- IPS 4000 pumping system controller - variable primary
Pump system controller (variable primary) · BACnet points list
Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary BACnet points list
Updated 11 November 2026
The IPS 4000 runs a group of variable-speed pumps. In the variable primary version its BACnet list adds chiller/boiler enables, minimum and maximum flow and differential pressure limits per chiller or boiler, and the related alarms, on top of pump modes, hand speeds, zone setpoints and values, pump speed, power, energy, head and flow, run hours and alarms.
This page lists 362 BACnet objects for the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary — 109 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.
- Manufacturer
- Armstrong Fluid Technology
- Model
- IPS 4000 pumping system controller - variable primary
- Equipment
- Pump system controller (variable primary)
- Equipment type
- VFDs & pumps
- BACnet objects
- 362 (109 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Communication interface ver 2.1.0
- Also known as
- IPS 4000, IPS4000, IPS 4000 primary, Integrated Pumping System 4000, 90.9751
Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.
BMS integration notes: Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary
Start and stop the IPS 4000 with BV 1 Remote Start, write the zone setpoints (AV 1-16) and read BI 110 IPS On Status, the active zone value, system flow and head, and BI 1 General Alarm. Reset alarms with BV 32. The BMS can also put each pump in Hand, Off or Auto (BV 2-25), set hand speeds, enable chillers/boilers and write zone values (bas Zone pv AVs).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Remote Start | Start/stop from the BMS (1 = start) | Write |
| AV 1 | Zone 1 sp | Zone 1 control setpoint | Write |
| BV 32 | Alarm Reset | Reset alarms | Write |
| BI 110 | IPS On Status | Pumping system on status | Read |
| AI 3 | Active Zone pv | Value of the zone in control | Read |
| AI 147 | System Flow | Total system flow | Read |
| AI 136 | System Head | Total system head | Read |
| BI 2 | Pump Alarm | Any pump alarm | Read |
| BI 1 | General Alarm | Any active alarm | Read |
Enable & remote start
BV 1 Remote Start (0 = Stop, 1 = Start). The Set Pump Hand/Off/Auto BVs are momentary commands that change one pump's mode.
Sensors & values from the BMS
The bas Zone 1-16 pv AVs (48-63) are writable, so the BMS can supply zone values, and the bas Chiller/Boiler dp pv AVs (78-85) do the same for chiller/boiler differential pressure. The data-points sheet does not say how the controller chooses between BMS and wired values.
Network setup
- The sheet lists BACnet TCP/IP and BACnet MS/TP. For BACnet IP use UDP port 47808 (0xBAC0).
- The device instance and MS/TP settings are not given in the sheet.
Watch out for
- Set Pump Hand/Off/Auto BVs are momentary: write 1 to change the mode, and read the pump mode BIs to confirm it.
- Design flow/head, BEP and dead-band AVs are commissioning settings; don't write them cyclically.
- Units for pressure, temperature and flow follow the controller's unit setting.
Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | Remote Start | Write | 0=Stop, 1=Start | ||
| BV | 2 | Set Pump 1 Hand | Momentary command | Write | 1=Hand | |
| BV | 3 | Set Pump 1 Off | Momentary command | Write | 1=Off | |
| BV | 4 | Set Pump 1 Auto | Momentary command | Write | 1=Auto | |
| BV | 5 | Set Pump 2 Hand | Momentary command | Write | 1=Hand | |
| BV | 6 | Set Pump 2 Off | Momentary command | Write | 1=Off | |
| BV | 7 | Set Pump 2 Auto | Momentary command | Write | 1=Auto | |
| BV | 8 | Set Pump 3 Hand | Momentary command | Write | 1=Hand | |
| BV | 9 | Set Pump 3 Off | Momentary command | Write | 1=Off | |
| BV | 10 | Set Pump 3 Auto | Momentary command | Write | 1=Auto | |
| BV | 11 | Set Pump 4 Hand | Momentary command | Write | 1=Hand | |
| BV | 12 | Set Pump 4 Off | Momentary command | Write | 1=Off | |
| BV | 13 | Set Pump 4 Auto | Momentary command | Write | 1=Auto | |
| BV | 14 | Set Pump 5 Hand | Momentary command | Write | 1=Hand | |
| BV | 15 | Set Pump 5 Off | Momentary command | Write | 1=Off | |
| BV | 16 | Set Pump 5 Auto | Momentary command | Write | 1=Auto | |
| BV | 17 | Set Pump 6 Hand | Momentary command | Write | 1=Hand | |
| BV | 18 | Set Pump 6 Off | Momentary command | Write | 1=Off | |
| BV | 19 | Set Pump 6 Auto | Momentary command | Write | 1=Auto | |
| BV | 20 | Set Pump 7 Hand | Momentary command | Write | 1=Hand | |
| BV | 21 | Set Pump 7 Off | Momentary command | Write | 1=Off | |
| BV | 22 | Set Pump 7 Auto | Momentary command | Write | 1=Auto | |
| BV | 23 | Set Pump 8 Hand | Momentary command | Write | 1=Hand | |
| BV | 24 | Set Pump 8 Off | Momentary command | Write | 1=Off | |
| BV | 25 | Set Pump 8 Auto | Momentary command | Write | 1=Auto | |
| BVmin | 32 | Alarm Reset | Write | 1=Reset | ||
| BV | 33 | Chiller/Boiler 1 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 34 | Chiller/Boiler 2 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 35 | Chiller/Boiler 3 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 36 | Chiller/Boiler 4 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 37 | Chiller/Boiler 5 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 38 | Chiller/Boiler 6 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 39 | Chiller/Boiler 7 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 40 | Chiller/Boiler 8 Enabled | Write | 0=Disabled, 1=Enabled | ||
| BV | 43 | Chiller/Boiler_bas_Enable | Write | 0=Disabled, 1=Enabled | ||
| BImin | 1 | General Alarm | Read | 0=Ok, 1=Alarm | ||
| BImin | 2 | Pump Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3 | Sensor Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 4 | Pump 1 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 5 | Pump 1 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 6 | Pump 1 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 7 | Pump 2 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 8 | Pump 2 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 9 | Pump 2 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 10 | Pump 3 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 11 | Pump 3 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 12 | Pump 3 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 13 | Pump 4 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 14 | Pump 4 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 15 | Pump 4 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 16 | Pump 5 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 17 | Pump 5 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 18 | Pump 5 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 19 | Pump 6 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 20 | Pump 6 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 21 | Pump 6 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 22 | Pump 7 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 23 | Pump 7 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 24 | Pump 7 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 25 | Pump 8 in Hand mode | Read | 0=Ok, 1=Hand | ||
