- Home
- BACnet points lists
- KMC Controls
- Conquest BAC-93x1A rooftop unit (Gen6)
Rooftop unit controller · BACnet points list
KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) BACnet points list
Updated 6 November 2026
KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the Rtu application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.
This page lists 112 BACnet objects for the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) — 72 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.
- Manufacturer
- KMC Controls
- Model
- Conquest BAC-93x1A rooftop unit (Gen6)
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 112 (72 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Gen6 application
- Also known as
- BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B
- Source document
- Conquest Gen6 Controller Application Guide · AG250415B
Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.
BMS integration notes: KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)
Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | OCCUPIED MODE | Occupancy command | Write |
| AV 5 | OCC_CL_STPT | Occupied cooling setpoint, °F | Write |
| AV 6 | OCC_HT_STPT | Occupied heating setpoint, °F | Write |
| MV 2 | SYSTEM_MODE | Heat / cool / auto mode | Write |
| AV 1 | SPACE_TEMP | Space temperature, °F | Read |
| AV 3 | ACT_COOL_STPT | Active cooling setpoint, °F | Read |
| MV 8 | OCCUPIED STATE | Current occupancy state | Read |
| AI 3 | DISCHARGE AIR | Discharge air temperature, °F | Read |
| BO 1 | FAN | Fan start/stop output | Command |
| BV 14 | FAN_STATUS | Fan proof status | Read |
Enable & remote start
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Sensors & values from the BMS
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
Network setup
- Conquest controllers are BACnet MS/TP, or BACnet IP on Ethernet models.
- Use KMC Connect, Converge or TotalControl to view or recreate objects.
Watch out for
- Do not reuse objects reserved for KMC default programs for custom programming; create new ones.
- A restart can zero objects or return present values to relinquish defaults depending on restart type.
KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | SPACE SENSOR | Space Sensor (KMC Type II Deg F (10K)) | °F | Read | |
| AI | 2 | SPACE SETPOINT | Space Setpoint (TABLE_4) | Read | ||
| AImin | 3 | DISCHARGE AIR | Discharge Air Temperature (KMC Type III Deg F (10K)) | °F | Read | |
| AI | 4 | OUTDOOR AIR | Outdoor Air Temp (KMC10K_Type_III) | Read | ||
| AI | 5 | HUMIDITY | Space Humidity (Humidity (0-100 % 0-5 v)) | Read | ||
| AI | 6 | AI_06 | Analog Input #6 (NONE) | Read | ||
| AI | 7 | AI_07 | Analog Input #7 (NONE) | Read | ||
| AI | 8 | AI_08 | Analog Input #8 (NONE) | Read | ||
| AO | 7 | COOLING_OUTPUT | Analog Cooling Output (default 0) | 0-100% (0-10 V) | Command | |
| AO | 8 | HEATING_OUTPUT | Analog Heating Output (default 0) | 0-100% (0-10 V) | Command | |
| AO | 9 | ECON_DAMPER | Economizer Output (default 0) | 0-100% (0-10 V) | Command | |
| AO | 10 | FAN_SPEED | Analog Output #10 (default Inactive) | PSI (0-100 % 0-10 V) | Command | |
| BOmin | 1 | FAN | Fan Start - Stop (default Inactive) | Command | ||
| BO | 2 | CL STAGE 1 | Cool Stage 1 (default Inactive) | Command | ||
| BO | 3 | CL STAGE 2 | Cool Stage 2 (default Inactive) | Command | ||
| BO | 4 | BO_04 | Binary Output #04 (default Inactive) | Command | ||
| BO | 5 | HT STAGE 1 | Heating Stage 1 (default Inactive) | Command | ||
| BO | 6 | HT STAGE 2 | Heating Stage 2 (default Inactive) | Command | ||
| AVmin | 1 | SPACE_TEMP | Space Temperature (default 0) | °F | Read | |
