- Home
- BACnet points lists
- Armstrong Fluid Technology
- IPC 9521 chilled water plant controller
Chiller plant controller (water-cooled chillers, pumps and towers) · BACnet points list
Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet points list
Updated 6 November 2026
The IPC 9521 is Armstrong's earlier water-cooled chilled water plant controller. Its BACnet object list covers plant start/stop, alarm reset, chiller group select, plant load, power and efficiency, chilled and condenser water temperatures and flows, chiller, pump and tower status and alarms, drive data and Hand/Auto overrides. The numbering is close to the EE-W20, but many object names differ.
This page lists 468 BACnet objects for the Armstrong Fluid Technology IPC 9521 chilled water plant controller — 99 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.
- Manufacturer
- Armstrong Fluid Technology
- Model
- IPC 9521 chilled water plant controller
- Equipment
- Chiller plant controller (water-cooled chillers, pumps and towers)
- Equipment type
- Chillers
- BACnet objects
- 468 (99 writable)
- Transport
- —
- Firmware
- Communication interface Rev 18.122
- Also known as
- IPC 9521, IPC9521, Armstrong IPC 9521, 90.874
Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.
BMS integration notes: Armstrong Fluid Technology IPC 9521 chilled water plant controller
The IPC 9521 publishes a fixed BACnet object list. Start and stop the plant with BO 1 Remote Start, write the zone setpoint (AV 2), and read BI 1 Plant Status, plant load, chilled water temperatures, plant power and efficiency. Use BO 3 to reset alarms. Per-chiller, per-pump and per-valve alarms, run feedbacks and Hand/Auto overrides are there if the BMS needs more detail.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Remote Start | Plant start/stop from the BMS (1 = start) | Write |
| AV 2 | Zone 1 Setpoint | Zone 1 control setpoint | Write |
| BO 3 | Alarm Reset | Reset plant alarms (positive edge) | Write |
| BI 1 | Plant Status | Plant on/off status | Read |
| AI 3 | Plant Load | Plant cooling load, tons | Read |
| AI 1001 | chws Temp | Chilled water supply temperature | Read |
| AI 1002 | chwr Temp | Chilled water return temperature | Read |
| AI 2 | Total Plant Power Consumption | Total plant power, kW | Read |
| AI 1 | Plant Efficiency | Plant efficiency, kW/ton | Read |
| BI 10 | Refrigerant Leak Alarm | Refrigerant leak detected | Read |
Enable & remote start
BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.
Network setup
- The data-points sheet does not give the device instance, MAC address, baud rate or IP settings; get them from the controller setup.
Watch out for
- BO 3 Alarm Reset acts on a positive edge (0 to 1); write 0 again before the next reset.
- Hand/Auto BVs and Hand Command / Hand Speed objects override the plant sequence; leave them in Auto for normal operation.
- Mode AVs are coded 0-3 (1 = Hand, 2 = Off, 3 = Auto); writing them takes that equipment out of automatic sequencing.
- Set Lead Chiller / Pump objects act only when the value changes, so rewriting the same value does nothing.
Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Remote Start | Write | 0=Stop, 1=Start | ||
| BO | 2 | Enable Plant Stand-by Mode Feature | Write | 0=False, 1=True | ||
| BOmin | 3 | Alarm Reset | Positive Edge command | Write | 0=n/a, 1=Reset | |
| BO | 4 | Chiller Group Select | Write | 0=Group 1, 1=Group 2 | ||
| BImin | 1 | Plant Status | Read | 0=Off, 1=On | ||
| BI | 2 | All Zone Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 3 | Zone 1 Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 4 | Zone 2 Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 5 | Zone 3 Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 6 | Zone 4 Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 7 | Zone 5 Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 8 | Dry Bulb Air Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 9 | Relative Humidity Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BImin | 10 | Refrigerant Leak Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 11 | Active Chiller Group | Read | 0=Group 1, 1=Group 2 | ||
| BI | 1001 | chwS Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1002 | chwR Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1003 | chw Flow Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1004 | chwP dp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1005 | System dp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1006 | chiller 1 chw Iso Valve Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1007 | chiller 2 chw Iso Valve Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1008 | chiller 3 chw Iso Valve Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1009 | chiller 4 chw Iso Valve Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1010 | chiller 5 chw Iso Valve Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1011 | chw Pump 1a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1012 | chw Pump 1a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1013 | chw Pump 2a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1014 | chw Pump 2a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1015 | chw Pump 3a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1016 | chw Pump 3a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1017 | chw Pump 4a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1018 | chw Pump 4a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1019 | chw Pump 5a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1020 | chw Pump 5a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1021 | chw Pump 1b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1022 | chw Pump 1b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1023 | chw Pump 2b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1024 | chw Pump 2b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1025 | chw Pump 3b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1026 | chw Pump 3b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1027 | chw Pump 4b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1028 | chw Pump 4b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1029 | chw Pump 5b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1030 | chw Pump 5b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1031 | Chiller 1 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1032 | Chiller 1 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1033 | Chiller 1 Power Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1034 | Chiller 2 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1035 | Chiller 2 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1036 | Chiller 2 Power Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1037 | Chiller 3 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1038 | Chiller 3 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1039 | Chiller 3 Power Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1040 | Chiller 4 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1041 | Chiller 4 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1042 | Chiller 4 Power Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1043 | Chiller 5 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 1044 | Chiller 5 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1045 | Chiller 5 Power Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 1046 | chw Bypass Valve Pos Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 1047 | Chiller 1 chw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 1048 | Chiller 2 chw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 1049 | Chiller 3 chw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 1050 | Chiller 4 chw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 1051 | Chiller 5 chw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3001 | cw Inlet Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 3002 | cw Outlet Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 3003 | cw Flow Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 3004 | cw dp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 3005 | chiller 1 cw Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3006 | chiller 2 cw Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3007 | chiller 3 cw Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3008 | chiller 4 cw Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3009 | chiller 5 cw Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3010 | chiller 1 cw Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3011 | chiller 2 cw Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3012 | chiller 3 cw Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3013 | chiller 4 cw Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3014 | chiller 5 