| BI | 26 | Pump 8 in Off mode | Read | 0=Ok, 1=Off | ||
| BI | 27 | Pump 8 in Auto mode | Read | 0=Ok, 1=Auto | ||
| BI | 34 | Pump 1 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 35 | Pump 2 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 36 | Pump 3 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 37 | Pump 4 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 38 | Pump 5 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 39 | Pump 6 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 40 | Pump 7 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 41 | Pump 8 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 44 | Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 47 | All Zones dp/Temperature Transmitters Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 48 | Zone 1 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 49 | Zone 2 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 50 | Zone 3 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 51 | Zone 4 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 52 | Zone 5 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 53 | Zone 6 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 54 | Zone 7 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 55 | Zone 8 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 56 | Zone 9 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 57 | Zone 10 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 58 | Zone 11 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 59 | Zone 12 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 60 | Zone 13 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 61 | Zone 14 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 62 | Zone 15 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 63 | Zone 16 dp/Temperature Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 68 | Chiller/Boiler Min Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 69 | Chiller/Boiler Max Flow Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 70 | Pump 1 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 71 | Pump 2 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 72 | Pump 3 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 73 | Pump 4 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 74 | Pump 5 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 75 | Pump 6 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 76 | Pump 7 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 77 | Pump 8 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 80 | Pump 1 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 81 | Pump 2 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 82 | Pump 3 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 83 | Pump 4 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 84 | Pump 5 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 85 | Pump 6 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 86 | Pump 7 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 87 | Pump 8 Run feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 90 | Pump 1 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 91 | Pump 2 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 92 | Pump 3 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 93 | Pump 4 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 94 | Pump 5 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 95 | Pump 6 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 96 | Pump 7 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BI | 97 | Pump 8 Drive Fault | Read | 0=Ok, 1=Alarm | ||
| BImin | 110 | IPS On Status | Read | 0=Off, 1=On | ||
| BI | 111 | PLC Board High Temperature Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 114 | All Chiller/Boiler Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 115 | Chiller/Boiler 1 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 116 | Chiller/Boiler 2 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 117 | Chiller/Boiler 3 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 118 | Chiller/Boiler 4 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 119 | Chiller/Boiler 5 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 120 | Chiller/Boiler 6 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 121 | Chiller/Boiler 7 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 122 | Chiller/Boiler 8 Sensor Fail | Read | 0=Ok, 1=Alarm | ||
| BI | 125 | Min Chiller/Boiler dp Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 126 | Max Chiller/Boiler dp Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 127 | Chiller/Boiler dp1 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 128 | Chiller/Boiler dp2 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 129 | Chiller/Boiler dp3 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 130 | Chiller/Boiler dp4 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 131 | Chiller/Boiler dp5 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 132 | Chiller/Boiler dp6 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 133 | Chiller/Boiler dp7 Above Maximum | Read | 0=Ok, 1=Warning | ||
| BI | 134 | Chiller/Boiler dp8 Above Maximum | Read | 0=Ok, 1=Warning | ||
| AVmin | 1 | Zone 1 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 2 | Zone 2 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 3 | Zone 3 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 4 | Zone 4 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 5 | Zone 5 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 6 | Zone 6 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 7 | Zone 7 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 8 | Zone 8 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 9 | Zone 9 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 10 | Zone 10 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 11 | Zone 11 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 12 | Zone 12 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 13 | Zone 13 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 14 | Zone 14 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 15 | Zone 15 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 16 | Zone 16 sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 21 | Pump 1 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 22 | Pump 2 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 23 | Pump 3 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 24 | Pump 4 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 25 | Pump 5 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 26 | Pump 6 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 27 | Pump 7 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 28 | Pump 8 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AV | 31 | Max Valve Opening | Range 0.0 to 100.0 | % | Write | |
