- Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
VAV terminal unit controller · BACnet points list
KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) BACnet points list
Updated 11 November 2026
KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the Pressure Independent Vav, Single Duct application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.
This page lists 92 BACnet objects for the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) — 59 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.
- Manufacturer
- KMC Controls
- Model
- Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
- Equipment
- VAV terminal unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 92 (59 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Gen6 application
- Also known as
- BAC-9001A, BAC-9001, BAC-9001AC, BAC-9001ACE, KMC Conquest, Conquest Gen6, AG250415B
- Source document
- Conquest Gen6 Controller Application Guide · AG250415B
Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.
BMS integration notes: KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | OCCUPIED MODE | Occupancy command | Write |
| AV 5 | OCC CL STPT | Occupied cooling setpoint, °F | Write |
| AV 6 | OCC HT STPT | Occupied heating setpoint, °F | Write |
| AV 1 | SPACE TEMP | Space temperature, °F | Read |
| AV 3 | ACT COOL STPT | Active cooling setpoint, °F | Read |
| MV 8 | OCCUPIED STATE | Current occupancy state | Read |
| AV 24 | PRI ACTUAL FLOW | Measured primary airflow | Read |
| AV 22 | PRI FLOW STPT | Airflow setpoint | Write |
| AV 50 | DAMPER POSITION | Damper position | Read |
| AI 3 | DISCHARGE AIR | Discharge air temperature, °F | Read |
Enable & remote start
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Sensors & values from the BMS
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
Network setup
- Conquest controllers are BACnet MS/TP, or BACnet IP on Ethernet models.
- Use KMC Connect, Converge or TotalControl to view or recreate objects.
Watch out for
- Do not reuse objects reserved for KMC default programs for custom programming; create new ones.
- A restart can zero objects or return present values to relinquish defaults depending on restart type.
KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 37 | SAT CHANGEOVER | SAT Changeover Temperature (default 72) | °F | Write | |
| AV | 38 | LOCAL OVRD TIME | Local Override Timer (default 60) | min | Write | |
| AV | 39 | STANDBY TIMER | Standby Timer (motion) (default 15) | min | Write | |
| AV | 40 | OCCUPANCY TRIGGE | Occupancy Trigger (default 5) | min | Write | |
| AV | 41 | REL_HUMIDITY | Relative Humidity (default 0) | %RH | Read | |
| AV | 43 | MEASURED MAX | Measured Maximum (default 0) | cfm | Read | |
| AV | 44 | MEASURED MIN | Measured Minimum (default 0) | cfm | Read | |
| AV | 45 | PRI SAVE MIN FLO | Primary Saved Minimum Airflow (default 0) | cfm | Write | |
| AV | 46 | AV_46 | Analog Value #46 (default 0) | Read | ||
| AV | 47 | DAT MAXIMUM | Maximum DAT Setpoint (default 90) | °F | Write | |
| AV | 48 | CCW DMP POS | CCW Damper Position (default 0) | V | Write | |
| AV | 49 | CW DMP POS | CW Damper Position (default 0.01) | V | Write | |
| AVmin | 50 | DAMPER POSITION | Damper Position (default 0) | % | Read | |
