- Home
- BACnet points lists
- iSMA CONTROLLI
- Control Point room panel (incl. Control Point VAV)
Room panel (thermostat display) · BACnet points list
iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet points list
Updated 12 November 2026
The Control Point room panel exposes its built-in temperature, humidity and CO2 sensors, a temperature setpoint with offset, fan mode and speed, occupancy mode and status, and its display and keypad settings as BACnet objects. The VAV version adds a commissioning submenu (BO 64-69, MV 5-17, AO 22-37) that mirrors the VAV14-IP controller settings: airflow limits, K-factor, damper and fan test commands. Seven menus of user-defined parameters let the BMS show its own values.
This page lists 218 BACnet objects for the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) — 207 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.
- Manufacturer
- iSMA CONTROLLI
- Model
- Control Point room panel (incl. Control Point VAV)
- Equipment
- Room panel (thermostat display)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 218 (207 writable)
- Transport
- BACnet MS/TP
- Firmware
- Control Point Software manual V1.1
- Also known as
- Control Point, iSMA Control Point, Control Point VAV, Control Point Software V1.1
Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.
BMS integration notes: iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)
Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode. With a VAV14-IP the VAV submenu objects are commissioning settings only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | OCCUPANCY_MODE | Occupancy mode, 1 = unoccupied, 2 = occupied | Write |
| AV 56 | SETPOINT | Temperature setpoint | Write |
| MV 1 | FAN_MODE | Fan mode: 1 off, 2-4 manual speed, 5 auto | Write |
| AI 4 | TEMPERATURE_SENSOR | Room temperature | Read |
| AI 3 | EFFECTIVE_SETPOINT | Effective setpoint (setpoint plus offset) | Read |
| MV 3 | CURRENT_OCCUPIED_STATUS | Occupancy status: 0 unocc, 1 occ, 2 standby, 3 forced | Write |
| AI 5 | HUMIDITY_SENSOR | Room humidity | Read |
| AI 6 | CO2_SENSOR | Room CO2 | Read |
Enable & remote start
BO 62 OCCUPIED_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.
Network setup
- Device instance and baud rate are Device-object properties (BACNET_DEVICE_ID default 0xFFFFFFFF, BAUD_RATE default 115200).
- The VAV submenu (password AO 36, default 1000) is for commissioning the VAV14-IP from the panel.
Watch out for
- Most configuration objects are stored in panel memory; avoid cyclic writes.
- Sensor objects exist only on panel versions with that sensor (MI 1 SENSORS lists them).
iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | LIVE_TIME | Device uptime in seconds | s | Read | |
| AO | 0 | PANEL_PASSWORD | Password for the panel settings | Write | ||
| MI | 1 | SENSORS | Sensors built-in in the panel: | Read | 0=Temperature sensor, 1=CO2 sensor, 2=Humidity sensor | |
| AI | 1 | BACKGROUND_LCD_CURRENT_VALUE | Current display illumination value | Read | ||
| AI | 2 | BACKGROUND_KEY_PAD_CURRENT_VALUE | Current keypad illumination value | Read | ||
| AO | 1 | HOURS | Hours part of time display | Write | ||
| AO | 2 | MINUTES | Minutes part of time display | Write | ||
| BO | 0 | BUZZER | Write | False=Not active, True=Active (default) | ||
| BO | 1 | TIME_FORMAT | Write | False=24 h (default), True=12 h | ||
| BO | 2 | DEFAULT_TEMPERATURE_UNIT | Write | False=Celsius (default), True=Fahrenheit | ||
| BO | 3 | BACKGROUND_ILLUMINATION_LCD_ACTIVE | Write | False=Not active, True=Active | ||
| BO | 4 | BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE | Write | False=Not active, True=Active | ||
| BO | 5 | CO2_IN_ALARM_FLASHING_LCD | Write | False=Not active, True=Active | ||
| BO | 6 | CO2_IN_ALARM_BUZZER | Write | False=Not active, True=Active | ||
| BO | 7 | CO2_IN_ALARM_SHOW_HIGH | Write | False=Not active, True=Active | ||
| BO | 63 | CO2_ALARM_CONFIRM_ENABLE | Write | False=Not active, True=Active | ||
| BO | 8 | SUBMENU_ICON_DISPLAY_OFF | Write | False=Not active, True=Active | ||
| BO | 9 | PANEL_OFF | Write | False=Panel on (default), True=Panel off | ||
| BO | 10 | KEY_PAD_OFF | Write | False=Keypad on (default), True=Keypad off | ||
| BO | 11 | LCD_FLASHING | Write | False=Not active (default), True=Active | ||
| BO | 12 | KEY_PAD_FLASHING | Write | False=Not active (default), True=Active | ||
| AO | 3 | BACKGROUND_LCD_FOR_ACTIVE_MODE | Default: 60% | Write | ||
| AO | 4 | BACKGROUND_LCD_FOR_IDLE_MODE | Default: 40% | Write | ||
| AO | 5 | BACKGROUND_LCD_FOR_STANDBY_MODE | Default: 0% | Write | ||
| AO | 6 | BACKGROUND_LCD_TIME_TO_IDLE | Default: 10 s | Write | ||
| AO | 7 | BACKGROUND_LCD_TIME_TO_STANDBY | Default: 5 s | Write | ||
| AO | 8 | BACKGROUND_KEY_PAD_ACTIVE_MODE | Default: 10% | Write | ||
