VAV terminal unit controller (remote actuator) · BACnet points list

KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) BACnet points list

Updated 6 November 2026

Short answer

KMC Conquest controllers ship with a default application per equipment type. This table lists the objects of the Vav With Remote Actuator application: inputs, outputs, setpoints and configuration values, binary flags and multi-state modes, with their factory defaults. Conquest controllers talk BACnet MS/TP, and the Ethernet models BACnet IP.

This page lists 90 BACnet objects for the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.

Manufacturer
KMC Controls
Model
Conquest BAC-9311A VAV with remote actuator (Gen6)
Equipment
VAV terminal unit controller (remote actuator)
Equipment type
Valves & actuators
BACnet objects
90 (58 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Gen6 application
Also known as
BAC-9311A, BAC-9311, KMC Conquest, Conquest Gen6, AG250415B
Source document
Conquest Gen6 Controller Application Guide · AG250415B
Download CSV 90 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.

BMS integration notes: KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)

Integration in brief

Discover the controller, check the application objects in KMC Connect if any are missing, then map occupancy, occupied setpoints and mode from the BMS and read space temperature and the equipment status points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1OCCUPIED MODEOccupancy commandWrite
AV 5OCC CL STPTOccupied cooling setpoint, °FWrite
AV 6OCC HT STPTOccupied heating setpoint, °FWrite
AV 1SPACE TEMPSpace temperature, °FRead
AV 3ACT COOL STPTActive cooling setpoint, °FRead
MV 8OCCUPIED STATECurrent occupancy stateRead
AV 24PRI ACTUAL FLOWMeasured primary airflowRead
AV 22PRI FLOW STPTAirflow setpointWrite
AI 8PRIMARY POSITIONDamper positionRead
AI 3DISCHARGE AIRDischarge air temperature, °FRead

Enable & remote start

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Sensors & values from the BMS

