- iSMA-B-FCU fan coil controller (default application)
Fan coil unit controller · BACnet points list
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet points list
Updated 12 November 2026Unofficial source
The iSMA-B-FCU ships with a ready-made fan coil application (2- or 4-pipe, digital or analog valve control, 3-speed or analog fan) that exposes a fixed set of BACnet Analog Value and Binary Value objects, the same data as its Modbus registers. The BMS can set occupancy mode, setpoint, fan mode and FCU mode, write the room temperature, and read the effective setpoint, valve and fan outputs and sensor values. Up to five slave FCUs can follow one master over BACnet.
This page lists 119 BACnet objects for the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) — 86 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of iSMA CONTROLLI’s documentation hosted by Innon (iSMA distributor), not by iSMA CONTROLLI itself, so treat it as unofficial.
- Manufacturer
- iSMA CONTROLLI
- Model
- iSMA-B-FCU fan coil controller (default application)
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 119 (86 writable)
- Transport
- BACnet MS/TP
- Firmware
- Default application 2.0 (App_version default)
- Default device instance
- 826 followed by the 3-digit MAC address (MAC 83 = 826083)
- Also known as
- iSMA-B-FCU, iSMA-B-FCU-HH, iSMA-B-FCU-HL, iSMA-B-FCU-LL, DMP241en
- Source document
- iSMA-B-FCU Application User Manual · DMP241en · rev. 1st Issue rev. 5, 02/2022 (unofficial copy, hosted by Innon (iSMA distributor))
Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.
BMS integration notes: iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)
Use the default application as shipped: write Occupancy_Mode, Setpoint, Fan_Mode and FCU_Mode from the BMS, and read Effective Setpoint, Occupancy Status, Fan Status and the valve outputs. If the room temperature comes from the BMS, write it to Net_Temperature. Only the master FCU of a group should be controlled from the BMS; slaves follow it.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Occupancy_Mode | 0 unoccupied, 1 occupied, 2 standby | Write |
| AV 4 | FCU_Mode | 0 off, 1 auto, 2 heat, 3 cool, 4 fan only | Write |
| AV 3 | Fan_Mode | 0 off, 1-3 manual speed, 4 auto | Write |
| AV 1 | Setpoint | Room temperature setpoint | Write |
| AV 100 | Effective Setpoint | Setpoint in use after offsets | Read |
| AV 101 | Occupancy Status | 0 unocc, 1 occ, 2 standby, 3 forced occupied | Read |
| AV 102 | Fan Status | 0 off, 1-3 manual speed, 4-6 auto speed | Read |
| AV 104 | Cv | Room temperature used for control | Read |
| AV 110 | Heating_Valve | Heating valve output, % | Read |
| AV 111 | Coolling_Valve | Cooling valve output, % | Read |
Sensors & values from the BMS
Net_Temperature (AV 6) takes a room temperature from the network as the control value source.
Network setup
- The MS/TP MAC address is set on the DIP switches (binary weights).
- Device instance = 826 followed by the 3-digit MAC address (MAC 83 gives 826083).
- For master/slave rooms, give slaves the BACnet device IDs from the auto-binding table, or set Remote_SlaveN_Device_ID and Local_Remote_Auto_Binding.
- Only the master works with the room panel and the BMS; up to 5 slaves follow it.
Watch out for
- Manual override objects (valve/fan manual value plus the matching enable BV) take outputs out of automatic control.
- Check value scaling: the table defaults look like tenths (210 = 21.0 °C).
