Room panel (thermostat display) · BACnet points list
iSMA CONTROLLI Touch Point 2.0 room panel BACnet points list
Updated 12 November 2026
The Touch Point 2.0 room panel has the same room objects as the first Touch Point (temperature, humidity, CO2, setpoint with offset, fan, occupancy, CO2 alarm) and adds seven generic buttons with their own mode, state and LED objects, a screen-select mode, buzzer tone and a USB on/off switch.
This page lists 59 BACnet objects for the iSMA CONTROLLI Touch Point 2.0 room panel — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.
- Manufacturer
- iSMA CONTROLLI
- Model
- Touch Point 2.0 room panel
- Equipment
- Room panel (thermostat display)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 59 (50 writable)
- Transport
- BACnet MS/TP
- Firmware
- Touch Point 2.0 Software manual V1.0.1
- Also known as
- Touch Point 2.0, Touch Point ONE 2.0, iSMA Touch Point 2.0, TP2.0
Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.
BMS integration notes: iSMA CONTROLLI Touch Point 2.0 room panel
Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode; BI 0 is the CO2 alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | OCCUPANCY_MODE | Occupancy mode | Write |
| AV 56 | SETPOINT_VALUE | Temperature setpoint | Write |
| MV 1 | FAN_MODE | Fan mode | Write |
| AI 4 | TEMPERATURE_SENSOR | Room temperature | Read |
| AI 3 | EFFECTIVE_SETPOINT | Effective setpoint (setpoint plus offset) | Read |
| MV 3 | OCCUPANCY_CURRENT_STATUS | Current occupancy status | Write |
| AI 5 | HUMIDITY_SENSOR | Room humidity | Read |
| AI 6 | CO2_SENSOR | Room CO2 | Read |
| BI 0 | ALARM_STATUS | CO2 alarm status | Read |
Enable & remote start
BO 62 OCCUPANCY_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.
Network setup
- Device instance and baud rate are Device-object properties (BACNET_DEVICE_ID default 0xFFFFFFFF, BAUD_RATE default 11520 = 115200 bps).
Watch out for
- Setpoint objects use tenths in the defaults (DEFAULT_SETPOINT 210 = 21.0 °C); check scaling before writing.
- Configuration objects are stored in panel memory; avoid cyclic writes.
iSMA CONTROLLI Touch Point 2.0 room panel BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | LIVE_TIME | Uptime of the panel in seconds | s | Read | |
| MI | 1 | SENSORS | Informs about built-in sensors | Read | ||
| AI | 1 | BACKLIGHT_LCD | Actual display illumination value | Read | ||
| AI | 2 | BACKLIGHT_KEYPAD | Actual keypad illumination value | Read | ||
| MV | 19 | SCREEN_SELECT_MODE | Screen mode in the Touch Point ONE 2.0 panel | Write | ||
| MV | 21 | GEN_BTN_1_MODE | Sets a mode of operation (7 objects, MV 21-27) | Write | ||
| BV | 56 | GEN_BTN_1_STATE | 1-7 generic buttons state (on/off) (7 objects, BV 56-62) | Write | ||
| BV | 63 | GEN_BTN_1_LED_LOCAL_MODE | (7 objects, BV 63-69) | Write | ||
| BV | 70 | GEN_BTN_1_LED_BMS_STATE | (7 objects, BV 70-76) | Write | ||
| BO | 0 | BUZZER_ACTIVE | Activates (1) or deactivates (0) a buzzer; default 1 | Write | ||
| BO | 3 | LCD_BACKLIGHT_ACTIVE | Switches the LCD background illumination on (1); default 1 | Write | ||
| BO | 4 | KEYPAD_BACKLIGHT_ACTIVE | Switches the keypad background illumination on (1); default 1 | Write | ||
| BO | 5 | CO2_ALARM_LCD | Switches on the function of LCD background illumination flashing when CO2 alarm | Write | ||
| BO | 6 | CO2_ALARM_BUZZER | Switches on a buzzer when the CO2 alarm occurs | Write | ||
| BO | 63 | CO2_ALARM_CONFIRM | Enable confirmation of the CO2 alarm with any button of the panel | Write | ||
| BO | 11 | PANEL_OFF | Switches the panel off (1); default 0 | Write | ||
| BO | 12 | KEYPAD_OFF | Switches the panel keypad off (1); default 0 | Write | ||
| AO | 3 | BACKLIGHT_LCD_ACTIVE | Contains a value of the LCD display illumination in the active mode | Write | ||
