Valve actuator / energy valve · BACnet points list

iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

These Controlli valve actuators talk BACnet MS/TP (or Modbus RTU). The object list covers control type and valve configuration, flow and position curve points, temperature and delta-T setpoints for the energy-valve functions, supply and return temperatures, flow, power and heating/cooling energy with monthly history, event counters, error flags and the actuator clock. Which objects are active depends on the actuator model and the valve selected.

This page lists 158 BACnet objects for the iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) — 67 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from iSMA CONTROLLI’s own free documentation, linked below.

Manufacturer
iSMA CONTROLLI
Model
MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)
Equipment
Valve actuator / energy valve
Equipment type
Valves & actuators
BACnet objects
158 (67 writable)
Transport
BACnet MS/TP
Firmware
iC Actuator Configurator manual V1.3
Also known as
MVE-2-RS, MVC-2-RS, EBV-2-RS, iC Actuator Configurator, Controlli MVE, Controlli EBV energy valve, VLX energy valve
Source document
iC Actuator Configurator Manual V1.3 - BACnet Object · rev. V1.3
Download CSV 158 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against iSMA CONTROLLI’s current documentation and the live device before use. Not official iSMA CONTROLLI information. Terms of use.

BMS integration notes: iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)

Integration in brief

Pick the control type (MV 0) and functions (MV 4), then read flow, supply and return temperature, delta T, power and energy. For energy-valve control write the delta-T or temperature setpoints (AV 37-48) and the design or maximum flow and power.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 0TYPE OF CONTROLControl type, 1 = Modbus/BACnetWrite
MV 4FUNCTIONS ENABLEFunction: BMS, temperature, delta T, power ...Write
AV 37SETPOINT DELTA T CONTROL - HEATINGDelta-T setpoint, heatingWrite
AV 13FEEDBACKFeedback (valve position)Read
AV 36INDICATED FLOW RATEIndicated flow rateWrite
AV 52INSTANT POWERInstant powerRead
MV 7ACTUATOR OPERATING MODEActuator operating modeRead
BV 4ACTUATOR OPERATING MODE (ERROR)Actuator in errorRead

Enable & remote start

MV 0 TYPE OF CONTROL must be Modbus/BACnet for the actuator to follow network commands.

