 "manufacturer": "OJ Electronics",
 "manufacturer_slug": "oj-electronics",
 "model": "OJ Air Plus AHU controller (EXcon-Plus), SW 1.09",
 "model_slug": "oj-air-plus-ahu-controller",
 "aliases": [
  "OJ Air Plus",
  "OJ-Air Plus",
  "AirPlus",
  "EXcon-Plus",
  "EXcon Plus",
  "670203"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "OJ Electronics OJ Air Plus air handling unit controllers (device name EXcon-Plus) with software 1.09.",
 "summary": "The OJ Air Plus is an air handling unit controller with a native BACnet server. Its EDE file lists close to a thousand objects: Analog Inputs for measured temperatures, pressures, flows and outputs; Analog Values for setpoints and configuration; Binary Inputs for status and alarm flags; Binary Values for function switches and BMS commands. Many objects only matter when the matching function or module is fitted.",
 "bacnet_transport": [],
 "firmware": "SW 1.09",
 "default_device_instance": 15530,
 "access_inferred": true,
 "notes": [
  "Built from the EDE export (B.I.G.-EU layout 2.3, 19/02/2026). The EDE has no read/write column, so access is inferred: AV/BV writable, AI/BI read-only.",
  "Object names are the controller's long texts, cut off at about 63 characters as in the EDE; the description holds the short internal tag.",
  "Many values are scaled: names marked [1/100C] or [1/100%] carry hundredths (2150 = 21.50).",
  "Units come from the EDE unit codes; a few names state a different unit in brackets (for example power named [kW] with the code for watts).",
  "Four object names contain a semicolon in the EDE (BI 173, 283, 284, 297); they are kept whole.",
  "The EDE does not say which BACnet transport the controller uses; check it on site."
 ],
 "source": {
  "title": "OJ Air Plus EDE file 670203_EDE_AirPlus_SW109",
  "doc_number": "670203",
  "revision_date": "19/02/2026",
  "url": "https://ojelectronics.com/controllers-sensors/wp-admin/admin-ajax.php?action=productdownload&media_id=70102341&filename=670203_EDE_AirPlus_SW109.csv"
 },
 "integration": {
  "summary": "Read the unit state from AI 0 and BI 0, the temperatures and flows from the AI block, and the two alarm relays (BI 30 A-alarm, BI 31 B-alarm). BMS run modes go through AV 108, which only works after the physical operation input is activated; BV 0 resets alarms.",
  "minimum_points": [
   {
    "ref": "AV 108",
    "name": "BMS-modes only avalable after activation of pysical input 'Oper",
    "why": "BMS run mode; needs the physical operation input"
   },
   {
    "ref": "AV 134",
    "name": "TempSet for actual RegMode [1/100C]",
    "why": "Temperature setpoint for the active control mode"
   },
   {
    "ref": "BV 0",
    "name": "Alarm reset signal (AutoReturn to zero)",
    "why": "Alarm reset (returns to 0 by itself)"
   },
   {
    "ref": "AI 0",
    "name": "Actual operating mode 000-099 Unit stopped 100-199: Unit in low",
    "why": "Actual operating mode code"
   },
   {
    "ref": "BI 0",
    "name": "Operation ON/OFF",
    "why": "Operation on/off status"
   },
   {
    "ref": "AI 16",
    "name": "Current SupplyTemp [1/100C]",
    "why": "Supply air temperature, 1/100 °C"
   },
   {
    "ref": "AI 5",
    "name": "Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u",
    "why": "Actual supply airflow"
   },
   {
    "ref": "BI 30",
    "name": "Alarm relay 1 (A-alarm)",
    "why": "A-alarm relay (critical alarm)"
   },
   {
    "ref": "BI 31",
    "name": "Alarm relay 2 (B-alarm)",
    "why": "B-alarm relay (non-critical alarm)"
   }
  ],
  "enable": "AV 108 sets the BMS run mode, but only after the physical operation input is activated (per the object name).",
  "heartbeat": null,
  "remote_sensors": "Outdoor and room temperature can come from the BMS: write AV 102 / AV 103 and switch them in with BV 15 / BV 16.",
  "setup": [
   "The EDE gives device instance 15530 and device name EXcon-Plus."
  ],
  "gotchas": [
   "Most temperatures and percentages are in hundredths.",
   "Object names are long texts cut at about 63 characters; map by type and instance, not by name.",
   "Outdoor and room temperature from the BMS (AV 102, AV 103) are only used when BV 15 / BV 16 activate them."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Actual operating mode 000-099 Unit stopped 100-199: Unit in low",
   "description": "OL_Act_DriftMode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "SA DuctPressure (Calc from PressSignal) [Pa]",
   "description": "AR_SupDuctPa",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Regulator SetPoint for DuctPressReg  [Pa] SA",
   "description": "AR_SupDuctPaRgSet",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Extract DuctPressure (Calc from PressSignal) [Pa]",
   "description": "AR_ExtDuctPa",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Regulator SetPoint for DuctPressReg  [Pa] EA",
   "description": "AR_ExtDuctPaRgSet",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Actual supply flow [l/s] or [m3/h] or [CFM] (Depending on the u",
   "description": "AR_Act_SA_Flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Setpoint for supply flow controller [l/s] or [m3/h] or [CFM] (D",
   "description": "AR_SA_FlowRegSet",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Actual Extract/Exhaust flow [l/s] or [m3/h] or [CFM] (Depending",
   "description": "AR_Act_EA_Flow",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Setpoint for Extract/Exhaust flow controller [l/s] or [m3/h]or",
   "description": "AR_EA_FlowRegSet",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "AR_CO2 Sensor ppm Measure [ppm]",
   "description": "AR_CO2_ppmMeas",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Signal from Fanoptimizer Input SA",
   "description": "FANOpt_SA_Ctrl_Vin",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Signal from Fanoptimizer Input EA",
   "description": "FANOpt_EA_Ctrl_Vin",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "FAN-Opt Supply Signal [1/100%]",
   "description": "FANOpt_SAPrc_An_In",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "FAN-Opt Extract Signal [1/100%]",
   "description": "FANOpt_EAPrc_An_In",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Supply Max Flow [l/s], Aggregate max",
   "description": "AR_SA_MaxFlow_AggSize",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Extract/Exhaust Max Flow [l/s], Aggregate",
   "description": "AR_EA_MaxFlow_AggSize",
   "units": "l/s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Current SupplyTemp [1/100C]",
   "description": "ATMP_SupTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Regulator SupplyTemp-Set [1/100C]",
   "description": "ATMP_SupTempRegSet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Actual extract temperature [1/100°C]",
   "description": "ATMP_ExtTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Regulator ExtractTemp-Set [1/100C]",
   "description": "ATMP_ExtTempRegSet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Actual outdoor temperature [1/100°C]",
   "description": "ATMP_Used_OATemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Current RoomTemp (External Sens)  [1/100C]",
   "description": "ATMP_RoomTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Current ExhaustTemp [1/100C]",
   "description": "ATMP_ExhaustTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "TempMeas for actual RegMode [1/100C]",
   "description": "TR_TempRegMeas",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "RegVal for actual RegMode [1/100C]",
   "description": "TR_TempRegVal",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Fluid EXC Temp after EXC [1/100C]",
   "description": "BattEXC_Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Current HeatWaterBatt 1 Temp [1/100C]",
   "description": "ATMP_HT1_CoilRT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Outdoor Filter Pressure (Avr-Meas) [Pa]",
   "description": "FM_SF_OA_ActFiltPress",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Extract Filter Pressure (Avr-Meas)  [Pa]",
   "description": "FM_SF_EA_ActFiltPress",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Supply Motor signal percent",
   "description": "AR_SA_MotorSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Extract/Exhaust Motor signal percent",
   "description": "AR_EA_MotorSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "OA Filter pressure for alarm-limit at actual flow [Pa]",
   "description": "Filt_AlrPa_OA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "EA Filter pressure for alarm-limit at actual flow [Pa]",
   "description": "Filt_AlrPa_EA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "FlowOutTempComp PercentOut [1/100%]",
   "description": "AR_FlwTmpCmpOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Sum/Wint-TempComp actual Setpoint offset [1/100C ]",
   "description": "SWTC_ActSetOfs",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "EXC-Regulator HeatPower [1/100 %]",
   "description": "HeatEXCPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "AfterHeat1-Regulator Power [1/100 %]",
   "description": "Heat1Power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Cool Regulator Power [1/100 %], Output",
   "description": "CL_Cool_Power_AO",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Actual Cool-Power [1/100%]",
   "description": "CL_Cool_ActPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Cool Force Flow Power [1/100 %]",
   "description": "CL_Cool_FlwForcePw",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Cool Alarm-1 VDC-Signal [1/100 %]",
   "description": "CL_Cool_Vin1Alarm",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Cool Alarm-2 VDC-Signal [1/100 %]",
   "description": "CL_Cool_Vin2Alarm",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Cool Alarm-3 VDC-Signal [1/100 %]",
   "description": "CL_Cool_Vin3Alarm",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Cool Alarm-4 VDC-Signal [1/100 %]",
   "description": "CL_Cool_Vin4Alarm",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Actual low pressure sensor 1 [1/100 bar]",
   "description": "CL_LoPress1Bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Actual high pressure sensor 1 [1/100 bar]",
   "description": "CL_HiPress1Bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Actual low pressure sensor 2 [1/100 bar]",
   "description": "CL_LoPress2Bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Actual high pressure sensor 2 [1/100 bar]",
   "description": "CL_HiPress2Bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Extract SFP [Ws/m3 same as J/m3]",
   "description": "AR_ExtSFP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Supply SFP  [Ws/m3 same as J/m3]",
   "description": "AR_SupSFP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "RotaryEXC – motor type",
   "description": "DRHX_Type",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "RotaryEXC – software version [1/100]",
   "description": "DRHX_MOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "RotaryEXC – percentage [1/100%]",
   "description": "DRHX_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "RotaryEXC – speed output [1/10 rpm]",
   "description": "DRHX_RpmOut",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "RotaryEXC - actual output [mA]",
   "description": "DRHX_I_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "RotaryEXC – output power [W]",
   "description": "DRHX_Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "RotaryEXC – days of operation",
   "description": "DRHX_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "RotaryEXC – percentage setpoint [1/100%]",
   "description": "DRHX_PercentSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "Extension module 1 software version [1/100]",
   "description": "IO2_ID1_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "Extension module 2 software version [1/100]",
   "description": "IO2_ID2_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "Act weekday Monday..Sunday (1 = Monday)",
   "description": "RTC_WeekDay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "Stack for active alarm's 0 (0 end of stack)",
   "description": "Alr_ReleasedId",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "Stack for active alarm's 1 (0 end of stack)",
   "description": "Alr_ReleasedId01",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "Stack for active alarm's 2 (0 end of stack)",
   "description": "Alr_ReleasedId02",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "Stack for active alarm's 3 (0 end of stack)",
   "description": "Alr_ReleasedId03",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "Stack for active alarm's 4 (0 end of stack)",
   "description": "Alr_ReleasedId04",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "Stack for active alarm's 5 (0 end of stack)",
   "description": "Alr_ReleasedId05",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "Stack for active alarm's 6 (0 end of stack)",
   "description": "Alr_ReleasedId06",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "Stack for active alarm's 7 (0 end of stack)",
   "description": "Alr_ReleasedId07",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "Stack for active alarm's 8 (0 end of stack)",
   "description": "Alr_ReleasedId08",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "Stack for active alarm's 9 (0 end of stack)",
   "description": "Alr_ReleasedId09",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "Stack for active alarm's 10 (0 end of stack)",
   "description": "Alr_ReleasedId10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Stack for active alarm's 11 (0 end of stack)",
   "description": "Alr_ReleasedId11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "Stack for active alarm's 12 (0 end of stack)",
   "description": "Alr_ReleasedId12",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "Stack for active alarm's 13 (0 end of stack)",
   "description": "Alr_ReleasedId13",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "Stack for active alarm's 14 (0 end of stack)",
   "description": "Alr_ReleasedId14",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "Stack for active alarm's 15 (0 end of stack)",
   "description": "Alr_ReleasedId15",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "Master Software Ver [1/100]",
   "description": "MasterSW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "Display Software Ver [1/100]",
   "description": "DisplaySW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "Additional TempSensor1  [1/100C]",
   "description": "ATMP_AddOnTSensor1",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Additional TempSensor2  [1/100C}",
   "description": "ATMP_AddOnTSensor2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Additional TempSensor3  [1/100C]",
   "description": "ATMP_AddOnTSensor3",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Additional TempSensor4  [1/100C]",
   "description": "ATMP_AddOnTSensor4",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "AfterHeat2-Regulator Power [1/100 %]",
   "description": "HW_EL_HT2_Power",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "Heatpower Preheater  [1/100%]",
   "description": "PH_HeatPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "Current Pre-HeatWaterBattTemp [1/100C] Coil/Return",
   "description": "ATMP_PH_CoilRT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "Heat exchanger efficiency [1/100%]",
   "description": "EXCActualEff",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "Voltage level, HWB1 Out2",
   "description": "HW12_VDCOut",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "Measured pressure loss over heat pump outdoor coil.",
   "description": "HP_CoilPaMeas",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "ModCO2, State 1-L/H, 2-H/L,0-nothing",
   "description": "MODREC_AltFlowAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "Recirce closedown timer",
   "description": "UPS_RecClosTimer",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "CombiBattery VDC-Signal out for AfterHeat/Cool [1/1000 V]",
   "description": "CombiVDC_Out",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "CombiBattery Power for Heat [1/100%]",
   "description": "CombiHeatPow",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 115,
   "name": "CombiBattery Power for Cool [1/100%]",
   "description": "CombiCoolPow",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "Current external OutDoorTemp [1/100C]",
   "description": "ATMP_ExtOA_SensTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "Temperature after pre-heating coil [1/100 °C]",
   "description": "ATMP_PHeatTempAir",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "Cold water supply temperature for cooling coil [1/100 °C]",
   "description": "ATMP_CW1_Inlet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "Damper position outdoor damper [1/100 %]",
   "description": "AR_REC_FreshAirDis",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "Damper position recirculation [1/100 %]",
   "description": "AR_REC_DampPrcDis",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "Output voltage cooling valve2 (only combi coil)",
   "description": "CL_CoolVDC_Out2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "OA filter  restime before filtershift alarm activated",
   "description": "FM_SF_OA_Timer_Rest_d",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "EA filter  restime before filtershift alarm activated",
