- IPS 4000 pumping system controller - variable secondary
Pump system controller (variable secondary) · BACnet points list
Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary BACnet points list
Updated 11 November 2026
The IPS 4000 runs a group of variable-speed pumps. The variable secondary version has no chiller/boiler points; its BACnet list covers start/stop, pump Hand/Off/Auto commands, hand speeds, zone setpoints and values, pump speed, power, energy, RPM, head and flow, run hours, and no-flow and drive alarms.
This page lists 292 BACnet objects for the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary — 74 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.
- Manufacturer
- Armstrong Fluid Technology
- Model
- IPS 4000 pumping system controller - variable secondary
- Equipment
- Pump system controller (variable secondary)
- Equipment type
- VFDs & pumps
- BACnet objects
- 292 (74 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Communication interface ver 2.1.0
- Also known as
- IPS 4000, IPS4000, IPS 4000 secondary, Integrated Pumping System 4000, 90.9761
Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.
BMS integration notes: Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary
Start and stop the IPS 4000 with BV 1 Remote Start, write the zone setpoints (AV 1-16) and read BI 110 IPS On Status, the active zone value, system flow and head, and BI 1 General Alarm. Reset alarms with BV 32. The BMS can also put each pump in Hand, Off or Auto (BV 2-25), set hand speeds and write zone values (bas Zone pv AVs).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Remote Start | Start/stop from the BMS (1 = start) | Write |
| AV 1 | Zone 1 SP | Zone 1 control setpoint | Write |
| BV 32 | Alarm Reset | Reset alarms | Write |
| BI 110 | IPS On Status | Pumping system on status | Read |
| AI 3 | Active Zone PV | Value of the zone in control | Read |
| AI 147 | System Flow | Total system flow | Read |
| AI 136 | System Head | Total system head | Read |
| BI 2 | Pump Alarm | Any pump alarm | Read |
| BI 1 | General Alarm | Any active alarm | Read |
Enable & remote start
BV 1 Remote Start (0 = Stop, 1 = Start). The Set Pump Hand/Off/Auto BVs are momentary commands that change one pump's mode.
Sensors & values from the BMS
The bas Zone 1-16 pv AVs (48-63) are writable, so the BMS can supply zone values. The data-points sheet does not say how the controller chooses between BMS and wired values.
Network setup
- The sheet lists BACnet TCP/IP and BACnet MS/TP. For BACnet IP use UDP port 47808 (0xBAC0).
- The device instance and MS/TP settings are not given in the sheet.
Watch out for
- Set Pump Hand/Off/Auto BVs are momentary: write 1 to change the mode, and read the pump mode BIs to confirm it.
- Design flow/head, BEP and dead-band AVs are commissioning settings; don't write them cyclically.
- Units for pressure, temperature and flow follow the controller's unit setting.
Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | Remote Start | Write | 0=Stop, 1=Start | ||
| BV | 2 | Set Pump 1 Hand | Momentary command | Write | 1=Hand | |
| BV | 3 | Set Pump 1 Off | Momentary command | Write | 1=Off | |
| BV | 4 | Set Pump 1 Auto | Momentary command | Write | 1=Auto | |
| BV | 5 | Set Pump 2 Hand | Momentary command | Write | 1=Hand | |
| BV | 6 | Set Pump 2 Off | Momentary command | Write | 1=Off | |
| BV | 7 | Set Pump 2 Auto | Momentary command | Write | 1=Auto | |
| BV | 8 | Set Pump 3 Hand | Momentary command | Write | 1=Hand | |
| BV | 9 | Set Pump 3 Off | Momentary command | Write | 1=Off | |
| BV | 10 | Set Pump 3 Auto | Momentary command | Write | 1=Auto | |
| BV | 11 | Set Pump 4 Hand | Momentary command | Write | 1=Hand | |
| BV | 12 | Set Pump 4 Off | Momentary command | Write | 1=Off | |
| BV | 13 | Set Pump 4 Auto | Momentary command | Write | 1=Auto | |
| BV | 14 | Set Pump 5 Hand | Momentary command | Write | 1=Hand | |
| BV | 15 | Set Pump 5 Off | Momentary command | Write | 1=Off | |
| BV | 16 | Set Pump 5 Auto | Momentary command | Write | 1=Auto | |
| BV | 17 | Set Pump 6 Hand | Momentary command | Write | 1=Hand | |
| BV | 18 | Set Pump 6 Off | Momentary command | Write | 1=Off | |
| BV | 19 | Set Pump 6 Auto | Momentary command | Write | 1=Auto | |
| BV | 20 | Set Pump 7 Hand | Momentary command | Write | 1=Hand | |
| BV | 21 | Set Pump 7 Off | Momentary command | Write | 1=Off | |
| BV | 22 | Set Pump 7 Auto | Momentary command | Write | 1=Auto | |
| BV | 23 | Set Pump 8 Hand | Momentary command | Write | 1=Hand | |
| BV | 24 | Set Pump 8 Off | Momentary command | Write | 1=Off | |
| BV | 25 | Set Pump 8 Auto | Momentary command | Write | 1=Auto | |
| BVmin | 32 | Alarm Reset | Write | 1=Reset | ||
| BImin | 1 | General Alarm | Read | 0=Ok, 1=Alarm | ||