| AV | 2 | STPT REFERENCE | Setpoint Reference (default 72) | °F | Write | |
| AVmin | 3 | ACT_COOL_STPT | Active Cooling Setpoint (default 74) | °F | Read | |
| AV | 4 | ACT_HEAT_STPT | Active Heating Setpoint (default 70) | °F | Read | |
| AVmin | 5 | OCC_CL_STPT | Occupied Cooling Setpoint (default 74) | °F | Write | |
| AVmin | 6 | OCC_HT_STPT | Occupied Heating Setpoint (default 70) | °F | Write | |
| AV | 7 | UNOCC_CL_STPT | Unoccupied Cooling Setpoint (default 80) | °F | Write | |
| AV | 8 | UNOCC_HT_STPT | Unoccupied Heating Setpoint (default 64) | °F | Write | |
| AV | 9 | MIN_CL_STPT | Minimum Cooling Setpoint (default 68) | °F | Write | |
| AV | 10 | MAX_HT_STPT | Maximum Heating Setpoint (default 76) | °F | Write | |
| AV | 11 | MIN_STPT_DIFF | Minimum Setpoint Differential (default 2) | °F | Write | |
| AV | 12 | STBY_OFFSET | Standby Offset (default 3) | °F | Write | |
| AV | 13 | DAT RESET | Discharge Air Temperature Setpoi (default 0) | °F | Write | |
| AV | 14 | MIN DAT | Min Dishcharge Air Temp (default 55) | °F | Write | |
| AV | 15 | MIN_ECON_DAMPER | Minimum Econ Damper (default 10) | % | Write | |
| AV | 16 | ECON_ENABLE_TEMP | Econimizer Enable Temperature (default 60) | °F | Write | |
| AV | 17 | AV_17 | Analog Value #17 (default 0) | Read | ||
| AV | 19 | OUTDOOR_TEMP | Outdoor Air Temperature (default 0) | °F | Write | |
| AV | 20 | DISCHARGE_TEMP | Discharge Air Temp (default 0) | °F | Write | |
| AV | 21 | REL_HUMIDITY | Relative Humidity (default 0) | % | Read | |
| AV | 22 | DEHUM_STPT | Dehumidification Setpoint (default 60) | % | Write | |
| AV | 23 | AV_23 | Analog Value #23 (default 0) | Read | ||
| AV | 24 | DEHUM_DIFF | Dehumidification Differential (default 5) | % | Write | |
| AV | 25 | FAN_OFF_DELAY | Fan Off Delay (default 2) | min | Write | |
| AV | 26 | MIN_ OFF_TIME | Equipment Delay (default 5) | min | Write | |
| AV | 27 | STAGE_DELAY | Stage Delay (default 10) | min | Write | |
| AV | 28 | STANDBY_TIMER | Inactivity Timer (default 20) | min | Write | |
| AV | 29 | OCCUPANCY TRIGGE | Occupancy Trigger (default 5) | min | Write | |
| AV | 30 | AV_30 | Analog Value #30 (default 0) | Read | ||
| AV | 33 | AV_33 | Analog Value #33 (default 0) | Read | ||
| AV | 34 | AV_34 | Analog Value #34 (default 0) | Read | ||
| AV | 35 | FAN_MAXIMUM | Fan Maximum Speed (default 90) | % | Write | |
| AV | 36 | FAN_MINIMUM | Fan Minimum Speed (default 30) | % | Write | |
| AV | 37 | AV_37 | Analog Value #37 (default 0) | Read | ||
| AV | 38 | OVRD_TIME | Local Override Timer (default 60) | min | Write | |
| AV | 39 | AV_39 | Analog Value #39 (default 0) | Read | ||
| AV | 51 | APP_ID | Application Identification (default 0) | Write | ||
| AV | 52 | COOL PROP | Cooling Proportional Band (default 2) | °F | Write | |
| AV | 53 | HEAT PROP | Heating Proportional Band (default 2) | °F | Write | |
| AV | 54 | COOL INTG | Cool Intergral (default 0) | Per Hour | Write | |
| AV | 55 | HEAT INTG | Heat Intergral (default 0) | Per Hour | Write | |
| AV | 56 | AV_56 | Analog Value #56 (default 0) | Read | ||
| AV | 57 | ROOM CO2 | Room CO2 Level (default 0) | ppm | Write | |
| AV | 58 | CO2_RANGE | CO2 Range (above setpoint) (default 200) | ppm | Write | |
| AV | 59 | CO2_SETPOINT | CO2 Setpoint (default 800) | ppm | Write | |
| BV | 1 | BV_1 | Binary Value #1 (default Inactive) | Read | ||
| BV | 2 | BV_2 | Binary Value #2 (default Inactive) | Read | ||
| BV | 3 | BV_3 | Binary Value #3 (default Inactive) | Read | ||
| BV | 4 | BV_4 | Binary Value #4 (default Inactive) | Read | ||
| BV | 5 | OCC_SCHEDULE | Occupy Schedule (default Inactive) | Write | ||
| BV | 6 | MOTION | Motion Detected (default Active) | Write | ||