| AO | 9 | BACKGROUND_KEY_PAD__IDLE_MODE | Default: 40% | Write | ||
| AO | 10 | BACKGROUND_KEY_PAD_STANDBY_MODE | Default: 60% | Write | ||
| AO | 11 | BACKGROUND_KEY_PAD_TIME_TO_IDLE | Default: 10 s | Write | ||
| AO | 12 | BACKGROUND_KEY_PAD_TIME_TO_STANDBY | Default: 5 s | Write | ||
| AO | 13 | REFRESH_TIME | Default: 2 s | Write | ||
| BO | 13 | TIME_CONFIGURATION | Write | False=Clock displayed (default), True=Clock not displayed | ||
| BO | 14 | LCD_ICON_DISPLAY | SUN | Write | ||
| BO | 15 | LCD_ICON_DISPLAY | MOON | Write | ||
| BO | 16 | LCD_ICON_DISPLAY | HEATING | Write | ||
| BO | 17 | LCD_ICON_DISPLAY | COOLING | Write | ||
| BO | 18 | LCD_ICON_DISPLAY | HUMIDIFIER | Write | ||
| BO | 19 | LCD_ICON_DISPLAY | DEHUMIDIFIER | Write | ||
| BO | 20 | LCD_ICON_DISPLAY | WIRELESS | Write | ||
| BO | 21 | LCD_ICON_DISPLAY | SETTINGS | Write | ||
| BO | 22 | LCD_ICON_DISPLAY | ECO | Write | ||
| BO | 23 | LCD_ICON_DISPLAY | RECIRCULATION | Write | ||
| BO | 24 | LCD_ICON_DISPLAY | PC | Write | ||
| BO | 25 | LCD_ICON_FLASHING | (11 objects, BO 25-35) | Write | ||
| AO | 14 | LCD_ICON_FLASHING_TIME | Icons blinking frequency | Write | ||
| AO | 15 | SUBMENU_ICON_FLASHING_TIME | Submenu icons flashing time | Write | ||
| AO | 16 | ENTER_MENU_TIME | Default: 2 s | Write | ||
| AO | 17 | EXIT_EDIT_TIME | Default: 5 s | Write | ||
| AO | 18 | EXIT_MENU_TIME | Default: 10 s | Write | ||
| AO | 19 | CO2_SETPOINT_FOR_ALARM | CO2 alarm setpoint | Write | ||
| AO | 20 | CO2_HYSTERESIS_FOR_ALARM | CO2 alarm hysteresis | Write | ||
| AImin | 4 | TEMPERATURE_SENSOR | Current temperature sensor value with offset | °C | Read | |
| AImin | 5 | HUMIDITY_SENSOR | Current humidity sensor value with offset | %RH | Read | |
| AImin | 6 | CO2_SENSOR | Current CO2 sensor value with offset | ppm | Read | |
| AVmin | 56 | SETPOINT | Actual setpoint value | Write | ||
| AImin | 3 | EFFECTIVE_SETPOINT | Sum of the temperature actual setpoint value and offset | Read | ||
| AV | 57 | DEFAULT_SETPOINT | Default: 21oC | Write | ||
| AV | 59 | OFFSET_RANGE | Offset value limit | Write | ||
| BO | 55 | OPERATING_MODE | Write | False=Changing offset, True=Changing setpoint (default) | ||
| BO | 56 | SETPOINT_DISPLAY | Write | False=Not active, True=Active (default) | ||
| BO | 57 | FAST_EDIT_MODE | Write | False=Not active (default), True=Active | ||
| MVmin | 1 | FAN_MODE | Write | 1=Off, 2=Manual, speed 1 (default), 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto | ||
| MV | 0 | FAN_CURRENT_SPEED | Write | 1=Off (default), 2=Manual, speed 1, 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto, speed 1, 6=Auto, speed 2, 7=Auto, speed 3 | ||
| BO | 59 | PART_EDITABLE | Write | False=Fully editable (default), True=Auto_Off_Mode | ||
| BO | 60 | FAST_EDIT_MODE | Write | False=Not active (default), True=Active | ||
| AO | 21 | FAN_ICON_FLASHING_TIME | Time base for calculating the frequency of the fan icon rotation | Write | ||
| MVmin | 4 | OCCUPANCY_MODE | Write | 1=Unoccupied, 2=Occupied | ||
| MVmin | 3 | CURRENT_OCCUPIED_STATUS | Write | 0=Unoccupied, 1=Occupied, 2=Standby, 3=Forced occupied | ||
| BO | 61 | FAST_EDIT_MODE | Write | False=Not active (default), True=Active | ||
| BO | 62 | OCCUPIED_CONFIG_LOCAL_MODE | Write | False=Local mode, True=BMS mode | ||
| AV | 58 | OFFSET_SETPOINT | Default: 0oC | Write | ||
| MV | 2 | FAN_TYPE | Write | 1=Analog, 0-10 V DC, 2=1-speed fan, 3=2-speed fan, 4=3-speed fan | ||
| BO | 68 | VAV_DEVICE_TYPE | Choose VAV device control type from airflow demand | Write | False=VAV, True=VVT | |
| MV | 10 | VAV_REHEATER_TYPE | Set the reheater type | Write | 1=none, 2=TimeProp, 3=staged, 4=float | |
| MV | 11 | VAV_PERIMETER_TYPE | Set the perimeter type | Write | 1=none, 2=TimeProp, 3=digital | |
| MV | 9 | VAV_FAN_TYPE | Set the fan type | Write | 1=none, 2=series, 3=parallel | |
| MV | 12 | VAV_DISCHARGE_TEMP_TYPE | Select the discharge temperature type | Write | 1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F | |
| MV | 13 | VAV_SPACE_TEMP_TYPE | Select the space temperature type | Write | 1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F | |
| AO | 37 | VAV_CO2_RANGE | Sets the range of the CO2 sensor used | Write | ||
| MV | 14 | VAV_HEATER_PRIORITY | Possibility to select heating priority for heating sources | Write | 1=reheater, 2=perimeter, 3=simultaneous | |
| BO | 69 | VAV_DUAL_HEAT | Enable dual heating mode with repeater/perimeter and damper (no effect without damper) | Write | False=no, True=yes | |
| BO | 66 | VAV_OCCUPANCY_CONTACT_TYPE | Invert the I1 input signal if required | Write | False=normal, True=invert | |
| BO | 67 | VAV_WINDOW_CONTACT_TYPE | Invert the I2 input signal if required | Write | False=normal, True=invert | |
