Cooling tower and condenser pump plant controller · BACnet points list
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet points list
Updated 6 November 2026
The ITC 9521 sequences cooling towers and condenser water pumps. Its BACnet object list covers start/stop, alarm reset, tower water temperatures, condenser flow, outdoor temperature and humidity, bypass valve positions, pump and fan drive data, run hours, duty/standby and running status, valve states, alarms and Hand/Auto overrides.
This page lists 210 BACnet objects for the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Fluid Technology’s own free documentation, linked below.
- Manufacturer
- Armstrong Fluid Technology
- Model
- Design Envelope Integrated Tower Controller (ITC 9521)
- Equipment
- Cooling tower and condenser pump plant controller
- Equipment type
- Cooling towers & fluid coolers
- BACnet objects
- 210 (44 writable)
- Transport
- —
- Firmware
- BACnet communication interface Rev 17.111
- Also known as
- ITC 9521, ITC9521, Design Envelope ITC, Integrated Tower Controller, 82.21
Reference only, provided as-is: verify against Armstrong Fluid Technology’s current documentation and the live device before use. Not official Armstrong Fluid Technology information. Terms of use.
BMS integration notes: Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)
The ITC 9521 runs the condenser water side: cooling towers, condenser pumps, tower isolation valves and bypass valves. Start and stop it with BO 1 Remote Start, read BI 1 Plant Status, tower water temperatures, condenser flow and outdoor conditions, and reset alarms with BO 2. Per-pump and per-fan modes, hand speeds and valve overrides are available.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Remote Start | Start/stop from the BMS (1 = start) | Write |
| BO 2 | Alarm Reset | Reset alarms (positive edge) | Write |
| BI 1 | Plant Status | Controller on/off status | Read |
| AI 1 | Leaving Tower Water Temp | Condenser water leaving the towers | Read |
| AI 2 | Entering Tower Water Temp | Condenser water entering the towers | Read |
| AI 3 | Condenser Flow | Condenser water flow | Read |
| AI 4 | Outside Air Temp (Dry Bulb) | Outdoor dry-bulb temperature | Read |
| BI 128 | Cooling Tower Water Low Level Alarm | Tower basin low water level | Read |
Enable & remote start
BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the controller from the BMS. The data-points sheet says nothing more about local/remote selection.
Network setup
- The data-points sheet does not give the device instance, MAC address, baud rate or IP settings; get them from the controller setup.
Watch out for
- BO 2 Alarm Reset acts on a positive edge (0 to 1).
- Mode/Selector AVs accept only 1-3 when written (1 = Hand, 2 = Off, 3 = Auto); Hand runs the pump or fan at its Hand Speed AO.
- Hand/Auto switch BVs and Hand Command BVs override the valve sequence; leave them in Auto for normal operation.
- The Sensorless Head points are printed with kW as the unit; treat that unit with care.
Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Remote Start | Write | 0=Stop, 1=Start | ||
| BOmin | 2 | Alarm Reset | Positive Edge command | Write | 0=N/A, 1=Reset | |
| BV | 1001 | ct 1 Inlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1002 | ct 2 Inlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1003 | ct 3 Inlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1004 | ct 4 Inlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1005 | ct 5 Inlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1006 | ct 1 Inlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1007 | ct 2 Inlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1008 | ct 3 Inlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1009 | ct 4 Inlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1010 | ct 5 Inlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1011 | ct 1 Outlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1012 | ct 2 Outlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1013 | ct 3 Outlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1014 | ct 4 Outlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1015 | ct 5 Outlet Isol Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1016 | ct 1 Outlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1017 | ct 2 Outlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1018 | ct 3 Outlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1019 | ct 4 Outlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1020 | ct 5 Outlet Isol Valve Hand Command | Write | 0=Close, 1=Open | ||
| BV | 1021 | Tower Bypass Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BV | 1022 | Distribution Bypass Valve Hand/Auto Switch | Write | 0=Hand, 1=Auto | ||
| BImin | 1 | Plant Status | Read | 0=Off, 1=On | ||
| BI | 2 | cw Pump 1 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 3 | cw Pump 1 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 4 | cw Pump 2 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 5 | cw Pump 2 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 6 | cw Pump 3 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 7 | cw Pump 3 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 8 | cw Pump 4 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 9 | cw Pump 4 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 10 | cw Pump 5 Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 11 | cw Pump 5 Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 12 | Cooling Tower 1 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 13 | Cooling Tower 1 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 14 | Cooling Tower 2 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 15 | Cooling Tower 2 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 16 | Cooling Tower 3 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 17 | Cooling Tower 3 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 18 | Cooling Tower 4 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 19 | Cooling Tower 4 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 20 | Cooling Tower 5 Fan Run Feedback | Read | 0=Stopped, 1=Running | ||
| BI | 21 | Cooling Tower 5 Fan Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 22 | Cooling Tower 1 Inlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 23 | Cooling Tower 2 Inlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 24 | Cooling Tower 3 Inlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 25 | Cooling Tower 4 Inlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 26 | Cooling Tower 5 Inlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 27 | Cooling Tower 1 Outlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 28 | Cooling Tower 2 Outlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 29 | Cooling Tower 3 Outlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 30 | Cooling Tower 4 Outlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 31 | Cooling Tower 5 Outlet Isol Valve State | Read | 0=Close, 1=Open | ||
| BI | 101 | Leaving Tower Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 102 | Entering Tower Temp Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 103 | OAT Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 104 | Relative Humidity Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 105 | Tower Bypass Valve Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 106 | Distribution Bypass Vlv Transmitter Failed | Read | 0=Ok, 1=Alarm | ||