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

Network setup

Watch out for

KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

90 of 90 shown
Type
Multi-state
Access
Show
KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) BACnet Points List
DescriptionStates
AI1SPACE SENSORSpace Sensor (KMC Type II Deg F)°FRead
AI2SPACE SETPOINTSpace Setpoint (Table 4)Read
AImin3DISCHARGE AIRDischarge Air Temperature (KMC Type III Deg F)°FRead
AImin8PRIMARY POSITIONPrimary Damper Position (0-12 Volts)Read
AO7ANALOG HEATAnalog Heat (default 0)0-100 % (0-10 V)Command
AO8FAN SPEEDFan Speed (default 0)%Command
AO9AO_09Analog Output #9 (default 0)Command
BO1FANFan (default Inactive)Command
BO2HT STAGE 1Heating Stage 1 (default Inactive)Command
BO3HT STAGE 2Heating Stage 2 (default Inactive)Command
BO4HT STAGE 3Heating Stage3 (default Inactive)Command
BO5PRI DAMPER CWPrimary Damper Clockwise (default Inactive)Command
BO6PRI DAMPER CCWPrimary Damper Counter Clockwise (default Inactive)Command
AVmin1SPACE TEMPSpace Temperature (default 0)°FRead
AV2STPT REFERENCESetpoint Reference (default 72)°FWrite
AVmin3ACT COOL STPTActive Cooling Setpoint (default 74)°FRead
AV4ACT HEAT STPTActive Heating Setpoint (default 70)°FRead
AVmin5OCC CL STPTOccupied Cooling Setpoint (default 74)°FWrite
AVmin6OCC HT STPTOccupied Heating Setpoint (default 70)°FWrite
AV7UNOCC CL STPTUnoccupied Cooling Setpoint (default 80)°FWrite
AV8UNOCC HT STPTUnoccupied Heating Setpoint (default 64)°FWrite
AV9MIN CL STPTMinimum Cooling Setpoint (default 68)°FWrite
AV10MAX HT STPTMaximum Heating Setpoint (default 76)°FWrite
AV11MIN STPT DIFFMinimum Setpoint Differential (default 4)°FWrite
AV12STBY_OFFSETStandby Offset (default 3)°FWrite
AV13MIN COOL FLOWMinimum Cooling Flow (default 100)cfmWrite
AV14MAX COOL FLOWMaximum Cooling Flow (default 400)cfmWrite
AV15MIN HEAT FLOWMinimum Heating Flow (default 100)cfmWrite
AV16MAX HEAT FLOWMaximum Heating Flow (default 400)cfmWrite
AV17AUXILLARY FLOWAuxillary Flow (default 200)cfmWrite
AV18PRI K FACTPrimary K Factor (default 904)Write
AV19PRI CORR SLOPEPrimary Correction Slope (default 1)Write
AV20PRI CORR OFFSTPrimary Correction Offset (default 0)cfmWrite
AV21PRI LO FLOW CORRPrimary Low Flow Correction (default 1)Write
AVmin22PRI FLOW STPTPrimary Flow Setpoint (default 0)cfmWrite
AV23PRI RAW FLOWPrimary Raw Flow (default 0)cfmRead
AVmin24PRI ACTUAL FLOWPrimary Actual Flow (default 0)cfmRead
AV25AV_25Analog Value #25 (default 0)Read
AV32MIN FAN SPEEDMinimum Fan Speed (default 25)%Write
AV33MAX FAN SPEEDMaximum Fan Speed (default 100)%Write
AV34AV_34Analog Value #34 (default 0)Read
AV36DAT STPTDischarge Air Temp Setpoint (default 90)°FWrite
AV37SAT CHANGEOVERSAT Changeover Temperature (default 72)°FWrite
AV38LOCAL OVRD TIMELocal Override Timer (default 60)minWrite
AV39STANDBY TIMERStandby Timer (motion) (default 15)minWrite
AV40OCCUPANCY TRIGGEOccupancy Trigger (default 5)minWrite
AV41REL_HUMIDITYRelative Humidity (default 0)%RHRead
AV43MEASURED MAXMeasured Maximum (default 0)cfmRead
AV44MEASURED MINMeasured Minimum (default 0)cfmRead
AV45PRI SAVE MIN FLOPrimary Saved Minimum Airflow (default 0)cfmWrite
AV46AV_46Analog Value #46 (default 0)Read
AV47DAT MAXIMUMMaximum DAT Setpoint (default 90)°FWrite
AV48CCW DMP POSCCW Damper Position (default 0)VWrite
AV49CW DMP POSCW Damper Position (default 0.01)VWrite
AV50DAMPER POSITIONDamper Position (default 0)%Read
AV51APP_IDApplication Identification (default 0)Write
AV55CHNG OVER DELAYHeating Change Over Delay (default 3)minWrite
AV56LOW AUTO OCCLow Limit for Auto Occupy (default 50)cfmWrite
AV57ROOM CO2Room CO2 Level (default 0)ppmWrite
BV1NEED AHUNeedl For AHU (default Inactive)Write
BV2NEED COLDER SPLYNeed For Colder Air Supply (default Inactive)Read
BV3NEED MORE STATICNeed For More Static Pressure (default Inactive)Read
BV4LOCAL OVRDLocal Override Mode (default Inactive)Write
BV5MOTION OVRDMotion Override Mode (default Inactive)Write
BV6MOTION SENSORMotion Sensor (Wall Stat) (default Inactive)Write
BV7NEED HOTTER SPLYNeed For Hotter Air Supply (default Inactive)Read
BV8SUPPLY AIR TYPESupply Air Type (default Active)Write
BV9DAT LIMITINGDischarge Air Temp Limiting (default Inactive)Write
BV10DIRECTION-CLOSEClockwise Close (default Inactive)Write
BV11AUTO OCCUPANCYAuto Occupancy Detection (default Inactive)Write
BV12BALANCE MODEBalance Mode (default Inactive)Write
BV13DAT SENSORDAT Sensor Present (default Inactive)Write
BV14PRI BAL TRIGGERPrimary Balance Trigger (default Inactive)Write
BV15BV_15Binary Value #15 (default Inactive)Read
BV40ICO_FANFan Icon (default Inactive)Read
BV41ICO_FAN_LOWIcon Fan Low Speed (default Inactive)Read
BV42ICO_FAN_MEDIUMIcon Fan Medium Speed (default Inactive)Read
BV43ICO_FAN_HIGHIcon Fan Auto (default Inactive)Read
BV44ICO_FAN_AUTOIcon Fan Auto (default Inactive)Read
BV45ICO_OCCUPIEDIcon Occupied (default Inactive)Read
BV46ICO_STANDBYIcon Standby (default Inactive)Read
BV47ICO_COOLINGIcon Cooling (default Inactive)Read
BV48ICO_HEATINGIcon Heating (default Inactive)Read
BV49ICO_AUTO_MODEIcon Auto Mode (default Inactive)Read
BV50ICO_OVERRIDEIcon Override (default Inactive)Read
MVmin1OCCUPIED MODEOccupied Mode (default OCCUPIED)Write1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE, 5=MOTION OVERRIDE
MV2FAN CONFIGFantype Configuration (default NONE)Write1=NONE, 2=SERIES, 3=PARALLEL
MV3REHEATReheat Type (default NONE)Write1=NONE, 2=STAGED, 3=MODULATING, 4=FLOATING, 5=TIME PROP
MVmin8OCCUPIED STATEOccupied State (default OCCUPIED)Read1=OCCUPIED, 2=STANDBY, 3=UNOCCUPIED, 4=LOCAL OVERRIDE
MV6WALL SENSORWall Sensor Type (default STE-9001 Temp)Write1=STE-9001 Temp, 2=STE-9021 Humidity, 3=STE-9201 Motion, 4=STE-9221 Humidity/Motion, 5=STE-9301 CO2, 6=STE-9321 Humidity/CO2, 7=STE-9501 Motion/CO2, 8=STE-9521 Humidity/Motion/CO2, 9=STE-6014/7, 10=STE-6010, 11=None
Object ID lookup: KMC Controls Conquest BAC-9311A VAV with remote actuator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conquest BAC-9311A VAV with remote actuator (Gen6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)

