Easy BACnet
  1. Home
  2. BACnet points lists
  3. iSMA CONTROLLI
  4. Control Point room panel (incl. Control Point VAV)

Room panel (thermostat display) · BACnet points list

iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet points list

Updated 12 November 2026

Short answer

The Control Point room panel exposes its built-in temperature, humidity and CO2 sensors, a temperature setpoint with offset, fan mode and speed, occupancy mode and status, and its display and keypad settings as BACnet objects. The VAV version adds a commissioning submenu (BO 64-69, MV 5-17, AO 22-37) that mirrors the VAV14-IP controller settings: airflow limits, K-factor, damper and fan test commands. Seven menus of user-defined parameters let the BMS show its own values.

This page lists 218 BACnet objects for the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) — 207 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.

Manufacturer
iSMA CONTROLLI
Model
Control Point room panel (incl. Control Point VAV)
Equipment
Room panel (thermostat display)
Equipment type
Thermostats, sensors & meters
BACnet objects
218 (207 writable)
Transport
BACnet MS/TP
Firmware
Control Point Software manual V1.1
Also known as
Control Point, iSMA Control Point, Control Point VAV, Control Point Software V1.1
Source document
Control Point Software User Manual V1.1 - List of BACnet Objects · rev. V1.1
Download CSV 218 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.

BMS integration notes: iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)

Integration in brief

Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode. With a VAV14-IP the VAV submenu objects are commissioning settings only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 4OCCUPANCY_MODEOccupancy mode, 1 = unoccupied, 2 = occupiedWrite
AV 56SETPOINTTemperature setpointWrite
MV 1FAN_MODEFan mode: 1 off, 2-4 manual speed, 5 autoWrite
AI 4TEMPERATURE_SENSORRoom temperatureRead
AI 3EFFECTIVE_SETPOINTEffective setpoint (setpoint plus offset)Read
MV 3CURRENT_OCCUPIED_STATUSOccupancy status: 0 unocc, 1 occ, 2 standby, 3 forcedWrite
AI 5HUMIDITY_SENSORRoom humidityRead
AI 6CO2_SENSORRoom CO2Read

Enable & remote start

BO 62 OCCUPIED_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.