Watch out for

iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

158 of 158 shown
Type
BinaryMulti-state
Access
Show
iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) BACnet Points List
DescriptionStates
AV0UP TIMERead
AV120PRESSURE SENSOR RESOLUTIONOnly for EBV and MVE-2-RS with Custom Energy ValveWrite
MV9MAX. FLOW SETTINGOptions depend on valve series (VLX1-5/VLX1P-5P or HF)Write
MVmin0TYPE OF CONTROLWrite1=Modbus/BACnet, 2=0-10V, 3=2-10V, 4=0-5V (only for EBV/MVE-2-RS), 5=5-10V (only for EBV/MVE-2-RS), 6=2-6V (only for EBV/MVE-2-RS), 7=6-10V (only for EBV/MVE-2-RS), 8=Selected by dip
BV0DIRECT/REVERSE ACTIONWrite
BV1FAILSAFE DIRECTIONWrite
BV15TYPE OF STROKE (only for MVC-2-RS)Write
BV2ENABLE CALIBRATIONWrite
BV3JUMPER ENABLE (ER BOARD)Visible only for EBV/MVE-2-RSWrite
MV1CHANGEOVER SETTINGWrite1=Heating, 2=Cooling, 3=Automatic (depends on delta T)
MV2TEMPERATURE SENSOR SELECTIONWrite1=T1 (supply), 2=T2 (return), 3=T1, T2 (delta T)
MV10ACTUATOR SPEEDMVC-2-RS onlyWrite1=5s/mm, 2=3s/mm
MV3VALVE CHARACTERISTICS CONFIGURATIONWrite1=Linear, 2=Equipercentage
MVmin4FUNCTIONS ENABLEWrite1=BMS, 2=Temperature control, 3=Temperature ΔT limit, 4=Temperature max limit, 5=Temperature min limit, 6=Power control, 7=Power limit
BV14FUNCTIONS ENABLE (ENERGY)Write
MV5Functions statusRead
AV1MINIMUM OPENING VALVEWrite
AV2DIP SWITCH SETTINGRead
MV6VALVE TYPEThe visible options depend on the connected actuatorWrite1=Generic, 2=Reserved, 3=Reserved, 4=Reserved, 5=Custom energy valve, 6=VLX6P, 7=VLX8P, 8=VLX1/VLX1P, 9=VLX2/VLX2P, 10=VLX3/VLX3P, 11=VLX4/VLX4P, 12=VLX5/VLX5P, 13=Custom PICV, 14=2FGB65B-EBV, 15=2FGB80B-EBV, 16=2FGB100B-EBV, 17=2FGB125B-EBV, 18=2FGB150B-EBV, 19=Reserved, 20=VLX2HF/VLX2PHF, 21=VLX3HF/VLX3PHF, 22=VLX4HF/VLX4PHF
AV3VALVE STROKE (mm*100)mmRead
AV4OVER VOLTAGE EVENTS (24 v ac > 20%) (230 v > 10%)Read
AV5UNDER VOLTAGE EVENTS (v ac < 20%) (230 v < 10%)Read
AV6FULLY OPEN EVENTSRead
AV7FULLY OPEN EVENTSRead
AV8UNEXPECTED STALL CONDITION EVENTS (within calculated stroke)Read
AV9UNEXPECTED STALL CONDITION EVENTS (outside calculated stroke)Read
AV10VALVE STROKE ERROR > MAX (60 mm EBV/MVE-2-RS e 12 mm MVC-2-RS)Read
AV11VALVE STROKE ERROR < MIN (5 mm EBV/MVE-2-RS e 2 mm MVC-2-RS)Read
MVmin7ACTUATOR OPERATING MODERead1=Normal running, 2=Initial positioning, 3=Stroke calibration, 4=Fail safe, 5=Manual override
BVmin4ACTUATOR OPERATING MODE (ERROR)Read
BV5TEMPERATURE SENSOR 1 ERRORRead
BV6TEMPERATURE SENSOR 2 ERRORRead
BV20PRESSURE SENSOR 1 ERRORRead
BV21PRESSURE SENSOR 2 ERRORRead
BV7CALIBRATED STROKE < MIN ERROR (5 mm for EBV/MVE-2-RS and 2 mm for MVC-2-RS)Read
BV8CALIBRATED STROKE > MAX ERROR (60 mm for EBV/MVE-2-RS and 12 mm for MVC-2-RS)Read
BV9UNEXPECTED STALL (INSIDE STROKE) ERRORRead
BV10UNEXPECTED STALL (OUTSIDE STROKE) ERRORRead
BV11UNDERVOLTAGERead
BV12OVERVOLTAGERead
BV13CLOCK ERRORRead
BV16COUNTERS RESETWrite
AVmin13FEEDBACKRead
AV14MAX. FLOW RATEWrite
AV15DESIGN FLOW RATEWrite
AI2INPUT PRESSURE VALUEAvailable only for EBV and MVE-2-RS with Custom Energy ValveRead
AI3OUTPUT PRESSURE VALUEAvailable only for EBV and MVE-2-RS with Custom Energy ValveRead
AV119DIFFERENTIAL PRESSUREAvailable only for EBV and MVE-2-RS with Custom Energy ValveRead
AV16FLOW RATE SP X1Read
AV17VALVE POSITION Y1Read
AV18FLOW RATE SP X2Write
AV19VALVE POSITION Y2Write
AV20FLOW RATE SP X3Write
AV21VALVE POSITION Y3Write
AV22FLOW RATE SP X4Write
AV23VALVE POSITION Y4Write
AV24FLOW RATE SP X5Write
AV25VALVE POSITION Y5Write
AV26FLOW RATE SP X6Write
AV27VALVE POSITION Y6Write
