 "manufacturer": "iSMA CONTROLLI",
 "manufacturer_slug": "isma-controlli",
 "model": "MVE-2-RS / MVC-2-RS / EBV-2-RS valve actuators (BACnet MS/TP)",
 "model_slug": "mve-mvc-ebv-2-rs-actuators",
 "aliases": [
  "MVE-2-RS",
  "MVC-2-RS",
  "EBV-2-RS",
  "iC Actuator Configurator",
  "Controlli MVE",
  "Controlli EBV energy valve",
  "VLX energy valve"
 ],
 "equipment_type": "Valve actuator / energy valve",
 "applies_to": "iSMA CONTROLLI (ex Controlli) MVE-2-RS, MVC-2-RS and EBV-2-RS communicating valve actuators, including energy-valve functions with VLX valves.",
 "summary": "These Controlli valve actuators talk BACnet MS/TP (or Modbus RTU). The object list covers control type and valve configuration, flow and position curve points, temperature and delta-T setpoints for the energy-valve functions, supply and return temperatures, flow, power and heating/cooling energy with monthly history, event counters, error flags and the actuator clock. Which objects are active depends on the actuator model and the valve selected.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "iC Actuator Configurator manual V1.3",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Instance numbers restart for each object type. Many objects apply only to some models (MVE/MVC/EBV) or valve types; the description says which when the manual does.",
  "AV 53, AV 54 and AV 68 are each printed twice (LSR and MSR halves of an energy value); both rows are kept as printed.",
  "AV 6 and AV 7 are both printed as \"FULLY OPEN EVENTS\"; AV 33 (VALVE POSITION Y9) and AV 76 are missing from the table.",
  "Network Port objects (MAC address, baud rate) and Device-object clock properties are left out; the clock is also on AV 81-85.",
  "MV states are numbered here in table order; the manual lists the texts without numbers."
 ],
 "source": {
  "title": "iC Actuator Configurator Manual V1.3 - BACnet Object",
  "doc_number": null,
  "revision_date": "V1.3",
  "url": "https://icdocs.ismacontrolli.com/en/ic-actuator-configurator/V1.3/bacnet-object"
 },
 "integration": {
  "summary": "Pick the control type (MV 0) and functions (MV 4), then read flow, supply and return temperature, delta T, power and energy. For energy-valve control write the delta-T or temperature setpoints (AV 37-48) and the design or maximum flow and power.",
  "minimum_points": [
   {
    "ref": "MV 0",
    "name": "TYPE OF CONTROL",
    "why": "Control type, 1 = Modbus/BACnet"
   },
   {
    "ref": "MV 4",
    "name": "FUNCTIONS ENABLE",
    "why": "Function: BMS, temperature, delta T, power ..."
   },
   {
    "ref": "AV 37",
    "name": "SETPOINT DELTA T CONTROL - HEATING",
    "why": "Delta-T setpoint, heating"
   },
   {
    "ref": "AV 13",
    "name": "FEEDBACK",
    "why": "Feedback (valve position)"
   },
   {
    "ref": "AV 36",
    "name": "INDICATED FLOW RATE",
    "why": "Indicated flow rate"
   },
   {
    "ref": "AV 52",
    "name": "INSTANT POWER",
    "why": "Instant power"
   },
   {
    "ref": "MV 7",
    "name": "ACTUATOR OPERATING MODE",
    "why": "Actuator operating mode"
   },
   {
    "ref": "BV 4",
    "name": "ACTUATOR OPERATING MODE (ERROR)",
    "why": "Actuator in error"
   }
  ],
  "enable": "MV 0 TYPE OF CONTROL must be Modbus/BACnet for the actuator to follow network commands.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [],
  "gotchas": [
   "Energy values are split over LSR/MSR rows in the manual; check how the actuator presents them over BACnet.",
   "BV 17/BV 18 force the valve fully closed/open and override control."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 0,
   "name": "UP TIME",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "PRESSURE SENSOR RESOLUTION",
   "description": "Only for EBV and MVE-2-RS with Custom Energy Valve",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "MAX. FLOW SETTING",
   "description": "Options depend on valve series (VLX1-5/VLX1P-5P or HF)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "TYPE OF CONTROL",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Modbus/BACnet, 2=0-10V, 3=2-10V, 4=0-5V (only for EBV/MVE-2-RS), 5=5-10V (only for EBV/MVE-2-RS), 6=2-6V (only for EBV/MVE-2-RS), 7=6-10V (only for EBV/MVE-2-RS), 8=Selected by dip"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "DIRECT/REVERSE ACTION",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "FAILSAFE DIRECTION",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "TYPE OF STROKE (only for MVC-2-RS)",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ENABLE CALIBRATION",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "JUMPER ENABLE (ER BOARD)",
   "description": "Visible only for EBV/MVE-2-RS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "CHANGEOVER SETTING",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Cooling, 3=Automatic (depends on delta T)"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "TEMPERATURE SENSOR SELECTION",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=T1 (supply), 2=T2 (return), 3=T1, T2 (delta T)"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "ACTUATOR SPEED",
   "description": "MVC-2-RS only",
   "units": "",
   "access": "W",
   "states": "1=5s/mm, 2=3s/mm"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "VALVE CHARACTERISTICS CONFIGURATION",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Linear, 2=Equipercentage"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "FUNCTIONS ENABLE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=BMS, 2=Temperature control, 3=Temperature ΔT limit, 4=Temperature max limit, 5=Temperature min limit, 6=Power control, 7=Power limit"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "FUNCTIONS ENABLE (ENERGY)",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Functions status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "MINIMUM OPENING VALVE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "DIP SWITCH SETTING",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "VALVE TYPE",
   "description": "The visible options depend on the connected actuator",