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Occupancy_Mode | Occupancy mode command | Write | 0=Unoccupied, 1=Occupied, 2=Standby | |
| AVmin | 1 | Setpoint | User temperature setpoint | °C | Write | |
| AV | 2 | Setpoint_Offset | User setpoint offset | °C | Write | |
| AVmin | 3 | Fan_Mode | Fan mode command | Write | 0=Off, 1=Speed 1 (manual), 2=Speed 2 (manual), 3=Speed 3 (manual), 4=Auto | |
| AVmin | 4 | FCU_Mode | Fan coil operating mode | Write | 0=Off, 1=Auto, 2=Heating only, 3=Cooling only, 4=Fan only | |
| AV | 5 | Setpoint_Offset_Range | Allowed setpoint offset range (+/-) | °C | Write | |
| AV | 6 | Net_Temperature | Room temperature written from the network (control value source) | °C | Write | |
| AV | 10 | Heating_Cooling_Switch_Diff | Heating/cooling changeover differential | °C | Write | |
| AV | 11 | Unoccupied_Offset | Setpoint offset in unoccupied mode | °C | Write | |
| AV | 12 | Standby_Offset | Setpoint offset in standby mode | °C | Write | |
| AV | 13 | Occupancy_Time_Remote_Trigger | Forced occupied time for I1 button / room panel | min | Write | |
| AV | 14 | Occupancy_Time_Presence_Sensor | Forced occupied time for I2 presence sensor | min | Write | |
| AV | 15 | PWM_Heating_Period | Heating valve PWM period | s | Write | |
| AV | 16 | PWM_Cooling_Period | Cooling valve PWM period | s | Write | |
| AV | 17 | Fan_Scale | Fan control scale (temperature error for 100 %) | °C | Write | |
| AV | 18 | Fan_Off_Threshold | Fan off threshold | % | Write | |
| AV | 19 | Fan_Speed_1_Threshold | Fan speed 1 threshold | % | Write | |
| AV | 20 | Fan_Speed_2_Threshold | Fan speed 2 threshold | % | Write | |
| AV | 21 | Fan_Speed_3_Threshold | Fan speed 3 threshold | % | Write | |
| AV | 22 | Fan_Off_Delay | Fan switch-off delay | s | Write | |
| AV | 23 | Fan_Soft_Start_Time | Fan soft start time | s | Write | |
| AV | 24 | Kp | PI proportional gain | Write | ||
| AV | 25 | Ti | PI integral time | min | Write | |
| AV | 26 | Heating_Binary_Diff | 1st stage heating thermostat differential | °C | Write | |
| AV | 27 | Cooling_Binary_Diff | 1st stage cooling thermostat differential | °C | Write | |
| AV | 28 | Second_Stage_Threshold_Binary | 2nd stage shift, digital control mode | °C | Write | |
| AV | 29 | Second_Stage_Diff_Binary | 2nd stage differential, digital control mode | °C | Write | |
| AV | 30 | Second_Stage_Threshold_Analog | 2nd stage shift, analog control mode | % | Write | |
| AV | 31 | Second_Stage_Diff_Analog | 2nd stage differential, analog control mode | % | Write | |
| AV | 32 | Supply_Temperature_Low_Limit | Supply air low limit | °C | Write | |
| AV | 33 | Supply_Temperature_High_Limit | Supply air high limit | °C | Write | |
| AV | 34 | Supply_Limits_Time | Supply air limit function time | s | Write | |
| AV | 35 | Window_Status_Delay | Open window function delay | s | Write | |
| AV | 36 | Return_To_Space_Time | Return-to-space sensor function time | s | Write | |
| AV | 37 | FCU_Test_Mode | Test mode | Write | 0=Auto operation, 1=Heating test, 2=Cooling test | |
| AV | 38 | Fan_Soft_Start_Value | Analog fan start value | % | Write | |
| AV | 39 | Valves_Dead_Band | Valve temperature dead band | °C | Write | |
| AV | 40 | Return_Temperature_Offset | Return sensor correction | °C | Write | |
| AV | 41 | Supply_Temperature_Offset | Supply sensor correction | °C | Write | |
| AV | 42 | Space_Temperature_Offset | Space sensor correction | °C | Write | |
| AV | 43 | S1_Sensor_Type | S1 input sensor type | Write | 0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC | |
| AV | 44 | S2_Sensor_Type | S2 input sensor type | Write | 0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC | |
| AV | 45 | S3_Sensor_Type | S3 input sensor type | Write | 0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC | |
| AV | 46 | Heating_Valve_Manual_Value | Heating valve manual override value | % | Write | |
| AV | 47 | Cooling_Valve_Manual_Value | Cooling valve manual override value | % | Write | |
| AV | 48 | Fan_Valve_Manual_Value | Fan output manual override value | % | Write | |
| AV | 50 | LCD_Panel_Temperature_Offset | Room panel temperature correction | °C | Write | |
| AV | 51 | LCD_Setpoint_Step | Room panel setpoint step | °C | Write | |
| AV | 52 | LCD_Setpoint_Low_Limit | Room panel setpoint low limit | °C | Write | |
| AV | 53 | LCD Setpoint High Limit | Room panel setpoint high limit | °C | Write | |
| AV | 54 | Remote_Slave1_Device_ID | Slave 1 BACnet device ID | Write | ||
| AV | 56 | Remote_Slave2_Device_ID | Slave 2 BACnet device ID | Write | ||
| AV | 58 | Remote_Slave3_Device_ID | Slave 3 BACnet device ID | Write | ||
| AV | 60 | Remote_Slave4_Device_ID | Slave 4 BACnet device ID | Write | ||
| AV | 62 | Remote_Slave5_Device_ID | Slave 5 BACnet device ID | Write | ||
| AV | 64 | Slaves_Ping_Frequency | Slave ping interval | min | Write | |
| AVmin | 100 | Effective Setpoint | Effective setpoint in use | °C | Read | |
| AVmin | 101 | Occupancy Status | Occupancy status | Read | 0=Unoccupied, 1=Occupied, 2=Standby, 3=Forced occupied | |
| AVmin | 102 | Fan Status | Fan status | Read | 0=Off, 1=Speed 1 (manual), 2=Speed 2 (manual), 3=Speed 3 (manual), 4=Speed 1 (auto), 5=Speed 2 (auto), 6=Speed 3 (auto) | |
| AV | 103 | Fan Type | Fan type | Read | 0=Analog, 1=Speed 1, 2=Speed 2, 3=Speed 3 | |
| AVmin | 104 | Cv | Temperature control value | °C | Read | |
| AV | 105 | Dip_Switch_Configuration | CFG DIP switch status bits | Read | ||
| AV | 106 | App_version | Application version | Read | ||
| AVmin | 110 | Heating_Valve | Heating valve output (analog or triac PWM) | % | Read | |
| AVmin | 111 | Coolling_Valve | Cooling valve output (analog or triac PWM) | % | Read | |
| AV | 112 | Fan Value | Fan output (analog % or speed step) | % | Read | |
| AV | 113 | S1_Return_Temperature | S1 return temperature | °C | Read | |
| AV | 114 | S2_Supply_Temperature | S2 supply temperature | °C | Read | |
| AV | 115 | S3_Space_Temperature | S3 space temperature | °C | Read | |
| AV | 120 | LCD Panel Temperature | Room panel temperature | °C | Read | |
| AV | 121 | LCD Panel Humidity | Room panel humidity | % | Read | |
| AV | 122 | LCD Panel CO2 | Room panel CO2 | ppm | Read | |
| BV | 0 | Offset In Occupied Only | Apply setpoint offset only when occupied | Write | 0=False, 1=True | |
| BV | 1 | Fan Heating Occupied Active | Fan low speed with no demand, heating occupied | Write | 0=False, 1=True | |
| BV | 2 | Fan Cooling Occupied Active | Fan low speed with no demand, cooling occupied | Write | 0=False, 1=True | |
| BV | 3 | Return_To_Space_Enable | Return-to-space sensor function enable | Write | 0=False, 1=True | |
| BV | 4 | HTG Relay Enable | Enable O4 heating relay | Write | 0=False, 1=True | |
| BV | 5 | CLG Relay Enable | Enable O5 cooling relay | Write | 0=False, 1=True | |
| BV | 6 | I1_Remote_Occ_Trigger_Invert | Invert I1 occupancy trigger input | Write | 0=False, 1=True | |
| BV | 7 | I2_Presence_Sensor_Invert | Invert I2 presence input | Write | 0=False, 1=True | |
| BV | 8 | I3_Window_Contact_Invert | Invert I3 window contact input | Write | 0=False, 1=True | |
| BV | 9 | Local_Remote_Auto_Binding | Slave ID source (auto binding or network) | Write | 0=False, 1=True | |