AV28FLOW RATE SP X7Write
AV29VALVE POSITION Y7Write
AV30FLOW RATE SP X8Write
AV31VALVE POSITION Y8Write
AV32FLOW RATE SP X9Write
AV34FLOW RATE SP X10Read
AV35VALVE POSITION Y10Read
AVmin36INDICATED FLOW RATEWrite
AVmin37SETPOINT DELTA T CONTROL - HEATINGWrite
AV38SETPOINT DELTA T CONTROL - COOLINGWrite
AV39SETPOINT SUPPLY TEMPERATURE CONTROL - HEATINGWrite
AV40SETPOINT SUPPLY TEMPERATURE CONTROL - COOLINGWrite
AV41SETPOINT RETURN TEMPERATURE CONTROL - HEATINGWrite
AV42SETPOINT RETURN TEMPERATURE CONTROL - COOLINGWrite
AV43SETPOINT MIN. DELTA T HEATINGWrite
AV44SETPOINT MIN. DELTA T COOLINGWrite
AV45SETPOINT MAX. SUPPLY TEMPERATURE - HEATINGWrite
AV46SETPOINT MIN. SUPPLY TEMPERATURE - COOLINGWrite
AV47SETPOINT MAX. RETURN TEMPERATURE - HEATINGWrite
AV48SETPOINT MIN. RETURN TEMPERATURE - COOLINGWrite
AV49DESIGN POWERWrite
AV50SET MAX. POWER LIMITWrite
AI0SUPPLY TEMPERATURE VALUEWritable in temperature test mode (BV 19)Write
AI1RETURN TEMPERATURE VALUEWritable in temperature test mode (BV 19)Write
AV51DELTA T VALUE (T1 – T2)Read
AVmin52INSTANT POWERRead
AV53HEATING ENERGY (LSR)Read
AV53HEATING ENERGY (MSR)Read
AV54COOLING ENERGY (LSR)Read
AV54COOLING ENERGY (MSR)Read
AV55HEATING ENERGY AT 31/12 (MSR)Read
AV56HEATING ENERGY AT VALUE 1Read
AV57HEATING ENERGY AT VALUE 2Read
AV58HEATING ENERGY AT VALUE 3Read
AV59HEATING ENERGY AT VALUE 4Read
AV60HEATING ENERGY AT VALUE 5Read
AV61HEATING ENERGY AT VALUE 6Read
AV62HEATING ENERGY AT VALUE 7Read
AV63HEATING ENERGY AT VALUE 8Read
AV64HEATING ENERGY AT VALUE 9Read
AV65HEATING ENERGY AT VALUE 10Read
AV66HEATING ENERGY AT VALUE 11Read
AV67HEATING ENERGY AT VALUE 12Read
AV68COOLING ENERGY AT 31/12 (LSR)Read
AV68COOLING ENERGY AT 31/12 (MSR)Read
AV69COOLING ENERGY VALUE 1Read
AV70COOLING ENERGY VALUE 2Read
AV71COOLING ENERGY VALUE 3Read
AV72COOLING ENERGY VALUE 4Read
AV73COOLING ENERGY VALUE 5Read
AV74COOLING ENERGY VALUE 6Read
AV75COOLING ENERGY VALUE 7Read
AV77COOLING ENERGY VALUE 9Read
AV78COOLING ENERGY VALUE 10Read
AV79COOLING ENERGY VALUE 11Read
AV80COOLING ENERGY VALUE 12Read
AV81CLOCK MINUTESWrite
AV82CLOCK HOURSWrite
AV83CLOCK DAYWrite
AV84CLOCK MONTHWrite
AV85CLOCK YEARWrite
BV17FORCE FULLY CLOSEWrite
BV18FORCE FULLY OPENWrite
BV19TEST TEMPERATURE MODEWrite
AV86MAX. POWERRead-only for EBV/MVC-2-RSWrite
AV87MEDIA DENSITYWrite
AV88MEDIA SPECIFIC HEATWrite
AV118DESIGN POWER DELTATWrite
MV8LOOP TYPE (P, P+I, P+I+D)Write
AV89DERIVATIVE TIME (GAIN)Write
AV90INTEGRAL TIME (MINUTES)minWrite
AV91PROPORTIONAL BANDWIDTH (°C*10)°CWrite
AV92MONTH TIMESTAMP OF 31TH DECEMBERRead
AV93YEAR TIMESTAMP OF 31TH DECEMBERRead
AV94MONTH TIMESTAMP OF VALUE 1Read
AV95YEAR TIMESTAMP OF VALUE 1Read
AV96MONTH TIMESTAMP OF VALUE 2Read
AV97YEAR TIMESTAMP OF VALUE 2Read
AV98MONTH TIMESTAMP OF VALUE 3Read
AV99YEAR TIMESTAMP OF VALUE 3Read
AV100MONTH TIMESTAMP OF VALUE 4Read
AV101YEAR TIMESTAMP OF VALUE 4Read
AV102MONTH TIMESTAMP OF VALUE 5Read
AV103YEAR TIMESTAMP OF VALUE 5Read
AV104MONTH TIMESTAMP OF VALUE 6Read
AV105YEAR TIMESTAMP OF VALUE 6Read
AV106MONTH TIMESTAMP OF VALUE 7Read
AV107YEAR TIMESTAMP OF VALUE 7Read
AV108MONTH TIMESTAMP OF VALUE 8Read
AV109YEAR TIMESTAMP OF VALUE 8Read
AV110MONTH TIMESTAMP OF VALUE 9Read
AV111YEAR TIMESTAMP OF VALUE 9Read
AV112MONTH TIMESTAMP OF VALUE 10Read
AV113YEAR TIMESTAMP OF VALUE 10Read
AV114MONTH TIMESTAMP OF VALUE 11Read
AV115YEAR TIMESTAMP OF VALUE 11Read
AV116MONTH TIMESTAMP OF VALUE 12Read
AV117YEAR TIMESTAMP OF VALUE 12Read
Object ID lookup: iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)

