Cooling tower and condenser pump plant controller · BACnet points list

Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet points list

Updated 6 November 2026

Short answer

The ITC 9521 sequences cooling towers and condenser water pumps. Its BACnet object list covers start/stop, alarm reset, tower water temperatures, condenser flow, outdoor temperature and humidity, bypass valve positions, pump and fan drive data, run hours, duty/standby and running status, valve states, alarms and Hand/Auto overrides.

This page lists 210 BACnet objects for the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.

Manufacturer
Armstrong Fluid Technology
Model
Design Envelope Integrated Tower Controller (ITC 9521)
Equipment
Cooling tower and condenser pump plant controller
Equipment type
Cooling towers & fluid coolers
BACnet objects
210 (44 writable)
Transport
—
Firmware
BACnet communication interface Rev 17.111
Also known as
ITC 9521, ITC9521, Design Envelope ITC, Integrated Tower Controller, 82.21
Source document
Design Envelope Integrated Tower Controller Data points (BACnet Communication Interface Rev 17.111) · 82.21 · rev. 2018-07-17
Download CSV 210 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.

BMS integration notes: Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)

Integration in brief

The ITC 9521 runs the condenser water side: cooling towers, condenser pumps, tower isolation valves and bypass valves. Start and stop it with BO 1 Remote Start, read BI 1 Plant Status, tower water temperatures, condenser flow and outdoor conditions, and reset alarms with BO 2. Per-pump and per-fan modes, hand speeds and valve overrides are available.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Remote StartStart/stop from the BMS (1 = start)Write
BO 2Alarm ResetReset alarms (positive edge)Write
BI 1Plant StatusController on/off statusRead
AI 1Leaving Tower Water TempCondenser water leaving the towersRead
AI 2Entering Tower Water TempCondenser water entering the towersRead
AI 3Condenser FlowCondenser water flowRead
AI 4Outside Air Temp (Dry Bulb)Outdoor dry-bulb temperatureRead
BI 128Cooling Tower Water Low Level AlarmTower basin low water levelRead

Enable & remote start

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the controller from the BMS. The data-points sheet says nothing more about local/remote selection.

