Room panel (thermostat display) · BACnet points list

iSMA CONTROLLI Touch Point room panel BACnet points list

Updated 12 November 2026

Short answer

The Touch Point room panel exposes built-in temperature, humidity and CO2 readings, a temperature setpoint with offset, fan mode and speed, occupancy mode and status, a CO2 alarm, the navigation LED colour and the display, keypad and buzzer settings as BACnet objects. Most objects are panel configuration; the room values and setpoint are what a BMS normally maps.

This page lists 53 BACnet objects for the iSMA CONTROLLI Touch Point room panel — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.

Manufacturer
iSMA CONTROLLI
Model
Touch Point room panel
Equipment
Room panel (thermostat display)
Equipment type
Thermostats, sensors & meters
BACnet objects
53 (44 writable)
Transport
BACnet MS/TP
Firmware
Touch Point Software manual V1.3
Also known as
Touch Point, iSMA Touch Point, Touch Point VAV, Touch Point Software V1.3
Source document
Touch Point Software User Manual V1.3 - List of BACnet Objects · rev. V1.3
Download CSV 53 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.

BMS integration notes: iSMA CONTROLLI Touch Point room panel

Integration in brief

Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode; BI 0 is the CO2 alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 4OCCUPANCY_MODEOccupancy modeWrite
AV 56SETPOINT_VALUETemperature setpointWrite
MV 1FAN_MODEFan modeWrite
AI 4TEMPERATURE_SENSORRoom temperatureRead
AI 3EFFECTIVE_SETPOINTEffective setpoint (setpoint plus offset)Read
MV 3OCCUPANCY_CURRENT_STATUSCurrent occupancy statusWrite
AI 5HUMIDITY_SENSORRoom humidityRead
AI 6CO2_SENSORRoom CO2Read
BI 0ALARM_STATUSCO2 alarm statusRead

Enable & remote start

BO 62 OCCUPANCY_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.

Network setup

Watch out for

iSMA CONTROLLI Touch Point room panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

