Actual ValueAI1611ZoneModule 7 Remote Setpoint Offset Actual ValueAI1612ZoneModule 7 CO2/VOC Actual ValueAI1613ZoneModule 7 RH Actual ValueAI1614ZoneModule 7 Room Temperature Actual SetpointAI1615ZoneModule 7 Room Panel Air ModeAI1616ZoneModule 7 Heating Valve Actual FlowAI1617ZoneModule 7 Cooling Valve Actual FlowAI1618ZoneModule 7 VAV Supply 1 Actual Damper pos. %AI1619ZoneModule 7 VAV Supply 2 Actual Damper pos. %AI1620ZoneModule 7 VAV Extract Actual Damper pos. %AI1621ZoneModule 7 EL Heater 1 Temp. Sensor ValueAI1622ZoneModule 7 EL Heater 2 Temp. Sensor ValueAI1623ZoneModule 7 Ext Aout1 OutputAI1624ZoneModule 7 Ext Aout2 OutputAI1625ZoneModule 7 ZoneModule Alarm Bitmap 1AI1626ZoneModule 7 ZoneModule Alarm Bitmap 2AI1627ZoneModule 7 ZoneModule Alarm Bitmap 3AI1628ZoneModule 7 ZoneModule Alarm Bitmap 4AI1629ZoneModule 7 VAV Extract 2 Actuator Setpoint %AI1630ZoneModule 7 VAV Extract 2 Actual FlowAI1631ZoneModule 7 VAV Extract 2 Actual Damper pos. %AI1700ZoneModule 8 StatusAI1701ZoneModule 8 VAV Supply 1 Actuator Setpoint %AI1702ZoneModule 8 VAV Supply 1 Actual FlowAI1703ZoneModule 8 VAV Supply 2 Actuator Setpoint %AI1704ZoneModule 8 VAV Supply 2 Actual FlowAI1705ZoneModule 8 VAV Extract Actuator Setpoint %AI1706ZoneModule 8 VAV Extract Actual FlowAI1707ZoneModule 8 Heating Valve Setpoint %AI1708ZoneModule 8 Cooling Valve Setpoint %AI1709ZoneModule 8 Room Temperature Actual ValueAI1710ZoneModule 8 Supply Temperature Actual ValueAI1711ZoneModule 8 Remote Setpoint Offset Actual ValueAI1712ZoneModule 8 CO2/VOC Actual ValueAI1713ZoneModule 8 RH Actual ValueAI1714ZoneModule 8 Room Temperature Actual SetpointAI1715ZoneModule 8 Room Panel Air ModeAI1716ZoneModule 8 Heating Valve Actual FlowAI1717ZoneModule 8 Cooling Valve Actual FlowAI1718ZoneModule 8 VAV Supply 1 Actual Damper pos. %AI1719ZoneModule 8 VAV Supply 2 Actual Damper pos. %AI1720ZoneModule 8 VAV Extract Actual Damper pos. %AI1721ZoneModule 8 EL Heater 1 Temp. Sensor ValueAI1722ZoneModule 8 EL Heater 2 Temp. Sensor ValueAI1723ZoneModule 8 Ext Aout1 OutputAI1724ZoneModule 8 Ext Aout2 OutputAI1725ZoneModule 8 ZoneModule Alarm Bitmap 1AI1726ZoneModule 8 ZoneModule Alarm Bitmap 2AI1727ZoneModule 8 ZoneModule Alarm Bitmap 3AI1728ZoneModule 8 ZoneModule Alarm Bitmap 4AI1729ZoneModule 8 VAV Extract 2 Actuator Setpoint %AI1730ZoneModule 8 VAV Extract 2 Actual FlowAI1731ZoneModule 8 VAV Extract 2 Actual Damper pos. %AI1800ZoneModule 9 StatusAI1801ZoneModule 9 VAV Supply 1 Actuator Setpoint %AI1802ZoneModule 9 VAV Supply 1 Actual FlowAI1803ZoneModule 9 VAV Supply 2 Actuator Setpoint %AI1804ZoneModule 9 VAV Supply 2 Actual FlowAI1805ZoneModule 9 VAV Extract Actuator Setpoint %AI1806ZoneModule 9 VAV Extract Actual FlowAI1807ZoneModule 9 Heating Valve Setpoint %AI1808ZoneModule 9 Cooling Valve Setpoint %AI1809ZoneModule 9 Room Temperature Actual ValueAI1810ZoneModule 9 Supply Temperature Actual ValueAI1811ZoneModule 9 Remote Setpoint Offset Actual ValueAI1812ZoneModule 9 CO2/VOC Actual ValueAI1813ZoneModule 9 RH Actual ValueAI1814ZoneModule 9 Room Temperature Actual SetpointAI1815ZoneModule 9 Room Panel Air ModeAI1816ZoneModule 9 Heating Valve Actual FlowAI1817ZoneModule 9 Cooling Valve Actual FlowAI1818ZoneModule 9 VAV Supply 1 Actual Damper pos. %AI1819ZoneModule 9 VAV Supply 2 Actual Damper pos. %AI1820ZoneModule 9 VAV Extract Actual Damper pos. %AI1821ZoneModule 9 EL Heater 1 Temp. Sensor ValueAI1822ZoneModule 9 EL Heater 2 Temp. Sensor ValueAI1823ZoneModule 9 Ext Aout1 OutputAI1824ZoneModule 9 Ext Aout2 OutputAI1825ZoneModule 9 ZoneModule Alarm Bitmap 1AI1826ZoneModule 9 ZoneModule Alarm Bitmap 2AI1827ZoneModule 9 ZoneModule Alarm Bitmap 3AI1828ZoneModule 9 ZoneModule Alarm Bitmap 4AI1829ZoneModule 9 VAV Extract 2 Actuator Setpoint %AI1830ZoneModule 9 VAV Extract 2 Actual FlowAI1831ZoneModule 9 VAV Extract 2 Actual Damper pos. %AI1900ZoneModule 10 StatusAI1901ZoneModule 10 VAV Supply 1 Actuator Setpoint %AI1902ZoneModule 10 VAV Supply 1 Actual FlowAI1903ZoneModule 10 VAV Supply 2 Actuator Setpoint %AI1904ZoneModule 10 VAV Supply 2 Actual FlowAI1905ZoneModule 10 VAV Extract Actuator Setpoint %AI1906ZoneModule 10 VAV Extract Actual FlowAI1907ZoneModule 10 Heating Valve Setpoint %AI1908ZoneModule 10 Cooling Valve Setpoint %AI1909ZoneModule 10 Room Temperature Actual ValueAI1910ZoneModule 10 Supply Temperature Actual ValueAI1911ZoneModule 10 Remote Setpoint Offset Actual ValueAI1912ZoneModule 10 CO2/VOC Actual ValueAI1913ZoneModule 10 RH Actual ValueAI1914ZoneModule 10 Room Temperature Actual SetpointAI1915ZoneModule 10 Room Panel Air ModeAI1916ZoneModule 10 Heating Valve Actual FlowAI1917ZoneModule 10 Cooling Valve Actual FlowAI1918ZoneModule 10 VAV Supply 1 Actual Damper pos. %AI1919ZoneModule 10 VAV Supply 2 Actual Damper pos. %AI1920ZoneModule 10 VAV Extract Actual Damper pos. %AI1921ZoneModule 10 EL Heater 1 Temp. Sensor ValueAI1922ZoneModule 10 EL Heater 2 Temp. Sensor ValueAI1923ZoneModule 10 Ext Aout1 OutputAI1924ZoneModule 10 Ext Aout2 OutputAI1925ZoneModule 10 ZoneModule Alarm Bitmap 1AI1926ZoneModule 10 ZoneModule Alarm Bitmap 2AI1927ZoneModule 10 ZoneModule Alarm Bitmap 3AI1928ZoneModule 10 ZoneModule Alarm Bitmap 4AI1929ZoneModule 10 VAV Extract 2 Actuator Setpoint %AI1930ZoneModule 10 VAV Extract 2 Actual FlowAI1931ZoneModule 10 VAV Extract 2 Actual Damper pos. %AI2000ZoneModule 11 StatusAI2001ZoneModule 11 VAV Supply 1 Actuator Setpoint %AI2002ZoneModule 11 VAV Supply 1 Actual FlowAI2003ZoneModule 11 VAV Supply 2 Actuator Setpoint %AI2004ZoneModule 11 VAV Supply 2 Actual FlowAI2005ZoneModule 11 VAV Extract Actuator Setpoint %AI2006ZoneModule 11 VAV Extract Actual FlowAI2007ZoneModule 11 Heating Valve Setpoint %AI2008ZoneModule 11 Cooling Valve Setpoint %AI2009ZoneModule 11 Room Temperature Actual ValueAI2010ZoneModule 11 Supply Temperature Actual ValueAI2011ZoneModule 11 Remote Setpoint Offset Actual ValueAI2012ZoneModule 11 CO2/VOC Actual ValueAI2013ZoneModule 11 RH Actual ValueAI2014ZoneModule 11 Room Temperature Actual SetpointAI2015ZoneModule 11 Room Panel Air ModeAI2016ZoneModule 11 Heating Valve Actual FlowAI2017ZoneModule 11 Cooling Valve Actual FlowAI2018ZoneModule 11 VAV Supply 1 Actual Damper pos. %AI2019ZoneModule 11 VAV Supply 2 Actual Damper pos. %AI2020ZoneModule 11 VAV Extract Actual Damper pos. %AI2021ZoneModule 11 EL Heater 1 Temp. Sensor ValueAI2022ZoneModule 11 EL Heater 2 Temp. Sensor ValueAI2023ZoneModule 11 Ext Aout1 OutputAI2024ZoneModule 11 Ext Aout2 OutputAI2025ZoneModule 11 ZoneModule Alarm Bitmap 1AI2026ZoneModule 11 ZoneModule Alarm Bitmap 2AI2027ZoneModule 11 ZoneModule Alarm Bitmap 3AI2028ZoneModule 11 ZoneModule Alarm Bitmap 4AI2029ZoneModule 11 VAV Extract 2 Actuator Setpoint %AI2030ZoneModule 11 VAV Extract 2 Actual FlowAI2031ZoneModule 11 VAV Extract 2 Actual Damper pos. %AI2100ZoneModule 12 StatusAI2101ZoneModule 12 VAV Supply 1 Actuator Setpoint %AI2102ZoneModule 12 VAV Supply 1 Actual FlowAI2103ZoneModule 12 VAV Supply 2 Actuator Setpoint %AI2104ZoneModule 12 VAV Supply 2 Actual FlowAI2105ZoneModule 12 VAV Extract Actuator Setpoint %AI2106ZoneModule 12 VAV Extract Actual FlowAI2107ZoneModule 12 Heating Valve Setpoint %AI2108ZoneModule 12 Cooling Valve Setpoint %AI2109ZoneModule 12 Room Temperature Actual ValueAI2110ZoneModule 12 Supply Temperature Actual ValueAI2111ZoneModule 12 Remote Setpoint Offset Actual ValueAI2112ZoneModule 12 CO2/VOC Actual ValueAI2113ZoneModule 12 RH Actual ValueAI2114ZoneModule 12 Room Temperature Actual SetpointAI2115ZoneModule 12 Room Panel Air ModeAI2116ZoneModule 12 Heating Valve Actual FlowAI2117ZoneModule 12 Cooling Valve Actual FlowAI2118ZoneModule 12 VAV Supply 1 Actual Damper pos. %AI2119ZoneModule 12 VAV Supply 2 Actual Damper pos. %AI2120ZoneModule 12 VAV Extract Actual Damper pos. %AI2121ZoneModule 12 EL Heater 1 Temp. Sensor ValueAI2122ZoneModule 12 EL Heater 2 Temp. Sensor