  4. Conquest BAC-5901 general purpose controller (Gen6 default application)

Programmable general purpose controller (room thermostat application) · BACnet points list

KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet points list

Updated 6 November 2026

Short answer

KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the General Purpose application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.

This page lists 30 BACnet objects for the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.

Manufacturer
KMC Controls
Model
Conquest BAC-5901 general purpose controller (Gen6 default application)
Equipment
Programmable general purpose controller (room thermostat application)
Equipment type
Thermostats, sensors & meters
BACnet objects
30 (12 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Gen6 application
Also known as
BAC-5901, BAC-5901A, BAC-5901AC, KMC Conquest, Conquest Gen6, AG250415B
Source document
Conquest Gen6 Controller Application Guide · AG250415B
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.

BMS integration notes: KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)

Integration in brief

Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 5OCC_CL_STPTOccupied cooling setpoint, °FWrite
AV 6OCC_HT_STPTOccupied heating setpoint, °FWrite
MV 2SYSTEM_MODEHeat / cool / auto modeWrite
AV 1SPACE_TEMPSpace temperature, °FRead
AV 3ACT_COOL_STPTActive cooling setpoint, °FRead

Enable & remote start

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Sensors & values from the BMS

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

Network setup

Watch out for

KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

30 of 30 shown
Type
BinaryMulti-state
Access
Show
KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet Points List
DescriptionStates
AI1SPACE SENSORSpace Sensor (KMC Type II Deg F)°FRead
AI2SPACE SETPOINTSpace Setpoint (TABLE_4)Read
AVmin1SPACE_TEMPSpace Temperature (default 0)°FRead
AV2AV_02Analog Value #2 (default 0)Read
AVmin3ACT_COOL_STPTActive Cooling Setpoint (default 74)°FRead
AV4ACT_HEAT_STPTActive Heating Setpoint (default 72)°FRead
AVmin5OCC_CL_STPTOccupied Cooling Setpoint (default 76)°FWrite
AVmin6OCC_HT_STPTOccupied Heating Setpoint (default 72)°FWrite
AV7UNOCC_CL_STPTUnoccupied Cooling Setpoint (default 80)°FWrite
AV8UNOCC_HT_STPTUnoccupied Heating Setpoint (default 65)°FWrite
AV9MIN_CL_STPTMinimum Cooling Setpoint (default 68)°FWrite
AV10MAX_HT_STPTMaximum Heating Setpoint (default 76)°FWrite
AV11MIN_STPT_DIFFMinimum Setpoint Differential (default 2)°FWrite
AV12STBY_OFFSETStandby Offset (default 3)°FWrite
AV21REL_HUMIDITYRelative Humidity (default 0)%RHRead
AV38OVRD_TIMELocal Override Timer (default 60)minWrite
AV57ROOM CO2Room CO2 Level (default 0)ppmWrite
BV28LOCAL_OVRDLocal Override Mode (default Inactive)Write
BV40ICO_FANFan Icon (default Inactive)Read
BV41ICO_FAN_LOWIcon Fan Low Speed (default Inactive)Read
BV42ICO_FAN_MEDIUMIcon Fan Medium Speed (default Inactive)Read
BV43ICO_FAN_HIGHIcon Fan Auto (default Inactive)Read
BV44ICO_FAN_AUTOIcon Fan Auto (default Inactive)Read
BV45ICO_OCCUPIEDIcon Occupied (default Inactive)Read
BV46ICO_STANDBYIcon Standby (default Inactive)Read
BV47ICO_COOLINGIcon Cooling (default Inactive)Read
BV48ICO_HEATINGIcon Heating (default Inactive)Read
BV49ICO_AUTO_MODEIcon Auto Mode (default Inactive)Read
BV50ICO_OVERRIDEIcon Override (default Inactive)Read
MVmin2SYSTEM_MODEControl Mode (default AUTO)Write1=OFF, 2=AUTO, 3=COOL, 4=HEAT
Object ID lookup: KMC Controls Conquest BAC-5901 general purpose controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-5901 general purpose controller (Gen6 default application) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)

How many BACnet points does the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) have?

This list has 30 BACnet objects: 2 analog inputs, 15 analog values, 12 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet points are writable?

12 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet documentation?

The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.

What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?

Start with AV 5 OCC_CL_STPT (Occupied cooling setpoint, °F); AV 6 OCC_HT_STPT (Occupied heating setpoint, °F); MV 2 SYSTEM_MODE (Heat / cool / auto mode); AV 1 SPACE_TEMP (Space temperature, °F); AV 3 ACT_COOL_STPT (Active cooling setpoint, °F).

How do I enable BMS control of the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Can the BMS supply sensor values to the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

How do I check these points on the real Conquest BAC-5901 general purpose controller (Gen6 default application)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More KMC Controls BACnet points lists

Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.