Easy BACnet
  1. Home
  2. BACnet points lists
  3. iSMA CONTROLLI
  4. iSMA-B-FCU fan coil controller (default application)

Fan coil unit controller · BACnet points list

iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The iSMA-B-FCU ships with a ready-made fan coil application (2- or 4-pipe, digital or analog valve control, 3-speed or analog fan) that exposes a fixed set of BACnet Analog Value and Binary Value objects, the same data as its Modbus registers. The BMS can set occupancy mode, setpoint, fan mode and FCU mode, write the room temperature, and read the effective setpoint, valve and fan outputs and sensor values. Up to five slave FCUs can follow one master over BACnet.

This page lists 119 BACnet objects for the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) — 86 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of iSMA CONTROLLI’s documentation hosted by Innon (iSMA distributor), not by iSMA CONTROLLI itself, so treat it as unofficial.

Manufacturer
iSMA CONTROLLI
Model
iSMA-B-FCU fan coil controller (default application)
Equipment
Fan coil unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
119 (86 writable)
Transport
BACnet MS/TP
Firmware
Default application 2.0 (App_version default)
Default device instance
826 followed by the 3-digit MAC address (MAC 83 = 826083)
Also known as
iSMA-B-FCU, iSMA-B-FCU-HH, iSMA-B-FCU-HL, iSMA-B-FCU-LL, DMP241en
Source document
iSMA-B-FCU Application User Manual · DMP241en · rev. 1st Issue rev. 5, 02/2022 (unofficial copy, hosted by Innon (iSMA distributor))
Download CSV 119 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.

BMS integration notes: iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)

Integration in brief

Use the default application as shipped: write Occupancy_Mode, Setpoint, Fan_Mode and FCU_Mode from the BMS, and read Effective Setpoint, Occupancy Status, Fan Status and the valve outputs. If the room temperature comes from the BMS, write it to Net_Temperature. Only the master FCU of a group should be controlled from the BMS; slaves follow it.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0Occupancy_Mode0 unoccupied, 1 occupied, 2 standbyWrite
AV 4FCU_Mode0 off, 1 auto, 2 heat, 3 cool, 4 fan onlyWrite
AV 3Fan_Mode0 off, 1-3 manual speed, 4 autoWrite
AV 1SetpointRoom temperature setpointWrite
AV 100Effective SetpointSetpoint in use after offsetsRead
AV 101Occupancy Status0 unocc, 1 occ, 2 standby, 3 forced occupiedRead
AV 102Fan Status0 off, 1-3 manual speed, 4-6 auto speedRead
AV 104CvRoom temperature used for controlRead
AV 110Heating_ValveHeating valve output, %Read
AV 111Coolling_ValveCooling valve output, %Read

Sensors & values from the BMS

Net_Temperature (AV 6) takes a room temperature from the network as the control value source.

