Chiller plant controller (chillers and chilled water pumps) · BACnet points list

Armstrong Fluid Technology SE-A20 chiller plant controller BACnet points list

Updated 6 November 2026

Short answer

The SE-A20 is the larger version of the SE-A10: up to 5 chillers, 5 zones and 10 chilled water pump positions (dualArm/Twin pump sides count separately), with no condenser water or tower objects. The BACnet list gives plant start/stop, alarm reset, plant load, power and efficiency, chilled water temperatures and flow, chiller and pump status, alarms, drive data and Hand/Auto overrides.

This page lists 222 BACnet objects for the Armstrong Fluid Technology SE-A20 chiller plant controller — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.

Manufacturer
Armstrong Fluid Technology
Model
SE-A20 chiller plant controller
Equipment
Chiller plant controller (chillers and chilled water pumps)
Equipment type
Chillers
BACnet objects
222 (48 writable)
Transport
—
Firmware
BACnet communication interface Rev 24.111
Also known as
SE-A20, SE-A 20, Armstrong SE-A20, 90.7681
Source document
SE-A20 Data points (BAS data points - BACnet, Communication Interface Rev 24.111) · 90.7681 · rev. 2025-05-15
Download CSV 222 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.

BMS integration notes: Armstrong Fluid Technology SE-A20 chiller plant controller

Integration in brief

The SE-A20 publishes a fixed BACnet object list. Start and stop the plant with BO 1 Remote Start, write the zone setpoint (AV 2), and read BI 1 Plant Status, plant load, chilled water temperatures, plant power and efficiency. Use BO 3 to reset alarms. Per-chiller, per-pump and per-valve alarms, run feedbacks and Hand/Auto overrides are there if the BMS needs more detail.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Remote StartPlant start/stop from the BMS (1 = start)Write
AV 2Zone 1 SetpointZone 1 control setpointWrite
BO 3Alarm ResetReset plant alarms (positive edge)Write
BI 1Plant StatusPlant on/off statusRead
AI 3Plant LoadPlant cooling load, tonsRead
AI 1001chws TempChilled water supply temperatureRead
AI 1002chwr TempChilled water return temperatureRead
AI 2Total Plant Power ConsumptionTotal plant power, kWRead
AI 1Plant EfficiencyPlant efficiency, kW/tonRead
BI 10Refrigerant Leak AlarmRefrigerant leak detectedRead

Enable & remote start

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

Network setup

Watch out for

Armstrong Fluid Technology SE-A20 chiller plant controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

