Chiller plant controller (water-cooled chillers, pumps and towers) · BACnet points list

Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet points list

Updated 6 November 2026

Short answer

The IPC 9521 is Armstrong's earlier water-cooled chilled water plant controller. Its BACnet object list covers plant start/stop, alarm reset, chiller group select, plant load, power and efficiency, chilled and condenser water temperatures and flows, chiller, pump and tower status and alarms, drive data and Hand/Auto overrides. The numbering is close to the EE-W20, but many object names differ.

This page lists 468 BACnet objects for the Armstrong Fluid Technology IPC 9521 chilled water plant controller — 99 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.

Manufacturer
Armstrong Fluid Technology
Model
IPC 9521 chilled water plant controller
Equipment
Chiller plant controller (water-cooled chillers, pumps and towers)
Equipment type
Chillers
BACnet objects
468 (99 writable)
Transport
—
Firmware
Communication interface Rev 18.122
Also known as
IPC 9521, IPC9521, Armstrong IPC 9521, 90.874
Source document
IPC 9521 Data points (Communication Interface Rev 18.122) · 90.874 · rev. 2019-09-16
Download CSV 468 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.

BMS integration notes: Armstrong Fluid Technology IPC 9521 chilled water plant controller

Integration in brief

The IPC 9521 publishes a fixed BACnet object list. Start and stop the plant with BO 1 Remote Start, write the zone setpoint (AV 2), and read BI 1 Plant Status, plant load, chilled water temperatures, plant power and efficiency. Use BO 3 to reset alarms. Per-chiller, per-pump and per-valve alarms, run feedbacks and Hand/Auto overrides are there if the BMS needs more detail.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Remote StartPlant start/stop from the BMS (1 = start)Write
AV 2Zone 1 SetpointZone 1 control setpointWrite
BO 3Alarm ResetReset plant alarms (positive edge)Write
BI 1Plant StatusPlant on/off statusRead
AI 3Plant LoadPlant cooling load, tonsRead
AI 1001chws TempChilled water supply temperatureRead
AI 1002chwr TempChilled water return temperatureRead
AI 2Total Plant Power ConsumptionTotal plant power, kWRead
AI 1Plant EfficiencyPlant efficiency, kW/tonRead
BI 10Refrigerant Leak AlarmRefrigerant leak detectedRead

