- Conquest BAC-5901 general purpose controller (Gen6 default application)
Programmable general purpose controller (room thermostat application) · BACnet points list
KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet points list
Updated 6 November 2026
KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the General Purpose application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.
This page lists 30 BACnet objects for the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.
- Manufacturer
- KMC Controls
- Model
- Conquest BAC-5901 general purpose controller (Gen6 default application)
- Equipment
- Programmable general purpose controller (room thermostat application)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 30 (12 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Gen6 application
- Also known as
- BAC-5901, BAC-5901A, BAC-5901AC, KMC Conquest, Conquest Gen6, AG250415B
- Source document
- Conquest Gen6 Controller Application Guide · AG250415B
Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.
BMS integration notes: KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)
Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 5 | OCC_CL_STPT | Occupied cooling setpoint, °F | Write |
| AV 6 | OCC_HT_STPT | Occupied heating setpoint, °F | Write |
| MV 2 | SYSTEM_MODE | Heat / cool / auto mode | Write |
| AV 1 | SPACE_TEMP | Space temperature, °F | Read |
| AV 3 | ACT_COOL_STPT | Active cooling setpoint, °F | Read |
Enable & remote start
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Sensors & values from the BMS
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
Network setup
- Conquest controllers are BACnet MS/TP, or BACnet IP on Ethernet models.
- Use KMC Connect, Converge or TotalControl to view or recreate objects.
Watch out for
- Do not reuse objects reserved for KMC default programs for custom programming; create new ones.
- A restart can zero objects or return present values to relinquish defaults depending on restart type.
KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | SPACE SENSOR | Space Sensor (KMC Type II Deg F) | °F | Read | |
| AI | 2 | SPACE SETPOINT | Space Setpoint (TABLE_4) | Read | ||
| AVmin | 1 | SPACE_TEMP | Space Temperature (default 0) | °F | Read | |
| AV | 2 | AV_02 | Analog Value #2 (default 0) | Read | ||
| AVmin | 3 | ACT_COOL_STPT | Active Cooling Setpoint (default 74) | °F | Read | |
| AV | 4 | ACT_HEAT_STPT | Active Heating Setpoint (default 72) | °F | Read | |
| AVmin | 5 | OCC_CL_STPT | Occupied Cooling Setpoint (default 76) | °F | Write | |
| AVmin | 6 | OCC_HT_STPT | Occupied Heating Setpoint (default 72) | °F | Write | |
| AV | 7 | UNOCC_CL_STPT | Unoccupied Cooling Setpoint (default 80) | °F | Write | |
| AV | 8 | UNOCC_HT_STPT | Unoccupied Heating Setpoint (default 65) | °F | Write | |
| AV | 9 | MIN_CL_STPT | Minimum Cooling Setpoint (default 68) | °F | Write | |
| AV | 10 | MAX_HT_STPT | Maximum Heating Setpoint (default 76) | °F | Write | |
| AV | 11 | MIN_STPT_DIFF | Minimum Setpoint Differential (default 2) | °F | Write | |
| AV | 12 | STBY_OFFSET | Standby Offset (default 3) | °F | Write | |
| AV | 21 | REL_HUMIDITY | Relative Humidity (default 0) | %RH | Read | |
| AV | 38 | OVRD_TIME | Local Override Timer (default 60) | min | Write | |
| AV | 57 | ROOM CO2 | Room CO2 Level (default 0) | ppm | Write | |
| BV | 28 | LOCAL_OVRD | Local Override Mode (default Inactive) | Write | ||
| BV | 40 | ICO_FAN | Fan Icon (default Inactive) | Read | ||
| BV | 41 | ICO_FAN_LOW | Icon Fan Low Speed (default Inactive) | Read | ||
| BV | 42 | ICO_FAN_MEDIUM | Icon Fan Medium Speed (default Inactive) | Read | ||
| BV | 43 | ICO_FAN_HIGH | Icon Fan Auto (default Inactive) | Read | ||
| BV | 44 | ICO_FAN_AUTO | Icon Fan Auto (default Inactive) | Read | ||
| BV | 45 | ICO_OCCUPIED | Icon Occupied (default Inactive) | Read | ||
| BV | 46 | ICO_STANDBY | Icon Standby (default Inactive) | Read | ||
| BV | 47 | ICO_COOLING | Icon Cooling (default Inactive) | Read | ||
| BV | 48 | ICO_HEATING | Icon Heating (default Inactive) | Read | ||
| BV | 49 | ICO_AUTO_MODE | Icon Auto Mode (default Inactive) | Read | ||
| BV | 50 | ICO_OVERRIDE | Icon Override (default Inactive) | Read | ||
| MVmin | 2 | SYSTEM_MODE | Control Mode (default AUTO) | Write | 1=OFF, 2=AUTO, 3=COOL, 4=HEAT |
No points match these filters.
