Rotary heat exchanger drive (energy recovery wheel) · BACnet points list

OJ Electronics OJ-DRHX rotary heat exchanger drive BACnet points list

Updated 12 November 2026

Short answer

The OJ-DRHX drives the rotor of a rotary heat exchanger and has BACnet MS/TP on RS-485. Binary Values give run, alarm reset, rotor guard and other alarm flags and a rotation-OK status; Integer Values carry the setpoint, speed limits, motor and rotor speed, torque and electrical readings. BACnet MS/TP has to be switched on first, through the OJ PC tool or Modbus.

This page lists 39 BACnet objects for the OJ Electronics OJ-DRHX rotary heat exchanger drive — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.

Manufacturer
OJ Electronics
Model
OJ-DRHX rotary heat exchanger drive
Equipment
Rotary heat exchanger drive (energy recovery wheel)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
39 (6 writable)
Transport
BACnet MS/TP
Firmware
AOC 2.50 or later
Also known as
OJ-DRHX, OJ DRHX, DRHX, 67854
Source document
OJ-DRHX BACnet MS/TP protocol (application note) · 67854 · rev. 10/20
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.

BMS integration notes: OJ Electronics OJ-DRHX rotary heat exchanger drive

Integration in brief

Enable BACnet MS/TP on the drive, write the setpoint to IV 0 and set BV 0 to run the wheel. Watch BV 17 (rotation OK), BV 3 (rotor guard alarm) and the other alarm flags; BV 1 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Motor ON/OFFRun command (1 = on); clears on any errorWrite
IV 0Setpoint / PrcSetSetpoint, 0-10000 = 0-100.00 %Write
BV 1Reset AlarmsAlarm reset (1 = reset)Write
BV 17Rotation OKRotation OK (1 = wheel turning)Read
IV 15Rotor Speed OutRotor speed, x0.01 rpmRead
IV 7Motor Speed OutMotor speed, x0.01 rpmRead
BV 3Rotorguard AlarmRotor guard alarmRead
BV 10Internal StopInternal stop alarmRead
BV 9Overload / Rotor BlockedOverload / rotor blocked alarmRead

Enable & remote start

BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the wheel.

Network setup

Watch out for

OJ Electronics OJ-DRHX rotary heat exchanger drive BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

39 of 39 shown
Type
BinaryOther
Access
Show
OJ Electronics OJ-DRHX rotary heat exchanger drive BACnet Points List
DescriptionStates
BVmin0Motor ON/OFFRun command; drive clears it on any errorWrite1=ON
BVmin1Reset AlarmsAlarm reset; returns to 0 after the resetWrite1=Reset
BV2BACnet Enable0 turns BACnet MS/TP off (recover via Modbus)Write1=Enabled
BVmin3Rotorguard AlarmRotor guard (rotation sensor) alarmRead1=Alarm
BV4V LO AlarmRead1=Alarm
BV5V HI AlarmRead1=Alarm
BV6I HI Alarm ( Motor out short)Read1=Alarm
BV7Temperature HighRead1=Warning
BV8Rotorguard signalRotor guard pulseRead1=Pulse
BVmin9Overload / Rotor BlockedRead1=Alarm
BVmin10Internal StopRead1=Alarm (Stop)
BV11I LimitRead1=Warning
BV12EEPROM errorRead1=Warning
BV13Communication error MOCRead1=Alarm
BV14Motor Phase ErrorRead1=Alarm
BV15MOC in bootloaderRead1=Alarm
BV16Communication error IOMRead1=Warning
BVmin17Rotation OKWheel rotation confirmedRead1=OK
BV18Test function activeRead1=Active
IVmin0Setpoint / PrcSetSetpoint, 0-100.00 %; value x0.01%Write
IV1Min. Motor Speedvalue x0.01rpmWrite
IV2Max. Motor Speedvalue x0.01rpmWrite
IV3DRHX TypeDRHX size codeNmRead
IV4MOC SW Versionvalue x0.01Read
IV5PrcOutvalue x0.01%Read
IV6Intern Tempvalue x0.01°CRead
IVmin7Motor Speed OutMotor speed; value x0.01rpmRead
IV8V InVRead
IV9I Out (RMS)mARead
IV10Power InWRead
IV11ExterSetmWRead
IV12Operation DaydaysRead
IV13Operation MinutesminRead
IV14AOC SW Versionvalue x0.01Read
IVmin15Rotor Speed OutRotor (wheel) speed; value x0.01rpmRead
IV16Torquevalue x0.01NmRead
IV17V DC Bus (Peak)VRead
IV18V Motor (Peak)VRead
IV19ExternSet (IOM)mVRead
Object ID lookup: OJ Electronics OJ-DRHX rotary heat exchanger drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ-DRHX rotary heat exchanger drive and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the OJ Electronics OJ-DRHX rotary heat exchanger drive

How many BACnet points does the OJ Electronics OJ-DRHX rotary heat exchanger drive have?

This list has 39 BACnet objects: 19 binary values, 20 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which OJ Electronics OJ-DRHX rotary heat exchanger drive BACnet points are writable?

6 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official OJ Electronics OJ-DRHX rotary heat exchanger drive BACnet documentation?

The source is OJ-DRHX BACnet MS/TP protocol (application note) (67854), revision 10/20, published free by OJ Electronics at https://ojelectronics.com/drives/wp-admin/admin-ajax.php?action=productdownload&media_id=48365800&filename=67854-11-20-OJ-DRHX-BACnet-SM-TP-protocol_GB+web.pdf&view=true.

What are the minimum BACnet points to integrate the OJ Electronics OJ-DRHX rotary heat exchanger drive?

Start with BV 0 Motor ON/OFF (Run command (1 = on); clears on any error); IV 0 Setpoint / PrcSet (Setpoint, 0-10000 = 0-100.00 %); BV 1 Reset Alarms (Alarm reset (1 = reset)); BV 17 Rotation OK (Rotation OK (1 = wheel turning)); IV 15 Rotor Speed Out (Rotor speed, x0.01 rpm); IV 7 Motor Speed Out (Motor speed, x0.01 rpm); BV 3 Rotorguard Alarm (Rotor guard alarm); BV 10 Internal Stop (Internal stop alarm); BV 9 Overload / Rotor Blocked (Overload / rotor blocked alarm).

How do I enable BMS control of the OJ Electronics OJ-DRHX rotary heat exchanger drive?

BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the wheel.

How do I check these points on the real OJ-DRHX rotary heat exchanger drive?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More OJ Electronics BACnet points lists

Source: OJ-DRHX BACnet MS/TP protocol (application note) · 67854 · rev. 10/20. Object names, instances and units are reproduced as published; descriptions are our own.