| AO | 4 | BACKLIGHT_LCD_IDLE | Contains a value of the LCD display illumination in the idle mode | Write | ||
| AO | 5 | BACKLIGHT_LCD_STANDBY | Contains a value of the LCD display illumination in the standby mode | Write | ||
| AO | 6 | BACKLIGHT_LCD_TIME_TO_IDLE | Sets the time after which the LCD display goes from the active | Write | ||
| AO | 7 | BACKLIGHT_LCD_TIME_TO_STANDBY | Sets the time after which the LCD display goes from the idle | Write | ||
| AO | 8 | BACKLIGHT_KEYPAD_ACTIVE | Contains a value of the keypad illumination in the active mode; default 10 | Write | ||
| AO | 9 | BACKLIGHT_KEYPAD_IDLE | Contains a value of the keypad illumination in the idle mode; default 40 | Write | ||
| AO | 10 | BACKLIGHT_KEYPAD_STANDBY | Contains a value of the keypad illumination in the standby mode; default 60 | Write | ||
| AO | 11 | BACKLIGHT_KEYPAD_TIME_TO_IDLE | Sets the time after which the keypad goes from the active mode | Write | ||
| AO | 12 | BACKLIGHT_KEYPAD_TIME_TO_STANDBY | Sets the time after which the keypad goes from the idle mode | Write | ||
| AO | 13 | REFRESH_TIME | Sets the duration of the display time of particular parameters; default 5 | Write | ||
| BO | 74 | USB_ON_OFF | Switches on/off the USB port | Write | ||
| BO | 22 | ECO | Switches on an ECO LED | Write | ||
| AO | 17 | EXIT_EDIT_TIME | Sets the time after which edition of any editable parameter is finished | Write | ||
| AO | 19 | CO2_SETPOINT_FOR_ALARM | CO2 alarm setpoint; default 1500 | Write | ||
| AO | 20 | CO2_HYSTERESIS_FOR_ALARM | CO2 alarm hysteresis; default 100 | Write | ||
| BImin | 0 | ALARM_STATUS | CO2 current alarm status | Read | ||
| MV | 5 | NAVIGATIONAL_LED_MODE | Sets a mode of the navigational LED; default 1 | Write | ||
| AO | 22 | NAVIGATIONAL_LED_BRIGHTNESS | Navigational LED brightness; default 100 | Write | ||
| AO | 23 | NAVIGATIONAL_LED_RED | Navigational LED color - red component intensity; default 100 | Write | ||
| AO | 24 | NAVIGATIONAL_LED_GREEN | Navigational LED color - green component intensity; default 100 | Write | ||
| AO | 25 | NAVIGATIONAL_LED_BLUE | Navigational LED color - blue component intensity; default 100 | Write | ||
| AImin | 4 | TEMPERATURE_SENSOR | Actual temperature sensor value with offset | °C | Read | |
| AImin | 5 | HUMIDITY_SENSOR | Actual humidity sensor value with offset | %RH | Read | |
| AImin | 6 | CO2_SENSOR | Actual CO2 sensor value with offset | ppm | Read | |
| AO | 27 | BUZZER_VOLUME | Buzzer volume (%); default 50 | Write | ||
| MV | 20 | BUZZER_TONE | Buzzer tone: discrete (1), loud (2), classic (3), retro (4) | Write | ||
| AVmin | 56 | SETPOINT_VALUE | Temperature setpoint value | Write | ||
| AImin | 3 | EFFECTIVE_SETPOINT | Sum of setpoint and offset values | Read | ||
| AV | 57 | DEFAULT_SETPOINT | Default temperature setpoint; default 210 | Write | ||
| AV | 58 | OFFSET_SETPOINT | Temperature offset for setpoint; default 0 | Write | ||
| AV | 59 | OFFSET_RANGE | Limits offset value; default 30 | Write | ||
| BO | 55 | OPERATING_MODE | Sets the operating mode of the temperature setpoint configuration | Write | ||
| BO | 56 | SETPOINT_DISPLAY | Configures the temperature setpoint display | Write | ||
| MV | 0 | FAN_CURRENT_SPEED | Not available for the Touch Point VAV series; default 0 | Write | ||
| MVmin | 1 | FAN_MODE | Not available for the Touch Point VAV series; default 1 | Write | ||
| MV | 2 | FAN_TYPE | Not available for the Touch Point VAV series | Write | ||
| BO | 58 | FAN_PART_EDITABLE | Not available for the Touch Point VAV series | Write | ||
| BO | 60 | FAN_CONFIG_LOCAL_MODE | Not available for the Touch Point VAV series | Write | ||
| MVmin | 3 | OCCUPANCY_CURRENT_STATUS | Occupancy status | Write | ||
| MVmin | 4 | OCCUPANCY_MODE | Occupancy mode | Write | ||
| BO | 62 | OCCUPANCY_CONFIG_LOCAL_MODE | Local/BMS mode | Write |
No points match these filters.