   "description": "FM_SF_EA_Timer_Rest_d",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "Combi HT-WaterBattTemp [1/100C] Coil/Return",
   "description": "ATMP_CMB_CoilRT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "Rel. Humidity Extract air",
   "description": "AR_RelHumExtract",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "Rel. Humidity Supply air",
   "description": "AR_RelHumSupply",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "Rel. Humidity Mixed air",
   "description": "AR_RelHumMixed",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "Extract Filter2 Pressure (Avr-Meas)  [Pa]",
   "description": "FM_SF_EA2_ActFiltPress",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "Supply Filter Pressure (Avr-Meas)  [Pa]",
   "description": "FM_SF_SA_ActFiltPress",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "Number of Detected ZoneModules",
   "description": "ZM_Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "ZoneControl Operation Mode",
   "description": "ZM_OpMode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "ZoneModule 1 - Status",
   "description": "ZM1_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "ZoneModule 1 - VAV Supply 1 Actuator Setpoint",
   "description": "ZM1_Sup1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "ZoneModule 1 - VAV Supply 1 Actuator Flow",
   "description": "ZM1_Sup1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "ZoneModule 1 - VAV Supply 2 Actuator Setpoint",
   "description": "ZM1_Sup2Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 138,
   "name": "ZoneModule 1 - VAV Supply 2 Actuator Flow",
   "description": "ZM1_Sup2Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "ZoneModule 1 - VAV Extract 1 Actuator Setpoint",
   "description": "ZM1_Ext1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "ZoneModule 1 - VAV Extract 1 Actuator Flow",
   "description": "ZM1_Ext1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "ZoneModule 1 - VAV Heating Actuator Setpoint",
   "description": "ZM1_HeatSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 142,
   "name": "ZoneModule 1 - VAV Heating Actuator Flow",
   "description": "ZM1_HeatFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "ZoneModule 1 - VAV Cooling Actuator Setpoint",
   "description": "ZM1_CoolSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "ZoneModule 1 - VAV Cooling Actuator Flow",
   "description": "ZM1_CoolFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "ZoneModule 1 - Room Temperature Value",
   "description": "ZM1_RoomTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "ZoneModule 1 - Supply Temperature Value",
   "description": "ZM1_SupTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "ZoneModule 1 - Remote Setpoint Offset",
   "description": "ZM1_SetOffset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "ZoneModule 1 - CO2/VOC Value",
   "description": "ZM1_CO2VOC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "ZoneModule 1 - RH Value",
   "description": "ZM1_RH",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "ZoneModule 2 - Status",
   "description": "ZM2_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "ZoneModule 2 - VAV Supply 1 Actuator Setpoint",
   "description": "ZM2_Sup1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "ZoneModule 2 - VAV Supply 1 Actuator Flow",
   "description": "ZM2_Sup1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "ZoneModule 2 - VAV Supply 2 Actuator Setpoint",
   "description": "ZM2_Sup2Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "ZoneModule 2 - VAV Supply 2 Actuator Flow",
   "description": "ZM2_Sup2Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 155,
   "name": "ZoneModule 2 - VAV Extract 1 Actuator Setpoint",
   "description": "ZM2_Ext1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 156,
   "name": "ZoneModule 2 - VAV Extract 1 Actuator Flow",
   "description": "ZM2_Ext1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 157,
   "name": "ZoneModule 2 - VAV Heating Actuator Setpoint",
   "description": "ZM2_HeatSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "ZoneModule 2 - VAV Heating Actuator Flow",
   "description": "ZM2_HeatFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "ZoneModule 2 - VAV Cooling Actuator Setpoint",
   "description": "ZM2_CoolSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 160,
   "name": "ZoneModule 2 - VAV Cooling Actuator Flow",
   "description": "ZM2_CoolFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 161,
   "name": "ZoneModule 2 - Room Temperature Value",
   "description": "ZM2_RoomTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 162,
   "name": "ZoneModule 2 - Supply Temperature Value",
   "description": "ZM2_SupTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 163,
   "name": "ZoneModule 2 - Remote Setpoint Offset",
   "description": "ZM2_SetOffset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "ZoneModule 2 - CO2/VOC Value",
   "description": "ZM2_CO2VOC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 165,
   "name": "ZoneModule 2 - RH Value",
   "description": "ZM2_RH",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 166,
   "name": "ZoneModule 3 - Status",
   "description": "ZM3_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 167,
   "name": "ZoneModule 3 - VAV Supply 1 Actuator Setpoint",
   "description": "ZM3_Sup1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "ZoneModule 3 - VAV Supply 1 Actuator Flow",
   "description": "ZM3_Sup1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "ZoneModule 3 - VAV Supply 2 Actuator Setpoint",
   "description": "ZM3_Sup2Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 170,
   "name": "ZoneModule 3 - VAV Supply 2 Actuator Flow",
   "description": "ZM3_Sup2Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 171,
   "name": "ZoneModule 3 - VAV Extract 1 Actuator Setpoint",
   "description": "ZM3_Ext1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 172,
   "name": "ZoneModule 3 - VAV Extract 1 Actuator Flow",
   "description": "ZM3_Ext1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 173,
   "name": "ZoneModule 3 - VAV Heating Actuator Setpoint",
   "description": "ZM3_HeatSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "ZoneModule 3 - VAV Heating Actuator Flow",
   "description": "ZM3_HeatFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 175,
   "name": "ZoneModule 3 - VAV Cooling Actuator Setpoint",
   "description": "ZM3_CoolSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 176,
   "name": "ZoneModule 3 - VAV Cooling Actuator Flow",
   "description": "ZM3_CoolFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 177,
   "name": "ZoneModule 3 - Room Temperature Value",
   "description": "ZM3_RoomTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 178,
   "name": "ZoneModule 3 - Supply Temperature Value",
   "description": "ZM3_SupTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 179,
   "name": "ZoneModule 3 - Remote Setpoint Offset",
   "description": "ZM3_SetOffset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "ZoneModule 3 - CO2/VOC Value",
   "description": "ZM3_CO2VOC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "ZoneModule 3 - RH Value",
   "description": "ZM3_RH",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 182,
   "name": "ZoneModule 4 - Status",
   "description": "ZM4_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 183,
   "name": "ZoneModule 4 - VAV Supply 1 Actuator Setpoint",
   "description": "ZM4_Sup1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 184,
   "name": "ZoneModule 4 - VAV Supply 1 Actuator Flow",
   "description": "ZM4_Sup1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 185,
   "name": "ZoneModule 4 - VAV Supply 2 Actuator Setpoint",
   "description": "ZM4_Sup2Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 186,
   "name": "ZoneModule 4 - VAV Supply 2 Actuator Flow",
   "description": "ZM4_Sup2Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 187,
   "name": "ZoneModule 4 - VAV Extract 1 Actuator Setpoint",
   "description": "ZM4_Ext1Set",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 188,
   "name": "ZoneModule 4 - VAV Extract 1 Actuator Flow",
   "description": "ZM4_Ext1Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 189,
   "name": "ZoneModule 4 - VAV Heating Actuator Setpoint",
   "description": "ZM4_HeatSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "ZoneModule 4 - VAV Heating Actuator Flow",
   "description": "ZM4_HeatFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 191,
   "name": "ZoneModule 4 - VAV Cooling Actuator Setpoint",
   "description": "ZM4_CoolSet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 192,
   "name": "ZoneModule 4 - VAV Cooling Actuator Flow",
   "description": "ZM4_CoolFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "ZoneModule 4 - Room Temperature Value",
   "description": "ZM4_RoomTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 194,
   "name": "ZoneModule 4 - Supply Temperature Value",
   "description": "ZM4_SupTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 195,
   "name": "ZoneModule 4 - Remote Setpoint Offset",
   "description": "ZM4_SetOffset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 196,
   "name": "ZoneModule 4 - CO2/VOC Value",
   "description": "ZM4_CO2VOC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 197,
   "name": "ZoneModule 4 - RH Value",
   "description": "ZM4_RH",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 198,
   "name": "CVM Phase L1 to neutral (N) voltage [V]",
   "description": "CVMVoltageL1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 199,
   "name": "CVM Current L1 value [mA]",
   "description": "CVMCurrentL1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 200,
   "name": "CVM Active power L1 [W]",
   "description": "CVMActPowerL1",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 201,
   "name": "CVM Phase L2 to neutral (N) voltage [V]",
   "description": "CVMVoltageL2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 202,
   "name": "CVM Current value [mA] L2",
   "description": "CVMCurrentL2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "CVM Active power [W] L2",
   "description": "CVMActPowerL2",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "CVM Phase L3 to neutral (N) voltage [V]",
   "description": "CVMVoltageL3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "CVM Current value L3 [mA]",
   "description": "CVMCurrentL3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 206,
   "name": "CVM Active power L3 [W]",
   "description": "CVMActPowerL3",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 207,
   "name": "CVM Active power three phases [W]",
   "description": "CVMActPowerIII",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 208,
   "name": "CVM Frequency value [Hz]",
   "description": "CVMFrequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 209,
   "name": "CVM Phase-phase Voltage L1 to L2 [V]",
   "description": "CVMVoltageL1L2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "CVM Phase-phase Voltage L2 to L3 [V]",
   "description": "CVMVoltageL2L3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 211,
   "name": "CVM Phase-phase Voltage L3 to L1 [V]",
   "description": "CVMVoltageL3L1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 212,
   "name": "CCVM Cool Phase L1 to neutral (N) voltage [V]",
   "description": "CCVMVoltageL1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 213,
   "name": "CCVM Cool Current L1 value [mA]",
   "description": "CCVMCurrentL1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "CCVM Cool Active power L1 [kW]",
   "description": "CCVMActPowerL1",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 215,
   "name": "CCVM Cool Phase L2 to neutral (N) voltage [V]",
   "description": "CCVMVoltageL2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 216,
   "name": "CCVM Cool Current L2 value [mA]",
   "description": "CCVMCurrentL2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 217,
   "name": "CCVM Cool Active power L2 [kW]",
   "description": "CCVMActPowerL2",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 218,
   "name": "CCVM Cool Phase L3 to neutral (N) voltage [V]",
   "description": "CCVMVoltageL3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 219,
   "name": "CCVM Cool Current L3 value [mA]",
   "description": "CCVMCurrentL3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "CCVM Cool Active power L3 [kW]",
   "description": "CCVMActPowerL3",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 221,
   "name": "CCVM Cool Active power three phases [W] (Low Byte)",
   "description": "CCVMActPowrIII",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 222,
   "name": "CCVM Cool Frequency value [Hz]",
   "description": "CCVMFrequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 223,
   "name": "CCVM Cool Phase-phase Voltage L1 to L2 [V]",
   "description": "CCVMVoltagL1L2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 224,
   "name": "CCVM Cool Phase-phase Voltage L2 to L3 [V]",
   "description": "CCVMVoltagL2L3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 225,
   "name": "CCVM Cool Phase-phase Voltage L3 to L1 [V]",
   "description": "CCVMVoltagL3L1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 226,
   "name": "Actual used Power (kW) Elektrik Heat Battery 1",
   "description": "El_HT1_ActPower",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 227,
   "name": "Actual used Power (kW) Elektrik Heat Battery 2",
   "description": "El_HT2_ActPower",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "CVM Active energy three phases [kWh]",
   "description": "CVMActEnergIII",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 231,
   "name": "CCVM Cool Active energy three phases [kWh]",
   "description": "CCVMActEnerIII",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 232,
   "name": "Current EfficiencyTemp [1/100C]",
   "description": "ATMP_EfficiencyTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 233,
   "name": "Internal OutDoorTemp [1/100C]",
   "description": "ATMP_OA_SensTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 234,
   "name": "Current SupplyTemp2 [1/100C]",
   "description": "ATMP_SupplyTemp2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 235,
   "name": "CVM Current value L1 high byte [mA]",
   "description": "CVMCurrentL1H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 236,
   "name": "CVM Active power L1 high byte [W]",
   "description": "CVMActPowerL1H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 237,
   "name": "CVM Current value L2 high byte [mA]",
   "description": "CVMCurrentL2H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 238,
   "name": "CVM  Active power L2 high byte [W]",
   "description": "CVMActPowerL2H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 239,
   "name": "CVM  Current value L3 high byte [mA]",
   "description": "CVMCurrentL3H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 240,
   "name": "CVM  Active power L3 high byte [W]",
   "description": "CVMActPowerL3H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 241,
   "name": "CVM  Active power three phases high byte [W]",
   "description": "CVMActPoweIIIH",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 242,
   "name": "CVM  Active energy three phases high byte [Wh]",
   "description": "CVMActEnerIIIH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 243,
   "name": "CCVM Current 1 value high byte [mA]",
   "description": "CCVMCurrentL1H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "CCVM Active power  1 high byte [W]",
   "description": "CCVMActPoweL1H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 245,
   "name": "CCVM Current 2 value high byte [mA]",
   "description": "CCVMCurrentL2H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 246,
   "name": "CCVM Active power 2 high byte [W]",
   "description": "CCVMActPoweL2H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 247,
   "name": "CCVM Current 3 value high byte [mA]",
   "description": "CCVMCurrentL3H",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 248,
   "name": "CCVM Active 3 power high byte [W]",
   "description": "CCVMActPoweL3H",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 249,
   "name": "CCVM Active power three phases high byte [W]",
   "description": "CCVMActPowIIIH",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 250,
   "name": "CCVM Active energy three phases high byte  [Wh]",
   "description": "CCVMActEnrIIIH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Supply SFPII  [Ws/m3 same as J/m3]",
   "description": "AR_SupSFPII",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Extract SFPII -2 [Ws/m3 same as J/m3]",
   "description": "AR_ExtSFPII",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 253,
   "name": "Combined SFP [Ws/m3 same as J/m3] High",
   "description": "AHU_FullSFPHigh",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "Combined SFP [Ws/m3 same as J/m3] Low",
   "description": "AHU_FullSFPLow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 256,
   "name": "Actual % rel. Huminity Mixed air",
   "description": "Humid_ActRHMix",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 263,
   "name": "Rel. Humidity Outdoor air",
   "description": "AR_RelHumOutdoor",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 264,
   "name": "Rel. Humidity Exhaust air",