| BV | 7 | DAT_SENSOR | DAT Sensor Present (default Inactive) | Write | ||
| BV | 8 | MODE | Heat or Cool Mode (default Active) | Write | ||
| BV | 9 | FAN_NEED | Call for Fan (default Inactive) | Write | ||
| BV | 10 | COOL_HEAT_NEED | Cooling or Heating Needed? (default Active) | Write | ||
| BV | 11 | SPEED_UP | Speed Up Timers X 15 (default Inactive) | Write | ||
| BV | 12 | HEATING_FAN | Fan Acitve In Heat (default Active) | Write | ||
| BV | 13 | OCCUPIED_FAN | Fan On During Occupied Mode (default Inactive) | Write | ||
| BVmin | 14 | FAN_STATUS | Fan Proof (default Inactive) | Read | ||
| BV | 15 | BV_15 | Binary Value#15 (default Inactive) | Write | ||
| BV | 16 | ECON_ENABLE | Econimizer (default Inactive) | Write | ||
| BV | 17 | ECON_MODE | Start Stop Econimizer (default Inactive) | Write | ||
| BV | 18 | CL_VLV_ACTION | Normal Close/Normal Open (default Inactive) | Write | ||
| BV | 19 | HT_VLV_ACTION | Normal Close/Normal Open (default Inactive) | Write | ||
| BV | 20 | COOL_STG_1 | Cooling Stage 1 (default Inactive) | Write | ||
| BV | 21 | COOL_STG_2 | Cooling Stage 2 (default Inactive) | Write | ||
| BV | 22 | HEAT_STG_1 | Heating Stage 1 (default Inactive) | Write | ||
| BV | 23 | HEAT_STG_2 | Heating Stage 2 (default Inactive) | Write | ||
| BV | 24 | BV_24 | Binary Value #24 (default Inactive) | Read | ||
| BV | 27 | OAT_SENSOR | Outdoor Sensor Present? (default Inactive) | Write | ||
| BV | 28 | LOCAL_OVRD | Local Override Mode (default Inactive) | Write | ||
| BV | 29 | CO2 VENT ENABLE | Enable/Disable CO2 Ventilation (default Inactive) | Write | ||
| BV | 31 | DEHUM_ENABLE | Enable Dehumidification (default Inactive) | Write | ||
| BV | 32 | DEHUM_MODE | Dehumidification Mode (default Inactive) | Write | ||
| BV | 33 | STANDBY_ENABLE | Enable Standby Mode (default Active) | Write | ||
| BV | 34 | BV_34 | Binary Value #34 (default Inactive) | Read | ||
| BV | 36 | STPT_HOLD | Hold Temperature Setpoint (default Inactive) | Write | ||
| BV | 37 | BV_37 | Binary Value #37 (default Inactive) | Read | ||
| BV | 40 | ICO_FAN | Fan Icon (default Inactive) | Read | ||
| BV | 41 | ICO_FAN_LOW | Icon Fan Low Speed (default Inactive) | Read | ||
| BV | 42 | ICO_FAN_MEDIUM | Icon Fan Medium Speed (default Inactive) | Read | ||
| BV | 43 | ICO_FAN_HIGH | Icon Fan Auto (default Inactive) | Read | ||
| BV | 44 | ICO_FAN_AUTO | Icon Fan Auto (default Inactive) | Read | ||
| BV | 45 | ICO_OCCUPIED | Icon Occupied (default Inactive) | Read | ||
| BV | 46 | ICO_STANDBY | Icon Standby (default Inactive) | Read | ||
| BV | 47 | ICO_COOLING | Icon Cooling (default Inactive) | Read | ||
| BV | 48 | ICO_HEATING | Icon Heating (default Inactive) | Read | ||
| BV | 49 | ICO_AUTO_MODE | Icon Auto Mode (default Inactive) | Read | ||
| BV | 50 | ICO_OVERRIDE | Icon Override (default Inactive) | Read | ||
| MVmin | 1 | OCCUPIED MODE | Occupied Mode (default OCCUPIED) | Write | 1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED | |
| MVmin | 2 | SYSTEM_MODE | Control Mode (default AUTO) | Write | 1=OFF, 2=AUTO, 3=COOL, 4=HEAT | |
| MV | 3 | FAN_MODE | Fan Auto-Manual Mode (default AUTO) | Write | 1=AUTO, 2=ON | |
| MVmin | 8 | OCCUPIED STATE | Occupied State (default OCCUPIED) | Read | 1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE | |
| MV | 10 | WALL SENSOR | Wall Sensor Type (default STE-9001 Temp) | Write | 1=STE-9001 Temp, 2=STE-9021 Humidity, 3=STE-9201 Motion, 4=STE-9221 Humidity/Motion, 5=STE-9301 CO2, 6=STE-9321 Humidity/CO2, 7=STE-9501 Motion/CO2, 8=STE-9521 Humidity/Motion/CO2, 9=STE-6014/7, 10=STE-6010, 11=None |
No points match these filters.