| AV | 32 | Design Flow | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 33 | Design Head | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 34 | Zero Flow Head | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 35 | Flow bep | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 36 | Head bep | Range 0.0 to 999.9 | ft, psi, kPa, m, bar | Write | |
| AV | 37 | Dead Band(K) | Range 0-0.5 | Write | ||
| AV | 38 | Sensor Adjust | Range 0 to 100.0% | Write | ||
| AV | 39 | Chiller/Boiler Min Flow | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 40 | Chiller/Boiler Max Flow | Range 0.0 to 999.9 | GPM, L/s, m3/h | Write | |
| AV | 48 | bas Zone 1 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 49 | bas Zone 2 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 50 | bas Zone 3 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 51 | bas Zone 4 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 52 | bas Zone 5 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 53 | bas Zone 6 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 54 | bas Zone 7 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 55 | bas Zone 8 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 56 | bas Zone 9 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 57 | bas Zone 10 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 58 | bas Zone 11 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 59 | bas Zone 12 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 60 | bas Zone 13 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 61 | bas Zone 14 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 62 | bas Zone 15 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 63 | bas Zone 16 pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Write | |
| AV | 68 | Chiller/Boiler dp 1 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 69 | Chiller/Boiler dp 2 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 70 | Chiller/Boiler dp 3 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 71 | Chiller/Boiler dp 4 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 72 | Chiller/Boiler dp 5 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 73 | Chiller/Boiler dp 6 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 74 | Chiller/Boiler dp 7 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 75 | Chiller/Boiler dp 8 Min | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 78 | bas Chiller/Boiler dp 1 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 79 | bas Chiller/Boiler dp 2 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 80 | bas Chiller/Boiler dp 3 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 81 | bas Chiller/Boiler dp 4 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 82 | bas Chiller/Boiler dp 5 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 83 | bas Chiller/Boiler dp 6 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 84 | bas Chiller/Boiler dp 7 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 85 | bas Chiller/Boiler dp 8 pv | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 88 | Chiller/Boiler dp 1 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 89 | Chiller/Boiler dp 2 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 90 | Chiller/Boiler dp 3 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 91 | Chiller/Boiler dp 4 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 92 | Chiller/Boiler dp 5 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 93 | Chiller/Boiler dp 6 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 94 | Chiller/Boiler dp 7 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AV | 95 | Chiller/Boiler dp 8 Max | Range 0.0 to 999.9 | psi, ft, kPA, m | Write | |
| AI | 1 | Active Zone | Range 0 to 16 | Read | ||
| AI | 2 | Active Zone Error | Range -999.9 to 999.9 | Read | ||
| AImin | 3 | Active Zone pv | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 4 | Active Zone sp | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 5 | Zone 1 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 6 | Zone 2 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 7 | Zone 3 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 8 | Zone 4 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 9 | Zone 5 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 10 | Zone 6 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 11 | Zone 7 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 12 | Zone 8 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 13 | Zone 9 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 14 | Zone 10 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 15 | Zone 11 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 16 | Zone 12 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 17 | Zone 13 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 18 | Zone 14 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 19 | Zone 15 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 20 | Zone 16 Value | Range 0.0 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 25 | Zone 1 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 26 | Zone 2 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 27 | Zone 3 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 28 | Zone 4 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 29 | Zone 5 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 30 | Zone 6 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 31 | Zone 7 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 32 | Zone 8 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 33 | Zone 9 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 34 | Zone 10 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 35 | Zone 11 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 36 | Zone 12 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 37 | Zone 13 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 38 | Zone 14 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 39 | Zone 15 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 40 | Zone 16 Error | Range -999.9 to 999.9 | psi, ft, kPA, m, °f or °c | Read | |
| AI | 45 | Pump 1 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 46 | Pump 2 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 47 | Pump 3 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 48 | Pump 4 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 49 | Pump 5 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 50 | Pump 6 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 51 | Pump 7 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 52 | Pump 8 Speed | Range 0.0 to 100.0 | % | Read | |
| AI | 55 | Temperature Sensor pv | Range 0.0 to 212.0 | °f or °c | Read | |