| BImin | 2 | Pump Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3 | Sensor Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 4 | Pump 1 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 5 | Pump 1 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 6 | Pump 1 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 7 | Pump 2 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 8 | Pump 2 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 9 | Pump 2 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 10 | Pump 3 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 11 | Pump 3 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 12 | Pump 3 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 13 | Pump 4 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 14 | Pump 4 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 15 | Pump 4 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 16 | Pump 5 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 17 | Pump 5 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 18 | Pump 5 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 19 | Pump 6 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 20 | Pump 6 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 21 | Pump 6 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 22 | Pump 7 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 23 | Pump 7 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 24 | Pump 7 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 25 | Pump 8 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 26 | Pump 8 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 27 | Pump 8 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 34 | Pump 1 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 35 | Pump 2 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 36 | Pump 3 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 37 | Pump 4 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 38 | Pump 5 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 39 | Pump 6 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 40 | Pump 7 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 41 | Pump 8 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 44 | Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 47 | All Zones DP/Temperature Transmitters Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 48 | Zone 1 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 49 | Zone 2 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 50 | Zone 3 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 51 | Zone 4 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 52 | Zone 5 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 53 | Zone 6 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 54 | Zone 7 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 55 | Zone 8 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 56 | Zone 9 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 57 | Zone 10 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 58 | Zone 11 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 59 | Zone 12 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 60 | Zone 13 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 61 | Zone 14 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 62 | Zone 15 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 63 | Zone 16 DP/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 70 | Pump 1 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 71 | Pump 2 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 72 | Pump 3 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 73 | Pump 4 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 74 | Pump 5 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 75 | Pump 6 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 76 | Pump 7 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 77 | Pump 8 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 80 | Pump 1 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 81 | Pump 2 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 82 | Pump 3 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 83 | Pump 4 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 84 | Pump 5 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 85 | Pump 6 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 86 | Pump 7 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 87 | Pump 8 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 90 | Pump 1 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 91 | Pump 2 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 92 | Pump 3 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 93 | Pump 4 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 94 | Pump 5 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 95 | Pump 6 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 96 | Pump 7 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 97 | Pump 8 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 100 | Pump 1 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 101 | Pump 2 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 102 | Pump 3 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 103 | Pump 4 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 104 | Pump 5 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 105 | Pump 6 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 106 | Pump 7 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 107 | Pump 8 No Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BImin | 110 | IPS On Status | Read | 0=Off, 1=On | ||