Network setup

Watch out for

iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

218 of 218 shown
Type
Access
Show
iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet Points List
DescriptionStates
AI0LIVE_TIMEDevice uptime in secondssRead
AO0PANEL_PASSWORDPassword for the panel settingsWrite
MI1SENSORSSensors built-in in the panel:Read0=Temperature sensor, 1=CO2 sensor, 2=Humidity sensor
AI1BACKGROUND_LCD_CURRENT_VALUECurrent display illumination valueRead
AI2BACKGROUND_KEY_PAD_CURRENT_VALUECurrent keypad illumination valueRead
AO1HOURSHours part of time displayWrite
AO2MINUTESMinutes part of time displayWrite
BO0BUZZERWriteFalse=Not active, True=Active (default)
BO1TIME_FORMATWriteFalse=24 h (default), True=12 h
BO2DEFAULT_TEMPERATURE_UNITWriteFalse=Celsius (default), True=Fahrenheit
BO3BACKGROUND_ILLUMINATION_LCD_ACTIVEWriteFalse=Not active, True=Active
BO4BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVEWriteFalse=Not active, True=Active
BO5CO2_IN_ALARM_FLASHING_LCDWriteFalse=Not active, True=Active
BO6CO2_IN_ALARM_BUZZERWriteFalse=Not active, True=Active
BO7CO2_IN_ALARM_SHOW_HIGHWriteFalse=Not active, True=Active
BO63CO2_ALARM_CONFIRM_ENABLEWriteFalse=Not active, True=Active
BO8SUBMENU_ICON_DISPLAY_OFFWriteFalse=Not active, True=Active
BO9PANEL_OFFWriteFalse=Panel on (default), True=Panel off
BO10KEY_PAD_OFFWriteFalse=Keypad on (default), True=Keypad off
BO11LCD_FLASHINGWriteFalse=Not active (default), True=Active
BO12KEY_PAD_FLASHINGWriteFalse=Not active (default), True=Active
AO3BACKGROUND_LCD_FOR_ACTIVE_MODEDefault: 60%Write
AO4BACKGROUND_LCD_FOR_IDLE_MODEDefault: 40%Write
AO5BACKGROUND_LCD_FOR_STANDBY_MODEDefault: 0%Write
AO6BACKGROUND_LCD_TIME_TO_IDLEDefault: 10 sWrite
AO7BACKGROUND_LCD_TIME_TO_STANDBYDefault: 5 sWrite
AO8BACKGROUND_KEY_PAD_ACTIVE_MODEDefault: 10%Write
AO9BACKGROUND_KEY_PAD__IDLE_MODEDefault: 40%Write
AO10BACKGROUND_KEY_PAD_STANDBY_MODEDefault: 60%Write
AO11BACKGROUND_KEY_PAD_TIME_TO_IDLEDefault: 10 sWrite
AO12BACKGROUND_KEY_PAD_TIME_TO_STANDBYDefault: 5 sWrite
AO13REFRESH_TIMEDefault: 2 sWrite
BO13TIME_CONFIGURATIONWriteFalse=Clock displayed (default), True=Clock not displayed
BO14LCD_ICON_DISPLAYSUNWrite
BO15LCD_ICON_DISPLAYMOONWrite
BO16LCD_ICON_DISPLAYHEATINGWrite
BO17LCD_ICON_DISPLAYCOOLINGWrite
BO18LCD_ICON_DISPLAYHUMIDIFIERWrite
BO19LCD_ICON_DISPLAYDEHUMIDIFIERWrite
BO20LCD_ICON_DISPLAYWIRELESSWrite
BO21LCD_ICON_DISPLAYSETTINGSWrite
BO22LCD_ICON_DISPLAYECOWrite
BO23LCD_ICON_DISPLAYRECIRCULATIONWrite
BO24LCD_ICON_DISPLAYPCWrite
BO25LCD_ICON_FLASHING(11 objects, BO 25-35)Write
AO14LCD_ICON_FLASHING_TIMEIcons blinking frequencyWrite
AO15SUBMENU_ICON_FLASHING_TIMESubmenu icons flashing timeWrite
AO16ENTER_MENU_TIMEDefault: 2 sWrite
AO17EXIT_EDIT_TIMEDefault: 5 sWrite
AO18EXIT_MENU_TIMEDefault: 10 sWrite
AO19CO2_SETPOINT_FOR_ALARMCO2 alarm setpointWrite
AO20CO2_HYSTERESIS_FOR_ALARMCO2 alarm hysteresisWrite
AImin4TEMPERATURE_SENSORCurrent temperature sensor value with offset°CRead
AImin5HUMIDITY_SENSORCurrent humidity sensor value with offset%RHRead
AImin6CO2_SENSORCurrent CO2 sensor value with offsetppmRead
AVmin56SETPOINTActual setpoint valueWrite
AImin3EFFECTIVE_SETPOINTSum of the temperature actual setpoint value and offsetRead
AV57DEFAULT_SETPOINTDefault: 21oCWrite
AV59OFFSET_RANGEOffset value limitWrite
BO55OPERATING_MODEWriteFalse=Changing offset, True=Changing setpoint (default)
BO56SETPOINT_DISPLAYWriteFalse=Not active, True=Active (default)