| BV | 10 | Heating_Valve_Manual_Enable | Heating valve manual override enable | Write | 0=False, 1=True | |
| BV | 11 | Cooling_Valve_Manual_Enable | Cooling valve manual override enable | Write | 0=False, 1=True | |
| BV | 12 | HTG_Relay_Manual_Enable | Heating relay manual override enable | Write | 0=False, 1=True | |
| BV | 13 | CLG_Relay_Manual_Enable | Cooling relay manual override enable | Write | 0=False, 1=True | |
| BV | 14 | Fan_Output_Manual_Enable | Fan output manual override enable | Write | 0=False, 1=True | |
| BV | 15 | LCD Submenu Icons Hidden | Hide room panel submenu icons | Write | 0=False, 1=True | |
| BV | 16 | LCD Temperature Active | Room panel option: temperature active | Write | 0=False, 1=True | |
| BV | 17 | LCD Setpoint Active | Room panel option: setpoint active | Write | 0=False, 1=True | |
| BV | 18 | LCD Setpoint Editable | Room panel option: setpoint editable | Write | 0=False, 1=True | |
| BV | 19 | LCD Setpoint Fast Edit Mode | Room panel option: setpoint fast edit mode | Write | 0=False, 1=True | |
| BV | 20 | LCD Fan Visable | Room panel option: fan visible | Write | 0=False, 1=True | |
| BV | 21 | LCD Fan Editable | Room panel option: fan editable | Write | 0=False, 1=True | |
| BV | 22 | LCD Fan Fast Edit Mode | Room panel option: fan fast edit mode | Write | 0=False, 1=True | |
| BV | 23 | LCD Occupancy Visable | Room panel option: occupancy visible | Write | 0=False, 1=True | |
| BV | 24 | LCD Occupancy Editable | Room panel option: occupancy editable | Write | 0=False, 1=True | |
| BV | 25 | LCD Occupancy Fast Edit Mode | Room panel option: occupancy fast edit mode | Write | 0=False, 1=True | |
| BV | 26 | LCD Humidity Active | Room panel option: humidity active | Write | 0=False, 1=True | |
| BV | 27 | LCD CO2 Active | Room panel option: co2 active | Write | 0=False, 1=True | |
| BV | 28 | HTG_Relay_Manual_State | Heating relay state in manual override | Write | 0=False, 1=True | |
| BV | 29 | CLG_Relay_Manual_State | Cooling relay state in manual override | Write | 0=False, 1=True | |
| BV | 64 | Occupied Forced | Forced occupied mode active | Read | 0=False, 1=True | |
| BV | 80 | Heating_Second_Stage | Heating 2nd stage active | Read | 0=False, 1=True | |
| BV | 81 | Cooling_Second_Stage | Cooling 2nd stage active | Read | 0=False, 1=True | |
| BV | 82 | I1_Remote_Occuapancy_Trigger | I1 occupancy trigger input state | Read | 0=False, 1=True | |
| BV | 83 | I2_Presence_Sensor_Card_Holder | I2 presence / card holder input state | Read | 0=False, 1=True | |
| BV | 84 | I3_Window_Conntact | I3 window contact input state | Read | 0=False, 1=True | |
| BV | 85 | I4_Occupancy_LED | I4 occupancy LED state | Read | 0=False, 1=True | |
| BV | 96 | Slave1_Active | Slave 1 connected | Read | 0=False, 1=True | |
| BV | 97 | Slave2_Active | Slave 2 connected | Read | 0=False, 1=True | |
| BV | 98 | Slave3_Active | Slave 3 connected | Read | 0=False, 1=True | |
| BV | 99 | Slave4_Active | Slave 4 connected | Read | 0=False, 1=True | |
| BV | 100 | Slave5_Active | Slave 5 connected | Read | 0=False, 1=True | |
| BV | 101 | Slave1_Window_Status | Slave 1 window input (I3) state | Read | 0=False, 1=True | |
| BV | 102 | Slave2_Window_Status | Slave 2 window input (I3) state | Read | 0=False, 1=True | |
| BV | 103 | Slave3_Window_Status | Slave 3 window input (I3) state | Read | 0=False, 1=True | |
| BV | 104 | Slave4_Window_Status | Slave 4 window input (I3) state | Read | 0=False, 1=True | |
| BV | 105 | Slave5_Window_Status | Slave 5 window input (I3) state | Read | 0=False, 1=True |
No points match these filters.