| BI | 111 | PLC Board High Temperature Alarm | Read | 0=Ok, 1=Alarm | ||
| AVmin | 1 | Zone 1 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 2 | Zone 2 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 3 | Zone 3 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 4 | Zone 4 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 5 | Zone 5 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 6 | Zone 6 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 7 | Zone 7 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 8 | Zone 8 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 9 | Zone 9 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 10 | Zone 10 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 11 | Zone 11 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 12 | Zone 12 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 13 | Zone 13 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 14 | Zone 14 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 15 | Zone 15 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 16 | Zone 16 SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 21 | Pump 1 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 22 | Pump 2 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 23 | Pump 3 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 24 | Pump 4 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 25 | Pump 5 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 26 | Pump 6 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 27 | Pump 7 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 28 | Pump 8 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 31 | Max Valve Opening | Range 0.0 to 100.0 | % | Write | |
| AV | 32 | Design Flow | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 33 | Design Head | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 34 | Zero Flow Head | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 35 | Flow BEP | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 36 | Head BEP | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 37 | Dead Band(K) | Range 0-0.5 | Write | ||
| AV | 38 | Sensor Adjust | Range 0 to 100.0% | Write | ||
| AV | 48 | BAS Zone 1 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 49 | BAS Zone 2 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 50 | BAS Zone 3 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 51 | BAS Zone 4 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 52 | BAS Zone 5 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 53 | BAS Zone 6 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 54 | BAS Zone 7 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 55 | BAS Zone 8 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 56 | BAS Zone 9 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 57 | BAS Zone 10 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 58 | BAS Zone 11 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 59 | BAS Zone 12 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 60 | BAS Zone 13 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 61 | BAS Zone 14 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 62 | BAS Zone 15 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AV | 63 | BAS Zone 16 PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Write | |
| AI | 1 | Active Zone | Range 0 to 16 | Read | ||
| AI | 2 | Active Zone Error | Range -999.9 to 999.9 | Read | ||