| BI | 107 | ct 1 Inlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 108 | ct 2 Inlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 109 | ct 3 Inlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 110 | ct 4 Inlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 111 | ct 5 Inlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 112 | ct 1 Inlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 113 | ct 2 Inlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 114 | ct 3 Inlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 115 | ct 4 Inlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 116 | ct 5 Inlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 117 | ct 1 Outlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 118 | ct 2 Outlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 119 | ct 3 Outlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 120 | ct 4 Outlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 121 | ct 5 Outlet Isol Vlv Open Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 122 | ct 1 Outlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 123 | ct 2 Outlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 124 | ct 3 Outlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 125 | ct 4 Outlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 126 | ct 5 Outlet Isol Vlv Close Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 127 | Cooling Tower Water High Level Alarm | Read | 0=Ok, 1=Alarm | ||
| BImin | 128 | Cooling Tower Water Low Level Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 129 | Water Treatment Run Feedback Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 130 | Freeze Protection Operation Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 131 | Tower 1 Circulator Pump Run Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 132 | Tower 2 Circulator Pump Run Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 133 | Tower 3 Circulator Pump Run Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 134 | Tower 4 Circulator Pump Run Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 135 | Tower 5 Circulator Pump Run Fbk Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 136 | Tower Bypass Valve Position Alarm | Read | 0=Ok, 1=Alarm | ||
| BI | 137 | Distribution Bypass Valve Position Alarm | Read | 0=Ok, 1=Alarm | ||
| AImin | 1 | Leaving Tower Water Temp | °f, °c | Read | ||
| AImin | 2 | Entering Tower Water Temp | °f, °c | Read | ||
| AImin | 3 | Condenser Flow | usgpm, lps, m3hr | Read | ||
| AImin | 4 | Outside Air Temp (Dry Bulb) | °f, °c | Read | ||
| AI | 5 | Relative Humidity | % | Read | ||
| AI | 6 | Tower Bypass Valve Position | % | Read | ||
| AI | 7 | Distribution Bypass Valve Position | % | Read | ||
| AI | 8 | cw Pumps Head | Ft, kPa, psi, m, bar | Read | ||
| AI | 50 | cw Pump 1 Drive Power | kW | Read | ||
| AI | 51 | cw Pump 1 Drive Volt AC | VAC | Read | ||
| AI | 52 | cw Pump 1 Drive Amp | Amp | Read | ||
| AI | 53 | cw Pump 1 Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 54 | cw Pump 1 Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 55 | cw Pump 1 Sensorless Head | kW | Read | ||
| AI | 56 | cw Pump 1 Sensorless Flow | gpm, lps, m3hr | Read | ||
| AI | 57 | cw Pump 2 Drive Power | kW | Read | ||
| AI | 58 | cw Pump 2 Drive Volt AC | VAC | Read | ||
| AI | 59 | cw Pump 2 Drive Amp | Amp | Read | ||
| AI | 60 | cw Pump 2 Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 61 | cw Pump 2 Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 62 | cw Pump 2 Sensorless Head | kW | Read | ||
| AI | 63 | cw Pump 2 Sensorless Flow | gpm, lps, m3hr | Read | ||
| AI | 64 | cw Pump 3 Drive Power | kW | Read | ||
| AI | 65 | cw Pump 3 Drive Volt AC | VAC | Read | ||
| AI | 66 | cw Pump 3 Drive Amp | Amp | Read | ||
| AI | 67 | cw Pump 3 Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 68 | cw Pump 3 Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 69 | cw Pump 3 Sensorless Head | kW | Read | ||
| AI | 70 | cw Pump 3 Sensorless Flow | gpm, lps, m3hr | Read | ||
| AI | 71 | cw Pump 4 Drive Power | kW | Read | ||
| AI | 72 | cw Pump 4 Drive Volt AC | VAC | Read | ||
| AI | 73 | cw Pump 4 Drive Amp | Amp | Read | ||
| AI | 74 | cw Pump 4 Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 75 | cw Pump 4 Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 76 | cw Pump 4 Sensorless Head | kW | Read | ||
| AI | 77 | cw Pump 4 Sensorless Flow | gpm, lps, m3hr | Read | ||
| AI | 78 | cw Pump 5 Drive Power | kW | Read | ||
| AI | 79 | cw Pump 5 Drive Volt AC | VAC | Read | ||
| AI | 80 | cw Pump 5 Drive Amp | Amp | Read | ||
| AI | 81 | cw Pump 5 Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 82 | cw Pump 5 Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 83 | cw Pump 5 Sensorless Head | kW | Read | ||
| AI | 84 | cw Pump 5 Sensorless Flow | gpm, lps, m3hr | Read | ||
| AI | 85 | ct 1 Fan Drive Power | kW | Read | ||
| AI | 86 | ct 1 Fan Drive Volt AC | VAC | Read | ||
| AI | 87 | ct 1 Fan Drive Amp | Amp | Read | ||
| AI | 88 | ct 1 Fan Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 89 | ct 1 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 90 | ct 2 Fan Drive Power | kW | Read | ||
| AI | 91 | ct 2 Fan Drive Volt AC | VAC | Read | ||