| AI | 56 | Pump 1 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 57 | Pump 1 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 58 | Pump 1 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 59 | Pump 1 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 60 | Pump 1 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 61 | Pump 1 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 62 | Pump 1 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 63 | Pump 1 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 64 | Pump 2 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 65 | Pump 2 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 66 | Pump 2 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 67 | Pump 2 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 68 | Pump 2 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 69 | Pump 2 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 70 | Pump 2 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 71 | Pump 2 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 72 | Pump 3 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 73 | Pump 3 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 74 | Pump 3 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 75 | Pump 3 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 76 | Pump 3 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 77 | Pump 3 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 78 | Pump 3 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 79 | Pump 3 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 80 | Pump 4 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 81 | Pump 4 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 82 | Pump 4 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 83 | Pump 4 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 84 | Pump 4 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 85 | Pump 4 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 86 | Pump 4 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 87 | Pump 4 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 88 | Pump 5 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 89 | Pump 5 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 90 | Pump 5 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 91 | Pump 5 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 92 | Pump 5 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 93 | Pump 5 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 94 | Pump 5 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 95 | Pump 5 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 96 | Pump 6 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 97 | Pump 6 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 98 | Pump 6 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 99 | Pump 6 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 100 | Pump 6 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 101 | Pump 6 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 102 | Pump 6 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 103 | Pump 6 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 104 | Pump 7 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 105 | Pump 7 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 106 | Pump 7 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 107 | Pump 7 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 108 | Pump 7 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 109 | Pump 7 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 110 | Pump 7 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 111 | Pump 7 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AI | 112 | Pump 8 Drive Amp | Range 0.0 to 1000.0 | Amp | Read | |
| AI | 113 | Pump 8 Drive Volt AC | Range 0.0 to 1000.0 | VAC | Read | |
| AI | 114 | Pump 8 Drive Power | Range 0.0 to 1000.0 | kW | Read | |
| AI | 115 | Pump 8 Drive KWH | Range 0.0 to 1000.0 | KWH | Read | |
| AI | 116 | Pump 8 Drive RPM | Range 0.0 to 1000.0 | RPM | Read | |
| AI | 117 | Pump 8 Drive Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 118 | Pump 8 Actual Run Hours | Range 0.0 to 1000.0 | Hours | Read | |
| AI | 119 | Pump 8 Drive Speed Feedback | Range 0.0 to 100.0 | % | Read | |
| AImin | 136 | System Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 137 | Pump 1 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 138 | Pump 2 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 139 | Pump 3 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 140 | Pump 4 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 141 | Pump 5 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 142 | Pump 6 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 143 | Pump 7 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AI | 144 | Pump 8 Head | Range 0.0 to 3276.7 | ft, psi, kPa, kPa, m, bar | Read | |
| AImin | 147 | System Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 148 | Pump 1 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 149 | Pump 2 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 150 | Pump 3 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 151 | Pump 4 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 152 | Pump 5 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 153 | Pump 6 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 154 | Pump 7 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 155 | Pump 8 Flow | Range 0.0 to 3276.7 | GPM, L/s, m3/h | Read | |
| AI | 159 | Bypass Valve Position | Range 0 to 100.0 | % | Read | |
| AI | 160 | Number of Pumps Running in Auto | Range 1 to 8 | Read | ||
| AI | 161 | Lead Pump id | Range 1 to 8 | Read | ||
| AI | 162 | Number Of Pumps Configured | Range 1 to 8 | Read | ||
| AI | 163 | Number Of Chiller/Boiler Configured | Range 1 to 8 | Read | ||
| AI | 164 | Lead Pump Switch Time | Range 0-32767 | Day/Hr | Read | |
| AI | 165 | Active Chiller/Boiler | Range 1 to 8 | Read | ||
| AI | 166 | Active Chiller/Boiler Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 167 | Active Chiller/Boiler pv | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 168 | Active Chiller/Boiler sp | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 169 | Chiller/Boiler 1 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 170 | Chiller/Boiler 2 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 171 | Chiller/Boiler 3 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 172 | Chiller/Boiler 4 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 173 | Chiller/Boiler 5 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 174 | Chiller/Boiler 6 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 175 | Chiller/Boiler 7 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 176 | Chiller/Boiler 8 Value | Range 0.0 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 179 | Chiller/Boiler 1 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 180 | Chiller/Boiler 2 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 181 | Chiller/Boiler 3 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 182 | Chiller/Boiler 4 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 183 | Chiller/Boiler 5 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 184 | Chiller/Boiler 6 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 185 | Chiller/Boiler 7 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read | |
| AI | 186 | Chiller/Boiler 8 Error | Range -999.9 to 999.9 | GPM, L/s, m3/h | Read |
No points match these filters.