ValueAI2123ZoneModule 12 Ext Aout1 OutputAI2124ZoneModule 12 Ext Aout2 OutputAI2125ZoneModule 12 ZoneModule Alarm Bitmap 1AI2126ZoneModule 12 ZoneModule Alarm Bitmap 2AI2127ZoneModule 12 ZoneModule Alarm Bitmap 3AI2128ZoneModule 12 ZoneModule Alarm Bitmap 4AI2129ZoneModule 12 VAV Extract 2 Actuator Setpoint %AI2130ZoneModule 12 VAV Extract 2 Actual FlowAI2131ZoneModule 12 VAV Extract 2 Actual Damper pos. %AI2200ZoneModule 13 StatusAI2201ZoneModule 13 VAV Supply 1 Actuator Setpoint %AI2202ZoneModule 13 VAV Supply 1 Actual FlowAI2203ZoneModule 13 VAV Supply 2 Actuator Setpoint %AI2204ZoneModule 13 VAV Supply 2 Actual FlowAI2205ZoneModule 13 VAV Extract Actuator Setpoint %AI2206ZoneModule 13 VAV Extract Actual FlowAI2207ZoneModule 13 Heating Valve Setpoint %AI2208ZoneModule 13 Cooling Valve Setpoint %AI2209ZoneModule 13 Room Temperature Actual ValueAI2210ZoneModule 13 Supply Temperature Actual ValueAI2211ZoneModule 13 Remote Setpoint Offset Actual ValueAI2212ZoneModule 13 CO2/VOC Actual ValueAI2213ZoneModule 13 RH Actual ValueAI2214ZoneModule 13 Room Temperature Actual SetpointAI2215ZoneModule 13 Room Panel Air ModeAI2216ZoneModule 13 Heating Valve Actual FlowAI2217ZoneModule 13 Cooling Valve Actual FlowAI2218ZoneModule 13 VAV Supply 1 Actual Damper pos. %AI2219ZoneModule 13 VAV Supply 2 Actual Damper pos. %AI2220ZoneModule 13 VAV Extract Actual Damper pos. %AI2221ZoneModule 13 EL Heater 1 Temp. Sensor ValueAI2222ZoneModule 13 EL Heater 2 Temp. Sensor ValueAI2223ZoneModule 13 Ext Aout1 OutputAI2224ZoneModule 13 Ext Aout2 OutputAI2225ZoneModule 13 ZoneModule Alarm Bitmap 1AI2226ZoneModule 13 ZoneModule Alarm Bitmap 2AI2227ZoneModule 13 ZoneModule Alarm Bitmap 3AI2228ZoneModule 13 ZoneModule Alarm Bitmap 4AI2229ZoneModule 13 VAV Extract 2 Actuator Setpoint %AI2230ZoneModule 13 VAV Extract 2 Actual FlowAI2231ZoneModule 13 VAV Extract 2 Actual Damper pos. %AI2300ZoneModule 14 StatusAI2301ZoneModule 14 VAV Supply 1 Actuator Setpoint %AI2302ZoneModule 14 VAV Supply 1 Actual FlowAI2303ZoneModule 14 VAV Supply 2 Actuator Setpoint %AI2304ZoneModule 14 VAV Supply 2 Actual FlowAI2305ZoneModule 14 VAV Extract Actuator Setpoint %AI2306ZoneModule 14 VAV Extract Actual FlowAI2307ZoneModule 14 Heating Valve Setpoint %AI2308ZoneModule 14 Cooling Valve Setpoint %AI2309ZoneModule 14 Room Temperature Actual ValueAI2310ZoneModule 14 Supply Temperature Actual ValueAI2311ZoneModule 14 Remote Setpoint Offset Actual ValueAI2312ZoneModule 14 CO2/VOC Actual ValueAI2313ZoneModule 14 RH Actual ValueAI2314ZoneModule 14 Room Temperature Actual SetpointAI2315ZoneModule 14 Room Panel Air ModeAI2316ZoneModule 14 Heating Valve Actual FlowAI2317ZoneModule 14 Cooling Valve Actual FlowAI2318ZoneModule 14 VAV Supply 1 Actual Damper pos. %AI2319ZoneModule 14 VAV Supply 2 Actual Damper pos. %AI2320ZoneModule 14 VAV Extract Actual Damper pos. %AI2321ZoneModule 14 EL Heater 1 Temp. Sensor ValueAI2322ZoneModule 14 EL Heater 2 Temp. Sensor ValueAI2323ZoneModule 14 Ext Aout1 OutputAI2324ZoneModule 14 Ext Aout2 OutputAI2325ZoneModule 14 ZoneModule Alarm Bitmap 1AI2326ZoneModule 14 ZoneModule Alarm Bitmap 2AI2327ZoneModule 14 ZoneModule Alarm Bitmap 3AI2328ZoneModule 14 ZoneModule Alarm Bitmap 4AI2329ZoneModule 14 VAV Extract 2 Actuator Setpoint %AI2330ZoneModule 14 VAV Extract 2 Actual FlowAI2331ZoneModule 14 VAV Extract 2 Actual Damper pos. %AI2400ZoneModule 15 StatusAI2401ZoneModule 15 VAV Supply 1 Actuator Setpoint %AI2402ZoneModule 15 VAV Supply 1 Actual FlowAI2403ZoneModule 15 VAV Supply 2 Actuator Setpoint %AI2404ZoneModule 15 VAV Supply 2 Actual FlowAI2405ZoneModule 15 VAV Extract Actuator Setpoint %AI2406ZoneModule 15 VAV Extract Actual FlowAI2407ZoneModule 15 Heating Valve Setpoint %AI2408ZoneModule 15 Cooling Valve Setpoint %AI2409ZoneModule 15 Room Temperature Actual ValueAI2410ZoneModule 15 Supply Temperature Actual ValueAI2411ZoneModule 15 Remote Setpoint Offset Actual ValueAI2412ZoneModule 15 CO2/VOC Actual ValueAI2413ZoneModule 15 RH Actual ValueAI2414ZoneModule 15 Room Temperature Actual SetpointAI2415ZoneModule 15 Room Panel Air ModeAI2416ZoneModule 15 Heating Valve Actual FlowAI2417ZoneModule 15 Cooling Valve Actual FlowAI2418ZoneModule 15 VAV Supply 1 Actual Damper pos. %AI2419ZoneModule 15 VAV Supply 2 Actual Damper pos. %AI2420ZoneModule 15 VAV Extract Actual Damper pos. %AI2421ZoneModule 15 EL Heater 1 Temp. Sensor ValueAI2422ZoneModule 15 EL Heater 2 Temp. Sensor ValueAI2423ZoneModule 15 Ext Aout1 OutputAI2424ZoneModule 15 Ext Aout2 OutputAI2425ZoneModule 15 ZoneModule Alarm Bitmap 1AI2426ZoneModule 15 ZoneModule Alarm Bitmap 2AI2427ZoneModule 15 ZoneModule Alarm Bitmap 3AI2428ZoneModule 15 ZoneModule Alarm Bitmap 4AI2429ZoneModule 15 VAV Extract 2 Actuator Setpoint %AI2430ZoneModule 15 VAV Extract 2 Actual FlowAI2431ZoneModule 15 VAV Extract 2 Actual Damper pos. %AI2500ZoneModule 16 StatusAI2501ZoneModule 16 VAV Supply 1 Actuator Setpoint %AI2502ZoneModule 16 VAV Supply 1 Actual FlowAI2503ZoneModule 16 VAV Supply 2 Actuator Setpoint %AI2504ZoneModule 16 VAV Supply 2 Actual FlowAI2505ZoneModule 16 VAV Extract Actuator Setpoint %AI2506ZoneModule 16 VAV Extract Actual FlowAI2507ZoneModule 16 Heating Valve Setpoint %AI2508ZoneModule 16 Cooling Valve Setpoint %AI2509ZoneModule 16 Room Temperature Actual ValueAI2510ZoneModule 16 Supply Temperature Actual ValueAI2511ZoneModule 16 Remote Setpoint Offset Actual ValueAI2512ZoneModule 16 CO2/VOC Actual ValueAI2513ZoneModule 16 RH Actual ValueAI2514ZoneModule 16 Room Temperature Actual SetpointAI2515ZoneModule 16 Room Panel Air ModeAI2516ZoneModule 16 Heating Valve Actual FlowAI2517ZoneModule 16 Cooling Valve Actual FlowAI2518ZoneModule 16 VAV Supply 1 Actual Damper pos. %AI2519ZoneModule 16 VAV Supply 2 Actual Damper pos. %AI2520ZoneModule 16 VAV Extract Actual Damper pos. %AI2521ZoneModule 16 EL Heater 1 Temp. Sensor ValueAI2522ZoneModule 16 EL Heater 2 Temp. Sensor ValueAI2523ZoneModule 16 Ext Aout1 OutputAI2524ZoneModule 16 Ext Aout2 OutputAI2525ZoneModule 16 ZoneModule Alarm Bitmap 1AI2526ZoneModule 16 ZoneModule Alarm Bitmap 2AI2527ZoneModule 16 ZoneModule Alarm Bitmap 3AI2528ZoneModule 16 ZoneModule Alarm Bitmap 4AI2529ZoneModule 16 VAV Extract 2 Actuator Setpoint %AI2530ZoneModule 16 VAV Extract 2 Actual FlowAI2531ZoneModule 16 VAV Extract 2 Actual Damper pos. %AI2600ZoneModule 17 StatusAI2601ZoneModule 17 VAV Supply 1 Actuator Setpoint %AI2602ZoneModule 17 VAV Supply 1 Actual FlowAI2603ZoneModule 17 VAV Supply 2 Actuator Setpoint %AI2604ZoneModule 17 VAV Supply 2 Actual FlowAI2605ZoneModule 17 VAV Extract Actuator Setpoint %AI2606ZoneModule 17 VAV Extract Actual FlowAI2607ZoneModule 17 Heating Valve Setpoint %AI2608ZoneModule 17 Cooling Valve Setpoint %AI2609ZoneModule 17 Room Temperature Actual ValueAI2610ZoneModule 17 Supply Temperature Actual ValueAI2611ZoneModule 17 Remote Setpoint Offset Actual ValueAI2612ZoneModule 17 CO2/VOC Actual ValueAI2613ZoneModule 17 RH Actual ValueAI2614ZoneModule 17 Room Temperature Actual SetpointAI2615ZoneModule 17 Room Panel Air ModeAI2616ZoneModule 17 Heating Valve Actual FlowAI2617ZoneModule 17 Cooling Valve Actual FlowAI2618ZoneModule 17 VAV Supply 1 Actual Damper pos. %AI2619ZoneModule 17 VAV Supply 2 Actual Damper pos. %AI2620ZoneModule 17 VAV Extract Actual Damper pos. %AI2621ZoneModule 17 EL Heater 1 Temp. Sensor ValueAI2622ZoneModule 17 EL Heater 2 Temp. Sensor ValueAI2623ZoneModule 17 Ext Aout1 OutputAI2624ZoneModule 17 Ext Aout2 OutputAI2625ZoneModule 17 ZoneModule Alarm Bitmap 1AI2626ZoneModule 17 ZoneModule Alarm Bitmap 2AI2627ZoneModule 17 ZoneModule Alarm Bitmap 3AI2628ZoneModule 17 ZoneModule Alarm Bitmap 4AI2629ZoneModule 17 VAV Extract 2 Actuator Setpoint %AI2630ZoneModule 17 VAV Extract 2 Actual FlowAI2631ZoneModule 17 VAV Extract 2 Actual Damper pos. %AI2700ZoneModule 18 StatusAI2701ZoneModule 18 VAV Supply 1 Actuator Setpoint %AI2702ZoneModule 