Object ID lookup: iSMA CONTROLLI Touch Point 2.0 room panel point IDs by name
AI0LIVE_TIMEMI1SENSORSAI1BACKLIGHT_LCDAI2BACKLIGHT_KEYPADMV19SCREEN_SELECT_MODEMV21GEN_BTN_1_MODEBV56GEN_BTN_1_STATEBV63GEN_BTN_1_LED_LOCAL_MODEBV70GEN_BTN_1_LED_BMS_STATEBO0BUZZER_ACTIVEBO3LCD_BACKLIGHT_ACTIVEBO4KEYPAD_BACKLIGHT_ACTIVEBO5CO2_ALARM_LCDBO6CO2_ALARM_BUZZERBO63CO2_ALARM_CONFIRMBO11PANEL_OFFBO12KEYPAD_OFFAO3BACKLIGHT_LCD_ACTIVEAO4BACKLIGHT_LCD_IDLEAO5BACKLIGHT_LCD_STANDBYAO6BACKLIGHT_LCD_TIME_TO_IDLEAO7BACKLIGHT_LCD_TIME_TO_STANDBYAO8BACKLIGHT_KEYPAD_ACTIVEAO9BACKLIGHT_KEYPAD_IDLEAO10BACKLIGHT_KEYPAD_STANDBYAO11BACKLIGHT_KEYPAD_TIME_TO_IDLEAO12BACKLIGHT_KEYPAD_TIME_TO_STANDBYAO13REFRESH_TIMEBO74USB_ON_OFFBO22ECOAO17EXIT_EDIT_TIMEAO19CO2_SETPOINT_FOR_ALARMAO20CO2_HYSTERESIS_FOR_ALARMBI0ALARM_STATUSMV5NAVIGATIONAL_LED_MODEAO22NAVIGATIONAL_LED_BRIGHTNESSAO23NAVIGATIONAL_LED_REDAO24NAVIGATIONAL_LED_GREENAO25NAVIGATIONAL_LED_BLUEAI4TEMPERATURE_SENSORAI5HUMIDITY_SENSORAI6CO2_SENSORAO27BUZZER_VOLUMEMV20BUZZER_TONEAV56SETPOINT_VALUEAI3EFFECTIVE_SETPOINTAV57DEFAULT_SETPOINTAV58OFFSET_SETPOINTAV59OFFSET_RANGEBO55OPERATING_MODEBO56SETPOINT_DISPLAYMV0FAN_CURRENT_SPEEDMV1FAN_MODEMV2FAN_TYPEBO58FAN_PART_EDITABLEBO60FAN_CONFIG_LOCAL_MODEMV3OCCUPANCY_CURRENT_STATUSMV4OCCUPANCY_MODEBO62OCCUPANCY_CONFIG_LOCAL_MODE
Integration notes
- The manual table mixes objects and object properties. Only Present Value rows are listed; other property rows (offsets, filters, limits, visibility, Device-object properties such as BACNET_DEVICE_ID and BAUD_RATE) are left out.
- Rows with a blank access cell (mostly BO display switches) are taken as writable.