| AImin | 3 | Active Zone PV | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 4 | Active Zone SP | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 5 | Zone 1 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 6 | Zone 2 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 7 | Zone 3 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 8 | Zone 4 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 9 | Zone 5 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 10 | Zone 6 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 11 | Zone 7 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 12 | Zone 8 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 13 | Zone 9 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 14 | Zone 10 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 15 | Zone 11 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 16 | Zone 12 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 17 | Zone 13 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 18 | Zone 14 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 19 | Zone 15 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 20 | Zone 16 Value | Range 0.0 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 25 | Zone 1 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 26 | Zone 2 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 27 | Zone 3 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 28 | Zone 4 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 29 | Zone 5 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 30 | Zone 6 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 31 | Zone 7 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 32 | Zone 8 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 33 | Zone 9 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 34 | Zone 10 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 35 | Zone 11 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 36 | Zone 12 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 37 | Zone 13 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 38 | Zone 14 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 39 | Zone 15 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 40 | Zone 16 Error | Range -999.9 to 999.9 | psi, ft, kPa, m, °f or °c | Read | |
| AI | 45 | Pump 1 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 46 | Pump 2 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 47 | Pump 3 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 48 | Pump 4 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 49 | Pump 5 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 50 | Pump 6 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 51 | Pump 7 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 52 | Pump 8 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 55 | Temperature Sensor PV | Range 0.0 to 212.0 | °F or °C | Read | |
| AI | 56 | Pump 1 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 57 | Pump 1 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 58 | Pump 1 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 59 | Pump 1 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 60 | Pump 1 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 61 | Pump 1 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 62 | Pump 1 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 63 | Pump 1 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 64 | Pump 2 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 65 | Pump 2 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 66 | Pump 2 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 67 | Pump 2 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 68 | Pump 2 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 69 | Pump 2 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 70 | Pump 2 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 71 | Pump 2 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 72 | Pump 3 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 73 | Pump 3 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 74 | Pump 3 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 75 | Pump 3 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 76 | Pump 3 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 77 | Pump 3 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 78 | Pump 3 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 79 | Pump 3 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 80 | Pump 4 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 81 | Pump 4 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 82 | Pump 4 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 83 | Pump 4 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 84 | Pump 4 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 85 | Pump 4 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 86 | Pump 4 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 87 | Pump 4 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 88 | Pump 5 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 89 | Pump 5 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 90 | Pump 5 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 91 | Pump 5 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 92 | Pump 5 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 93 | Pump 5 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 94 | Pump 5 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 95 | Pump 5 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 96 | Pump 6 