How many BACnet points does the iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) have?

This list has 158 BACnet objects: 4 analog inputs, 121 analog values, 22 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) BACnet points are writable?

67 of the 158 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP) BACnet documentation?

The source is iC Actuator Configurator Manual V1.3 - BACnet Object, revision V1.3, published free by iSMA CONTROLLI at https://icdocs.ismacontrolli.com/en/ic-actuator-configurator/V1.3/bacnet-object.

What are the minimum BACnet points to integrate the iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)?

Start with MV 0 TYPE OF CONTROL (Control type, 1 = Modbus/BACnet); MV 4 FUNCTIONS ENABLE (Function: BMS, temperature, delta T, power ); AV 37 SETPOINT DELTA T CONTROL - HEATING (Delta-T setpoint, heating); AV 13 FEEDBACK (Feedback (valve position)); AV 36 INDICATED FLOW RATE (Indicated flow rate); AV 52 INSTANT POWER (Instant power); MV 7 ACTUATOR OPERATING MODE (Actuator operating mode); BV 4 ACTUATOR OPERATING MODE (ERROR) (Actuator in error).

How do I enable BMS control of the iSMA CONTROLLI MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)?

MV 0 TYPE OF CONTROL must be Modbus/BACnet for the actuator to follow network commands.

How do I check these points on the real MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More iSMA CONTROLLI BACnet points lists

Source: iC Actuator Configurator Manual V1.3 - BACnet Object · rev. V1.3. Object names, instances and units are reproduced as published; descriptions are our own.