| AI | 92 | ct 2 Fan Drive Amp | Amp | Read | ||
| AI | 93 | ct 2 Fan Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 94 | ct 2 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 95 | ct 3 Fan Drive Power | kW | Read | ||
| AI | 96 | ct 3 Fan Drive Volt AC | VAC | Read | ||
| AI | 97 | ct 3 Fan Drive Amp | Amp | Read | ||
| AI | 98 | ct 3 Fan Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 99 | ct 3 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 100 | ct 4 Fan Drive Power | kW | Read | ||
| AI | 101 | ct 4 Fan Drive Volt AC | VAC | Read | ||
| AI | 102 | ct 4 Fan Drive Amp | Amp | Read | ||
| AI | 103 | ct 4 Fan Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 104 | ct 4 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 105 | ct 5 Fan Drive Power | kW | Read | ||
| AI | 106 | ct 5 Fan Drive Volt AC | VAC | Read | ||
| AI | 107 | ct 5 Fan Drive Amp | Amp | Read | ||
| AI | 108 | ct 5 Fan Drive Speed Reference | Range 0 to 100.0 | % | Read | |
| AI | 109 | ct 5 Fan Drive Speed Feedback | Range 0 to 100.0 | % | Read | |
| AI | 110 | cw Pump 1 Run Hours | hours | Read | ||
| AI | 111 | cw Pump 2 Run Hours | hours | Read | ||
| AI | 112 | cw Pump 3 Run Hours | hours | Read | ||
| AI | 113 | cw Pump 4 Run Hours | hours | Read | ||
| AI | 114 | cw Pump 5 Run Hours | hours | Read | ||
| AI | 115 | Cooling Tower 1 Fan Run Hours | hours | Read | ||
| AI | 116 | Cooling Tower 2 Fan Run Hours | hours | Read | ||
| AI | 117 | Cooling Tower 3 Fan Run Hours | hours | Read | ||
| AI | 118 | Cooling Tower 4 Fan Run Hours | hours | Read | ||
| AI | 119 | Cooling Tower 5 Fan Run Hours | hours | Read | ||
| AI | 201 | cw Pump 1 Duty/Standby Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 202 | cw Pump 2 Duty/Standby Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 203 | cw Pump 3 Duty/Standby Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 204 | cw Pump 4 Duty/Standby Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 205 | cw Pump 5 Duty/Standby Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 206 | Cooling Tower 1 Duty Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 207 | Cooling Tower 2 Duty Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 208 | Cooling Tower 3 Duty Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 209 | Cooling Tower 4 Duty Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 210 | Cooling Tower 5 Duty Status | Coded value, range 0 to 5 | Read | 0=Not Used, 1=Duty 1, 2=Duty 2, 3=Duty 3, 4=Duty 4, 5=Duty 5, 6=Standby | |
| AI | 211 | cw Pump 1 Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 212 | cw Pump 2 Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 213 | cw Pump 3 Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 214 | cw Pump 4 Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 215 | cw Pump 5 Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 216 | Cooling Tower 1 Fan Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 217 | Cooling Tower 2 Fan Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 218 | Cooling Tower 3 Fan Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 219 | Cooling Tower 4 Fan Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AI | 220 | Cooling Tower 5 Fan Running Status | Coded value, range 0 to 2 | Read | 0=Stopped, 1=Running, 2=Alarm | |
| AV | 1 | cw Pump 1 Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 2 | cw Pump 2 Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 3 | cw Pump 3 Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 4 | cw Pump 4 Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 5 | cw Pump 5 Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 6 | Cooling Tower 1 Fan Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 7 | Cooling Tower 2 Fan Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 8 | Cooling Tower 3 Fan Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 9 | Cooling Tower 4 Fan Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AV | 10 | Cooling Tower 5 Fan Mode/Selector | Coded value, range 0 to 3 | Write | 0=Not Used, 1=Hand, 2=Off, 3=Auto | |
| AO | 1 | cw Pump 1 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 2 | cw Pump 2 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 3 | cw Pump 3 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 4 | cw Pump 4 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 5 | cw Pump 5 Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 6 | Cooling Tower 1 Fan Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 7 | Cooling Tower 2 Fan Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 8 | Cooling Tower 3 Fan Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 9 | Cooling Tower 4 Fan Hand Speed | Range 0.0 to 100.0 | % | Write | |
| AO | 10 | Cooling Tower 5 Fan Hand Speed | Range 0.0 to 100.0 | % | Write |
No points match these filters.