Enable & remote start

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

Network setup

Watch out for

Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

468 of 468 shown
Type
Access
Show
Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet Points List
DescriptionStates
BOmin1Remote StartWrite0=Stop, 1=Start
BO2Enable Plant Stand-by Mode FeatureWrite0=False, 1=True
BOmin3Alarm ResetPositive Edge commandWrite0=n/a, 1=Reset
BO4Chiller Group SelectWrite0=Group 1, 1=Group 2
BImin1Plant StatusRead0=Off, 1=On
BI2All Zone Transmitter FailedRead0=Ok, 1=Alarm
BI3Zone 1 Transmitter FailedRead0=Ok, 1=Alarm
BI4Zone 2 Transmitter FailedRead0=Ok, 1=Alarm
BI5Zone 3 Transmitter FailedRead0=Ok, 1=Alarm
BI6Zone 4 Transmitter FailedRead0=Ok, 1=Alarm
BI7Zone 5 Transmitter FailedRead0=Ok, 1=Alarm
BI8Dry Bulb Air Temp Transmitter FailedRead0=Ok, 1=Alarm
BI9Relative Humidity Transmitter FailedRead0=Ok, 1=Alarm
BImin10Refrigerant Leak AlarmRead0=Ok, 1=Alarm
BI11Active Chiller GroupRead0=Group 1, 1=Group 2
BI1001chwS Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1002chwR Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1003chw Flow Transmitter FailedRead0=Ok, 1=Alarm
BI1004chwP dp Transmitter FailedRead0=Ok, 1=Alarm
BI1005System dp Transmitter FailedRead0=Ok, 1=Alarm
BI1006chiller 1 chw Iso Valve AlarmRead0=Ok, 1=Alarm
BI1007chiller 2 chw Iso Valve AlarmRead0=Ok, 1=Alarm
BI1008chiller 3 chw Iso Valve AlarmRead0=Ok, 1=Alarm
BI1009chiller 4 chw Iso Valve AlarmRead0=Ok, 1=Alarm
BI1010chiller 5 chw Iso Valve AlarmRead0=Ok, 1=Alarm
BI1011chw Pump 1a Run FeedbackRead0=Stopped, 1=Running
BI1012chw Pump 1a AlarmRead0=Ok, 1=Alarm
BI1013chw Pump 2a Run FeedbackRead0=Stopped, 1=Running
BI1014chw Pump 2a AlarmRead0=Ok, 1=Alarm
BI1015chw Pump 3a Run FeedbackRead0=Stopped, 1=Running
BI1016chw Pump 3a AlarmRead0=Ok, 1=Alarm
BI1017chw Pump 4a Run FeedbackRead0=Stopped, 1=Running
BI1018chw Pump 4a AlarmRead0=Ok, 1=Alarm
BI1019chw Pump 5a Run FeedbackRead0=Stopped, 1=Running
BI1020chw Pump 5a AlarmRead0=Ok, 1=Alarm
BI1021chw Pump 1b Run FeedbackRead0=Stopped, 1=Running
BI1022chw Pump 1b AlarmRead0=Ok, 1=Alarm
BI1023chw Pump 2b Run FeedbackRead0=Stopped, 1=Running
BI1024chw Pump 2b AlarmRead0=Ok, 1=Alarm
BI1025chw Pump 3b Run FeedbackRead0=Stopped, 1=Running
BI1026chw Pump 3b AlarmRead0=Ok, 1=Alarm
BI1027chw Pump 4b Run FeedbackRead0=Stopped, 1=Running
BI1028chw Pump 4b AlarmRead0=Ok, 1=Alarm
BI1029chw Pump 5b Run FeedbackRead0=Stopped, 1=Running
BI1030chw Pump 5b AlarmRead0=Ok, 1=Alarm
BI1031Chiller 1 Run FeedbackRead0=Stopped, 1=Running
BI1032Chiller 1 AlarmRead0=Ok, 1=Alarm
BI1033Chiller 1 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1034Chiller 2 Run FeedbackRead0=Stopped, 1=Running
BI1035Chiller 2 AlarmRead0=Ok, 1=Alarm
BI1036Chiller 2 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1037Chiller 3 Run FeedbackRead0=Stopped, 1=Running
BI1038Chiller 3 AlarmRead0=Ok, 1=Alarm
BI1039Chiller 3 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1040Chiller 4 Run FeedbackRead0=Stopped, 1=Running
BI1041Chiller 4 AlarmRead0=Ok, 1=Alarm
BI1042Chiller 4 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1043Chiller 5 Run FeedbackRead0=Stopped, 1=Running
BI1044Chiller 5 AlarmRead0=Ok, 1=Alarm
BI1045Chiller 5 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1046chw Bypass Valve Pos Fbk AlarmRead0=Ok, 1=Alarm
BI1047Chiller 1 chw Iso Valve StatusRead0=Close, 1=Open
BI1048Chiller 2 chw Iso Valve StatusRead0=Close, 1=Open
BI1049Chiller 3 chw Iso Valve StatusRead0=Close, 1=Open
BI1050Chiller 4 chw Iso Valve StatusRead0=Close, 1=Open
BI1051Chiller 5 chw Iso Valve StatusRead0=Close, 1=Open
BI3001cw Inlet Temp Transmitter FailedRead0=Ok, 1=Alarm
BI3002cw Outlet Temp Transmitter FailedRead0=Ok, 1=Alarm
BI3003cw Flow Transmitter FailedRead0=Ok, 1=Alarm
BI3004cw dp Transmitter FailedRead0=Ok, 1=Alarm