cw Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3015 | cw Pump 1a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3016 | cw Pump 1a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3017 | cw Pump 2a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3018 | cw Pump 2a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3019 | cw Pump 3a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3020 | cw Pump 3a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3021 | cw Pump 4a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3022 | cw Pump 4a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3023 | cw Pump 5a Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3024 | cw Pump 5a Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3025 | cw Pump 1b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3026 | cw Pump 1b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3027 | cw Pump 2b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3028 | cw Pump 2b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3029 | cw Pump 3b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3030 | cw Pump 3b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3031 | cw Pump 4b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3032 | cw Pump 4b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3033 | cw Pump 5b Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3034 | cw Pump 5b Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3035 | Tower 1 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3036 | Tower 1 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3037 | Tower 2 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3038 | Tower 2 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3039 | Tower 3 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3040 | Tower 3 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3041 | Tower 4 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3042 | Tower 4 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3043 | Tower 5 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3044 | Tower 5 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3045 | Tower 1 Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3046 | Tower 2 Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3047 | Tower 3 Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3048 | Tower 4 Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3049 | Tower 5 Iso Valve Open Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3050 | Tower 1 Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3051 | Tower 2 Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3052 | Tower 3 Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3053 | Tower 4 Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3054 | Tower 5 Iso Valve Close Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3055 | cw Bypass Valve Pos Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3056 | Tower Water High Level Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3057 | Tower Water Low Level Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3058 | High Daily ct Water Consumption Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3059 | High-High Daily ct Water Cons Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3060 | Low Tower Water Cycles of Operation | Read | 0=Ok, 1=Alarm | ||
| BI | 3061 | Water Treatment Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3062 | Solid Separator Sys Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3063 | Heat Trace Operation Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3064 | Water Treatment Run Feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3065 | Solid Separator Sys Run Fdbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3066 | Heat Trace Operation Feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 3067 | Chiller 1 cw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3068 | Chiller 2 cw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3069 | Chiller 3 cw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3070 | Chiller 4 cw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3071 | Chiller 5 cw Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3072 | Cooling Tower 1 Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3073 | Cooling Tower 2 Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3074 | Cooling Tower 3 Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3075 | Cooling Tower 4 Iso Valve Status | Read | 0=Close, 1=Open | ||
| BI | 3076 | Cooling Tower 5 Iso Valve Status | Read | 0=Close, 1=Open | ||
| BV | 1001 | chw Bypass Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1002 | Chiller 1 chw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1003 | Chiller 2 chw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1004 | Chiller 3 chw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1005 | Chiller 4 chw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1006 | Chiller 5 chw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 1007 | Chiller 1 chw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1008 | Chiller 2 chw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1009 | Chiller 3 chw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1010 | Chiller 4 chw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1011 | Chiller 5 chw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3001 | cw Bypass Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3002 | Chiller 1 cw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3003 | Chiller 2 cw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3004 | Chiller 3 cw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3005 | Chiller 4 cw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3006 | Chiller 5 cw Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3007 | Chiller 1 cw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3008 | Chiller 2 cw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3009 | Chiller 3 cw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3010 | Chiller 4 cw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3011 | Chiller 5 cw Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3012 | Tower 1 Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3013 | Tower 2 Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3014 | Tower 3 Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3015 | Tower 4 Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3016 | Tower 5 Iso Valve Hand/Auto | Write | 0=Hand, 1=Auto | ||
| BV | 3017 | Tower 1 Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3018 | Tower 2 Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3019 | Tower 3 Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3020 | Tower 4 Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 3021 | Tower 5 Iso Valve Hand Command | Write | 0=Close, 1=Open | ||
| AImin | 1 | Plant Efficiency | kW/Ton | Read | ||
| AImin | 2 | Total Plant Power Consumption | kW | Read | ||
| AImin | 3 | Plant Load | tons | Read | ||
| AI | 4 | Dry Bulb Air Temp | °f or °c | Read | ||
| AI | 5 | Relative Humidity | Range 0 to 100.0 | % | Read | |
| AI | 6 | Sensorless Head | feet | Read | ||
| AI | 7 | Sensorless Flow | usgpm | Read | ||
| AI | 9 | Zone 1 pv | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 10 | Zone 1 Error | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 11 | Zone 2 pv | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 12 | Zone 2 Error | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 13 | Zone 3 pv | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 14 | Zone 3 Error | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 15 | Zone 4 pv | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 16 | Zone 4 Error | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 17 | Zone 5 pv | psi, ft, kPa, m,°f or °c | Read | ||
| AI | 18 | Zone 5 Error | psi, ft, kPa, m,°f or °c | Read | ||
| AV | 1 | Max Open Cooling Valve Position Fdbck | Range 0 to 100.0 | % | Write | |
| AVmin | 2 | Zone 1 Setpoint | psi, ft, kPa, m,°f or °c | Write | ||
| AV | 3 | Zone 2 Setpoint | psi, ft, kPa, m,°f or °c | Write | ||
| AV | 4 | Zone 3 Setpoint | psi, ft, kPa, m,°f or °c | Write | ||
| AV | 5 | Zone 4 Setpoint | psi, ft, kPa, m,°f or °c | Write | ||
| AV | 6 | Zone 5 Setpoint | psi, ft, kPa, m,°f or °c | Write | ||
| AImin | 1001 | chws Temp | °f or °c | Read | ||
| AImin | 1002 | chwr Temp | °f or °c | Read | ||
| AI | 1003 | chw Flow | usgpm, lps, m3/hr | Read | ||
| AI | 1004 | chwp dp | psi, ft, kPa, m | Read | ||
| AI | 1005 | System dp | psi, ft, kPa, m | Read | ||
| AI | 1006 | Chiller 1 Leaving chw Temperature | °f or °c | Read | ||
| AI | 1007 | Chiller 1 Entering chw Temperature | °f or °c | Read | ||
| AI | 1008 | Chiller 1 Power | kW | Read | ||
| AI | 1009 | Chiller 2 Leaving chw Temperature | °f or °c | Read | ||