   "units": "",
   "access": "W",
   "states": "1=Generic, 2=Reserved, 3=Reserved, 4=Reserved, 5=Custom energy valve, 6=VLX6P, 7=VLX8P, 8=VLX1/VLX1P, 9=VLX2/VLX2P, 10=VLX3/VLX3P, 11=VLX4/VLX4P, 12=VLX5/VLX5P, 13=Custom PICV, 14=2FGB65B-EBV, 15=2FGB80B-EBV, 16=2FGB100B-EBV, 17=2FGB125B-EBV, 18=2FGB150B-EBV, 19=Reserved, 20=VLX2HF/VLX2PHF, 21=VLX3HF/VLX3PHF, 22=VLX4HF/VLX4PHF"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "VALVE STROKE (mm*100)",
   "description": "",
   "units": "mm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "OVER VOLTAGE EVENTS (24 v ac > 20%) (230 v > 10%)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "UNDER VOLTAGE EVENTS (v ac < 20%) (230 v < 10%)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "FULLY OPEN EVENTS",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "FULLY OPEN EVENTS",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "UNEXPECTED STALL CONDITION EVENTS (within calculated stroke)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "UNEXPECTED STALL CONDITION EVENTS (outside calculated stroke)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "VALVE STROKE ERROR > MAX (60 mm EBV/MVE-2-RS e 12 mm MVC-2-RS)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "VALVE STROKE ERROR < MIN (5 mm EBV/MVE-2-RS e 2 mm MVC-2-RS)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "ACTUATOR OPERATING MODE",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Normal running, 2=Initial positioning, 3=Stroke calibration, 4=Fail safe, 5=Manual override"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "ACTUATOR OPERATING MODE (ERROR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "TEMPERATURE SENSOR 1 ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "TEMPERATURE SENSOR 2 ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "PRESSURE SENSOR 1 ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "PRESSURE SENSOR 2 ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "CALIBRATED STROKE < MIN ERROR (5 mm for EBV/MVE-2-RS and 2 mm for MVC-2-RS)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "CALIBRATED STROKE > MAX ERROR (60 mm for EBV/MVE-2-RS and 12 mm for MVC-2-RS)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "UNEXPECTED STALL (INSIDE STROKE) ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "UNEXPECTED STALL (OUTSIDE STROKE) ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "UNDERVOLTAGE",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "OVERVOLTAGE",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "CLOCK ERROR",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "COUNTERS RESET",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "FEEDBACK",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "MAX. FLOW RATE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "DESIGN FLOW RATE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "INPUT PRESSURE VALUE",
   "description": "Available only for EBV and MVE-2-RS with Custom Energy Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "OUTPUT PRESSURE VALUE",
   "description": "Available only for EBV and MVE-2-RS with Custom Energy Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "DIFFERENTIAL PRESSURE",
   "description": "Available only for EBV and MVE-2-RS with Custom Energy Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "FLOW RATE SP X1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "VALVE POSITION Y1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "FLOW RATE SP X2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "VALVE POSITION Y2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "FLOW RATE SP X3",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "VALVE POSITION Y3",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "FLOW RATE SP X4",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "VALVE POSITION Y4",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "FLOW RATE SP X5",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "VALVE POSITION Y5",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "FLOW RATE SP X6",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "VALVE POSITION Y6",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "FLOW RATE SP X7",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "VALVE POSITION Y7",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "FLOW RATE SP X8",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "VALVE POSITION Y8",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "FLOW RATE SP X9",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "FLOW RATE SP X10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "VALVE POSITION Y10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "INDICATED FLOW RATE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SETPOINT DELTA T CONTROL - HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "SETPOINT DELTA T CONTROL - COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SETPOINT SUPPLY TEMPERATURE CONTROL - HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SETPOINT SUPPLY TEMPERATURE CONTROL - COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SETPOINT RETURN TEMPERATURE CONTROL - HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SETPOINT RETURN TEMPERATURE CONTROL - COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "SETPOINT MIN. DELTA T HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "SETPOINT MIN. DELTA T COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "SETPOINT MAX. SUPPLY TEMPERATURE - HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "SETPOINT MIN. SUPPLY TEMPERATURE - COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "SETPOINT MAX. RETURN TEMPERATURE - HEATING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "SETPOINT MIN. RETURN TEMPERATURE - COOLING",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "DESIGN POWER",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "SET MAX. POWER LIMIT",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "SUPPLY TEMPERATURE VALUE",