BI3005chiller 1 cw Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3006chiller 2 cw Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3007chiller 3 cw Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3008chiller 4 cw Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3009chiller 5 cw Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3010chiller 1 cw Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3011chiller 2 cw Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3012chiller 3 cw Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3013chiller 4 cw Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3014chiller 5 cw Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3015cw Pump 1a Run FeedbackRead0=Stopped, 1=Running
BI3016cw Pump 1a AlarmRead0=Ok, 1=Alarm
BI3017cw Pump 2a Run FeedbackRead0=Stopped, 1=Running
BI3018cw Pump 2a AlarmRead0=Ok, 1=Alarm
BI3019cw Pump 3a Run FeedbackRead0=Stopped, 1=Running
BI3020cw Pump 3a AlarmRead0=Ok, 1=Alarm
BI3021cw Pump 4a Run FeedbackRead0=Stopped, 1=Running
BI3022cw Pump 4a AlarmRead0=Ok, 1=Alarm
BI3023cw Pump 5a Run FeedbackRead0=Stopped, 1=Running
BI3024cw Pump 5a AlarmRead0=Ok, 1=Alarm
BI3025cw Pump 1b Run FeedbackRead0=Stopped, 1=Running
BI3026cw Pump 1b AlarmRead0=Ok, 1=Alarm
BI3027cw Pump 2b Run FeedbackRead0=Stopped, 1=Running
BI3028cw Pump 2b AlarmRead0=Ok, 1=Alarm
BI3029cw Pump 3b Run FeedbackRead0=Stopped, 1=Running
BI3030cw Pump 3b AlarmRead0=Ok, 1=Alarm
BI3031cw Pump 4b Run FeedbackRead0=Stopped, 1=Running
BI3032cw Pump 4b AlarmRead0=Ok, 1=Alarm
BI3033cw Pump 5b Run FeedbackRead0=Stopped, 1=Running
BI3034cw Pump 5b AlarmRead0=Ok, 1=Alarm
BI3035Tower 1 Fan Run FeedbackRead0=Stopped, 1=Running
BI3036Tower 1 Fan AlarmRead0=Ok, 1=Alarm
BI3037Tower 2 Fan Run FeedbackRead0=Stopped, 1=Running
BI3038Tower 2 Fan AlarmRead0=Ok, 1=Alarm
BI3039Tower 3 Fan Run FeedbackRead0=Stopped, 1=Running
BI3040Tower 3 Fan AlarmRead0=Ok, 1=Alarm
BI3041Tower 4 Fan Run FeedbackRead0=Stopped, 1=Running
BI3042Tower 4 Fan AlarmRead0=Ok, 1=Alarm
BI3043Tower 5 Fan Run FeedbackRead0=Stopped, 1=Running
BI3044Tower 5 Fan AlarmRead0=Ok, 1=Alarm
BI3045Tower 1 Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3046Tower 2 Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3047Tower 3 Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3048Tower 4 Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3049Tower 5 Iso Valve Open AlarmRead0=Ok, 1=Alarm
BI3050Tower 1 Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3051Tower 2 Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3052Tower 3 Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3053Tower 4 Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3054Tower 5 Iso Valve Close AlarmRead0=Ok, 1=Alarm
BI3055cw Bypass Valve Pos Fbk AlarmRead0=Ok, 1=Alarm
BI3056Tower Water High Level AlarmRead0=Ok, 1=Alarm
BI3057Tower Water Low Level AlarmRead0=Ok, 1=Alarm
BI3058High Daily ct Water Consumption AlarmRead0=Ok, 1=Alarm
BI3059High-High Daily ct Water Cons AlarmRead0=Ok, 1=Alarm
BI3060Low Tower Water Cycles of OperationRead0=Ok, 1=Alarm
BI3061Water Treatment Run FeedbackRead0=Stopped, 1=Running
BI3062Solid Separator Sys Run FeedbackRead0=Stopped, 1=Running
BI3063Heat Trace Operation FeedbackRead0=Stopped, 1=Running
BI3064Water Treatment Run Feedback AlarmRead0=Ok, 1=Alarm
BI3065Solid Separator Sys Run Fdbk AlarmRead0=Ok, 1=Alarm
BI3066Heat Trace Operation Feedback AlarmRead0=Ok, 1=Alarm
BI3067Chiller 1 cw Iso Valve StatusRead0=Close, 1=Open
BI3068Chiller 2 cw Iso Valve StatusRead0=Close, 1=Open
BI3069Chiller 3 cw Iso Valve StatusRead0=Close, 1=Open
BI3070Chiller 4 cw Iso Valve StatusRead0=Close, 1=Open
BI3071Chiller 5 cw Iso Valve StatusRead0=Close, 1=Open
BI3072Cooling Tower 1 Iso Valve StatusRead0=Close, 1=Open
BI3073Cooling Tower 2 Iso Valve StatusRead0=Close, 1=Open
BI3074Cooling Tower 3 Iso Valve StatusRead0=Close, 1=Open
BI3075Cooling Tower 4 Iso Valve StatusRead0=Close, 1=Open
BI3076Cooling Tower 5 Iso Valve StatusRead0=Close, 1=Open
BV1001chw Bypass Valve Hand/AutoWrite0=Hand, 1=Auto
BV1002Chiller 1 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1003Chiller 2 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1004Chiller 3 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1005Chiller 4 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1006Chiller 5 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1007Chiller 1 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1008Chiller 2 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1009Chiller 3 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1010Chiller 4 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1011Chiller 5 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3001cw Bypass Valve Hand/AutoWrite0=Hand, 1=Auto