| AI | 1010 | Chiller 2 Entering chw Temperature | °f or °c | Read | ||
| AI | 1011 | Chiller 2 Power | kW | Read | ||
| AI | 1012 | Chiller 3 Leaving chw Temperature | °f or °c | Read | ||
| AI | 1013 | Chiller 3 Entering chw Temperature | °f or °c | Read | ||
| AI | 1014 | Chiller 3 Power | kW | Read | ||
| AI | 1015 | Chiller 4 Leaving chw Temperature | °f or °c | Read | ||
| AI | 1016 | Chiller 4 Entering chw Temperature | °f or °c | Read | ||
| AI | 1017 | Chiller 4 Power | kW | Read | ||
| AI | 1018 | Chiller 5 Leaving chw Temperature | °f or °c | Read | ||
| AI | 1019 | Chiller 5 Entering chw Temperature | °f or °c | Read | ||
| AI | 1020 | Chiller 5 Power | kW | Read | ||
| AI | 1021 | chw Pump 1a Drive Power | kW | Read | ||
| AI | 1022 | chw Pump 1a Drive Volt ac | VAC | Read | ||
| AI | 1023 | chw Pump 1a Drive Amp | Amp | Read | ||
| AI | 1024 | chw Pump 1a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1025 | chw Pump 2a Drive Power | kW | Read | ||
| AI | 1026 | chw Pump 2a Drive Volt ac | VAC | Read | ||
| AI | 1027 | chw Pump 2a Drive Amp | Amp | Read | ||
| AI | 1028 | chw Pump 2a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1029 | chw Pump 3a Drive Power | kW | Read | ||
| AI | 1030 | chw Pump 3a Drive Volt ac | VAC | Read | ||
| AI | 1031 | chw Pump 3a Drive Amp | Amp | Read | ||
| AI | 1032 | chw Pump 3a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1033 | chw Pump 4a Drive Power | kW | Read | ||
| AI | 1034 | chw Pump 4a Drive Volt ac | VAC | Read | ||
| AI | 1035 | chw Pump 4a Drive Amp | Amp | Read | ||
| AI | 1036 | chw Pump 4a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1037 | chw Pump 5a Drive Power | kW | Read | ||
| AI | 1038 | chw Pump 5a Drive Volt ac | VAC | Read | ||
| AI | 1039 | chw Pump 5a Drive Amp | Amp | Read | ||
| AI | 1040 | chw Pump 5a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1041 | chw Pump 1b Drive Power | kW | Read | ||
| AI | 1042 | chw Pump 1b Drive Volt ac | VAC | Read | ||
| AI | 1043 | chw Pump 1b Drive Amp | Amp | Read | ||
| AI | 1044 | chw Pump 1b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1045 | chw Pump 2b Drive Power | kW | Read | ||
| AI | 1046 | chw Pump 2b Drive Volt ac | VAC | Read | ||
| AI | 1047 | chw Pump 2b Drive Amp | Amp | Read | ||
| AI | 1048 | chw Pump 2b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1049 | chw Pump 3b Drive Power | kW | Read | ||
| AI | 1050 | chw Pump 3b Drive Volt ac | VAC | Read | ||
| AI | 1051 | chw Pump 3b Drive Amp | Amp | Read | ||
| AI | 1052 | chw Pump 3b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1053 | chw Pump 4b Drive Power | kW | Read | ||
| AI | 1054 | chw Pump 4b Drive Volt ac | VAC | Read | ||
| AI | 1055 | chw Pump 4b Drive Amp | Amp | Read | ||
| AI | 1056 | chw Pump 4b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1057 | chw Pump 5b Drive Power | kW | Read | ||
| AI | 1058 | chw Pump 5b Drive Volt ac | VAC | Read | ||
| AI | 1059 | chw Pump 5b Drive Amp | Amp | Read | ||
| AI | 1060 | chw Pump 5b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 1061 | chw Pump 1a Run Hours | hours | Read | ||
| AI | 1062 | chw Pump 2a Run Hours | hours | Read | ||
| AI | 1063 | chw Pump 3a Run Hours | hours | Read | ||
| AI | 1064 | chw Pump 4a Run Hours | hours | Read | ||
| AI | 1065 | chw Pump 5a Run Hours | hours | Read | ||
| AI | 1066 | chw Pump 1b Run Hours | hours | Read | ||
| AI | 1067 | chw Pump 2b Run Hours | hours | Read | ||
| AI | 1068 | chw Pump 3b Run Hours | hours | Read | ||
| AI | 1069 | chw Pump 4b Run Hours | hours | Read | ||
| AI | 1070 | chw Pump 5b Run Hours | hours | Read | ||
| AI | 1071 | Chiller 1 Run Hours | hours | Read | ||
| AI | 1072 | Chiller 2 Run Hours | hours | Read | ||
| AI | 1073 | Chiller 3 Run Hours | hours | Read | ||
| AI | 1074 | Chiller 4 Run Hours | hours | Read | ||
| AI | 1075 | Chiller 5 Run Hours | hours | Read | ||
| AI | 1076 | chw Bypass Valve Position | Range 0 to 100.0 | % | Read | |
| AI | 2001 | Chiller 1 Duty | Coded value, range 0 to 5 | Read | 0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4 | |
| AI | 2002 | Chiller 1 State | Coded value, range 0 to 7 | Read | 0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready | |
| AI | 2003 | Chiller 2 Duty | Coded value, range 0 to 5 | Read | 0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4 | |
| AI | 2004 | Chiller 2 State | Coded value, range 0 to 7 | Read | 0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready | |
| AI | 2005 | Chiller 3 Duty | Coded value, range 0 to 5 | Read | 0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4 | |
| AI | 2006 | Chiller 3 State | Coded value, range 0 to 7 | Read | 0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready | |
| AI | 2007 | Chiller 4 Duty | Coded value, range 0 to 5 | Read | 0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4 | |
| AI | 2008 | Chiller 4 State | Coded value, range 0 to 7 | Read | 0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready | |
| AI | 2009 | Chiller 5 Duty | Coded value, range 0 to 5 | Read | 0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4 | |
| AI | 2010 | Chiller 5 State | Coded value, range 0 to 7 | Read | 0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready | |
| AI | 2011 | chw Pump 1 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2012 | chw Pump 2 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2013 | chw Pump 3 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2014 | chw Pump 4 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2015 | chw Pump 5 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2016 | chw Pump 1a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2017 | chw Pump 2a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2018 | chw Pump 3a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2019 | chw Pump 4a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2020 | chw Pump 5a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2021 | chw Pump 1b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2022 | chw Pump 2b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2023 | chw Pump 3b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2024 | chw Pump 4b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 2025 | chw Pump 5b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AV | 2001 | Chiller 1 Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2002 | Chiller 2 Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2003 | Chiller 3 Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2004 | Chiller 4 Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2005 | Chiller 5 Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2006 | chw Pump 1/1a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2007 | chw Pump 2/2a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2008 | chw Pump 3/3a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2009 | chw Pump 4/4a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2010 | chw Pump 5/5a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2011 | chw Pump 1b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2012 | chw Pump 2b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2013 | chw Pump 3b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2014 | chw Pump 4b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2015 | chw Pump 5b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AI | 3001 | cw Inlet Temp | °f or °c | Read | ||
| AI | 3002 | cw Outlet Temp | °f or °c | Read | ||
| AI | 3003 | cw Flow | usgpm, lps, m3/hr | Read | ||
| AI | 3004 | cwp dp | psi, ft, kPa, m | Read | ||
| AI | 3005 | Chiller 1 Leaving cw Temperature | °f or °c | Read | ||
| AI | 3006 | Chiller 1 Entering cw Temperature | °f or °c | Read | ||
| AI | 3007 | Chiller 2 Leaving cw Temperature | °f or °c | Read | ||
| AI | 3008 | Chiller 2 Entering cw Temperature | °f or °c | Read | ||
| AI | 3009 | Chiller 3 Leaving cw Temperature | °f or °c | Read | ||
| AI | 3010 | Chiller 3 Entering cw Temperature | °f or °c | Read | ||
| AI | 3011 | Chiller 4 Leaving cw Temperature | °f or °c | Read | ||
| AI | 3012 | Chiller 4 Entering cw Temperature | °f or °c | Read | ||
| AI | 3013 | Chiller 5 Leaving cw Temperature | °f or °c | Read | ||
| AI | 3014 | Chiller 5 Entering cw Temperature | °f or °c | Read | ||
| AI | 3015 | cw Pump 1a Drive Power | kW | Read | ||
| AI | 3016 | cw Pump 1a Drive Volt ac | VAC | Read | ||
| AI | 3017 | cw Pump 1a Drive Amp | Amp | Read | ||
| AI | 3018 | cw Pump 1a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3019 | cw Pump 2a Drive Power | kW | Read | ||
| AI | 3020 | cw Pump 2a Drive Volt ac | VAC | Read | ||
| AI | 3021 | cw Pump 2a Drive Amp | Amp | Read | ||
| AI | 3022 | cw Pump 2a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3023 | cw Pump 3a Drive Power | kW | Read | ||