222 of 222 shown
Type
Access
Show
Armstrong Fluid Technology SE-A20 chiller plant controller BACnet Points List
DescriptionStates
BOmin1Remote StartWrite0=Stop, 1=Start
BO2Enable Plant Stand-by Mode FeatureWrite0=FALSE, 1=TRUE
BOmin3Alarm ResetPositive Edge commandWrite0=N/A, 1=Reset
BImin1Plant StatusRead0=Off, 1=On
BI2All Zone Transmitter FailedRead0=Ok, 1=Alarm
BI3Zone 1 Transmitter FailedRead0=Ok, 1=Alarm
BI4Zone 2 Transmitter FailedRead0=Ok, 1=Alarm
BI5Zone 3 Transmitter FailedRead0=Ok, 1=Alarm
BI6Zone 4 Transmitter FailedRead0=Ok, 1=Alarm
BI7Zone 5 Transmitter FailedRead0=Ok, 1=Alarm
BI8Dry Bulb Air Temp Transmitter FailedRead0=Ok, 1=Alarm
BI9Relative Humidity Transmitter FailedRead0=Ok, 1=Alarm
BImin10Refrigerant Leak AlarmRead0=Ok, 1=Alarm
BI1001chws Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1002chwr Temp Transmitter FailedRead0=Ok, 1=Alarm
BI1003chw Flow Transmitter FailedRead0=Ok, 1=Alarm
BI1004chwp DP Transmitter FailedRead0=Ok, 1=Alarm
BI1005System DP Transmitter FailedRead0=Ok, 1=Alarm
BI1006Chlr 1 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1007Chlr 2 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1008Chlr 3 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1009Chlr 4 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1010Chlr 5 chw Iso Vlv AlarmRead0=Ok, 1=Alarm
BI1011chw Pump 1 Run FeedbackRead0=Stopped, 1=Running
BI1012chw Pump 1 AlarmRead0=Ok, 1=Alarm
BI1013chw Pump 2 Run FeedbackRead0=Stopped, 1=Running
BI1014chw Pump 2 AlarmRead0=Ok, 1=Alarm
BI1015chw Pump 3 Run FeedbackRead0=Stopped, 1=Running
BI1016chw Pump 3 AlarmRead0=Ok, 1=Alarm
BI1017chw Pump 4 Run FeedbackRead0=Stopped, 1=Running
BI1018chw Pump 4 AlarmRead0=Ok, 1=Alarm
BI1019chw Pump 5 Run FeedbackRead0=Stopped, 1=Running
BI1020chw Pump 5 AlarmRead0=Ok, 1=Alarm
BI1021chw Pump 6 Run FeedbackRead0=Stopped, 1=Running
BI1022chw Pump 6 AlarmRead0=Ok, 1=Alarm
BI1023chw Pump 7 Run FeedbackRead0=Stopped, 1=Running
BI1024chw Pump 7 AlarmRead0=Ok, 1=Alarm
BI1025chw Pump 8 Run FeedbackRead0=Stopped, 1=Running
BI1026chw Pump 8 AlarmRead0=Ok, 1=Alarm
BI1027chw Pump 9 Run FeedbackRead0=Stopped, 1=Running
BI1028chw Pump 9 AlarmRead0=Ok, 1=Alarm
BI1029chw Pump 10 Run FeedbackRead0=Stopped, 1=Running
BI1030chw Pump 10 AlarmRead0=Ok, 1=Alarm
BI1031Chiller 1 Run FeedbackRead0=Stopped, 1=Running
BI1032Chiller 1 AlarmRead0=Ok, 1=Alarm
BI1033Chiller 1 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1034Chiller 2 Run FeedbackRead0=Stopped, 1=Running
BI1035Chiller 2 AlarmRead0=Ok, 1=Alarm
BI1036Chiller 2 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1037Chiller 3 Run FeedbackRead0=Stopped, 1=Running
BI1038Chiller 3 AlarmRead0=Ok, 1=Alarm
BI1039Chiller 3 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1040Chiller 4 Run FeedbackRead0=Stopped, 1=Running
BI1041Chiller 4 AlarmRead0=Ok, 1=Alarm
BI1042Chiller 4 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1043Chiller 5 Run FeedbackRead0=Stopped, 1=Running
BI1044Chiller 5 AlarmRead0=Ok, 1=Alarm
BI1045Chiller 5 Power Transmitter FailedRead0=Ok, 1=Alarm
BI1046chw Bypass Valve Pos Fbk AlarmRead0=Ok, 1=Alarm
BI1047Chiller 1 chw Iso Valve StatusRead0=Close, 1=Open
BI1048Chiller 2 chw Iso Valve StatusRead0=Close, 1=Open
BI1049Chiller 3 chw Iso Valve StatusRead0=Close, 1=Open
BI1050Chiller 4 chw Iso Valve StatusRead0=Close, 1=Open
BI1051Chiller 5 chw Iso Valve StatusRead0=Close, 1=Open
BV1001chw Bypass Valve Hand/AutoWrite0=Hand, 1=Auto
BV1002Chiller 1 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1003Chiller 2 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1004Chiller 3 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1005Chiller 4 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1006Chiller 5 chw Iso Valve Hand/AutoWrite0=Hand, 1=Auto
BV1007Chiller 1 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1008Chiller 2 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1009Chiller 3 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1010Chiller 4 chw Iso Valve Hand CommandWrite0=Close, 1=Open
BV1011Chiller 5 chw Iso Valve Hand CommandWrite0=Close, 1=Open
AO1001chw Bypass Valve Hand PositionRange 0 to 100.0%Write
AO1002chw Pump 1 Hand SpeedRange 0 to 100.0%Write
AO1003chw Pump 2 Hand SpeedRange 0 to 100.0%Write
AO1004chw Pump 3 Hand SpeedRange 0 to 100.0%Write
AO1005chw Pump 4 Hand SpeedRange 0 to 100.0%Write
AO1006chw Pump 5 Hand SpeedRange 0 to 100.0%Write
AO1007chw Pump 6 Hand SpeedRange 0 to 100.0%Write
AO1008chw Pump 7 Hand SpeedRange 0 to 100.0%Write
AO1009chw Pump 8 Hand SpeedRange 0 to 100.0%Write
AO1010chw Pump 9 Hand SpeedRange 0 to 100.0%Write
AO1011chw Pump 10 Hand SpeedRange 0 to 100.0%Write
AImin1Plant EfficiencykW/TonRead
AImin2Total Plant Power ConsumptionkWRead
AImin3Plant LoadtonsRead
AI4Dry Bulb Air Temp°F or °CRead
AI5Relative HumidityRange 0 to 100.0%Read
AI6Sensorless HeadfeetRead
AI7Sensorless FlowusgpmRead
AI9Zone 1 PVpsi, ft, kPA, m, °F or °CRead
AI10Zone 1 Errorpsi, ft, kPA, m, °F or °CRead
AI11Zone 2 PVpsi, ft, kPA, m, °F or °CRead
AI12Zone 2 Errorpsi, ft, kPA, m, °F or °CRead
AI13Zone 3 PVpsi, ft, kPA, m, °F or °CRead
AI14Zone 3 Errorpsi, ft, kPA, m, °F or °CRead
AI15Zone 4 PVpsi, ft, kPA, m, °F or °CRead
AI16Zone 4 Errorpsi, ft, kPA, m, °F or °CRead
AI17Zone 5 PVpsi, ft, kPA, m, °F or °CRead
AI18Zone 5 Errorpsi, ft, kPA, m, °F or °CRead
AV1Max Open Cooling Valve Position FdbckRange 0 to 100.0%Write
AVmin2Zone 1 Setpointpsi, ft, kPA, m, °F or °CWrite
AV3Zone 2 Setpointpsi, ft, kPA, m, °F or °CWrite
AV4Zone 3 Setpointpsi, ft, kPA, m, °F or °CWrite
AV5Zone 4 Setpointpsi, ft, kPA, m, °F or °CWrite
AV6Zone 5 Setpointpsi, ft, kPA, m, °F or °CWrite
AImin1001chws Temp°F or °CRead
AImin1002chwr Temp°F or °CRead
AI1003chw Flowusgpm, lps, m3/hrRead
AI1004chwp DPpsi, ft, kPA, mRead
AI1005System DPpsi, ft, kPA, mRead
AI1006Chiller 1 Leaving chw Temperature°F or °CRead