BV3002Chiller 1 cw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3003Chiller 2 cw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3004Chiller 3 cw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3005Chiller 4 cw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3006Chiller 5 cw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3007Chiller 1 cw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3008Chiller 2 cw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3009Chiller 3 cw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3010Chiller 4 cw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3011Chiller 5 cw Iso Valve Hand CommandWrite0=Close, 1=Open
BV3012Tower 1 Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3013Tower 2 Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3014Tower 3 Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3015Tower 4 Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3016Tower 5 Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV3017Tower 1 Iso Valve Hand CommandWrite0=Close, 1=Open
BV3018Tower 2 Iso Valve Hand CommandWrite0=Close, 1=Open
BV3019Tower 3 Iso Valve Hand CommandWrite0=Close, 1=Open
BV3020Tower 4 Iso Valve Hand CommandWrite0=Close, 1=Open
BV3021Tower 5 Iso Valve Hand CommandWrite0=Close, 1=Open
AImin1Plant EfficiencykW/TonRead
AImin2Total Plant Power ConsumptionkWRead
AImin3Plant LoadtonsRead
AI4Dry Bulb Air Temp°f or °cRead
AI5Relative HumidityRange 0 to 100.0%Read
AI6Sensorless HeadfeetRead
AI7Sensorless FlowusgpmRead
AI9Zone 1 pvpsi, ft, kPa, m,°f or °cRead
AI10Zone 1 Errorpsi, ft, kPa, m,°f or °cRead
AI11Zone 2 pvpsi, ft, kPa, m,°f or °cRead
AI12Zone 2 Errorpsi, ft, kPa, m,°f or °cRead
AI13Zone 3 pvpsi, ft, kPa, m,°f or °cRead
AI14Zone 3 Errorpsi, ft, kPa, m,°f or °cRead
AI15Zone 4 pvpsi, ft, kPa, m,°f or °cRead
AI16Zone 4 Errorpsi, ft, kPa, m,°f or °cRead
AI17Zone 5 pvpsi, ft, kPa, m,°f or °cRead
AI18Zone 5 Errorpsi, ft, kPa, m,°f or °cRead
AV1Max Open Cooling Valve Position FdbckRange 0 to 100.0%Write
AVmin2Zone 1 Setpointpsi, ft, kPa, m,°f or °cWrite
AV3Zone 2 Setpointpsi, ft, kPa, m,°f or °cWrite
AV4Zone 3 Setpointpsi, ft, kPa, m,°f or °cWrite
AV5Zone 4 Setpointpsi, ft, kPa, m,°f or °cWrite
AV6Zone 5 Setpointpsi, ft, kPa, m,°f or °cWrite
AImin1001chws Temp°f or °cRead
AImin1002chwr Temp°f or °cRead
AI1003chw Flowusgpm, lps, m3/hrRead
AI1004chwp dppsi, ft, kPa, mRead
AI1005System dppsi, ft, kPa, mRead
AI1006Chiller 1 Leaving chw Temperature°f or °cRead
AI1007Chiller 1 Entering chw Temperature°f or °cRead
AI1008Chiller 1 PowerkWRead
AI1009Chiller 2 Leaving chw Temperature°f or °cRead
AI1010Chiller 2 Entering chw Temperature°f or °cRead
AI1011Chiller 2 PowerkWRead
AI1012Chiller 3 Leaving chw Temperature°f or °cRead
AI1013Chiller 3 Entering chw Temperature°f or °cRead
AI1014Chiller 3 PowerkWRead
AI1015Chiller 4 Leaving chw Temperature°f or °cRead
AI1016Chiller 4 Entering chw Temperature°f or °cRead
AI1017Chiller 4 PowerkWRead
AI1018Chiller 5 Leaving chw Temperature°f or °cRead
AI1019Chiller 5 Entering chw Temperature°f or °cRead
AI1020Chiller 5 PowerkWRead
AI1021chw Pump 1a Drive PowerkWRead
AI1022chw Pump 1a Drive Volt acVACRead
AI1023chw Pump 1a Drive AmpAmpRead
AI1024chw Pump 1a Drive Speed FeedbackRange 0 to 100.0%Read
AI1025chw Pump 2a Drive PowerkWRead
AI1026chw Pump 2a Drive Volt acVACRead
AI1027chw Pump 2a Drive AmpAmpRead
AI1028chw Pump 2a Drive Speed FeedbackRange 0 to 100.0%Read
AI1029chw Pump 3a Drive PowerkWRead
AI1030chw Pump 3a Drive Volt acVACRead
AI1031chw Pump 3a Drive AmpAmpRead
AI1032chw Pump 3a Drive Speed FeedbackRange 0 to 100.0%Read
AI1033chw Pump 4a Drive PowerkWRead
AI1034chw Pump 4a Drive Volt acVACRead
AI1035chw Pump 4a Drive AmpAmpRead
AI1036chw Pump 4a Drive Speed FeedbackRange 0 to 100.0%Read
AI1037chw Pump 5a Drive PowerkWRead
AI1038chw Pump 5a Drive Volt acVACRead