BO57FAST_EDIT_MODEWriteFalse=Not active (default), True=Active
MVmin1FAN_MODEWrite1=Off, 2=Manual, speed 1 (default), 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto
MV0FAN_CURRENT_SPEEDWrite1=Off (default), 2=Manual, speed 1, 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto, speed 1, 6=Auto, speed 2, 7=Auto, speed 3
BO59PART_EDITABLEWriteFalse=Fully editable (default), True=Auto_Off_Mode
BO60FAST_EDIT_MODEWriteFalse=Not active (default), True=Active
AO21FAN_ICON_FLASHING_TIMETime base for calculating the frequency of the fan icon rotationWrite
MVmin4OCCUPANCY_MODEWrite1=Unoccupied, 2=Occupied
MVmin3CURRENT_OCCUPIED_STATUSWrite0=Unoccupied, 1=Occupied, 2=Standby, 3=Forced occupied
BO61FAST_EDIT_MODEWriteFalse=Not active (default), True=Active
BO62OCCUPIED_CONFIG_LOCAL_MODEWriteFalse=Local mode, True=BMS mode
AV58OFFSET_SETPOINTDefault: 0oCWrite
MV2FAN_TYPEWrite1=Analog, 0-10 V DC, 2=1-speed fan, 3=2-speed fan, 4=3-speed fan
BO68VAV_DEVICE_TYPEChoose VAV device control type from airflow demandWriteFalse=VAV, True=VVT
MV10VAV_REHEATER_TYPESet the reheater typeWrite1=none, 2=TimeProp, 3=staged, 4=float
MV11VAV_PERIMETER_TYPESet the perimeter typeWrite1=none, 2=TimeProp, 3=digital
MV9VAV_FAN_TYPESet the fan typeWrite1=none, 2=series, 3=parallel
MV12VAV_DISCHARGE_TEMP_TYPESelect the discharge temperature typeWrite1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F
MV13VAV_SPACE_TEMP_TYPESelect the space temperature typeWrite1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F
AO37VAV_CO2_RANGESets the range of the CO2 sensor usedWrite
MV14VAV_HEATER_PRIORITYPossibility to select heating priority for heating sourcesWrite1=reheater, 2=perimeter, 3=simultaneous
BO69VAV_DUAL_HEATEnable dual heating mode with repeater/perimeter and damper (no effect without damper)WriteFalse=no, True=yes
BO66VAV_OCCUPANCY_CONTACT_TYPEInvert the I1 input signal if requiredWriteFalse=normal, True=invert
BO67VAV_WINDOW_CONTACT_TYPEInvert the I2 input signal if requiredWriteFalse=normal, True=invert
BO65VAV_DAMPER_DIRECTIONSets the damper opening directionWriteFalse=CW, True=CCW
MV15VAV_SPACE_TEMPERATURE_SOURCEChoose the temperature source for control logicWrite1=panel, 2=input, 3=network
MV17VAV_CO2_SOURCESelect the CO2 source for control logicWrite1=panel, 2=input, 3=network
MV16VAV_SETPOINT_OFFSET_SOURCEChoose the setpoint offset source for control logicWrite1=panel, 2=input, 3=network
AO29VAV_MAX_FLOW_COOLINGMaximum airflow setpoint for cooling in the occupied stateWrite
AO30VAV_MIN_FLOW_COOLINGMinimum airflow setpoint for cooling in the occupied stateWrite
AO31VAV_MAX_FLOW_HEATINGMaximum airflow setpoint for heating in the occupied stateWrite
AO32VAV_MIN_FLOW_HEATINGMinimum airflow setpoint for heating in the occupied stateWrite
AO33VAV_MIN_FLOW_STANDBYAirflow setpoint in the standby stateWrite
AO34VAV_MIN_FLOW_UNOCCUPIEDAirflow setpoint in the unoccupied stateWrite
AO35VAV_FLOW_FAN_STARTAirflow setpoint for a fan startup onlyWrite
AO23VAV_K_FACTOR_VALUESets the K-FactorWrite
AO36VAV_MENU_PASSWORDNon-volatile password protecting access to commissioning menuWrite
BO64VAV_PRESSURE_SENSOR_RESET_TRIGGERPerform zeroing action on the built-in PI pressure transducer if there isWrite
AO22VAV_PRESSURE_SENSOR_VALUEActual differential pressure sensor-measured value from the built-in pressure inputRead
AO24VAV_CALCULATED_DAMPER_POSITIONActual damper opening level coming from the Rotary Actuator componentRead