Object ID lookup: Armstrong Fluid Technology Design Envelope Integrated Tower Controller point IDs by name
BO1Remote StartBO2Alarm ResetBV1001ct 1 Inlet Isol Valve Hand/Auto SwitchBV1002ct 2 Inlet Isol Valve Hand/Auto SwitchBV1003ct 3 Inlet Isol Valve Hand/Auto SwitchBV1004ct 4 Inlet Isol Valve Hand/Auto SwitchBV1005ct 5 Inlet Isol Valve Hand/Auto SwitchBV1006ct 1 Inlet Isol Valve Hand CommandBV1007ct 2 Inlet Isol Valve Hand CommandBV1008ct 3 Inlet Isol Valve Hand CommandBV1009ct 4 Inlet Isol Valve Hand CommandBV1010ct 5 Inlet Isol Valve Hand CommandBV1011ct 1 Outlet Isol Valve Hand/Auto SwitchBV1012ct 2 Outlet Isol Valve Hand/Auto SwitchBV1013ct 3 Outlet Isol Valve Hand/Auto SwitchBV1014ct 4 Outlet Isol Valve Hand/Auto SwitchBV1015ct 5 Outlet Isol Valve Hand/Auto SwitchBV1016ct 1 Outlet Isol Valve Hand CommandBV1017ct 2 Outlet Isol Valve Hand CommandBV1018ct 3 Outlet Isol Valve Hand CommandBV1019ct 4 Outlet Isol Valve Hand CommandBV1020ct 5 Outlet Isol Valve Hand CommandBV1021Tower Bypass Valve Hand/Auto SwitchBV1022Distribution Bypass Valve Hand/Auto SwitchBI1Plant StatusBI2cw Pump 1 Run FeedbackBI3cw Pump 1 AlarmBI4cw Pump 2 Run FeedbackBI5cw Pump 2 AlarmBI6cw Pump 3 Run FeedbackBI7cw Pump 3 AlarmBI8cw Pump 4 Run FeedbackBI9cw Pump 4 AlarmBI10cw Pump 5 Run FeedbackBI11cw Pump 5 AlarmBI12Cooling Tower 1 Fan Run FeedbackBI13Cooling Tower 1 Fan AlarmBI14Cooling Tower 2 Fan Run FeedbackBI15Cooling Tower 2 Fan AlarmBI16Cooling Tower 3 Fan Run FeedbackBI17Cooling Tower 3 Fan AlarmBI18Cooling Tower 4 Fan Run FeedbackBI19Cooling Tower 4 Fan AlarmBI20Cooling Tower 5 Fan Run FeedbackBI21Cooling Tower 5 Fan AlarmBI22Cooling Tower 1 Inlet Isol Valve StateBI23Cooling Tower 2 Inlet Isol Valve StateBI24Cooling Tower 3 Inlet Isol Valve StateBI25Cooling Tower 4 Inlet Isol Valve StateBI26Cooling Tower 5 Inlet Isol Valve StateBI27Cooling Tower 1 Outlet Isol Valve StateBI28Cooling Tower 2 Outlet Isol Valve StateBI29Cooling Tower 3 Outlet Isol Valve StateBI30Cooling Tower 4 Outlet Isol Valve StateBI31Cooling Tower 5 Outlet Isol Valve StateBI101Leaving Tower Temp Transmitter FailedBI102Entering Tower Temp Transmitter FailedBI103OAT Transmitter FailedBI104Relative Humidity Transmitter FailedBI105Tower Bypass Valve Transmitter FailedBI106Distribution Bypass Vlv Transmitter FailedBI107ct 1 Inlet Isol Vlv Open Fbk AlarmBI108ct 2 Inlet Isol Vlv Open Fbk AlarmBI109ct 3 Inlet Isol Vlv Open Fbk AlarmBI110ct 4 Inlet Isol Vlv Open Fbk AlarmBI111ct 5 Inlet Isol Vlv Open Fbk AlarmBI112ct 1 Inlet Isol Vlv Close Fbk AlarmBI113ct 2 Inlet Isol Vlv Close Fbk AlarmBI114ct 3 Inlet Isol Vlv Close Fbk AlarmBI115ct 4 Inlet Isol Vlv Close