AI1039chw Pump 5a Drive AmpAmpRead
AI1040chw Pump 5a Drive Speed FeedbackRange 0 to 100.0%Read
AI1041chw Pump 1b Drive PowerkWRead
AI1042chw Pump 1b Drive Volt acVACRead
AI1043chw Pump 1b Drive AmpAmpRead
AI1044chw Pump 1b Drive Speed FeedbackRange 0 to 100.0%Read
AI1045chw Pump 2b Drive PowerkWRead
AI1046chw Pump 2b Drive Volt acVACRead
AI1047chw Pump 2b Drive AmpAmpRead
AI1048chw Pump 2b Drive Speed FeedbackRange 0 to 100.0%Read
AI1049chw Pump 3b Drive PowerkWRead
AI1050chw Pump 3b Drive Volt acVACRead
AI1051chw Pump 3b Drive AmpAmpRead
AI1052chw Pump 3b Drive Speed FeedbackRange 0 to 100.0%Read
AI1053chw Pump 4b Drive PowerkWRead
AI1054chw Pump 4b Drive Volt acVACRead
AI1055chw Pump 4b Drive AmpAmpRead
AI1056chw Pump 4b Drive Speed FeedbackRange 0 to 100.0%Read
AI1057chw Pump 5b Drive PowerkWRead
AI1058chw Pump 5b Drive Volt acVACRead
AI1059chw Pump 5b Drive AmpAmpRead
AI1060chw Pump 5b Drive Speed FeedbackRange 0 to 100.0%Read
AI1061chw Pump 1a Run HourshoursRead
AI1062chw Pump 2a Run HourshoursRead
AI1063chw Pump 3a Run HourshoursRead
AI1064chw Pump 4a Run HourshoursRead
AI1065chw Pump 5a Run HourshoursRead
AI1066chw Pump 1b Run HourshoursRead
AI1067chw Pump 2b Run HourshoursRead
AI1068chw Pump 3b Run HourshoursRead
AI1069chw Pump 4b Run HourshoursRead
AI1070chw Pump 5b Run HourshoursRead
AI1071Chiller 1 Run HourshoursRead
AI1072Chiller 2 Run HourshoursRead
AI1073Chiller 3 Run HourshoursRead
AI1074Chiller 4 Run HourshoursRead
AI1075Chiller 5 Run HourshoursRead
AI1076chw Bypass Valve PositionRange 0 to 100.0%Read
AI2001Chiller 1 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2002Chiller 1 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2003Chiller 2 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2004Chiller 2 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2005Chiller 3 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2006Chiller 3 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2007Chiller 4 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2008Chiller 4 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2009Chiller 5 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2010Chiller 5 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2011chw Pump 1 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2012chw Pump 2 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2013chw Pump 3 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2014chw Pump 4 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2015chw Pump 5 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2016chw Pump 1a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2017chw Pump 2a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2018chw Pump 3a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2019chw Pump 4a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2020chw Pump 5a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2021chw Pump 1b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2022chw Pump 2b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2023chw Pump 3b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2024chw Pump 4b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2025chw Pump 5b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AV2001Chiller 1 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2002Chiller 2 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2003Chiller 3 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2004Chiller 4 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2005Chiller 5 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2006chw Pump 1/1a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2007chw Pump 2/2a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2008chw Pump 3/3a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2009chw Pump 4/4a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2010chw Pump 5/5a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2011chw Pump 1b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2012chw Pump 2b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2013chw Pump 3b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2014chw Pump 4b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2015chw Pump 5b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AI3001cw Inlet Temp°f or °cRead
