VAV box controller · BACnet points list

KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) BACnet points list

Updated 4 November 2026

Short answer

SimplyVAV controllers are BACnet MS/TP application specific controllers (B-ASC) with a built-in damper actuator, set up from the STE-8001 wall sensor. The guide lists the objects most likely to be monitored from a BACnet workstation: physical inputs and outputs, setpoint and airflow AVs, status BVs, four multistate values and three PID loops. Objects use short instances and uppercase names (AV5 OCC CL STPT). Not every object exists on every model.

This page lists 76 BACnet objects for the KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from KMC Controls’s own free documentation, linked below.

Manufacturer
KMC Controls
Model
SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)
Equipment
VAV box controller
Equipment type
VAV boxes & fan coils
BACnet objects
76 (36 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SimplyVAV, Simply VAV, BAC-8001, BAC-8005, BAC-8007, BAC-8205
Source document
Application and Installation Guide: SimplyVAV Controllers · Revision N
Download CSV 76 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against KMC Controls’s current documentation and the live device before use. Not official KMC Controls information. Terms of use.

BMS integration notes: KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)

Integration in brief

Set the device instance, MAC address and baud from the STE-8001 sensor (COMM menu, Password 2) before putting the controller on the MS/TP trunk. Monitor AV 1 space temperature, AV 3/AV 4 active setpoints, AV 24 actual airflow and AV 50 damper position; the occupied setpoints are AV 5/AV 6. BV 1-3 and BV 7 are reset requests for the air handler.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1OCCUPIED MODEOccupancy mode of the boxWrite
AV 5OCC CL STPTOccupied cooling setpointWrite
AV 6OCC HT SPTOccupied heating setpointWrite
AV 1SPACE TEMPSpace temperatureRead
AV 3ACT COOL STPTCooling setpoint in useRead
AV 4ACT HEAT STPTHeating setpoint in useRead
AV 24PRI ACTUAL FLOWMeasured primary airflowRead
AV 50DAMPER POSITIONDamper positionRead
BV 1NEED AHUBox needs the air handler runningRead