Object ID lookup: Armstrong Fluid Technology IPS 4000 Variable Primary point IDs by name
BV1Remote StartBV2Set Pump 1 HandBV3Set Pump 1 OffBV4Set Pump 1 AutoBV5Set Pump 2 HandBV6Set Pump 2 OffBV7Set Pump 2 AutoBV8Set Pump 3 HandBV9Set Pump 3 OffBV10Set Pump 3 AutoBV11Set Pump 4 HandBV12Set Pump 4 OffBV13Set Pump 4 AutoBV14Set Pump 5 HandBV15Set Pump 5 OffBV16Set Pump 5 AutoBV17Set Pump 6 HandBV18Set Pump 6 OffBV19Set Pump 6 AutoBV20Set Pump 7 HandBV21Set Pump 7 OffBV22Set Pump 7 AutoBV23Set Pump 8 HandBV24Set Pump 8 OffBV25Set Pump 8 AutoBV32Alarm ResetBV33Chiller/Boiler 1 EnabledBV34Chiller/Boiler 2 EnabledBV35Chiller/Boiler 3 EnabledBV36Chiller/Boiler 4 EnabledBV37Chiller/Boiler 5 EnabledBV38Chiller/Boiler 6 EnabledBV39Chiller/Boiler 7 EnabledBV40Chiller/Boiler 8 EnabledBV43Chiller/Boiler_bas_EnableBI1General AlarmBI2Pump AlarmBI3Sensor AlarmBI4Pump 1 in Hand modeBI5Pump 1 in Off modeBI6Pump 1 in Auto modeBI7Pump 2 in Hand modeBI8Pump 2 in Off modeBI9Pump 2 in Auto modeBI10Pump 3 in Hand modeBI11Pump 3 in Off modeBI12Pump 3 in Auto modeBI13Pump 4 in Hand modeBI14Pump 4 in Off modeBI15Pump 4 in Auto modeBI16Pump 5 in Hand modeBI17Pump 5 in Off modeBI18Pump 5 in Auto modeBI19Pump 6 in Hand modeBI20Pump 6 in Off modeBI21Pump 6 in Auto modeBI22Pump 7 in Hand modeBI23Pump 7 in Off modeBI24Pump 7 in Auto modeBI25Pump 8 in Hand modeBI26Pump 8 in Off modeBI27Pump 8 in Auto modeBI34Pump 1 Run FeedbackBI35Pump 2 Run FeedbackBI36Pump 3 Run FeedbackBI37Pump 4 Run FeedbackBI38Pump 5 Run FeedbackBI39Pump 6 Run FeedbackBI40Pump 7 Run FeedbackBI41Pump 8 Run FeedbackBI44Temperature Transmitter FailedBI47All Zones dp/Temperature Transmitters FailedBI48Zone 1 dp/Temperature Transmitter FailedBI49Zone 2 dp/Temperature Transmitter FailedBI50Zone 3 dp/Temperature Transmitter FailedBI51Zone 4 dp/Temperature Transmitter FailedBI52Zone 5 dp/Temperature Transmitter FailedBI53Zone 6 dp/Temperature Transmitter FailedBI54Zone 7 dp/Temperature Transmitter FailedBI55Zone 8 dp/Temperature Transmitter FailedBI56Zone 9 dp/Temperature Transmitter FailedBI57Zone 10 dp/Temperature Transmitter FailedBI58Zone 11 dp/Temperature Transmitter FailedBI59Zone 12 dp/Temperature Transmitter FailedBI60Zone 13 dp/Temperature Transmitter FailedBI61Zone 14 dp/Temperature Transmitter FailedBI62Zone 15 dp/Temperature Transmitter FailedBI63Zone 16 dp/Temperature Transmitter FailedBI68Chiller/Boiler Min Flow AlarmBI69Chiller/Boiler Max Flow AlarmBI70Pump 1 AlarmBI71Pump 2 AlarmBI72Pump 3 AlarmBI73Pump 4 AlarmBI74Pump 5 AlarmBI75Pump 6 AlarmBI76Pump 7 AlarmBI77Pump 8 AlarmBI80Pump 1 Run feedback AlarmBI81Pump 2 Run feedback AlarmBI82Pump 3 Run feedback AlarmBI83Pump 4 Run feedback AlarmBI84Pump 5 Run feedback AlarmBI85Pump 6 Run feedback AlarmBI86Pump 7 Run feedback AlarmBI87Pump 8 Run feedback AlarmBI90Pump 1 Drive FaultBI91Pump 2 Drive FaultBI92Pump 