AI1007Chiller 1 Entering chw Temperature°F or °CRead
AI1008Chiller 1 PowerkWRead
AI1009Chiller 2 Leaving chw Temperature°F or °CRead
AI1010Chiller 2 Entering chw Temperature°F or °CRead
AI1011Chiller 2 PowerkWRead
AI1012Chiller 3 Leaving chw Temperature°F or °CRead
AI1013Chiller 3 Entering chw Temperature°F or °CRead
AI1014Chiller 3 PowerkWRead
AI1015Chiller 4 Leaving chw Temperature°F or °CRead
AI1016Chiller 4 Entering chw Temperature°F or °CRead
AI1017Chiller 4 PowerkWRead
AI1018Chiller 5 Leaving chw Temperature°F or °CRead
AI1019Chiller 5 Entering chw Temperature°F or °CRead
AI1020Chiller 5 PowerkWRead
AI1021chw Pump 1 Drive PowerkWRead
AI1022chw Pump 1 Drive Volt ACVACRead
AI1023chw Pump 1 Drive AmpAmpRead
AI1024chw Pump 1 Drive Speed FeedbackRange 0 to 100.0%Read
AI1025chw Pump 2 Drive PowerkWRead
AI1026chw Pump 2 Drive Volt ACVACRead
AI1027chw Pump 2 Drive AmpAmpRead
AI1028chw Pump 2 Drive Speed FeedbackRange 0 to 100.0%Read
AI1029chw Pump 3 Drive PowerkWRead
AI1030chw Pump 3 Drive Volt ACVACRead
AI1031chw Pump 3 Drive AmpAmpRead
AI1032chw Pump 3 Drive Speed FeedbackRange 0 to 100.0%Read
AI1033chw Pump 4 Drive PowerkWRead
AI1034chw Pump 4 Drive Volt ACVACRead
AI1035chw Pump 4 Drive AmpAmpRead
AI1036chw Pump 4 Drive Speed FeedbackRange 0 to 100.0%Read
AI1037chw Pump 5 Drive PowerkWRead
AI1038chw Pump 5 Drive Volt ACVACRead
AI1039chw Pump 5 Drive AmpAmpRead
AI1040chw Pump 5 Drive Speed FeedbackRange 0 to 100.0%Read
AI1041chw Pump 6 Drive PowerkWRead
AI1042chw Pump 6 Drive Volt ACVACRead
AI1043chw Pump 6 Drive AmpAmpRead
AI1044chw Pump 6 Drive Speed FeedbackRange 0 to 100.0%Read
AI1045chw Pump 7 Drive PowerkWRead
AI1046chw Pump 7 Drive Volt ACVACRead
AI1047chw Pump 7 Drive AmpAmpRead
AI1048chw Pump 7 Drive Speed FeedbackRange 0 to 100.0%Read
AI1049chw Pump 8 Drive PowerkWRead
AI1050chw Pump 8 Drive Volt ACVACRead
AI1051chw Pump 8 Drive AmpAmpRead
AI1052chw Pump 8 Drive Speed FeedbackRange 0 to 100.0%Read
AI1053chw Pump 9 Drive PowerkWRead
AI1054chw Pump 9 Drive Volt ACVACRead
AI1055chw Pump 9 Drive AmpAmpRead
AI1056chw Pump 9 Drive Speed FeedbackRange 0 to 100.0%Read
AI1057chw Pump 10 Drive PowerkWRead
AI1058chw Pump 10 Drive Volt ACVACRead
AI1059chw Pump 10 Drive AmpAmpRead
AI1060chw Pump 10 Drive Speed FeedbackRange 0 to 100.0%Read
AI1061chw Pump 1 Run HourshoursRead
AI1062chw Pump 2 Run HourshoursRead
AI1063chw Pump 3 Run HourshoursRead
AI1064chw Pump 4 Run HourshoursRead
AI1065chw Pump 5 Run HourshoursRead
AI1066chw Pump 6 Run HourshoursRead
AI1067chw Pump 7 Run HourshoursRead
AI1068chw Pump 8 Run HourshoursRead
AI1069chw Pump 9 Run HourshoursRead
AI1070chw Pump 10 Run HourshoursRead
AI1071Chiller 1 Run HourshoursRead
AI1072Chiller 2 Run HourshoursRead
AI1073Chiller 3 Run HourshoursRead
AI1074Chiller 4 Run HourshoursRead
AI1075Chiller 5 Run HourshoursRead
AI1076chw Bypass Valve PositionRange 0 to 100.0%Read
AI2001Chiller 1 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2002Chiller 1 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2003Chiller 2 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2004Chiller 2 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2005Chiller 3 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2006Chiller 3 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2007Chiller 4 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2008Chiller 4 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2009Chiller 5 DutyCoded value, range 0 to 5Read0=n/a, 1=Lead, 2=Lag 1, 3=Lag 2, 4=Lag 3, 5=Lag 4
AI2010Chiller 5 StateCoded value, range 0 to 7Read0=n/a, 1=Ready, 2=Enabled, 3=Started, 4=Running, 5=Shutdown, 6=Alarm, 7=Not Ready
AI2011chw Pump 1 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2012chw Pump 2 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2013chw Pump 3 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2014chw Pump 4 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2015chw Pump 5 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2016chw Pump 6 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2017chw Pump 7 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2018chw Pump 8 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2019chw Pump 9 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AI2020chw Pump 10 Duty StandbyCoded value, range 0 to 7Read0=n/a, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby, 7=Duty
AV2001Chiller 1 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2002Chiller 2 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2003Chiller 3 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2004Chiller 4 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2005Chiller 5 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2006chw Pump 1 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2007chw Pump 2 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2008chw Pump 3 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2009chw Pump 4 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2010chw Pump 5 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2011chw Pump 6 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2012chw Pump 7 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2013chw Pump 8 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2014chw Pump 9 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2015chw Pump 10 ModeCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2016Set Lead ChillerWrite 1 to 5; acted on when the value changesWrite
AV2017Set Lead chw PumpWrite 1 to 5; acted on when the value changesWrite
Object ID lookup: Armstrong Fluid Technology SE-A20 chiller plant controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SE-A20 chiller plant controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Armstrong Fluid Technology SE-A20 chiller plant controller