Object ID lookup: iSMA CONTROLLI iSMA-B-FCU fan coil controller point IDs by name
AV0Occupancy_ModeAV1SetpointAV2Setpoint_OffsetAV3Fan_ModeAV4FCU_ModeAV5Setpoint_Offset_RangeAV6Net_TemperatureAV10Heating_Cooling_Switch_DiffAV11Unoccupied_OffsetAV12Standby_OffsetAV13Occupancy_Time_Remote_TriggerAV14Occupancy_Time_Presence_SensorAV15PWM_Heating_PeriodAV16PWM_Cooling_PeriodAV17Fan_ScaleAV18Fan_Off_ThresholdAV19Fan_Speed_1_ThresholdAV20Fan_Speed_2_ThresholdAV21Fan_Speed_3_ThresholdAV22Fan_Off_DelayAV23Fan_Soft_Start_TimeAV24KpAV25TiAV26Heating_Binary_DiffAV27Cooling_Binary_DiffAV28Second_Stage_Threshold_BinaryAV29Second_Stage_Diff_BinaryAV30Second_Stage_Threshold_AnalogAV31Second_Stage_Diff_AnalogAV32Supply_Temperature_Low_LimitAV33Supply_Temperature_High_LimitAV34Supply_Limits_TimeAV35Window_Status_DelayAV36Return_To_Space_TimeAV37FCU_Test_ModeAV38Fan_Soft_Start_ValueAV39Valves_Dead_BandAV40Return_Temperature_OffsetAV41Supply_Temperature_OffsetAV42Space_Temperature_OffsetAV43S1_Sensor_TypeAV44S2_Sensor_TypeAV45S3_Sensor_TypeAV46Heating_Valve_Manual_ValueAV47Cooling_Valve_Manual_ValueAV48Fan_Valve_Manual_ValueAV50LCD_Panel_Temperature_OffsetAV51LCD_Setpoint_StepAV52LCD_Setpoint_Low_LimitAV53LCD Setpoint High LimitAV54Remote_Slave1_Device_IDAV56Remote_Slave2_Device_IDAV58Remote_Slave3_Device_IDAV60Remote_Slave4_Device_IDAV62Remote_Slave5_Device_IDAV64Slaves_Ping_FrequencyAV100Effective SetpointAV101Occupancy StatusAV102Fan StatusAV103Fan TypeAV104CvAV105Dip_Switch_ConfigurationAV106App_versionAV110Heating_ValveAV111Coolling_ValveAV112Fan ValueAV113S1_Return_TemperatureAV114S2_Supply_TemperatureAV115S3_Space_TemperatureAV120LCD Panel TemperatureAV121LCD Panel HumidityAV122LCD Panel CO2BV0Offset In Occupied OnlyBV1Fan Heating Occupied ActiveBV2Fan Cooling Occupied ActiveBV3Return_To_Space_EnableBV4HTG Relay EnableBV5CLG Relay EnableBV6I1_Remote_Occ_Trigger_InvertBV7I2_Presence_Sensor_InvertBV8I3_Window_Contact_InvertBV9Local_Remote_Auto_BindingBV10Heating_Valve_Manual_EnableBV11Cooling_Valve_Manual_EnableBV12HTG_Relay_Manual_EnableBV13CLG_Relay_Manual_EnableBV14Fan_Output_Manual_EnableBV15LCD Submenu Icons HiddenBV16LCD Temperature ActiveBV17LCD Setpoint ActiveBV18LCD Setpoint EditableBV19LCD Setpoint Fast Edit ModeBV20LCD Fan VisableBV21LCD Fan EditableBV22LCD Fan Fast Edit ModeBV23LCD Occupancy VisableBV24LCD Occupancy EditableBV25LCD Occupancy Fast Edit ModeBV26LCD Humidity ActiveBV27LCD CO2 ActiveBV28HTG_Relay_Manual_StateBV29CLG_Relay_Manual_StateBV64Occupied ForcedBV80Heating_Second_StageBV81Cooling_Second_StageBV82I1_Remote_Occuapancy_TriggerBV83I2_Presence_Sensor_Card_HolderBV84I3_Window_ConntactBV85I4_Occupancy_LEDBV96Slave1_ActiveBV97Slave2_ActiveBV98Slave3_ActiveBV99Slave4_ActiveBV100Slave5_ActiveBV101Slave1_Window_StatusBV102Slave2_Window_StatusBV103Slave3_Window_StatusBV104Slave4_Window_StatusBV105Slave5_Window_Status