AI3002cw Outlet Temp°f or °cRead
AI3003cw Flowusgpm, lps, m3/hrRead
AI3004cwp dppsi, ft, kPa, mRead
AI3005Chiller 1 Leaving cw Temperature°f or °cRead
AI3006Chiller 1 Entering cw Temperature°f or °cRead
AI3007Chiller 2 Leaving cw Temperature°f or °cRead
AI3008Chiller 2 Entering cw Temperature°f or °cRead
AI3009Chiller 3 Leaving cw Temperature°f or °cRead
AI3010Chiller 3 Entering cw Temperature°f or °cRead
AI3011Chiller 4 Leaving cw Temperature°f or °cRead
AI3012Chiller 4 Entering cw Temperature°f or °cRead
AI3013Chiller 5 Leaving cw Temperature°f or °cRead
AI3014Chiller 5 Entering cw Temperature°f or °cRead
AI3015cw Pump 1a Drive PowerkWRead
AI3016cw Pump 1a Drive Volt acVACRead
AI3017cw Pump 1a Drive AmpAmpRead
AI3018cw Pump 1a Drive Speed FeedbackRange 0 to 100.0%Read
AI3019cw Pump 2a Drive PowerkWRead
AI3020cw Pump 2a Drive Volt acVACRead
AI3021cw Pump 2a Drive AmpAmpRead
AI3022cw Pump 2a Drive Speed FeedbackRange 0 to 100.0%Read
AI3023cw Pump 3a Drive PowerkWRead
AI3024cw Pump 3a Drive Volt acVACRead
AI3025cw Pump 3a Drive AmpAmpRead
AI3026cw Pump 3a Drive Speed FeedbackRange 0 to 100.0%Read
AI3027cw Pump 4a Drive PowerkWRead
AI3028cw Pump 4a Drive Volt acVACRead
AI3029cw Pump 4a Drive AmpAmpRead
AI3030cw Pump 4a Drive Speed FeedbackRange 0 to 100.00 % to 100.0Read
AI3031cw Pump 5a Drive PowerkWRead
AI3032cw Pump 5a Drive Volt acVACRead
AI3033cw Pump 5a Drive AmpAmpRead
AI3034cw Pump 5a Drive Speed FeedbackRange 0 to 100.0%Read
AI3035cw Pump 1b Drive PowerkWRead
AI3036cw Pump 1b Drive Volt acVACRead
AI3037cw Pump 1b Drive AmpAmpRead
AI3038cw Pump 1b Drive Speed FeedbackRange 0 to 100.0%Read
AI3039cw Pump 2b Drive PowerkWRead
AI3040cw Pump 2b Drive Volt acVACRead
AI3041cw Pump 2b Drive AmpAmpRead
AI3042cw Pump 2b Drive Speed FeedbackRange 0 to 100.0%Read
AI3043cw Pump 3b Drive PowerkWRead
AI3044cw Pump 3b Drive Volt acVACRead
AI3045cw Pump 3b Drive AmpAmpRead
AI3046cw Pump 3b Drive Speed FeedbackRange 0 to 100.0%Read
AI3047cw Pump 4b Drive PowerkWRead
AI3048cw Pump 4b Drive Volt acVACRead
AI3049cw Pump 4b Drive AmpAmpRead
AI3050cw Pump 4b Drive Speed FeedbackRange 0 to 100.0%Read
AI3051cw Pump 5b Drive PowerkWRead
AI3052cw Pump 5b Drive Volt acVACRead
AI3053cw Pump 5b Drive AmpAmpRead
AI3054cw Pump 5b Drive Speed FeedbackRange 0 to 100.0%Read
AI3055Tower 1 Fan Drive PowerkWRead
AI3056Tower 1 Fan Drive Volt acVACRead
AI3057Tower 1 Fan Drive AmpAmpRead
AI3058Tower 1 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI3059Tower 2 Fan Drive PowerkWRead
AI3060Tower 2 Fan Drive Volt acVACRead
AI3061Tower 2 Fan Drive AmpAmpRead
AI3062Tower 2 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI3063Tower 3 Fan Drive PowerkWRead
AI3064Tower 3 Fan Drive Volt acVACRead
AI3065Tower 3 Fan Drive AmpAmpRead
AI3066Tower 3 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI3067Tower 4 Fan Drive PowerkWRead
AI3068Tower 4 Fan Drive Volt acVACRead
AI3069Tower 4 Fan Drive AmpAmpRead
AI3070Tower 4 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI3071Tower 5 Fan Drive PowerkWRead
AI3072Tower 5 Fan Drive Volt acVACRead
AI3073Tower 5 Fan Drive AmpAmpRead
AI3074Tower 5 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI3075cw Pump 1/1a Run HourshoursRead
AI3076cw Pump 2/2a Run HourshoursRead
AI3077cw Pump 3/3a Run HourshoursRead
AI3078cw Pump 4/4a Run HourshoursRead
AI3079cw Pump 5/5a Run HourshoursRead
AI3080cw Pump 1b Run HourshoursRead
AI3081cw Pump 2b Run HourshoursRead
AI3082cw Pump 3b Run HourshoursRead
AI3083cw Pump 4b Run HourshoursRead
AI3084cw Pump 5b Run HourshoursRead
AI3085Tower 1 Run HourshoursRead
AI3086Tower 2 Run HourshoursRead
AI3087Tower 3 Run HourshoursRead
AI3088Tower 4 Run HourshoursRead
AI3089Tower 5 Run HourshoursRead
AI3090Make up water daily consumptionGallons or LitersRead
AI3091Blowdown water daily consumptionGallons or LitersRead
AI3092Cycles of concentrationRead
AI3093cw Bypass Valve PositionRange 0 to 100.0%Read