3 Drive FaultBI93Pump 4 Drive FaultBI94Pump 5 Drive FaultBI95Pump 6 Drive FaultBI96Pump 7 Drive FaultBI97Pump 8 Drive FaultBI110IPS On StatusBI111PLC Board High Temperature AlarmBI114All Chiller/Boiler FailedBI115Chiller/Boiler 1 Sensor FailBI116Chiller/Boiler 2 Sensor FailBI117Chiller/Boiler 3 Sensor FailBI118Chiller/Boiler 4 Sensor FailBI119Chiller/Boiler 5 Sensor FailBI120Chiller/Boiler 6 Sensor FailBI121Chiller/Boiler 7 Sensor FailBI122Chiller/Boiler 8 Sensor FailBI125Min Chiller/Boiler dp AlarmBI126Max Chiller/Boiler dp AlarmBI127Chiller/Boiler dp1 Above MaximumBI128Chiller/Boiler dp2 Above MaximumBI129Chiller/Boiler dp3 Above MaximumBI130Chiller/Boiler dp4 Above MaximumBI131Chiller/Boiler dp5 Above MaximumBI132Chiller/Boiler dp6 Above MaximumBI133Chiller/Boiler dp7 Above MaximumBI134Chiller/Boiler dp8 Above MaximumAV1Zone 1 spAV2Zone 2 spAV3Zone 3 spAV4Zone 4 spAV5Zone 5 spAV6Zone 6 spAV7Zone 7 spAV8Zone 8 spAV9Zone 9 spAV10Zone 10 spAV11Zone 11 spAV12Zone 12 spAV13Zone 13 spAV14Zone 14 spAV15Zone 15 spAV16Zone 16 spAV21Pump 1 Hand SpeedAV22Pump 2 Hand SpeedAV23Pump 3 Hand SpeedAV24Pump 4 Hand SpeedAV25Pump 5 Hand SpeedAV26Pump 6 Hand SpeedAV27Pump 7 Hand SpeedAV28Pump 8 Hand SpeedAV31Max Valve OpeningAV32Design FlowAV33Design HeadAV34Zero Flow HeadAV35Flow bepAV36Head bepAV37Dead Band(K)AV38Sensor AdjustAV39Chiller/Boiler Min FlowAV40Chiller/Boiler Max FlowAV48bas Zone 1 pvAV49bas Zone 2 pvAV50bas Zone 3 pvAV51bas Zone 4 pvAV52bas Zone 5 pvAV53bas Zone 6 pvAV54bas Zone 7 pvAV55bas Zone 8 pvAV56bas Zone 9 pvAV57bas Zone 10 pvAV58bas Zone 11 pvAV59bas Zone 12 pvAV60bas Zone 13 pvAV61bas Zone 14 pvAV62bas Zone 15 pvAV63bas Zone 16 pvAV68Chiller/Boiler dp 1 MinAV69Chiller/Boiler dp 2 MinAV70Chiller/Boiler dp 3 MinAV71Chiller/Boiler dp 4 MinAV72Chiller/Boiler dp 5 MinAV73Chiller/Boiler dp 6 MinAV74Chiller/Boiler dp 7 MinAV75Chiller/Boiler dp 8 MinAV78bas Chiller/Boiler dp 1 pvAV79bas Chiller/Boiler dp 2 pvAV80bas Chiller/Boiler dp 3 pvAV81bas Chiller/Boiler dp 4 pvAV82bas Chiller/Boiler dp 5 pvAV83bas Chiller/Boiler dp 6 pvAV84bas Chiller/Boiler dp 7 pvAV85bas Chiller/Boiler dp 8 pvAV88Chiller/Boiler dp 1 MaxAV89Chiller/Boiler dp 2 MaxAV90Chiller/Boiler dp 3 MaxAV91Chiller/Boiler dp 4 MaxAV92Chiller/Boiler dp 5 MaxAV93Chiller/Boiler dp 6 MaxAV94Chiller/Boiler dp 7 MaxAV95Chiller/Boiler dp 8 MaxAI1Active ZoneAI2Active Zone ErrorAI3Active Zone pvAI4Active Zone spAI5Zone 1 ValueAI6Zone 2 ValueAI7Zone 3 ValueAI8Zone 4 ValueAI9Zone 5 ValueAI10Zone 6 ValueAI11Zone 7 ValueAI12Zone 8 ValueAI13Zone 9 ValueAI14Zone 10 ValueAI15Zone 11 ValueAI16Zone 12 ValueAI17Zone 13 ValueAI18Zone 14 ValueAI19Zone 15 ValueAI20Zone 16 ValueAI25Zone 1 ErrorAI26Zone 2 ErrorAI27Zone 3 ErrorAI28Zone 4 ErrorAI29Zone 5 ErrorAI30Zone 6 ErrorAI31Zone 7 ErrorAI32Zone 8 ErrorAI33Zone 9 ErrorAI34Zone 10 ErrorAI35Zone 11 ErrorAI36Zone 