| AI | 3024 | cw Pump 3a Drive Volt ac | VAC | Read | ||
| AI | 3025 | cw Pump 3a Drive Amp | Amp | Read | ||
| AI | 3026 | cw Pump 3a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3027 | cw Pump 4a Drive Power | kW | Read | ||
| AI | 3028 | cw Pump 4a Drive Volt ac | VAC | Read | ||
| AI | 3029 | cw Pump 4a Drive Amp | Amp | Read | ||
| AI | 3030 | cw Pump 4a Drive Speed Feedback | Range 0 to 100.0 | 0 % to 100.0 | Read | |
| AI | 3031 | cw Pump 5a Drive Power | kW | Read | ||
| AI | 3032 | cw Pump 5a Drive Volt ac | VAC | Read | ||
| AI | 3033 | cw Pump 5a Drive Amp | Amp | Read | ||
| AI | 3034 | cw Pump 5a Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3035 | cw Pump 1b Drive Power | kW | Read | ||
| AI | 3036 | cw Pump 1b Drive Volt ac | VAC | Read | ||
| AI | 3037 | cw Pump 1b Drive Amp | Amp | Read | ||
| AI | 3038 | cw Pump 1b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3039 | cw Pump 2b Drive Power | kW | Read | ||
| AI | 3040 | cw Pump 2b Drive Volt ac | VAC | Read | ||
| AI | 3041 | cw Pump 2b Drive Amp | Amp | Read | ||
| AI | 3042 | cw Pump 2b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3043 | cw Pump 3b Drive Power | kW | Read | ||
| AI | 3044 | cw Pump 3b Drive Volt ac | VAC | Read | ||
| AI | 3045 | cw Pump 3b Drive Amp | Amp | Read | ||
| AI | 3046 | cw Pump 3b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3047 | cw Pump 4b Drive Power | kW | Read | ||
| AI | 3048 | cw Pump 4b Drive Volt ac | VAC | Read | ||
| AI | 3049 | cw Pump 4b Drive Amp | Amp | Read | ||
| AI | 3050 | cw Pump 4b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3051 | cw Pump 5b Drive Power | kW | Read | ||
| AI | 3052 | cw Pump 5b Drive Volt ac | VAC | Read | ||
| AI | 3053 | cw Pump 5b Drive Amp | Amp | Read | ||
| AI | 3054 | cw Pump 5b Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3055 | Tower 1 Fan Drive Power | kW | Read | ||
| AI | 3056 | Tower 1 Fan Drive Volt ac | VAC | Read | ||
| AI | 3057 | Tower 1 Fan Drive Amp | Amp | Read | ||
| AI | 3058 | Tower 1 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3059 | Tower 2 Fan Drive Power | kW | Read | ||
| AI | 3060 | Tower 2 Fan Drive Volt ac | VAC | Read | ||
| AI | 3061 | Tower 2 Fan Drive Amp | Amp | Read | ||
| AI | 3062 | Tower 2 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3063 | Tower 3 Fan Drive Power | kW | Read | ||
| AI | 3064 | Tower 3 Fan Drive Volt ac | VAC | Read | ||
| AI | 3065 | Tower 3 Fan Drive Amp | Amp | Read | ||
| AI | 3066 | Tower 3 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3067 | Tower 4 Fan Drive Power | kW | Read | ||
| AI | 3068 | Tower 4 Fan Drive Volt ac | VAC | Read | ||
| AI | 3069 | Tower 4 Fan Drive Amp | Amp | Read | ||
| AI | 3070 | Tower 4 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3071 | Tower 5 Fan Drive Power | kW | Read | ||
| AI | 3072 | Tower 5 Fan Drive Volt ac | VAC | Read | ||
| AI | 3073 | Tower 5 Fan Drive Amp | Amp | Read | ||
| AI | 3074 | Tower 5 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 3075 | cw Pump 1/1a Run Hours | hours | Read | ||
| AI | 3076 | cw Pump 2/2a Run Hours | hours | Read | ||
| AI | 3077 | cw Pump 3/3a Run Hours | hours | Read | ||
| AI | 3078 | cw Pump 4/4a Run Hours | hours | Read | ||
| AI | 3079 | cw Pump 5/5a Run Hours | hours | Read | ||
| AI | 3080 | cw Pump 1b Run Hours | hours | Read | ||
| AI | 3081 | cw Pump 2b Run Hours | hours | Read | ||
| AI | 3082 | cw Pump 3b Run Hours | hours | Read | ||
| AI | 3083 | cw Pump 4b Run Hours | hours | Read | ||
| AI | 3084 | cw Pump 5b Run Hours | hours | Read | ||
| AI | 3085 | Tower 1 Run Hours | hours | Read | ||
| AI | 3086 | Tower 2 Run Hours | hours | Read | ||
| AI | 3087 | Tower 3 Run Hours | hours | Read | ||
| AI | 3088 | Tower 4 Run Hours | hours | Read | ||
| AI | 3089 | Tower 5 Run Hours | hours | Read | ||
| AI | 3090 | Make up water daily consumption | Gallons or Liters | Read | ||
| AI | 3091 | Blowdown water daily consumption | Gallons or Liters | Read | ||
| AI | 3092 | Cycles of concentration | Read | |||
| AI | 3093 | cw Bypass Valve Position | Range 0 to 100.0 | % | Read | |
| AI | 4001 | cw Pump 1 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4002 | cw Pump 2 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4003 | cw Pump 3 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4004 | cw Pump 4 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4005 | cw Pump 5 Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4006 | cw Pump 1a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4007 | cw Pump 2a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4008 | cw Pump 3a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4009 | cw Pump 4a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4010 | cw Pump 5a Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4011 | cw Pump 1b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4012 | cw Pump 2b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4013 | cw Pump 3b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4014 | cw Pump 4b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4015 | cw Pump 5b Duty Standby | Coded value, range 0 to 7 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4016 | Tower 1 Duty Standby | Coded value, range 0 to 5 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4017 | Tower 2 Duty Standby | Coded value, range 0 to 5 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4018 | Tower 3 Duty Standby | Coded value, range 0 to 5 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4019 | Tower 4 Duty Standby | Coded value, range 0 to 5 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AI | 4020 | Tower 5 Duty Standby | Coded value, range 0 to 5 | Read | 0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty | |
| AV | 4001 | cw Pump 1/1a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4002 | cw Pump 2/2a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4003 | cw Pump 3/3a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4004 | cw Pump 4/4a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4005 | cw Pump 5/5a Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4006 | cw Pump 1b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4007 | cw Pump 2b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4008 | cw Pump 3b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4009 | cw Pump 4b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4010 | cw Pump 5b Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4011 | Tower 1 Fan Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4012 | Tower 2 Fan Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4013 | Tower 3 Fan Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4014 | Tower 4 Fan Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4015 | Tower 5 Fan Mode | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AO | 1001 | chw Bypass Valve Hand Position | Range 0 to 100.0 | % | Write | |
| AO | 1002 | chw Pump 1/1a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1003 | chw Pump 2/2a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1004 | chw Pump 3/3a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1005 | chw Pump 4/4a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1006 | chw Pump 5/5a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1007 | chw Pump 1b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1008 | chw Pump 2b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1009 | chw Pump 3b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1010 | chw Pump 4b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 1011 | chw Pump 5b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3001 | cw Bypass Valve Hand Position | Range 0 to 100.0 | % | Write | |
| AO | 3002 | cw Pump 1/1a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3003 | cw Pump 2/2a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3004 | cw Pump 3/3a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3005 | cw Pump 4/4a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3006 | cw Pump 5/5a Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3007 | cw Pump 1b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3008 | cw Pump 2b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3009 | cw Pump 3b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3010 | cw Pump 4b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3011 | cw Pump 5b Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3012 | Tower 1 Fan Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3013 | Tower 2 Fan Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3014 | Tower 3 Fan Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3015 | Tower 4 Fan Hand Speed | Range 0 to 100.0 | % | Write | |
| AO | 3016 | Tower 5 Fan Hand Speed | Range 0 to 100.0 | % | Write |
No points match these filters.