Fbk AlarmBI116ct 5 Inlet Isol Vlv Close Fbk AlarmBI117ct 1 Outlet Isol Vlv Open Fbk AlarmBI118ct 2 Outlet Isol Vlv Open Fbk AlarmBI119ct 3 Outlet Isol Vlv Open Fbk AlarmBI120ct 4 Outlet Isol Vlv Open Fbk AlarmBI121ct 5 Outlet Isol Vlv Open Fbk AlarmBI122ct 1 Outlet Isol Vlv Close Fbk AlarmBI123ct 2 Outlet Isol Vlv Close Fbk AlarmBI124ct 3 Outlet Isol Vlv Close Fbk AlarmBI125ct 4 Outlet Isol Vlv Close Fbk AlarmBI126ct 5 Outlet Isol Vlv Close Fbk AlarmBI127Cooling Tower Water High Level AlarmBI128Cooling Tower Water Low Level AlarmBI129Water Treatment Run Feedback AlarmBI130Freeze Protection Operation Fbk AlarmBI131Tower 1 Circulator Pump Run Fbk AlarmBI132Tower 2 Circulator Pump Run Fbk AlarmBI133Tower 3 Circulator Pump Run Fbk AlarmBI134Tower 4 Circulator Pump Run Fbk AlarmBI135Tower 5 Circulator Pump Run Fbk AlarmBI136Tower Bypass Valve Position AlarmBI137Distribution Bypass Valve Position AlarmAI1Leaving Tower Water TempAI2Entering Tower Water TempAI3Condenser FlowAI4Outside Air Temp (Dry Bulb)AI5Relative HumidityAI6Tower Bypass Valve PositionAI7Distribution Bypass Valve PositionAI8cw Pumps HeadAI50cw Pump 1 Drive PowerAI51cw Pump 1 Drive Volt ACAI52cw Pump 1 Drive AmpAI53cw Pump 1 Drive Speed ReferenceAI54cw Pump 1 Drive Speed FeedbackAI55cw Pump 1 Sensorless HeadAI56cw Pump 1 Sensorless FlowAI57cw Pump 2 Drive PowerAI58cw Pump 2 Drive Volt ACAI59cw Pump 2 Drive AmpAI60cw Pump 2 Drive Speed ReferenceAI61cw Pump 2 Drive Speed FeedbackAI62cw Pump 2 Sensorless HeadAI63cw Pump 2 Sensorless FlowAI64cw Pump 3 Drive PowerAI65cw Pump 3 Drive Volt ACAI66cw Pump 3 Drive AmpAI67cw Pump 3 Drive Speed ReferenceAI68cw Pump 3 Drive Speed FeedbackAI69cw Pump 3 Sensorless HeadAI70cw Pump 3 Sensorless FlowAI71cw Pump 4 Drive PowerAI72cw Pump 4 Drive Volt ACAI73cw Pump 4 Drive AmpAI74cw Pump 4 Drive Speed ReferenceAI75cw Pump 4 Drive Speed FeedbackAI76cw Pump 4 Sensorless HeadAI77cw Pump 4 Sensorless FlowAI78cw Pump 5 Drive PowerAI79cw Pump 5 Drive Volt ACAI80cw Pump 5 Drive AmpAI81cw Pump 5 Drive Speed ReferenceAI82cw Pump 5 Drive Speed FeedbackAI83cw Pump 5 Sensorless HeadAI84cw Pump 5 Sensorless FlowAI85ct 1 Fan Drive PowerAI86ct 1 Fan Drive Volt ACAI87ct 1 Fan Drive AmpAI88ct 1 Fan Drive Speed ReferenceAI89ct 1 Fan Drive Speed FeedbackAI90ct 2 Fan Drive PowerAI91ct 2 Fan Drive Volt ACAI92ct 2 Fan Drive AmpAI93ct 2 Fan Drive Speed ReferenceAI94ct 2 Fan Drive Speed FeedbackAI95ct 3 Fan Drive PowerAI96ct 3 Fan Drive Volt ACAI97ct 3 Fan Drive AmpAI98ct 3 Fan Drive Speed ReferenceAI99ct 3 Fan Drive Speed FeedbackAI100ct 4 Fan Drive PowerAI101ct 4 Fan Drive Volt ACAI102ct 4 Fan Drive AmpAI103ct 4 Fan Drive Speed