How many BACnet points does the Armstrong Fluid Technology SE-A20 chiller plant controller have?

This list has 222 BACnet objects: 113 analog inputs, 11 analog outputs, 23 analog values, 61 binary inputs, 3 binary outputs, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Armstrong Fluid Technology SE-A20 chiller plant controller BACnet points are writable?

48 of the 222 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Armstrong Fluid Technology SE-A20 chiller plant controller BACnet documentation?

The source is SE-A20 Data points (BAS data points - BACnet, Communication Interface Rev 24.111) (90.7681), revision 2025-05-15, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/90-7681_se_a20_datapoints.pdf.

What are the minimum BACnet points to integrate the Armstrong Fluid Technology SE-A20 chiller plant controller?

Start with BO 1 Remote Start (Plant start/stop from the BMS (1 = start)); AV 2 Zone 1 Setpoint (Zone 1 control setpoint); BO 3 Alarm Reset (Reset plant alarms (positive edge)); BI 1 Plant Status (Plant on/off status); AI 3 Plant Load (Plant cooling load, tons); AI 1001 chws Temp (Chilled water supply temperature); AI 1002 chwr Temp (Chilled water return temperature); AI 2 Total Plant Power Consumption (Total plant power, kW); AI 1 Plant Efficiency (Plant efficiency, kW/ton); BI 10 Refrigerant Leak Alarm (Refrigerant leak detected).

How do I enable BMS control of the Armstrong Fluid Technology SE-A20 chiller plant controller?

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the plant from the BMS. The data-points sheet says nothing more about local/remote selection.

How do I check these points on the real SE-A20 chiller plant controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Armstrong Fluid Technology BACnet points lists

Source: SE-A20 Data points (BAS data points - BACnet, Communication Interface Rev 24.111) · 90.7681 · rev. 2025-05-15. Object names, instances and units are reproduced as published; descriptions are our own.