The iSMA-B-LP is an LCD room panel on BACnet MS/TP. It exposes its temperature, humidity and CO2 readings, a temperature setpoint with offset, fan mode and speed, and occupancy mode as objects, plus many display and keypad settings. Seven menus of user-defined numeric and boolean parameters let the BMS show and edit its own values on the panel.
This page lists 171 BACnet objects for the iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP) — 163 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.
- Manufacturer
- iSMA CONTROLLI
- Model
- iSMA-B-LP room panel (BACnet MS/TP)
- Equipment
- Room panel (thermostat display)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 171 (163 writable)
- Transport
- BACnet MS/TP
- Firmware
- LP BACnet manual V1.2
- Also known as
- iSMA-B-LP, iSMA-B-LP-H, iSMA-B-LP-C, iSMA-B-LP-HC, LP BACnet
Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.
BMS integration notes: iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)
Read the room temperature (AI 4), humidity (AI 5) and CO2 (AI 6) and the effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) when the BMS drives the room. BO 62 decides whether occupancy is local or set by the BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | OCCUPANCY_MODE | Occupancy mode, 1 = unoccupied, 2 = occupied | Write |
| AV 56 | SETPOINT_VALUE | Temperature setpoint | Write |
| MV 1 | FAN_MODE | Fan mode: 1 off, 2-4 manual speed, 5 auto | Write |
| AI 4 | TEMPERATURE_SENSOR | Room temperature | Read |
| AI 3 | EFFECTIVE_SETPOINT | Effective setpoint (setpoint plus offset) | Read |
| AI 5 | HUMIDITY_SENSOR | Room humidity | Read |
| AI 6 | CO2_SENSOR | Room CO2 | Read |
| MV 0 | FAN_CURRENT_SPEED | Current fan speed | Write |
Enable & remote start
BO 62 OCCUPIED_LOCAL_MODE selects local or BMS occupancy mode.
Network setup
- Device instance and baud rate are Device-object properties (BACNET_DEVICE_ID default 0xFFFFFFFF, BAUD_RATE default 115200).
Watch out for
- Most configuration objects are stored in panel memory; avoid cyclic writes.
- Sensor objects exist only on panel versions with that sensor (MI 1 SENSORS gives the version).
iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | LIVE_TIME | Uptime in sec | s | Read | |
| AO | 0 | PANEL_PASSWORD | Password for the menu edit mode | Write | ||
| MI | 1 | SENSORS | Read | 1=iSMA-B-LP 2=iSMA-B-LP-H 3=iSMA-B-LP-C 4=iSMA-B-LP-HC | ||
| AI | 1 | BACKGROUND_ILLUMINATION LCD_CURRENT_VALUE | Current display illumination value | Read | ||
| AI | 2 | BACKGROUND_ILLUMINATION KEY_PAD_CURRENT_VALUE | Current keypad illumination value | Read | ||
| AO | 1 | HOURS | Hours in the time displaying | Write | ||
| AO | 2 | MINUTES | Minutes in the time displaying | Write | ||
| BO | 0 | BEEPER | Write | False=Inactive, True=Active(def) | ||
| BO | 1 | FORMAT | Write | False=24h(def), True=12h | ||
| BO | 2 | TEMPERATURE_UNIT | Write | False=C, True=F | ||
| BO | 3 | BACKGROUND_ILLUMINATION LCD_ACTIVE | Write | False=Inactive, True=Active | ||
| BO | 4 | ILLUMINATION KEY_PAD | Write | False=Inactive, True=Active | ||
| BO | 5 | CO2_ALARM LCD | Write | False=Inactive True=Active | ||
| BO | 6 | CO2_ALARM BUZZER | Write | False=Inactive True=Active | ||
| BO | 7 | CO2_ALARM HIGH | Write | False=Inactive True=Active | ||
| BO | 8 | SUBMENU_ICON_DISPLAY_OFF | Write | False=Inactive True=Active | ||