AO25VAV_CALCULATED_FLOWActual calculated airflow based on the K-Factor value and differential pressure measureRead
MV5VAV_DAMPER_COMMANDSet different damper command modes for calibration, balancing, or testingWrite1=Auto/none (null), 2=Max flow, 3=Min flow, 4=User flow, 5=User position, 6=Full open, 7=Full close, 8=Calibrate
MV6VAV_FAN_COMMANDSet different fan command modes for testingWrite1=Auto/none (null), 2=Max speed, 3=Min speed, 4=Stop
MV7VAV_REHEATER_COMMANDSet different reheater command modes for testingWrite1=Auto/none (null), 2=Full open, 3=Full close
MV8VAV_PERIMETER_COMMANDSet different perimeter command modes for testingWrite1=Auto/none (null), 2=Full open, 3=Full close
AO26USER_DESIRED_DAMPER_POSITIONUser-set damper opening levelWrite
AO27USER_DESIRED_FLOWUser-set airflow setpointWrite
AO28USER_MEASURED_FLOWEnter the airflow value measured by the hood for calibrationWrite
AV0MAIN_MENU_NUMERIC1:Present ValueUser-defined numeric parameter 1, main menu menuWrite
AV1MAIN_MENU_NUMERIC2:Present ValueUser-defined numeric parameter 2, main menu menuWrite
AV3MAIN_MENU_NUMERIC4:Present ValueUser-defined numeric parameter 4, main menu menuWrite
AV4MAIN_MENU_NUMERIC5:Present ValueUser-defined numeric parameter 5, main menu menuWrite
AV5MAIN_MENU_NUMERIC6:Present ValueUser-defined numeric parameter 6, main menu menuWrite
AV7MAIN_MENU_NUMERIC8:Present ValueUser-defined numeric parameter 8, main menu menuWrite
BV0MAIN_MENU_BOOLEAN1:Present ValueUser-defined boolean parameter 1, main menu menuWrite
BV1MAIN_MENU_BOOLEAN2:Present ValueUser-defined boolean parameter 2, main menu menuWrite
BV2MAIN_MENU_BOOLEAN3:Present ValueUser-defined boolean parameter 3, main menu menuWrite
BV3MAIN_MENU_BOOLEAN4:Present ValueUser-defined boolean parameter 4, main menu menuWrite
BV4MAIN_MENU_BOOLEAN5:Present ValueUser-defined boolean parameter 5, main menu menuWrite
BV5MAIN_MENU_BOOLEAN6:Present ValueUser-defined boolean parameter 6, main menu menuWrite
BV6MAIN_MENU_BOOLEAN7:Present ValueUser-defined boolean parameter 7, main menu menuWrite
BV7MAIN_MENU_BOOLEAN8:Present ValueUser-defined boolean parameter 8, main menu menuWrite
AV8TEMPERATURE_NUMERIC1:Present ValueUser-defined numeric parameter 1, temperature menuWrite
AV9TEMPERATURE_NUMERIC2:Present ValueUser-defined numeric parameter 2, temperature menuWrite
AV10TEMPERATURE_NUMERIC3:Present ValueUser-defined numeric parameter 3, temperature menuWrite
AV11TEMPERATURE_NUMERIC4:Present ValueUser-defined numeric parameter 4, temperature menuWrite
AV12TEMPERATURE_NUMERIC5:Present ValueUser-defined numeric parameter 5, temperature menuWrite
AV13TEMPERATURE_NUMERIC6:Present ValueUser-defined numeric parameter 6, temperature menuWrite
AV14TEMPERATURE_NUMERIC7:Present ValueUser-defined numeric parameter 7, temperature menuWrite
AV15TEMPERATURE_NUMERIC8:Present ValueUser-defined numeric parameter 8, temperature menuWrite
BV8TEMPERATURE_BOOLEAN1:Present ValueUser-defined boolean parameter 1, temperature menuWrite
BV9TEMPERATURE_BOOLEAN2:Present ValueUser-defined boolean parameter 2, temperature menuWrite
BV10TEMPERATURE_BOOLEAN3:Present ValueUser-defined boolean parameter 3, temperature menuWrite
BV11TEMPERATURE_BOOLEAN4:Present ValueUser-defined boolean parameter 4, temperature menuWrite
BV12TEMPERATURE_BOOLEAN5:Present ValueUser-defined boolean parameter 5, temperature menuWrite
BV13TEMPERATURE_BOOLEAN6:Present ValueUser-defined boolean parameter 6, temperature menuWrite
BV14TEMPERATURE_BOOLEAN7:Present ValueUser-defined boolean parameter 7, temperature menuWrite
