Compressor frequency drive · BACnet points list

OJ Electronics OJ-DC compressor drive BACnet points list

Updated 12 November 2026

Short answer

The OJ-DC compressor drive has BACnet MS/TP on its RS-485 terminals and RJ12 ports. Binary Values give run, alarm reset and alarm, warning and compressor-protection flags (lubrication, oil boost, minimum run time); Integer Values carry the speed setpoint, limits, ramps and running data. BACnet MS/TP has to be switched on first, through the OJ PC tool or Modbus.

This page lists 56 BACnet objects for the OJ Electronics OJ-DC compressor drive — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from OJ Electronics’s own free documentation, linked below.

Manufacturer
OJ Electronics
Model
OJ-DC compressor drive
Equipment
Compressor frequency drive
Equipment type
VFDs & pumps
BACnet objects
56 (9 writable)
Transport
BACnet MS/TP
Firmware
AOC 1.00 or later
Also known as
OJ-DC, OJ DC, OJ Drives DC, 67958B
Source document
OJ DC BACnet MS/TP protocol (application note) · 67958B · rev. 05/25
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against OJ Electronics’s current documentation and the live device before use. Not official OJ Electronics information. Terms of use.

BMS integration notes: OJ Electronics OJ-DC compressor drive

Integration in brief

Enable BACnet MS/TP on the drive, write the speed setpoint to IV 0 and set BV 0 to run the compressor. Read IV 7/IV 8 for output and speed and the BV alarm flags; BV 1 resets alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Motor on/offRun command (1 = on); clears on any errorWrite
IV 0Setpoint / PrcSetSpeed setpoint, 0-10000 = 0-100.00 %Write
BV 1Reset AlarmsAlarm reset (1 = reset)Write
IV 8RPMOutCompressor speed output, HzRead
IV 7PrcOutOutput level, x0.01 %Read
IV 12Power In (filtered)Input power, WRead
BV 15Internal StopInternal stop alarmRead
BV 10Rotor BlockedRotor blocked alarmRead

Enable & remote start

BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the compressor.

Network setup

Watch out for

OJ Electronics OJ-DC compressor drive BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
BinaryOther
Access
Show
OJ Electronics OJ-DC compressor drive BACnet Points List
DescriptionStates
BVmin0Motor on/offRun command; drive clears it on any errorWrite0=Off, 1=On
BVmin1Reset AlarmsAlarm reset; returns to 0 after the resetWrite1=Reset
BV3Motor output offKeep motor output offWrite1=Keep motor output off
BV4Enable BACnet0 = Modbus, 1 = BACnetWrite0=Modbus 1=BACnet
BV5V LO AlarmRead1=Alarm
BV6V HI AlarmRead1=Alarm
BV7I HI Alarm (Motor out short)Read1=Alarm
BV8Temperature HighRead1=Warning
BV9Input Phase ErrorRead1=Warning
BVmin10Rotor BlockedRead1=Alarm
BV11Current LimitRead1=Warning
BV12Voltage LimitRead1=Warning
BV13Rotor DirectionRead1=Alarm
BV14EEPROM ErrorRead1=Warning
BVmin15Internal StopRead1=Alarm (Stop)
BV16Earth fault (H5 only)Read1=Alarm
BV23STO FaultRead1=Alarm
BV17Motor Phase ErrorRead1=Alarm
BV18Communication error MOCRead1=Alarm
BV19Ext. 24V supply overloadRead1=Overload
BV20MOC in bootloaderRead1=Alarm
BV21Communication error IOMRead1=Warning*
BV22Motor Overheat (IOM)Read1=Alarm
BV40Lubrication activeLubrication cycle runningRead1=Warning
BV41Oil boosting activeOil boost runningRead1=Warning
BV42Minimum run time activeRead1=Warning
BV43Pressure relax time activeRead1=Warning
BV44Maximum oil boost ramp up timeRead1=Alarm
IVmin0Setpoint / PrcSetSpeed setpoint, 0-100.00 %; value x0.01%Write
IV1Min. RPMrpmWrite
IV2Max. RPMrpmWrite
IV3UpRampTimesWrite
IV4DownRampTimesWrite
IV5AOC SW versionvalue x0.01Read
IV6MOC SW versionvalue x0.01Read
IVmin7PrcOutvalue x0.01%Read
IVmin8RPMOutCompressor speed outputHzRead
IV9IGBT TempPower stage (IGBT) temperature; value x0.01°CRead
IV10V In (RMS)VRead
IV11I OutmARead
IVmin12Power In (filtered)WRead
IV13Operation MinutesminRead
IV14Operation DaydaysRead
IV15ExternSetmVRead
IV16V DC Bus (Peak)VRead
IV17V Motor (Peak)VRead
IV18Power Consumpt.Energy, Wh partWhRead
IV19Power Consumpt.Energy, kWh partkWhRead
IV20Power Consumpt.Energy, MWh partMWhRead
IV21BACnet SW versionvalue x0.01Read
IV22Vin L1 - GND (RMS)VRead
IV23Vin L2 - GND (RMS)VRead
IV24Vin L3 - GND (RMS)VRead
IV25Vibration_SUM_RMS2 mgRead
IV26AOC Thermist.Tempvalue x0.01°CRead
IV27CurrentTimeLow1sRead
Object ID lookup: OJ Electronics OJ-DC compressor drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OJ-DC compressor drive and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the OJ Electronics OJ-DC compressor drive

How many BACnet points does the OJ Electronics OJ-DC compressor drive have?

This list has 56 BACnet objects: 28 binary values, 28 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which OJ Electronics OJ-DC compressor drive BACnet points are writable?

9 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official OJ Electronics OJ-DC compressor drive BACnet documentation?

The source is OJ DC BACnet MS/TP protocol (application note) (67958B), revision 05/25, published free by OJ Electronics at https://ojelectronics.com/drives/wp-admin/admin-ajax.php?action=productdownload&media_id=67464802&filename=67958B-05-25-OJ+DC-BACnet-MS-TP-protocol_GB+WEB.pdf&view=true.

What are the minimum BACnet points to integrate the OJ Electronics OJ-DC compressor drive?

Start with BV 0 Motor on/off (Run command (1 = on); clears on any error); IV 0 Setpoint / PrcSet (Speed setpoint, 0-10000 = 0-100.00 %); BV 1 Reset Alarms (Alarm reset (1 = reset)); IV 8 RPMOut (Compressor speed output, Hz); IV 7 PrcOut (Output level, x0.01 %); IV 12 Power In (filtered) (Input power, W); BV 15 Internal Stop (Internal stop alarm); BV 10 Rotor Blocked (Rotor blocked alarm).

How do I enable BMS control of the OJ Electronics OJ-DC compressor drive?

BACnet MS/TP must be enabled (OJ PC tool or Modbus coils); then BV 0 starts and stops the compressor.

How do I check these points on the real OJ-DC compressor drive?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More OJ Electronics BACnet points lists

Source: OJ DC BACnet MS/TP protocol (application note) · 67958B · rev. 05/25. Object names, instances and units are reproduced as published; descriptions are our own.