| BO | 65 | VAV_DAMPER_DIRECTION | Sets the damper opening direction | Write | False=CW, True=CCW | |
| MV | 15 | VAV_SPACE_TEMPERATURE_SOURCE | Choose the temperature source for control logic | Write | 1=panel, 2=input, 3=network | |
| MV | 17 | VAV_CO2_SOURCE | Select the CO2 source for control logic | Write | 1=panel, 2=input, 3=network | |
| MV | 16 | VAV_SETPOINT_OFFSET_SOURCE | Choose the setpoint offset source for control logic | Write | 1=panel, 2=input, 3=network | |
| AO | 29 | VAV_MAX_FLOW_COOLING | Maximum airflow setpoint for cooling in the occupied state | Write | ||
| AO | 30 | VAV_MIN_FLOW_COOLING | Minimum airflow setpoint for cooling in the occupied state | Write | ||
| AO | 31 | VAV_MAX_FLOW_HEATING | Maximum airflow setpoint for heating in the occupied state | Write | ||
| AO | 32 | VAV_MIN_FLOW_HEATING | Minimum airflow setpoint for heating in the occupied state | Write | ||
| AO | 33 | VAV_MIN_FLOW_STANDBY | Airflow setpoint in the standby state | Write | ||
| AO | 34 | VAV_MIN_FLOW_UNOCCUPIED | Airflow setpoint in the unoccupied state | Write | ||
| AO | 35 | VAV_FLOW_FAN_START | Airflow setpoint for a fan startup only | Write | ||
| AO | 23 | VAV_K_FACTOR_VALUE | Sets the K-Factor | Write | ||
| AO | 36 | VAV_MENU_PASSWORD | Non-volatile password protecting access to commissioning menu | Write | ||
| BO | 64 | VAV_PRESSURE_SENSOR_RESET_TRIGGER | Perform zeroing action on the built-in PI pressure transducer if there is | Write | ||
| AO | 22 | VAV_PRESSURE_SENSOR_VALUE | Actual differential pressure sensor-measured value from the built-in pressure input | Read | ||
| AO | 24 | VAV_CALCULATED_DAMPER_POSITION | Actual damper opening level coming from the Rotary Actuator component | Read | ||
| AO | 25 | VAV_CALCULATED_FLOW | Actual calculated airflow based on the K-Factor value and differential pressure measure | Read | ||
| MV | 5 | VAV_DAMPER_COMMAND | Set different damper command modes for calibration, balancing, or testing | Write | 1=Auto/none (null), 2=Max flow, 3=Min flow, 4=User flow, 5=User position, 6=Full open, 7=Full close, 8=Calibrate | |
| MV | 6 | VAV_FAN_COMMAND | Set different fan command modes for testing | Write | 1=Auto/none (null), 2=Max speed, 3=Min speed, 4=Stop | |
| MV | 7 | VAV_REHEATER_COMMAND | Set different reheater command modes for testing | Write | 1=Auto/none (null), 2=Full open, 3=Full close | |
| MV | 8 | VAV_PERIMETER_COMMAND | Set different perimeter command modes for testing | Write | 1=Auto/none (null), 2=Full open, 3=Full close | |
| AO | 26 | USER_DESIRED_DAMPER_POSITION | User-set damper opening level | Write | ||
| AO | 27 | USER_DESIRED_FLOW | User-set airflow setpoint | Write | ||
| AO | 28 | USER_MEASURED_FLOW | Enter the airflow value measured by the hood for calibration | Write | ||
| AV | 0 | MAIN_MENU_NUMERIC1:Present Value | User-defined numeric parameter 1, main menu menu | Write | ||
| AV | 1 | MAIN_MENU_NUMERIC2:Present Value | User-defined numeric parameter 2, main menu menu | Write | ||
| AV | 3 | MAIN_MENU_NUMERIC4:Present Value | User-defined numeric parameter 4, main menu menu | Write | ||
| AV | 4 | MAIN_MENU_NUMERIC5:Present Value | User-defined numeric parameter 5, main menu menu | Write | ||
| AV | 5 | MAIN_MENU_NUMERIC6:Present Value | User-defined numeric parameter 6, main menu menu | Write | ||
| AV | 7 | MAIN_MENU_NUMERIC8:Present Value | User-defined numeric parameter 8, main menu menu | Write | ||
| BV | 0 | MAIN_MENU_BOOLEAN1:Present Value | User-defined boolean parameter 1, main menu menu | Write | ||
| BV | 1 | MAIN_MENU_BOOLEAN2:Present Value | User-defined boolean parameter 2, main menu menu | Write | ||
| BV | 2 | MAIN_MENU_BOOLEAN3:Present Value | User-defined boolean parameter 3, main menu menu | Write | ||
| BV | 3 | MAIN_MENU_BOOLEAN4:Present Value | User-defined boolean parameter 4, main menu menu | Write | ||
| BV | 4 | MAIN_MENU_BOOLEAN5:Present Value | User-defined boolean parameter 5, main menu menu | Write | ||
| BV | 5 | MAIN_MENU_BOOLEAN6:Present Value | User-defined boolean parameter 6, main menu menu | Write | ||
| BV | 6 | MAIN_MENU_BOOLEAN7:Present Value | User-defined boolean parameter 7, main menu menu | Write | ||
| BV | 7 | MAIN_MENU_BOOLEAN8:Present Value | User-defined boolean parameter 8, main menu menu | Write | ||
| AV | 8 | TEMPERATURE_NUMERIC1:Present Value | User-defined numeric parameter 1, temperature menu | Write | ||
| AV | 9 | TEMPERATURE_NUMERIC2:Present Value | User-defined numeric parameter 2, temperature menu | Write | ||
| AV | 10 | TEMPERATURE_NUMERIC3:Present Value | User-defined numeric parameter 3, temperature menu | Write | ||
| AV | 11 | TEMPERATURE_NUMERIC4:Present Value | User-defined numeric parameter 4, temperature menu | Write | ||