BV15TEMPERATURE_BOOLEAN8:Present ValueUser-defined boolean parameter 8, temperature menuWrite
AV16FAN_NUMERIC1:Present ValueUser-defined numeric parameter 1, fan menuWrite
AV17FAN_NUMERIC2:Present ValueUser-defined numeric parameter 2, fan menuWrite
AV18FAN_NUMERIC3:Present ValueUser-defined numeric parameter 3, fan menuWrite
AV19FAN_NUMERIC4:Present ValueUser-defined numeric parameter 4, fan menuWrite
AV20FAN_NUMERIC5:Present ValueUser-defined numeric parameter 5, fan menuWrite
AV21FAN_NUMERIC6:Present ValueUser-defined numeric parameter 6, fan menuWrite
AV22FANNUMERIC7:Present ValueUser-defined numeric parameter 7, fan menuWrite
AV23FAN_NUMERIC8:Present ValueUser-defined numeric parameter 8, fan menuWrite
BV16FAN_BOOLEAN1:Present ValueUser-defined boolean parameter 1, fan menuWrite
BV17FAN_BOOLEAN2:Present ValueUser-defined boolean parameter 2, fan menuWrite
BV18FAN_BOOLEAN3:Present ValueUser-defined boolean parameter 3, fan menuWrite
BV19FAN_BOOLEAN4:Present ValueUser-defined boolean parameter 4, fan menuWrite
BV20FAN_BOOLEAN5:Present ValueUser-defined boolean parameter 5, fan menuWrite
BV21FAN_BOOLEAN6:Present ValueUser-defined boolean parameter 6, fan menuWrite
BV22FAN_BOOLEAN7:Present ValueUser-defined boolean parameter 7, fan menuWrite
BV23FAN_BOOLEAN8:Present ValueUser-defined boolean parameter 8, fan menuWrite
AV24LIGHT_NUMERIC1:Present ValueUser-defined numeric parameter 1, light menuWrite
AV25LIGHT_NUMERIC2:Present ValueUser-defined numeric parameter 2, light menuWrite
AV26LIGHT_NUMERIC3:Present ValueUser-defined numeric parameter 3, light menuWrite
AV27LIGHT_NUMERIC4:Present ValueUser-defined numeric parameter 4, light menuWrite
AV28LIGHT_NUMERIC5:Present ValueUser-defined numeric parameter 5, light menuWrite
AV29LIGHT_NUMERIC6:Present ValueUser-defined numeric parameter 6, light menuWrite
AV30LIGHTNUMERIC7:Present ValueUser-defined numeric parameter 7, light menuWrite
AV31LIGHT_NUMERIC8:Present ValueUser-defined numeric parameter 8, light menuWrite
BV24LIGHT_BOOLEAN1:Present ValueUser-defined boolean parameter 1, light menuWrite
BV25LIGHT_BOOLEAN2:Present ValueUser-defined boolean parameter 2, light menuWrite
BV26LIGHT_BOOLEAN3:Present ValueUser-defined boolean parameter 3, light menuWrite
BV27LIGHT_BOOLEAN4:Present ValueUser-defined boolean parameter 4, light menuWrite
BV28LIGHT_BOOLEAN5:Present ValueUser-defined boolean parameter 5, light menuWrite
BV29LIGHT_BOOLEAN6:Present ValueUser-defined boolean parameter 6, light menuWrite
BV30LIGHT_BOOLEAN7:Present ValueUser-defined boolean parameter 7, light menuWrite
BV31LIGHT_BOOLEAN8:Present ValueUser-defined boolean parameter 8, light menuWrite
AV32BLIND_NUMERIC1:Present ValueUser-defined numeric parameter 1, blind menuWrite
AV33BLIND_NUMERIC2:Present ValueUser-defined numeric parameter 2, blind menuWrite
AV34BLIND_NUMERIC3:Present ValueUser-defined numeric parameter 3, blind menuWrite
AV35BLIND_NUMERIC4:Present ValueUser-defined numeric parameter 4, blind menuWrite
AV36BLIND_NUMERIC5:Present ValueUser-defined numeric parameter 5, blind menuWrite
AV37BLIND_NUMERIC6:Present ValueUser-defined numeric parameter 6, blind menuWrite
AV38BLINDNUMERIC7:Present ValueUser-defined numeric parameter 7, blind menuWrite
AV39BLIND_NUMERIC8:Present ValueUser-defined numeric parameter 8, blind menuWrite
BV32BLIND_BOOLEAN1:Present ValueUser-defined boolean parameter 1, blind menuWrite
BV33BLIND_BOOLEAN2:Present ValueUser-defined boolean parameter 2, blind menuWrite