Integration notes
- The manual lists App_status (application diagnostics) as BACnet Device object property 5002, not as an object; it is left out here.
- Default values in the table look scaled x10 (Setpoint 210 for 21.0 °C; Fan_Scale default 30 while the text says 3 °C). Check whether the live BACnet values are scaled before writing.
- AV 29 is printed wrapped as 'Second_Stage_Diff / Binary'; it is listed as Second_Stage_Diff_Binary to match AV 31 Second_Stage_Diff_Analog.
- Names are kept as printed, including spelling slips (Coolling_Valve, Visable, Occuapancy, Conntact) and the few names printed with spaces.
- The MAC address is set with DIP switches; master/slave grouping works only over BACnet.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iSMA-B-FCU fan coil controller (default application) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)
How many BACnet points does the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) have?
This list has 119 BACnet objects: 72 analog values, 47 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet points are writable?
86 of the 119 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet documentation?
iSMA CONTROLLI does not publish it on its own website. This list comes from iSMA-B-FCU Application User Manual (DMP241en), revision 1st Issue rev. 5, 02/2022, a copy hosted by Innon (iSMA distributor) at https://downloads.innon.com/hubfs/downloads.innon.com/iSMA/iSMA-B-FCU/Manuals/iSMA_B_FCU_Application_Manual.pdf. Ask iSMA CONTROLLI or its representative for the current revision.
What are the minimum BACnet points to integrate the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)?
Start with AV 0 Occupancy_Mode (0 unoccupied, 1 occupied, 2 standby); AV 4 FCU_Mode (0 off, 1 auto, 2 heat, 3 cool, 4 fan only); AV 3 Fan_Mode (0 off, 1-3 manual speed, 4 auto); AV 1 Setpoint (Room temperature setpoint); AV 100 Effective Setpoint (Setpoint in use after offsets); AV 101 Occupancy Status (0 unocc, 1 occ, 2 standby, 3 forced occupied); AV 102 Fan Status (0 off, 1-3 manual speed, 4-6 auto speed); AV 104 Cv (Room temperature used for control); AV 110 Heating_Valve (Heating valve output, %); AV 111 Coolling_Valve (Cooling valve output, %).
Can the BMS supply sensor values to the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)?
Net_Temperature (AV 6) takes a room temperature from the network as the control value source.
How do I check these points on the real iSMA-B-FCU fan coil controller (default application)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: iSMA-B-FCU Application User Manual · DMP241en · rev. 1st Issue rev. 5, 02/2022. Object names, instances and units are reproduced as published; descriptions are our own.