 "manufacturer": "iSMA CONTROLLI",
 "manufacturer_slug": "isma-controlli",
 "model": "Control Point room panel (incl. Control Point VAV)",
 "model_slug": "control-point-room-panel",
 "aliases": [
  "Control Point",
  "iSMA Control Point",
  "Control Point VAV",
  "Control Point Software V1.1"
 ],
 "equipment_type": "Room panel (thermostat display)",
 "applies_to": "iSMA CONTROLLI Control Point room panels, including the VAV version used with the iSMA-B-VAV14-IP controller.",
 "summary": "The Control Point room panel exposes its built-in temperature, humidity and CO2 sensors, a temperature setpoint with offset, fan mode and speed, occupancy mode and status, and its display and keypad settings as BACnet objects. The VAV version adds a commissioning submenu (BO 64-69, MV 5-17, AO 22-37) that mirrors the VAV14-IP controller settings: airflow limits, K-factor, damper and fan test commands. Seven menus of user-defined parameters let the BMS show its own values.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Control Point Software manual V1.1",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "The manual table mixes objects and object properties. Only Present Value rows are listed; rows for other properties (offset, filter, limits, names, visibility, Device-object properties such as BACNET_DEVICE_ID and BAUD_RATE) are left out.",
  "AV 58 OFFSET_SETPOINT and MV 2 FAN_TYPE are printed with a property number (1503, 1602) instead of Present value; they are listed because the Touch Point manuals show them as Present value objects. DEFAULT_SETPOINT is printed as \"AC57\" and listed as AV 57.",
  "BO 14-24 are all named LCD_ICON_DISPLAY (one per icon, given in the description); BO 25-35 LCD_ICON_FLASHING is a range shown by its first object.",
  "The VAV submenu objects come from a separate page; each one is linked to a VAV14-IP application object (named in the manual). AO 23 is printed twice there and listed once.",
  "User-defined parameter slots (NUMERIC1-8 as AV 0-55, BOOLEAN1-8 as BV 0-55) for the main menu and six submenus are all listed; the manual gives no Present value row for MAIN_MENU_NUMERIC3 and NUMERIC7 (AV 2, AV 6)."
 ],
 "source": {
  "title": "Control Point Software User Manual V1.1 - List of BACnet Objects",
  "doc_number": null,
  "revision_date": "V1.1",
  "url": "https://icdocs.ismacontrolli.com/control-point-software/V1.1/list-of-bacnet-objects"
 },
 "integration": {
  "summary": "Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode. With a VAV14-IP the VAV submenu objects are commissioning settings only.",
  "minimum_points": [
   {
    "ref": "MV 4",
    "name": "OCCUPANCY_MODE",
    "why": "Occupancy mode, 1 = unoccupied, 2 = occupied"
   },
   {
    "ref": "AV 56",
    "name": "SETPOINT",
    "why": "Temperature setpoint"
   },
   {
    "ref": "MV 1",
    "name": "FAN_MODE",
    "why": "Fan mode: 1 off, 2-4 manual speed, 5 auto"
   },
   {
    "ref": "AI 4",
    "name": "TEMPERATURE_SENSOR",
    "why": "Room temperature"
   },
   {
    "ref": "AI 3",
    "name": "EFFECTIVE_SETPOINT",
    "why": "Effective setpoint (setpoint plus offset)"
   },
   {
    "ref": "MV 3",
    "name": "CURRENT_OCCUPIED_STATUS",
    "why": "Occupancy status: 0 unocc, 1 occ, 2 standby, 3 forced"
   },
   {
    "ref": "AI 5",
    "name": "HUMIDITY_SENSOR",
    "why": "Room humidity"
   },
   {
    "ref": "AI 6",
    "name": "CO2_SENSOR",
    "why": "Room CO2"
   }
  ],
  "enable": "BO 62 OCCUPIED_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance and baud rate are Device-object properties (BACNET_DEVICE_ID default 0xFFFFFFFF, BAUD_RATE default 115200).",
   "The VAV submenu (password AO 36, default 1000) is for commissioning the VAV14-IP from the panel."