| BO | 9 | PANEL_OFF | Write | False=Panel on(def) True=Panel off | ||
| BO | 10 | KEY_PAD_OFF | Write | False=keypad on(def), True=keypad off | ||
| BO | 11 | FLASHING_LCD | Write | False=Inactive(def) True=Active | ||
| BO | 12 | FLASHING__KEY_PAD | Write | False=Inactive(def) True=Active | ||
| AO | 3 | BACKGROUND_ILLUMINATION LCD_FOR_ACTIVE_MODE | Default 60% | Write | ||
| AO | 4 | BACKGROUND_ILLUMINATION LCD_FOR_IDLE_MODE | Default 40% | Write | ||
| AO | 5 | BACKGROUND_ILLUMINATION LCD_FOR_STANDBY_MODE | Default 0% | Write | ||
| AO | 6 | BACKGROUND_ILLUMINATION LCD_TIME_TO_IDLE | Default 10 sec | Write | ||
| AO | 7 | BACKGROUND_ILLUMINATION LCD_TIME_TO_STANDBY | Default 5 sec | Write | ||
| AO | 8 | BACKGROUND_ILLUMINATION KEY_PAD_ACTIVE_MODE | Default 10% | Write | ||
| AO | 9 | BACKGROUND_ILLUMINATION KEY_PAD__IDLE_MODE | Default 40% | Write | ||
| AO | 10 | BACKGROUND_ILLUMINATION KEY_PAD_STANDBY_MODE | Default 60% | Write | ||
| AO | 11 | BACKGROUND_ILLUMINATION KEY_PAD_TIME_TO_IDLE | Default 10 sec | Write | ||
| AO | 12 | BACKGROUND_ILLUMINATION KEY_PAD_TIME_TO_STANDBY | Default 5 sec | Write | ||
| AO | 13 | REFRESH_TIME | Default 2 sec | Write | ||
| BO | 13 | TIME_CONFIGURATION | Write | True=the clock is visible(default) False=the clock is not visible | ||
| BO | 14 | SUN | Write | |||
| BO | 15 | MOON | Write | |||
| BO | 16 | HEATING | Write | |||
| BO | 17 | COOLING | Write | |||
| BO | 18 | HUMIDFIRE | Write | |||
| BO | 19 | DEHUMIDFIRE | Write | |||
| BO | 20 | WIRELESS | Write | |||
| BO | 21 | SETTINGS | Write | |||
| BO | 22 | ECO | Write | |||
| BO | 23 | RECIRCULATION | Write | |||
| BO | 24 | PC | Write | |||
| AO | 14 | LCD_ICON_FLASHING_TIME | The time, which is the basis for calculating the frequency of icon | Write | ||
| AO | 15 | SUBMENU_ICON_FLASHING_TIME | The time, which is the basis for calculating the frequency of icon | Write | ||
| AO | 16 | ENTER_MENU_TIME | Default value: 2 sec | Write | ||
| AO | 17 | EXIT_EDIT_TIME | Default value: 5 sec | Write | ||
| AO | 18 | EXIT_MENU_TIME | Default value: 10 sec | Write | ||
| AO | 19 | CO2_SETPOINT_FOR_ALARM | CO2 Alarm setpoint | Write | ||
| AO | 20 | CO2_HYSTERESIS_FOR_ALARM | CO2 Alarm hysteresis | Write | ||
| AImin | 4 | TEMPERATURE_SENSOR | Actual temperature sensor value with offset | °C | Read | |
| AImin | 5 | HUMIDITY_SENSOR | Actual humidity sensor value with offset | %RH | Read | |
| AImin | 6 | CO2_SENSOR | Actual CO2 sensor value with offset | ppm | Read | |
| AVmin | 56 | SETPOINT_VALUE | Actual setpoint value | Write | ||
| AImin | 3 | EFFECTIVE_SETPOINT | Sum of effective setpoints and offset values | Read | ||
| AV | 57 | DEFAULT_SETPOINT | Default value: 21oC | Write | ||
| AV | 59 | OFFSET_RANGE | Offset value limit | Write | ||
| BO | 55 | SETPOINT_CONFIG OPERATING_MODE | Write | False=Changing offset True=Changing setpoint(def) | ||
| BO | 56 | SETPOINT_CONFIG SETPOINT_DISPLAY | Write | False=Inactive True=Active(def) | ||
| BO | 57 | SETPOINT_CONFIG FAST_EDIT_MODE | Write | False=Inactive(def) True=Active | ||
| MVmin | 1 | FAN_MODE | Write | 1=OFF, 2=Manual Speed 1 (def), 3=Manual Speed 2, 4=Manual Speed 3, 5=AUTO | ||
| MVmin | 0 | FAN_CURRENT_SPEED | Write | 1=OFF(def) 2=Manual Speed 1 3=Manual Speed 2 4=Manual Speed 3 5=Auto Speed 1 6=Auto Speed 2 7=Auto Speed 3 | ||