Network setup

Watch out for

KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

76 of 76 shown
Type
Multi-stateOther
Access
Show
KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) BACnet Points List
DescriptionStates
AI1DISCHARGE AIRDischarge air temperature, KMC 10K Type IIIRead
AI2SPACE SENSORSpace sensor, KMC Type IIRead
AI3SETPOINT OFFSETSetpoint offset input (table 4)Read
AI4PRIMARY DUCTPrimary Duct PressureRead
AI5SECONDARY DUCTSecondary Duct PressureRead
AO3ANALOG HEATAnalog heat output, 0-100%%Read
AO4FAN SPEEDFan speed output, 0-100%%Read
BO1DAMPER CWDamper ClockwiseRead
BO2DAMPER CCWDamper Counter ClockwiseRead
BO5FANFanRead
BO6HT STAGE 1Heating Stage 1Read
BO7HT STAGE 2Heating Stage 2Read
BO8HT STAGE 3Heating Stage3Read
AVmin1SPACE TEMPSpace TemperatureRead
AV2STPT OFFSETSetpoint OffsetRead
AVmin3ACT COOL STPTActive Cooling SetpointRead
AVmin4ACT HEAT STPTActive Heating SetpointRead
AVmin5OCC CL STPTOccupied Cooling SetpointWrite
AVmin6OCC HT SPTOccupied Heating SetpointWrite
AV7UNOCC CL STPTUnoccupied Cooling SetpointWrite
AV8UNOCC HT STPTUnoccupied Heating SetpointWrite
AV9MIN CL STPTMinimum Cooling SetpointWrite
AV10MAX HT STPTMaximum Heating SetpointWrite
AV11MIN STPT DIFFMinimum Setpoint DifferentialWrite
AV12STBY OFFSETStandby OffsetWrite
AV13MIN COOL FLOWMinimum Cooling FlowWrite
AV14MAX COOL FLOWMaximum Cooling FlowWrite
AV15MIN HEAT FLOWMinimum Heating FlowWrite
AV16MAX HEAT FLOWMaximum Heating FlowWrite
AV17AUXILIARY FLOWAuxiliary FlowWrite
AV18PRI K FACTPrimary K FactorWrite
AV19PRI CORR SLOPEPrimary Correction SlopeWrite
AV20PRI CORR OFFSTPrimary Correction OffsetWrite
AV21PRI LO FLOW CORRPrimary Low Flow CorrectionWrite
AV22PRI FLOW STPTPrimary Flow SetpointWrite
AV23PRI RAW FLOWPrimary Raw FlowRead
AVmin24PRI ACTUAL FLOWPrimary Actual FlowRead
AV32MIN FAN SPEEDMinimum Fan SpeedWrite
AV33MAX FAN SPEEDMaximum Fan SpeedWrite
AV36DAT STPTDischarge Air Temp SetpointWrite
AV37SAT CHANGEOVERSAT Changeover TemperatureWrite
AV38LOCAL OVRD TIMELocal Override TimerRead
AV39STANDBY TIMEStandby timer (motion)Write
AV40STANDBY TRIGGERStandby TriggerWrite
AV43MEASURED MAXMeasured MaximumRead
AV44MEASURED MINMeasured MinimumRead
AV45PRI SAVE MIN FLOPrimary Saved Minimum AirflowRead
AV47DAT MAXIMUMMaximum DAT SetpointWrite
AV48CW DMP POSCW Damper PositionRead
AV49CCW DMP POSCCW Damper PositionRead
AVmin50DAMPER POSITIONDamper PositionRead
AV51ApplicationIDApplication IDRead
AV54MOTOR PAUSEMotor pause (printed description: Analog Value #54)Read
AV55CHNG_OVER_DELAYCooling Changeover DelayWrite
AV56LOW AUTO OCCLow Limit for Auto OccupyWrite
BVmin1NEED AHUNeed For AHURead
BV2NEED COLDER SPLYNeed For Colder Air SupplyRead
BV3NEED MORE STATICNeed for more duct static (printed description: Need For AHU)Read
BV4LOCAL OVRDLocal Override ModeRead
BV5MOTION OVRDMotion Override ModeRead
BV6MOTION SENSORMotion sensor (wall stat)Read
BV7NEED HOTTER SPLYNeed For Hotter Air SupplyRead
BV8CHANGEOVER MODESAT Changeover ModeRead
BV9DAT LIMITINGDischarge Air Temp LimitingRead
BV10CLOCKWISE CLOSEClockwise CloseWrite
BV11AUTO OCCUPANCYAuto Occupancy DetectionWrite
BV12BALANCE MODEBalance ModeWrite
BV13DAT SENSORDAT Sensor PresentWrite
BV14PRI BAL TRIGGERPrimary Balance TriggerWrite
MVmin1OCCUPIED MODEOccupied modeWrite
MV2FAN CONFIGFan type configurationWrite
MV3REHEATReheat typeWrite
MV6WALL SENSORWall sensor (printed description: Multi-state Value #6)Write
LO1CL LOOPCooling PID loopRead
LO2HT LOOPHeating PID loopRead
LO3DAT LoopDischarge air temperature PID loopRead
Object ID lookup: KMC Controls SimplyVAV point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)

How many BACnet points does the KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) have?

This list has 76 BACnet objects: 5 analog inputs, 2 analog outputs, 42 analog values, 6 binary outputs, 14 binary values, 3 loops, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) BACnet points are writable?

36 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205) BACnet documentation?

The source is Application and Installation Guide: SimplyVAV Controllers (Revision N), published free by KMC Controls at https://www.kmccontrols.com/wp-content/uploads/kmc_documents/APPLICATION-AND-INSTALLATION-GUIDE-SimplyVAV-Controllers-Rev-N.pdf.

What are the minimum BACnet points to integrate the KMC Controls SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)?

Start with MV 1 OCCUPIED MODE (Occupancy mode of the box); AV 5 OCC CL STPT (Occupied cooling setpoint); AV 6 OCC HT SPT (Occupied heating setpoint); AV 1 SPACE TEMP (Space temperature); AV 3 ACT COOL STPT (Cooling setpoint in use); AV 4 ACT HEAT STPT (Heating setpoint in use); AV 24 PRI ACTUAL FLOW (Measured primary airflow); AV 50 DAMPER POSITION (Damper position); BV 1 NEED AHU (Box needs the air handler running).

How do I check these points on the real SimplyVAV (BAC-8001 / 8005 / 8007 / 8205)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More KMC Controls BACnet points lists

Source: Application and Installation Guide: SimplyVAV Controllers · Revision N. Object names, instances and units are reproduced as published; descriptions are our own.