  ],
  "gotchas": [
   "Most configuration objects are stored in panel memory; avoid cyclic writes.",
   "Sensor objects exist only on panel versions with that sensor (MI 1 SENSORS lists them)."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "LIVE_TIME",
   "description": "Device uptime in seconds",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "PANEL_PASSWORD",
   "description": "Password for the panel settings",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "SENSORS",
   "description": "Sensors built-in in the panel:",
   "units": "",
   "access": "R",
   "states": "0=Temperature sensor, 1=CO2 sensor, 2=Humidity sensor"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "BACKGROUND_LCD_CURRENT_VALUE",
   "description": "Current display illumination value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "BACKGROUND_KEY_PAD_CURRENT_VALUE",
   "description": "Current keypad illumination value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "HOURS",
   "description": "Hours part of time display",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "MINUTES",
   "description": "Minutes part of time display",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "BUZZER",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active (default)"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "TIME_FORMAT",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=24 h (default), True=12 h"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "DEFAULT_TEMPERATURE_UNIT",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Celsius (default), True=Fahrenheit"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "BACKGROUND_ILLUMINATION_LCD_ACTIVE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "CO2_IN_ALARM_FLASHING_LCD",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "CO2_IN_ALARM_BUZZER",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "CO2_IN_ALARM_SHOW_HIGH",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 63,
   "name": "CO2_ALARM_CONFIRM_ENABLE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "SUBMENU_ICON_DISPLAY_OFF",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "PANEL_OFF",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Panel on (default), True=Panel off"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "KEY_PAD_OFF",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Keypad on (default), True=Keypad off"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "LCD_FLASHING",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active (default), True=Active"
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "KEY_PAD_FLASHING",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active (default), True=Active"
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "BACKGROUND_LCD_FOR_ACTIVE_MODE",
   "description": "Default: 60%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "BACKGROUND_LCD_FOR_IDLE_MODE",
   "description": "Default: 40%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "BACKGROUND_LCD_FOR_STANDBY_MODE",
   "description": "Default: 0%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "BACKGROUND_LCD_TIME_TO_IDLE",
   "description": "Default: 10 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "BACKGROUND_LCD_TIME_TO_STANDBY",
   "description": "Default: 5 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "BACKGROUND_KEY_PAD_ACTIVE_MODE",
   "description": "Default: 10%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "BACKGROUND_KEY_PAD__IDLE_MODE",
   "description": "Default: 40%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "BACKGROUND_KEY_PAD_STANDBY_MODE",
   "description": "Default: 60%",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "BACKGROUND_KEY_PAD_TIME_TO_IDLE",
   "description": "Default: 10 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "BACKGROUND_KEY_PAD_TIME_TO_STANDBY",
   "description": "Default: 5 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "REFRESH_TIME",
   "description": "Default: 2 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 13,
   "name": "TIME_CONFIGURATION",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Clock displayed (default), True=Clock not displayed"
  },
  {
   "type": "BO",
   "instance": 14,
   "name": "LCD_ICON_DISPLAY",
   "description": "SUN",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 15,
   "name": "LCD_ICON_DISPLAY",
   "description": "MOON",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 16,
   "name": "LCD_ICON_DISPLAY",
   "description": "HEATING",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 17,
   "name": "LCD_ICON_DISPLAY",
   "description": "COOLING",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "LCD_ICON_DISPLAY",
   "description": "HUMIDIFIER",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 19,
   "name": "LCD_ICON_DISPLAY",
   "description": "DEHUMIDIFIER",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 20,
   "name": "LCD_ICON_DISPLAY",
   "description": "WIRELESS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 21,
   "name": "LCD_ICON_DISPLAY",
   "description": "SETTINGS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 22,
   "name": "LCD_ICON_DISPLAY",
   "description": "ECO",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 23,
   "name": "LCD_ICON_DISPLAY",
   "description": "RECIRCULATION",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 24,
   "name": "LCD_ICON_DISPLAY",
   "description": "PC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 25,
   "name": "LCD_ICON_FLASHING",
   "description": "(11 objects, BO 25-35)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 14,
   "name": "LCD_ICON_FLASHING_TIME",
   "description": "Icons blinking frequency",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15,
   "name": "SUBMENU_ICON_FLASHING_TIME",
   "description": "Submenu icons flashing time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "ENTER_MENU_TIME",
   "description": "Default: 2 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "EXIT_EDIT_TIME",
   "description": "Default: 5 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 18,
   "name": "EXIT_MENU_TIME",
   "description": "Default: 10 s",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 19,
   "name": "CO2_SETPOINT_FOR_ALARM",