18 VAV Supply 1 Actual FlowAI2703ZoneModule 18 VAV Supply 2 Actuator Setpoint %AI2704ZoneModule 18 VAV Supply 2 Actual FlowAI2705ZoneModule 18 VAV Extract Actuator Setpoint %AI2706ZoneModule 18 VAV Extract Actual FlowAI2707ZoneModule 18 Heating Valve Setpoint %AI2708ZoneModule 18 Cooling Valve Setpoint %AI2709ZoneModule 18 Room Temperature Actual ValueAI2710ZoneModule 18 Supply Temperature Actual ValueAI2711ZoneModule 18 Remote Setpoint Offset Actual ValueAI2712ZoneModule 18 CO2/VOC Actual ValueAI2713ZoneModule 18 RH Actual ValueAI2714ZoneModule 18 Room Temperature Actual SetpointAI2715ZoneModule 18 Room Panel Air ModeAI2716ZoneModule 18 Heating Valve Actual FlowAI2717ZoneModule 18 Cooling Valve Actual FlowAI2718ZoneModule 18 VAV Supply 1 Actual Damper pos. %AI2719ZoneModule 18 VAV Supply 2 Actual Damper pos. %AI2720ZoneModule 18 VAV Extract Actual Damper pos. %AI2721ZoneModule 18 EL Heater 1 Temp. Sensor ValueAI2722ZoneModule 18 EL Heater 2 Temp. Sensor ValueAI2723ZoneModule 18 Ext Aout1 OutputAI2724ZoneModule 18 Ext Aout2 OutputAI2725ZoneModule 18 ZoneModule Alarm Bitmap 1AI2726ZoneModule 18 ZoneModule Alarm Bitmap 2AI2727ZoneModule 18 ZoneModule Alarm Bitmap 3AI2728ZoneModule 18 ZoneModule Alarm Bitmap 4AI2729ZoneModule 18 VAV Extract 2 Actuator Setpoint %AI2730ZoneModule 18 VAV Extract 2 Actual FlowAI2731ZoneModule 18 VAV Extract 2 Actual Damper pos. %AI2800ZoneModule 19 StatusAI2801ZoneModule 19 VAV Supply 1 Actuator Setpoint %AI2802ZoneModule 19 VAV Supply 1 Actual FlowAI2803ZoneModule 19 VAV Supply 2 Actuator Setpoint %AI2804ZoneModule 19 VAV Supply 2 Actual FlowAI2805ZoneModule 19 VAV Extract Actuator Setpoint %AI2806ZoneModule 19 VAV Extract Actual FlowAI2807ZoneModule 19 Heating Valve Setpoint %AI2808ZoneModule 19 Cooling Valve Setpoint %AI2809ZoneModule 19 Room Temperature Actual ValueAI2810ZoneModule 19 Supply Temperature Actual ValueAI2811ZoneModule 19 Remote Setpoint Offset Actual ValueAI2812ZoneModule 19 CO2/VOC Actual ValueAI2813ZoneModule 19 RH Actual ValueAI2814ZoneModule 19 Room Temperature Actual SetpointAI2815ZoneModule 19 Room Panel Air ModeAI2816ZoneModule 19 Heating Valve Actual FlowAI2817ZoneModule 19 Cooling Valve Actual FlowAI2818ZoneModule 19 VAV Supply 1 Actual Damper pos. %AI2819ZoneModule 19 VAV Supply 2 Actual Damper pos. %AI2820ZoneModule 19 VAV Extract Actual Damper pos. %AI2821ZoneModule 19 EL Heater 1 Temp. Sensor ValueAI2822ZoneModule 19 EL Heater 2 Temp. Sensor ValueAI2823ZoneModule 19 Ext Aout1 OutputAI2824ZoneModule 19 Ext Aout2 OutputAI2825ZoneModule 19 ZoneModule Alarm Bitmap 1AI2826ZoneModule 19 ZoneModule Alarm Bitmap 2AI2827ZoneModule 19 ZoneModule Alarm Bitmap 3AI2828ZoneModule 19 ZoneModule Alarm Bitmap 4AI2829ZoneModule 19 VAV Extract 2 Actuator Setpoint %AI2830ZoneModule 19 VAV Extract 2 Actual FlowAI2831ZoneModule 19 VAV Extract 2 Actual Damper pos. %AI2900ZoneModule 20 StatusAI2901ZoneModule 20 VAV Supply 1 Actuator Setpoint %AI2902ZoneModule 20 VAV Supply 1 Actual FlowAI2903ZoneModule 20 VAV Supply 2 Actuator Setpoint %AI2904ZoneModule 20 VAV Supply 2 Actual FlowAI2905ZoneModule 20 VAV Extract Actuator Setpoint %AI2906ZoneModule 20 VAV Extract Actual FlowAI2907ZoneModule 20 Heating Valve Setpoint %AI2908ZoneModule 20 Cooling Valve Setpoint %AI2909ZoneModule 20 Room Temperature Actual ValueAI2910ZoneModule 20 Supply Temperature Actual ValueAI2911ZoneModule 20 Remote Setpoint Offset Actual ValueAI2912ZoneModule 20 CO2/VOC Actual ValueAI2913ZoneModule 20 RH Actual ValueAI2914ZoneModule 20 Room Temperature Actual SetpointAI2915ZoneModule 20 Room Panel Air ModeAI2916ZoneModule 20 Heating Valve Actual FlowAI2917ZoneModule 20 Cooling Valve Actual FlowAI2918ZoneModule 20 VAV Supply 1 Actual Damper pos. %AI2919ZoneModule 20 VAV Supply 2 Actual Damper pos. %AI2920ZoneModule 20 VAV Extract Actual Damper pos. %AI2921ZoneModule 20 EL Heater 1 Temp. Sensor ValueAI2922ZoneModule 20 EL Heater 2 Temp. Sensor ValueAI2923ZoneModule 20 Ext Aout1 OutputAI2924ZoneModule 20 Ext Aout2 OutputAI2925ZoneModule 20 ZoneModule Alarm Bitmap 1AI2926ZoneModule 20 ZoneModule Alarm Bitmap 2AI2927ZoneModule 20 ZoneModule Alarm Bitmap 3AI2928ZoneModule 20 ZoneModule Alarm Bitmap 4AI2929ZoneModule 20 VAV Extract 2 Actuator Setpoint %AI2930ZoneModule 20 VAV Extract 2 Actual FlowAI2931ZoneModule 20 VAV Extract 2 Actual Damper pos. %AI3000ZoneModule 21 StatusAI3001ZoneModule 21 VAV Supply 1 Actuator Setpoint %AI3002ZoneModule 21 VAV Supply 1 Actual FlowAI3003ZoneModule 21 VAV Supply 2 Actuator Setpoint %AI3004ZoneModule 21 VAV Supply 2 Actual FlowAI3005ZoneModule 21 VAV Extract Actuator Setpoint %AI3006ZoneModule 21 VAV Extract Actual FlowAI3007ZoneModule 21 Heating Valve Setpoint %AI3008ZoneModule 21 Cooling Valve Setpoint %AI3009ZoneModule 21 Room Temperature Actual ValueAI3010ZoneModule 21 Supply Temperature Actual ValueAI3011ZoneModule 21 Remote Setpoint Offset Actual ValueAI3012ZoneModule 21 CO2/VOC Actual ValueAI3013ZoneModule 21 RH Actual ValueAI3014ZoneModule 21 Room Temperature Actual SetpointAI3015ZoneModule 21 Room Panel Air ModeAI3016ZoneModule 21 Heating Valve Actual FlowAI3017ZoneModule 21 Cooling Valve Actual FlowAI3018ZoneModule 21 VAV Supply 1 Actual Damper pos. %AI3019ZoneModule 21 VAV Supply 2 Actual Damper pos. %AI3020ZoneModule 21 VAV Extract Actual Damper pos. %AI3021ZoneModule 21 EL Heater 1 Temp. Sensor ValueAI3022ZoneModule 21 EL Heater 2 Temp. Sensor ValueAI3023ZoneModule 21 Ext Aout1 OutputAI3024ZoneModule 21 Ext Aout2 OutputAI3025ZoneModule 21 ZoneModule Alarm Bitmap 1AI3026ZoneModule 21 ZoneModule Alarm Bitmap 2AI3027ZoneModule 21 ZoneModule Alarm Bitmap 3AI3028ZoneModule 21 ZoneModule Alarm Bitmap 4AI3029ZoneModule 21 VAV Extract 2 Actuator Setpoint %AI3030ZoneModule 21 VAV Extract 2 Actual FlowAI3031ZoneModule 21 VAV Extract 2 Actual Damper pos. %AI3100ZoneModule 22 StatusAI3101ZoneModule 22 VAV Supply 1 Actuator Setpoint %AI3102ZoneModule 22 VAV Supply 1 Actual FlowAI3103ZoneModule 22 VAV Supply 2 Actuator Setpoint %AI3104ZoneModule 22 VAV Supply 2 Actual FlowAI3105ZoneModule 22 VAV Extract Actuator Setpoint %AI3106ZoneModule 22 VAV Extract Actual FlowAI3107ZoneModule 22 Heating Valve Setpoint %AI3108ZoneModule 22 Cooling Valve Setpoint %AI3109ZoneModule 22 Room Temperature Actual ValueAI3110ZoneModule 22 Supply Temperature Actual ValueAI3111ZoneModule 22 Remote Setpoint Offset Actual ValueAI3112ZoneModule 22 CO2/VOC Actual ValueAI3113ZoneModule 22 RH Actual ValueAI3114ZoneModule 22 Room Temperature Actual SetpointAI3115ZoneModule 22 Room Panel Air ModeAI3116ZoneModule 22 Heating Valve Actual FlowAI3117ZoneModule 22 Cooling Valve Actual FlowAI3118ZoneModule 22 VAV Supply 1 Actual Damper pos. %AI3119ZoneModule 22 VAV Supply 2 Actual Damper pos. %AI3120ZoneModule 22 VAV Extract Actual Damper pos. %AI3121ZoneModule 22 EL Heater 1 Temp. Sensor ValueAI3122ZoneModule 22 EL Heater 2 Temp. Sensor ValueAI3123ZoneModule 22 Ext Aout1 OutputAI3124ZoneModule 22 Ext Aout2 OutputAI3125ZoneModule 22 ZoneModule Alarm Bitmap 1AI3126ZoneModule 22 ZoneModule Alarm Bitmap 2AI3127ZoneModule 22 ZoneModule Alarm Bitmap 3AI3128ZoneModule 22 ZoneModule Alarm Bitmap 4AI3129ZoneModule 22 VAV Extract 2 Actuator Setpoint %AI3130ZoneModule 22 VAV Extract 2 Actual FlowAI3131ZoneModule 22 VAV Extract 2 Actual Damper pos. %AI3200ZoneModule 23 StatusAI3201ZoneModule 23 VAV Supply 1 Actuator Setpoint %AI3202ZoneModule 23 VAV Supply 1 Actual FlowAI3203ZoneModule 23 VAV Supply 2 Actuator Setpoint %AI3204ZoneModule 23 VAV Supply 2 Actual FlowAI3205ZoneModule 23 VAV Extract Actuator Setpoint %AI3206ZoneModule 23 VAV Extract Actual FlowAI3207ZoneModule 23 Heating Valve Setpoint %AI3208ZoneModule 23 Cooling Valve Setpoint %AI3209ZoneModule 23 Room Temperature Actual ValueAI3210ZoneModule 23 Supply Temperature Actual ValueAI3211ZoneModule 23 Remote Setpoint Offset Actual ValueAI3212ZoneModule 23 CO2/VOC Actual