12 ErrorAI37Zone 13 ErrorAI38Zone 14 ErrorAI39Zone 15 ErrorAI40Zone 16 ErrorAI45Pump 1 SpeedAI46Pump 2 SpeedAI47Pump 3 SpeedAI48Pump 4 SpeedAI49Pump 5 SpeedAI50Pump 6 SpeedAI51Pump 7 SpeedAI52Pump 8 SpeedAI55Temperature Sensor pvAI56Pump 1 Drive AmpAI57Pump 1 Drive Volt ACAI58Pump 1 Drive PowerAI59Pump 1 Drive KWHAI60Pump 1 Drive RPMAI61Pump 1 Drive Run HoursAI62Pump 1 Actual Run HoursAI63Pump 1 Drive Speed FeedbackAI64Pump 2 Drive AmpAI65Pump 2 Drive Volt ACAI66Pump 2 Drive PowerAI67Pump 2 Drive KWHAI68Pump 2 Drive RPMAI69Pump 2 Drive Run HoursAI70Pump 2 Actual Run HoursAI71Pump 2 Drive Speed FeedbackAI72Pump 3 Drive AmpAI73Pump 3 Drive Volt ACAI74Pump 3 Drive PowerAI75Pump 3 Drive KWHAI76Pump 3 Drive RPMAI77Pump 3 Drive Run HoursAI78Pump 3 Actual Run HoursAI79Pump 3 Drive Speed FeedbackAI80Pump 4 Drive AmpAI81Pump 4 Drive Volt ACAI82Pump 4 Drive PowerAI83Pump 4 Drive KWHAI84Pump 4 Drive RPMAI85Pump 4 Drive Run HoursAI86Pump 4 Actual Run HoursAI87Pump 4 Drive Speed FeedbackAI88Pump 5 Drive AmpAI89Pump 5 Drive Volt ACAI90Pump 5 Drive PowerAI91Pump 5 Drive KWHAI92Pump 5 Drive RPMAI93Pump 5 Drive Run HoursAI94Pump 5 Actual Run HoursAI95Pump 5 Drive Speed FeedbackAI96Pump 6 Drive AmpAI97Pump 6 Drive Volt ACAI98Pump 6 Drive PowerAI99Pump 6 Drive KWHAI100Pump 6 Drive RPMAI101Pump 6 Drive Run HoursAI102Pump 6 Actual Run HoursAI103Pump 6 Drive Speed FeedbackAI104Pump 7 Drive AmpAI105Pump 7 Drive Volt ACAI106Pump 7 Drive PowerAI107Pump 7 Drive KWHAI108Pump 7 Drive RPMAI109Pump 7 Drive Run HoursAI110Pump 7 Actual Run HoursAI111Pump 7 Drive Speed FeedbackAI112Pump 8 Drive AmpAI113Pump 8 Drive Volt ACAI114Pump 8 Drive PowerAI115Pump 8 Drive KWHAI116Pump 8 Drive RPMAI117Pump 8 Drive Run HoursAI118Pump 8 Actual Run HoursAI119Pump 8 Drive Speed FeedbackAI136System HeadAI137Pump 1 HeadAI138Pump 2 HeadAI139Pump 3 HeadAI140Pump 4 HeadAI141Pump 5 HeadAI142Pump 6 HeadAI143Pump 7 HeadAI144Pump 8 HeadAI147System FlowAI148Pump 1 FlowAI149Pump 2 FlowAI150Pump 3 FlowAI151Pump 4 FlowAI152Pump 5 FlowAI153Pump 6 FlowAI154Pump 7 FlowAI155Pump 8 FlowAI159Bypass Valve PositionAI160Number of Pumps Running in AutoAI161Lead Pump idAI162Number Of Pumps ConfiguredAI163Number Of Chiller/Boiler ConfiguredAI164Lead Pump Switch TimeAI165Active Chiller/BoilerAI166Active Chiller/Boiler ErrorAI167Active Chiller/Boiler pvAI168Active Chiller/Boiler spAI169Chiller/Boiler 1 ValueAI170Chiller/Boiler 2 ValueAI171Chiller/Boiler 3 ValueAI172Chiller/Boiler 4 ValueAI173Chiller/Boiler 5 ValueAI174Chiller/Boiler 6 ValueAI175Chiller/Boiler 7 ValueAI176Chiller/Boiler 8 ValueAI179Chiller/Boiler 1 ErrorAI180Chiller/Boiler 2 ErrorAI181Chiller/Boiler 3 ErrorAI182Chiller/Boiler 4 ErrorAI183Chiller/Boiler 5 ErrorAI184Chiller/Boiler 6 ErrorAI185Chiller/Boiler 7 ErrorAI186Chiller/Boiler 8 Error
Integration notes
- 121 rows printed as Reserved are left out.