Object ID lookup: Armstrong Fluid Technology IPC 9521 chilled water plant controller point IDs by name
BO1Remote StartBO2Enable Plant Stand-by Mode FeatureBO3Alarm ResetBO4Chiller Group SelectBI1Plant StatusBI2All Zone Transmitter FailedBI3Zone 1 Transmitter FailedBI4Zone 2 Transmitter FailedBI5Zone 3 Transmitter FailedBI6Zone 4 Transmitter FailedBI7Zone 5 Transmitter FailedBI8Dry Bulb Air Temp Transmitter FailedBI9Relative Humidity Transmitter FailedBI10Refrigerant Leak AlarmBI11Active Chiller GroupBI1001chwS Temp Transmitter FailedBI1002chwR Temp Transmitter FailedBI1003chw Flow Transmitter FailedBI1004chwP dp Transmitter FailedBI1005System dp Transmitter FailedBI1006chiller 1 chw Iso Valve AlarmBI1007chiller 2 chw Iso Valve AlarmBI1008chiller 3 chw Iso Valve AlarmBI1009chiller 4 chw Iso Valve AlarmBI1010chiller 5 chw Iso Valve AlarmBI1011chw Pump 1a Run FeedbackBI1012chw Pump 1a AlarmBI1013chw Pump 2a Run FeedbackBI1014chw Pump 2a AlarmBI1015chw Pump 3a Run FeedbackBI1016chw Pump 3a AlarmBI1017chw Pump 4a Run FeedbackBI1018chw Pump 4a AlarmBI1019chw Pump 5a Run FeedbackBI1020chw Pump 5a AlarmBI1021chw Pump 1b Run FeedbackBI1022chw Pump 1b AlarmBI1023chw Pump 2b Run FeedbackBI1024chw Pump 2b AlarmBI1025chw Pump 3b Run FeedbackBI1026chw Pump 3b AlarmBI1027chw Pump 4b Run FeedbackBI1028chw Pump 4b AlarmBI1029chw Pump 5b Run FeedbackBI1030chw Pump 5b AlarmBI1031Chiller 1 Run FeedbackBI1032Chiller 1 AlarmBI1033Chiller 1 Power Transmitter FailedBI1034Chiller 2 Run FeedbackBI1035Chiller 2 AlarmBI1036Chiller 2 Power Transmitter FailedBI1037Chiller 3 Run FeedbackBI1038Chiller 3 AlarmBI1039Chiller 3 Power Transmitter FailedBI1040Chiller 4 Run FeedbackBI1041Chiller 4 AlarmBI1042Chiller 4 Power Transmitter FailedBI1043Chiller 5 Run FeedbackBI1044Chiller 5 AlarmBI1045Chiller 5 Power Transmitter FailedBI1046chw Bypass Valve Pos Fbk AlarmBI1047Chiller 1 chw Iso Valve StatusBI1048Chiller 2 chw Iso Valve StatusBI1049Chiller 3 chw Iso Valve StatusBI1050Chiller 4 chw Iso Valve StatusBI1051Chiller 5 chw Iso Valve StatusBI3001cw Inlet Temp Transmitter FailedBI3002cw Outlet Temp Transmitter FailedBI3003cw Flow Transmitter FailedBI3004cw dp Transmitter FailedBI3005chiller 1 cw Iso Valve Open AlarmBI3006chiller 2 cw Iso Valve Open AlarmBI3007chiller 3 cw Iso Valve Open AlarmBI3008chiller 4 cw Iso Valve Open AlarmBI3009chiller 5 cw Iso Valve Open AlarmBI3010chiller 1 cw Iso Valve Close AlarmBI3011chiller 2 cw Iso Valve Close AlarmBI3012chiller 3 cw Iso Valve Close AlarmBI3013chiller 4 cw Iso Valve Close AlarmBI3014chiller 5 cw Iso Valve Close AlarmBI3015cw Pump 1a Run FeedbackBI3016cw Pump 1a AlarmBI3017cw Pump 2a Run FeedbackBI3018cw Pump 2a AlarmBI3019cw Pump 3a Run FeedbackBI3020cw Pump 3a AlarmBI3021cw Pump 4a Run FeedbackBI3022cw Pump 4a AlarmBI3023cw Pump 5a Run FeedbackBI3024cw Pump 5a AlarmBI3025cw Pump 1b Run FeedbackBI3026cw Pump 1b AlarmBI3027cw Pump 2b Run FeedbackBI3028cw Pump 2b AlarmBI3029cw Pump 3b Run FeedbackBI3030cw Pump 3b AlarmBI3031cw Pump 4b Run FeedbackBI3032cw Pump 4b AlarmBI3033cw Pump 5b Run FeedbackBI3034cw Pump 5b AlarmBI3035Tower 1 Fan Run FeedbackBI3036Tower 1 Fan AlarmBI3037Tower 2 Fan Run FeedbackBI3038Tower 2 Fan AlarmBI3039Tower 3 Fan Run FeedbackBI3040Tower 3 Fan AlarmBI3041Tower 4 Fan Run FeedbackBI3042Tower 4 Fan AlarmBI3043Tower 5 Fan Run FeedbackBI3044Tower 5 Fan AlarmBI3045Tower 1 Iso Valve Open AlarmBI3046Tower 2 Iso Valve Open AlarmBI3047Tower 3 Iso Valve Open AlarmBI3048Tower 4 Iso Valve Open AlarmBI3049Tower 5 Iso Valve Open AlarmBI3050Tower 1 Iso Valve Close AlarmBI3051Tower 2 Iso Valve Close AlarmBI3052Tower 3 Iso Valve Close AlarmBI3053Tower 4 Iso Valve Close AlarmBI3054Tower 5 Iso Valve Close AlarmBI3055cw Bypass Valve Pos Fbk AlarmBI3056Tower Water High Level AlarmBI3057Tower Water Low Level AlarmBI3058High Daily ct Water Consumption AlarmBI3059High-High Daily ct Water Cons AlarmBI3060Low Tower Water Cycles of OperationBI3061Water Treatment Run FeedbackBI3062Solid Separator Sys Run FeedbackBI3063Heat Trace Operation FeedbackBI3064Water Treatment Run Feedback AlarmBI3065Solid Separator Sys Run Fdbk AlarmBI3066Heat Trace Operation Feedback AlarmBI3067Chiller 1 cw Iso Valve StatusBI3068Chiller 2 cw Iso Valve StatusBI3069Chiller 3 cw Iso Valve StatusBI3070Chiller 4 cw Iso Valve StatusBI3071Chiller 5 cw Iso Valve StatusBI3072Cooling Tower 1 Iso Valve StatusBI3073Cooling Tower 2 Iso Valve StatusBI3074Cooling Tower 3 Iso Valve StatusBI3075Cooling Tower 4 Iso Valve StatusBI3076Cooling Tower 5 Iso Valve StatusBV1001chw Bypass Valve Hand/AutoBV1002Chiller 1 chw Iso Valve Hand/AutoBV1003Chiller 2 chw Iso Valve Hand/AutoBV1004Chiller 3 chw Iso Valve Hand/AutoBV1005Chiller 4 chw Iso Valve Hand/AutoBV1006Chiller 5 chw Iso Valve Hand/AutoBV1007Chiller 