| AV | 12 | TEMPERATURE_NUMERIC5:Present Value | User-defined numeric parameter 5, temperature menu | Write | ||
| AV | 13 | TEMPERATURE_NUMERIC6:Present Value | User-defined numeric parameter 6, temperature menu | Write | ||
| AV | 14 | TEMPERATURE_NUMERIC7:Present Value | User-defined numeric parameter 7, temperature menu | Write | ||
| AV | 15 | TEMPERATURE_NUMERIC8:Present Value | User-defined numeric parameter 8, temperature menu | Write | ||
| BV | 8 | TEMPERATURE_BOOLEAN1:Present Value | User-defined boolean parameter 1, temperature menu | Write | ||
| BV | 9 | TEMPERATURE_BOOLEAN2:Present Value | User-defined boolean parameter 2, temperature menu | Write | ||
| BV | 10 | TEMPERATURE_BOOLEAN3:Present Value | User-defined boolean parameter 3, temperature menu | Write | ||
| BV | 11 | TEMPERATURE_BOOLEAN4:Present Value | User-defined boolean parameter 4, temperature menu | Write | ||
| BV | 12 | TEMPERATURE_BOOLEAN5:Present Value | User-defined boolean parameter 5, temperature menu | Write | ||
| BV | 13 | TEMPERATURE_BOOLEAN6:Present Value | User-defined boolean parameter 6, temperature menu | Write | ||
| BV | 14 | TEMPERATURE_BOOLEAN7:Present Value | User-defined boolean parameter 7, temperature menu | Write | ||
| BV | 15 | TEMPERATURE_BOOLEAN8:Present Value | User-defined boolean parameter 8, temperature menu | Write | ||
| AV | 16 | FAN_NUMERIC1:Present Value | User-defined numeric parameter 1, fan menu | Write | ||
| AV | 17 | FAN_NUMERIC2:Present Value | User-defined numeric parameter 2, fan menu | Write | ||
| AV | 18 | FAN_NUMERIC3:Present Value | User-defined numeric parameter 3, fan menu | Write | ||
| AV | 19 | FAN_NUMERIC4:Present Value | User-defined numeric parameter 4, fan menu | Write | ||
| AV | 20 | FAN_NUMERIC5:Present Value | User-defined numeric parameter 5, fan menu | Write | ||
| AV | 21 | FAN_NUMERIC6:Present Value | User-defined numeric parameter 6, fan menu | Write | ||
| AV | 22 | FANNUMERIC7:Present Value | User-defined numeric parameter 7, fan menu | Write | ||
| AV | 23 | FAN_NUMERIC8:Present Value | User-defined numeric parameter 8, fan menu | Write | ||
| BV | 16 | FAN_BOOLEAN1:Present Value | User-defined boolean parameter 1, fan menu | Write | ||
| BV | 17 | FAN_BOOLEAN2:Present Value | User-defined boolean parameter 2, fan menu | Write | ||
| BV | 18 | FAN_BOOLEAN3:Present Value | User-defined boolean parameter 3, fan menu | Write | ||
| BV | 19 | FAN_BOOLEAN4:Present Value | User-defined boolean parameter 4, fan menu | Write | ||
| BV | 20 | FAN_BOOLEAN5:Present Value | User-defined boolean parameter 5, fan menu | Write | ||
| BV | 21 | FAN_BOOLEAN6:Present Value | User-defined boolean parameter 6, fan menu | Write | ||
| BV | 22 | FAN_BOOLEAN7:Present Value | User-defined boolean parameter 7, fan menu | Write | ||
| BV | 23 | FAN_BOOLEAN8:Present Value | User-defined boolean parameter 8, fan menu | Write | ||
| AV | 24 | LIGHT_NUMERIC1:Present Value | User-defined numeric parameter 1, light menu | Write | ||
| AV | 25 | LIGHT_NUMERIC2:Present Value | User-defined numeric parameter 2, light menu | Write | ||
| AV | 26 | LIGHT_NUMERIC3:Present Value | User-defined numeric parameter 3, light menu | Write | ||
| AV | 27 | LIGHT_NUMERIC4:Present Value | User-defined numeric parameter 4, light menu | Write | ||
| AV | 28 | LIGHT_NUMERIC5:Present Value | User-defined numeric parameter 5, light menu | Write | ||
| AV | 29 | LIGHT_NUMERIC6:Present Value | User-defined numeric parameter 6, light menu | Write | ||
| AV | 30 | LIGHTNUMERIC7:Present Value | User-defined numeric parameter 7, light menu | Write | ||
| AV | 31 | LIGHT_NUMERIC8:Present Value | User-defined numeric parameter 8, light menu | Write | ||
| BV | 24 | LIGHT_BOOLEAN1:Present Value | User-defined boolean parameter 1, light menu | Write | ||
| BV | 25 | LIGHT_BOOLEAN2:Present Value | User-defined boolean parameter 2, light menu | Write | ||
| BV | 26 | LIGHT_BOOLEAN3:Present Value | User-defined boolean parameter 3, light menu | Write | ||
| BV | 27 | LIGHT_BOOLEAN4:Present Value | User-defined boolean parameter 4, light menu | Write | ||
| BV | 28 | LIGHT_BOOLEAN5:Present Value | User-defined boolean parameter 5, light menu | Write | ||
| BV | 29 | LIGHT_BOOLEAN6:Present Value | User-defined boolean parameter 6, light menu | Write | ||
| BV | 30 | LIGHT_BOOLEAN7:Present Value | User-defined boolean parameter 7, light menu | Write | ||
| BV | 31 | LIGHT_BOOLEAN8:Present Value | User-defined boolean parameter 8, light menu | Write | ||
| AV | 32 | BLIND_NUMERIC1:Present Value | User-defined numeric parameter 1, blind menu | Write | ||
| AV | 33 | BLIND_NUMERIC2:Present Value | User-defined numeric parameter 2, blind menu | Write | ||