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 97 | Pump 6 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 98 | Pump 6 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 99 | Pump 6 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 100 | Pump 6 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 101 | Pump 6 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 102 | Pump 6 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 103 | Pump 6 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 104 | Pump 7 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 105 | Pump 7 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 106 | Pump 7 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 107 | Pump 7 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 108 | Pump 7 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 109 | Pump 7 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 110 | Pump 7 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 111 | Pump 7 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 112 | Pump 8 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 113 | Pump 8 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 114 | Pump 8 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 115 | Pump 8 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 116 | Pump 8 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 117 | Pump 8 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 118 | Pump 8 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 119 | Pump 8 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AImin | 136 | System Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 137 | Pump 1 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 138 | Pump 2 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 139 | Pump 3 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 140 | Pump 4 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 141 | Pump 5 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 142 | Pump 6 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 143 | Pump 7 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AI | 144 | Pump 8 Head | Range 0.0 to 3276.7 | ft, psi, kPa, m, bar | Read | |
| AImin | 147 | System Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 148 | Pump 1 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 149 | Pump 2 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 150 | Pump 3 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 151 | Pump 4 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 152 | Pump 5 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 153 | Pump 6 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 154 | Pump 7 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 155 | Pump 8 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 160 | Number of Pumps Running in Auto | Range 1 to 8 | Read | ||
| AI | 161 | Lead Pump ID | Range 1 to 8 | Read | ||
| AI | 162 | Number Of Pumps Configured | Range 1 to 8 | Read | ||
| AI | 164 | Lead Pump Switch Time | Range 0-32767 | Day/Hr | Read |
No points match these filters.
Object ID lookup: Armstrong Fluid Technology IPS 4000 Variable Secondary point IDs by name
BV1Remote StartBV2Set Pump 1 HandBV3Set Pump 1 OffBV4Set Pump 1 AutoBV5Set Pump 2 HandBV6Set Pump 2 OffBV7Set Pump 2 AutoBV8Set Pump 3 HandBV9Set Pump 3 OffBV10Set Pump 3 AutoBV11Set Pump 4 HandBV12Set Pump 4 OffBV13Set Pump 4 AutoBV14Set Pump 5 HandBV15Set Pump 5 OffBV16Set Pump 5 AutoBV17Set Pump 6 HandBV18Set Pump 6 OffBV19Set Pump 6 AutoBV20Set Pump 7 HandBV21Set Pump 7 OffBV22Set Pump 7 AutoBV23Set Pump 8 HandBV24Set Pump 8 OffBV25Set Pump 8 AutoBV32Alarm ResetBI1General AlarmBI2Pump AlarmBI3Sensor AlarmBI4Pump 1 in Hand modeBI5Pump 1 in Off modeBI6Pump 1 in Auto modeBI7Pump 2 in Hand modeBI8Pump 2 in Off modeBI9Pump 2 in Auto modeBI10Pump 3 in Hand modeBI11Pump 3 in Off modeBI12Pump 3 in Auto modeBI13Pump 4 in Hand modeBI14Pump 4 in Off modeBI15Pump 4 in Auto modeBI16Pump 5 in Hand modeBI17Pump 5 in Off modeBI18Pump 5 in Auto modeBI19Pump 6 in Hand modeBI20Pump 6 in Off modeBI21Pump 6 in Auto modeBI22Pump 7 in Hand modeBI23Pump 7 in Off modeBI24Pump 7 in Auto modeBI25Pump 8 in Hand modeBI26Pump 8 in Off modeBI27Pump 8 in Auto modeBI34Pump 1 Run FeedbackBI35Pump 2 Run FeedbackBI36Pump 3 Run FeedbackBI37Pump 4 Run FeedbackBI38Pump 5 Run FeedbackBI39Pump 6 Run FeedbackBI40Pump 7 Run FeedbackBI41Pump 8 Run FeedbackBI44Temperature Transmitter FailedBI47All Zones DP/Temperature Transmitters FailedBI48Zone 1 DP/Temperature Transmitter FailedBI49Zone 2 DP/Temperature Transmitter FailedBI50Zone 3 DP/Temperature Transmitter FailedBI51Zone 4 DP/Temperature Transmitter FailedBI52Zone 5 DP/Temperature Transmitter FailedBI53Zone 6 DP/Temperature Transmitter FailedBI54Zone 7 DP/Temperature Transmitter FailedBI55Zone 8 DP/Temperature Transmitter FailedBI56Zone 