   "description": "AR_RelHumExhaust",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 265,
   "name": "Current Temperature OutdoorTempSensor 6040 (External Sens) [1/1",
   "description": "TTH_ID5_Temp_Average",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 266,
   "name": "Average Outdoorflow-pressure [Pa]",
   "description": "Filt_DynFlowAvr_SA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 267,
   "name": "Average Extract/Exhaustflow-pressure [Pa]",
   "description": "Filt_DynFlowAvr_EA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 268,
   "name": "Average OA-Filter-pressure [Pa] DYNAMICMODE",
   "description": "Filt_AlrLimDynPa_OA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 269,
   "name": "Average EA-Filter-pressure [Pa] DYNAMICMODE",
   "description": "Filt_AlrLimDynPa_EA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 270,
   "name": "Current air temperature just before the outdoor coil of the hea",
   "description": "ATMP_HP_OutdCoilTmp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 271,
   "name": "Average SA-Filter-pressure [Pa] DYNAMICMODE",
   "description": "Filt_AlrLimDynPa_SA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 272,
   "name": "Average EA2-Filter-pressure [Pa] DYNAMICMODE",
   "description": "Filt_AlrLimDynPa_EA2",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 273,
   "name": "SummerNight Time with Heat Demand [sec]",
   "description": "SNC_Heat_On_Time",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 274,
   "name": "Timer for DX-Cool RE-1 ON-Periode [sec]",
   "description": "DX_OnTimerRE1",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 275,
   "name": "Timer for DX-Cool RE-2 ON-Periode [sec]",
   "description": "DX_OnTimerRE2",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 276,
   "name": "Timer for DX-Cool RE-3 ON-Periode [sec]",
   "description": "DX_OnTimerRE3",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 277,
   "name": "Timer for DX-Cool RE-4 ON-Periode [sec]",
   "description": "DX_OnTimerRE4",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 278,
   "name": "Counter for DX-Cool RE-1 starts per hour",
   "description": "DX_RestartCnt1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 279,
   "name": "Current Heat2 WaterBatt Temp [1/100C] Coil/Return",
   "description": "ATMP_HT2_CoilRT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 280,
   "name": "Counter for DX-Cool RE-3 starts per hour",
   "description": "DX_RestartCnt3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 281,
   "name": "Counter for DX-Cool RE-4 starts per hour",
   "description": "DX_RestartCnt4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 282,
   "name": "Timer for DX-Cool K1 Restart-Periode",
   "description": "DX_RestartTim1",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 283,
   "name": "Timer for DX-Cool K2 Restart-Periode",
   "description": "DX_RestartTim2",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 284,
   "name": "Timer for DX-Cool K3 Restart-Periode",
   "description": "DX_RestartTim3",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 285,
   "name": "Timer for DX-Cool K14Restart-Periode",
   "description": "DX_RestartTim4",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 286,
   "name": "Filter actual alarmstatus for OA-filter [1/100%]",
   "description": "Filt_PrcStat_OA",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 287,
   "name": "Filter actual alarmstatus for EA-filter [1/100%]",
   "description": "Filt_PrcStat_EA",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 288,
   "name": "OA Filter pressure for new-filter at actual flow [Pa]",
   "description": "Filt_TabValPa_OA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "EA Filter pressure for new-filter at actual flow [Pa]",
   "description": "Filt_TabValPa_EA",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "Condenser Valve Power",
   "description": "ROHCondPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 291,
   "name": "Voltage level, to condenser valve",
   "description": "ROHCondOutVDC",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 292,
   "name": "Shunt Valve Power",
   "description": "ROHShuntPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 293,
   "name": "Voltage level, to shunt valve",
   "description": "ROHShuntOutVDC",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 294,
   "name": "Output to SteamHuminifier [1/1000 V]",
   "description": "Humid_OutVDC",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 295,
   "name": "Timer delayed heat 2",
   "description": "Ht2DelayTimer",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 296,
   "name": "Average press  Rotary EXC Flow Measure, Extract channel",
   "description": "REXCPressAvg",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 297,
   "name": "HeatPump power used when heating is demanded. Otherwise CoolPow",
   "description": "HP_HeatPower",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 298,
   "name": "Supply air fan 2 Type",
   "description": "SA2_Slave_Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "Supply air fan 2 Software Ver [1/100]",
   "description": "SA2_Slave_MOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "Supply air fan 2 Boot Software / HW Ver [1/100]",
   "description": "SA2_Slave_AOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "Supply air fan 2 procent output  [1/100%]",
   "description": "SA2_Slave_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "Supply air fan 2 actual RPM  [RPM]",
   "description": "SA2_Slave_RPM_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 303,
   "name": "Supply air fan 2 actual current output [1/100mA]",
   "description": "SA2_Slave_I_Out",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 304,
   "name": "Supply air fan 2 actual power input  [Watt]",
   "description": "SA2_Slave_Power_In",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 305,
   "name": "Supply air fan 2 actual running time [minutes]",
   "description": "SA2_Slave_DriftMinute",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 306,
   "name": "Supply air fan 2 actual running time [days]",
   "description": "SA2_Slave_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 307,
   "name": "Supply air fan 2 Percent to Fan",
   "description": "SA2_Slave_PercentSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 308,
   "name": "Extract air fan 2 Type",
   "description": "EA2_Slave_Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 309,
   "name": "Extract air fan 2 Software Ver [1/100]",
   "description": "EA2_Slave_MOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 310,
   "name": "Extract air fan 2 Boot Software / HW Ver [1/100]",
   "description": "EA2_Slave_AOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 311,
   "name": "Extract air fan 2 procent output  [1/100%]",
   "description": "EA2_Slave_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 312,
   "name": "Extract air fan 2 actual RPM  [RPM]",
   "description": "EA2_Slave_RPM_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 313,
   "name": "Extract air fan 2 actual current output [1/100mA]",
   "description": "EA2_Slave_I_Out",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 314,
   "name": "Extract air fan 2 actual power input  [Watt]",
   "description": "EA2_Slave_Power_In",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 315,
   "name": "Extract air fan 2 actual running time [minutes]",
   "description": "EA2_Slave_DriftMinute",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 316,
   "name": "Extract air fan 2 actual running time [days]",
   "description": "EA2_Slave_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 317,
   "name": "Extract air fan 2 Percent to Fan",
   "description": "EA2_Slave_PercentSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 318,
   "name": "Supply air fan Type",
   "description": "SA_Master_Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 319,
   "name": "Supply air fan Software Ver [1/100]",
   "description": "SA_Master_MOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 320,
   "name": "Supply air fan Boot Software Ver [1/100]",
   "description": "SA_Master_AOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 321,
   "name": "Supply air fan procent ouput  [1/100%]",
   "description": "SA_Master_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 322,
   "name": "Supply air fan actual RPM  [RPM]",
   "description": "SA_Master_RPM_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 323,
   "name": "Supply air fan actual current output [1/100mA]",
   "description": "SA_Master_I_Out",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 324,
   "name": "Supply air fan actual running time [minutes]",
   "description": "SA_Master_DriftMinute",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 325,
   "name": "Supply air fan actual running time [days]",
   "description": "SA_Master_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 326,
   "name": "Supply air fan Percent to Fan",
   "description": "SA_Master_PercentSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 327,
   "name": "Extract  air fan Boot Software Ver [1/100]",
   "description": "EA_Master_AOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 328,
   "name": "Extract  air fan procent ouput  [1/100%]",
   "description": "EA_Master_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 329,
   "name": "Extract  air fan actual RPM  [RPM]",
   "description": "EA_Master_RPM_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 330,
   "name": "Extract  air fan actual current output [1/100mA]",
   "description": "EA_Master_I_Out",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 331,
   "name": "Extract  air fan actual running time [minutes]",
   "description": "EA_Master_DriftMinute",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 332,
   "name": "Extract  air fan actual running time [days]",
   "description": "EA_Master_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 333,
   "name": "Extract air fan Percent to Fan",
   "description": "EA_Master_PercentSet",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 334,
   "name": "Extract  air fan Type",
   "description": "EA_Master_Size",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 335,
   "name": "Extract  air fan Software Ver [1/100]",
   "description": "EA_Master_MOC_SW_Ver",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 336,
   "name": "SA filter  restime before filtershift alarm activated",
   "description": "FM_SF_SA_Timer_Rest_d",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 337,
   "name": "EA filter 2 restime before filtershift alarm activated",
   "description": "FM_SF_EA2_Timer_Rest_d",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 338,
   "name": "Extract air temperature after Heatpump value  [1/100C]",
   "description": "ATMP_HP_ExtAirTemp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 339,
   "name": "Daikin:Suction air temperature",
   "description": "DaikSucTmpSet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 341,
   "name": "Drives Compressor Drive Type",
   "description": "DC_Compressor_DriveType",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 342,
   "name": "Drives Compressor AOC SW version",
   "description": "DC_Compressor_AOCSWVer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 343,
   "name": "Drives Compressor MOC SW version",
   "description": "DC_Compressor_MOCSWVer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 344,
   "name": "Drives Compressor PrcOut",
   "description": "DC_Compressor_PercentOut",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 345,
   "name": "Drives Compressor RPMOut",
   "description": "DC_Compressor_RPM_Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 346,
   "name": "Drives Compressor Power In (filtered)",
   "description": "DC_Compressor_Power_In",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 347,
   "name": "Drives Compressor Operation Day",
   "description": "DC_Compressor_DriftDays",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 348,
   "name": "Cross-EXC pressure average, depent on flow",
   "description": "EXC_FlwAvr",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 351,
   "name": "Consumed kWh High  Note!: Values are calculated as (High byte)",
   "description": "CVMConActEner3PhkWHH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 352,
   "name": "Consumed kWh Low Note!: Values are calculated as (High byte) x",
   "description": "CVMConActEner3PhkWH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 353,
   "name": "Consumed Wh  High Note!: Values are calculated as (High byte) x",
   "description": "CVMConActEner3PhWHH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 354,
   "name": "Consumed Wh  Low Note!: Values are calculated as (High byte) x",
   "description": "CVMConActEner3PhWH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 355,
   "name": "Consumed [kWh] High. Note: Values are calculated as (High byte)",
   "description": "CCVMConActEner3PhkWHH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 356,
   "name": "Consumed [kWh] Low. Note: Values are calculated as (High byte)",
   "description": "CCVMConActEner3PhkWH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 357,
   "name": "Consumed [Wh] High. Note: Values are calculated as (High byte)",
   "description": "CCVMConActEner3PhWHH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 358,
   "name": "Consumed [Wh] Low. Note: Values are calculated as (High byte) x",
   "description": "CCVMConActEner3PhWH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 365,
   "name": "Supply air fan actual power input  [Watt]",
   "description": "SA_Master_Power_In",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 366,
   "name": "Extract  air fan actual power input  [Watt]",
   "description": "EA_Master_Power_In",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 390,
   "name": "Display temperature, not in regulation PH Inlet",
   "description": "ATMP_PH_Inlet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 391,
   "name": "Display temperature, not in regulation HT1 Inlet",
   "description": "ATMP_HT1_Inlet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 392,
   "name": "Display temperature, not in regulation HT2 Inlet",
   "description": "ATMP_HT2_Inlet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 393,
   "name": "Display temperature, not in regulation Cmb HT Inlet",
   "description": "ATMP_CMB_Inlet",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 450,
   "name": "Outdoor-Damper setpoint in percent",
   "description": "BDInletSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 451,
   "name": "Outdoor-Damper actual position in percent",
   "description": "BDInletRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 452,
   "name": "Exhaust-Damper setpoint in percent",
   "description": "BDExhauSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 453,
   "name": "Exhaust-Damper actual position in percent",
   "description": "BDExhauRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 454,
   "name": "Exhaust-Backup-Damper setpoint in percent",
   "description": "BDExhBakSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 455,
   "name": "Exhaust-Backup-Damper actual position in percent",
   "description": "BDExhBakRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 456,
   "name": "Recirculation-Damper setpoint in percent",
   "description": "BDRecSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 457,
   "name": "Recirculation-Damper actual position in percent",
   "description": "BDRecRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 458,
   "name": "CrossByPass-Damper setpoint in percent",
   "description": "BDByPasSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 459,
   "name": "CrossByPass-Damper actual position in percent",
   "description": "BDByPasRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 460,
   "name": "Drying-Damper setpoint in percent",
   "description": "BDDryinSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 461,
   "name": "Drying-Damper actual position in percent",
   "description": "BDDryinRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 462,
   "name": "Supply-Damper setpoint in percent",
   "description": "BDSASetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 463,
   "name": "Supply-Damper actual position in percent",
   "description": "BDSARelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 464,
   "name": "Supply-Backup-Damper setpoint in percent",
   "description": "BDSupBakSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 465,
   "name": "Supply-Backup-Damper actual position in percent",
   "description": "BDSupBakRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 466,
   "name": "SmokeEvac-Damper setpoint in percent",
   "description": "BDSmokeSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 467,
   "name": "SmokeEvac-Damper actual position in percent",
   "description": "BDSmokeRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 468,
   "name": "SmokeByPass-Damper setpoint in percent",
   "description": "BDSMBPSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 469,
   "name": "SmokeByPass-Damper actual position in percent",
   "description": "BDSMBPRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 470,