| AV | 34 | BLIND_NUMERIC3:Present Value | User-defined numeric parameter 3, blind menu | Write | ||
| AV | 35 | BLIND_NUMERIC4:Present Value | User-defined numeric parameter 4, blind menu | Write | ||
| AV | 36 | BLIND_NUMERIC5:Present Value | User-defined numeric parameter 5, blind menu | Write | ||
| AV | 37 | BLIND_NUMERIC6:Present Value | User-defined numeric parameter 6, blind menu | Write | ||
| AV | 38 | BLINDNUMERIC7:Present Value | User-defined numeric parameter 7, blind menu | Write | ||
| AV | 39 | BLIND_NUMERIC8:Present Value | User-defined numeric parameter 8, blind menu | Write | ||
| BV | 32 | BLIND_BOOLEAN1:Present Value | User-defined boolean parameter 1, blind menu | Write | ||
| BV | 33 | BLIND_BOOLEAN2:Present Value | User-defined boolean parameter 2, blind menu | Write | ||
| BV | 34 | BLIND_BOOLEAN3:Present Value | User-defined boolean parameter 3, blind menu | Write | ||
| BV | 35 | BLIND_BOOLEAN4:Present Value | User-defined boolean parameter 4, blind menu | Write | ||
| BV | 36 | BLIND_BOOLEAN5:Present Value | User-defined boolean parameter 5, blind menu | Write | ||
| BV | 37 | BLIND_BOOLEAN6:Present Value | User-defined boolean parameter 6, blind menu | Write | ||
| BV | 38 | BLIND_BOOLEAN7:Present Value | User-defined boolean parameter 7, blind menu | Write | ||
| BV | 39 | BLIND_BOOLEAN8:Present Value | User-defined boolean parameter 8, blind menu | Write | ||
| AV | 40 | ALARMS_NUMERIC1:Present Value | User-defined numeric parameter 1, alarms menu | Write | ||
| AV | 41 | ALARMS_NUMERIC2:Present Value | User-defined numeric parameter 2, alarms menu | Write | ||
| AV | 42 | ALARMS_NUMERIC3:Present Value | User-defined numeric parameter 3, alarms menu | Write | ||
| AV | 43 | ALARMS_NUMERIC4:Present Value | User-defined numeric parameter 4, alarms menu | Write | ||
| AV | 44 | ALARMS_NUMERIC5:Present Value | User-defined numeric parameter 5, alarms menu | Write | ||
| AV | 45 | ALARMS_NUMERIC6:Present Value | User-defined numeric parameter 6, alarms menu | Write | ||
| AV | 46 | ALARMSNUMERIC7:Present Value | User-defined numeric parameter 7, alarms menu | Write | ||
| AV | 47 | ALARMS_NUMERIC8:Present Value | User-defined numeric parameter 8, alarms menu | Write | ||
| BV | 40 | ALARMS_BOOLEAN1:Present Value | User-defined boolean parameter 1, alarms menu | Write | ||
| BV | 41 | ALARMS_BOOLEAN2:Present Value | User-defined boolean parameter 2, alarms menu | Write | ||
| BV | 42 | ALARMS_BOOLEAN3:Present Value | User-defined boolean parameter 3, alarms menu | Write | ||
| BV | 43 | ALARMS_BOOLEAN4:Present Value | User-defined boolean parameter 4, alarms menu | Write | ||
| BV | 44 | ALARMS_BOOLEAN5:Present Value | User-defined boolean parameter 5, alarms menu | Write | ||
| BV | 45 | ALARMS_BOOLEAN6:Present Value | User-defined boolean parameter 6, alarms menu | Write | ||
| BV | 46 | ALARMS_BOOLEAN7:Present Value | User-defined boolean parameter 7, alarms menu | Write | ||
| BV | 47 | ALARMS_BOOLEAN8:Present Value | User-defined boolean parameter 8, alarms menu | Write | ||
| AV | 48 | SETTINGS_NUMERIC1:Present Value | User-defined numeric parameter 1, settings menu | Write | ||
| AV | 49 | SETTINGS_NUMERIC2:Present Value | User-defined numeric parameter 2, settings menu | Write | ||
| AV | 50 | SETTINGS_NUMERIC3:Present Value | User-defined numeric parameter 3, settings menu | Write | ||
| AV | 51 | SETTINGS_NUMERIC4:Present Value | User-defined numeric parameter 4, settings menu | Write | ||
| AV | 52 | SETTINGS_NUMERIC5:Present Value | User-defined numeric parameter 5, settings menu | Write | ||
| AV | 53 | SETTINGS_NUMERIC6:Present Value | User-defined numeric parameter 6, settings menu | Write | ||
| AV | 54 | SETTINGSNUMERIC7:Present Value | User-defined numeric parameter 7, settings menu | Write | ||
| AV | 55 | SETTINGS_NUMERIC8:Present Value | User-defined numeric parameter 8, settings menu | Write | ||
| BV | 48 | SETTINGS_BOOLEAN1:Present Value | User-defined boolean parameter 1, settings menu | Write | ||
| BV | 49 | SETTINGS_BOOLEAN2:Present Value | User-defined boolean parameter 2, settings menu | Write | ||
| BV | 50 | SETTINGS_BOOLEAN3:Present Value | User-defined boolean parameter 3, settings menu | Write | ||
| BV | 51 | SETTINGS_BOOLEAN4:Present Value | User-defined boolean parameter 4, settings menu | Write | ||
| BV | 52 | SETTINGS_BOOLEAN5:Present Value | User-defined boolean parameter 5, settings menu | Write | ||
| BV | 53 | SETTINGS_BOOLEAN6:Present Value | User-defined boolean parameter 6, settings menu | Write | ||
| BV | 54 | SETTINGS_BOOLEAN7:Present Value | User-defined boolean parameter 7, settings menu | Write | ||
| BV | 55 | SETTINGS_BOOLEAN8:Present Value | User-defined boolean parameter 8, settings menu | Write |
No points match these filters.