9 DP/Temperature Transmitter FailedBI57Zone 10 DP/Temperature Transmitter FailedBI58Zone 11 DP/Temperature Transmitter FailedBI59Zone 12 DP/Temperature Transmitter FailedBI60Zone 13 DP/Temperature Transmitter FailedBI61Zone 14 DP/Temperature Transmitter FailedBI62Zone 15 DP/Temperature Transmitter FailedBI63Zone 16 DP/Temperature Transmitter FailedBI70Pump 1 AlarmBI71Pump 2 AlarmBI72Pump 3 AlarmBI73Pump 4 AlarmBI74Pump 5 AlarmBI75Pump 6 AlarmBI76Pump 7 AlarmBI77Pump 8 AlarmBI80Pump 1 Run feedback AlarmBI81Pump 2 Run feedback AlarmBI82Pump 3 Run feedback AlarmBI83Pump 4 Run feedback AlarmBI84Pump 5 Run feedback AlarmBI85Pump 6 Run feedback AlarmBI86Pump 7 Run feedback AlarmBI87Pump 8 Run feedback AlarmBI90Pump 1 Drive FaultBI91Pump 2 Drive FaultBI92Pump 3 Drive FaultBI93Pump 4 Drive FaultBI94Pump 5 Drive FaultBI95Pump 6 Drive FaultBI96Pump 7 Drive FaultBI97Pump 8 Drive FaultBI100Pump 1 No Flow AlarmBI101Pump 2 No Flow AlarmBI102Pump 3 No Flow AlarmBI103Pump 4 No Flow AlarmBI104Pump 5 No Flow AlarmBI105Pump 6 No Flow AlarmBI106Pump 7 No Flow AlarmBI107Pump 8 No Flow AlarmBI110IPS On StatusBI111PLC Board High Temperature AlarmAV1Zone 1 SPAV2Zone 2 SPAV3Zone 3 SPAV4Zone 4 SPAV5Zone 5 SPAV6Zone 6 SPAV7Zone 7 SPAV8Zone 8 SPAV9Zone 9 SPAV10Zone 10 SPAV11Zone 11 SPAV12Zone 12 SPAV13Zone 13 SPAV14Zone 14 SPAV15Zone 15 SPAV16Zone 16 SPAV21Pump 1 Hand SpeedAV22Pump 2 Hand SpeedAV23Pump 3 Hand SpeedAV24Pump 4 Hand SpeedAV25Pump 5 Hand SpeedAV26Pump 6 Hand SpeedAV27Pump 7 Hand SpeedAV28Pump 8 Hand SpeedAV31Max Valve OpeningAV32Design FlowAV33Design HeadAV34Zero Flow HeadAV35Flow BEPAV36Head BEPAV37Dead Band(K)AV38Sensor AdjustAV48BAS Zone 1 PVAV49BAS Zone 2 PVAV50BAS Zone 3 PVAV51BAS Zone 4 PVAV52BAS Zone 5 PVAV53BAS Zone 6 PVAV54BAS Zone 7 PVAV55BAS Zone 8 PVAV56BAS Zone 9 PVAV57BAS Zone 10 PVAV58BAS Zone 11 PVAV59BAS Zone 12 PVAV60BAS Zone 13 PVAV61BAS Zone 14 PVAV62BAS Zone 15 PVAV63BAS Zone 16 PVAI1Active ZoneAI2Active Zone ErrorAI3Active Zone PVAI4Active Zone SPAI5Zone 1 ValueAI6Zone 2 ValueAI7Zone 3 ValueAI8Zone 4 ValueAI9Zone 5 ValueAI10Zone 6 ValueAI11Zone 7 ValueAI12Zone 8 ValueAI13Zone 9 ValueAI14Zone 10 ValueAI15Zone 11 ValueAI16Zone 12 ValueAI17Zone 13 ValueAI18Zone 14 ValueAI19Zone 15 ValueAI20Zone 16 ValueAI25Zone 1 ErrorAI26Zone 2 ErrorAI27Zone 3 ErrorAI28Zone 4 ErrorAI29Zone 5 ErrorAI30Zone 6 ErrorAI31Zone 7 ErrorAI32Zone 8 ErrorAI33Zone 9 ErrorAI34Zone 10 ErrorAI35Zone 11 ErrorAI36Zone 12 ErrorAI37Zone 13 ErrorAI38Zone 14 ErrorAI39Zone 15 ErrorAI40Zone 16 ErrorAI45Pump 1 SpeedAI46Pump 2 SpeedAI47Pump 3 SpeedAI48Pump 4 SpeedAI49Pump 5 SpeedAI50Pump 6 SpeedAI51Pump 7 SpeedAI52Pump 8 SpeedAI55Temperature Sensor PVAI56Pump 1 Drive AmpAI57Pump 1 Drive Volt ACAI58Pump 1 Drive PowerAI59Pump 1 Drive KWHAI60Pump 1 Drive RPMAI61Pump 1 Drive Run HoursAI62Pump 1 Actual Run HoursAI63Pump 1 Drive Speed FeedbackAI64Pump 2 Drive AmpAI65Pump 2 Drive Volt ACAI66Pump 2 Drive PowerAI67Pump 2 Drive KWHAI68Pump 2 Drive RPMAI69Pump 2 Drive Run HoursAI70Pump 2 Actual Run HoursAI71Pump 2 Drive Speed FeedbackAI72Pump 3 Drive AmpAI73Pump 3 Drive Volt ACAI74Pump 3 Drive PowerAI75Pump 3 Drive KWHAI76Pump 3 Drive RPMAI77Pump 3 Drive Run HoursAI78Pump 3 Actual Run HoursAI79Pump 3 Drive Speed FeedbackAI80Pump 4 Drive AmpAI81Pump 4 Drive Volt ACAI82Pump 4 Drive PowerAI83Pump 4 Drive KWHAI84Pump 4 Drive RPMAI85Pump 4 Drive Run HoursAI86Pump 4 Actual Run HoursAI87Pump 4 Drive Speed FeedbackAI88Pump 5 Drive AmpAI89Pump 5 Drive Volt ACAI90Pump 5 Drive PowerAI91Pump 5 Drive KWHAI92Pump 5 Drive RPMAI93Pump 5 Drive Run HoursAI94Pump 5 Actual Run HoursAI95Pump 5 Drive Speed FeedbackAI96Pump 6 Drive AmpAI97Pump 6 Drive Volt ACAI98Pump 6 Drive PowerAI99Pump 6 Drive KWHAI100Pump 6 Drive RPMAI101Pump 6 Drive Run HoursAI102Pump 6 Actual Run HoursAI103Pump 6 Drive Speed FeedbackAI104Pump 7 Drive AmpAI105Pump 7 Drive Volt ACAI106Pump 7 Drive PowerAI107Pump 7 Drive KWHAI108Pump 7 Drive RPMAI109Pump 7 Drive Run HoursAI110Pump 7 Actual Run HoursAI111Pump 7 Drive Speed FeedbackAI112Pump 8 Drive AmpAI113Pump 8 Drive Volt ACAI114Pump 8 Drive PowerAI115Pump 8 Drive KWHAI116Pump 8 Drive RPMAI117Pump 8 Drive Run HoursAI118Pump 8 Actual Run HoursAI119Pump 8 Drive Speed FeedbackAI136System HeadAI137Pump 1 HeadAI138Pump 2 HeadAI139Pump 3 HeadAI140Pump 4 HeadAI141Pump 5 HeadAI142Pump 6 HeadAI143Pump 7 HeadAI144Pump 8 HeadAI147System FlowAI148Pump 1 FlowAI149Pump 2 FlowAI150Pump 3 FlowAI151Pump 4 FlowAI152Pump 5 FlowAI153Pump 6 FlowAI154Pump 7 FlowAI155Pump 8 FlowAI160Number of Pumps Running in AutoAI161Lead Pump IDAI162Number Of Pumps ConfiguredAI164Lead Pump Switch Time
Integration notes
- 121 rows printed as Reserved are left out.
- The cover prints File No 90.761; the file name on Armstrong's site is 90-9761.
- Analog descriptions give the scaled range from the Represent column; the PDF also prints a raw integer range.