BV34BLIND_BOOLEAN3:Present ValueUser-defined boolean parameter 3, blind menuWrite
BV35BLIND_BOOLEAN4:Present ValueUser-defined boolean parameter 4, blind menuWrite
BV36BLIND_BOOLEAN5:Present ValueUser-defined boolean parameter 5, blind menuWrite
BV37BLIND_BOOLEAN6:Present ValueUser-defined boolean parameter 6, blind menuWrite
BV38BLIND_BOOLEAN7:Present ValueUser-defined boolean parameter 7, blind menuWrite
BV39BLIND_BOOLEAN8:Present ValueUser-defined boolean parameter 8, blind menuWrite
AV40ALARMS_NUMERIC1:Present ValueUser-defined numeric parameter 1, alarms menuWrite
AV41ALARMS_NUMERIC2:Present ValueUser-defined numeric parameter 2, alarms menuWrite
AV42ALARMS_NUMERIC3:Present ValueUser-defined numeric parameter 3, alarms menuWrite
AV43ALARMS_NUMERIC4:Present ValueUser-defined numeric parameter 4, alarms menuWrite
AV44ALARMS_NUMERIC5:Present ValueUser-defined numeric parameter 5, alarms menuWrite
AV45ALARMS_NUMERIC6:Present ValueUser-defined numeric parameter 6, alarms menuWrite
AV46ALARMSNUMERIC7:Present ValueUser-defined numeric parameter 7, alarms menuWrite
AV47ALARMS_NUMERIC8:Present ValueUser-defined numeric parameter 8, alarms menuWrite
BV40ALARMS_BOOLEAN1:Present ValueUser-defined boolean parameter 1, alarms menuWrite
BV41ALARMS_BOOLEAN2:Present ValueUser-defined boolean parameter 2, alarms menuWrite
BV42ALARMS_BOOLEAN3:Present ValueUser-defined boolean parameter 3, alarms menuWrite
BV43ALARMS_BOOLEAN4:Present ValueUser-defined boolean parameter 4, alarms menuWrite
BV44ALARMS_BOOLEAN5:Present ValueUser-defined boolean parameter 5, alarms menuWrite
BV45ALARMS_BOOLEAN6:Present ValueUser-defined boolean parameter 6, alarms menuWrite
BV46ALARMS_BOOLEAN7:Present ValueUser-defined boolean parameter 7, alarms menuWrite
BV47ALARMS_BOOLEAN8:Present ValueUser-defined boolean parameter 8, alarms menuWrite
AV48SETTINGS_NUMERIC1:Present ValueUser-defined numeric parameter 1, settings menuWrite
AV49SETTINGS_NUMERIC2:Present ValueUser-defined numeric parameter 2, settings menuWrite
AV50SETTINGS_NUMERIC3:Present ValueUser-defined numeric parameter 3, settings menuWrite
AV51SETTINGS_NUMERIC4:Present ValueUser-defined numeric parameter 4, settings menuWrite
AV52SETTINGS_NUMERIC5:Present ValueUser-defined numeric parameter 5, settings menuWrite
AV53SETTINGS_NUMERIC6:Present ValueUser-defined numeric parameter 6, settings menuWrite
AV54SETTINGSNUMERIC7:Present ValueUser-defined numeric parameter 7, settings menuWrite
AV55SETTINGS_NUMERIC8:Present ValueUser-defined numeric parameter 8, settings menuWrite
BV48SETTINGS_BOOLEAN1:Present ValueUser-defined boolean parameter 1, settings menuWrite
BV49SETTINGS_BOOLEAN2:Present ValueUser-defined boolean parameter 2, settings menuWrite
BV50SETTINGS_BOOLEAN3:Present ValueUser-defined boolean parameter 3, settings menuWrite
BV51SETTINGS_BOOLEAN4:Present ValueUser-defined boolean parameter 4, settings menuWrite
BV52SETTINGS_BOOLEAN5:Present ValueUser-defined boolean parameter 5, settings menuWrite
BV53SETTINGS_BOOLEAN6:Present ValueUser-defined boolean parameter 6, settings menuWrite
BV54SETTINGS_BOOLEAN7:Present ValueUser-defined boolean parameter 7, settings menuWrite
BV55SETTINGS_BOOLEAN8:Present ValueUser-defined boolean parameter 8, settings menuWrite
Object ID lookup: iSMA CONTROLLI Control Point room panel point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Point room panel (incl. Control Point VAV) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)