| AV | 51 | APP_ID | Application Identification (default 0) | Write | ||
| AV | 54 | MOTOR PAUSE | Delays Motor Close to Setpoint (default 0) | s | Write | |
| AV | 55 | CHNG OVER DELAY | Heating Change Over Delay (default 3) | min | Write | |
| AV | 56 | LOW AUTO OCC | Low Limit for Auto Occupy (default 50) | cfm | Write | |
| AV | 57 | ROOM CO2 | Room CO2 Level (default 0) | ppm | Write | |
| BV | 1 | NEED AHU | Needl For AHU (default Inactive) | Write | ||
| BV | 2 | NEED COLDER SPLY | Need For Colder Air Supply (default Inactive) | Read | ||
| BV | 3 | NEED MORE STATIC | Need For More Static Pressure (default Inactive) | Read | ||
| BV | 4 | LOCAL OVRD | Local Override Mode (default Inactive) | Write | ||
| BV | 5 | MOTION OVRD | Motion Override Mode (default Inactive) | Write | ||
| BV | 6 | MOTION SENSOR | Motion Sensor (Wall Stat) (default Inactive) | Write | ||
| BV | 7 | NEED HOTTER SPLY | Need For Hotter Air Supply (default Inactive) | Read | ||
| BV | 8 | SUPPLY AIR TYPE | Supply Air Type (default Active) | Write | ||
| BV | 9 | DAT LIMITING | Discharge Air Temp Limiting (default Inactive) | Write | ||
| BV | 10 | DIR TO CLOSE | Direction to Close (default Inactive) | Write | ||
| BV | 11 | AUTO OCCUPANCY | Auto Occupancy Detection (default Inactive) | Write | ||
| BV | 12 | BALANCE MODE | Balance Mode (default Inactive) | Write | ||
| BV | 13 | DAT SENSOR | DAT Sensor Present (default Inactive) | Write | ||
| BV | 14 | PRI BAL TRIGGER | Primary Balance Trigger (default Inactive) | Write | ||
| BV | 15 | BV_15 | Binary Value #15 (default Inactive) | Read | ||
| BV | 40 | ICO_FAN | Fan Icon (default Inactive) | Read | ||
| BV | 41 | ICO_FAN_LOW | Icon Fan Low Speed (default Inactive) | Read | ||
| BV | 42 | ICO_FAN_MEDIUM | Icon Fan Medium Speed (default Inactive) | Read | ||
| BV | 43 | ICO_FAN_HIGH | Icon Fan Auto (default Inactive) | Read | ||
| BV | 44 | ICO_FAN_AUTO | Icon Fan Auto (default Inactive) | Read | ||
| BV | 45 | ICO_OCCUPIED | Icon Occupied (default Inactive) | Read | ||
| BV | 46 | ICO_STANDBY | Icon Standby (default Inactive) | Read | ||
| BV | 47 | ICO_COOLING | Icon Cooling (default Inactive) | Read | ||
| BV | 48 | ICO_HEATING | Icon Heating (default Inactive) | Read | ||
| BV | 49 | ICO_AUTO_MODE | Icon Auto Mode (default Inactive) | Read | ||
| BV | 50 | ICO_OVERRIDE | Icon Override (default Inactive) | Read | ||
| AI | 1 | SPACE SENSOR | Space Sensor (KMC Type II Deg F) | °F | Read | |
| AI | 2 | SPACE SETPOINT | Space Setpoint (TABLE_4) | Read | ||
| AImin | 3 | DISCHARGE AIR | Discharge Air Temperature (KMC10K_Type_III) | Read | ||
| AI | 7 | PRIMARY DUCT | Primary Duct Pressure (NONE) | Read | ||
| AI | 8 | PRIMARY POSITION | Primary Damper Position | Read | ||
| AO | 3 | ANALOG HEAT | Analog Heat (default 0) | % | Command | |
| AO | 4 | FAN SPEED | Fan Speed (default 0) | % | Command | |
| BO | 1 | PRI DAMPER CW | Primary Damper Clockwise (default Inactive) | Command | ||
| BO | 2 | PRI DAMPER CCW | Primary Damper Counter Clockwise (default Inactive) | Command | ||
| BO | 6 | FAN | Fan (default Inactive) | Command | ||
| BO | 7 | HT STAGE 1 | Heating Stage 1 (default Inactive) | Command | ||
| BO | 8 | HT STAGE 2 | Heating Stage 2 (default Inactive) | Command | ||