| BO | 59 | PART_EDITABLE | Write | False=Full editable(def) True=Auto_Off_Mode | ||
| BO | 60 | FASTEDITMODE | Write | False=Inactive(def) True=Active | ||
| AO | 21 | FAN_ICON_FLASHING_TIME | Time basis for calculating the frequency of the fan icon rotation simulation | Write | ||
| MVmin | 4 | OCCUPANCY_MODE | Occupancy mode setting from the room panel | Write | 1=Unoccupied 2=Occupied | |
| MV | 4 | OCCUPANCY_CURRENT_STATUS | Write | 0=Unoccupied 1=Occupied 2=Standby 3=Forced occupied | ||
| BO | 61 | OCCUPANCY_MODE FAST_EDIT_MODE | Write | False=Inactive(def) True=Active | ||
| BO | 62 | OCCUPIED_LOCAL_MODE | Write | False=Local Mode True=BMS Mode | ||
| AV | 58 | OFFSET_SETPOINT | Default value: 0oC | Write | ||
| MV | 2 | FAN_TYPE | Write | 1=Fan is controlled by an analog value 0-10 VDC 2=1-Speed Fan 3=2-Speed Fan 4=3-Speed Fan | ||
| AV | 0 | MAINMENU_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, main menu menu | Write | ||
| AV | 1 | MAINMENU_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, main menu menu | Write | ||
| AV | 3 | MAINMENU_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, main menu menu | Write | ||
| AV | 4 | MAINMENU_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, main menu menu | Write | ||
| AV | 5 | MAINMENU_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, main menu menu | Write | ||
| AV | 7 | MAINMENU_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, main menu menu | Write | ||
| BV | 0 | MAINMENU_BOOLEAN1 PRESENT_VALUE | User-defined boolean parameter 1, main menu menu | Write | ||
| BV | 1 | MAINMENU_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, main menu menu | Write | ||
| BV | 2 | MAINMENU_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, main menu menu | Write | ||
| BV | 3 | MAINMENU_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, main menu menu | Write | ||
| BV | 4 | MAINMENU_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, main menu menu | Write | ||
| BV | 5 | MAINMENU_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, main menu menu | Write | ||
| BV | 6 | MAINMENU_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, main menu menu | Write | ||
| BV | 7 | MAINMENU_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, main menu menu | Write | ||
| AV | 8 | TEMPERATURE_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, temperature menu | Write | ||
| AV | 9 | TEMPERATURE_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, temperature menu | Write | ||
| AV | 10 | TEMPERATURE_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, temperature menu | Write | ||
| AV | 11 | TEMPERATURE_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, temperature menu | Write | ||
| AV | 12 | TEMPERATURE_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, temperature menu | Write | ||
| AV | 13 | TEMPERATURE_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, temperature menu | Write | ||
| AV | 14 | TEMPERATURE_NUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, temperature menu | Write | ||
| AV | 15 | TEMPERATURE_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, temperature menu | Write | ||
| BV | 8 | TEMPERATURE_BOOLEAN1 PRESENT_VALUE | User-defined boolean parameter 1, temperature menu | Write | ||