   "name": "Heater 1 Setpoint in percent",
   "description": "BVHeat1SetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 471,
   "name": "Heater 1 Valve actual position in percent",
   "description": "BVHeat1RelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 472,
   "name": "Cooler Setpoint in percent",
   "description": "BVCoolSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 473,
   "name": "Cooler Valve actual position in percent",
   "description": "BVCoolRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 474,
   "name": "Heater 2 Setpoint in percent",
   "description": "BVHeat2SetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 475,
   "name": "Heater 2 Valve actual position in percent",
   "description": "BVHeat2RelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 476,
   "name": "FluidExchanger Setpoint in percent",
   "description": "BVFlExcSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 477,
   "name": "FluidExchanger Valve actual position in percent",
   "description": "BVFlExcRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 478,
   "name": "Preheater Setpoint in percent",
   "description": "BVPrHeatSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 479,
   "name": "Preheater Valve actual position in percent",
   "description": "BVPrHeatRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 480,
   "name": "CombiCoil Setpoint in percent",
   "description": "BVCombSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 481,
   "name": "CombiCoil Valve actual position in percent",
   "description": "BVCombRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 482,
   "name": "Opt7 Setpoint in percent",
   "description": "BVOpt7SetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 483,
   "name": "Opt7 Valve actual position in percent",
   "description": "BVOpt7RelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 484,
   "name": "Extract-Damper setpoint in percent",
   "description": "BDExtSetPrc",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 485,
   "name": "Extract-Damper actual position in percent",
   "description": "BDExtRelPos",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Manual Operation Mode [GUI]",
   "description": "OL_Manual_Modes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Fan Regulation Mode",
   "description": "AR_MtrRegMode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Offset for Sup/Ext Motor Slave and CO2 Reg [1/100%]",
   "description": "AR_MtrRegOffset",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "AR_CO2 Regulator MinFlow [l/s]",
   "description": "AR_CO2_MinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "AR_CO2 Regulator MaxFlow [l/s]",
   "description": "AR_CO2_MaxFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AR_CO2 Regulator SupFlow Offset [1/100%]",
   "description": "AR_CO2_SupFlwOffs",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AR_CO2 ppm AlarmLimet Set [ppm]",
   "description": "AR_CO2_AlrLimit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AR_CO2 Regulator P-Band [ppm]",
   "description": "AR_CO2_PB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AR_CO2 Regulator I-Time [sec]",
   "description": "AR_CO2_I_Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "FAN-Opt Supply Regulator MinFlow [l/s]",
   "description": "FANOpt_SA_MinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "FAN-Opt Supply Regulator MaxFlow [l/s]",
   "description": "FANOpt_SA_MaxFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "FAN-Opt Extract Regulator MinFlow [l/s]",
   "description": "FANOpt_EA_MinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "FAN-Opt Extract Regulator MaxFlow [l/s]",
   "description": "FANOpt_EA_MaxFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "FAN-Opt Regulator ExtFlow Offset [1/100%]",
   "description": "FANOpt_EA_FlwOffs",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Supply Motor Reg I-Time Set [Sec]",
   "description": "AR_SupMtr_I_Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Extract Motor Reg I-Time Set [Sec]",
   "description": "AR_ExtMtr_I_Time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "User Supply Motor Percent Set at Fire [%]",
   "description": "AH_SA_FlowFireSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "User Extract Motor Percent Set at Fire [%]",
   "description": "AH_EA_FlowFireSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "HiSpeed AfterRun TimeOut Set [min]",
   "description": "OL_HS_AfterRun_SetTimer",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "FlowOutTempComp PercentSet [1/100%]",
   "description": "AR_FlwTmpCmpSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "FlowOutTempComp StartTempSet [1/100C]",
   "description": "AR_FlwTmpCmpStart",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "FlowOutTempComp StopTempSet [1/100C]",
   "description": "AR_FlwTmpCmpStop",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Actual year",
   "description": "RTC_Year_Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "Actual month",
   "description": "RTC_Month_Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "Actual date",
   "description": "RTC_Date_Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Actual hour",
   "description": "RTC_Hour_Uset",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Actual minutes",
   "description": "RTC_Minute_Uset",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Actual seconds",
   "description": "RTC_Second_Uset",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Extended Drift Start Day (0-Mon..6-Sun)",
   "description": "ExtDrfStartDay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Extended Drift Start Minute (Hour*60+Min)",
   "description": "ExtDrfStartMin",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Extended Drift Stop Day (0-Mon..6-Sun)",
   "description": "ExtDrfStopDay",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Extended Drift Stop Minute (Hour*60+Min)",
   "description": "ExtDrfStopMin",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Supply LoSpeed DuctPressure Set [Pa]",
   "description": "AR_SA_DuctPaLoSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Supply MediumSpeed DuctPressure Set [Pa]",
   "description": "AR_SA_DuctPaMedSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Supply HiSpeed DuctPressure Set [Pa]",
   "description": "AR_SA_DuctPaHiSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Extract/Exhaust LoSpeed DuctPressure Set [Pa]",
   "description": "AR_EA_DuctPaLoSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Extract/Exhaust MediumSpeed DuctPressure Set [Pa]",
   "description": "AR_EA_DuctPaMedSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Extract/Exhaust HiSpeed DuctPressure Set [Pa]",
   "description": "AR_EA_DuctPaHiSet",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "User Supply Flow-LoSpeedSet [l/s]",
   "description": "AR_SA_LoSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "User Supply Flow-MedSpeedSet [l/s]",
   "description": "AR_SA_MedSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "User Supply Flow-HiSpeedSet [l/s]",
   "description": "AR_SA_HiSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "User Extract/Exhaust Flow-LoSpeedSet [l/s]",
   "description": "AR_EA_LoSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "User Extract/Exhaust Flow-MedSpeedSet [l/s]",
   "description": "AR_EA_MedSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "User Extract/Exhaust Flow-HiSpeedSet [l/s]",
   "description": "AR_EA_HiSpeedFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Supply Motor Lowspeed [1/100%], FFS",
   "description": "AR_SA_FixLoPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Supply Motor Mediumspeed [1/100%], FFS",
   "description": "AR_SA_FixMedPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Supply Motor Highspeed [1/100%], FFS",
   "description": "AR_SA_FixHiPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Extract/Exhaust Motor Lowspeed [1/100%], FFS",
   "description": "AR_EA_FixLoPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Extract/Exhaust Motor Mediumspeed [1/100%], FFS",
   "description": "AR_EA_FixMedPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Extract/Exhaust Motor Highspeed [1/100%], FFS",
   "description": "AR_EA_FixHiPrcSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "AR_CO2 Regulator User SetPoint for Lo timer Periode (HI AR_CO2",
   "description": "AR_CO2_UsetLP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "AR_CO2 Regulator User SetPoint for Medium timer Periode(Med AR_",
   "description": "AR_CO2_UsetMP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "AR_CO2 Regulator User SetPoint for Hi timer Periode(LO AR_CO2 V",
   "description": "AR_CO2_UsetHP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Extract/Exhaust Min Flow for DuctReg [l/s]",
   "description": "AR_EA_DuctMinFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Extract/Exhaust Max Flow for DuctReg [l/s]",
   "description": "AR_EA_DuctMaxFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Supply Min Flow for DuctReg [l/s]",
   "description": "AR_SA_DuctMinFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "Supply Max Flow for DuctReg [l/s]",
   "description": "AR_SA_DuctMaxFlowSet",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "TempDiff2 between Set/Meas Alarm Limit SA [1/100C]",
   "description": "SupTempDif2Alr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "TempDiff between Set/Meas Alarm Limit SA [1/100C]",
   "description": "SupTempDiffAlr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "P-Band for Supply TempReg heating [1/100C]",
   "description": "SupTempHeatPB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "SA I-Time for Reg on Heat2 Out [sec]",
   "description": "TR_SupTempHeat2IT",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "SA I-Time for supply tempReg Heat pump while heating [sec]",
   "description": "TR_SupTempHP_IT",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Huminifier Supply Setpoint [1/100%] RH",
   "description": "Humid_SupSet",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Current external Modbus OutDoorTemp [1/100C]",
   "description": "STMP_MBT_OutDoor",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "Current external Modbus RoomTemp [1/100C]",
   "description": "STMP_MBT_Room1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "Customer set of alarmlimit modbus outdoorsensor min",
   "description": "TR_AlrLimOA_MBT_Min",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "Customer set of alarmlimit modbus outdoorsensor max",
   "description": "TR_AlrLimOA_MBT_Max",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "Customer set of alarmlimit modbus roomsensor min",
   "description": "TR_AlrLimRoomMin",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "Customer set of alarmlimit modbus roomsensor max",
   "description": "TR_AlrLimRoomMax",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "BMS-modes only avalable after activation of pysical input 'Oper",
   "description": "OL_BMS_Ctrl_Modes",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "Temp-Regulationmode0-Sup, 1-Ext, 2-Room, 3-Sup/Ext -Diff",
   "description": "AHU_TempRegMode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "TempSet for actual RegMode [1/100C]",
   "description": "TR_TempRegSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "Min Allowed SupplyTemp [1/100C]",
   "description": "STMP_SupTempMinSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "Max Allowed SupplyTemp [1/100C]",
   "description": "STMP_SupTempMaxSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "TempDiff Set between Extract/Supply TempRegMode = 3",
   "description": "STMP_SupTempDiffSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "SA I-Time for Reg on CoolOut [sec]",
   "description": "TR_SupTempCool_IT",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "SA I-Time for Reg on EXC Out [sec]",
   "description": "TR_SupTempEXC_IT",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "SA I-Time for Reg on Heat Out [sec]",
   "description": "TR_SupTempHeat_IT",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "SA I-Time for SupTempReg Flow DownReg Out [sec]",
   "description": "TR_SupTempDnRegIt",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "TempDiff between Set/Meas Alarm Limit EA [1/100C]",
   "description": "STMP_ExtTempDiffAlr",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "P-Band for Extract TempReg heating [1/100C]",
   "description": "ExtTempHeatPB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "EA I-Time for Reg on CoolOut [sec]",
   "description": "TR_ExtTempCool_It",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "EA I-Time for Reg on EXC Out [sec]",
   "description": "TR_ExtTempEXC_It",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "EA I-Time for Reg on Heat Out [sec]",
   "description": "TR_ExtTempHeat_It",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "EA I-Time for ExtTempReg Flow DownReg Out [sec]",
   "description": "TR_ExtTempDnRegIt",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "Sum/Wint-TempComp Winter Lo OutDoor TempSet [1/100C]",
   "description": "SWTC_WintX1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "Sum/Wint-TempComp Winter Hi OutDoor TempSet [1/100C]",
   "description": "SWTC_WintX2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "Sum/Wint-TempComp Summer Lo OutDoor TempSet [1/100C]",
   "description": "SWTC_SumX1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "Sum/Wint-TempComp Summer Hi OutDoor TempSet [1/100C]",
   "description": "SWTC_SumX2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "Sum/Wint-TempComp Winter compensation [1/100C]",
   "description": "SWTCWinComVal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "Sum/Wint-TempComp Summer compensation [1/100C]",
   "description": "SWTCSumComVal",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "Summer/Winter Mode: 0 - 4",
   "description": "SW_Mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "OutdoorTemp for start WinterMode (SW_Mode = 1)",
   "description": "SW_OutWinterON",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "OutdoorTemp for start SummerMode (SW_Mode = 1)",
   "description": "SW_OutSummerON",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "Month for Start WinterMode (SW_Mode = 2)",
   "description": "SW_MonthWintON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "Date for Start WinterMode (SW_Mode = 2)",
   "description": "SW_DateWintON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "Month for Start SummerMode (SW_Mode = 2)",
   "description": "SW_MonthSumON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "Date for Start SummerMode (SW_Mode = 2)",
   "description": "SW_DateSumON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "StartTemp for Nightheat Function [1/100 C]",
   "description": "NH_Recirce_StartTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "StopTemp for Nightheat Function [1/100 C]",
   "description": "NH_Recirce_StopTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "SupplyTempSet for Internal FireAlr [1/100C]",
   "description": "AH_SA_Temp_InternFireAlr",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "ExtractTempSet for Internal FireAlr [1/100C]",
   "description": "AH_EA_Temp_InternFireAlr",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "Cool-FlowForce Percent Set [1/100 %]",
   "description": "CL_Cool_FlwForcePc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "Min OutDoorTemp for CoolAgg. Active",
   "description": "CL_Cool_OutTmpMin",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "Min SupplyTemp for Cool (Used for RoomReg)",
   "description": "CL_Cool_SupMinTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "SummerNight Ext/Room Temp Start [1/100C]",
   "description": "SNC_EATempStart",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "SummerNight Ext/Room Temp Stop [1/100C]",
   "description": "SNC_EA_TempStop",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 172,
   "name": "SummerNight OutDoor Temp Start [1/100C]",
   "description": "SNC_OA_TempStart",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 173,
   "name": "SummerNight SupTemp Reg Set [1/100C]",
   "description": "SNC_SA_TempSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "SummerNight StartTime [Min] 20:00 - 02-00, in server checked",
   "description": "SNC_StartTime",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "SummerNight StopTime [Min] 03:00 - 08:00, in server checked",
   "description": "SNC_StopTime",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "Min ExhaustTempSet for Cross EXC [1/100C]",
   "description": "CExcDeIceTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "P-Band for BypaasReg for Cross EXC [1/100C]",
   "description": "CExcDeIceTempP",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "Fluid EXC PumpFunc: 0 - 3",
   "description": "BattEXC_PumpFc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "Fluid EXC PumpStartTemp. Is used",
   "description": "BattEXC_PumpSt",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "Fluid EXC TempDiff Alarm Set Alarm",
   "description": "BattEXC_AlrSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "HWB1  Upstart PowerSet [1/100%]",
   "description": "HW1_UpStartPow",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "HeatWaterBatt 1  PumpFunc: 0 - 3",
