Chiller plant controller (chillers and chilled water pumps) · BACnet points list

Armstrong Fluid Technology SE-A10 chiller plant controller BACnet points list

Updated 6 November 2026

Short answer

The SE-A10 controls a small chilled water plant with up to 3 chillers and 3 chilled water pumps and no condenser water or tower points. Its BACnet object list gives plant start/stop, alarm reset, plant load, power and efficiency, chilled water temperatures and flow, chiller and pump status, alarms, drive data and Hand/Auto overrides.

This page lists 106 BACnet objects for the Armstrong Fluid Technology SE-A10 chiller plant controller — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.

Manufacturer
Armstrong Fluid Technology
Model
SE-A10 chiller plant controller
Equipment
Chiller plant controller (chillers and chilled water pumps)
Equipment type
Chillers
BACnet objects
106 (24 writable)
Transport
—
Firmware
BACnet communication interface Rev 24.111
Also known as
SE-A10, SE-A 10, Armstrong SE-A10, 90.7671
Source document
SE-A10 Data points (BAS data points - BACnet, Communication Interface Rev 24.111) · 90.7671 · rev. 2025-07-10
Download CSV 106 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.

BMS integration notes: Armstrong Fluid Technology SE-A10 chiller plant controller

Integration in brief

The SE-A10 publishes a fixed BACnet object list. Start and stop the plant with BO 1 Remote Start, write the zone setpoint (AV 2), and read BI 1 Plant Status, plant load, chilled water temperatures, plant power and efficiency. Use BO 3 to reset alarms. Per-chiller, per-pump and per-valve alarms, run feedbacks and Hand/Auto overrides are there if the BMS needs more detail.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Remote StartPlant start/stop from the BMS (1 = start)Write
AV 2Zone 1 SetpointZone 1 control setpointWrite
BO 3Alarm ResetReset plant alarms (positive edge)Write
BI 1Plant StatusPlant on/off statusRead
AI 3Plant LoadPlant cooling load, tonsRead
AI 1001chws TempChilled water supply temperatureRead
AI 1002chwr TempChilled water return temperatureRead
AI 2Total Plant Power ConsumptionTotal plant power, kWRead
AI 1Plant EfficiencyPlant efficiency, kW/tonRead
BI 10Refrigerant Leak AlarmRefrigerant leak detectedRead

Enable & remote start

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

Network setup

Watch out for

Armstrong Fluid Technology SE-A10 chiller plant controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