| BV | 9 | TEMPERATURE_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, temperature menu | Write | ||
| BV | 10 | TEMPERATURE_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, temperature menu | Write | ||
| BV | 11 | TEMPERATURE_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, temperature menu | Write | ||
| BV | 12 | TEMPERATURE_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, temperature menu | Write | ||
| BV | 13 | TEMPERATURE_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, temperature menu | Write | ||
| BV | 14 | TEMPERATURE_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, temperature menu | Write | ||
| BV | 15 | TEMPERATURE_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, temperature menu | Write | ||
| AV | 16 | FAN_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, fan menu | Write | ||
| AV | 17 | FAN_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, fan menu | Write | ||
| AV | 18 | FAN_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, fan menu | Write | ||
| AV | 19 | FAN_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, fan menu | Write | ||
| AV | 20 | FAN_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, fan menu | Write | ||
| AV | 21 | FAN_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, fan menu | Write | ||
| AV | 22 | FANNUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, fan menu | Write | ||
| AV | 23 | FAN_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, fan menu | Write | ||
| AV | 24 | LIGHT_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, light menu | Write | ||
| AV | 25 | LIGHT_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, light menu | Write | ||
| AV | 26 | LIGHT_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, light menu | Write | ||
| AV | 27 | LIGHT_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, light menu | Write | ||
| AV | 28 | LIGHT_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, light menu | Write | ||
| AV | 29 | LIGHT_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, light menu | Write | ||
| AV | 30 | LIGHTNUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, light menu | Write | ||
| AV | 31 | LIGHT_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, light menu | Write | ||
| BV | 25 | LIGHT_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, light menu | Write | ||
| BV | 26 | LIGHT_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, light menu | Write | ||
| BV | 27 | LIGHT_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, light menu | Write | ||
| BV | 28 | LIGHT_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, light menu | Write | ||
| BV | 29 | LIGHT_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, light menu | Write | ||
| BV | 30 | LIGHT_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, light menu | Write | ||
| BV | 31 | LIGHT_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, light menu | Write | ||
| AV | 32 | BLIND_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, blind menu | Write | ||
| AV | 33 | BLIND_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, blind menu | Write | ||
| AV | 35 | BLIND_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, blind menu | Write | ||
| AV | 36 | BLIND_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, blind menu | Write | ||