| BO | 9 | HT STAGE 3 | Heating Stage3 (default Inactive) | Command | ||
| AVmin | 1 | SPACE TEMP | Space Temperature (default 0) | °F | Read | |
| AV | 2 | STPT REFERENCE | Setpoint Reference (default 72) | °F | Write | |
| AVmin | 3 | ACT COOL STPT | Active Cooling Setpoint (default 74) | °F | Read | |
| AV | 4 | ACT HEAT STPT | Active Heating Setpoint (default 70) | °F | Read | |
| AVmin | 5 | OCC CL STPT | Occupied Cooling Setpoint (default 74) | °F | Write | |
| AVmin | 6 | OCC HT STPT | Occupied Heating Setpoint (default 70) | °F | Write | |
| AV | 7 | UNOCC CL STPT | Unoccupied Cooling Setpoint (default 80) | °F | Write | |
| AV | 8 | UNOCC HT STPT | Unoccupied Heating Setpoint (default 64) | °F | Write | |
| AV | 9 | MIN CL STPT | Minimum Cooling Setpoint (default 68) | °F | Write | |
| AV | 10 | MAX HT STPT | Maximum Heating Setpoint (default 76) | °F | Write | |
| AV | 11 | MIN STPT DIFF | Minimum Setpoint Differential (default 4) | °F | Write | |
| AV | 12 | STBY_OFFSET | Standby Offset (default 3) | °F | Write | |
| AV | 13 | MIN COOL FLOW | Minimum Cooling Flow (default 100) | cfm | Write | |
| AV | 14 | MAX COOL FLOW | Maximum Cooling Flow (default 400) | cfm | Write | |
| AV | 15 | MIN HEAT FLOW | Minimum Heating Flow (default 100) | cfm | Write | |
| AV | 16 | MAX HEAT FLOW | Maximum Heating Flow (default 400) | cfm | Write | |
| AV | 17 | AUXILLARY FLOW | Auxillary Flow (default 200) | cfm | Write | |
| AV | 18 | PRI K FACT | Primary K Factor (default 904) | Write | ||
| AV | 19 | PRI CORR SLOPE | Primary Correction Slope (default 1) | Write | ||
| AV | 20 | PRI CORR OFFST | Primary Correction Offset (default 0) | cfm | Write | |
| AV | 21 | PRI LO FLOW CORR | Primary Low Flow Correction (default 1) | Write | ||
| AVmin | 22 | PRI FLOW STPT | Primary Flow Setpoint (default 0) | cfm | Write | |
| AV | 23 | PRI RAW FLOW | Primary Raw Flow (default 0) | cfm | Read | |
| AVmin | 24 | PRI ACTUAL FLOW | Primary Actual Flow (default 0) | cfm | Read | |
| AV | 25 | AV_25 | Analog Value #25 (default 0) | Read | ||
| AV | 32 | MIN FAN SPEED | Minimum Fan Speed (default 25) | % | Write | |
| AV | 33 | MAX FAN SPEED | Maximum Fan Speed (default 100) | % | Write | |
| AV | 34 | AV_34 | Analog Value #34 (default 0) | Read | ||
| AV | 36 | DAT RESET | Discharge Air Temp Setpoint (default 90) | °F | Write | |
| MVmin | 1 | OCCUPIED MODE | Occupied Mode (default OCCUPIED) | Write | 1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE, 5=MOTION OVERRIDE | |
| MV | 2 | FAN CONFIG | Fantype Configuration (default NONE) | Write | 1=NONE, 2=SERIES, 3=PARALLEL | |
| MV | 3 | REHEAT | Reheat Type (default NONE) | Write | 1=NONE, 2=STAGED, 3=MODULATING, 4=FLOATING, 5=TIME PROP | |
| MV | 4 | STPT_MODE | User Setpoint Mode (default Heat) | Write | 1=Heat, 2=Cool, 3=Unocc Heat, 4=Unocc Cool | |
| MVmin | 8 | OCCUPIED STATE | Occupied State (default OCCUPIED) | Read | 1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE | |
| MV | 10 | WALL SENSOR | Wall Sensor Type (default STE-9001 TEMP) | Write | 1=STE-9001 TEMP, 2=STE-9021 HUMIDITY, 3=STE-9201 MOTION, 4=STE-9221 HUMIDITY/MOTION, 5=STE-9301 CO2, 6=STE-9321 HUMIDITY/CO2, 7=STE-9501 MOTION/CO2, 8=STE-9521 HUMIDITY/MOTION/CO2, 9=STE-6014/7, 10=STE-6010, 11=NONE |
No points match these filters.