106 of 106 shown
Type
Access
Show
Armstrong Fluid Technology SE-A10 chiller plant controller BACnet Points List
DescriptionStates
BOmin1Remote StartWrite0=Stop, 1=Start
BO2Enable Plant Stand-by Mode FeatureWrite0=FALSE, 1=TRUE
BOmin3Alarm ResetPositive Edge commandWrite0=N/A, 1=Reset
BImin1Plant StatusRead0=Off, 1=On
BI2All Zone Transmitter FailedRead0=Ok, 1=Alarm
BI3Zone 1 Transmitter FailedRead0=Ok, 1=Alarm
BI8Dry Bulb Air Temp Transmitter FailedRead0=Ok, 1=Alarm
BI9Relative Humidity Transmitter FailedRead0=Ok, 1=Alarm
BImin10Refrigerant Leak AlarmRead0=Ok, 1=Alarm
BI1001chwS Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1002chwR Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1003chw Flow Transmitter FailedRead0=Ok, 1=Alarm
BI1006Chlr 1 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1007Chlr 2 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1008Chlr 3 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1011chw Pump 1 Run FeedbackRead0=Stopped, 1=Running
BI1012chw Pump 1 AlarmRead0=Ok, 1=Alarm
BI1013chw Pump 2 Run FeedbackRead0=Stopped, 1=Running
BI1014chw Pump 2 AlarmRead0=Ok, 1=Alarm
BI1015chw Pump 3 Run FeedbackRead0=Stopped, 1=Running
BI1016chw Pump 3 AlarmRead0=Ok, 1=Alarm
BI1031Chiller 1 Run FeedbackRead0=Stopped, 1=Running
BI1032Chiller 1 AlarmRead0=Ok, 1=Alarm
BI1033Chiller 1 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1034Chiller 2 Run FeedbackRead0=Stopped, 1=Running
BI1035Chiller 2 AlarmRead0=Ok, 1=Alarm
BI1036Chiller 2 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1037Chiller 3 Run FeedbackRead0=Stopped, 1=Running
BI1038Chiller 3 AlarmRead0=Ok, 1=Alarm
BI1039Chiller 3 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1046chw Bypass Valve Pos Fbk AlarmRead0=Ok, 1=Alarm
BI1047Chiller 1 chw Iso Valve StatusRead0=Close, 1=Open
BI1048Chiller 2 chw Iso Valve StatusRead0=Close, 1=Open
BI1049Chiller 3 chw Iso Valve StatusRead0=Close, 1=Open
BV1001chw Bypass Valve Hand/AutoWrite0=Hand, 1=Auto
BV1002Chiller 1 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1003Chiller 2 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1004Chiller 3 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1007Chiller 1 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1008Chiller 2 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1009Chiller 3 chw Iso Valve Hand CommandWrite0=Close, 1=Open
AO1001chw Bypass Valve Hand PositionRange 0 to 100.0%Write
AO1002chw Pump 1 Hand SpeedRange 0 to 100.0%Write
AO1003chw Pump 2 Hand SpeedRange 0 to 100.0%Write
AO1004chw Pump 3 Hand SpeedRange 0 to 100.0%Write
AImin1Plant EfficiencykW/TonRead
AImin2Total Plant Power ConsumptionkWRead
AImin3Plant LoadtonsRead
AI4Dry Bulb Air Temp°F or °CRead
AI5Relative HumidityRange 0 to 100.0%Read
AI6Sensorless HeadfeetRead
AI7Sensorless FlowusgpmRead
AI9Zone 1 PVpsi, ft, kPA, m, °F, or °CRead
AI10Zone 1 Errorpsi, ft, kPA, m, °F, or °CRead
AV1Max Open Cooling Valve Position FdbkRange 0 to 100.0%Write
AVmin2Zone 1 Setpointpsi, ft, kPA, m, °F, or °CWrite
AImin1001chws Temp°F or °CRead
AImin1002chwr Temp°F or °CRead
AI1003chw Flowusgpm, lps, m3/hrRead
AI1004chwp DPpsi, ft, kPA, mRead
AI1005System DPpsi, ft, kPA, mRead
AI1006Chiller 1 Leaving chw Temperature°F or °CRead
AI1007Chiller 1 Entering chw Temperature°F or °CRead
AI1008Chiller 1 PowerkWRead
AI1009Chiller 2 Leaving chw Temperature°F or °CRead
AI1010Chiller 2 Entering chw Temperature°F or °CRead
AI1011Chiller 2 PowerkWRead
AI1012Chiller 3 Leaving chw Temperature°F or °CRead
AI1013Chiller 3 Entering chw Temperature°F or °CRead
AI1014Chiller 3 PowerkWRead
AI1021chw Pump 1 Drive PowerkWRead
AI1022chw Pump 1 Drive Volt ACVACRead
AI1023chw Pump 1 Drive AmpAmpRead
AI1024chw Pump 1 Drive Speed FeedbackRange 0 to 100.0%Read
AI1025chw Pump 2 Drive PowerkWRead
AI1026chw Pump 2 Drive Volt ACVACRead
AI1027chw Pump 2 Drive AmpAmpRead
AI1028chw Pump 2 Drive Speed FeedbackRange 0 to 100.0%Read
AI1029chw Pump 3 Drive PowerkWRead
AI1030chw Pump 3 Drive Volt ACVACRead
AI1031chw Pump 3 Drive AmpAmpRead
AI1032chw Pump 3 Drive Speed FeedbackRange 0 to 100.0%Read
AI1061chw Pump 1 Run HourshoursRead
AI1062chw Pump 2 Run HourshoursRead
AI1063chw Pump 3 Run HourshoursRead
AI1071Chiller 1 Run HourshoursRead
AI1072Chiller 2 Run HourshoursRead
AI1073Chiller 3 Run HourshoursRead
AI1076chw Bypass Valve PositionRange 0 to 100.0%Read
AI2001Chiller 1 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2002Chiller 1 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2003Chiller 2 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2004Chiller 2 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2005Chiller 3 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2006Chiller 3 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2011chw Pump 1 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2012chw Pump 2 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2013chw Pump 3 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AV2001Chiller 1 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2002Chiller 2 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2003Chiller 3 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2006chw Pump 1 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2007chw Pump 2 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2008chw Pump 3 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2016Set Lead ChillerWrite 1 to 5; acted on when the value changesWrite
AV2017Set Lead chw PumpWrite 1 to 5; acted on when the value changesWrite
Object ID lookup: Armstrong Fluid Technology SE-A10 chiller plant controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SE-A10 chiller plant controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Armstrong Fluid Technology SE-A10 chiller plant controller

How many BACnet points does the Armstrong Fluid Technology SE-A10 chiller plant controller have?

This list has 106 BACnet objects: 51 analog inputs, 4 analog outputs, 10 analog values, 31 binary inputs, 3 binary outputs, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Armstrong Fluid Technology SE-A10 chiller plant controller BACnet points are writable?

24 of the 106 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Armstrong Fluid Technology SE-A10 chiller plant controller BACnet documentation?

The source is SE-A10 Data points (BAS data points - BACnet, Communication Interface Rev 24.111) (90.7671), revision 2025-07-10, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-7671_se_a10_datapoints.pdf.

What are the minimum BACnet points to integrate the Armstrong Fluid Technology SE-A10 chiller plant controller?

Start with BO 1 Remote Start (Plant start/stop from the BMS (1 = start)); AV 2 Zone 1 Setpoint (Zone 1 control setpoint); BO 3 Alarm Reset (Reset plant alarms (positive edge)); BI 1 Plant Status (Plant on/off status); AI 3 Plant Load (Plant cooling load, tons); AI 1001 chws Temp (Chilled water supply temperature); AI 1002 chwr Temp (Chilled water return temperature); AI 2 Total Plant Power Consumption (Total plant power, kW); AI 1 Plant Efficiency (Plant efficiency, kW/ton); BI 10 Refrigerant Leak Alarm (Refrigerant leak detected).

How do I enable BMS control of the Armstrong Fluid Technology SE-A10 chiller plant controller?

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

How do I check these points on the real SE-A10 chiller plant controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Armstrong Fluid Technology BACnet points lists