Object ID lookup: iSMA CONTROLLI Control Point room panel point IDs by name
AI0LIVE_TIMEAO0PANEL_PASSWORDMI1SENSORSAI1BACKGROUND_LCD_CURRENT_VALUEAI2BACKGROUND_KEY_PAD_CURRENT_VALUEAO1HOURSAO2MINUTESBO0BUZZERBO1TIME_FORMATBO2DEFAULT_TEMPERATURE_UNITBO3BACKGROUND_ILLUMINATION_LCD_ACTIVEBO4BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVEBO5CO2_IN_ALARM_FLASHING_LCDBO6CO2_IN_ALARM_BUZZERBO7CO2_IN_ALARM_SHOW_HIGHBO63CO2_ALARM_CONFIRM_ENABLEBO8SUBMENU_ICON_DISPLAY_OFFBO9PANEL_OFFBO10KEY_PAD_OFFBO11LCD_FLASHINGBO12KEY_PAD_FLASHINGAO3BACKGROUND_LCD_FOR_ACTIVE_MODEAO4BACKGROUND_LCD_FOR_IDLE_MODEAO5BACKGROUND_LCD_FOR_STANDBY_MODEAO6BACKGROUND_LCD_TIME_TO_IDLEAO7BACKGROUND_LCD_TIME_TO_STANDBYAO8BACKGROUND_KEY_PAD_ACTIVE_MODEAO9BACKGROUND_KEY_PAD__IDLE_MODEAO10BACKGROUND_KEY_PAD_STANDBY_MODEAO11BACKGROUND_KEY_PAD_TIME_TO_IDLEAO12BACKGROUND_KEY_PAD_TIME_TO_STANDBYAO13REFRESH_TIMEBO13TIME_CONFIGURATIONBO14LCD_ICON_DISPLAYBO15LCD_ICON_DISPLAYBO16LCD_ICON_DISPLAYBO17LCD_ICON_DISPLAYBO18LCD_ICON_DISPLAYBO19LCD_ICON_DISPLAYBO20LCD_ICON_DISPLAYBO21LCD_ICON_DISPLAYBO22LCD_ICON_DISPLAYBO23LCD_ICON_DISPLAYBO24LCD_ICON_DISPLAYBO25LCD_ICON_FLASHINGAO14LCD_ICON_FLASHING_TIMEAO15SUBMENU_ICON_FLASHING_TIMEAO16ENTER_MENU_TIMEAO17EXIT_EDIT_TIMEAO18EXIT_MENU_TIMEAO19CO2_SETPOINT_FOR_ALARMAO20CO2_HYSTERESIS_FOR_ALARMAI4TEMPERATURE_SENSORAI5HUMIDITY_SENSORAI6CO2_SENSORAV56SETPOINTAI3EFFECTIVE_SETPOINTAV57DEFAULT_SETPOINTAV59OFFSET_RANGEBO55OPERATING_MODEBO56SETPOINT_DISPLAYBO57FAST_EDIT_MODEMV1FAN_MODEMV0FAN_CURRENT_SPEEDBO59PART_EDITABLEBO60FAST_EDIT_MODEAO21FAN_ICON_FLASHING_TIMEMV4OCCUPANCY_MODEMV3CURRENT_OCCUPIED_STATUSBO61FAST_EDIT_MODEBO62OCCUPIED_CONFIG_LOCAL_MODEAV58OFFSET_SETPOINTMV2FAN_TYPEBO68VAV_DEVICE_TYPEMV10VAV_REHEATER_TYPEMV11VAV_PERIMETER_TYPEMV9VAV_FAN_TYPEMV12VAV_DISCHARGE_TEMP_TYPEMV13VAV_SPACE_TEMP_TYPEAO37VAV_CO2_RANGEMV14VAV_HEATER_PRIORITYBO69VAV_DUAL_HEATBO66VAV_OCCUPANCY_CONTACT_TYPEBO67VAV_WINDOW_CONTACT_TYPEBO65VAV_DAMPER_DIRECTIONMV15VAV_SPACE_TEMPERATURE_SOURCEMV17VAV_CO2_SOURCEMV16VAV_SETPOINT_OFFSET_SOURCEAO29VAV_MAX_FLOW_COOLINGAO30VAV_MIN_FLOW_COOLINGAO31VAV_MAX_FLOW_HEATINGAO32VAV_MIN_FLOW_HEATINGAO33VAV_MIN_FLOW_STANDBYAO34VAV_MIN_FLOW_UNOCCUPIEDAO35VAV_FLOW_FAN_STARTAO23VAV_K_FACTOR_VALUEAO36VAV_MENU_PASSWORDBO64VAV_PRESSURE_SENSOR_RESET_TRIGGERAO22VAV_PRESSURE_SENSOR_VALUEAO24VAV_CALCULATED_DAMPER_POSITIONAO25VAV_CALCULATED_FLOWMV5VAV_DAMPER_COMMANDMV6VAV_FAN_COMMANDMV7VAV_REHEATER_COMMANDMV8VAV_PERIMETER_COMMANDAO26USER_DESIRED_DAMPER_POSITIONAO27USER_DESIRED_FLOWAO28USER_MEASURED_FLOWAV0MAIN_MENU_NUMERIC1:Present ValueAV1MAIN_MENU_NUMERIC2:Present ValueAV3MAIN_MENU_NUMERIC4:Present ValueAV4MAIN_MENU_NUMERIC5:Present ValueAV5MAIN_MENU_NUMERIC6:Present ValueAV7MAIN_MENU_NUMERIC8:Present ValueBV0MAIN_MENU_BOOLEAN1:Present ValueBV1MAIN_MENU_BOOLEAN2:Present ValueBV2MAIN_MENU_BOOLEAN3:Present ValueBV3MAIN_MENU_BOOLEAN4:Present ValueBV4MAIN_MENU_BOOLEAN5:Present ValueBV5MAIN_MENU_BOOLEAN6:Present ValueBV6MAIN_MENU_BOOLEAN7:Present ValueBV7MAIN_MENU_BOOLEAN8:Present ValueAV8TEMPERATURE_NUMERIC1:Present ValueAV9TEMPERATURE_NUMERIC2:Present ValueAV10TEMPERATURE_NUMERIC3:Present ValueAV11TEMPERATURE_NUMERIC4:Present ValueAV12TEMPERATURE_NUMERIC5:Present ValueAV13TEMPERATURE_NUMERIC6:Present