ValueAI3213ZoneModule 23 RH Actual ValueAI3214ZoneModule 23 Room Temperature Actual SetpointAI3215ZoneModule 23 Room Panel Air ModeAI3216ZoneModule 23 Heating Valve Actual FlowAI3217ZoneModule 23 Cooling Valve Actual FlowAI3218ZoneModule 23 VAV Supply 1 Actual Damper pos. %AI3219ZoneModule 23 VAV Supply 2 Actual Damper pos. %AI3220ZoneModule 23 VAV Extract Actual Damper pos. %AI3221ZoneModule 23 EL Heater 1 Temp. Sensor ValueAI3222ZoneModule 23 EL Heater 2 Temp. Sensor ValueAI3223ZoneModule 23 Ext Aout1 OutputAI3224ZoneModule 23 Ext Aout2 OutputAI3225ZoneModule 23 ZoneModule Alarm Bitmap 1AI3226ZoneModule 23 ZoneModule Alarm Bitmap 2AI3227ZoneModule 23 ZoneModule Alarm Bitmap 3AI3228ZoneModule 23 ZoneModule Alarm Bitmap 4AI3229ZoneModule 23 VAV Extract 2 Actuator Setpoint %AI3230ZoneModule 23 VAV Extract 2 Actual FlowAI3231ZoneModule 23 VAV Extract 2 Actual Damper pos. %AI3300ZoneModule 24 StatusAI3301ZoneModule 24 VAV Supply 1 Actuator Setpoint %AI3302ZoneModule 24 VAV Supply 1 Actual FlowAI3303ZoneModule 24 VAV Supply 2 Actuator Setpoint %AI3304ZoneModule 24 VAV Supply 2 Actual FlowAI3305ZoneModule 24 VAV Extract Actuator Setpoint %AI3306ZoneModule 24 VAV Extract Actual FlowAI3307ZoneModule 24 Heating Valve Setpoint %AI3308ZoneModule 24 Cooling Valve Setpoint %AI3309ZoneModule 24 Room Temperature Actual ValueAI3310ZoneModule 24 Supply Temperature Actual ValueAI3311ZoneModule 24 Remote Setpoint Offset Actual ValueAI3312ZoneModule 24 CO2/VOC Actual ValueAI3313ZoneModule 24 RH Actual ValueAI3314ZoneModule 24 Room Temperature Actual SetpointAI3315ZoneModule 24 Room Panel Air ModeAI3316ZoneModule 24 Heating Valve Actual FlowAI3317ZoneModule 24 Cooling Valve Actual FlowAI3318ZoneModule 24 VAV Supply 1 Actual Damper pos. %AI3319ZoneModule 24 VAV Supply 2 Actual Damper pos. %AI3320ZoneModule 24 VAV Extract Actual Damper pos. %AI3321ZoneModule 24 EL Heater 1 Temp. Sensor ValueAI3322ZoneModule 24 EL Heater 2 Temp. Sensor ValueAI3323ZoneModule 24 Ext Aout1 OutputAI3324ZoneModule 24 Ext Aout2 OutputAI3325ZoneModule 24 ZoneModule Alarm Bitmap 1AI3326ZoneModule 24 ZoneModule Alarm Bitmap 2AI3327ZoneModule 24 ZoneModule Alarm Bitmap 3AI3328ZoneModule 24 ZoneModule Alarm Bitmap 4AI3329ZoneModule 24 VAV Extract 2 Actuator Setpoint %AI3330ZoneModule 24 VAV Extract 2 Actual FlowAI3331ZoneModule 24 VAV Extract 2 Actual Damper pos. %AI3400ZoneModule 25 StatusAI3401ZoneModule 25 VAV Supply 1 Actuator Setpoint %AI3402ZoneModule 25 VAV Supply 1 Actual FlowAI3403ZoneModule 25 VAV Supply 2 Actuator Setpoint %AI3404ZoneModule 25 VAV Supply 2 Actual FlowAI3405ZoneModule 25 VAV Extract Actuator Setpoint %AI3406ZoneModule 25 VAV Extract Actual FlowAI3407ZoneModule 25 Heating Valve Setpoint %AI3408ZoneModule 25 Cooling Valve Setpoint %AI3409ZoneModule 25 Room Temperature Actual ValueAI3410ZoneModule 25 Supply Temperature Actual ValueAI3411ZoneModule 25 Remote Setpoint Offset Actual ValueAI3412ZoneModule 25 CO2/VOC Actual ValueAI3413ZoneModule 25 RH Actual ValueAI3414ZoneModule 25 Room Temperature Actual SetpointAI3415ZoneModule 25 Room Panel Air ModeAI3416ZoneModule 25 Heating Valve Actual FlowAI3417ZoneModule 25 Cooling Valve Actual FlowAI3418ZoneModule 25 VAV Supply 1 Actual Damper pos. %AI3419ZoneModule 25 VAV Supply 2 Actual Damper pos. %AI3420ZoneModule 25 VAV Extract Actual Damper pos. %AI3421ZoneModule 25 EL Heater 1 Temp. Sensor ValueAI3422ZoneModule 25 EL Heater 2 Temp. Sensor ValueAI3423ZoneModule 25 Ext Aout1 OutputAI3424ZoneModule 25 Ext Aout2 OutputAI3425ZoneModule 25 ZoneModule Alarm Bitmap 1AI3426ZoneModule 25 ZoneModule Alarm Bitmap 2AI3427ZoneModule 25 ZoneModule Alarm Bitmap 3AI3428ZoneModule 25 ZoneModule Alarm Bitmap 4AI3429ZoneModule 25 VAV Extract 2 Actuator Setpoint %AI3430ZoneModule 25 VAV Extract 2 Actual FlowAI3431ZoneModule 25 VAV Extract 2 Actual Damper pos. %AI3500Number Of ZonemastersAI3501ZoneMaster Chain IDAI4000ZoneMaster 1 ZoneMaster Local Alarm StatusAI4100ZoneMaster 2 ZoneMaster Local Alarm StatusAI4200ZoneMaster 3 ZoneMaster Local Alarm StatusAI4300ZoneMaster 4 ZoneMaster Local Alarm StatusAI4400ZoneMaster 5 ZoneMaster Local Alarm StatusAV0System Time YearAV1System Time MonthAV2System Time DateAV3System Time HourAV4System Time MinuteAV5System Time SecondAV100AHU Min Supply Fan SpeedAV101AHU Max Supply Fan SpeedAV102AHU Min Extract Fan SpeedAV103AHU Max Extract Fan SpeedAV104Minimum Supply Air TemperatureAV105Highest Allowed Cooling Water TempAV106Lowest Allowed Heating Water TempAV107Winter Start TemperatureAV108Winter Max TemperatureAV109Winter Temp DiffAV110Summer Start TemperatureAV111Summer Max TemperatureAV112Summer Temp DiffAV113Max Supply PressureAV114Max Extract PressureAV1001ZoneModule 1 Room Temperature SetpointAV1002ZoneModule 1 Minimum Supply TemperatureAV1003ZoneModule 1 Maximum Supply TemperatureAV1004ZoneModule 1 Room CO2 SetpointAV1005ZoneModule 1 Room RH SetpointAV1006ZoneModule 1 VAV Supply PIR Min. Air FlowAV1007ZoneModule 1 VAV Supply 1 Min. Air FlowAV1008ZoneModule 1 VAV Supply 1 Max. Air FlowAV1009ZoneModule 1 VAV Supply 2 Min. Air FlowAV1010ZoneModule 1 VAV Supply 2 Max. Air FlowAV1011ZoneModule 1 VAV Extract Min. Air FlowAV1012ZoneModule 1 VAV Extract Max. Air FlowAV1013ZoneModule 1 VAV Supply 1 Nominal Air FlowAV1014ZoneModule 1 VAV Supply 2 Nominal Air FlowAV1015ZoneModule 1 VAV Extract Nominal Air FlowAV1016ZoneModule 1 Room Panel Low Air FlowAV1017ZoneModule 1 Room Panel High Air FlowAV1018ZoneModule 1 Room Panel Override TimeoutAV1019ZoneModule 1 Heat Valve Max. FlowAV1020ZoneModule 1 Cool Valve Max. FlowAV1022ZoneModule 1 VAV Extract 2 Nominal Air FlowAV1023ZoneModule 1 VAV Extract 2 Min. Air FlowAV1024ZoneModule 1 VAV Extract 2 Max. Air FlowAV1101ZoneModule 2 Room Temperature SetpointAV1102ZoneModule 2 Minimum Supply TemperatureAV1103ZoneModule 2 Maximum Supply TemperatureAV1104ZoneModule 2 Room CO2 SetpointAV1105ZoneModule 2 Room RH SetpointAV1106ZoneModule 2 VAV Supply PIR Min. Air FlowAV1107ZoneModule 2 VAV Supply 1 Min. Air FlowAV1108ZoneModule 2 VAV Supply 1 Max. Air FlowAV1109ZoneModule 2 VAV Supply 2 Min. Air FlowAV1110ZoneModule 2 VAV Supply 2 Max. Air FlowAV1111ZoneModule 2 VAV Extract Min. Air FlowAV1112ZoneModule 2 VAV Extract Max. Air FlowAV1113ZoneModule 2 VAV Supply 1 Nominal Air FlowAV1114ZoneModule 2 VAV Supply 2 Nominal Air FlowAV1115ZoneModule 2 VAV Extract Nominal Air FlowAV1116ZoneModule 2 Room Panel Low Air FlowAV1117ZoneModule 2 Room Panel High Air FlowAV1118ZoneModule 2 Room Panel Override TimeoutAV1119ZoneModule 2 Heat Valve Max. FlowAV1120ZoneModule 2 Cool Valve Max. FlowAV1122ZoneModule 2 VAV Extract 2 Nominal Air FlowAV1123ZoneModule 2 VAV Extract 2 Min. Air FlowAV1124ZoneModule 2 VAV Extract 2 Max. Air FlowAV1201ZoneModule 3 Room Temperature SetpointAV1202ZoneModule 3 Minimum Supply TemperatureAV1203ZoneModule 3 Maximum Supply TemperatureAV1204ZoneModule 3 Room CO2 SetpointAV1205ZoneModule 3 Room RH SetpointAV1206ZoneModule 3 VAV Supply PIR Min. Air FlowAV1207ZoneModule 3 VAV Supply 1 Min. Air FlowAV1208ZoneModule 3 VAV Supply 1 Max. Air FlowAV1209ZoneModule 3 VAV Supply 2 Min. Air FlowAV1210ZoneModule 3 VAV Supply 2 Max. Air FlowAV1211ZoneModule 3 VAV Extract Min. Air FlowAV1212ZoneModule 3 VAV Extract Max. Air FlowAV1213ZoneModule 3 VAV Supply 1 Nominal Air FlowAV1214ZoneModule 3 VAV Supply 2 Nominal Air FlowAV1215ZoneModule 3 VAV Extract Nominal Air FlowAV1216ZoneModule 3 Room Panel Low Air FlowAV1217ZoneModule 3 Room Panel High Air FlowAV1218ZoneModule 3 Room Panel Override TimeoutAV1219ZoneModule 3 Heat Valve Max. FlowAV1220ZoneModule 3 Cool Valve Max. FlowAV1222ZoneModule 3 VAV Extract 2 Nominal Air FlowAV1223ZoneModule 3 VAV Extract 2 Min. Air FlowAV1224ZoneModule 3 VAV Extract 2 Max. Air FlowAV1301ZoneModule 4 Room Temperature SetpointAV1302ZoneModule 4 Minimum Supply TemperatureAV1303ZoneModule 4 Maximum Supply TemperatureAV1304ZoneModule 4 