| AV | 37 | BLIND_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, blind menu | Write | ||
| AV | 38 | BLINDNUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, blind menu | Write | ||
| AV | 39 | BLIND_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, blind menu | Write | ||
| BV | 32 | BLIND_BOOLEAN1 PRESENT_VALUE | User-defined boolean parameter 1, blind menu | Write | ||
| BV | 33 | BLIND_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, blind menu | Write | ||
| BV | 34 | BLIND_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, blind menu | Write | ||
| BV | 35 | BLIND_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, blind menu | Write | ||
| BV | 36 | BLIND_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, blind menu | Write | ||
| BV | 37 | BLIND_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, blind menu | Write | ||
| BV | 38 | BLIND_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, blind menu | Write | ||
| BV | 39 | BLIND_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, blind menu | Write | ||
| AV | 40 | ALARMS_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, alarms menu | Write | ||
| AV | 41 | ALARMS_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, alarms menu | Write | ||
| AV | 42 | ALARMS_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, alarms menu | Write | ||
| AV | 43 | ALARMS_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, alarms menu | Write | ||
| AV | 44 | ALARMS_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, alarms menu | Write | ||
| AV | 45 | ALARMS_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, alarms menu | Write | ||
| AV | 46 | ALARMSNUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, alarms menu | Write | ||
| AV | 47 | ALARMS_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, alarms menu | Write | ||
| BV | 40 | ALARMS_BOOLEAN1 PRESENT_VALUE | User-defined boolean parameter 1, alarms menu | Write | ||
| BV | 41 | ALARMS_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, alarms menu | Write | ||
| BV | 42 | ALARMS_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, alarms menu | Write | ||
| BV | 43 | ALARMS_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, alarms menu | Write | ||
| BV | 44 | ALARMS_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, alarms menu | Write | ||
| BV | 45 | ALARMS_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, alarms menu | Write | ||
| BV | 46 | ALARMS_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, alarms menu | Write | ||
| BV | 47 | ALARMS_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, alarms menu | Write | ||
| AV | 48 | SETTINGS_NUMERIC1 PRESENT_VALUE | User-defined numeric parameter 1, settings menu | Write | ||
| AV | 49 | SETTINGS_NUMERIC2 PRESENT_VALUE | User-defined numeric parameter 2, settings menu | Write | ||
| AV | 50 | SETTINGS_NUMERIC3 PRESENT_VALUE | User-defined numeric parameter 3, settings menu | Write | ||
| AV | 51 | SETTINGS_NUMERIC4 PRESENT_VALUE | User-defined numeric parameter 4, settings menu | Write | ||
| AV | 52 | SETTINGS_NUMERIC5 PRESENT_VALUE | User-defined numeric parameter 5, settings menu | Write | ||
| AV | 53 | SETTINGS_NUMERIC6 PRESENT_VALUE | User-defined numeric parameter 6, settings menu | Write | ||