Network setup

Watch out for

iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

119 of 119 shown
Type
AnalogBinary
Access
Show
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet Points List
DescriptionStates
AVmin0Occupancy_ModeOccupancy mode commandWrite0=Unoccupied, 1=Occupied, 2=Standby
AVmin1SetpointUser temperature setpoint°CWrite
AV2Setpoint_OffsetUser setpoint offset°CWrite
AVmin3Fan_ModeFan mode commandWrite0=Off, 1=Speed 1 (manual), 2=Speed 2 (manual), 3=Speed 3 (manual), 4=Auto
AVmin4FCU_ModeFan coil operating modeWrite0=Off, 1=Auto, 2=Heating only, 3=Cooling only, 4=Fan only
AV5Setpoint_Offset_RangeAllowed setpoint offset range (+/-)°CWrite
AV6Net_TemperatureRoom temperature written from the network (control value source)°CWrite
AV10Heating_Cooling_Switch_DiffHeating/cooling changeover differential°CWrite
AV11Unoccupied_OffsetSetpoint offset in unoccupied mode°CWrite
AV12Standby_OffsetSetpoint offset in standby mode°CWrite
AV13Occupancy_Time_Remote_TriggerForced occupied time for I1 button / room panelminWrite
AV14Occupancy_Time_Presence_SensorForced occupied time for I2 presence sensorminWrite
AV15PWM_Heating_PeriodHeating valve PWM periodsWrite
AV16PWM_Cooling_PeriodCooling valve PWM periodsWrite
AV17Fan_ScaleFan control scale (temperature error for 100 %)°CWrite
AV18Fan_Off_ThresholdFan off threshold%Write
AV19Fan_Speed_1_ThresholdFan speed 1 threshold%Write
AV20Fan_Speed_2_ThresholdFan speed 2 threshold%Write
AV21Fan_Speed_3_ThresholdFan speed 3 threshold%Write
AV22Fan_Off_DelayFan switch-off delaysWrite
AV23Fan_Soft_Start_TimeFan soft start timesWrite
AV24KpPI proportional gainWrite
AV25TiPI integral timeminWrite
AV26Heating_Binary_Diff1st stage heating thermostat differential°CWrite
AV27Cooling_Binary_Diff1st stage cooling thermostat differential°CWrite
AV28Second_Stage_Threshold_Binary2nd stage shift, digital control mode°CWrite
AV29Second_Stage_Diff_Binary2nd stage differential, digital control mode°CWrite
AV30Second_Stage_Threshold_Analog2nd stage shift, analog control mode%Write
AV31Second_Stage_Diff_Analog2nd stage differential, analog control mode%Write
AV32Supply_Temperature_Low_LimitSupply air low limit°CWrite
AV33Supply_Temperature_High_LimitSupply air high limit°CWrite
AV34Supply_Limits_TimeSupply air limit function timesWrite
AV35Window_Status_DelayOpen window function delaysWrite
AV36Return_To_Space_TimeReturn-to-space sensor function timesWrite
AV37FCU_Test_ModeTest modeWrite0=Auto operation, 1=Heating test, 2=Cooling test
AV38Fan_Soft_Start_ValueAnalog fan start value%Write
AV39Valves_Dead_BandValve temperature dead band°CWrite
AV40Return_Temperature_OffsetReturn sensor correction°CWrite
AV41Supply_Temperature_OffsetSupply sensor correction°CWrite
AV42Space_Temperature_OffsetSpace sensor correction°CWrite
AV43S1_Sensor_TypeS1 input sensor typeWrite0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC
AV44S2_Sensor_TypeS2 input sensor typeWrite0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC
AV45S3_Sensor_TypeS3 input sensor typeWrite0=Voltage, 1=10K3A1 NTC, 2=10K4A1 NTC, 3=10K NTC, 4=20K6A1 NTC, 5=2.2K3A1 NTC, 6=3K3A1 NTC, 7=30K6A1 NTC, 8=SIE1 NTC, 9=TAC1 NTC, 10=SAT1 NTC
AV46Heating_Valve_Manual_ValueHeating valve manual override value%Write
AV47Cooling_Valve_Manual_ValueCooling valve manual override value%Write
AV48Fan_Valve_Manual_ValueFan output manual override value%Write
AV50LCD_Panel_Temperature_OffsetRoom panel temperature correction°CWrite
AV51LCD_Setpoint_StepRoom panel setpoint step°CWrite
AV52LCD_Setpoint_Low_LimitRoom panel setpoint low limit°CWrite
AV53LCD Setpoint High LimitRoom panel setpoint high limit°CWrite
AV54Remote_Slave1_Device_IDSlave 1 BACnet device IDWrite
AV56Remote_Slave2_Device_IDSlave 2 BACnet device IDWrite
AV58Remote_Slave3_Device_IDSlave 3 BACnet device IDWrite
AV60Remote_Slave4_Device_IDSlave 4 BACnet device IDWrite
AV62Remote_Slave5_Device_IDSlave 5 BACnet device IDWrite
AV64Slaves_Ping_FrequencySlave ping intervalminWrite
AVmin100Effective SetpointEffective setpoint in use°CRead
AVmin101Occupancy StatusOccupancy statusRead0=Unoccupied, 1=Occupied, 2=Standby, 3=Forced occupied
AVmin102Fan StatusFan statusRead0=Off, 1=Speed 1 (manual), 2=Speed 2 (manual), 3=Speed 3 (manual), 4=Speed 1 (auto), 5=Speed 2 (auto), 6=Speed 3 (auto)
AV103Fan TypeFan typeRead0=Analog, 1=Speed 1, 2=Speed 2, 3=Speed 3
AVmin104CvTemperature control value°CRead