- Analog descriptions give the scaled range from the Represent column; the PDF also prints a raw integer range.
- This list is for communication interface ver 2.1.0. Older IPS 4000 controllers (interface ver 1.0.0, Data Points 90.975, and the legacy 90.971) have their own data-point sheets; check which one matches the controller.
- The PDF table is on pages 15-25.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IPS 4000 pumping system controller - variable primary and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary
How many BACnet points does the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary have?
This list has 362 BACnet objects: 153 analog inputs, 74 analog values, 100 binary inputs, 35 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary BACnet points are writable?
109 of the 362 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary BACnet documentation?
The source is IPS 4000 Integrated pumping system for variable primary application, Data points (communication interface ver-2.1.0) (90.9751), revision 2020-12-07, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-9751_ips4000_primary_bas-_ver-2-1-0_datapoints.pdf.
What are the minimum BACnet points to integrate the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary?
Start with BV 1 Remote Start (Start/stop from the BMS (1 = start)); AV 1 Zone 1 sp (Zone 1 control setpoint); BV 32 Alarm Reset (Reset alarms); BI 110 IPS On Status (Pumping system on status); AI 3 Active Zone pv (Value of the zone in control); AI 147 System Flow (Total system flow); AI 136 System Head (Total system head); BI 2 Pump Alarm (Any pump alarm); BI 1 General Alarm (Any active alarm).
How do I enable BMS control of the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary?
BV 1 Remote Start (0 = Stop, 1 = Start). The Set Pump Hand/Off/Auto BVs are momentary commands that change one pump's mode.
Can the BMS supply sensor values to the Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary?
The bas Zone 1-16 pv AVs (48-63) are writable, so the BMS can supply zone values, and the bas Chiller/Boiler dp pv AVs (78-85) do the same for chiller/boiler differential pressure. The data-points sheet does not say how the controller chooses between BMS and wired values.
How do I check these points on the real IPS 4000 pumping system controller - variable primary?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Armstrong Fluid Technology BACnet points lists
- Cooling tower and condenser pump plant controller
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)
Armstrong Design Envelope Integrated Tower Controller for the condenser water side: up to 5 cooling towers (fans, inlet/outlet isolation valves) and 5 condenser water pumps.
Also known as: ITC 9521, ITC9521, Design Envelope ITC, Integrated Tower Controller, 82.21 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W10 chiller plant controller (water-cooled)
Armstrong EE-W10 water-cooled chilled water plant controls; the object list covers up to 3 chillers, 3 chilled water pumps, 3 condenser water pumps and 3 towers.
Also known as: EE-W10, EE-W 10, Armstrong EE-W10, 90.7651 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W20 chiller plant controller (water-cooled)
Armstrong EE-W20 water-cooled chilled water plant controls; the object list covers up to 5 chillers, 10 chilled water pumps, 10 condenser water pumps, 5 towers and 5 control zones.
Also known as: EE-W20, EE-W 20, Armstrong EE-W20, 90.7661 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology IPC 9521 chilled water plant controller
Armstrong IPC 9521 water-cooled chilled water plant controls (legacy product); the object list covers up to 5 chillers, 5 chilled and 5 condenser water pumps (A and B sides), 5 towers and 5 zones.
Also known as: IPC 9521, IPC9521, Armstrong IPC 9521, 90.874 - Pump system controller (variable secondary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary
Armstrong IPS 4000 controllers set up for variable secondary pumping: up to 8 pumps and 16 control zones.
Also known as: IPS 4000, IPS4000, IPS 4000 secondary, Integrated Pumping System 4000, 90.9761 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A10 chiller plant controller
Armstrong SE-A10 chilled water plant controls with no condenser water side; the object list covers up to 3 chillers and 3 chilled water pumps.
Also known as: SE-A10, SE-A 10, Armstrong SE-A10, 90.7671 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A20 chiller plant controller
Armstrong SE-A20 chilled water plant controls with no condenser water side; the object list covers up to 5 chillers, 10 chilled water pumps and 5 control zones.
Also known as: SE-A20, SE-A 20, Armstrong SE-A20, 90.7681
Source: IPS 4000 Integrated pumping system for variable primary application, Data points (communication interface ver-2.1.0) · 90.9751 · rev. 2020-12-07. Object names, instances and units are reproduced as published; descriptions are our own.