How many BACnet points does the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) have?

This list has 90 BACnet objects: 4 analog inputs, 3 analog outputs, 46 analog values, 6 binary outputs, 26 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) BACnet points are writable?

58 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6) BACnet documentation?

The source is Conquest Gen6 Controller Application Guide (AG250415B), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/AG_Conquest-Controllers-Gen6_SAG250415B.pdf.

What are the minimum BACnet points to integrate the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)?

Start with MV 1 OCCUPIED MODE (Occupancy command); AV 5 OCC CL STPT (Occupied cooling setpoint, °F); AV 6 OCC HT STPT (Occupied heating setpoint, °F); AV 1 SPACE TEMP (Space temperature, °F); AV 3 ACT COOL STPT (Active cooling setpoint, °F); MV 8 OCCUPIED STATE (Current occupancy state); AV 24 PRI ACTUAL FLOW (Measured primary airflow); AV 22 PRI FLOW STPT (Airflow setpoint); AI 8 PRIMARY POSITION (Damper position); AI 3 DISCHARGE AIR (Discharge air temperature, °F).

How do I enable BMS control of the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)?

Occupancy is controlled through value objects such as MSV1 Occupied Mode and BV6 motion sensor; KMC's troubleshooting section says to check these when occupancy does not change.

Can the BMS supply sensor values to the KMC Controls Conquest BAC-9311A VAV with remote actuator (Gen6)?

Room temperature and setpoint come from STE-9000 NetSensors (mapped to value objects) or from AI1/AI2 analog sensors.

How do I check these points on the real Conquest BAC-9311A VAV with remote actuator (Gen6)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More KMC Controls BACnet points lists

Source: Conquest Gen6 Controller Application Guide · AG250415B. Object names, instances and units are reproduced as published; descriptions are our own.