 "manufacturer": "iSMA CONTROLLI",
 "manufacturer_slug": "isma-controlli",
 "model": "Touch Point room panel",
 "model_slug": "touch-point-room-panel",
 "aliases": [
  "Touch Point",
  "iSMA Touch Point",
  "Touch Point VAV",
  "Touch Point Software V1.3"
 ],
 "equipment_type": "Room panel (thermostat display)",
 "applies_to": "iSMA CONTROLLI Touch Point touch-button room panels (software manual V1.3), including the Touch Point VAV series.",
 "summary": "The Touch Point room panel exposes built-in temperature, humidity and CO2 readings, a temperature setpoint with offset, fan mode and speed, occupancy mode and status, a CO2 alarm, the navigation LED colour and the display, keypad and buzzer settings as BACnet objects. Most objects are panel configuration; the room values and setpoint are what a BMS normally maps.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Touch Point Software manual V1.3",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "The manual table mixes objects and object properties. Only Present Value rows are listed; other property rows (offsets, filters, limits, visibility, Device-object properties such as BACNET_DEVICE_ID and BAUD_RATE) are left out.",
  "Rows with a blank access cell (mostly BO display switches) are taken as writable.",
  "Fan objects (MV 0-2, BO 58, BO 60) are not available on the Touch Point VAV series."
 ],
 "source": {
  "title": "Touch Point Software User Manual V1.3 - List of BACnet Objects",
  "doc_number": null,
  "revision_date": "V1.3",
  "url": "https://icdocs.ismacontrolli.com/touch-point-software/V1.3/list-of-bacnet-obejcts"
 },
 "integration": {
  "summary": "Read the room temperature (AI 4), humidity (AI 5), CO2 (AI 6) and effective setpoint (AI 3); write the setpoint (AV 56), fan mode (MV 1) and occupancy mode (MV 4) from the BMS. BO 62 switches occupancy between local and BMS mode; BI 0 is the CO2 alarm.",
  "minimum_points": [
   {
    "ref": "MV 4",
    "name": "OCCUPANCY_MODE",
    "why": "Occupancy mode"
   },
   {
    "ref": "AV 56",
    "name": "SETPOINT_VALUE",
    "why": "Temperature setpoint"
   },
   {
    "ref": "MV 1",
    "name": "FAN_MODE",
    "why": "Fan mode"
   },
   {
    "ref": "AI 4",
    "name": "TEMPERATURE_SENSOR",
    "why": "Room temperature"
   },
   {
    "ref": "AI 3",
    "name": "EFFECTIVE_SETPOINT",
    "why": "Effective setpoint (setpoint plus offset)"
   },
   {
    "ref": "MV 3",
    "name": "OCCUPANCY_CURRENT_STATUS",
    "why": "Current occupancy status"
   },
   {
    "ref": "AI 5",
    "name": "HUMIDITY_SENSOR",
    "why": "Room humidity"
   },
   {
    "ref": "AI 6",
    "name": "CO2_SENSOR",
    "why": "Room CO2"
   },
   {
    "ref": "BI 0",
    "name": "ALARM_STATUS",
    "why": "CO2 alarm status"
   }
  ],
  "enable": "BO 62 OCCUPANCY_CONFIG_LOCAL_MODE selects local or BMS occupancy mode.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance and baud rate are Device-object properties (BACNET_DEVICE_ID default 0xFFFFFFFF, BAUD_RATE default 11520 = 115200 bps)."