Network setup

Watch out for

Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

210 of 210 shown
Type
Access
Show
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet Points List
DescriptionStates
BOmin1Remote StartWrite0=Stop, 1=Start
BOmin2Alarm ResetPositive Edge commandWrite0=N/A, 1=Reset
BV1001ct 1 Inlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1002ct 2 Inlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1003ct 3 Inlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1004ct 4 Inlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1005ct 5 Inlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1006ct 1 Inlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1007ct 2 Inlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1008ct 3 Inlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1009ct 4 Inlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1010ct 5 Inlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1011ct 1 Outlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1012ct 2 Outlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1013ct 3 Outlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1014ct 4 Outlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1015ct 5 Outlet Isol Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1016ct 1 Outlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1017ct 2 Outlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1018ct 3 Outlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1019ct 4 Outlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1020ct 5 Outlet Isol Valve Hand CommandWrite0=Close, 1=Open
BV1021Tower Bypass Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BV1022Distribution Bypass Valve Hand/Auto SwitchWrite0=Hand, 1=Auto
BImin1Plant StatusRead0=Off, 1=On
BI2cw Pump 1 Run FeedbackRead0=Stopped, 1=Running
BI3cw Pump 1 AlarmRead0=Ok, 1=Alarm
BI4cw Pump 2 Run FeedbackRead0=Stopped, 1=Running
BI5cw Pump 2 AlarmRead0=Ok, 1=Alarm
BI6cw Pump 3 Run FeedbackRead0=Stopped, 1=Running
BI7cw Pump 3 AlarmRead0=Ok, 1=Alarm
BI8cw Pump 4 Run FeedbackRead0=Stopped, 1=Running
BI9cw Pump 4 AlarmRead0=Ok, 1=Alarm
BI10cw Pump 5 Run FeedbackRead0=Stopped, 1=Running
BI11cw Pump 5 AlarmRead0=Ok, 1=Alarm
BI12Cooling Tower 1 Fan Run FeedbackRead0=Stopped, 1=Running
BI13Cooling Tower 1 Fan AlarmRead0=Ok, 1=Alarm
BI14Cooling Tower 2 Fan Run FeedbackRead0=Stopped, 1=Running
BI15Cooling Tower 2 Fan AlarmRead0=Ok, 1=Alarm
BI16Cooling Tower 3 Fan Run FeedbackRead0=Stopped, 1=Running
BI17Cooling Tower 3 Fan AlarmRead0=Ok, 1=Alarm
BI18Cooling Tower 4 Fan Run FeedbackRead0=Stopped, 1=Running
BI19Cooling Tower 4 Fan AlarmRead0=Ok, 1=Alarm
BI20Cooling Tower 5 Fan Run FeedbackRead0=Stopped, 1=Running
BI21Cooling Tower 5 Fan AlarmRead0=Ok, 1=Alarm
BI22Cooling Tower 1 Inlet Isol Valve StateRead0=Close, 1=Open
BI23Cooling Tower 2 Inlet Isol Valve StateRead0=Close, 1=Open
BI24Cooling Tower 3 Inlet Isol Valve StateRead0=Close, 1=Open
BI25Cooling Tower 4 Inlet Isol Valve StateRead0=Close, 1=Open
BI26Cooling Tower 5 Inlet Isol Valve StateRead0=Close, 1=Open
BI27Cooling Tower 1 Outlet Isol Valve StateRead0=Close, 1=Open
BI28Cooling Tower 2 Outlet Isol Valve StateRead0=Close, 1=Open
BI29Cooling Tower 3 Outlet Isol Valve StateRead0=Close, 1=Open
BI30Cooling Tower 4 Outlet Isol Valve StateRead0=Close, 1=Open
BI31Cooling Tower 5 Outlet Isol Valve StateRead0=Close, 1=Open
BI101Leaving Tower Temp Transmitter FailedRead0=Ok, 1=Alarm
BI102Entering Tower Temp Transmitter FailedRead0=Ok, 1=Alarm
BI103OAT Transmitter FailedRead0=Ok, 1=Alarm
BI104Relative Humidity Transmitter FailedRead0=Ok, 1=Alarm
BI105Tower Bypass Valve Transmitter FailedRead0=Ok, 1=Alarm
BI106Distribution Bypass Vlv Transmitter FailedRead0=Ok, 1=Alarm
BI107ct 1 Inlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI108ct 2 Inlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI109ct 3 Inlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI110ct 4 Inlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI111ct 5 Inlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI112ct 1 Inlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI113ct 2 Inlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI114ct 3 Inlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI115ct 4 Inlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI116ct 5 Inlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI117ct 1 Outlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI118ct 2 Outlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI119ct 3 Outlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI120ct 4 Outlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI121ct 5 Outlet Isol Vlv Open Fbk AlarmRead0=Ok, 1=Alarm