AI4001cw Pump 1 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4002cw Pump 2 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4003cw Pump 3 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4004cw Pump 4 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4005cw Pump 5 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4006cw Pump 1a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4007cw Pump 2a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4008cw Pump 3a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4009cw Pump 4a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4010cw Pump 5a Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4011cw Pump 1b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4012cw Pump 2b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4013cw Pump 3b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4014cw Pump 4b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4015cw Pump 5b Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4016Tower 1 Duty StandbyCoded value, range 0 to 5Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4017Tower 2 Duty StandbyCoded value, range 0 to 5Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4018Tower 3 Duty StandbyCoded value, range 0 to 5Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4019Tower 4 Duty StandbyCoded value, range 0 to 5Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI4020Tower 5 Duty StandbyCoded value, range 0 to 5Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AV4001cw Pump 1/1a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4002cw Pump 2/2a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4003cw Pump 3/3a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4004cw Pump 4/4a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4005cw Pump 5/5a ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4006cw Pump 1b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4007cw Pump 2b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4008cw Pump 3b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4009cw Pump 4b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4010cw Pump 5b ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4011Tower 1 Fan ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4012Tower 2 Fan ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4013Tower 3 Fan ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4014Tower 4 Fan ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4015Tower 5 Fan ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AO1001chw Bypass Valve Hand PositionRange 0 to 100.0%Write
AO1002chw Pump 1/1a Hand SpeedRange 0 to 100.0%Write
AO1003chw Pump 2/2a Hand SpeedRange 0 to 100.0%Write
AO1004chw Pump 3/3a Hand SpeedRange 0 to 100.0%Write
AO1005chw Pump 4/4a Hand SpeedRange 0 to 100.0%Write
AO1006chw Pump 5/5a Hand SpeedRange 0 to 100.0%Write
AO1007chw Pump 1b Hand SpeedRange 0 to 100.0%Write
AO1008chw Pump 2b Hand SpeedRange 0 to 100.0%Write
AO1009chw Pump 3b Hand SpeedRange 0 to 100.0%Write
AO1010chw Pump 4b Hand SpeedRange 0 to 100.0%Write
AO1011chw Pump 5b Hand SpeedRange 0 to 100.0%Write
AO3001cw Bypass Valve Hand PositionRange 0 to 100.0%Write
AO3002cw Pump 1/1a Hand SpeedRange 0 to 100.0%Write
AO3003cw Pump 2/2a Hand SpeedRange 0 to 100.0%Write
AO3004cw Pump 3/3a Hand SpeedRange 0 to 100.0%Write
AO3005cw Pump 4/4a Hand SpeedRange 0 to 100.0%Write
AO3006cw Pump 5/5a Hand SpeedRange 0 to 100.0%Write
AO3007cw Pump 1b Hand SpeedRange 0 to 100.0%Write
AO3008cw Pump 2b Hand SpeedRange 0 to 100.0%Write
AO3009cw Pump 3b Hand SpeedRange 0 to 100.0%Write
AO3010cw Pump 4b Hand SpeedRange 0 to 100.0%Write
AO3011cw Pump 5b Hand SpeedRange 0 to 100.0%Write
AO3012Tower 1 Fan Hand SpeedRange 0 to 100.0%Write
AO3013Tower 2 Fan Hand SpeedRange 0 to 100.0%Write
AO3014Tower 3 Fan Hand SpeedRange 0 to 100.0%Write
AO3015Tower 4 Fan Hand SpeedRange 0 to 100.0%Write
AO3016Tower 5 Fan Hand SpeedRange 0 to 100.0%Write
Object ID lookup: Armstrong Fluid Technology IPC 9521 chilled water plant controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IPC 9521 chilled water plant controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Armstrong Fluid Technology IPC 9521 chilled water plant controller