1 chw Iso Valve Hand CommandBV1008Chiller 2 chw Iso Valve Hand CommandBV1009Chiller 3 chw Iso Valve Hand CommandBV1010Chiller 4 chw Iso Valve Hand CommandBV1011Chiller 5 chw Iso Valve Hand CommandBV3001cw Bypass Valve Hand/AutoBV3002Chiller 1 cw Iso Valve Hand/AutoBV3003Chiller 2 cw Iso Valve Hand/AutoBV3004Chiller 3 cw Iso Valve Hand/AutoBV3005Chiller 4 cw Iso Valve Hand/AutoBV3006Chiller 5 cw Iso Valve Hand/AutoBV3007Chiller 1 cw Iso Valve Hand CommandBV3008Chiller 2 cw Iso Valve Hand CommandBV3009Chiller 3 cw Iso Valve Hand CommandBV3010Chiller 4 cw Iso Valve Hand CommandBV3011Chiller 5 cw Iso Valve Hand CommandBV3012Tower 1 Iso Valve Hand/AutoBV3013Tower 2 Iso Valve Hand/AutoBV3014Tower 3 Iso Valve Hand/AutoBV3015Tower 4 Iso Valve Hand/AutoBV3016Tower 5 Iso Valve Hand/AutoBV3017Tower 1 Iso Valve Hand CommandBV3018Tower 2 Iso Valve Hand CommandBV3019Tower 3 Iso Valve Hand CommandBV3020Tower 4 Iso Valve Hand CommandBV3021Tower 5 Iso Valve Hand CommandAI1Plant EfficiencyAI2Total Plant Power ConsumptionAI3Plant LoadAI4Dry Bulb Air TempAI5Relative HumidityAI6Sensorless HeadAI7Sensorless FlowAI9Zone 1 pvAI10Zone 1 ErrorAI11Zone 2 pvAI12Zone 2 ErrorAI13Zone 3 pvAI14Zone 3 ErrorAI15Zone 4 pvAI16Zone 4 ErrorAI17Zone 5 pvAI18Zone 5 ErrorAV1Max Open Cooling Valve Position FdbckAV2Zone 1 SetpointAV3Zone 2 SetpointAV4Zone 3 SetpointAV5Zone 4 SetpointAV6Zone 5 SetpointAI1001chws TempAI1002chwr TempAI1003chw FlowAI1004chwp dpAI1005System dpAI1006Chiller 1 Leaving chw TemperatureAI1007Chiller 1 Entering chw TemperatureAI1008Chiller 1 PowerAI1009Chiller 2 Leaving chw TemperatureAI1010Chiller 2 Entering chw TemperatureAI1011Chiller 2 PowerAI1012Chiller 3 Leaving chw TemperatureAI1013Chiller 3 Entering chw TemperatureAI1014Chiller 3 PowerAI1015Chiller 4 Leaving chw TemperatureAI1016Chiller 4 Entering chw TemperatureAI1017Chiller 4 PowerAI1018Chiller 5 Leaving chw TemperatureAI1019Chiller 5 Entering chw TemperatureAI1020Chiller 5 PowerAI1021chw Pump 1a Drive PowerAI1022chw Pump 1a Drive Volt acAI1023chw Pump 1a Drive AmpAI1024chw Pump 1a Drive Speed FeedbackAI1025chw Pump 2a Drive PowerAI1026chw Pump 2a Drive Volt acAI1027chw Pump 2a Drive AmpAI1028chw Pump 2a Drive Speed FeedbackAI1029chw Pump 3a Drive PowerAI1030chw Pump 3a Drive Volt acAI1031chw Pump 3a Drive AmpAI1032chw Pump 3a Drive Speed FeedbackAI1033chw Pump 4a Drive PowerAI1034chw Pump 4a Drive Volt acAI1035chw Pump 4a Drive AmpAI1036chw Pump 4a Drive Speed FeedbackAI1037chw Pump 5a Drive PowerAI1038chw Pump 5a Drive Volt acAI1039chw Pump 5a Drive AmpAI1040chw Pump 5a Drive Speed FeedbackAI1041chw Pump 1b Drive PowerAI1042chw Pump 1b Drive Volt acAI1043chw Pump 1b Drive AmpAI1044chw Pump 1b Drive Speed FeedbackAI1045chw Pump 2b Drive PowerAI1046chw Pump 2b Drive Volt acAI1047chw Pump 2b Drive AmpAI1048chw Pump 2b Drive Speed FeedbackAI1049chw Pump 3b Drive PowerAI1050chw Pump 3b Drive Volt acAI1051chw Pump 3b Drive AmpAI1052chw Pump 3b Drive Speed FeedbackAI1053chw Pump 4b Drive PowerAI1054chw Pump 4b Drive Volt acAI1055chw Pump 4b Drive AmpAI1056chw Pump 4b Drive Speed FeedbackAI1057chw Pump 5b Drive PowerAI1058chw Pump 5b Drive Volt acAI1059chw Pump 5b Drive AmpAI1060chw Pump 5b Drive Speed FeedbackAI1061chw Pump 1a Run HoursAI1062chw Pump 2a Run HoursAI1063chw Pump 3a Run HoursAI1064chw Pump 4a Run HoursAI1065chw Pump 5a Run HoursAI1066chw Pump 1b Run HoursAI1067chw Pump 2b Run HoursAI1068chw Pump 3b Run HoursAI1069chw Pump 4b Run HoursAI1070chw Pump 5b Run HoursAI1071Chiller 1 Run HoursAI1072Chiller 2 Run HoursAI1073Chiller 3 Run HoursAI1074Chiller 4 Run HoursAI1075Chiller 5 Run HoursAI1076chw Bypass Valve PositionAI2001Chiller 1 DutyAI2002Chiller 1 StateAI2003Chiller 2 DutyAI2004Chiller 2 StateAI2005Chiller 3 DutyAI2006Chiller 3 StateAI2007Chiller 4 DutyAI2008Chiller 4 StateAI2009Chiller 5 DutyAI2010Chiller 5 StateAI2011chw Pump 1 Duty StandbyAI2012chw Pump 2 Duty StandbyAI2013chw Pump 3 Duty StandbyAI2014chw Pump 4 Duty StandbyAI2015chw Pump 5 Duty StandbyAI2016chw Pump 1a Duty StandbyAI2017chw Pump 2a Duty StandbyAI2018chw Pump 3a Duty StandbyAI2019chw Pump 4a Duty StandbyAI2020chw Pump 5a Duty StandbyAI2021chw Pump 1b Duty StandbyAI2022chw Pump 2b Duty StandbyAI2023chw Pump 3b Duty StandbyAI2024chw Pump 4b Duty StandbyAI2025chw Pump 5b Duty StandbyAV2001Chiller 1 ModeAV2002Chiller 2 ModeAV2003Chiller 3 ModeAV2004Chiller 4 ModeAV2005Chiller 5 ModeAV2006chw Pump 1/1a ModeAV2007chw Pump 2/2a ModeAV2008chw Pump 3/3a ModeAV2009chw Pump 4/4a ModeAV2010chw Pump 5/5a ModeAV2011chw Pump 1b ModeAV2012chw Pump 2b ModeAV2013chw Pump 3b ModeAV2014chw Pump 4b ModeAV2015chw Pump 5b ModeAI3001cw Inlet TempAI3002cw Outlet TempAI3003cw FlowAI3004cwp dpAI3005Chiller 1 Leaving cw TemperatureAI3006Chiller 1 Entering cw