53 of 53 shown
Type
Access
Show
iSMA CONTROLLI Touch Point room panel BACnet Points List
DescriptionStates
AI0LIVE_TIMEUptime of the panel in secondssRead
MI1SENSORSInforms about built-in sensorsRead
AI1BACKLIGHT_LCDActual display illumination valueRead
AI2BACKLIGHT_KEYPADActual keypad illumination valueRead
BO0BUZZER_ACTIVEActivates (1) or deactivates (0) a buzzer; default 1Write
BO3LCD_BACKLIGHT_ACTIVESwitches the LCD background illumination on (1); default 1Write
BO4KEYPAD_BACKLIGHT_ACTIVESwitches the keypad background illumination on (1); default 1Write
BO5CO2_ALARM_LCDSwitches on the function of LCD background illumination flashing when CO2 alarmWrite
BO6CO2_ALARM_BUZZERSwitches on a buzzer when the CO2 alarm occursWrite
BO63CO2_ALARM_CONFIRMEnable confirmation of the CO2 alarm with any button of the panelWrite
BO11PANEL_OFFSwitches the panel off (1); default 0Write
BO12KEYPAD_OFFSwitches the panel keypad off (1); default 0Write
AO3BACKLIGHT_LCD_ACTIVEContains a value of the LCD display illumination in the active modeWrite
AO4BACKLIGHT_LCD_IDLEContains a value of the LCD display illumination in the idle modeWrite
AO5BACKLIGHT_LCD_STANDBYContains a value of the LCD display illumination in the standby modeWrite
AO6BACKLIGHT_LCD_TIME_TO_IDLESets the time after which the LCD display goes from the activeWrite
AO7BACKLIGHT_LCD_TIME_TO_STANDBYSets the time after which the LCD display goes from the idleWrite
AO8BACKLIGHT_KEYPAD_ACTIVEContains a value of the keypad illumination in the active mode; default 10Write
AO9BACKLIGHT_KEYPAD_IDLEContains a value of the keypad illumination in the idle mode; default 40Write
AO10BACKLIGHT_KEYPAD_STANDBYContains a value of the keypad illumination in the standby mode; default 60Write
AO11BACKLIGHT_KEYPAD_TIME_TO_IDLESets the time after which the keypad goes from the active modeWrite
AO12BACKLIGHT_KEYPAD_TIME_TO_STANDBYSets the time after which the keypad goes from the idle modeWrite
AO13REFRESH_TIMESets the duration of the display time of particular parameters; default 5Write
BO22ECOSwitches on an ECO LEDWrite
AO17EXIT_EDIT_TIMESets the time after which edition of any editable parameter is finishedWrite
AO19CO2_SETPOINT_FOR_ALARMCO2 alarm setpoint; default 1500Write
AO20CO2_HYSTERESIS_FOR_ALARMCO2 alarm hysteresis; default 100Write
BImin0ALARM_STATUSCO2 current alarm statusRead
MV5NAVIGATIONAL_LED_MODESets a mode of the navigational LED; default 1Write
AO22NAVIGATIONAL_LED_BRIGHTNESSNavigational LED brightness; default 100Write
AO23NAVIGATIONAL_LED_REDNavigational LED color - red component intensity; default 100Write
AO24NAVIGATIONAL_LED_GREENNavigational LED color - green component intensity; default 100Write
AO25NAVIGATIONAL_LED_BLUENavigational LED color - blue component intensity; default 100Write
AImin4TEMPERATURE_SENSORActual temperature sensor value with offset°CRead
AImin5HUMIDITY_SENSORActual humidity sensor value with offset%RHRead
AImin6CO2_SENSORActual CO2 sensor value with offsetppmRead
AO27BUZZER_VOLUMEBuzzer volume (%); default 50Write
AO28BUZZER_FREQUENCYBuzzer frequency (Hz); default 400Write
AVmin56SETPOINT_VALUETemperature setpoint valueWrite
AImin3EFFECTIVE_SETPOINTSum of setpoint and offset valuesRead
AV57DEFAULT_SETPOINTDefault temperature setpoint; default 210Write
AV58OFFSET_SETPOINTTemperature offset for setpoint; default 0Write
AV59OFFSET_RANGELimits offset value; default 30Write
BO55OPERATING_MODESets the operating mode of the temperature setpoint configurationWrite
BO56SETPOINT_DISPLAYConfigures the temperature setpoint displayWrite
MV0FAN_CURRENT_SPEEDNot available for the Touch Point VAV series; default 0Write
MVmin1FAN_MODENot available for the Touch Point VAV series; default 1Write
MV2FAN_TYPENot available for the Touch Point VAV seriesWrite
BO58FAN_PART_EDITABLENot available for the Touch Point VAV seriesWrite
BO60FAN_CONFIG_LOCAL_MODENot available for the Touch Point VAV seriesWrite
MVmin3OCCUPANCY_CURRENT_STATUSOccupancy statusWrite
MVmin4OCCUPANCY_MODEOccupancy modeWrite
BO62OCCUPANCY_CONFIG_LOCAL_MODELocal/BMS modeWrite
Object ID lookup: iSMA CONTROLLI Touch Point room panel point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Touch Point room panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the iSMA CONTROLLI Touch Point room panel

How many BACnet points does the iSMA CONTROLLI Touch Point room panel have?

This list has 53 BACnet objects: 7 analog inputs, 20 analog outputs, 4 analog values, 1 binary input, 14 binary outputs, 1 multi-state input, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which iSMA CONTROLLI Touch Point room panel BACnet points are writable?

44 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official iSMA CONTROLLI Touch Point room panel BACnet documentation?

The source is Touch Point Software User Manual V1.3 - List of BACnet Objects, revision V1.3, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/touch-point-software/V1.3/list-of-bacnet-obejcts.

What are the minimum BACnet points to integrate the iSMA CONTROLLI Touch Point room panel?

Start with MV 4 OCCUPANCY_MODE (Occupancy mode); AV 56 SETPOINT_VALUE (Temperature setpoint); MV 1 FAN_MODE (Fan mode); AI 4 TEMPERATURE_SENSOR (Room temperature); AI 3 EFFECTIVE_SETPOINT (Effective setpoint (setpoint plus offset)); MV 3 OCCUPANCY_CURRENT_STATUS (Current occupancy status); AI 5 HUMIDITY_SENSOR (Room humidity); AI 6 CO2_SENSOR (Room CO2); BI 0 ALARM_STATUS (CO2 alarm status).

How do I enable BMS control of the iSMA CONTROLLI Touch Point room panel?

BO 62 OCCUPANCY_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.

How do I check these points on the real Touch Point room panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More iSMA CONTROLLI BACnet points lists

Source: Touch Point Software User Manual V1.3 - List of BACnet Objects · rev. V1.3. Object names, instances and units are reproduced as published; descriptions are our own.