| AV | 54 | SETTINGSNUMERIC7 PRESENT_VALUE | User-defined numeric parameter 7, settings menu | Write | ||
| AV | 55 | SETTINGS_NUMERIC8 PRESENT_VALUE | User-defined numeric parameter 8, settings menu | Write | ||
| BV | 48 | SETTINGS_BOOLEAN1 PRESENT_VALUE | User-defined boolean parameter 1, settings menu | Write | ||
| BV | 49 | SETTINGS_BOOLEAN2 PRESENT_VALUE | User-defined boolean parameter 2, settings menu | Write | ||
| BV | 50 | SETTINGS_BOOLEAN3 PRESENT_VALUE | User-defined boolean parameter 3, settings menu | Write | ||
| BV | 51 | SETTINGS_BOOLEAN4 PRESENT_VALUE | User-defined boolean parameter 4, settings menu | Write | ||
| BV | 52 | SETTINGS_BOOLEAN5 PRESENT_VALUE | User-defined boolean parameter 5, settings menu | Write | ||
| BV | 53 | SETTINGS_BOOLEAN6 PRESENT_VALUE | User-defined boolean parameter 6, settings menu | Write | ||
| BV | 54 | SETTINGS_BOOLEAN7 PRESENT_VALUE | User-defined boolean parameter 7, settings menu | Write | ||
| BV | 55 | SETTINGS_BOOLEAN8 PRESENT_VALUE | User-defined boolean parameter 8, settings menu | Write |
No points match these filters.
Object ID lookup: iSMA CONTROLLI iSMA-B-LP room panel point IDs by name
AI0LIVE_TIMEAO0PANEL_PASSWORDMI1SENSORSAI1BACKGROUND_ILLUMINATION LCD_CURRENT_VALUEAI2BACKGROUND_ILLUMINATION KEY_PAD_CURRENT_VALUEAO1HOURSAO2MINUTESBO0BEEPERBO1FORMATBO2TEMPERATURE_UNITBO3BACKGROUND_ILLUMINATION LCD_ACTIVEBO4ILLUMINATION KEY_PADBO5CO2_ALARM LCDBO6CO2_ALARM BUZZERBO7CO2_ALARM HIGHBO8SUBMENU_ICON_DISPLAY_OFFBO9PANEL_OFFBO10KEY_PAD_OFFBO11FLASHING_LCDBO12FLASHING__KEY_PADAO3BACKGROUND_ILLUMINATION LCD_FOR_ACTIVE_MODEAO4BACKGROUND_ILLUMINATION LCD_FOR_IDLE_MODEAO5BACKGROUND_ILLUMINATION LCD_FOR_STANDBY_MODEAO6BACKGROUND_ILLUMINATION LCD_TIME_TO_IDLEAO7BACKGROUND_ILLUMINATION LCD_TIME_TO_STANDBYAO8BACKGROUND_ILLUMINATION KEY_PAD_ACTIVE_MODEAO9BACKGROUND_ILLUMINATION KEY_PAD__IDLE_MODEAO10BACKGROUND_ILLUMINATION KEY_PAD_STANDBY_MODEAO11BACKGROUND_ILLUMINATION KEY_PAD_TIME_TO_IDLEAO12BACKGROUND_ILLUMINATION KEY_PAD_TIME_TO_STANDBYAO13REFRESH_TIMEBO13TIME_CONFIGURATIONBO14SUNBO15MOONBO16HEATINGBO17COOLINGBO18HUMIDFIREBO19DEHUMIDFIREBO20WIRELESSBO21SETTINGSBO22ECOBO23RECIRCULATIONBO24PCAO14LCD_ICON_FLASHING_TIMEAO15SUBMENU_ICON_FLASHING_TIMEAO16ENTER_MENU_TIMEAO17EXIT_EDIT_TIMEAO18EXIT_MENU_TIMEAO19CO2_SETPOINT_FOR_ALARMAO20CO2_HYSTERESIS_FOR_ALARMAI4TEMPERATURE_SENSORAI5HUMIDITY_SENSORAI6CO2_SENSORAV56SETPOINT_VALUEAI3EFFECTIVE_SETPOINTAV57DEFAULT_SETPOINTAV59OFFSET_RANGEBO55SETPOINT_CONFIG OPERATING_MODEBO56SETPOINT_CONFIG SETPOINT_DISPLAYBO57SETPOINT_CONFIG FAST_EDIT_MODEMV1FAN_MODEMV0FAN_CURRENT_SPEEDBO59PART_EDITABLEBO60FASTEDITMODEAO21FAN_ICON_FLASHING_TIMEMV4OCCUPANCY_MODEMV4OCCUPANCY_CURRENT_STATUSBO61OCCUPANCY_MODE FAST_EDIT_MODEBO62OCCUPIED_LOCAL_MODEAV58OFFSET_SETPOINTMV2FAN_TYPEAV0MAINMENU_NUMERIC1 PRESENT_VALUEAV1MAINMENU_NUMERIC2 PRESENT_VALUEAV3MAINMENU_NUMERIC4 PRESENT_VALUEAV4MAINMENU_NUMERIC5 PRESENT_VALUEAV5MAINMENU_NUMERIC6 PRESENT_VALUEAV7MAINMENU_NUMERIC8 PRESENT_VALUEBV0MAINMENU_BOOLEAN1 PRESENT_VALUEBV1MAINMENU_BOOLEAN2 PRESENT_VALUEBV2MAINMENU_BOOLEAN3 PRESENT_VALUEBV3MAINMENU_BOOLEAN4 PRESENT_VALUEBV4MAINMENU_BOOLEAN5 PRESENT_VALUEBV5MAINMENU_BOOLEAN6 PRESENT_VALUEBV6MAINMENU_BOOLEAN7 PRESENT_VALUEBV7MAINMENU_BOOLEAN8 PRESENT_VALUEAV8TEMPERATURE_NUMERIC1 PRESENT_VALUEAV9TEMPERATURE_NUMERIC2 PRESENT_VALUEAV10TEMPERATURE_NUMERIC3 