Room CO2 SetpointAV1305ZoneModule 4 Room RH SetpointAV1306ZoneModule 4 VAV Supply PIR Min. Air FlowAV1307ZoneModule 4 VAV Supply 1 Min. Air FlowAV1308ZoneModule 4 VAV Supply 1 Max. Air FlowAV1309ZoneModule 4 VAV Supply 2 Min. Air FlowAV1310ZoneModule 4 VAV Supply 2 Max. Air FlowAV1311ZoneModule 4 VAV Extract Min. Air FlowAV1312ZoneModule 4 VAV Extract Max. Air FlowAV1313ZoneModule 4 VAV Supply 1 Nominal Air FlowAV1314ZoneModule 4 VAV Supply 2 Nominal Air FlowAV1315ZoneModule 4 VAV Extract Nominal Air FlowAV1316ZoneModule 4 Room Panel Low Air FlowAV1317ZoneModule 4 Room Panel High Air FlowAV1318ZoneModule 4 Room Panel Override TimeoutAV1319ZoneModule 4 Heat Valve Max. FlowAV1320ZoneModule 4 Cool Valve Max. FlowAV1322ZoneModule 4 VAV Extract 2 Nominal Air FlowAV1323ZoneModule 4 VAV Extract 2 Min. Air FlowAV1324ZoneModule 4 VAV Extract 2 Max. Air FlowAV1401ZoneModule 5 Room Temperature SetpointAV1402ZoneModule 5 Minimum Supply TemperatureAV1403ZoneModule 5 Maximum Supply TemperatureAV1404ZoneModule 5 Room CO2 SetpointAV1405ZoneModule 5 Room RH SetpointAV1406ZoneModule 5 VAV Supply PIR Min. Air FlowAV1407ZoneModule 5 VAV Supply 1 Min. Air FlowAV1408ZoneModule 5 VAV Supply 1 Max. Air FlowAV1409ZoneModule 5 VAV Supply 2 Min. Air FlowAV1410ZoneModule 5 VAV Supply 2 Max. Air FlowAV1411ZoneModule 5 VAV Extract Min. Air FlowAV1412ZoneModule 5 VAV Extract Max. Air FlowAV1413ZoneModule 5 VAV Supply 1 Nominal Air FlowAV1414ZoneModule 5 VAV Supply 2 Nominal Air FlowAV1415ZoneModule 5 VAV Extract Nominal Air FlowAV1416ZoneModule 5 Room Panel Low Air FlowAV1417ZoneModule 5 Room Panel High Air FlowAV1418ZoneModule 5 Room Panel Override TimeoutAV1419ZoneModule 5 Heat Valve Max. FlowAV1420ZoneModule 5 Cool Valve Max. FlowAV1422ZoneModule 5 VAV Extract 2 Nominal Air FlowAV1423ZoneModule 5 VAV Extract 2 Min. Air FlowAV1424ZoneModule 5 VAV Extract 2 Max. Air FlowAV1501ZoneModule 6 Room Temperature SetpointAV1502ZoneModule 6 Minimum Supply TemperatureAV1503ZoneModule 6 Maximum Supply TemperatureAV1504ZoneModule 6 Room CO2 SetpointAV1505ZoneModule 6 Room RH SetpointAV1506ZoneModule 6 VAV Supply PIR Min. Air FlowAV1507ZoneModule 6 VAV Supply 1 Min. Air FlowAV1508ZoneModule 6 VAV Supply 1 Max. Air FlowAV1509ZoneModule 6 VAV Supply 2 Min. Air FlowAV1510ZoneModule 6 VAV Supply 2 Max. Air FlowAV1511ZoneModule 6 VAV Extract Min. Air FlowAV1512ZoneModule 6 VAV Extract Max. Air FlowAV1513ZoneModule 6 VAV Supply 1 Nominal Air FlowAV1514ZoneModule 6 VAV Supply 2 Nominal Air FlowAV1515ZoneModule 6 VAV Extract Nominal Air FlowAV1516ZoneModule 6 Room Panel Low Air FlowAV1517ZoneModule 6 Room Panel High Air FlowAV1518ZoneModule 6 Room Panel Override TimeoutAV1519ZoneModule 6 Heat Valve Max. FlowAV1520ZoneModule 6 Cool Valve Max. FlowAV1522ZoneModule 6 VAV Extract 2 Nominal Air FlowAV1523ZoneModule 6 VAV Extract 2 Min. Air FlowAV1524ZoneModule 6 VAV Extract 2 Max. Air FlowAV1601ZoneModule 7 Room Temperature SetpointAV1602ZoneModule 7 Minimum Supply TemperatureAV1603ZoneModule 7 Maximum Supply TemperatureAV1604ZoneModule 7 Room CO2 SetpointAV1605ZoneModule 7 Room RH SetpointAV1606ZoneModule 7 VAV Supply PIR Min. Air FlowAV1607ZoneModule 7 VAV Supply 1 Min. Air FlowAV1608ZoneModule 7 VAV Supply 1 Max. Air FlowAV1609ZoneModule 7 VAV Supply 2 Min. Air FlowAV1610ZoneModule 7 VAV Supply 2 Max. Air FlowAV1611ZoneModule 7 VAV Extract Min. Air FlowAV1612ZoneModule 7 VAV Extract Max. Air FlowAV1613ZoneModule 7 VAV Supply 1 Nominal Air FlowAV1614ZoneModule 7 VAV Supply 2 Nominal Air FlowAV1615ZoneModule 7 VAV Extract Nominal Air FlowAV1616ZoneModule 7 Room Panel Low Air FlowAV1617ZoneModule 7 Room Panel High Air FlowAV1618ZoneModule 7 Room Panel Override TimeoutAV1619ZoneModule 7 Heat Valve Max. FlowAV1620ZoneModule 7 Cool Valve Max. FlowAV1622ZoneModule 7 VAV Extract 2 Nominal Air FlowAV1623ZoneModule 7 VAV Extract 2 Min. Air FlowAV1624ZoneModule 7 VAV Extract 2 Max. Air FlowAV1701ZoneModule 8 Room Temperature SetpointAV1702ZoneModule 8 Minimum Supply TemperatureAV1703ZoneModule 8 Maximum Supply TemperatureAV1704ZoneModule 8 Room CO2 SetpointAV1705ZoneModule 8 Room RH SetpointAV1706ZoneModule 8 VAV Supply PIR Min. Air FlowAV1707ZoneModule 8 VAV Supply 1 Min. Air FlowAV1708ZoneModule 8 VAV Supply 1 Max. Air FlowAV1709ZoneModule 8 VAV Supply 2 Min. Air FlowAV1710ZoneModule 8 VAV Supply 2 Max. Air FlowAV1711ZoneModule 8 VAV Extract Min. Air FlowAV1712ZoneModule 8 VAV Extract Max. Air FlowAV1713ZoneModule 8 VAV Supply 1 Nominal Air FlowAV1714ZoneModule 8 VAV Supply 2 Nominal Air FlowAV1715ZoneModule 8 VAV Extract Nominal Air FlowAV1716ZoneModule 8 Room Panel Low Air FlowAV1717ZoneModule 8 Room Panel High Air FlowAV1718ZoneModule 8 Room Panel Override TimeoutAV1719ZoneModule 8 Heat Valve Max. FlowAV1720ZoneModule 8 Cool Valve Max. FlowAV1722ZoneModule 8 VAV Extract 2 Nominal Air FlowAV1723ZoneModule 8 VAV Extract 2 Min. Air FlowAV1724ZoneModule 8 VAV Extract 2 Max. Air FlowAV1801ZoneModule 9 Room Temperature SetpointAV1802ZoneModule 9 Minimum Supply TemperatureAV1803ZoneModule 9 Maximum Supply TemperatureAV1804ZoneModule 9 Room CO2 SetpointAV1805ZoneModule 9 Room RH SetpointAV1806ZoneModule 9 VAV Supply PIR Min. Air FlowAV1807ZoneModule 9 VAV Supply 1 Min. Air FlowAV1808ZoneModule 9 VAV Supply 1 Max. Air FlowAV1809ZoneModule 9 VAV Supply 2 Min. Air FlowAV1810ZoneModule 9 VAV Supply 2 Max. Air FlowAV1811ZoneModule 9 VAV Extract Min. Air FlowAV1812ZoneModule 9 VAV Extract Max. Air FlowAV1813ZoneModule 9 VAV Supply 1 Nominal Air FlowAV1814ZoneModule 9 VAV Supply 2 Nominal Air FlowAV1815ZoneModule 9 VAV Extract Nominal Air FlowAV1816ZoneModule 9 Room Panel Low Air FlowAV1817ZoneModule 9 Room Panel High Air FlowAV1818ZoneModule 9 Room Panel Override TimeoutAV1819ZoneModule 9 Heat Valve Max. FlowAV1820ZoneModule 9 Cool Valve Max. FlowAV1822ZoneModule 9 VAV Extract 2 Nominal Air FlowAV1823ZoneModule 9 VAV Extract 2 Min. Air FlowAV1824ZoneModule 9 VAV Extract 2 Max. Air FlowAV1901ZoneModule 10 Room Temperature SetpointAV1902ZoneModule 10 Minimum Supply TemperatureAV1903ZoneModule 10 Maximum Supply TemperatureAV1904ZoneModule 10 Room CO2 SetpointAV1905ZoneModule 10 Room RH SetpointAV1906ZoneModule 10 VAV Supply PIR Min. Air FlowAV1907ZoneModule 10 VAV Supply 1 Min. Air FlowAV1908ZoneModule 10 VAV Supply 1 Max. Air FlowAV1909ZoneModule 10 VAV Supply 2 Min. Air FlowAV1910ZoneModule 10 VAV Supply 2 Max. Air FlowAV1911ZoneModule 10 VAV Extract Min. Air FlowAV1912ZoneModule 10 VAV Extract Max. Air FlowAV1913ZoneModule 10 VAV Supply 1 Nominal Air FlowAV1914ZoneModule 10 VAV Supply 2 Nominal Air FlowAV1915ZoneModule 10 VAV Extract Nominal Air FlowAV1916ZoneModule 10 Room Panel Low Air FlowAV1917ZoneModule 10 Room Panel High Air FlowAV1918ZoneModule 10 Room Panel Override TimeoutAV1919ZoneModule 10 Heat Valve Max. FlowAV1920ZoneModule 10 Cool Valve Max. FlowAV1922ZoneModule 10 VAV Extract 2 Nominal Air FlowAV1923ZoneModule 10 VAV Extract 2 Min. Air FlowAV1924ZoneModule 10 VAV Extract 2 Max. Air FlowAV2001ZoneModule 11 Room Temperature SetpointAV2002ZoneModule 11 Minimum Supply TemperatureAV2003ZoneModule 11 Maximum Supply TemperatureAV2004ZoneModule 11 Room CO2 SetpointAV2005ZoneModule 11 Room RH SetpointAV2006ZoneModule 11 VAV Supply PIR Min. Air FlowAV2007ZoneModule 11 VAV Supply 1 Min. Air FlowAV2008ZoneModule 11 VAV Supply 1 Max. Air FlowAV2009ZoneModule 11 VAV Supply 2 Min. Air FlowAV2010ZoneModule 11 VAV Supply 2 Max. Air FlowAV2011ZoneModule 11 VAV Extract Min. Air FlowAV2012ZoneModule 11 VAV Extract Max. Air FlowAV2013ZoneModule 11 VAV Supply 1 Nominal Air FlowAV2014ZoneModule 11 VAV Supply 2 Nominal Air FlowAV2015ZoneModule 11 VAV Extract Nominal Air FlowAV2016ZoneModule 11 Room Panel Low Air FlowAV2017ZoneModule 11 Room Panel High Air FlowAV2018ZoneModule 11 Room Panel Override TimeoutAV2019ZoneModule 11 Heat Valve Max. FlowAV2020ZoneModule 11 Cool Valve Max. FlowAV2022ZoneModule 