ValueAV14TEMPERATURE_NUMERIC7:Present ValueAV15TEMPERATURE_NUMERIC8:Present ValueBV8TEMPERATURE_BOOLEAN1:Present ValueBV9TEMPERATURE_BOOLEAN2:Present ValueBV10TEMPERATURE_BOOLEAN3:Present ValueBV11TEMPERATURE_BOOLEAN4:Present ValueBV12TEMPERATURE_BOOLEAN5:Present ValueBV13TEMPERATURE_BOOLEAN6:Present ValueBV14TEMPERATURE_BOOLEAN7:Present ValueBV15TEMPERATURE_BOOLEAN8:Present ValueAV16FAN_NUMERIC1:Present ValueAV17FAN_NUMERIC2:Present ValueAV18FAN_NUMERIC3:Present ValueAV19FAN_NUMERIC4:Present ValueAV20FAN_NUMERIC5:Present ValueAV21FAN_NUMERIC6:Present ValueAV22FANNUMERIC7:Present ValueAV23FAN_NUMERIC8:Present ValueBV16FAN_BOOLEAN1:Present ValueBV17FAN_BOOLEAN2:Present ValueBV18FAN_BOOLEAN3:Present ValueBV19FAN_BOOLEAN4:Present ValueBV20FAN_BOOLEAN5:Present ValueBV21FAN_BOOLEAN6:Present ValueBV22FAN_BOOLEAN7:Present ValueBV23FAN_BOOLEAN8:Present ValueAV24LIGHT_NUMERIC1:Present ValueAV25LIGHT_NUMERIC2:Present ValueAV26LIGHT_NUMERIC3:Present ValueAV27LIGHT_NUMERIC4:Present ValueAV28LIGHT_NUMERIC5:Present ValueAV29LIGHT_NUMERIC6:Present ValueAV30LIGHTNUMERIC7:Present ValueAV31LIGHT_NUMERIC8:Present ValueBV24LIGHT_BOOLEAN1:Present ValueBV25LIGHT_BOOLEAN2:Present ValueBV26LIGHT_BOOLEAN3:Present ValueBV27LIGHT_BOOLEAN4:Present ValueBV28LIGHT_BOOLEAN5:Present ValueBV29LIGHT_BOOLEAN6:Present ValueBV30LIGHT_BOOLEAN7:Present ValueBV31LIGHT_BOOLEAN8:Present ValueAV32BLIND_NUMERIC1:Present ValueAV33BLIND_NUMERIC2:Present ValueAV34BLIND_NUMERIC3:Present ValueAV35BLIND_NUMERIC4:Present ValueAV36BLIND_NUMERIC5:Present ValueAV37BLIND_NUMERIC6:Present ValueAV38BLINDNUMERIC7:Present ValueAV39BLIND_NUMERIC8:Present ValueBV32BLIND_BOOLEAN1:Present ValueBV33BLIND_BOOLEAN2:Present ValueBV34BLIND_BOOLEAN3:Present ValueBV35BLIND_BOOLEAN4:Present ValueBV36BLIND_BOOLEAN5:Present ValueBV37BLIND_BOOLEAN6:Present ValueBV38BLIND_BOOLEAN7:Present ValueBV39BLIND_BOOLEAN8:Present ValueAV40ALARMS_NUMERIC1:Present ValueAV41ALARMS_NUMERIC2:Present ValueAV42ALARMS_NUMERIC3:Present ValueAV43ALARMS_NUMERIC4:Present ValueAV44ALARMS_NUMERIC5:Present ValueAV45ALARMS_NUMERIC6:Present ValueAV46ALARMSNUMERIC7:Present ValueAV47ALARMS_NUMERIC8:Present ValueBV40ALARMS_BOOLEAN1:Present ValueBV41ALARMS_BOOLEAN2:Present ValueBV42ALARMS_BOOLEAN3:Present ValueBV43ALARMS_BOOLEAN4:Present ValueBV44ALARMS_BOOLEAN5:Present ValueBV45ALARMS_BOOLEAN6:Present ValueBV46ALARMS_BOOLEAN7:Present ValueBV47ALARMS_BOOLEAN8:Present ValueAV48SETTINGS_NUMERIC1:Present ValueAV49SETTINGS_NUMERIC2:Present ValueAV50SETTINGS_NUMERIC3:Present ValueAV51SETTINGS_NUMERIC4:Present ValueAV52SETTINGS_NUMERIC5:Present ValueAV53SETTINGS_NUMERIC6:Present ValueAV54SETTINGSNUMERIC7:Present ValueAV55SETTINGS_NUMERIC8:Present ValueBV48SETTINGS_BOOLEAN1:Present ValueBV49SETTINGS_BOOLEAN2:Present ValueBV50SETTINGS_BOOLEAN3:Present ValueBV51SETTINGS_BOOLEAN4:Present ValueBV52SETTINGS_BOOLEAN5:Present ValueBV53SETTINGS_BOOLEAN6:Present ValueBV54SETTINGS_BOOLEAN7:Present ValueBV55SETTINGS_BOOLEAN8:Present Value
Integration notes
- The manual table mixes objects and object properties. Only Present Value rows are listed; rows for other properties (offset, filter, limits, names, visibility, Device-object properties such as BACNET_DEVICE_ID and BAUD_RATE) are left out.