   "description": "CO2 alarm setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "CO2_HYSTERESIS_FOR_ALARM",
   "description": "CO2 alarm hysteresis",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "TEMPERATURE_SENSOR",
   "description": "Current temperature sensor value with offset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "HUMIDITY_SENSOR",
   "description": "Current humidity sensor value with offset",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "CO2_SENSOR",
   "description": "Current CO2 sensor value with offset",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "SETPOINT",
   "description": "Actual setpoint value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "EFFECTIVE_SETPOINT",
   "description": "Sum of the temperature actual setpoint value and offset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "DEFAULT_SETPOINT",
   "description": "Default: 21oC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "OFFSET_RANGE",
   "description": "Offset value limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 55,
   "name": "OPERATING_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Changing offset, True=Changing setpoint (default)"
  },
  {
   "type": "BO",
   "instance": 56,
   "name": "SETPOINT_DISPLAY",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active, True=Active (default)"
  },
  {
   "type": "BO",
   "instance": 57,
   "name": "FAST_EDIT_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active (default), True=Active"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "FAN_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Manual, speed 1 (default), 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "FAN_CURRENT_SPEED",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Off (default), 2=Manual, speed 1, 3=Manual, speed 2, 4=Manual, speed 3, 5=Auto, speed 1, 6=Auto, speed 2, 7=Auto, speed 3"
  },
  {
   "type": "BO",
   "instance": 59,
   "name": "PART_EDITABLE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Fully editable (default), True=Auto_Off_Mode"
  },
  {
   "type": "BO",
   "instance": 60,
   "name": "FAST_EDIT_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active (default), True=Active"
  },
  {
   "type": "AO",
   "instance": 21,
   "name": "FAN_ICON_FLASHING_TIME",
   "description": "Time base for calculating the frequency of the fan icon rotation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "OCCUPANCY_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Unoccupied, 2=Occupied"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "CURRENT_OCCUPIED_STATUS",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=Unoccupied, 1=Occupied, 2=Standby, 3=Forced occupied"
  },
  {
   "type": "BO",
   "instance": 61,
   "name": "FAST_EDIT_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Not active (default), True=Active"
  },
  {
   "type": "BO",
   "instance": 62,
   "name": "OCCUPIED_CONFIG_LOCAL_MODE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "False=Local mode, True=BMS mode"
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "OFFSET_SETPOINT",
   "description": "Default: 0oC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "FAN_TYPE",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=Analog, 0-10 V DC, 2=1-speed fan, 3=2-speed fan, 4=3-speed fan"
  },
  {
   "type": "BO",
   "instance": 68,
   "name": "VAV_DEVICE_TYPE",
   "description": "Choose VAV device control type from airflow demand",
   "units": "",
   "access": "W",
   "states": "False=VAV, True=VVT"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "VAV_REHEATER_TYPE",
   "description": "Set the reheater type",
   "units": "",
   "access": "W",
   "states": "1=none, 2=TimeProp, 3=staged, 4=float"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "VAV_PERIMETER_TYPE",
   "description": "Set the perimeter type",
   "units": "",
   "access": "W",
   "states": "1=none, 2=TimeProp, 3=digital"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "VAV_FAN_TYPE",
   "description": "Set the fan type",
   "units": "",
   "access": "W",
   "states": "1=none, 2=series, 3=parallel"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "VAV_DISCHARGE_TEMP_TYPE",
   "description": "Select the discharge temperature type",
   "units": "",
   "access": "W",
   "states": "1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "VAV_SPACE_TEMP_TYPE",
   "description": "Select the space temperature type",
   "units": "",
   "access": "W",
   "states": "1=Voltage measurement, 2=Current, 3=Resistance input, 4=10K3A1 NTC, 5=10K4A1 NTC, 6=10K NTC Carel, 7=20K6A1 NTC, 8=2,2K3A1 NTC, 9=3K3A1 NTC, 10=30K6A1 NTC, 11=SIE1, 12=TAC1, 13=SAT1, 14=PT1000, 15=NI1000, 16=NI1000 21C, 17=NI1000 LG F, 18=10K Type2 NTC F, 19=10K Type3 NTC F, 20=20K NTC F, 21=3K NTC F, 22=PT1000 F, 23=NI1000 32F, 24=NI1000 70F"
  },
  {
   "type": "AO",
   "instance": 37,
   "name": "VAV_CO2_RANGE",
   "description": "Sets the range of the CO2 sensor used",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "VAV_HEATER_PRIORITY",
   "description": "Possibility to select heating priority for heating sources",
   "units": "",
   "access": "W",
   "states": "1=reheater, 2=perimeter, 3=simultaneous"
  },
  {
   "type": "BO",
   "instance": 69,
   "name": "VAV_DUAL_HEAT",
   "description": "Enable dual heating mode with repeater/perimeter and damper (no effect without damper)",
   "units": "",
   "access": "W",
   "states": "False=no, True=yes"
  },
  {
   "type": "BO",
   "instance": 66,
   "name": "VAV_OCCUPANCY_CONTACT_TYPE",
   "description": "Invert the I1 input signal if required",
   "units": "",
   "access": "W",
   "states": "False=normal, True=invert"
  },
  {
   "type": "BO",
   "instance": 67,
   "name": "VAV_WINDOW_CONTACT_TYPE",
   "description": "Invert the I2 input signal if required",
   "units": "",
   "access": "W",
   "states": "False=normal, True=invert"
  },
  {
   "type": "BO",
   "instance": 65,
   "name": "VAV_DAMPER_DIRECTION",
   "description": "Sets the damper opening direction",
   "units": "",
   "access": "W",
   "states": "False=CW, True=CCW"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "VAV_SPACE_TEMPERATURE_SOURCE",
   "description": "Choose the temperature source for control logic",
   "units": "",
   "access": "W",
   "states": "1=panel, 2=input, 3=network"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "VAV_CO2_SOURCE",