11 VAV Extract 2 Nominal Air FlowAV2023ZoneModule 11 VAV Extract 2 Min. Air FlowAV2024ZoneModule 11 VAV Extract 2 Max. Air FlowAV2101ZoneModule 12 Room Temperature SetpointAV2102ZoneModule 12 Minimum Supply TemperatureAV2103ZoneModule 12 Maximum Supply TemperatureAV2104ZoneModule 12 Room CO2 SetpointAV2105ZoneModule 12 Room RH SetpointAV2106ZoneModule 12 VAV Supply PIR Min. Air FlowAV2107ZoneModule 12 VAV Supply 1 Min. Air FlowAV2108ZoneModule 12 VAV Supply 1 Max. Air FlowAV2109ZoneModule 12 VAV Supply 2 Min. Air FlowAV2110ZoneModule 12 VAV Supply 2 Max. Air FlowAV2111ZoneModule 12 VAV Extract Min. Air FlowAV2112ZoneModule 12 VAV Extract Max. Air FlowAV2113ZoneModule 12 VAV Supply 1 Nominal Air FlowAV2114ZoneModule 12 VAV Supply 2 Nominal Air FlowAV2115ZoneModule 12 VAV Extract Nominal Air FlowAV2116ZoneModule 12 Room Panel Low Air FlowAV2117ZoneModule 12 Room Panel High Air FlowAV2118ZoneModule 12 Room Panel Override TimeoutAV2119ZoneModule 12 Heat Valve Max. FlowAV2120ZoneModule 12 Cool Valve Max. FlowAV2122ZoneModule 12 VAV Extract 2 Nominal Air FlowAV2123ZoneModule 12 VAV Extract 2 Min. Air FlowAV2124ZoneModule 12 VAV Extract 2 Max. Air FlowAV2201ZoneModule 13 Room Temperature SetpointAV2202ZoneModule 13 Minimum Supply TemperatureAV2203ZoneModule 13 Maximum Supply TemperatureAV2204ZoneModule 13 Room CO2 SetpointAV2205ZoneModule 13 Room RH SetpointAV2206ZoneModule 13 VAV Supply PIR Min. Air FlowAV2207ZoneModule 13 VAV Supply 1 Min. Air FlowAV2208ZoneModule 13 VAV Supply 1 Max. Air FlowAV2209ZoneModule 13 VAV Supply 2 Min. Air FlowAV2210ZoneModule 13 VAV Supply 2 Max. Air FlowAV2211ZoneModule 13 VAV Extract Min. Air FlowAV2212ZoneModule 13 VAV Extract Max. Air FlowAV2213ZoneModule 13 VAV Supply 1 Nominal Air FlowAV2214ZoneModule 13 VAV Supply 2 Nominal Air FlowAV2215ZoneModule 13 VAV Extract Nominal Air FlowAV2216ZoneModule 13 Room Panel Low Air FlowAV2217ZoneModule 13 Room Panel High Air FlowAV2218ZoneModule 13 Room Panel Override TimeoutAV2219ZoneModule 13 Heat Valve Max. FlowAV2220ZoneModule 13 Cool Valve Max. FlowAV2222ZoneModule 13 VAV Extract 2 Nominal Air FlowAV2223ZoneModule 13 VAV Extract 2 Min. Air FlowAV2224ZoneModule 13 VAV Extract 2 Max. Air FlowAV2301ZoneModule 14 Room Temperature SetpointAV2302ZoneModule 14 Minimum Supply TemperatureAV2303ZoneModule 14 Maximum Supply TemperatureAV2304ZoneModule 14 Room CO2 SetpointAV2305ZoneModule 14 Room RH SetpointAV2306ZoneModule 14 VAV Supply PIR Min. Air FlowAV2307ZoneModule 14 VAV Supply 1 Min. Air FlowAV2308ZoneModule 14 VAV Supply 1 Max. Air FlowAV2309ZoneModule 14 VAV Supply 2 Min. Air FlowAV2310ZoneModule 14 VAV Supply 2 Max. Air FlowAV2311ZoneModule 14 VAV Extract Min. Air FlowAV2312ZoneModule 14 VAV Extract Max. Air FlowAV2313ZoneModule 14 VAV Supply 1 Nominal Air FlowAV2314ZoneModule 14 VAV Supply 2 Nominal Air FlowAV2315ZoneModule 14 VAV Extract Nominal Air FlowAV2316ZoneModule 14 Room Panel Low Air FlowAV2317ZoneModule 14 Room Panel High Air FlowAV2318ZoneModule 14 Room Panel Override TimeoutAV2319ZoneModule 14 Heat Valve Max. FlowAV2320ZoneModule 14 Cool Valve Max. FlowAV2322ZoneModule 14 VAV Extract 2 Nominal Air FlowAV2323ZoneModule 14 VAV Extract 2 Min. Air FlowAV2324ZoneModule 14 VAV Extract 2 Max. Air FlowAV2401ZoneModule 15 Room Temperature SetpointAV2402ZoneModule 15 Minimum Supply TemperatureAV2403ZoneModule 15 Maximum Supply TemperatureAV2404ZoneModule 15 Room CO2 SetpointAV2405ZoneModule 15 Room RH SetpointAV2406ZoneModule 15 VAV Supply PIR Min. Air FlowAV2407ZoneModule 15 VAV Supply 1 Min. Air FlowAV2408ZoneModule 15 VAV Supply 1 Max. Air FlowAV2409ZoneModule 15 VAV Supply 2 Min. Air FlowAV2410ZoneModule 15 VAV Supply 2 Max. Air FlowAV2411ZoneModule 15 VAV Extract Min. Air FlowAV2412ZoneModule 15 VAV Extract Max. Air FlowAV2413ZoneModule 15 VAV Supply 1 Nominal Air FlowAV2414ZoneModule 15 VAV Supply 2 Nominal Air FlowAV2415ZoneModule 15 VAV Extract Nominal Air FlowAV2416ZoneModule 15 Room Panel Low Air FlowAV2417ZoneModule 15 Room Panel High Air FlowAV2418ZoneModule 15 Room Panel Override TimeoutAV2419ZoneModule 15 Heat Valve Max. FlowAV2420ZoneModule 15 Cool Valve Max. FlowAV2422ZoneModule 15 VAV Extract 2 Nominal Air FlowAV2423ZoneModule 15 VAV Extract 2 Min. Air FlowAV2424ZoneModule 15 VAV Extract 2 Max. Air FlowAV2501ZoneModule 16 Room Temperature SetpointAV2502ZoneModule 16 Minimum Supply TemperatureAV2503ZoneModule 16 Maximum Supply TemperatureAV2504ZoneModule 16 Room CO2 SetpointAV2505ZoneModule 16 Room RH SetpointAV2506ZoneModule 16 VAV Supply PIR Min. Air FlowAV2507ZoneModule 16 VAV Supply 1 Min. Air FlowAV2508ZoneModule 16 VAV Supply 1 Max. Air FlowAV2509ZoneModule 16 VAV Supply 2 Min. Air FlowAV2510ZoneModule 16 VAV Supply 2 Max. Air FlowAV2511ZoneModule 16 VAV Extract Min. Air FlowAV2512ZoneModule 16 VAV Extract Max. Air FlowAV2513ZoneModule 16 VAV Supply 1 Nominal Air FlowAV2514ZoneModule 16 VAV Supply 2 Nominal Air FlowAV2515ZoneModule 16 VAV Extract Nominal Air FlowAV2516ZoneModule 16 Room Panel Low Air FlowAV2517ZoneModule 16 Room Panel High Air FlowAV2518ZoneModule 16 Room Panel Override TimeoutAV2519ZoneModule 16 Heat Valve Max. FlowAV2520ZoneModule 16 Cool Valve Max. FlowAV2522ZoneModule 16 VAV Extract 2 Nominal Air FlowAV2523ZoneModule 16 VAV Extract 2 Min. Air FlowAV2524ZoneModule 16 VAV Extract 2 Max. Air FlowAV2601ZoneModule 17 Room Temperature SetpointAV2602ZoneModule 17 Minimum Supply TemperatureAV2603ZoneModule 17 Maximum Supply TemperatureAV2604ZoneModule 17 Room CO2 SetpointAV2605ZoneModule 17 Room RH SetpointAV2606ZoneModule 17 VAV Supply PIR Min. Air FlowAV2607ZoneModule 17 VAV Supply 1 Min. Air FlowAV2608ZoneModule 17 VAV Supply 1 Max. Air FlowAV2609ZoneModule 17 VAV Supply 2 Min. Air FlowAV2610ZoneModule 17 VAV Supply 2 Max. Air FlowAV2611ZoneModule 17 VAV Extract Min. Air FlowAV2612ZoneModule 17 VAV Extract Max. Air FlowAV2613ZoneModule 17 VAV Supply 1 Nominal Air FlowAV2614ZoneModule 17 VAV Supply 2 Nominal Air FlowAV2615ZoneModule 17 VAV Extract Nominal Air FlowAV2616ZoneModule 17 Room Panel Low Air FlowAV2617ZoneModule 17 Room Panel High Air FlowAV2618ZoneModule 17 Room Panel Override TimeoutAV2619ZoneModule 17 Heat Valve Max. FlowAV2620ZoneModule 17 Cool Valve Max. FlowAV2622ZoneModule 17 VAV Extract 2 Nominal Air FlowAV2623ZoneModule 17 VAV Extract 2 Min. Air FlowAV2624ZoneModule 17 VAV Extract 2 Max. Air FlowAV2701ZoneModule 18 Room Temperature SetpointAV2702ZoneModule 18 Minimum Supply TemperatureAV2703ZoneModule 18 Maximum Supply TemperatureAV2704ZoneModule 18 Room CO2 SetpointAV2705ZoneModule 18 Room RH SetpointAV2706ZoneModule 18 VAV Supply PIR Min. Air FlowAV2707ZoneModule 18 VAV Supply 1 Min. Air FlowAV2708ZoneModule 18 VAV Supply 1 Max. Air FlowAV2709ZoneModule 18 VAV Supply 2 Min. Air FlowAV2710ZoneModule 18 VAV Supply 2 Max. Air FlowAV2711ZoneModule 18 VAV Extract Min. Air FlowAV2712ZoneModule 18 VAV Extract Max. Air FlowAV2713ZoneModule 18 VAV Supply 1 Nominal Air FlowAV2714ZoneModule 18 VAV Supply 2 Nominal Air FlowAV2715ZoneModule 18 VAV Extract Nominal Air FlowAV2716ZoneModule 18 Room Panel Low Air FlowAV2717ZoneModule 18 Room Panel High Air FlowAV2718ZoneModule 18 Room Panel Override TimeoutAV2719ZoneModule 18 Heat Valve Max. FlowAV2720ZoneModule 18 Cool Valve Max. FlowAV2722ZoneModule 18 VAV Extract 2 Nominal Air FlowAV2723ZoneModule 18 VAV Extract 2 Min. Air FlowAV2724ZoneModule 18 VAV Extract 2 Max. Air FlowAV2801ZoneModule 19 Room Temperature SetpointAV2802ZoneModule 19 Minimum Supply TemperatureAV2803ZoneModule 19 Maximum Supply TemperatureAV2804ZoneModule 19 Room CO2 SetpointAV2805ZoneModule 19 Room RH SetpointAV2806ZoneModule 19 VAV Supply PIR Min. Air FlowAV2807ZoneModule 19 VAV Supply 1 Min. Air FlowAV2808ZoneModule 19 VAV Supply 1 Max. Air FlowAV2809ZoneModule 19 VAV Supply 2 Min. Air FlowAV2810ZoneModule 19 VAV Supply 2 Max. Air FlowAV2811ZoneModule 19 VAV Extract