Object ID lookup: KMC Controls Conquest BAC-93x1A rooftop unit point IDs by name
AI1SPACE SENSORAI2SPACE SETPOINTAI3DISCHARGE AIRAI4OUTDOOR AIRAI5HUMIDITYAI6AI_06AI7AI_07AI8AI_08AO7COOLING_OUTPUTAO8HEATING_OUTPUTAO9ECON_DAMPERAO10FAN_SPEEDBO1FANBO2CL STAGE 1BO3CL STAGE 2BO4BO_04BO5HT STAGE 1BO6HT STAGE 2AV1SPACE_TEMPAV2STPT REFERENCEAV3ACT_COOL_STPTAV4ACT_HEAT_STPTAV5OCC_CL_STPTAV6OCC_HT_STPTAV7UNOCC_CL_STPTAV8UNOCC_HT_STPTAV9MIN_CL_STPTAV10MAX_HT_STPTAV11MIN_STPT_DIFFAV12STBY_OFFSETAV13DAT RESETAV14MIN DATAV15MIN_ECON_DAMPERAV16ECON_ENABLE_TEMPAV17AV_17AV19OUTDOOR_TEMPAV20DISCHARGE_TEMPAV21REL_HUMIDITYAV22DEHUM_STPTAV23AV_23AV24DEHUM_DIFFAV25FAN_OFF_DELAYAV26MIN_ OFF_TIMEAV27STAGE_DELAYAV28STANDBY_TIMERAV29OCCUPANCY TRIGGEAV30AV_30AV33AV_33AV34AV_34AV35FAN_MAXIMUMAV36FAN_MINIMUMAV37AV_37AV38OVRD_TIMEAV39AV_39AV51APP_IDAV52COOL PROPAV53HEAT PROPAV54COOL INTGAV55HEAT INTGAV56AV_56AV57ROOM CO2AV58CO2_RANGEAV59CO2_SETPOINTBV1BV_1BV2BV_2BV3BV_3BV4BV_4BV5OCC_SCHEDULEBV6MOTIONBV7DAT_SENSORBV8MODEBV9FAN_NEEDBV10COOL_HEAT_NEEDBV11SPEED_UPBV12HEATING_FANBV13OCCUPIED_FANBV14FAN_STATUSBV15BV_15BV16ECON_ENABLEBV17ECON_MODEBV18CL_VLV_ACTIONBV19HT_VLV_ACTIONBV20COOL_STG_1BV21COOL_STG_2BV22HEAT_STG_1BV23HEAT_STG_2BV24BV_24BV27OAT_SENSORBV28LOCAL_OVRDBV29CO2 VENT ENABLEBV31DEHUM_ENABLEBV32DEHUM_MODEBV33STANDBY_ENABLEBV34BV_34BV36STPT_HOLDBV37BV_37BV40ICO_FANBV41ICO_FAN_LOWBV42ICO_FAN_MEDIUMBV43ICO_FAN_HIGHBV44ICO_FAN_AUTOBV45ICO_OCCUPIEDBV46ICO_STANDBYBV47ICO_COOLINGBV48ICO_HEATINGBV49ICO_AUTO_MODEBV50ICO_OVERRIDEMV1OCCUPIED MODEMV2SYSTEM_MODEMV3FAN_MODEMV8OCCUPIED STATEMV10WALL SENSOR
Integration notes
- Table 'BAC-93X1A RTU OBJECTS', pdf pages 49-50 of the guide.