TemperatureAI3007Chiller 2 Leaving cw TemperatureAI3008Chiller 2 Entering cw TemperatureAI3009Chiller 3 Leaving cw TemperatureAI3010Chiller 3 Entering cw TemperatureAI3011Chiller 4 Leaving cw TemperatureAI3012Chiller 4 Entering cw TemperatureAI3013Chiller 5 Leaving cw TemperatureAI3014Chiller 5 Entering cw TemperatureAI3015cw Pump 1a Drive PowerAI3016cw Pump 1a Drive Volt acAI3017cw Pump 1a Drive AmpAI3018cw Pump 1a Drive Speed FeedbackAI3019cw Pump 2a Drive PowerAI3020cw Pump 2a Drive Volt acAI3021cw Pump 2a Drive AmpAI3022cw Pump 2a Drive Speed FeedbackAI3023cw Pump 3a Drive PowerAI3024cw Pump 3a Drive Volt acAI3025cw Pump 3a Drive AmpAI3026cw Pump 3a Drive Speed FeedbackAI3027cw Pump 4a Drive PowerAI3028cw Pump 4a Drive Volt acAI3029cw Pump 4a Drive AmpAI3030cw Pump 4a Drive Speed FeedbackAI3031cw Pump 5a Drive PowerAI3032cw Pump 5a Drive Volt acAI3033cw Pump 5a Drive AmpAI3034cw Pump 5a Drive Speed FeedbackAI3035cw Pump 1b Drive PowerAI3036cw Pump 1b Drive Volt acAI3037cw Pump 1b Drive AmpAI3038cw Pump 1b Drive Speed FeedbackAI3039cw Pump 2b Drive PowerAI3040cw Pump 2b Drive Volt acAI3041cw Pump 2b Drive AmpAI3042cw Pump 2b Drive Speed FeedbackAI3043cw Pump 3b Drive PowerAI3044cw Pump 3b Drive Volt acAI3045cw Pump 3b Drive AmpAI3046cw Pump 3b Drive Speed FeedbackAI3047cw Pump 4b Drive PowerAI3048cw Pump 4b Drive Volt acAI3049cw Pump 4b Drive AmpAI3050cw Pump 4b Drive Speed FeedbackAI3051cw Pump 5b Drive PowerAI3052cw Pump 5b Drive Volt acAI3053cw Pump 5b Drive AmpAI3054cw Pump 5b Drive Speed FeedbackAI3055Tower 1 Fan Drive PowerAI3056Tower 1 Fan Drive Volt acAI3057Tower 1 Fan Drive AmpAI3058Tower 1 Fan Drive Speed FeedbackAI3059Tower 2 Fan Drive PowerAI3060Tower 2 Fan Drive Volt acAI3061Tower 2 Fan Drive AmpAI3062Tower 2 Fan Drive Speed FeedbackAI3063Tower 3 Fan Drive PowerAI3064Tower 3 Fan Drive Volt acAI3065Tower 3 Fan Drive AmpAI3066Tower 3 Fan Drive Speed FeedbackAI3067Tower 4 Fan Drive PowerAI3068Tower 4 Fan Drive Volt acAI3069Tower 4 Fan Drive AmpAI3070Tower 4 Fan Drive Speed FeedbackAI3071Tower 5 Fan Drive PowerAI3072Tower 5 Fan Drive Volt acAI3073Tower 5 Fan Drive AmpAI3074Tower 5 Fan Drive Speed FeedbackAI3075cw Pump 1/1a Run HoursAI3076cw Pump 2/2a Run HoursAI3077cw Pump 3/3a Run HoursAI3078cw Pump 4/4a Run HoursAI3079cw Pump 5/5a Run HoursAI3080cw Pump 1b Run HoursAI3081cw Pump 2b Run HoursAI3082cw Pump 3b Run HoursAI3083cw Pump 4b Run HoursAI3084cw Pump 5b Run HoursAI3085Tower 1 Run HoursAI3086Tower 2 Run HoursAI3087Tower 3 Run HoursAI3088Tower 4 Run HoursAI3089Tower 5 Run HoursAI3090Make up water daily consumptionAI3091Blowdown water daily consumptionAI3092Cycles of concentrationAI3093cw Bypass Valve PositionAI4001cw Pump 1 Duty StandbyAI4002cw Pump 2 Duty StandbyAI4003cw Pump 3 Duty StandbyAI4004cw Pump 4 Duty StandbyAI4005cw Pump 5 Duty StandbyAI4006cw Pump 1a Duty StandbyAI4007cw Pump 2a Duty StandbyAI4008cw Pump 3a Duty StandbyAI4009cw Pump 4a Duty StandbyAI4010cw Pump 5a Duty StandbyAI4011cw Pump 1b Duty StandbyAI4012cw Pump 2b Duty StandbyAI4013cw Pump 3b Duty StandbyAI4014cw Pump 4b Duty StandbyAI4015cw Pump 5b Duty StandbyAI4016Tower 1 Duty StandbyAI4017Tower 2 Duty StandbyAI4018Tower 3 Duty StandbyAI4019Tower 4 Duty StandbyAI4020Tower 5 Duty StandbyAV4001cw Pump 1/1a ModeAV4002cw Pump 2/2a ModeAV4003cw Pump 3/3a ModeAV4004cw Pump 4/4a ModeAV4005cw Pump 5/5a ModeAV4006cw Pump 1b ModeAV4007cw Pump 2b ModeAV4008cw Pump 3b ModeAV4009cw Pump 4b ModeAV4010cw Pump 5b ModeAV4011Tower 1 Fan ModeAV4012Tower 2 Fan ModeAV4013Tower 3 Fan ModeAV4014Tower 4 Fan ModeAV4015Tower 5 Fan ModeAO1001chw Bypass Valve Hand PositionAO1002chw Pump 1/1a Hand SpeedAO1003chw Pump 2/2a Hand SpeedAO1004chw Pump 3/3a Hand SpeedAO1005chw Pump 4/4a Hand SpeedAO1006chw Pump 5/5a Hand SpeedAO1007chw Pump 1b Hand SpeedAO1008chw Pump 2b Hand SpeedAO1009chw Pump 3b Hand SpeedAO1010chw Pump 4b Hand SpeedAO1011chw Pump 5b Hand SpeedAO3001cw Bypass Valve Hand PositionAO3002cw Pump 1/1a Hand SpeedAO3003cw Pump 2/2a Hand SpeedAO3004cw Pump 3/3a Hand SpeedAO3005cw Pump 4/4a Hand SpeedAO3006cw Pump 5/5a Hand SpeedAO3007cw Pump 1b Hand SpeedAO3008cw Pump 2b Hand SpeedAO3009cw Pump 3b Hand SpeedAO3010cw Pump 4b Hand SpeedAO3011cw Pump 5b Hand SpeedAO3012Tower 1 Fan Hand SpeedAO3013Tower 2 Fan Hand SpeedAO3014Tower 3 Fan Hand SpeedAO3015Tower 4 Fan Hand SpeedAO3016Tower 5 Fan Hand Speed
Integration notes
- The data-points sheet titles the table BACnet but does not say whether it is BACnet IP or MS/TP.
- Mode objects (AV) use 0 = Not Used, 1 = Hand, 2 = Off, 3 = Auto. Duty/standby, chiller duty and chiller state objects are coded values; the codes are in each point's states.
- Hand/Auto BVs and Hand Command BVs, plus the Hand Speed / Hand Position AOs, let the BMS run a valve, pump or fan by hand. Set Lead objects act only when the written value changes.