   "description": "HW1_PumpFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "HeatWaterBatt 1 PumpStartTemp. Is used together with WaterPumpF",
   "description": "HW1_PmpStartTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "SetVal for HWB1 AntiFrost Reg when Agg. = Stop [1/100C]",
   "description": "HW1_FrzStopSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 185,
   "name": "SetVal for HWB1 AntiFrost Reg when Agg. = Drift [1/100C",
   "description": "HW1_FrzDriftSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 186,
   "name": "HW1 P-Band for AntiFrost Reg [1/100C]",
   "description": "HW1FreezePB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 187,
   "name": "SetVal for HWB1 AntiFrost TempAlarm [1/100C]",
   "description": "HW1_FrzAlrTpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "CoolWater PumpFunc: 0 - 3",
   "description": "CL_CW_PumpFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 189,
   "name": "CoolWaterBatt PumpStartTemp. Is used together with WaterPumpFun",
   "description": "CL_CW_PmpStartTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "Filter Pressure Alr Limit for OA-Filter (static mode)",
   "description": "Filt_StatAlr_OA",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "Filter Pressure Alr Limit for EA-Filter (static mode)",
   "description": "Filt_StatAlr_EA",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "Filter Pressure Alr Limit for OA-Filter (dynamic mode)",
   "description": "Filt_DynAlrSetPrc_OA",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "Filter Pressure Alr Limit for EA-Filter (dynamic mode)",
   "description": "Filt_DynAlrSetPrc_EA",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "Alarm Mail Config: 0 - Mail are not send 1 - Mail on A-Alarm 2",
   "description": "Alr_MailSetup",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 195,
   "name": "UserRE Function: 0 B-Alarm 1 Lo Speed indicator 2 Hi Speed indi",
   "description": "AHU_UserAlr_RE_Func",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 196,
   "name": "HWB2 Upstart PowerSet [1/100%]",
   "description": "HW2UpStartPow",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "HWB 2 PumpFunc: 0 - 3",
   "description": "HW2PumpFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "HWB 2 PumpFunc start Temperature",
   "description": "HW2PmpStartTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "SetVal for HWB2 AntiFrost Reg when Agg. = Stop [1/100C]",
   "description": "HW2FrzStopSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "SetVal for HWB2 AntiFrost Reg when Agg. = Drift [1/100C]",
   "description": "HW2FrzDriftSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "HW2 P-Band for AntiFrost Reg [1/100C]",
   "description": "HW2FreezePB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "SetVal for HWB2 AntiFrost TempAlarm [1/100C]",
   "description": "HW2FrzAlrTpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "Setpoint Preheater",
   "description": "PH_HeatSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "PreHeater SetVal for AntiFrost TempAlarm [1/100C]",
   "description": "PH_MinAlrFrz",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "PreHeater SetVal for AntiFrost Reg when Agg. = Stop [1/100C] Pr",
   "description": "PH_StandbyTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "Preheater Heatpower Percent under startup [1/100%]",
   "description": "PH_StartPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "Pre-heating coil P-band for frost protection control [1/100°C]",
   "description": "PHeatFrzPB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "Preheat PumpStart OutDoorTemp. Is used together with",
   "description": "STMP_PHPmpStTmpH",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 209,
   "name": "SetVal for Preheat AntiFrost Reg when Agg. = Drift [1/100C] Hea",
   "description": "STMP_PHFrzDrSetH",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "Mode for  PumpFunc: 0 - 3",
   "description": "PH_PumpMode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "Min OutDoorTemp for CoolAgg. Relay 1 Active",
   "description": "DXOutTempMin1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "Min OutDoorTemp for CoolAgg. Relay 2 Active",
   "description": "DXOutTempMin2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "Min OutDoorTemp for CoolAgg. Relay 3 Active",
   "description": "DXOutTempMin3",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "Min OutDoorTemp for CoolAgg. Relay 4 Active",
   "description": "DXOutTempMin4",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 215,
   "name": "Min air temp at outdoor coil for HeatPump operate Relay1",
   "description": "STMP_HP_MinOpTemp1",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 216,
   "name": "Min air temp at outdoor coil for HeatPump operate Relay2",
   "description": "STMP_HP_MinOpTemp2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 217,
   "name": "Min air temp at outdoor coil for HeatPump operate Relay3",
   "description": "STMP_HP_MinOpTemp3",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 218,
   "name": "Min air temp at outdoor coil for HeatPump operate Relay4",
   "description": "STMP_HP_MinOpTemp4",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 219,
   "name": "Fluid EXC SetVal for AntiFrost Reg when Agg. = Stop [1/100C]",
   "description": "BattEXCFrzStop",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 220,
   "name": "Fluid EXC SetVal for AntiFrost Reg when Agg. = Drift [1/100C]",
   "description": "BattEXCFrzDrf",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "Fluid EXC P-Band for AntiFrost Reg [1/100C]",
   "description": "BattEXCFrzePB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "Fluid EXCSetVal for AntiFrost TempAlarm [1/100C]",
   "description": "BattEXCFrzASet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "Extern Signal Greenzone, Supply",
   "description": "FANOpt_SA_GZ_An_In",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 224,
   "name": "Extern Signal Greenzone, Extract",
   "description": "FANOpt_EA_GZ_An_In",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 225,
   "name": "HeatWater VDC out function(Out 12): 0->0-10V, 1->2-10V",
   "description": "HW12_VDCOutFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "Pressure percent over calibration",
   "description": "REXDeIcePerc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "Stop temperature freshair cooling",
   "description": "STMP_NO_FAirCoolBlk",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "Stop cooling over roomtemperature",
   "description": "CL_NO_CStopRTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "Heat2 limiting type 1Room, 2 Outdoor",
   "description": "Ht2LimitTyp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 230,
   "name": "Startdifference temperature",
   "description": "HT2StLimRTemp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "Stepsize limiting roomtemp",
   "description": "Ht2StLimRPer",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "DownCounter for HeatStart allowed [sec]",
   "description": "Ht2StLimOTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "Offset in % of Flow if Heat2 is on",
   "description": "Ht2FlowOffset",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 234,
   "name": "Timeset delayed Heat 2",
   "description": "HT2_SetDelayStartTime",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 235,
   "name": "Set Change Airflow Recirce",
   "description": "TR_RecFlowShift",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 236,
   "name": "Temperature for start with open damper",
   "description": "STMP_RecClosDAStart",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 237,
   "name": "Timeset for CO2 DX-Cooling-Aggregate from 0 ..100%",
   "description": "ROHRiseT100",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 238,
   "name": "SA SummerNight Motor percent Set",
   "description": "SNC_SupCoolFlw",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 239,
   "name": "EA SummerNight Motor Flow Set",
   "description": "SNC_ExtCoolFlw",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "SA SummerNight Motor Flow Set",
   "description": "SNC_SupCoolPa",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "EA SummerNight Motor Press Set",
   "description": "SNC_ExtCoolPa",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "SA SummerNight Motor Press Set",
   "description": "SNC_SupCoolPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "EA SummerNight Motor percent Set",
   "description": "SNC_ExtCoolPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "SummerNight Motor percent Set",
   "description": "SNC_SlvOffsPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 248,
   "name": "AR_CO2 Max Value Mod Rec/Rema1000 Mode",
   "description": "AR_CO2_MaxModRec",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 249,
   "name": "AR_CO2 Min Value Mod Rec/Rema1000 Mode",
   "description": "AR_CO2_MinModRec",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 250,
   "name": "Setpoint % Humidity Extract RH, Dehumidity",
   "description": "DehumSet_RH",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 257,
   "name": "Min FreshAir part in percent",
   "description": "AR_REC_MinFreshAir",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 258,
   "name": "Filter Pressure Alr Limit for SA-Filter (static mode)",
   "description": "Filt_StaAlr_SA",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 259,
   "name": "Filter Pressure Alr Limit for EA-Filter2 (static mode)",
   "description": "Filt_StaAlr_EA2",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 260,
   "name": "Filter Pressure Alr Limit for SA-Filter (dynamic mode)",
   "description": "Filt_DynAlrSetPrc_SA",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 261,
   "name": "Filter Pressure Alr Limit for EA-Filter2 (dynamic mode)",
   "description": "Filt_DynAlrSetPrc_EA2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 262,
   "name": "ZoneModule 1 - Room Temperature Setpoint",
   "description": "ZM1_RoomTmpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 263,
   "name": "ZoneModule 1 - Minimum Supply Temperature",
   "description": "ZM1_MinSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 264,
   "name": "ZoneModule 1 - Maximum Supply Temperature",
   "description": "ZM1_MaxSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 265,
   "name": "ZoneModule 1 - Room CO2 Setpoint",
   "description": "ZM1_CO2Set",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 266,
   "name": "ZoneModule 1 - Room RH Setpoint",
   "description": "ZM1_RHSet",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 267,
   "name": "ZoneModule 1 - VAV Supply PIR Min Air Flow",
   "description": "ZM1_PIRMinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 268,
   "name": "ZoneModule 2 - Room Temperature Setpoint",
   "description": "ZM2_RoomTmpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 269,
   "name": "ZoneModule 2 - Minimum Supply Temperature",
   "description": "ZM2_MinSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "ZoneModule 2 - Maximum Supply Temperature",
   "description": "ZM2_MaxSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "ZoneModule 2 - Room CO2 Setpoint",
   "description": "ZM2_CO2Set",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "ZoneModule 2 - Room RH Setpoint",
   "description": "ZM2_RHSet",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "ZoneModule 2 - VAV Supply PIR Min Air Flow",
   "description": "ZM2_PIRMinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 274,
   "name": "ZoneModule 3 - Room Temperature Setpoint",
   "description": "ZM3_RoomTmpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 275,
   "name": "ZoneModule 3 - Minimum Supply Temperature",
   "description": "ZM3_MinSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 276,
   "name": "ZoneModule 3 - Maximum Supply Temperature",
   "description": "ZM3_MaxSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 277,
   "name": "ZoneModule 3 - Room CO2 Setpoint",
   "description": "ZM3_CO2Set",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 278,
   "name": "ZoneModule 3 - Room RH Setpoint",
   "description": "ZM3_RHSet",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 279,
   "name": "ZoneModule 3 - VAV Supply PIR Min Air Flow",
   "description": "ZM3_PIRMinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 280,
   "name": "ZoneModule 4 - Room Temperature Setpoint",
   "description": "ZM4_RoomTmpSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 281,
   "name": "ZoneModule 4 - Minimum Supply Temperature",
   "description": "ZM4_MinSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 282,
   "name": "ZoneModule 4 - Maximum Supply Temperature",
   "description": "ZM4_MaxSupTemp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 283,
   "name": "ZoneModule 4 - Room CO2 Setpoint",
   "description": "ZM4_CO2Set",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 284,
   "name": "ZoneModule 4 - Room RH Setpoint",
   "description": "ZM4_RHSet",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "ZoneModule 4 - VAV Supply PIR Min Air Flow",
   "description": "ZM4_PIRMinFlow",
   "units": "l/s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "CombiHeatWaterBatt Upstart PowerSet [1/100%]",
   "description": "CombiUpStPow",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "CombiWaterBatt PumpFunc: 0 - 3",
   "description": "CombiPumpFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "CombiBatt PumpStartTemp. Is used together with WaterPumpFunc =",
   "description": "STMP_CombiPmpStTmpH",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "Combi PumpFunc=3 then pump only starts when heatingpower exceed",
   "description": "CombiPmpStPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 290,
   "name": "SetVal for CombiBatt AntiFrost Reg when Agg. = Stop [1/100C] He",
   "description": "STMP_CombFrzStopSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 291,
   "name": "SetVal for CombiBatt AntiFrost Reg when Agg. = Drift [1/100C] H",
   "description": "STMP_CombFrzDrSetH",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 292,
   "name": "Combi P-Band for AntiFrost Reg [1/100C]",
   "description": "CombiFrzPB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 293,
   "name": "SetVal for CombiBatt AntiFrost TempAlarm [1/100C]",
   "description": "STMP_CombiFrzAlHSet",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 294,
   "name": "Max % CoolPower for Dehumidity without DewPointSensor",
   "description": "DewCoolPower",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 295,
   "name": "StartTemp for Nightheat Function ROH under 5 deg  [1/100 C]",
   "description": "NH_Recirce_StartTmp2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 296,
   "name": "StopTemp for Recirc heat Function ROH under 5 deg [1/100 C]",
   "description": "NH_Recirce_StopTmp2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "SwitchTemp for Nightheat Function ROH [1/100 C]",
   "description": "NH_Recirce_SwitchTmp2",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 304,
   "name": "Mod. recirce max FreshAir part, Damper position",
   "description": "AR_REC_MaxFreshAir",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 305,
   "name": "Risetime 0..100%, in sec",
   "description": "HW1_RiseT100",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 306,
   "name": "Night lowering temperatur correction",
   "description": "STMP_NightSetBack",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 307,
   "name": "Alarmlevel in percent, if dusty",
   "description": "ALR_REXLevelPrcDus",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 308,
   "name": "Alarmlevel in percent if froozen",
   "description": "ALR_REXLevelPrcFrz",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 309,
   "name": "Fluid EXC PumpFunc=3 then pump only starts when EXCpower exceed",
   "description": "BattEXCPmpStPr",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 310,
   "name": "Cool PumpFunc=3 pump only starts when Coolpower exceeds this se",
   "description": "CL_CW_PumpStartPr",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "HWB 2 PumpFunc=3 then pump only starts when heatingpower exceed",
   "description": "HW2PmpStartPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "When PumpFunc=3 then pump only starts when heatingpower exceeds",
   "description": "HW1_PmpStartPrc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 313,
   "name": "Pressure to start deicing of cross Exc. [Pa]",
   "description": "CEXC_DeIcePress",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 314,
   "name": "Time for deicing cross exc. when pressure monitored.",
   "description": "CExcDeIceTime",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "LoPressSens-1 AlarmLimit [1/100 Bar]",
   "description": "CL_LoPress1Alr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "HiPressSens-1 AlarmLimit [1/100 Bar]",
   "description": "CL_HiPress1Alr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "LoPressSens-2 AlarmLimit [1/100 Bar]",
   "description": "CL_LoPress2Alr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 318,
   "name": "HiPressSens-2 AlarmLimit [1/100 Bar]",
   "description": "CL_HiPress2Alr",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 319,
   "name": "Heat 2 limited over this Temperatur",