- The guide gives no read/write column; access is inferred (inputs read-only, outputs commandable, calculated values and display icons read-only, setpoints and configuration writable).
- Descriptions carry the factory default from the guide; multi-state state lists are numbered 1..n in printed order (the printed defaults use that numbering).
- Objects depend on controller model and application, and can be deleted or created in KMC Connect, Converge or TotalControl.
- Placeholder objects named AV_nn / BV_nn ('Analog Value #nn') are spare objects in the default database.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-93x1A rooftop unit (Gen6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)
How many BACnet points does the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) have?
This list has 112 BACnet objects: 8 analog inputs, 4 analog outputs, 45 analog values, 6 binary outputs, 44 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) BACnet points are writable?
72 of the 112 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official KMC Controls Conquest BAC-93x1A rooftop unit (Gen6) BACnet documentation?
The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.
What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)?
Start with MV 1 OCCUPIED MODE (Occupancy command); AV 5 OCC_CL_STPT (Occupied cooling setpoint, °F); AV 6 OCC_HT_STPT (Occupied heating setpoint, °F); MV 2 SYSTEM_MODE (Heat / cool / auto mode); AV 1 SPACE_TEMP (Space temperature, °F); AV 3 ACT_COOL_STPT (Active cooling setpoint, °F); MV 8 OCCUPIED STATE (Current occupancy state); AI 3 DISCHARGE AIR (Discharge air temperature, °F); BO 1 FAN (Fan start/stop output); BV 14 FAN_STATUS (Fan proof status).
How do I enable BMS control of the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)?
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Can the BMS supply sensor values to the KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)?
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
How do I check these points on the real Conquest BAC-93x1A rooftop unit (Gen6)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More KMC Controls BACnet points lists
- Fan coil unit controller (four-pipe)
KMC Controls BAC-4000 AppStat, four-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the four-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Heat pump controller / thermostat
KMC Controls BAC-4000 AppStat, heat pump application
KMC AppStat (BAC-4000 series) room controllers configured for the heat pump application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Rooftop unit controller / thermostat
KMC Controls BAC-4000 AppStat, rooftop unit application
KMC AppStat (BAC-4000 series) room controllers configured for the rooftop unit application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Fan coil unit controller (two-pipe)
KMC Controls BAC-4000 AppStat, two-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the two-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - VAV terminal unit controller
KMC Controls BAC-7000 series VAV controllers (BAC-7001 / 7003 / 7051 / 7053)
KMC BAC-7001, BAC-7003, BAC-7051 and BAC-7053 VAV controllers with the factory VAV applications version 2.2 (pressure independent or dependent, with reheat).
Also known as: BAC-7001, BAC-7003, BAC-7051, BAC-7053, BAC-7000, AN0311A - Programmable general purpose controller (room thermostat application)
KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)
KMC Conquest BAC-5901 controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-5901, BAC-5901A, BAC-5901AC, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (dual duct)
KMC Controls Conquest BAC-9001A pressure independent VAV, dual duct (Gen6)
KMC Conquest BAC-9001A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9001A, BAC-9001, dual duct VAV, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller
KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
KMC Conquest BAC-9001A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9001A, BAC-9001, BAC-9001AC, BAC-9001ACE, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (pressure dependent)
KMC Controls Conquest BAC-9021A pressure dependent VAV, single duct (Gen6)
KMC Conquest BAC-9021A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9021A, BAC-9021, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (four-pipe)
KMC Controls Conquest BAC-9301A four-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (two-pipe)
KMC Controls Conquest BAC-9301A two-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (remote actuator)
KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)
KMC Conquest BAC-9311A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9311A, BAC-9311, KMC Conquest, Conquest Gen6, AG250415B - Heat pump unit controller
KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)
KMC Conquest BAC-93x1A (BAC-9301A / BAC-9311A) controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B - VAV box controller
KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)
KMC SimplyVAV controller-actuators for single duct cooling/heating, fan powered with reheat and dual duct VAV boxes.
Also known as: SimplyVAV, Simply VAV, BAC-8001, BAC-8005, BAC-8007, BAC-8205
Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.