BI122ct 1 Outlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI123ct 2 Outlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI124ct 3 Outlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI125ct 4 Outlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI126ct 5 Outlet Isol Vlv Close Fbk AlarmRead0=Ok, 1=Alarm
BI127Cooling Tower Water High Level AlarmRead0=Ok, 1=Alarm
BImin128Cooling Tower Water Low Level AlarmRead0=Ok, 1=Alarm
BI129Water Treatment Run Feedback AlarmRead0=Ok, 1=Alarm
BI130Freeze Protection Operation Fbk AlarmRead0=Ok, 1=Alarm
BI131Tower 1 Circulator Pump Run Fbk AlarmRead0=Ok, 1=Alarm
BI132Tower 2 Circulator Pump Run Fbk AlarmRead0=Ok, 1=Alarm
BI133Tower 3 Circulator Pump Run Fbk AlarmRead0=Ok, 1=Alarm
BI134Tower 4 Circulator Pump Run Fbk AlarmRead0=Ok, 1=Alarm
BI135Tower 5 Circulator Pump Run Fbk AlarmRead0=Ok, 1=Alarm
BI136Tower Bypass Valve Position AlarmRead0=Ok, 1=Alarm
BI137Distribution Bypass Valve Position AlarmRead0=Ok, 1=Alarm
AImin1Leaving Tower Water Temp°f, °cRead
AImin2Entering Tower Water Temp°f, °cRead
AImin3Condenser Flowusgpm, lps, m3hrRead
AImin4Outside Air Temp (Dry Bulb)°f, °cRead
AI5Relative Humidity%Read
AI6Tower Bypass Valve Position%Read
AI7Distribution Bypass Valve Position%Read
AI8cw Pumps HeadFt, kPa, psi, m, barRead
AI50cw Pump 1 Drive PowerkWRead
AI51cw Pump 1 Drive Volt ACVACRead
AI52cw Pump 1 Drive AmpAmpRead
AI53cw Pump 1 Drive Speed ReferenceRange 0 to 100.0%Read
AI54cw Pump 1 Drive Speed FeedbackRange 0 to 100.0%Read
AI55cw Pump 1 Sensorless HeadkWRead
AI56cw Pump 1 Sensorless Flowgpm, lps, m3hrRead
AI57cw Pump 2 Drive PowerkWRead
AI58cw Pump 2 Drive Volt ACVACRead
AI59cw Pump 2 Drive AmpAmpRead
AI60cw Pump 2 Drive Speed ReferenceRange 0 to 100.0%Read
AI61cw Pump 2 Drive Speed FeedbackRange 0 to 100.0%Read
AI62cw Pump 2 Sensorless HeadkWRead
AI63cw Pump 2 Sensorless Flowgpm, lps, m3hrRead
AI64cw Pump 3 Drive PowerkWRead
AI65cw Pump 3 Drive Volt ACVACRead
AI66cw Pump 3 Drive AmpAmpRead
AI67cw Pump 3 Drive Speed ReferenceRange 0 to 100.0%Read
AI68cw Pump 3 Drive Speed FeedbackRange 0 to 100.0%Read
AI69cw Pump 3 Sensorless HeadkWRead
AI70cw Pump 3 Sensorless Flowgpm, lps, m3hrRead
AI71cw Pump 4 Drive PowerkWRead
AI72cw Pump 4 Drive Volt ACVACRead
AI73cw Pump 4 Drive AmpAmpRead
AI74cw Pump 4 Drive Speed ReferenceRange 0 to 100.0%Read
AI75cw Pump 4 Drive Speed FeedbackRange 0 to 100.0%Read
AI76cw Pump 4 Sensorless HeadkWRead
AI77cw Pump 4 Sensorless Flowgpm, lps, m3hrRead
AI78cw Pump 5 Drive PowerkWRead
AI79cw Pump 5 Drive Volt ACVACRead
AI80cw Pump 5 Drive AmpAmpRead
AI81cw Pump 5 Drive Speed ReferenceRange 0 to 100.0%Read
AI82cw Pump 5 Drive Speed FeedbackRange 0 to 100.0%Read
AI83cw Pump 5 Sensorless HeadkWRead
AI84cw Pump 5 Sensorless Flowgpm, lps, m3hrRead
AI85ct 1 Fan Drive PowerkWRead
AI86ct 1 Fan Drive Volt ACVACRead
AI87ct 1 Fan Drive AmpAmpRead
AI88ct 1 Fan Drive Speed ReferenceRange 0 to 100.0%Read
AI89ct 1 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI90ct 2 Fan Drive PowerkWRead
AI91ct 2 Fan Drive Volt ACVACRead
AI92ct 2 Fan Drive AmpAmpRead
AI93ct 2 Fan Drive Speed ReferenceRange 0 to 100.0%Read
AI94ct 2 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI95ct 3 Fan Drive PowerkWRead
AI96ct 3 Fan Drive Volt ACVACRead
AI97ct 3 Fan Drive AmpAmpRead
AI98ct 3 Fan Drive Speed ReferenceRange 0 to 100.0%Read
AI99ct 3 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI100ct 4 Fan Drive PowerkWRead
AI101ct 4 Fan Drive Volt ACVACRead
AI102ct 4 Fan Drive AmpAmpRead
AI103ct 4 Fan Drive Speed ReferenceRange 0 to 100.0%Read
AI104ct 4 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI105ct 5 Fan Drive PowerkWRead
AI106ct 5 Fan Drive Volt ACVACRead
AI107ct 5 Fan Drive AmpAmpRead
AI108ct 5 Fan Drive Speed ReferenceRange 0 to 100.0%Read
AI109ct 5 Fan Drive Speed FeedbackRange 0 to 100.0%Read
AI110cw Pump 1 Run HourshoursRead
AI111cw Pump 2 Run HourshoursRead
AI112cw Pump 3 Run HourshoursRead
AI113cw Pump 4 Run HourshoursRead
AI114cw Pump 5 Run HourshoursRead
AI115Cooling Tower 1 Fan Run HourshoursRead
AI116Cooling Tower 2 Fan Run HourshoursRead
AI117Cooling Tower 3 Fan Run HourshoursRead
AI118Cooling Tower 4 Fan Run HourshoursRead
AI119Cooling Tower 5 Fan Run HourshoursRead