- Fan objects (MV 0-2, BO 58, BO 60) are not available on the Touch Point VAV series.
- The generic-button objects are printed as ranges (MV 21-27, BV 56-62, BV 63-69, BV 70-76); each range is shown by its first object, button 1.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Touch Point 2.0 room panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the iSMA CONTROLLI Touch Point 2.0 room panel
How many BACnet points does the iSMA CONTROLLI Touch Point 2.0 room panel have?
This list has 59 BACnet objects: 7 analog inputs, 19 analog outputs, 4 analog values, 1 binary input, 15 binary outputs, 3 binary values, 1 multi-state input, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which iSMA CONTROLLI Touch Point 2.0 room panel BACnet points are writable?
50 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official iSMA CONTROLLI Touch Point 2.0 room panel BACnet documentation?
The source is Touch Point 2.0 Software User Manual V1.0.1 - List of BACnet Objects, revision V1.0.1, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/tp2.0-sw/V1.0.1/list-of-bacnet-objects.
What are the minimum BACnet points to integrate the iSMA CONTROLLI Touch Point 2.0 room panel?
Start with MV 4 OCCUPANCY_MODE (Occupancy mode); AV 56 SETPOINT_VALUE (Temperature setpoint); MV 1 FAN_MODE (Fan mode); AI 4 TEMPERATURE_SENSOR (Room temperature); AI 3 EFFECTIVE_SETPOINT (Effective setpoint (setpoint plus offset)); MV 3 OCCUPANCY_CURRENT_STATUS (Current occupancy status); AI 5 HUMIDITY_SENSOR (Room humidity); AI 6 CO2_SENSOR (Room CO2); BI 0 ALARM_STATUS (CO2 alarm status).
How do I enable BMS control of the iSMA CONTROLLI Touch Point 2.0 room panel?
BO 62 OCCUPANCY_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.
How do I check these points on the real Touch Point 2.0 room panel?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More iSMA CONTROLLI BACnet points lists
- Room panel (thermostat display)
iSMA CONTROLLI Control Point room panel (incl. Control Point VAV)
iSMA CONTROLLI Control Point room panels, including the VAV version used with the iSMA-B-VAV14-IP controller.
Also known as: Control Point, iSMA Control Point, Control Point VAV, Control Point Software V1.1 - Fan coil unit controller
iSMA CONTROLLI iSMA-B-FCU fan coil controller (default application)
iSMA CONTROLLI iSMA-B-FCU fan coil controllers running the factory default FCU application.
Also known as: iSMA-B-FCU, iSMA-B-FCU-HH, iSMA-B-FCU-HL, iSMA-B-FCU-LL, DMP241en - Room panel (thermostat display)
iSMA CONTROLLI iSMA-B-LP room panel (BACnet MS/TP)
iSMA CONTROLLI iSMA-B-LP wall room panels with BACnet MS/TP firmware, with or without humidity and CO2 sensors.
Also known as: iSMA-B-LP, iSMA-B-LP-H, iSMA-B-LP-C, iSMA-B-LP-HC, LP BACnet - VAV box controller
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controller (default VAV application)
iSMA CONTROLLI iSMA-B-VAV14-IP VAV controllers running the factory VAV application (manual V1.4.0).
Also known as: iSMA-B-VAV14-IP, VAV14-IP, iSMA VAV14, VAV14-IP default application - Valve actuator / energy valve
iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)
iSMA CONTROLLI (ex Controlli) MVE-2-RS, MVC-2-RS and EBV-2-RS communicating valve actuators, including energy-valve functions with VLX valves.
Also known as: MVE-2-RS, MVC-2-RS, EBV-2-RS, iC Actuator Configurator, Controlli MVE, Controlli EBV energy valve, VLX energy valve - Room panel (thermostat display)
iSMA CONTROLLI Touch Point room panel
iSMA CONTROLLI Touch Point touch-button room panels (software manual V1.3), including the Touch Point VAV series.
Also known as: Touch Point, iSMA Touch Point, Touch Point VAV, Touch Point Software V1.3
Source: Touch Point 2.0 Software User Manual V1.0.1 - List of BACnet Objects · rev. V1.0.1. Object names, instances and units are reproduced as published; descriptions are our own.