   "description": "ROHOutdBlkTmp",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 320,
   "name": "AR_CO2 Regulator Fan Min % Setpoint [1/100%]",
   "description": "AR_CO2_MinPerc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "AR_CO2 Regulator Fan Max % Setpoint [1/100%]",
   "description": "AR_CO2_MaxPerc",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "Temperature Offiset Slider from Web [1/100C]",
   "description": "TR_TempRegOffset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 323,
   "name": "Drives Compressor Setpoint/PrcSet",
   "description": "DC_Compressor_PercentSet",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 324,
   "name": "IOC Digital input Heatpump Frost / Lubrication",
   "description": "IOC_DI_FP_Oil_HPT_Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "Operation ON/OFF",
   "description": "Operation",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "External stop",
   "description": "ExtStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "External HiSpeed",
   "description": "ExtHiSpeed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Extended low speed –> Active",
   "description": "ExtDrfLoSpeed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Extended high speed –> Active",
   "description": "ExtDrfHiSpeed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Power to electric heating coil reduced due to low flow",
   "description": "El_HT1_BattPowerRed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Summer night cooling is active",
   "description": "SNC_Drift",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Reset parameters for summer night cooling new calculation is in",
   "description": "SNC_Reset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Winter temperature compensation is active",
   "description": "SWTC_WintComp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Summer temperature compensation is active",
   "description": "SWTC_SumComp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Summer/winter actual status OFF –> winter operation ('0') ON",
   "description": "SW_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Recirculation status ('1' = Open damper)",
   "description": "MODREC_Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Exercising heat exchanger –> Active",
   "description": "EXC_Exercise",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Signal to cross-flow exchanger reduced (frost protection)",
   "description": "CExcIceProtect",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Supply duct pressure controller reduced to min. Flow",
   "description": "AR_SA_DuctMinFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Supply duct pressure controller increased to max. Flow",
   "description": "AR_SA_DuctMaxFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Extract/Exhaust duct pressure controller reduced to min. Flow",
   "description": "AR_EA_DuctMinFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Extract/Exhaust duct pressure controller increased to max. Flow",
   "description": "AR_EA_DuctMaxFlow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Cooling recovery –> status",
   "description": "CoolRecovery",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Circulation pump on heating coil: Frost protection –> Active",
   "description": "HW1_FrostReg",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "Circulation pump on heating coil: Pump exercising –> Active",
   "description": "HW1_PumpExer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "CoolWaterCoil PumpExercise active",
   "description": "CL_CW_PumpExer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "Signal to heating coil reduced (insufficient flow) –> Active",
   "description": "Heat_FlwDnReg",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "1-when min. supply temperature control is active.Only active wh",
   "description": "TempRegMinSup",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "1-when max. supply temperature control is active.Only active wh",
   "description": "TempRegMaxSup",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "Circulation pump on heat recovery coil: Pump exercising –> Ac",
   "description": "BattEXC_Exer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "Heating relay 1",
   "description": "Heat_RE1_DO1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "Cool Relay 1",
   "description": "Cool_RE1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Circulation pump on Fluid EXC coil: Pump –> Running",
   "description": "BattEXC_PumpRE",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "At least one active alarm",
   "description": "AlrActive",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "Alarm relay 1 (A-alarm)",
   "description": "Alr_RE1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "Alarm relay 2 (B-alarm)",
   "description": "Alr_RE2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Fire alarm signal (room sensor)",
   "description": "Alr_ExtFireSignal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Smoke Alarm Signal (Sensor in duct)",
   "description": "Alr_ExtSmokeSignal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Filter alarm for outdoor filter (pressure drop above set limit)",
   "description": "Filt_Alarm_OA",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "Filter alarm for extract filter (pressure drop above set limit)",
   "description": "Filt_Alarm_EA",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Supply temperature sensor – sensor fault",
   "description": "SupTempSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Extract temperature sensor – sensor fault",
   "description": "ExtTempSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "Outdoor temperature sensor – sensor fault",
   "description": "OutDoorSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "Room temperature sensor – sensor fault",
   "description": "RoomSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "Exhaust temperature sensor – sensor fault",
   "description": "ExhaustSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "Heating coil temperature sensor – sensor fault",
   "description": "HW1_SensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Fluid EXC temperature sensor – sensor fault",
   "description": "BattEXC_SensEr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Heating coil frost alarm",
   "description": "HW1_FrostAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "Cooling shared alarm",
   "description": "CL_Cool_SumAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "Cooling digital alarm 1 input",
   "description": "CL_Cool_DI1_Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "Cooling digital alarm 2 input",
   "description": "CL_Cool_DI2_Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "Cooling digital alarm 3 input",
   "description": "CL_Cool_DI3_Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "Cooling digital alarm 4 input",
   "description": "CL_Cool_DI4_Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "Supply motor ON/OFF",
   "description": "AR_SA_SupMotorON",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "Supply Motor Alarm",
   "description": "SupMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "Supply air fan ripple alarm",
   "description": "Alr_SA_Controler_Ripple",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 59,
   "name": "Extract/Exhaust motor ON/OFF",
   "description": "AR_EA_EA_MotorON",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 60,
   "name": "Extract Motor Alarm",
   "description": "ExtMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "Extract/exhaust air fan 2 Ripple Alarm",
   "description": "Alr_EA2_Controler_Ripple",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "Rotary heat exchanger – motor control ON/OFF",
   "description": "DRHX_DriftON",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 69,
   "name": "Rotary heat exchanger – reset signal",
   "description": "DRHX_AlrReset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 70,
   "name": "Rotary heat exchanger – rotation direction",
   "description": "DRHX_CCW_Rotation",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 71,
   "name": "Rotary heat exchanger rotation alarm",
   "description": "DRHX_RotorAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 72,
   "name": "Rotary heat exchanger low voltage alarm",
   "description": "DRHX_V_LowAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 73,
   "name": "Rotary heat exchanger hihg voltage alarm",
   "description": "DRHX_V_HighAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 74,
   "name": "Rotary heat exchanger high current",
   "description": "DRHX_I_HighAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "Rotary heat exchanger temperature alarm",
   "description": "DRHX_TempAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "Rotary heat exchanger  rotation signal",
   "description": "DRHX_RotorSignal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "Rotary heat exchanger torque overload",
   "description": "DRHX_Blocked",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 78,
   "name": "Status Brandstop input",
   "description": "ExtBrandStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 79,
   "name": "Add on sensor 1 - Sensor fault",
   "description": "AddOnTSens1Err",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 80,
   "name": "Add on sensor 2 - Sensor fault",
   "description": "AddOnTSens2Err",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 81,
   "name": "Add on sensor 3 - Sensor fault",
   "description": "AddOnTSens3Err",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 82,
   "name": "Add on sensor 4 - Sensor fault",
   "description": "AddOnTSens4Err",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 83,
   "name": "Alarm frost thermostat alarm (digital input)",
   "description": "Alr_Frost_OA_Luftsensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 84,
   "name": "Heating coil 2 - Frost control active",
   "description": "HW2FrostReg",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 85,
   "name": "Heating coil 2 - Circulation pump, pump exercising active",
   "description": "HW2PumpExer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 86,
   "name": "Heating coil 2 - Return sensor - Sensor fault",
   "description": "HW2SensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 87,
   "name": "Heating coil 2 - Frost alarm",
   "description": "HW2FrostAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 88,
   "name": "Pre-heating coil - Frost alarm",
   "description": "PH_FreezeAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 89,
   "name": "Pre-heating coil - Frost protection active",
   "description": "PH_FrostRegAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 90,
   "name": "Pre-heater Pump exercise active",
   "description": "PH_PumpExer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 91,
   "name": "Preheater - heat relay 1",
   "description": "PH_HeatRelay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 92,
   "name": "Pre-heating coil - Overheating fault",
   "description": "PH_Overheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 93,
   "name": "Pre-heating coil - Output reduction, low air volume",
   "description": "PH_PowReduce",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 94,
   "name": "Returnwater sensor error",
   "description": "PH_HWBSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 95,
   "name": "Alarm - Heat recovery efficiency below alarm limit",
   "description": "Alr_EXCEffToLow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 96,
   "name": "Alarm Atv Comm Supply",
   "description": "Alr_AtvSA_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 97,
   "name": "Alarm Atv Comm Extract",
   "description": "Alr_AtvEA_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 98,
   "name": "Alarm Atv FC Supply",
   "description": "Alr_AtvSAMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 99,
   "name": "Alarm Atv FC Extract",
   "description": "Alr_AtvEAMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "Frost alarm fluid-coupled coil (CoilEXC)",
   "description": "Alr_FrostBatt_EXC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "Contact error DeIcer El-Battery",
   "description": "Alr_DeIceContact",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "DeIcer overheatingsalarm El-Battery",
   "description": "Alr_DeIceOverheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "DeIcer power reduction alarm El-Battery",
   "description": "Alr_DeIceReduced",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "Alarm - pressure transmitter not calibrated (Ice guard rotor he",
   "description": "Alr_NoREXCali",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "Alarm - pressure transmitter not configured (Ice guard rotor he",
   "description": "Alr_SensREXNConf",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "Coolrecovery over damper active ('1' = Open damper)",
   "description": "NO_CRecovStat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 107,
   "name": "Cooling stopped by room temperature",
   "description": "NO_CStopRTStat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 108,
   "name": "Signal for the 4-way-valve in HeatPump",
   "description": "HP_CoolingActv",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "Status bit: De-icing of heatpump",
   "description": "HP_De_icingAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "Alarm - rotor heat exchanger blocked by ice (high pressure over",
   "description": "Alr_RotEXCFrozen",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 111,
   "name": "Alarm - rotor heat exchanger blocked by dirt (high pressure ove",
   "description": "Alr_RotEXCDusty",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 112,
   "name": "Flow is change heat2 active",
   "description": "HT2FlowChgAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 113,
   "name": "Status of delaytimer Heat 2",
   "description": "HT2DelayStatus",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 114,
   "name": "Limit of heat 2 is avoid",
   "description": "HT2DelLimBlkNo",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 115,
   "name": "Blocking  Heat2 in recirkulation mode = Aktivated",
   "description": "HT2RecBlkAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 116,
   "name": "Status of low flow under 100% recirculation",
   "description": "NH_LowRecFlowStat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 117,
   "name": "Closed damper running active",
   "description": "RecClosDmpAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 118,
   "name": "Max. raise-/fall-time is activated",
   "description": "HW1_RiseFallActiv",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 119,
   "name": "Supply air fan 2 high current limit",
   "description": "Alr_SA2_Contr_HiIOAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 120,
   "name": "Supply air fan 2 voltage low alarm",
   "description": "Alr_SA2_Contr_LoVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 121,
   "name": "Supply air fan 2 voltage high alarm",
   "description": "Alr_SA2_Contr_HiVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 122,
   "name": "Supply air fan 2 high current limit alarm",
   "description": "Alr_SA2_Control_I_MaxAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 123,
   "name": "Supply air fan 2 temperature alarm",
   "description": "Alr_SA2_Contr_HiTemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 124,
   "name": "Supply air fan 2 alarm for phase error",
   "description": "Alr_SA2_Contr_PhaseErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 125,
   "name": "Supply air fan 2 Direction error",
   "description": "Alr_SA2_Contr_Rot_DirErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 126,
   "name": "Supply air fan 2 alarm for blocked rotor",
   "description": "Alr_SA2_Controler_RotBlk",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 128,
   "name": "Extract/exhaust air fan 2 voltage low alarm",
   "description": "Alr_EA2_Contr_LoVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 129,
   "name": "Extract/exhaust air fan 2 voltage high alarm",
   "description": "Alr_EA2_Contr_HiVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 130,
   "name": "Extract/exhaust air fan 2 high current limit alarm",
   "description": "Alr_EA2_Control_I_MaxAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 131,
   "name": "Extract/exhaust air fan 2 temperature alarm",
   "description": "Alr_EA2_Contr_HiTemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 132,
   "name": "Extract/exhaust air fan 2 alarm for phase error",
   "description": "Alr_EA2_Contr_PhaseErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 133,
   "name": "Extract/exhaust air fan 2 Direction error",
   "description": "Alr_EA2_Contr_Rot_DirErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 134,
   "name": "Extract/exhaust air fan 2 alarm for blocked rotor",
   "description": "Alr_EA2_Controler_RotBlk",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 135,
   "name": "Alarm SA2 Controler Comm Alarm",
   "description": "Alr_SA2Controler_Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 136,
   "name": "Alarm EA2 Controler Comm Alarm",
   "description": "Alr_EA2Controler_Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 137,