   "description": "Writable in temperature test mode (BV 19)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "RETURN TEMPERATURE VALUE",
   "description": "Writable in temperature test mode (BV 19)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "DELTA T VALUE (T1 – T2)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "INSTANT POWER",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "HEATING ENERGY (LSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "HEATING ENERGY (MSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "COOLING ENERGY (LSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "COOLING ENERGY (MSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "HEATING ENERGY AT 31/12 (MSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "HEATING ENERGY AT VALUE 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "HEATING ENERGY AT VALUE 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "HEATING ENERGY AT VALUE 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "HEATING ENERGY AT VALUE 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "HEATING ENERGY AT VALUE 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "HEATING ENERGY AT VALUE 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "HEATING ENERGY AT VALUE 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "HEATING ENERGY AT VALUE 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "HEATING ENERGY AT VALUE 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "HEATING ENERGY AT VALUE 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "HEATING ENERGY AT VALUE 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "HEATING ENERGY AT VALUE 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "COOLING ENERGY AT 31/12 (LSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "COOLING ENERGY AT 31/12 (MSR)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "COOLING ENERGY VALUE 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "COOLING ENERGY VALUE 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "COOLING ENERGY VALUE 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "COOLING ENERGY VALUE 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "COOLING ENERGY VALUE 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "COOLING ENERGY VALUE 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "COOLING ENERGY VALUE 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "COOLING ENERGY VALUE 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "COOLING ENERGY VALUE 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "COOLING ENERGY VALUE 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "COOLING ENERGY VALUE 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "CLOCK MINUTES",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "CLOCK HOURS",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "CLOCK DAY",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "CLOCK MONTH",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "CLOCK YEAR",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "FORCE FULLY CLOSE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "FORCE FULLY OPEN",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "TEST TEMPERATURE MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "MAX. POWER",
   "description": "Read-only for EBV/MVC-2-RS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "MEDIA DENSITY",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "MEDIA SPECIFIC HEAT",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "DESIGN POWER DELTAT",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "LOOP TYPE (P, P+I, P+I+D)",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "DERIVATIVE TIME (GAIN)",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "INTEGRAL TIME (MINUTES)",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "PROPORTIONAL BANDWIDTH (°C*10)",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "MONTH TIMESTAMP OF 31TH DECEMBER",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "YEAR TIMESTAMP OF 31TH DECEMBER",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "MONTH TIMESTAMP OF VALUE 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "YEAR TIMESTAMP OF VALUE 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "MONTH TIMESTAMP OF VALUE 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "YEAR TIMESTAMP OF VALUE 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "MONTH TIMESTAMP OF VALUE 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "YEAR TIMESTAMP OF VALUE 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "MONTH TIMESTAMP OF VALUE 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "YEAR TIMESTAMP OF VALUE 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "MONTH TIMESTAMP OF VALUE 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "YEAR TIMESTAMP OF VALUE 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "MONTH TIMESTAMP OF VALUE 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "YEAR TIMESTAMP OF VALUE 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "MONTH TIMESTAMP OF VALUE 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "YEAR TIMESTAMP OF VALUE 7",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "MONTH TIMESTAMP OF VALUE 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "YEAR TIMESTAMP OF VALUE 8",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "MONTH TIMESTAMP OF VALUE 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "YEAR TIMESTAMP OF VALUE 9",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "MONTH TIMESTAMP OF VALUE 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "YEAR TIMESTAMP OF VALUE 10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "MONTH TIMESTAMP OF VALUE 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "YEAR TIMESTAMP OF VALUE 11",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "MONTH TIMESTAMP OF VALUE 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "YEAR TIMESTAMP OF VALUE 12",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/isma-controlli/mve-mvc-ebv-2-rs-actuators",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}