- This list is for communication interface ver 2.1.0. Older IPS 4000 controllers (interface ver 1.0.0, Data Points 90.976, and the legacy 90.972) have their own data-point sheets; check which one matches the controller.
- The PDF table is on pages 14-23.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IPS 4000 pumping system controller - variable secondary and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary
How many BACnet points does the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary have?
This list has 292 BACnet objects: 131 analog inputs, 48 analog values, 87 binary inputs, 26 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary BACnet points are writable?
74 of the 292 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary BACnet documentation?
The source is IPS 4000 Integrated pumping system for variable secondary application, Data points (communication interface ver-2.1.0) (90.761 (file 90-9761)), revision 2020-12-07, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-9761_ips4000_secondary_bas-_ver-2-1-0_datapoints.pdf.
What are the minimum BACnet points to integrate the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary?
Start with BV 1 Remote Start (Start/stop from the BMS (1 = start)); AV 1 Zone 1 SP (Zone 1 control setpoint); BV 32 Alarm Reset (Reset alarms); BI 110 IPS On Status (Pumping system on status); AI 3 Active Zone PV (Value of the zone in control); AI 147 System Flow (Total system flow); AI 136 System Head (Total system head); BI 2 Pump Alarm (Any pump alarm); BI 1 General Alarm (Any active alarm).
How do I enable BMS control of the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary?
BV 1 Remote Start (0 = Stop, 1 = Start). The Set Pump Hand/Off/Auto BVs are momentary commands that change one pump's mode.
Can the BMS supply sensor values to the Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary?
The bas Zone 1-16 pv AVs (48-63) are writable, so the BMS can supply zone values. The data-points sheet does not say how the controller chooses between BMS and wired values.
How do I check these points on the real IPS 4000 pumping system controller - variable secondary?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Armstrong Fluid Technology BACnet points lists
- Cooling tower and condenser pump plant controller
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)
Armstrong Design Envelope Integrated Tower Controller for the condenser water side: up to 5 cooling towers (fans, inlet/outlet isolation valves) and 5 condenser water pumps.
Also known as: ITC 9521, ITC9521, Design Envelope ITC, Integrated Tower Controller, 82.21 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W10 chiller plant controller (water-cooled)
Armstrong EE-W10 water-cooled chilled water plant controls; the object list covers up to 3 chillers, 3 chilled water pumps, 3 condenser water pumps and 3 towers.
Also known as: EE-W10, EE-W 10, Armstrong EE-W10, 90.7651 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W20 chiller plant controller (water-cooled)
Armstrong EE-W20 water-cooled chilled water plant controls; the object list covers up to 5 chillers, 10 chilled water pumps, 10 condenser water pumps, 5 towers and 5 control zones.
Also known as: EE-W20, EE-W 20, Armstrong EE-W20, 90.7661 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology IPC 9521 chilled water plant controller
Armstrong IPC 9521 water-cooled chilled water plant controls (legacy product); the object list covers up to 5 chillers, 5 chilled and 5 condenser water pumps (A and B sides), 5 towers and 5 zones.
Also known as: IPC 9521, IPC9521, Armstrong IPC 9521, 90.874 - Pump system controller (variable primary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary
Armstrong IPS 4000 controllers set up for variable primary pumping: up to 8 pumps, 16 control zones and 8 chillers or boilers with flow and differential pressure limits.
Also known as: IPS 4000, IPS4000, IPS 4000 primary, Integrated Pumping System 4000, 90.9751 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A10 chiller plant controller
Armstrong SE-A10 chilled water plant controls with no condenser water side; the object list covers up to 3 chillers and 3 chilled water pumps.
Also known as: SE-A10, SE-A 10, Armstrong SE-A10, 90.7671 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A20 chiller plant controller
Armstrong SE-A20 chilled water plant controls with no condenser water side; the object list covers up to 5 chillers, 10 chilled water pumps and 5 control zones.
Also known as: SE-A20, SE-A 20, Armstrong SE-A20, 90.7681
Source: IPS 4000 Integrated pumping system for variable secondary application, Data points (communication interface ver-2.1.0) · 90.761 (file 90-9761) · rev. 2020-12-07. Object names, instances and units are reproduced as published; descriptions are our own.