   "name": "Supply air fan high current limit",
   "description": "Alr_SA_ControlerI_MaxAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 138,
   "name": "Supply air fan voltage low alarm",
   "description": "Alr_SA_Contr_LoVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 139,
   "name": "Supply air fan voltage high alarm",
   "description": "Alr_SA_Contr_HiVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 140,
   "name": "Supply air fan high current limit alarm",
   "description": "Alr_SA_Contr_HiIOAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 141,
   "name": "Supply air fan temperature alarm",
   "description": "Alr_SA_Contr_HiTemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 142,
   "name": "Supply air fan alarm for phase error",
   "description": "Alr_SA_Contr_PhaseErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 143,
   "name": "Supply air fan Direction error",
   "description": "Alr_SA_Contr_Rot_DirErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 144,
   "name": "Supply air fan alarm for blocked rotor",
   "description": "Alr_SA_Controler_RotBlk",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 145,
   "name": "Extract/exhaust air fan high current limit",
   "description": "Alr_EA_ControlerI_MaxAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 146,
   "name": "Extract/exhaust air fan voltage low alarm",
   "description": "Alr_EA_Contr_LoVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 147,
   "name": "Extract/exhaust air fan voltage high alarm",
   "description": "Alr_EA_Contr_HiVIn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 148,
   "name": "Extract/exhaust air fan high current limit alarm",
   "description": "Alr_EA_Contr_HiIOAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 149,
   "name": "Extract/exhaust air fan temperature alarm",
   "description": "Alr_EA_Contr_HiTemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 150,
   "name": "Extract/exhaust air fan alarm for phase error",
   "description": "Alr_EA_Contr_PhaseErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 151,
   "name": "Extract/exhaust air fan Direction error",
   "description": "Alr_EA_Contr_Rot_DirErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 152,
   "name": "Extract/exhaust air fan alarm for blocked rotor",
   "description": "Alr_EA_Controler_RotBlk",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 153,
   "name": "OJ-DV Supply Comm Alarm",
   "description": "Alr_SA_Controler_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 154,
   "name": "OJ-DV Extract Comm Alarm",
   "description": "Alr_EA_Controler_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 155,
   "name": "TTH-6202 communication error",
   "description": "Alr_TTH6202Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 156,
   "name": "Communication Alarm Belimo Smoke Damper",
   "description": "Alr_BDSmokeCom_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 157,
   "name": "Position Alarm Belimo Smoke Damper",
   "description": "Alr_BDSmokePos_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 158,
   "name": "Extention IO-Modul no 1 - communication error",
   "description": "Alr_Ext_Modul1_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 159,
   "name": "Extention IO-Modul no 2 - communication error",
   "description": "Alr_Ext_Modul2_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 160,
   "name": "Extention IO-Modul no 3 - communication error",
   "description": "Alr_Ext_Modul3_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 161,
   "name": "Extention IO-Modul no 4 - communication error",
   "description": "Alr_Ext_Modul4_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 162,
   "name": "Extention IO-Modul no 5 - communication error",
   "description": "Alr_Ext_Modul5_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 163,
   "name": "Extention IO-Modul no 6 - communication error",
   "description": "Alr_Ext_Modul6_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 164,
   "name": "Extention IO-Modul no 7 - communication error",
   "description": "Alr_Ext_Modul7_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 165,
   "name": "Extention IO-Modul no 8 - communication error",
   "description": "Alr_Ext_Modul8_Comm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 166,
   "name": "Supplysensor 2 alarm",
   "description": "Alr_SupAirTemp2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 167,
   "name": "Addon sensor 1 - Sensor error",
   "description": "Alr_AddOnSens1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 168,
   "name": "Addon sensor 2 - Sensor error",
   "description": "Alr_AddOnSens2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 169,
   "name": "Addon sensor 3 - Sensor error",
   "description": "Alr_AddOnSens3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 170,
   "name": "Addon sensor 4 - Sensor error",
   "description": "Alr_AddOnSens4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 171,
   "name": "SupMotor Alarm",
   "description": "Alr_SA_Controler",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 172,
   "name": "ExtMotor Alarm",
   "description": "Alr_EA_Controler",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 173,
   "name": "Combi coil; Cooling relay no. 2 aktive",
   "description": "Cmb2CoolRel",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 174,
   "name": "Flag for Rise-Falltime active DX-CO2-Cooling",
   "description": "ROHRiFaActiv",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 176,
   "name": "Preheater - heat relay 3",
   "description": "PH_HeatRelay3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 177,
   "name": "State of extern start input",
   "description": "ExternInput_StartState",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 178,
   "name": "Supply air fan EEprom error",
   "description": "Alr_SA_Contr_EE_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 179,
   "name": "Supply air fan 2 EEprom error",
   "description": "Alr_SA2_Contr_EE_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 180,
   "name": "Extract/exhaust air fan EEprom error",
   "description": "Alr_EA_Contr_EE_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 181,
   "name": "Extract/exhaust air fan 2 EEprom error",
   "description": "Alr_EA2_Contr_EE_Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 182,
   "name": "Sensor alarm TTH6040 no Com",
   "description": "Alr_TTH6040Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 183,
   "name": "Low oil level cooling compressor",
   "description": "Alr_LowOilDXHP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 184,
   "name": "Common-Alarm circulationpumps",
   "description": "Alr_Common_HWPump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 185,
   "name": "Common-Alarm Supplyfan",
   "description": "Alr_Common_SupFan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 186,
   "name": "Common-Alarm Extractfan",
   "description": "Alr_Common_ExtFan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 187,
   "name": "Common-Alarm Supply duct/flow",
   "description": "Alr_Common_SupFlDu",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 188,
   "name": "Common-Alarm Extract duct/flow",
   "description": "Alr_Common_ExtFlDu",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 189,
   "name": "Common-Alarm Exchanger",
   "description": "Alr_Common_EXC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 190,
   "name": "Common-Alarm antifreeze",
   "description": "Alr_Common_Freeze",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 191,
   "name": "Common-Alarm El-Batteries",
   "description": "Alr_Common_ElHeat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 192,
   "name": "Common-Alarm Temperatures low/high",
   "description": "Alr_Common_Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 193,
   "name": "Common-Alarm Supply Filter",
   "description": "Alr_Common_SFilt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 194,
   "name": "Common-Alarm Extract Filter",
   "description": "Alr_Common_EFilt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 195,
   "name": "Common-Alarm Temperaturesensors",
   "description": "Alr_Common_TmpSens",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 196,
   "name": "Common-Alarm Cooling",
   "description": "Alr_Common_Cool",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 197,
   "name": "Common-Alarm Dampers Belimo",
   "description": "Alr_Common_BDamp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 198,
   "name": "Common-Alarm Internals / SysModBus",
   "description": "Alr_Common_Intern",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 199,
   "name": "Value in Control Reg BMS Ctrl",
   "description": "BMS_InpRegState",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 200,
   "name": "State of extern lowspeed input",
   "description": "ExternInput_LowSpeed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "BMS-Sensor Room Out of Range",
   "description": "Alr_BMS_Room_TS_OOR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "BMS-Sensor Outdoor Out of Range",
   "description": "Alr_BMS_OA_TS_OOR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 203,
   "name": "Fire mann stop",
   "description": "Alr_FireManStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "Smoke evacuation activated",
   "description": "Alr_SmokEvacAct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 205,
   "name": "Smoke evacuation fan alarm",
   "description": "Alr_SmokEvaFan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 206,
   "name": "Output for supply air damper aktive",
   "description": "DO_OA_BigDamp_Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 207,
   "name": "Big Damper relay Supply",
   "description": "DO_SA_BigDamp_Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 208,
   "name": "Recirce DamperSignal",
   "description": "AR_DA_REC_DO",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 209,
   "name": "External OutDoorTemp -Sensor Error",
   "description": "ExOutDSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 210,
   "name": "PreHeatWaterBatt Sensor Alarm",
   "description": "Alr_PreheatAirSens",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 211,
   "name": "Cooling water supply temperature - sensor error",
   "description": "CL_CW_TSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 212,
   "name": "Heat Relay 21 (ExtMod-Reserve)",
   "description": "Heat_RE21_DO21",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 213,
   "name": "Heat Relay 22 (ExtMod-Reserve)",
   "description": "Heat_RE22_DO22",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 214,
   "name": "Heat Relay 23 (ExtMod-Reserve)",
   "description": "Heat_RE23_DO23",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 215,
   "name": "Heat Relay 24 (ExtMod-Reserve)",
   "description": "Heat_RE24_DO24",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 216,
   "name": "Heat Relay 25 (ExtMod-Reserve)",
   "description": "Heat_RE25_DO25",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 217,
   "name": "Heating relay26 (ExtMod-Reserve)",
   "description": "Heat_RE26_DO26",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 218,
   "name": "Pump relay combi coil activated",
   "description": "Combi_PumpRE_DO",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 219,
   "name": "Electric coil: High temperature alarm signal",
   "description": "EL1_OverHtBac",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 220,
   "name": "Electric coil: Relay stuck",
   "description": "Alr_HT1_EL_Coil_Contact",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 221,
   "name": "Electric coil 2: High temperature alarm signal",
   "description": "EL2_OverHtBac",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 222,
   "name": "Electric coil 2: Relay stuck",
   "description": "Alr_HT2_EL_Coil_Contact",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 223,
   "name": "Alarm - Time is out for filter change supply air filter",
   "description": "Alr_OAFilt_TimerAlrOn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 224,
   "name": "Alarm - Time is out for filter change extract air filter",
   "description": "Alr_EAFilt_TimerAlrOn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 225,
   "name": "Extended medium speed –> Active",
   "description": "ExtDrfMeSpeed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 226,
   "name": "Preheater - heat relay 2",
   "description": "PH_HeatRelay2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 229,
   "name": "Supply air fan, Power limit",
   "description": "Alr_SA_Contr_PowLim",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 230,
   "name": "Extract/exhaust air fan, Power limit",
   "description": "Alr_EA_Contr_PowLim",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 233,
   "name": "Supply air fan2 Ripple Alarm",
   "description": "Alr_SA2_Controler_Ripple",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 234,
   "name": "Extract/exhaust air fan, Intern Stop",
   "description": "Alr_EA_Controler_IStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 235,
   "name": "Supply air fan2 Intern Stop",
   "description": "Alr_SA2_Controler_IStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 236,
   "name": "Extract/exhaust air fan 2, Intern Stop",
   "description": "Alr_EA2_Controler_IStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 237,
   "name": "CombiBattery heat usable",
   "description": "CmbHeatState",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 238,
   "name": "CombiBattery cool usable",
   "description": "CmbCoolState",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 239,
   "name": "ElPrehheat Overheat State",
   "description": "Pre_OverHtBac",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 240,
   "name": "Contact error Preheater El-Battery",
   "description": "Alr_Preheat_Contact",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 244,
   "name": "Extract/exhaust air fan 2 high current limit",
   "description": "Alr_EA2_Contr_HiIOAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 245,
   "name": "B-Alr SupFan is stopped",
   "description": "Alr_SA_FanStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 246,
   "name": "Smoke Evac Damper not in position",
   "description": "Alr_SMEvacDmpNotInPos",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 247,
   "name": "Smoke Bypass Damper not in position",
   "description": "Alr_SMBPassDmpNotInPos",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 248,
   "name": "Communication Alarm DPTH1",
   "description": "Alr_DPTH_1Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 249,
   "name": "Communication Alarm DPTH2",
   "description": "Alr_DPTH_2Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 250,
   "name": "Communication Alarm DPTH3",
   "description": "Alr_DPTH_3Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 251,
   "name": "Communication Alarm DPTH4",
   "description": "Alr_DPTH_4Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 252,
   "name": "Communication Alarm DPTH5",
   "description": "Alr_DPTH_5Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 253,
   "name": "Filter Alarm for SA-Filter (pressure above Limit)",
   "description": "Filt_Alarm_SA",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 254,
   "name": "Filter Alarm for EA2-Filter (pressure above Limit)",
   "description": "Filt_Alarm_EA2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 255,
   "name": "Alarm from Supplyfilter timer",
   "description": "Alr_SAFilt_TimerAlrOn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 256,
   "name": "Alarm from Extractfilter2 timer",
   "description": "Alr_EAFilt2_TimerAlrOn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 257,
   "name": "ZoneControl PIR Active",
   "description": "ZM_PIR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 258,
   "name": "ZoneModule 1 - WindowFrost Value",
   "description": "ZM1_WinFrost",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 259,
   "name": "ZoneModule 1 - PIR Active",
   "description": "ZM1_PIR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 260,
   "name": "ZoneModule 1 - Room Temp Sensor Error",
   "description": "ZM1_RoomTmpErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 261,
   "name": "ZoneModule 1 - Supply Temp Sensor Error",
   "description": "ZM1_SupTempErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 262,
   "name": "ZoneModule 2 - WindowFrost Value",
   "description": "ZM2_WinFrost",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 263,
   "name": "ZoneModule 2 - PIR Active",
   "description": "ZM2_PIR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 264,
   "name": "ZoneModule 2 - Room Temp Sensor Error",
   "description": "ZM2_RoomTmpErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 265,
   "name": "ZoneModule 2 - Supply Temp Sensor Error",
   "description": "ZM2_SupTempErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 266,
   "name": "ZoneModule 3 - WindowFrost Value",
   "description": "ZM3_WinFrost",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 267,
   "name": "ZoneModule 3 - PIR Active",
   "description": "ZM3_PIR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 268,
   "name": "ZoneModule 3 - Room Temp Sensor Error",
   "description": "ZM3_RoomTmpErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 269,