AI201cw Pump 1 Duty/Standby StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI202cw Pump 2 Duty/Standby StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI203cw Pump 3 Duty/Standby StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI204cw Pump 4 Duty/Standby StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI205cw Pump 5 Duty/Standby StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI206Cooling Tower 1 Duty StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI207Cooling Tower 2 Duty StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI208Cooling Tower 3 Duty StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI209Cooling Tower 4 Duty StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI210Cooling Tower 5 Duty StatusCoded value, range 0 to 5Read0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby
AI211cw Pump 1 Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI212cw Pump 2 Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI213cw Pump 3 Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI214cw Pump 4 Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI215cw Pump 5 Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI216Cooling Tower 1 Fan Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI217Cooling Tower 2 Fan Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI218Cooling Tower 3 Fan Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI219Cooling Tower 4 Fan Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AI220Cooling Tower 5 Fan Running StatusCoded value, range 0 to 2Read0=Stopped, 1=Running, 2=Alarm
AV1cw Pump 1 Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV2cw Pump 2 Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV3cw Pump 3 Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV4cw Pump 4 Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV5cw Pump 5 Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV6Cooling Tower 1 Fan Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV7Cooling Tower 2 Fan Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV8Cooling Tower 3 Fan Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV9Cooling Tower 4 Fan Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AV10Cooling Tower 5 Fan Mode/SelectorCoded value, range 0 to 3Write0=Not Used, 1=Hand, 2=Off, 3=Auto
AO1cw Pump 1 Hand SpeedRange 0.0 to 100.0%Write
AO2cw Pump 2 Hand SpeedRange 0.0 to 100.0%Write
AO3cw Pump 3 Hand SpeedRange 0.0 to 100.0%Write
AO4cw Pump 4 Hand SpeedRange 0.0 to 100.0%Write
AO5cw Pump 5 Hand SpeedRange 0.0 to 100.0%Write
AO6Cooling Tower 1 Fan Hand SpeedRange 0.0 to 100.0%Write
AO7Cooling Tower 2 Fan Hand SpeedRange 0.0 to 100.0%Write
AO8Cooling Tower 3 Fan Hand SpeedRange 0.0 to 100.0%Write
AO9Cooling Tower 4 Fan Hand SpeedRange 0.0 to 100.0%Write
AO10Cooling Tower 5 Fan Hand SpeedRange 0.0 to 100.0%Write
Object ID lookup: Armstrong Fluid Technology Design Envelope Integrated Tower Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Design Envelope Integrated Tower Controller (ITC 9521) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)

How many BACnet points does the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) have?

This list has 210 BACnet objects: 98 analog inputs, 10 analog outputs, 10 analog values, 68 binary inputs, 2 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet points are writable?

44 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet documentation?

The source is Design Envelope Integrated Tower Controller Data points (BACnet Communication Interface Rev 17.111) (82.21), revision 2018-07-17, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/82-21_designenvelope_itc9521_datapoints.pdf.

What are the minimum BACnet points to integrate the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)?

Start with BO 1 Remote Start (Start/stop from the BMS (1 = start)); BO 2 Alarm Reset (Reset alarms (positive edge)); BI 1 Plant Status (Controller on/off status); AI 1 Leaving Tower Water Temp (Condenser water leaving the towers); AI 2 Entering Tower Water Temp (Condenser water entering the towers); AI 3 Condenser Flow (Condenser water flow); AI 4 Outside Air Temp (Dry Bulb) (Outdoor dry-bulb temperature); BI 128 Cooling Tower Water Low Level Alarm (Tower basin low water level).

How do I enable BMS control of the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)?

BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the controller from the BMS. The data-points sheet says nothing more about local/remote selection.

How do I check these points on the real Design Envelope Integrated Tower Controller (ITC 9521)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.