  ],
  "gotchas": [
   "Setpoint objects use tenths in the defaults (DEFAULT_SETPOINT 210 = 21.0 °C); check scaling before writing.",
   "Configuration objects are stored in panel memory; avoid cyclic writes."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "LIVE_TIME",
   "description": "Uptime of the panel in seconds",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "SENSORS",
   "description": "Informs about built-in sensors",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "BACKLIGHT_LCD",
   "description": "Actual display illumination value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "BACKLIGHT_KEYPAD",
   "description": "Actual keypad illumination value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "BUZZER_ACTIVE",
   "description": "Activates (1) or deactivates (0) a buzzer; default 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "LCD_BACKLIGHT_ACTIVE",
   "description": "Switches the LCD background illumination on (1); default 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "KEYPAD_BACKLIGHT_ACTIVE",
   "description": "Switches the keypad background illumination on (1); default 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "CO2_ALARM_LCD",
   "description": "Switches on the function of LCD background illumination flashing when CO2 alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "CO2_ALARM_BUZZER",
   "description": "Switches on a buzzer when the CO2 alarm occurs",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 63,
   "name": "CO2_ALARM_CONFIRM",
   "description": "Enable confirmation of the CO2 alarm with any button of the panel",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "PANEL_OFF",
   "description": "Switches the panel off (1); default 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 12,
   "name": "KEYPAD_OFF",
   "description": "Switches the panel keypad off (1); default 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "BACKLIGHT_LCD_ACTIVE",
   "description": "Contains a value of the LCD display illumination in the active mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "BACKLIGHT_LCD_IDLE",
   "description": "Contains a value of the LCD display illumination in the idle mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "BACKLIGHT_LCD_STANDBY",
   "description": "Contains a value of the LCD display illumination in the standby mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "BACKLIGHT_LCD_TIME_TO_IDLE",
   "description": "Sets the time after which the LCD display goes from the active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "BACKLIGHT_LCD_TIME_TO_STANDBY",
   "description": "Sets the time after which the LCD display goes from the idle",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "BACKLIGHT_KEYPAD_ACTIVE",
   "description": "Contains a value of the keypad illumination in the active mode; default 10",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "BACKLIGHT_KEYPAD_IDLE",
   "description": "Contains a value of the keypad illumination in the idle mode; default 40",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "BACKLIGHT_KEYPAD_STANDBY",
   "description": "Contains a value of the keypad illumination in the standby mode; default 60",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "BACKLIGHT_KEYPAD_TIME_TO_IDLE",
   "description": "Sets the time after which the keypad goes from the active mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "BACKLIGHT_KEYPAD_TIME_TO_STANDBY",
   "description": "Sets the time after which the keypad goes from the idle mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "REFRESH_TIME",
   "description": "Sets the duration of the display time of particular parameters; default 5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 22,
   "name": "ECO",
   "description": "Switches on an ECO LED",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "EXIT_EDIT_TIME",
   "description": "Sets the time after which edition of any editable parameter is finished",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 19,
   "name": "CO2_SETPOINT_FOR_ALARM",
   "description": "CO2 alarm setpoint; default 1500",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "CO2_HYSTERESIS_FOR_ALARM",
   "description": "CO2 alarm hysteresis; default 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "ALARM_STATUS",
   "description": "CO2 current alarm status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "NAVIGATIONAL_LED_MODE",
   "description": "Sets a mode of the navigational LED; default 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "NAVIGATIONAL_LED_BRIGHTNESS",
   "description": "Navigational LED brightness; default 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 23,
   "name": "NAVIGATIONAL_LED_RED",
   "description": "Navigational LED color - red component intensity; default 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 24,
   "name": "NAVIGATIONAL_LED_GREEN",
   "description": "Navigational LED color - green component intensity; default 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "NAVIGATIONAL_LED_BLUE",
   "description": "Navigational LED color - blue component intensity; default 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "TEMPERATURE_SENSOR",
   "description": "Actual temperature sensor value with offset",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "HUMIDITY_SENSOR",
   "description": "Actual humidity sensor value with offset",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "CO2_SENSOR",
   "description": "Actual CO2 sensor value with offset",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 27,
   "name": "BUZZER_VOLUME",
   "description": "Buzzer volume (%); default 50",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 28,
   "name": "BUZZER_FREQUENCY",
   "description": "Buzzer frequency (Hz); default 400",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "SETPOINT_VALUE",
   "description": "Temperature setpoint value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "EFFECTIVE_SETPOINT",
   "description": "Sum of setpoint and offset values",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "DEFAULT_SETPOINT",
   "description": "Default temperature setpoint; default 210",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "OFFSET_SETPOINT",
   "description": "Temperature offset for setpoint; default 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "OFFSET_RANGE",
   "description": "Limits offset value; default 30",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 55,
   "name": "OPERATING_MODE",
   "description": "Sets the operating mode of the temperature setpoint configuration",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 56,
   "name": "SETPOINT_DISPLAY",
   "description": "Configures the temperature setpoint display",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "FAN_CURRENT_SPEED",
   "description": "Not available for the Touch Point VAV series; default 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "FAN_MODE",
   "description": "Not available for the Touch Point VAV series; default 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "FAN_TYPE",
   "description": "Not available for the Touch Point VAV series",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 58,
   "name": "FAN_PART_EDITABLE",
   "description": "Not available for the Touch Point VAV series",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 60,
   "name": "FAN_CONFIG_LOCAL_MODE",
   "description": "Not available for the Touch Point VAV series",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "OCCUPANCY_CURRENT_STATUS",
   "description": "Occupancy status",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "OCCUPANCY_MODE",
   "description": "Occupancy mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 62,
   "name": "OCCUPANCY_CONFIG_LOCAL_MODE",
   "description": "Local/BMS mode",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/isma-controlli/touch-point-room-panel",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}