   "name": "ZoneModule 3 - Supply Temp Sensor Error",
   "description": "ZM3_SupTempErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 270,
   "name": "ZoneModule 4 - WindowFrost Value",
   "description": "ZM4_WinFrost",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 271,
   "name": "ZoneModule 4 - PIR Active",
   "description": "ZM4_PIR",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 272,
   "name": "ZoneModule 4 - Room Temp Sensor Error",
   "description": "ZM4_RoomTmpErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 273,
   "name": "ZoneModule 4 - Supply Temp Sensor Error",
   "description": "ZM4_SupTempErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 274,
   "name": "Cool Relay 2",
   "description": "Cool_RE2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 275,
   "name": "Cool Relay 3",
   "description": "Cool_RE3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 276,
   "name": "Cool Relay 4",
   "description": "Cool_RE4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 277,
   "name": "Alarm smoke evacuation damper is activated ('1' = Open damper)",
   "description": "Alr_FireEvaDmp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 278,
   "name": "Heat Relay 2 (ExtMod-Reserve)",
   "description": "Heat_RE2_DO2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 279,
   "name": "Combi coil - Return sensor - Sensor fault",
   "description": "CombiTSenErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 280,
   "name": "Combi coil - Frost alarm",
   "description": "CombiFrostAlrH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 281,
   "name": "Combi coil - Frost protection active",
   "description": "CombiFrostReg",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 282,
   "name": "Combi coil - Circulation pump, pump exercising active",
   "description": "CombiPumpExer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 283,
   "name": "Combi coil; Cooling relay aktive",
   "description": "CombiCoolRel",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 284,
   "name": "Combi coil; Heating relay aktive",
   "description": "CombiHeatRel",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 286,
   "name": "Supply Fan wall Alarm (B)",
   "description": "Alr_SA_FanWallAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 287,
   "name": "Extract Fan wall Alarm (B)",
   "description": "Alr_EA_FanWallAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 288,
   "name": "Extract digital damper output signal ('1' = Open damper)",
   "description": "DO_EA_Damper_Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 289,
   "name": "Exhaust digital damper output signal ('1' = Open damper)",
   "description": "DO_EXH_Damper_Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 290,
   "name": "Exhaust backup digital damper output signal ('1' = Open damper)",
   "description": "DO_EXHBa_Damper_Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 291,
   "name": "Supply backup digital damper output signal ('1' = Open damper)",
   "description": "DO_SABa_Damper_Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 292,
   "name": "SupBackupMotor Alarm",
   "description": "AlrSupBMtr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 293,
   "name": "ExhBackupMotor Alarm",
   "description": "AlrExhBMtr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 294,
   "name": "Sensor alarm TTH6040 OutDoor no Com (port A)",
   "description": "TTH_6040OA_PortA_Com",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 295,
   "name": "Supply Backup Motor Alarm",
   "description": "SupBMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 296,
   "name": "Exhaust Backup Motor Alarm",
   "description": "ExhBMotorAlarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 297,
   "name": "Reduction of cross-flow exchanger due to de-icing; deicing star",
   "description": "CExcDeIcing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 298,
   "name": "Electric coil 2 - Output reduction active due to low flow",
   "description": "El_HT2_BatPowerRed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 299,
   "name": "Extract/exhaust air fan Ripplealarm",
   "description": "Alr_EA_Controler_Ripple",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 300,
   "name": "Supply air fan, Intern Stop",
   "description": "Alr_SA_Controler_IStop",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 301,
   "name": "Preheater Frost Alarm Cooling",
   "description": "PH_FrzAlrCool",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 302,
   "name": "Status frost thermostat alarm (digital input)",
   "description": "AR_DI_State_LuftAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 303,
   "name": "Humidifier alarm status",
   "description": "HumidAlrInp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 304,
   "name": "Freshair cooling is stopped",
   "description": "NO_CStopStat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 305,
   "name": "Communication CVM Mini Meter",
   "description": "Alr_CommCVMMini",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 306,
   "name": "Communication CVM Mini Cool Meter",
   "description": "Alr_CommCVMCool",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 307,
   "name": "A-Alr Comm Error HMI_20T",
   "description": "Alr_ComHMI_20T",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 308,
   "name": "Alarm, Fire damper not closed",
   "description": "AlrFireDmpNCls",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 309,
   "name": "Alarm, Fire damper not opened",
   "description": "AlrFireDmpNOpn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 310,
   "name": "Fire damper test is ongoing",
   "description": "FireDmpTstActv",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 311,
   "name": "Extract air temperature after Heatpump, sensor error",
   "description": "HP_TSExtAirErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 312,
   "name": "Start of AHU is blocked, if mounted and open",
   "description": "AggBlKAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 313,
   "name": "Firethermostat alarm via El-Heater input",
   "description": "FireEHtCoilAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 314,
   "name": "Firethermostat alarm via El-Pre-Heater input",
   "description": "FireEPrHeatAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 315,
   "name": "Daikin EVKit communications Alarm",
   "description": "AlrCommDaikin",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 316,
   "name": "Daikin 'warning' bits from register 30003",
   "description": "AlrDaikinWrn",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 317,
   "name": "Daikin 'alarm' bits from register 30003",
   "description": "AlrDaikinAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 318,
   "name": "Daikin 'error' bits from register 30003",
   "description": "AlrDaikinErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 320,
   "name": "Drives Compressor communication alarm",
   "description": "Alr_DrCmpComAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 321,
   "name": "Drives Compressor high current alarm",
   "description": "Alr_DrCmp_IHgh",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 322,
   "name": "Drives Compressor low voltage alarm",
   "description": "Alr_DrCmpLwVlt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 323,
   "name": "Drives Compressor high voltage alarm",
   "description": "Alr_DrCmpHghVlt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 324,
   "name": "Drives Compressor high temperature alarm",
   "description": "Alr_DrCmpHiTmp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 325,
   "name": "Drives Compressor compressor alarm",
   "description": "Alr_DrCmpInpPhAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 326,
   "name": "Drives Compressor rotor blocked",
   "description": "Alr_DrCmpRtrBlkAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 327,
   "name": "Drives Compressor current limit alarm",
   "description": "Alr_DrCmpILimitAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 328,
   "name": "Drives Compressor voltage limit alarm",
   "description": "Alr_DrCmpVLimitAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 329,
   "name": "Drives Compressor rotor direction alarm",
   "description": "Alr_DrCmpRtrDirAlr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 330,
   "name": "Drives Compressor Eeprom error",
   "description": "Alr_DrCmpEEPROM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 331,
   "name": "Drives Compressor internal Stop",
   "description": "Alr_DrCmpIntrnStp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 332,
   "name": "Drives Compressor Earth fault alarm",
   "description": "Alr_DrCmpEarthFlt",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 333,
   "name": "Drives Compressor Motor phase alarm",
   "description": "Alr_DrCmpPhaseErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 334,
   "name": "Drives Compressot MOC communication err",
   "description": "Alr_DrCmpComErrMOC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 335,
   "name": "Drives Compressor 24V overload alarm",
   "description": "Alr_DrCmp24VOvrlad",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 336,
   "name": "Drives Compressor internal bootloader alarm",
   "description": "Alr_DrCmpMOCinBoot",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 337,
   "name": "Drives Compressor internal com alarm",
   "description": "Alr_DrCmpComErrIOM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 338,
   "name": "Drives Compressor Motor overheat alarm",
   "description": "Alr_DrCmpOverheat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 339,
   "name": "Drives Compressor Start up alarm",
   "description": "Alr_DrCmpErStrtup",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 340,
   "name": "Drives Compressor Pressure relax alarm",
   "description": "Alr_DrCmpPrssRlx",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 341,
   "name": "Drives Compressor Max start alarm",
   "description": "Alr_DrCmpMaxStarts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 342,
   "name": "Drives Compressor Min run time alarm",
   "description": "Alr_DrCmpMinRntime",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 343,
   "name": "Drives Compressor Overloaded",
   "description": "Alr_DrCmp_Overload",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 348,
   "name": "Heat pump deicing not correct",
   "description": "Alr_HP_Deice_Incorrect",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 349,
   "name": "Heat pump water temp alarm",
   "description": "Alr_HP_WaterTemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 350,
   "name": "State of the Heat pump Oil/Defrost input",
   "description": "HP_Stat_Lub",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 352,
   "name": "Alarm Counterflow EXC Deicing is active for too long time",
   "description": "Alr_CF_Timerunout_On",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 353,
   "name": "Filter calibration completed OA (valid filter data)ONLY IF 'DYN",
   "description": "FiltCaliDone_OA",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 354,
   "name": "Filter calibration completed SA (valid filter data)ONLY IF 'DYN",
   "description": "FiltCaliDone_SA",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 355,
   "name": "Filter calibration completed EA1 (valid filter data)ONLY IF 'DY",
   "description": "FiltCaliDone_EA1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 356,
   "name": "Filter calibration completed EA2 (valid filter data)ONLY IF 'DY",
   "description": "FiltCaliDone_EA2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 357,
   "name": "Pre-heating coil - Return sensor - Sensor fault",
   "description": "PH_TempSensErr",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 358,
   "name": "Drive Compressor Existflag",
   "description": "EXISTS_DV_Compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Alarm reset signal (AutoReturn to zero)",
   "description": "Alr_Reset_Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Cooling recovery: ON/OFF",
   "description": "AHU_CoolRecovFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Summer night cooling: ON/OFF",
   "description": "SNC_Func",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Summer/winter temp. compensation: ON/OFF",
   "description": "SWTC_Func",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Flow/outdoor temperature compensation: ON/OFF",
   "description": "AR_FlwTmpCmpFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Recirculation: ON/OFF ('1' = Open damper)",
   "description": "NH_REC_Func_On",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Forced flow with cooling demand: ON/OFF",
   "description": "CL_Cool_FlwForceFc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Automatic summer/winter time: ON/OFF",
   "description": "SWTC_SumFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Input for forced high speed",
   "description": "ExtDrfHiPeriod",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Run-on time for forced high speed active",
   "description": "ExtDrfPeriodON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Start manual zero calibration (can be used together with automa",
   "description": "AHU_ManZeroCali",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Automatic zero calibration: ON/OFF",
   "description": "AHU_AutoZeroCali",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Dynamic filter alarm: ON/OFF OFF static limit on  dynamic limit",
   "description": "FiltDynAlrFunc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Start filter calibration. Is automatically reset to zero (OFF)",
   "description": "FM_FiltCalibrate_Start",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Activate outdoor temperature from BMS",
   "description": "TR_MBT_OA_Act",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Activate room temperature from BMS",
   "description": "TR_MBT_Room1Activ",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Hot water supply is available for the combi coil",
   "description": "CmbEnHeatMB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Cold water supply is available for the combi coil",
   "description": "CmbEnCoolMB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Force recirc via Ext. Modbus ('1' = Open damper)",
   "description": "ExtMB_ForceRecirc",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Enable Modbus Force recirc signal",
   "description": "ExtMBEnbl_ForceRec",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Enable combi coil for control via external Modbus [1=Modbus/0=D",
   "description": "CmbEnCtrlMB",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Filter (OA) Dynamic Alarm function ON/OFF OFF -> Static Limit O",
   "description": "Filt_DynAlrFunc_OA",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Filter (SA) Dynamic Alarm function ON/OFF OFF -> Static Limit O",
   "description": "Filt_DynAlrFunc_SA",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Filter (EX) Dynamic Alarm function ON/OFF OFF -> Static Limit O",
   "description": "Filt_DynAlrFunc_EA1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Filter (EX2) Dynamic Alarm function ON/OFF OFF -> Static Limit",
   "description": "Filt_DynAlrFunc_EA2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Rotary heatexchanger, turn ratation direction to counter clock",
   "description": "EXC_CCV",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "Summer Night Cooling activated in low speed",
   "description": "SNC_FuncLoSpeed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "External high speed start signal",
   "description": "ExtHighSpdSet",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "Drive Compressor Mountflag",
   "description": "MNT_DV_Compressor",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Input for forced medium speed",
   "description": "ExtDrfMePeriod",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "Limit the first step between min / max SA-BattFlow El-Heater 1",
   "description": "EL_HT1_LimitStep_1Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Limit the first step between min / max SA-BattFlow El-Heater 2",
   "description": "EL_HT2_LimitStep_1Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "Limit the first step between min / max SA-BattFlow El- Preheate",
   "description": "PH_EL_LimitStep_1Uset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 0,
   "name": "Calendar #1",
   "description": "Calendar #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 1,
   "name": "Calendar #2",
   "description": "Calendar #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CAL",
   "instance": 2,
   "name": "Calendar #3",
   "description": "Calendar #3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 0,
   "name": "NC 00 A-Alarm",
   "description": "Notification Class 00 A-Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "NC",
   "instance": 1,
   "name": "NC 01 B-Alarm",
   "description": "Notification Class 01 B-Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "SCH",
   "instance": 0,
   "name": "Schedule #1",
   "description": "Schedule #1",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/oj-electronics/oj-air-plus-ahu-controller",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}