Min. Air FlowAV2812ZoneModule 19 VAV Extract Max. Air FlowAV2813ZoneModule 19 VAV Supply 1 Nominal Air FlowAV2814ZoneModule 19 VAV Supply 2 Nominal Air FlowAV2815ZoneModule 19 VAV Extract Nominal Air FlowAV2816ZoneModule 19 Room Panel Low Air FlowAV2817ZoneModule 19 Room Panel High Air FlowAV2818ZoneModule 19 Room Panel Override TimeoutAV2819ZoneModule 19 Heat Valve Max. FlowAV2820ZoneModule 19 Cool Valve Max. FlowAV2822ZoneModule 19 VAV Extract 2 Nominal Air FlowAV2823ZoneModule 19 VAV Extract 2 Min. Air FlowAV2824ZoneModule 19 VAV Extract 2 Max. Air FlowAV2901ZoneModule 20 Room Temperature SetpointAV2902ZoneModule 20 Minimum Supply TemperatureAV2903ZoneModule 20 Maximum Supply TemperatureAV2904ZoneModule 20 Room CO2 SetpointAV2905ZoneModule 20 Room RH SetpointAV2906ZoneModule 20 VAV Supply PIR Min. Air FlowAV2907ZoneModule 20 VAV Supply 1 Min. Air FlowAV2908ZoneModule 20 VAV Supply 1 Max. Air FlowAV2909ZoneModule 20 VAV Supply 2 Min. Air FlowAV2910ZoneModule 20 VAV Supply 2 Max. Air FlowAV2911ZoneModule 20 VAV Extract Min. Air FlowAV2912ZoneModule 20 VAV Extract Max. Air FlowAV2913ZoneModule 20 VAV Supply 1 Nominal Air FlowAV2914ZoneModule 20 VAV Supply 2 Nominal Air FlowAV2915ZoneModule 20 VAV Extract Nominal Air FlowAV2916ZoneModule 20 Room Panel Low Air FlowAV2917ZoneModule 20 Room Panel High Air FlowAV2918ZoneModule 20 Room Panel Override TimeoutAV2919ZoneModule 20 Heat Valve Max. FlowAV2920ZoneModule 20 Cool Valve Max. FlowAV2922ZoneModule 20 VAV Extract 2 Nominal Air FlowAV2923ZoneModule 20 VAV Extract 2 Min. Air FlowAV2924ZoneModule 20 VAV Extract 2 Max. Air FlowAV3001ZoneModule 21 Room Temperature SetpointAV3002ZoneModule 21 Minimum Supply TemperatureAV3003ZoneModule 21 Maximum Supply TemperatureAV3004ZoneModule 21 Room CO2 SetpointAV3005ZoneModule 21 Room RH SetpointAV3006ZoneModule 21 VAV Supply PIR Min. Air FlowAV3007ZoneModule 21 VAV Supply 1 Min. Air FlowAV3008ZoneModule 21 VAV Supply 1 Max. Air FlowAV3009ZoneModule 21 VAV Supply 2 Min. Air FlowAV3010ZoneModule 21 VAV Supply 2 Max. Air FlowAV3011ZoneModule 21 VAV Extract Min. Air FlowAV3012ZoneModule 21 VAV Extract Max. Air FlowAV3013ZoneModule 21 VAV Supply 1 Nominal Air FlowAV3014ZoneModule 21 VAV Supply 2 Nominal Air FlowAV3015ZoneModule 21 VAV Extract Nominal Air FlowAV3016ZoneModule 21 Room Panel Low Air FlowAV3017ZoneModule 21 Room Panel High Air FlowAV3018ZoneModule 21 Room Panel Override TimeoutAV3019ZoneModule 21 Heat Valve Max. FlowAV3020ZoneModule 21 Cool Valve Max. FlowAV3022ZoneModule 21 VAV Extract 2 Nominal Air FlowAV3023ZoneModule 21 VAV Extract 2 Min. Air FlowAV3024ZoneModule 21 VAV Extract 2 Max. Air FlowAV3101ZoneModule 22 Room Temperature SetpointAV3102ZoneModule 22 Minimum Supply TemperatureAV3103ZoneModule 22 Maximum Supply TemperatureAV3104ZoneModule 22 Room CO2 SetpointAV3105ZoneModule 22 Room RH SetpointAV3106ZoneModule 22 VAV Supply PIR Min. Air FlowAV3107ZoneModule 22 VAV Supply 1 Min. Air FlowAV3108ZoneModule 22 VAV Supply 1 Max. Air FlowAV3109ZoneModule 22 VAV Supply 2 Min. Air FlowAV3110ZoneModule 22 VAV Supply 2 Max. Air FlowAV3111ZoneModule 22 VAV Extract Min. Air FlowAV3112ZoneModule 22 VAV Extract Max. Air FlowAV3113ZoneModule 22 VAV Supply 1 Nominal Air FlowAV3114ZoneModule 22 VAV Supply 2 Nominal Air FlowAV3115ZoneModule 22 VAV Extract Nominal Air FlowAV3116ZoneModule 22 Room Panel Low Air FlowAV3117ZoneModule 22 Room Panel High Air FlowAV3118ZoneModule 22 Room Panel Override TimeoutAV3119ZoneModule 22 Heat Valve Max. FlowAV3120ZoneModule 22 Cool Valve Max. FlowAV3122ZoneModule 22 VAV Extract 2 Nominal Air FlowAV3123ZoneModule 22 VAV Extract 2 Min. Air FlowAV3124ZoneModule 22 VAV Extract 2 Max. Air FlowAV3201ZoneModule 23 Room Temperature SetpointAV3202ZoneModule 23 Minimum Supply TemperatureAV3203ZoneModule 23 Maximum Supply TemperatureAV3204ZoneModule 23 Room CO2 SetpointAV3205ZoneModule 23 Room RH SetpointAV3206ZoneModule 23 VAV Supply PIR Min. Air FlowAV3207ZoneModule 23 VAV Supply 1 Min. Air FlowAV3208ZoneModule 23 VAV Supply 1 Max. Air FlowAV3209ZoneModule 23 VAV Supply 2 Min. Air FlowAV3210ZoneModule 23 VAV Supply 2 Max. Air FlowAV3211ZoneModule 23 VAV Extract Min. Air FlowAV3212ZoneModule 23 VAV Extract Max. Air FlowAV3213ZoneModule 23 VAV Supply 1 Nominal Air FlowAV3214ZoneModule 23 VAV Supply 2 Nominal Air FlowAV3215ZoneModule 23 VAV Extract Nominal Air FlowAV3216ZoneModule 23 Room Panel Low Air FlowAV3217ZoneModule 23 Room Panel High Air FlowAV3218ZoneModule 23 Room Panel Override TimeoutAV3219ZoneModule 23 Heat Valve Max. FlowAV3220ZoneModule 23 Cool Valve Max. FlowAV3222ZoneModule 23 VAV Extract 2 Nominal Air FlowAV3223ZoneModule 23 VAV Extract 2 Min. Air FlowAV3224ZoneModule 23 VAV Extract 2 Max. Air FlowAV3301ZoneModule 24 Room Temperature SetpointAV3302ZoneModule 24 Minimum Supply TemperatureAV3303ZoneModule 24 Maximum Supply TemperatureAV3304ZoneModule 24 Room CO2 SetpointAV3305ZoneModule 24 Room RH SetpointAV3306ZoneModule 24 VAV Supply PIR Min. Air FlowAV3307ZoneModule 24 VAV Supply 1 Min. Air FlowAV3308ZoneModule 24 VAV Supply 1 Max. Air FlowAV3309ZoneModule 24 VAV Supply 2 Min. Air FlowAV3310ZoneModule 24 VAV Supply 2 Max. Air FlowAV3311ZoneModule 24 VAV Extract Min. Air FlowAV3312ZoneModule 24 VAV Extract Max. Air FlowAV3313ZoneModule 24 VAV Supply 1 Nominal Air FlowAV3314ZoneModule 24 VAV Supply 2 Nominal Air FlowAV3315ZoneModule 24 VAV Extract Nominal Air FlowAV3316ZoneModule 24 Room Panel Low Air FlowAV3317ZoneModule 24 Room Panel High Air FlowAV3318ZoneModule 24 Room Panel Override TimeoutAV3319ZoneModule 24 Heat Valve Max. FlowAV3320ZoneModule 24 Cool Valve Max. FlowAV3322ZoneModule 24 VAV Extract 2 Nominal Air FlowAV3323ZoneModule 24 VAV Extract 2 Min. Air FlowAV3324ZoneModule 24 VAV Extract 2 Max. Air FlowAV3401ZoneModule 25 Room Temperature SetpointAV3402ZoneModule 25 Minimum Supply TemperatureAV3403ZoneModule 25 Maximum Supply TemperatureAV3404ZoneModule 25 Room CO2 SetpointAV3405ZoneModule 25 Room RH SetpointAV3406ZoneModule 25 VAV Supply PIR Min. Air FlowAV3407ZoneModule 25 VAV Supply 1 Min. Air FlowAV3408ZoneModule 25 VAV Supply 1 Max. Air FlowAV3409ZoneModule 25 VAV Supply 2 Min. Air FlowAV3410ZoneModule 25 VAV Supply 2 Max. Air FlowAV3411ZoneModule 25 VAV Extract Min. Air FlowAV3412ZoneModule 25 VAV Extract Max. Air FlowAV3413ZoneModule 25 VAV Supply 1 Nominal Air FlowAV3414ZoneModule 25 VAV Supply 2 Nominal Air FlowAV3415ZoneModule 25 VAV Extract Nominal Air FlowAV3416ZoneModule 25 Room Panel Low Air FlowAV3417ZoneModule 25 Room Panel High Air FlowAV3418ZoneModule 25 Room Panel Override TimeoutAV3419ZoneModule 25 Heat Valve Max. FlowAV3420ZoneModule 25 Cool Valve Max. FlowAV3422ZoneModule 25 VAV Extract 2 Nominal Air FlowAV3423ZoneModule 25 VAV Extract 2 Min. Air FlowAV3424ZoneModule 25 VAV Extract 2 Max. Air FlowBI100AHU Heating Pump StateBI101Combined DIN Supply Fan AlarmBI102Combined DIN Extract Fan AlarmBI103Combined DIN StartBI104Combined DIN FireBI105Combined DIN Max AirBI106Combined DIN Min AirBI107Combined DIN Summer Night CoolingBI300Section PIR StatusBI301Section Frost Protection StatusBI1000ZoneModule 1 Window/Frost ValueBI1001ZoneModule 1 PIR Active FlagBI1002ZoneModule 1 Room Temp Sensor Short Circuit FlagBI1003ZoneModule 1 Supply Temp Sensor Short Circuit FlaBI1100ZoneModule 2 Window/Frost ValueBI1101ZoneModule 2 PIR Active FlagBI1102ZoneModule 2 Room Temp Sensor Short Circuit FlagBI1103ZoneModule 2 Supply Temp Sensor Short Circuit FlaBI1200ZoneModule 3 Window/Frost ValueBI1201ZoneModule 3 PIR Active FlagBI1202ZoneModule 3 Room Temp Sensor Short Circuit FlagBI1203ZoneModule 3 Supply Temp Sensor Short Circuit FlaBI1300ZoneModule 4 Window/Frost ValueBI1301ZoneModule 4 PIR Active FlagBI1302ZoneModule 4 Room Temp Sensor Short Circuit FlagBI1303ZoneModule 4 Supply Temp Sensor Short Circuit FlaBI1400ZoneModule 5 Window/Frost ValueBI1401ZoneModule 5 PIR Active FlagBI1402ZoneModule 