Object ID lookup: KMC Controls BAC-9001A VAV Single Duct point IDs by name
AV37SAT CHANGEOVERAV38LOCAL OVRD TIMEAV39STANDBY TIMERAV40OCCUPANCY TRIGGEAV41REL_HUMIDITYAV43MEASURED MAXAV44MEASURED MINAV45PRI SAVE MIN FLOAV46AV_46AV47DAT MAXIMUMAV48CCW DMP POSAV49CW DMP POSAV50DAMPER POSITIONAV51APP_IDAV54MOTOR PAUSEAV55CHNG OVER DELAYAV56LOW AUTO OCCAV57ROOM CO2BV1NEED AHUBV2NEED COLDER SPLYBV3NEED MORE STATICBV4LOCAL OVRDBV5MOTION OVRDBV6MOTION SENSORBV7NEED HOTTER SPLYBV8SUPPLY AIR TYPEBV9DAT LIMITINGBV10DIR TO CLOSEBV11AUTO OCCUPANCYBV12BALANCE MODEBV13DAT SENSORBV14PRI BAL TRIGGERBV15BV_15BV40ICO_FANBV41ICO_FAN_LOWBV42ICO_FAN_MEDIUMBV43ICO_FAN_HIGHBV44ICO_FAN_AUTOBV45ICO_OCCUPIEDBV46ICO_STANDBYBV47ICO_COOLINGBV48ICO_HEATINGBV49ICO_AUTO_MODEBV50ICO_OVERRIDEAI1SPACE SENSORAI2SPACE SETPOINTAI3DISCHARGE AIRAI7PRIMARY DUCTAI8PRIMARY POSITIONAO3ANALOG HEATAO4FAN SPEEDBO1PRI DAMPER CWBO2PRI DAMPER CCWBO6FANBO7HT STAGE 1BO8HT STAGE 2BO9HT STAGE 3AV1SPACE TEMPAV2STPT REFERENCEAV3ACT COOL STPTAV4ACT HEAT STPTAV5OCC CL STPTAV6OCC HT STPTAV7UNOCC CL STPTAV8UNOCC HT STPTAV9MIN CL STPTAV10MAX HT STPTAV11MIN STPT DIFFAV12STBY_OFFSETAV13MIN COOL FLOWAV14MAX COOL FLOWAV15MIN HEAT FLOWAV16MAX HEAT FLOWAV17AUXILLARY FLOWAV18PRI K FACTAV19PRI CORR SLOPEAV20PRI CORR OFFSTAV21PRI LO FLOW CORRAV22PRI FLOW STPTAV23PRI RAW FLOWAV24PRI ACTUAL FLOWAV25AV_25AV32MIN FAN SPEEDAV33MAX FAN SPEEDAV34AV_34AV36DAT RESETMV1OCCUPIED MODEMV2FAN CONFIGMV3REHEATMV4STPT_MODEMV8OCCUPIED STATEMV10WALL SENSOR
Integration notes
- Table 'BAC-9001 PRESSURE INDEPENDENT VAV, SINGLE DUCT OBJECTS', pdf pages 42-43 of the guide.
- The guide gives no read/write column; access is inferred (inputs read-only, outputs commandable, calculated values and display icons read-only, setpoints and configuration writable).
- Descriptions carry the factory default from the guide; multi-state state lists are numbered 1..n in printed order (the printed defaults use that numbering).
- Objects depend on controller model and application, and can be deleted or created in KMC Connect, Converge or TotalControl.
- Placeholder objects named AV_nn / BV_nn ('Analog Value #nn') are spare objects in the default database.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-9001A pressure independent VAV, single duct (Gen6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)
How many BACnet points does the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) have?
This list has 92 BACnet objects: 5 analog inputs, 2 analog outputs, 47 analog values, 6 binary outputs, 26 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) BACnet points are writable?
59 of the 92 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6) BACnet documentation?
The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.
What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)?