PRESENT_VALUEAV11TEMPERATURE_NUMERIC4 PRESENT_VALUEAV12TEMPERATURE_NUMERIC5 PRESENT_VALUEAV13TEMPERATURE_NUMERIC6 PRESENT_VALUEAV14TEMPERATURE_NUMERIC7 PRESENT_VALUEAV15TEMPERATURE_NUMERIC8 PRESENT_VALUEBV8TEMPERATURE_BOOLEAN1 PRESENT_VALUEBV9TEMPERATURE_BOOLEAN2 PRESENT_VALUEBV10TEMPERATURE_BOOLEAN3 PRESENT_VALUEBV11TEMPERATURE_BOOLEAN4 PRESENT_VALUEBV12TEMPERATURE_BOOLEAN5 PRESENT_VALUEBV13TEMPERATURE_BOOLEAN6 PRESENT_VALUEBV14TEMPERATURE_BOOLEAN7 PRESENT_VALUEBV15TEMPERATURE_BOOLEAN8 PRESENT_VALUEAV16FAN_NUMERIC1 PRESENT_VALUEAV17FAN_NUMERIC2 PRESENT_VALUEAV18FAN_NUMERIC3 PRESENT_VALUEAV19FAN_NUMERIC4 PRESENT_VALUEAV20FAN_NUMERIC5 PRESENT_VALUEAV21FAN_NUMERIC6 PRESENT_VALUEAV22FANNUMERIC7 PRESENT_VALUEAV23FAN_NUMERIC8 PRESENT_VALUEAV24LIGHT_NUMERIC1 PRESENT_VALUEAV25LIGHT_NUMERIC2 PRESENT_VALUEAV26LIGHT_NUMERIC3 PRESENT_VALUEAV27LIGHT_NUMERIC4 PRESENT_VALUEAV28LIGHT_NUMERIC5 PRESENT_VALUEAV29LIGHT_NUMERIC6 PRESENT_VALUEAV30LIGHTNUMERIC7 PRESENT_VALUEAV31LIGHT_NUMERIC8 PRESENT_VALUEBV25LIGHT_BOOLEAN2 PRESENT_VALUEBV26LIGHT_BOOLEAN3 PRESENT_VALUEBV27LIGHT_BOOLEAN4 PRESENT_VALUEBV28LIGHT_BOOLEAN5 PRESENT_VALUEBV29LIGHT_BOOLEAN6 PRESENT_VALUEBV30LIGHT_BOOLEAN7 PRESENT_VALUEBV31LIGHT_BOOLEAN8 PRESENT_VALUEAV32BLIND_NUMERIC2 PRESENT_VALUEAV33BLIND_NUMERIC3 PRESENT_VALUEAV35BLIND_NUMERIC4 PRESENT_VALUEAV36BLIND_NUMERIC5 PRESENT_VALUEAV37BLIND_NUMERIC6 PRESENT_VALUEAV38BLINDNUMERIC7 PRESENT_VALUEAV39BLIND_NUMERIC8 PRESENT_VALUEBV32BLIND_BOOLEAN1 PRESENT_VALUEBV33BLIND_BOOLEAN2 PRESENT_VALUEBV34BLIND_BOOLEAN3 PRESENT_VALUEBV35BLIND_BOOLEAN4 PRESENT_VALUEBV36BLIND_BOOLEAN5 PRESENT_VALUEBV37BLIND_BOOLEAN6 PRESENT_VALUEBV38BLIND_BOOLEAN7 PRESENT_VALUEBV39BLIND_BOOLEAN8 PRESENT_VALUEAV40ALARMS_NUMERIC1 PRESENT_VALUEAV41ALARMS_NUMERIC2 PRESENT_VALUEAV42ALARMS_NUMERIC3 PRESENT_VALUEAV43ALARMS_NUMERIC4 PRESENT_VALUEAV44ALARMS_NUMERIC5 PRESENT_VALUEAV45ALARMS_NUMERIC6 PRESENT_VALUEAV46ALARMSNUMERIC7 PRESENT_VALUEAV47ALARMS_NUMERIC8 PRESENT_VALUEBV40ALARMS_BOOLEAN1 PRESENT_VALUEBV41ALARMS_BOOLEAN2 PRESENT_VALUEBV42ALARMS_BOOLEAN3 PRESENT_VALUEBV43ALARMS_BOOLEAN4 PRESENT_VALUEBV44ALARMS_BOOLEAN5 PRESENT_VALUEBV45ALARMS_BOOLEAN6 PRESENT_VALUEBV46ALARMS_BOOLEAN7 PRESENT_VALUEBV47ALARMS_BOOLEAN8 PRESENT_VALUEAV48SETTINGS_NUMERIC1 PRESENT_VALUEAV49SETTINGS_NUMERIC2 PRESENT_VALUEAV50SETTINGS_NUMERIC3 PRESENT_VALUEAV51SETTINGS_NUMERIC4 PRESENT_VALUEAV52SETTINGS_NUMERIC5 PRESENT_VALUEAV53SETTINGS_NUMERIC6 PRESENT_VALUEAV54SETTINGSNUMERIC7 PRESENT_VALUEAV55SETTINGS_NUMERIC8 PRESENT_VALUEBV48SETTINGS_BOOLEAN1 PRESENT_VALUEBV49SETTINGS_BOOLEAN2 PRESENT_VALUEBV50SETTINGS_BOOLEAN3 PRESENT_VALUEBV51SETTINGS_BOOLEAN4 PRESENT_VALUEBV52SETTINGS_BOOLEAN5 PRESENT_VALUEBV53SETTINGS_BOOLEAN6 PRESENT_VALUEBV54SETTINGS_BOOLEAN7 PRESENT_VALUEBV55SETTINGS_BOOLEAN8 PRESENT_VALUE
Integration notes
- The manual table mixes objects and object properties. Only Present Value rows are listed as points; rows for other properties (offset, filter, limits, names, visibility, Device-object properties such as BACNET_DEVICE_ID and BAUD_RATE) are left out.
- AV 58 OFFSET_SETPOINT and MV 2 FAN_TYPE are printed with a property number (1503, 1602) instead of Present value; they are listed because the Touch Point manuals show them as Present value objects.
- DEFAULT_SETPOINT is printed as "AC 57"; it is listed as AV 57.