How many BACnet points does the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) have?

This list has 218 BACnet objects: 7 analog inputs, 38 analog outputs, 58 analog values, 40 binary outputs, 56 binary values, 1 multi-state input, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet points are writable?

207 of the 218 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet documentation?

The source is Control Point Software User Manual V1.1 - List of BACnet Objects, revision V1.1, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/control-point-software/V1.1/list-of-bacnet-objects.

What are the minimum BACnet points to integrate the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)?

Start with MV 4 OCCUPANCY_MODE (Occupancy mode, 1 = unoccupied, 2 = occupied); AV 56 SETPOINT (Temperature setpoint); MV 1 FAN_MODE (Fan mode: 1 off, 2-4 manual speed, 5 auto); AI 4 TEMPERATURE_SENSOR (Room temperature); AI 3 EFFECTIVE_SETPOINT (Effective setpoint (setpoint plus offset)); MV 3 CURRENT_OCCUPIED_STATUS (Occupancy status: 0 unocc, 1 occ, 2 standby, 3 forced); AI 5 HUMIDITY_SENSOR (Room humidity); AI 6 CO2_SENSOR (Room CO2).

How do I enable BMS control of the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)?

BO 62 OCCUPIED_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.

How do I check these points on the real Control Point room panel (incl. Control Point VAV)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More iSMA CONTROLLI BACnet points lists

Source: Control Point Software User Manual V1.1 - List of BACnet Objects · rev. V1.1. Object names, instances and units are reproduced as published; descriptions are our own.