Object ID lookup: KMC Controls Conquest BAC-5901 general purpose controller point IDs by name
AI1SPACE SENSORAI2SPACE SETPOINTAV1SPACE_TEMPAV2AV_02AV3ACT_COOL_STPTAV4ACT_HEAT_STPTAV5OCC_CL_STPTAV6OCC_HT_STPTAV7UNOCC_CL_STPTAV8UNOCC_HT_STPTAV9MIN_CL_STPTAV10MAX_HT_STPTAV11MIN_STPT_DIFFAV12STBY_OFFSETAV21REL_HUMIDITYAV38OVRD_TIMEAV57ROOM CO2BV28LOCAL_OVRDBV40ICO_FANBV41ICO_FAN_LOWBV42ICO_FAN_MEDIUMBV43ICO_FAN_HIGHBV44ICO_FAN_AUTOBV45ICO_OCCUPIEDBV46ICO_STANDBYBV47ICO_COOLINGBV48ICO_HEATINGBV49ICO_AUTO_MODEBV50ICO_OVERRIDEMV2SYSTEM_MODE
Integration notes
- Table 'BAC-5901 GENERAL PURPOSE OBJECTS', pdf pages 41-41 of the guide.
- The guide gives no read/write column; access is inferred (inputs read-only, outputs commandable, calculated values and display icons read-only, setpoints and configuration writable).
- Descriptions carry the factory default from the guide; multi-state state lists are numbered 1..n in printed order (the printed defaults use that numbering).
- Objects depend on controller model and application, and can be deleted or created in KMC Connect, Converge or TotalControl.
- Placeholder objects named AV_nn / BV_nn ('Analog Value #nn') are spare objects in the default database.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-5901 general purpose controller (Gen6 default application) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)
How many BACnet points does the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) have?
This list has 30 BACnet objects: 2 analog inputs, 15 analog values, 12 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet points are writable?
12 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application) BACnet documentation?
The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.
What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?
Start with AV 5 OCC_CL_STPT (Occupied cooling setpoint, °F); AV 6 OCC_HT_STPT (Occupied heating setpoint, °F); MV 2 SYSTEM_MODE (Heat / cool / auto mode); AV 1 SPACE_TEMP (Space temperature, °F); AV 3 ACT_COOL_STPT (Active cooling setpoint, °F).
How do I enable BMS control of the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Can the BMS supply sensor values to the KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)?
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
How do I check these points on the real Conquest BAC-5901 general purpose controller (Gen6 default application)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More KMC Controls BACnet points lists
- Fan coil unit controller (four-pipe)
KMC Controls BAC-4000 AppStat, four-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the four-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Heat pump controller / thermostat
KMC Controls BAC-4000 AppStat, heat pump application
KMC AppStat (BAC-4000 series) room controllers configured for the heat pump application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Rooftop unit controller / thermostat
KMC Controls BAC-4000 AppStat, rooftop unit application
KMC AppStat (BAC-4000 series) room controllers configured for the rooftop unit application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Fan coil unit controller (two-pipe)
KMC Controls BAC-4000 AppStat, two-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the two-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - VAV terminal unit controller
KMC Controls BAC-7000 series VAV controllers (BAC-7001 / 7003 / 7051 / 7053)
KMC BAC-7001, BAC-7003, BAC-7051 and BAC-7053 VAV controllers with the factory VAV applications version 2.2 (pressure independent or dependent, with reheat).
Also known as: BAC-7001, BAC-7003, BAC-7051, BAC-7053, BAC-7000, AN0311A - VAV terminal unit controller (dual duct)
KMC Controls Conquest BAC-9001A pressure independent VAV, dual duct (Gen6)
KMC Conquest BAC-9001A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9001A, BAC-9001, dual duct VAV, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller
KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
KMC Conquest BAC-9001A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9001A, BAC-9001, BAC-9001AC, BAC-9001ACE, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (pressure dependent)
KMC Controls Conquest BAC-9021A pressure dependent VAV, single duct (Gen6)
KMC Conquest BAC-9021A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9021A, BAC-9021, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (four-pipe)
KMC Controls Conquest BAC-9301A four-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (two-pipe)
KMC Controls Conquest BAC-9301A two-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (remote actuator)
KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)
KMC Conquest BAC-9311A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9311A, BAC-9311, KMC Conquest, Conquest Gen6, AG250415B - Heat pump unit controller
KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)
KMC Conquest BAC-93x1A (BAC-9301A / BAC-9311A) controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B - Rooftop unit controller
KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)
KMC Conquest BAC-93x1A (BAC-9301A / BAC-9311A) controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B - VAV box controller
KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)
KMC SimplyVAV controller-actuators for single duct cooling/heating, fan powered with reheat and dual duct VAV boxes.
Also known as: SimplyVAV, Simply VAV, BAC-8001, BAC-8005, BAC-8007, BAC-8205
Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.