Heat pump unit controller · BACnet points list

KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) BACnet points list

Updated 6 November 2026

Short answer

KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the Hpu application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.

This page lists 110 BACnet objects for the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) — 74 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.

Manufacturer
KMC Controls
Model
Conquest BAC-93x1A heat pump unit (Gen6)
Equipment
Heat pump unit controller
Equipment type
Heat pumps
BACnet objects
110 (74 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Gen6 application
Also known as
BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B
Source document
Conquest Gen6 Controller Application Guide · AG250415B
Download CSV 110 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.

BMS integration notes: KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)

Integration in brief

Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1OCCUPIED MODEOccupancy commandWrite
AV 5OCC_CL_STPTOccupied cooling setpoint, °FWrite
AV 6OCC_HT_STPTOccupied heating setpoint, °FWrite
MV 2SYSTEM_MODEHeat / cool / auto modeWrite
AV 1SPACE_TEMPSpace temperature, °FRead
AV 3ACT_COOL_STPTActive cooling setpoint, °FRead
AI 3DISCHARGE AIRDischarge air temperature, °FRead
BO 1FANFan start/stop outputCommand
BV 14FAN_STATUSFan proof statusRead

Enable & remote start

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Sensors & values from the BMS

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

Network setup

Watch out for

KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

110 of 110 shown
Type
Multi-state
Access
Show
KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) BACnet Points List
DescriptionStates
AI1SPACE SENSORSpace Sensor (KMC Type II Deg F (10K))°FRead
AI2SPACE SETPOINTSpace Setpoint (TABLE_4)Read
AImin3DISCHARGE AIRDischarge Air Temperature (KMC Type III Deg F (10K))°FRead
AI4OUTDOOR AIROutdoor Air Temp (KMC10K_Type_III)Read
AI5HUMIDITYSpace Humidity (Humidity (0-100 % 0-5 v))Read
AI7AI_07Analog Input #7 (NONE)Read
AI8AI_08Analog Input #8 (NONE)Read
BI6FAN_STFanRead
AO7AO_07Analog Output #7 (default 0)Command
AO8AO_08Analog Output #8 (default 0)Command
AO9ECON_DAMPEREconomizer Output (default 0)0-100% (0-10 V)Command
AO10AO_10Analog Output #10 (default 0)Command
BOmin1FANFan Start - Stop (default Inactive)Command
BO2COMPRESSOR_1Stage 1 Compressor (default Inactive)Command
BO3COMPRESSOR_2Stage 2 Compressor (default Inactive)Command
BO4REVERSING _VALVEReversing Valve (default Inactive)Command
BO5AUXILIARY_HEATAuxiliary Heat (default Inactive)Command
BO6BO_06Binary Output #6 (default Inactive)Command
AVmin1SPACE_TEMPSpace Temperature (default 0)°FRead
AV2STPT REFERENCESetpoint Reference (default 72)°FWrite
AVmin3ACT_COOL_STPTActive Cooling Setpoint (default 80)°FRead
AV4ACT_HEAT_STPTActive Heating Setpoint (default 64)°FRead
AVmin5OCC_CL_STPTOccupied Cooling Setpoint (default 74)°FWrite
AVmin6OCC_HT_STPTOccupied Heating Setpoint (default 70)°FWrite
AV7UNOCC_CL_STPTUnoccupied Cooling Setpoint (default 80)°FWrite
AV8UNOCC_HT_STPTUnoccupied Heating Setpoint (default 64)°FWrite
AV9MIN_CL_STPTMinimum Cooling Setpoint (default 68)°FWrite
AV10MAX_HT_STPTMaximum Heating Setpoint (default 76)°FWrite