- The manual prints both OCCUPANCY_MODE and OCCUPANCY_CURRENT_STATUS as MV 4 (the Control Point manual puts the status on MV 3); both are kept as printed.
- User-defined parameter slots (NUMERIC1-8 as AV, BOOLEAN1-8 as BV) for the main menu and the temperature, fan, light, blind, alarm and occupancy submenus are all listed; the manual prints no MAINMENU_NUMERIC3 or NUMERIC7 row. Some slots are printed with clashing IDs: FAN_BOOLEAN1-8 as BV 8-15 (same as TEMPERATURE_BOOLEAN1-8), LIGHT_BOOLEAN1 as BV 31 (same as LIGHT_BOOLEAN8) and BLIND_NUMERIC1 as AV 31 (same as LIGHT_NUMERIC8). Those clashing rows are left out; the Control Point manual numbers the same slots fan BV 16-23, light BV 24-31 and blind AV 32-39.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iSMA-B-LP room panel (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)
How many BACnet points does the iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP) have?
This list has 171 BACnet objects: 7 analog inputs, 22 analog outputs, 57 analog values, 32 binary outputs, 47 binary values, 1 multi-state input, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP) BACnet points are writable?
163 of the 171 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP) BACnet documentation?
The source is LP BACnet User Manual V1.2 - List of BACnet Objects, revision V1.2, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/lp-bacnet/V1.2/list-of-bacnet-objects.
What are the minimum BACnet points to integrate the iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)?
Start with MV 4 OCCUPANCY_MODE (Occupancy mode, 1 = unoccupied, 2 = occupied); AV 56 SETPOINT_VALUE (Temperature setpoint); MV 1 FAN_MODE (Fan mode: 1 off, 2-4 manual speed, 5 auto); AI 4 TEMPERATURE_SENSOR (Room temperature); AI 3 EFFECTIVE_SETPOINT (Effective setpoint (setpoint plus offset)); AI 5 HUMIDITY_SENSOR (Room humidity); AI 6 CO2_SENSOR (Room CO2); MV 0 FAN_CURRENT_SPEED (Current fan speed).
How do I enable BMS control of the iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)?
BO 62 OCCUPIED_LOCAL_MODE selects local or BMS occupancy mode.
How do I check these points on the real iSMA-B-LP room panel (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More iSMA CONTROLLI BACnet points lists
- Room panel (thermostat display)
iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)
iSMA CONTROLLI Control Point room panels, including the VAV version used with the iSMA-B-VAV14-IP controller.
Also known as: Control Point, iSMA Control Point, Control Point VAV, Control Point Software V1.1 - Fan coil unit controller
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)
iSMA CONTROLLI iSMA-B-FCU fan coil controllers running the factory default FCU application.
Also known as: iSMA-B-FCU, iSMA-B-FCU-HH, iSMA-B-FCU-HL, iSMA-B-FCU-LL, DMP241en - VAV box controller
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controller (default VAV application)
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controllers running the factory VAV application (manual V1.4.0).
Also known as: iSMA-B-VAV14-IP, VAV14-IP, iSMA VAV14, VAV14-IP default application - Valve actuator / energy valve
iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)
iSMA CONTROLLI (ex Controlli) MVE-2-RS, MVC-2-RS and EBV-2-RS communicating valve actuators, including energy-valve functions with VLX valves.
Also known as: MVE-2-RS, MVC-2-RS, EBV-2-RS, iC Actuator Configurator, Controlli MVE, Controlli EBV energy valve, VLX energy valve - Room panel (thermostat display)
iSMA CONTROLLI Touch Point 2.0 room panel
iSMA CONTROLLI Touch Point 2.0 room panels (software manual V1.0.1).
Also known as: Touch Point 2.0, Touch Point ONE 2.0, iSMA Touch Point 2.0, TP2.0 - Room panel (thermostat display)
iSMA CONTROLLI Touch Point room panel
iSMA CONTROLLI Touch Point touch-button room panels (software manual V1.3), including the Touch Point VAV series.
Also known as: Touch Point, iSMA Touch Point, Touch Point VAV, Touch Point Software V1.3
Source: LP BACnet User Manual V1.2 - List of BACnet Objects · rev. V1.2. Object names, instances and units are reproduced as published; descriptions are our own.