How many BACnet points does the Armstrong Fluid Technology IPC 9521 chilled water plant controller have?

This list has 468 BACnet objects: 231 analog inputs, 27 analog outputs, 36 analog values, 138 binary inputs, 4 binary outputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet points are writable?

99 of the 468 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet documentation?

The source is IPC 9521 Data points (Communication Interface Rev 18.122) (90.874), revision 2019-09-16, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-874_ipc9521_datapoints_iando.pdf.

What are the minimum BACnet points to integrate the Armstrong Fluid Technology IPC 9521 chilled water plant controller?

Start with BO 1 Remote Start (Plant start/stop from the BMS (1 = start)); AV 2 Zone 1 Setpoint (Zone 1 control setpoint); BO 3 Alarm Reset (Reset plant alarms (positive edge)); BI 1 Plant Status (Plant on/off status); AI 3 Plant Load (Plant cooling load, tons); AI 1001 chws Temp (Chilled water supply temperature); AI 1002 chwr Temp (Chilled water return temperature); AI 2 Total Plant Power Consumption (Total plant power, kW); AI 1 Plant Efficiency (Plant efficiency, kW/ton); BI 10 Refrigerant Leak Alarm (Refrigerant leak detected).

How do I enable BMS control of the Armstrong Fluid Technology IPC 9521 chilled water plant controller?

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

How do I check these points on the real IPC 9521 chilled water plant controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Armstrong Fluid Technology BACnet points lists

Source: IPC 9521 Data points (Communication Interface Rev 18.122) · 90.874 · rev. 2019-09-16. Object names, instances and units are reproduced as published; descriptions are our own.