AV11MIN_STPT_DIFFMinimum Setpoint Differential (default 2)°FWrite
AV12STBY_OFFSETStandby Offset (default 3)°FWrite
AV13DAT_RESETDischarge Air Reset STPT (default 0)°FWrite
AV14MIN DATMin Discharge Air Temp (default 55)°FWrite
AV15MIN_ECON_DAMPERMinimum Econ Damper (default 10)%Write
AV16ECON_ENABLE_TEMPEconomizer Enable Temperature (default 60)°FWrite
AV17CMP_LOCKOUTCompressor Lockout Temperature (default 25)°FWrite
AV18AUX_HT_LOCKOUTOAT AUX Heat Lockout (default 60)°FWrite
AV19OUTDOOR_TEMPOutdoor Air Temperature (default 0)°FWrite
AV20DISCHARGE_TEMPDischarge Air Temp (default 0)°FWrite
AV21REL_HUMIDITYRelative Humidity (default 0)%RHRead
AV22DEHUM_STPTDehumidification Setpoint (default 60)%Write
AV23AV_23Analog Value #23 (default 5)Read
AV24DEHUM_DIFFDehumidification Differential (default 5)%Write
AV25FAN_OFF_DELAYFan Off Delay (default 2)minWrite
AV26MIN_ OFF_TIMEEquipment Delay (default 5)minWrite
AV27STAGE_DELAYStage Delay (default 10)minWrite
AV28STANDBY_TIMERInactivity Timer (default 20)minWrite
AV29OCCUPANCY TRIGGEOccupancy Trigger (default 5)minWrite
AV30AV_30Analog Value #30 (default 0)Read
AV38OVRD_TIMELocal Override Timer (default 60)minWrite
AV39AV_39Analog Value #39 (default 0)Read
AV51APP_IDApplication Identification (default 0)Write
AV52COOL PROPCooling Proportional Band (default 2)°FWrite
AV53HEAT PROPHeating Proportional Band (default 2)°FWrite
AV54COOL INTGCool Intergral (default 0)Per HourWrite
AV55HEAT INTGHeat Intergral (default 0)Per HourWrite
AV56AV_56Analog Value #56 (default 0)Read
AV57ROOM CO2Room CO2 Level (default 0)ppmWrite
AV58CO2_RANGECO2 Range (above setpoint) (default 200)ppmWrite
AV59CO2_SETPOINTCO2 Setpoint (default 800)ppmWrite
BV1BV_1Binary Value #1 (default Inactive)Read
BV2BV_2Binary Value #2 (default Inactive)Read
BV3BV_3Binary Value #3 (default Inactive)Read
BV4BV_4Binary Value #4 (default Inactive)Read
BV5OCC_SCHEDULEOccupy Schedule (default Inactive)Write
BV6MOTIONMotion Detected (default Active)Write
BV7DAT_SENSORDAT Sensor Present (default Inactive)Write
BV8MODEHeat or Cool Mode (default Active)Write
BV9FAN_NEEDCall for Fan (default Inactive)Write
BV10COOL_HEAT_NEEDCooling or Heating Needed? (default Active)Write
BV11SPEED_UPSpeed Up Timers X 15 (default Inactive)Write
BV12BV_12Binary Value #12 (default Inactive)Read
BV13OCCUPIED_FANFan On During Occupied Mode (default Inactive)Write
BVmin14FAN_STATUSFan Proof (default Inactive)Read
BV15REV_VLV_POLARITYReversing Valve Action (default Inactive)Write
BV16ECON_ENABLEEconomizer (default Inactive)Write
BV17ECON_MODEStart Stop Economizer (default Inactive)Write
BV18BV_18Binary Value #18 (default Inactive)Read
BV20COOL_STG_1Cooling Stage 1 (default Inactive)Write
BV21COOL_STG_2Cooling Stage 2 (default Inactive)Write
BV22HEAT_STG_1Heating Stage 1 (default Inactive)Write
BV23HEAT_STG_2Heating Stage 2 (default Inactive)Write
BV24AUX_HEAT_STGAuxiliary Heat Stage (default Inactive)Write
BV25AUX_LOCKOUTAux Heat Lockout (default Inactive)Write
BV26COMP_LOCKOUTCompressor Lockout (default Inactive)Write
BV27OAT_SENSOROutdoor Sensor Present? (default Inactive)Write
BV28LOCAL_OVRDLocal Override Mode (default Inactive)Write
BV29CO2 VENT ENABLEEnable/Disable CO2 Ventilation (default Inactive)Write
BV31DEHUM_ENABLEEnable Dehumidification (default Inactive)Write