- Units for temperatures, pressures and flows follow the controller's unit setting (the PDF lists the options).
- Footnote asterisks after some pump names in the PDF are left off the object names. They mean: 1/1a is a single pump or side A of a dualArm/Twin pump, and the b points are side B (not used for single pumps).
- The PDF table is on pages 15-25. One Reserved AI is left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IPC 9521 chilled water plant controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Armstrong Fluid Technology IPC 9521 chilled water plant controller
How many BACnet points does the Armstrong Fluid Technology IPC 9521 chilled water plant controller have?
This list has 468 BACnet objects: 231 analog inputs, 27 analog outputs, 36 analog values, 138 binary inputs, 4 binary outputs, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet points are writable?
99 of the 468 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Armstrong Fluid Technology IPC 9521 chilled water plant controller BACnet documentation?
The source is IPC 9521 Data points (Communication Interface Rev 18.122) (90.874), revision 2019-09-16, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-874_ipc9521_datapoints_iando.pdf.
What are the minimum BACnet points to integrate the Armstrong Fluid Technology IPC 9521 chilled water plant controller?
Start with BO 1 Remote Start (Plant start/stop from the BMS (1 = start)); AV 2 Zone 1 Setpoint (Zone 1 control setpoint); BO 3 Alarm Reset (Reset plant alarms (positive edge)); BI 1 Plant Status (Plant on/off status); AI 3 Plant Load (Plant cooling load, tons); AI 1001 chws Temp (Chilled water supply temperature); AI 1002 chwr Temp (Chilled water return temperature); AI 2 Total Plant Power Consumption (Total plant power, kW); AI 1 Plant Efficiency (Plant efficiency, kW/ton); BI 10 Refrigerant Leak Alarm (Refrigerant leak detected).
How do I enable BMS control of the Armstrong Fluid Technology IPC 9521 chilled water plant controller?
BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.
How do I check these points on the real IPC 9521 chilled water plant controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Armstrong Fluid Technology BACnet points lists
- Cooling tower and condenser pump plant controller
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)
Armstrong Design Envelope Integrated Tower Controller for the condenser water side: up to 5 cooling towers (fans, inlet/outlet isolation valves) and 5 condenser water pumps.
Also known as: ITC 9521, ITC9521, Design Envelope ITC, Integrated Tower Controller, 82.21 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W10 chiller plant controller (water-cooled)
Armstrong EE-W10 water-cooled chilled water plant controls; the object list covers up to 3 chillers, 3 chilled water pumps, 3 condenser water pumps and 3 towers.
Also known as: EE-W10, EE-W 10, Armstrong EE-W10, 90.7651 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W20 chiller plant controller (water-cooled)
Armstrong EE-W20 water-cooled chilled water plant controls; the object list covers up to 5 chillers, 10 chilled water pumps, 10 condenser water pumps, 5 towers and 5 control zones.
Also known as: EE-W20, EE-W 20, Armstrong EE-W20, 90.7661 - Pump system controller (variable primary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary
Armstrong IPS 4000 controllers set up for variable primary pumping: up to 8 pumps, 16 control zones and 8 chillers or boilers with flow and differential pressure limits.
Also known as: IPS 4000, IPS4000, IPS 4000 primary, Integrated Pumping System 4000, 90.9751 - Pump system controller (variable secondary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary
Armstrong IPS 4000 controllers set up for variable secondary pumping: up to 8 pumps and 16 control zones.
Also known as: IPS 4000, IPS4000, IPS 4000 secondary, Integrated Pumping System 4000, 90.9761 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A10 chiller plant controller
Armstrong SE-A10 chilled water plant controls with no condenser water side; the object list covers up to 3 chillers and 3 chilled water pumps.
Also known as: SE-A10, SE-A 10, Armstrong SE-A10, 90.7671 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A20 chiller plant controller
Armstrong SE-A20 chilled water plant controls with no condenser water side; the object list covers up to 5 chillers, 10 chilled water pumps and 5 control zones.
Also known as: SE-A20, SE-A 20, Armstrong SE-A20, 90.7681
Source: IPC 9521 Data points (Communication Interface Rev 18.122) · 90.874 · rev. 2019-09-16. Object names, instances and units are reproduced as published; descriptions are our own.