AV105Dip_Switch_ConfigurationCFG DIP switch status bitsRead
AV106App_versionApplication versionRead
AVmin110Heating_ValveHeating valve output (analog or triac PWM)%Read
AVmin111Coolling_ValveCooling valve output (analog or triac PWM)%Read
AV112Fan ValueFan output (analog % or speed step)%Read
AV113S1_Return_TemperatureS1 return temperature°CRead
AV114S2_Supply_TemperatureS2 supply temperature°CRead
AV115S3_Space_TemperatureS3 space temperature°CRead
AV120LCD Panel TemperatureRoom panel temperature°CRead
AV121LCD Panel HumidityRoom panel humidity%Read
AV122LCD Panel CO2Room panel CO2ppmRead
BV0Offset In Occupied OnlyApply setpoint offset only when occupiedWrite0=False, 1=True
BV1Fan Heating Occupied ActiveFan low speed with no demand, heating occupiedWrite0=False, 1=True
BV2Fan Cooling Occupied ActiveFan low speed with no demand, cooling occupiedWrite0=False, 1=True
BV3Return_To_Space_EnableReturn-to-space sensor function enableWrite0=False, 1=True
BV4HTG Relay EnableEnable O4 heating relayWrite0=False, 1=True
BV5CLG Relay EnableEnable O5 cooling relayWrite0=False, 1=True
BV6I1_Remote_Occ_Trigger_InvertInvert I1 occupancy trigger inputWrite0=False, 1=True
BV7I2_Presence_Sensor_InvertInvert I2 presence inputWrite0=False, 1=True
BV8I3_Window_Contact_InvertInvert I3 window contact inputWrite0=False, 1=True
BV9Local_Remote_Auto_BindingSlave ID source (auto binding or network)Write0=False, 1=True
BV10Heating_Valve_Manual_EnableHeating valve manual override enableWrite0=False, 1=True
BV11Cooling_Valve_Manual_EnableCooling valve manual override enableWrite0=False, 1=True
BV12HTG_Relay_Manual_EnableHeating relay manual override enableWrite0=False, 1=True
BV13CLG_Relay_Manual_EnableCooling relay manual override enableWrite0=False, 1=True
BV14Fan_Output_Manual_EnableFan output manual override enableWrite0=False, 1=True
BV15LCD Submenu Icons HiddenHide room panel submenu iconsWrite0=False, 1=True
BV16LCD Temperature ActiveRoom panel option: temperature activeWrite0=False, 1=True
BV17LCD Setpoint ActiveRoom panel option: setpoint activeWrite0=False, 1=True
BV18LCD Setpoint EditableRoom panel option: setpoint editableWrite0=False, 1=True
BV19LCD Setpoint Fast Edit ModeRoom panel option: setpoint fast edit modeWrite0=False, 1=True
BV20LCD Fan VisableRoom panel option: fan visibleWrite0=False, 1=True
BV21LCD Fan EditableRoom panel option: fan editableWrite0=False, 1=True
BV22LCD Fan Fast Edit ModeRoom panel option: fan fast edit modeWrite0=False, 1=True
BV23LCD Occupancy VisableRoom panel option: occupancy visibleWrite0=False, 1=True
BV24LCD Occupancy EditableRoom panel option: occupancy editableWrite0=False, 1=True
BV25LCD Occupancy Fast Edit ModeRoom panel option: occupancy fast edit modeWrite0=False, 1=True
BV26LCD Humidity ActiveRoom panel option: humidity activeWrite0=False, 1=True
BV27LCD CO2 ActiveRoom panel option: co2 activeWrite0=False, 1=True
BV28HTG_Relay_Manual_StateHeating relay state in manual overrideWrite0=False, 1=True
BV29CLG_Relay_Manual_StateCooling relay state in manual overrideWrite0=False, 1=True
BV64Occupied ForcedForced occupied mode activeRead0=False, 1=True
BV80Heating_Second_StageHeating 2nd stage activeRead0=False, 1=True
BV81Cooling_Second_StageCooling 2nd stage activeRead0=False, 1=True
BV82I1_Remote_Occuapancy_TriggerI1 occupancy trigger input stateRead0=False, 1=True
BV83I2_Presence_Sensor_Card_HolderI2 presence / card holder input stateRead0=False, 1=True
BV84I3_Window_ConntactI3 window contact input stateRead0=False, 1=True
BV85I4_Occupancy_LEDI4 occupancy LED stateRead0=False, 1=True
BV96Slave1_ActiveSlave 1 connectedRead0=False, 1=True
BV97Slave2_ActiveSlave 2 connectedRead0=False, 1=True
BV98Slave3_ActiveSlave 3 connectedRead0=False, 1=True
BV99Slave4_ActiveSlave 4 connectedRead0=False, 1=True
BV100Slave5_ActiveSlave 5 connectedRead0=False, 1=True
BV101Slave1_Window_StatusSlave 1 window input (I3) stateRead0=False, 1=True
BV102Slave2_Window_StatusSlave 2 window input (I3) stateRead0=False, 1=True
BV103Slave3_Window_StatusSlave 3 window input (I3) stateRead0=False, 1=True
BV104Slave4_Window_StatusSlave 4 window input (I3) stateRead0=False, 1=True
BV105Slave5_Window_StatusSlave 5 window input (I3) stateRead0=False, 1=True
Object ID lookup: iSMA CONTROLLI iSMA-B-FCU fan coil controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the iSMA-B-FCU fan coil controller (default application) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)