BV32DEHUM_MODEDehumidification Mode (default Inactive)Write
BV33STANDBY_ENABLEEnable Standby Mode (default Active)Write
BV34BV_34Binary Value #34 (default Inactive)Read
BV36STPT_HOLDHold Temperature Setpoint (default Inactive)Write
BV37ENBL_CMP_LOCKOUTEnable Compressor Lockout (default Active)Write
BV40ICO_FANFan Icon (default Inactive)Read
BV41ICO_FAN_LOWIcon Fan Low Speed (default Inactive)Read
BV42ICO_FAN_MEDIUMIcon Fan Medium Speed (default Inactive)Read
BV43ICO_FAN_HIGHIcon Fan Auto (default Inactive)Read
BV44ICO_FAN_AUTOIcon Fan Auto (default Inactive)Read
BV45ICO_OCCUPIEDIcon Occupied (default Inactive)Read
BV46ICO_STANDBYIcon Standby (default Inactive)Read
BV47ICO_COOLINGIcon Cooling (default Inactive)Read
BV48ICO_HEATINGIcon Heating (default Inactive)Read
BV49ICO_AUTO_MODEIcon Auto Mode (default Inactive)Read
BV50ICO_OVERRIDEIcon Override (default Inactive)Read
MVmin1OCCUPIED MODEOccupied Mode (default OCCUPIED)Write1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED
MVmin2SYSTEM_MODEControl Mode (default AUTO)Write1=OFF, 2=AUTO, 3=COOL, 4=HEAT, 5=EMERGENCY_HEAT
MV3FAN_MODEFan Auto-Manual Mode (default AUTO)Write1=AUTO, 2=ON
MV5AUX_HEATAuxiliary Heat (default None)Write1=None, 2=3rd Stage, 3=Comp Lockout
MV8OCCUPIED STATEOccupied Mode (default OCCUPIED)Read1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE
MV10WALL SENSORWall Sensor Type (default STE-9001 Temp)Write1=STE-9001 Temp, 2=STE-9021 Humidity, 3=STE-9201 Motion, 4=STE-9221 Humidity/Motion, 5=STE-9301 CO2, 6=STE-9321 Humidity/CO2, 7=STE-9501 Motion/CO2, 8=STE-9521 Humidity/Motion/CO2, 9=STE-6014/7, 10=STE-6010, 11=None
Object ID lookup: KMC Controls Conquest BAC-93x1A heat pump unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-93x1A heat pump unit (Gen6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)

How many BACnet points does the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) have?

This list has 110 BACnet objects: 7 analog inputs, 4 analog outputs, 41 analog values, 1 binary input, 6 binary outputs, 45 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) BACnet points are writable?

74 of the 110 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official KMC Controls Conquest BAC-93x1A heat pump unit (Gen6) BACnet documentation?

The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.

What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)?

Start with MV 1 OCCUPIED MODE (Occupancy command); AV 5 OCC_CL_STPT (Occupied cooling setpoint, °F); AV 6 OCC_HT_STPT (Occupied heating setpoint, °F); MV 2 SYSTEM_MODE (Heat / cool / auto mode); AV 1 SPACE_TEMP (Space temperature, °F); AV 3 ACT_COOL_STPT (Active cooling setpoint, °F); AI 3 DISCHARGE AIR (Discharge air temperature, °F); BO 1 FAN (Fan start/stop output); BV 14 FAN_STATUS (Fan proof status).

How do I enable BMS control of the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)?

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Can the BMS supply sensor values to the KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)?

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

How do I check these points on the real Conquest BAC-93x1A heat pump unit (Gen6)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More KMC Controls BACnet points lists

Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.