Start with MV 1 OCCUPIED MODE (Occupancy command); AV 5 OCC CL STPT (Occupied cooling setpoint, °F); AV 6 OCC HT STPT (Occupied heating setpoint, °F); AV 1 SPACE TEMP (Space temperature, °F); AV 3 ACT COOL STPT (Active cooling setpoint, °F); MV 8 OCCUPIED STATE (Current occupancy state); AV 24 PRI ACTUAL FLOW (Measured primary airflow); AV 22 PRI FLOW STPT (Airflow setpoint); AV 50 DAMPER POSITION (Damper position); AI 3 DISCHARGE AIR (Discharge air temperature, °F).
How do I enable BMS control of the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)?
Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.
Can the BMS supply sensor values to the KMC Controls Conquest BAC-9001A pressure independent VAV, single duct (Gen6)?
Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.
How do I check these points on the real Conquest BAC-9001A pressure independent VAV, single duct (Gen6)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More KMC Controls BACnet points lists
- Fan coil unit controller (four-pipe)
KMC Controls BAC-4000 AppStat, four-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the four-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Heat pump controller / thermostat
KMC Controls BAC-4000 AppStat, heat pump application
KMC AppStat (BAC-4000 series) room controllers configured for the heat pump application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Rooftop unit controller / thermostat
KMC Controls BAC-4000 AppStat, rooftop unit application
KMC AppStat (BAC-4000 series) room controllers configured for the rooftop unit application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - Fan coil unit controller (two-pipe)
KMC Controls BAC-4000 AppStat, two-pipe fan coil application
KMC AppStat (BAC-4000 series) room controllers configured for the two-pipe fan coil application.
Also known as: BAC-4000, AppStat, KMC AppStat, BAC-4001CW, BAC-4002CW, BAC-4003CW, BAC-4007CW - VAV terminal unit controller
KMC Controls BAC-7000 series VAV controllers (BAC-7001 / 7003 / 7051 / 7053)
KMC BAC-7001, BAC-7003, BAC-7051 and BAC-7053 VAV controllers with the factory VAV applications version 2.2 (pressure independent or dependent, with reheat).
Also known as: BAC-7001, BAC-7003, BAC-7051, BAC-7053, BAC-7000, AN0311A - Programmable general purpose controller (room thermostat application)
KMC Controls Conquest BAC-5901 general purpose controller (Gen6 default application)
KMC Conquest BAC-5901 controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-5901, BAC-5901A, BAC-5901AC, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (dual duct)
KMC Controls Conquest BAC-9001A pressure independent VAV, dual duct (Gen6)
KMC Conquest BAC-9001A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9001A, BAC-9001, dual duct VAV, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (pressure dependent)
KMC Controls Conquest BAC-9021A pressure dependent VAV, single duct (Gen6)
KMC Conquest BAC-9021A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9021A, BAC-9021, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (four-pipe)
KMC Controls Conquest BAC-9301A four-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - Fan coil unit controller (two-pipe)
KMC Controls Conquest BAC-9301A two-pipe fan coil (Gen6)
KMC Conquest BAC-9301A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9301, BAC-9301AC, KMC Conquest, Conquest Gen6, AG250415B - VAV terminal unit controller (remote actuator)
KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)
KMC Conquest BAC-9311A controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9311A, BAC-9311, KMC Conquest, Conquest Gen6, AG250415B - Heat pump unit controller
KMC Controls Conquest BAC-93x1A heat pump unit (Gen6)
KMC Conquest BAC-93x1A (BAC-9301A / BAC-9311A) controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B - Rooftop unit controller
KMC Controls Conquest BAC-93x1A rooftop unit (Gen6)
KMC Conquest BAC-93x1A (BAC-9301A / BAC-9311A) controllers running the factory Gen6 application for this equipment type.
Also known as: BAC-9301A, BAC-9311A, BAC-93x1A, KMC Conquest, Conquest Gen6, AG250415B - VAV box controller
KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)
KMC SimplyVAV controller-actuators for single duct cooling/heating, fan powered with reheat and dual duct VAV boxes.
Also known as: SimplyVAV, Simply VAV, BAC-8001, BAC-8005, BAC-8007, BAC-8205
Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.