- AV 58 OFFSET_SETPOINT and MV 2 FAN_TYPE are printed with a property number (1503, 1602) instead of Present value; they are listed because the Touch Point manuals show them as Present value objects. DEFAULT_SETPOINT is printed as "AC57" and listed as AV 57.
- BO 14-24 are all named LCD_ICON_DISPLAY (one per icon, given in the description); BO 25-35 LCD_ICON_FLASHING is a range shown by its first object.
- The VAV submenu objects come from a separate page; each one is linked to a VAV14-IP application object (named in the manual). AO 23 is printed twice there and listed once.
- User-defined parameter slots (NUMERIC1-8 as AV 0-55, BOOLEAN1-8 as BV 0-55) for the main menu and six submenus are all listed; the manual gives no Present value row for MAIN_MENU_NUMERIC3 and NUMERIC7 (AV 2, AV 6).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Point room panel (incl. Control Point VAV) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)
How many BACnet points does the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) have?
This list has 218 BACnet objects: 7 analog inputs, 38 analog outputs, 58 analog values, 40 binary outputs, 56 binary values, 1 multi-state input, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet points are writable?
207 of the 218 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official iSMA CONTROLLI Control Point room panel (incl. Control Point VAV) BACnet documentation?
The source is Control Point Software User Manual V1.1 - List of BACnet Objects, revision V1.1, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/control-point-software/V1.1/list-of-bacnet-objects.
What are the minimum BACnet points to integrate the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)?
Start with MV 4 OCCUPANCY_MODE (Occupancy mode, 1 = unoccupied, 2 = occupied); AV 56 SETPOINT (Temperature setpoint); MV 1 FAN_MODE (Fan mode: 1 off, 2-4 manual speed, 5 auto); AI 4 TEMPERATURE_SENSOR (Room temperature); AI 3 EFFECTIVE_SETPOINT (Effective setpoint (setpoint plus offset)); MV 3 CURRENT_OCCUPIED_STATUS (Occupancy status: 0 unocc, 1 occ, 2 standby, 3 forced); AI 5 HUMIDITY_SENSOR (Room humidity); AI 6 CO2_SENSOR (Room CO2).
How do I enable BMS control of the iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)?
BO 62 OCCUPIED_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.
How do I check these points on the real Control Point room panel (incl. Control Point VAV)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More iSMA CONTROLLI BACnet points lists
- Fan coil unit controller
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)
iSMA CONTROLLI iSMA-B-FCU fan coil controllers running the factory default FCU application.
Also known as: iSMA-B-FCU, iSMA-B-FCU-HH, iSMA-B-FCU-HL, iSMA-B-FCU-LL, DMP241en - Room panel (thermostat display)
iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)
iSMA CONTROLLI iSMA-B-LP wall room panels with BACnet MS/TP firmware, with or without humidity and CO2 sensors.
Also known as: iSMA-B-LP, iSMA-B-LP-H, iSMA-B-LP-C, iSMA-B-LP-HC, LP BACnet - VAV box controller
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controller (default VAV application)
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controllers running the factory VAV application (manual V1.4.0).
Also known as: iSMA-B-VAV14-IP, VAV14-IP, iSMA VAV14, VAV14-IP default application - Valve actuator / energy valve
iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)
iSMA CONTROLLI (ex Controlli) MVE-2-RS, MVC-2-RS and EBV-2-RS communicating valve actuators, including energy-valve functions with VLX valves.
Also known as: MVE-2-RS, MVC-2-RS, EBV-2-RS, iC Actuator Configurator, Controlli MVE, Controlli EBV energy valve, VLX energy valve - Room panel (thermostat display)
iSMA CONTROLLI Touch Point 2.0 room panel
iSMA CONTROLLI Touch Point 2.0 room panels (software manual V1.0.1).
Also known as: Touch Point 2.0, Touch Point ONE 2.0, iSMA Touch Point 2.0, TP2.0 - Room panel (thermostat display)
iSMA CONTROLLI Touch Point room panel
iSMA CONTROLLI Touch Point touch-button room panels (software manual V1.3), including the Touch Point VAV series.
Also known as: Touch Point, iSMA Touch Point, Touch Point VAV, Touch Point Software V1.3
Source: Control Point Software User Manual V1.1 - List of BACnet Objects · rev. V1.1. Object names, instances and units are reproduced as published; descriptions are our own.