   "description": "Select the CO2 source for control logic",
   "units": "",
   "access": "W",
   "states": "1=panel, 2=input, 3=network"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "VAV_SETPOINT_OFFSET_SOURCE",
   "description": "Choose the setpoint offset source for control logic",
   "units": "",
   "access": "W",
   "states": "1=panel, 2=input, 3=network"
  },
  {
   "type": "AO",
   "instance": 29,
   "name": "VAV_MAX_FLOW_COOLING",
   "description": "Maximum airflow setpoint for cooling in the occupied state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 30,
   "name": "VAV_MIN_FLOW_COOLING",
   "description": "Minimum airflow setpoint for cooling in the occupied state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 31,
   "name": "VAV_MAX_FLOW_HEATING",
   "description": "Maximum airflow setpoint for heating in the occupied state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 32,
   "name": "VAV_MIN_FLOW_HEATING",
   "description": "Minimum airflow setpoint for heating in the occupied state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 33,
   "name": "VAV_MIN_FLOW_STANDBY",
   "description": "Airflow setpoint in the standby state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 34,
   "name": "VAV_MIN_FLOW_UNOCCUPIED",
   "description": "Airflow setpoint in the unoccupied state",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 35,
   "name": "VAV_FLOW_FAN_START",
   "description": "Airflow setpoint for a fan startup only",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 23,
   "name": "VAV_K_FACTOR_VALUE",
   "description": "Sets the K-Factor",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 36,
   "name": "VAV_MENU_PASSWORD",
   "description": "Non-volatile password protecting access to commissioning menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 64,
   "name": "VAV_PRESSURE_SENSOR_RESET_TRIGGER",
   "description": "Perform zeroing action on the built-in PI pressure transducer if there is",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "VAV_PRESSURE_SENSOR_VALUE",
   "description": "Actual differential pressure sensor-measured value from the built-in pressure input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 24,
   "name": "VAV_CALCULATED_DAMPER_POSITION",
   "description": "Actual damper opening level coming from the Rotary Actuator component",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "VAV_CALCULATED_FLOW",
   "description": "Actual calculated airflow based on the K-Factor value and differential pressure measure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "VAV_DAMPER_COMMAND",
   "description": "Set different damper command modes for calibration, balancing, or testing",
   "units": "",
   "access": "W",
   "states": "1=Auto/none (null), 2=Max flow, 3=Min flow, 4=User flow, 5=User position, 6=Full open, 7=Full close, 8=Calibrate"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "VAV_FAN_COMMAND",
   "description": "Set different fan command modes for testing",
   "units": "",
   "access": "W",
   "states": "1=Auto/none (null), 2=Max speed, 3=Min speed, 4=Stop"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "VAV_REHEATER_COMMAND",
   "description": "Set different reheater command modes for testing",
   "units": "",
   "access": "W",
   "states": "1=Auto/none (null), 2=Full open, 3=Full close"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "VAV_PERIMETER_COMMAND",
   "description": "Set different perimeter command modes for testing",
   "units": "",
   "access": "W",
   "states": "1=Auto/none (null), 2=Full open, 3=Full close"
  },
  {
   "type": "AO",
   "instance": 26,
   "name": "USER_DESIRED_DAMPER_POSITION",
   "description": "User-set damper opening level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 27,
   "name": "USER_DESIRED_FLOW",
   "description": "User-set airflow setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 28,
   "name": "USER_MEASURED_FLOW",
   "description": "Enter the airflow value measured by the hood for calibration",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "MAIN_MENU_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "MAIN_MENU_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "MAIN_MENU_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "MAIN_MENU_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "MAIN_MENU_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "MAIN_MENU_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "MAIN_MENU_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "MAIN_MENU_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "MAIN_MENU_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "MAIN_MENU_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "MAIN_MENU_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "MAIN_MENU_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "MAIN_MENU_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "MAIN_MENU_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, main menu menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "TEMPERATURE_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "TEMPERATURE_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "TEMPERATURE_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "TEMPERATURE_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "TEMPERATURE_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "TEMPERATURE_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "TEMPERATURE_NUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "TEMPERATURE_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "TEMPERATURE_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "TEMPERATURE_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "TEMPERATURE_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "TEMPERATURE_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "TEMPERATURE_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "TEMPERATURE_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "TEMPERATURE_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "TEMPERATURE_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, temperature menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "FAN_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "FAN_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "FAN_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "FAN_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "FAN_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "FAN_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "FANNUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "FAN_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "FAN_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "FAN_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "FAN_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "FAN_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "FAN_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "FAN_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "FAN_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "FAN_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, fan menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "LIGHT_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "LIGHT_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "LIGHT_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "LIGHT_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "LIGHT_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "LIGHT_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "LIGHTNUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "LIGHT_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "LIGHT_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "LIGHT_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "LIGHT_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "LIGHT_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "LIGHT_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "LIGHT_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "LIGHT_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "LIGHT_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, light menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "BLIND_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "BLIND_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "BLIND_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "BLIND_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "BLIND_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "BLIND_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "BLINDNUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "BLIND_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "BLIND_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "BLIND_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "BLIND_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "BLIND_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "BLIND_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "BLIND_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "BLIND_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "BLIND_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, blind menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "ALARMS_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "ALARMS_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "ALARMS_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "ALARMS_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "ALARMS_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "ALARMS_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "ALARMSNUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "ALARMS_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "ALARMS_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "ALARMS_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "ALARMS_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "ALARMS_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "ALARMS_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "ALARMS_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "ALARMS_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "ALARMS_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, alarms menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "SETTINGS_NUMERIC1:Present Value",
   "description": "User-defined numeric parameter 1, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "SETTINGS_NUMERIC2:Present Value",
   "description": "User-defined numeric parameter 2, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "SETTINGS_NUMERIC3:Present Value",
   "description": "User-defined numeric parameter 3, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "SETTINGS_NUMERIC4:Present Value",
   "description": "User-defined numeric parameter 4, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "SETTINGS_NUMERIC5:Present Value",
   "description": "User-defined numeric parameter 5, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "SETTINGS_NUMERIC6:Present Value",
   "description": "User-defined numeric parameter 6, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "SETTINGSNUMERIC7:Present Value",
   "description": "User-defined numeric parameter 7, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "SETTINGS_NUMERIC8:Present Value",
   "description": "User-defined numeric parameter 8, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "SETTINGS_BOOLEAN1:Present Value",
   "description": "User-defined boolean parameter 1, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "SETTINGS_BOOLEAN2:Present Value",
   "description": "User-defined boolean parameter 2, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "SETTINGS_BOOLEAN3:Present Value",
   "description": "User-defined boolean parameter 3, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "SETTINGS_BOOLEAN4:Present Value",
   "description": "User-defined boolean parameter 4, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "SETTINGS_BOOLEAN5:Present Value",
   "description": "User-defined boolean parameter 5, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "SETTINGS_BOOLEAN6:Present Value",
   "description": "User-defined boolean parameter 6, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "SETTINGS_BOOLEAN7:Present Value",
   "description": "User-defined boolean parameter 7, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "SETTINGS_BOOLEAN8:Present Value",
   "description": "User-defined boolean parameter 8, settings menu",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/isma-controlli/control-point-room-panel",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}