How many BACnet points does the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) have?

This list has 119 BACnet objects: 72 analog values, 47 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet points are writable?

86 of the 119 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application) BACnet documentation?

iSMA CONTROLLI does not publish it on its own website. This list comes from iSMA-B-FCU Application User Manual (DMP241en), revision 1st Issue rev. 5, 02/2022, a copy hosted by Innon (iSMA distributor) at https://downloads.innon.com/hubfs/downloads.innon.com/iSMA/iSMA-B-FCU/Manuals/iSMA_B_FCU_Application_Manual.pdf. Ask iSMA CONTROLLI or its representative for the current revision.

What are the minimum BACnet points to integrate the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)?

Start with AV 0 Occupancy_Mode (0 unoccupied, 1 occupied, 2 standby); AV 4 FCU_Mode (0 off, 1 auto, 2 heat, 3 cool, 4 fan only); AV 3 Fan_Mode (0 off, 1-3 manual speed, 4 auto); AV 1 Setpoint (Room temperature setpoint); AV 100 Effective Setpoint (Setpoint in use after offsets); AV 101 Occupancy Status (0 unocc, 1 occ, 2 standby, 3 forced occupied); AV 102 Fan Status (0 off, 1-3 manual speed, 4-6 auto speed); AV 104 Cv (Room temperature used for control); AV 110 Heating_Valve (Heating valve output, %); AV 111 Coolling_Valve (Cooling valve output, %).

Can the BMS supply sensor values to the iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)?

Net_Temperature (AV 6) takes a room temperature from the network as the control value source.

How do I check these points on the real iSMA-B-FCU fan coil controller (default application)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: iSMA-B-FCU Application User Manual · DMP241en · rev. 1st Issue rev. 5, 02/2022. Object names, instances and units are reproduced as published; descriptions are our own.