5 Room Temp Sensor Short Circuit FlagBI1403ZoneModule 5 Supply Temp Sensor Short Circuit FlaBI1500ZoneModule 6 Window/Frost ValueBI1501ZoneModule 6 PIR Active FlagBI1502ZoneModule 6 Room Temp Sensor Short Circuit FlagBI1503ZoneModule 6 Supply Temp Sensor Short Circuit FlaBI1600ZoneModule 7 Window/Frost ValueBI1601ZoneModule 7 PIR Active FlagBI1602ZoneModule 7 Room Temp Sensor Short Circuit FlagBI1603ZoneModule 7 Supply Temp Sensor Short Circuit FlaBI1700ZoneModule 8 Window/Frost ValueBI1701ZoneModule 8 PIR Active FlagBI1702ZoneModule 8 Room Temp Sensor Short Circuit FlagBI1703ZoneModule 8 Supply Temp Sensor Short Circuit FlaBI1800ZoneModule 9 Window/Frost ValueBI1801ZoneModule 9 PIR Active FlagBI1802ZoneModule 9 Room Temp Sensor Short Circuit FlagBI1803ZoneModule 9 Supply Temp Sensor Short Circuit FlaBI1900ZoneModule 10 Window/Frost ValueBI1901ZoneModule 10 PIR Active FlagBI1902ZoneModule 10 Room Temp Sensor Short Circuit FlagBI1903ZoneModule 10 Supply Temp Sensor Short Circuit FlBI2000ZoneModule 11 Window/Frost ValueBI2001ZoneModule 11 PIR Active FlagBI2002ZoneModule 11 Room Temp Sensor Short Circuit FlagBI2003ZoneModule 11 Supply Temp Sensor Short Circuit FlBI2100ZoneModule 12 Window/Frost ValueBI2101ZoneModule 12 PIR Active FlagBI2102ZoneModule 12 Room Temp Sensor Short Circuit FlagBI2103ZoneModule 12 Supply Temp Sensor Short Circuit FlBI2200ZoneModule 13 Window/Frost ValueBI2201ZoneModule 13 PIR Active FlagBI2202ZoneModule 13 Room Temp Sensor Short Circuit FlagBI2203ZoneModule 13 Supply Temp Sensor Short Circuit FlBI2300ZoneModule 14 Window/Frost ValueBI2301ZoneModule 14 PIR Active FlagBI2302ZoneModule 14 Room Temp Sensor Short Circuit FlagBI2303ZoneModule 14 Supply Temp Sensor Short Circuit FlBI2400ZoneModule 15 Window/Frost ValueBI2401ZoneModule 15 PIR Active FlagBI2402ZoneModule 15 Room Temp Sensor Short Circuit FlagBI2403ZoneModule 15 Supply Temp Sensor Short Circuit FlBI2500ZoneModule 16 Window/Frost ValueBI2501ZoneModule 16 PIR Active FlagBI2502ZoneModule 16 Room Temp Sensor Short Circuit FlagBI2503ZoneModule 16 Supply Temp Sensor Short Circuit FlBI2600ZoneModule 17 Window/Frost ValueBI2601ZoneModule 17 PIR Active FlagBI2602ZoneModule 17 Room Temp Sensor Short Circuit FlagBI2603ZoneModule 17 Supply Temp Sensor Short Circuit FlBI2700ZoneModule 18 Window/Frost ValueBI2701ZoneModule 18 PIR Active FlagBI2702ZoneModule 18 Room Temp Sensor Short Circuit FlagBI2703ZoneModule 18 Supply Temp Sensor Short Circuit FlBI2800ZoneModule 19 Window/Frost ValueBI2801ZoneModule 19 PIR Active FlagBI2802ZoneModule 19 Room Temp Sensor Short Circuit FlagBI2803ZoneModule 19 Supply Temp Sensor Short Circuit FlBI2900ZoneModule 20 Window/Frost ValueBI2901ZoneModule 20 PIR Active FlagBI2902ZoneModule 20 Room Temp Sensor Short Circuit FlagBI2903ZoneModule 20 Supply Temp Sensor Short Circuit FlBI3000ZoneModule 21 Window/Frost ValueBI3001ZoneModule 21 PIR Active FlagBI3002ZoneModule 21 Room Temp Sensor Short Circuit FlagBI3003ZoneModule 21 Supply Temp Sensor Short Circuit FlBI3100ZoneModule 22 Window/Frost ValueBI3101ZoneModule 22 PIR Active FlagBI3102ZoneModule 22 Room Temp Sensor Short Circuit FlagBI3103ZoneModule 22 Supply Temp Sensor Short Circuit FlBI3200ZoneModule 23 Window/Frost ValueBI3201ZoneModule 23 PIR Active FlagBI3202ZoneModule 23 Room Temp Sensor Short Circuit FlagBI3203ZoneModule 23 Supply Temp Sensor Short Circuit FlBI3300ZoneModule 24 Window/Frost ValueBI3301ZoneModule 24 PIR Active FlagBI3302ZoneModule 24 Room Temp Sensor Short Circuit FlagBI3303ZoneModule 24 Supply Temp Sensor Short Circuit FlBI3400ZoneModule 25 Window/Frost ValueBI3401ZoneModule 25 PIR Active FlagBI3402ZoneModule 25 Room Temp Sensor Short Circuit FlagBI3403ZoneModule 25 Supply Temp Sensor Short Circuit FlBV100Summer/Winter Compensation EnableBV103DIN Start (BMS)BV104DIN Fire (BMS)BV105DIN Max Air (BMS)BV106DIN Min Air (BMS)BV107DIN Combi-Heat Available (BMS)BV108DIN Combi-Cool Available (BMS)BV109DIN Summer Night Cooling (BMS)BV110Enable Digital Input Values from BMSBV111Week Schedule Enabled in ZonesBV112Clear All Alarms (BMS)
Integration notes
- Built from the installer EDE export (67851, 06-07-2020). The EDE has no read/write column, units or descriptions, so access is inferred (AV/BV writable, AI/BI read-only) and units are blank.
- Each ZoneModule n uses its own instance block (ZoneModule 1 = 1000-range, ZoneModule 9 = 1800-range); objects for zone modules that are not installed will read nothing useful.
- ZoneMaster 1-5 local alarm status sits on AI 4000, 4100, 4200, 4300 and 4400.
- The EDE does not say which BACnet transport the controller uses; check it on site.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ GreenZone ZoneMaster, SW 3.47 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the OJ Electronics OJ GreenZone ZoneMaster, SW 3.47
How many BACnet points does the OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 have?
This list has 1544 BACnet objects: 827 analog inputs, 596 analog values, 110 binary inputs, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 BACnet points are writable?
607 of the 1544 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official OJ Electronics OJ GreenZone ZoneMaster, SW 3.47 BACnet documentation?
The source is OJ GreenZone ZoneControl EDE file (installer), v3.47 (67851), revision 06-07-2020, published free by OJ Electronics at https://ojelectronics.com/controllers-sensors/wp-admin/admin-ajax.php?action=productdownload&media_id=46526948&filename=67851-ZoneControl_v347_ede-installer.csv.
What are the minimum BACnet points to integrate the OJ Electronics OJ GreenZone ZoneMaster, SW 3.47?
Start with BV 103 DIN Start (BMS) (Start command from the BMS); BV 110 Enable Digital Input Values from BMS (Use BMS values instead of the digital inputs); BV 105 DIN Max Air (BMS) (Max air command from the BMS); BV 106 DIN Min Air (BMS) (Min air command from the BMS); BV 112 Clear All Alarms (BMS) (Clear all alarms); AI 111 ZoneMaster Operation Mode (Current operating mode of the zone system); AI 104 AHU status (Status of the air handling unit); AI 1009 ZoneModule 1 Room Temperature Actual Value (ZoneModule 1 room temperature); AI 109 Section Master Alarm Status (Section master alarm status).
How do I enable BMS control of the OJ Electronics OJ GreenZone ZoneMaster, SW 3.47?
Going by the object names, BV 110 (Enable Digital Input Values from BMS) has to be on before the BMS input values BV 103-109 (start, fire, max/min air, summer night cooling) are used. The EDE has no further explanation.
How do I check these points on the real OJ GreenZone ZoneMaster, SW 3.47?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More OJ Electronics BACnet points lists
- Air handling unit controller
OJ Electronics OJ Air Plus AHU controller (EXcon-Plus), SW 1.09
OJ Electronics OJ Air Plus air handling unit controllers (device name EXcon-Plus) with software 1.09.
Also known as: OJ Air Plus, OJ-Air Plus, AirPlus, EXcon-Plus, EXcon Plus, 670203 - Compressor frequency drive
OJ Electronics OJ-DC compressor drive
OJ Electronics OJ-DC drives for compressors in air handling units, heat pumps and chillers.
Also known as: OJ-DC, OJ DC, OJ Drives DC, 67958B - Rotary heat exchanger drive (energy recovery wheel)
OJ Electronics OJ-DRHX rotary heat exchanger drive
OJ Electronics OJ-DRHX drives for rotary heat exchanger wheels in air handling units.
Also known as: OJ-DRHX, OJ DRHX, DRHX, 67854 - EC/PM fan motor frequency drive
OJ Electronics OJ-DV / OJ-DV GEN II ventilation drive
OJ Electronics OJ-DV ventilation drives for EC/PM fan motors, first generation and GEN II.
Also known as: OJ-DV, OJ DV, OJ-DV GEN II, DV GEN II, OJ Drives DV, 670092, 67855
Source: OJ GreenZone ZoneControl EDE file (installer), v3.47 · 67851 · rev. 06-07-2020. Object names, instances and units are reproduced as published; descriptions are our own.