ReferenceAI104ct 4 Fan Drive Speed FeedbackAI105ct 5 Fan Drive PowerAI106ct 5 Fan Drive Volt ACAI107ct 5 Fan Drive AmpAI108ct 5 Fan Drive Speed ReferenceAI109ct 5 Fan Drive Speed FeedbackAI110cw Pump 1 Run HoursAI111cw Pump 2 Run HoursAI112cw Pump 3 Run HoursAI113cw Pump 4 Run HoursAI114cw Pump 5 Run HoursAI115Cooling Tower 1 Fan Run HoursAI116Cooling Tower 2 Fan Run HoursAI117Cooling Tower 3 Fan Run HoursAI118Cooling Tower 4 Fan Run HoursAI119Cooling Tower 5 Fan Run HoursAI201cw Pump 1 Duty/Standby StatusAI202cw Pump 2 Duty/Standby StatusAI203cw Pump 3 Duty/Standby StatusAI204cw Pump 4 Duty/Standby StatusAI205cw Pump 5 Duty/Standby StatusAI206Cooling Tower 1 Duty StatusAI207Cooling Tower 2 Duty StatusAI208Cooling Tower 3 Duty StatusAI209Cooling Tower 4 Duty StatusAI210Cooling Tower 5 Duty StatusAI211cw Pump 1 Running StatusAI212cw Pump 2 Running StatusAI213cw Pump 3 Running StatusAI214cw Pump 4 Running StatusAI215cw Pump 5 Running StatusAI216Cooling Tower 1 Fan Running StatusAI217Cooling Tower 2 Fan Running StatusAI218Cooling Tower 3 Fan Running StatusAI219Cooling Tower 4 Fan Running StatusAI220Cooling Tower 5 Fan Running StatusAV1cw Pump 1 Mode/SelectorAV2cw Pump 2 Mode/SelectorAV3cw Pump 3 Mode/SelectorAV4cw Pump 4 Mode/SelectorAV5cw Pump 5 Mode/SelectorAV6Cooling Tower 1 Fan Mode/SelectorAV7Cooling Tower 2 Fan Mode/SelectorAV8Cooling Tower 3 Fan Mode/SelectorAV9Cooling Tower 4 Fan Mode/SelectorAV10Cooling Tower 5 Fan Mode/SelectorAO1cw Pump 1 Hand SpeedAO2cw Pump 2 Hand SpeedAO3cw Pump 3 Hand SpeedAO4cw Pump 4 Hand SpeedAO5cw Pump 5 Hand SpeedAO6Cooling Tower 1 Fan Hand SpeedAO7Cooling Tower 2 Fan Hand SpeedAO8Cooling Tower 3 Fan Hand SpeedAO9Cooling Tower 4 Fan Hand SpeedAO10Cooling Tower 5 Fan Hand Speed
Integration notes
- The data-points sheet titles the table BACnet but does not say whether it is BACnet IP or MS/TP.
- Mode/Selector AVs: 0 = Not Used, 1 = Hand, 2 = Off, 3 = Auto (writes limited to 1-3). Duty/standby, running status and valve position status AIs are coded; the codes are in each point's states.
- Units for temperatures, pressures and flows follow the controller's unit setting (the PDF lists the options).
- Some Speed Reference/Speed Feedback pairs share one range cell in the PDF; both are given 0-100 %.
- The PDF table is on pages 10-15.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Design Envelope Integrated Tower Controller (ITC 9521) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)
How many BACnet points does the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) have?
This list has 210 BACnet objects: 98 analog inputs, 10 analog outputs, 10 analog values, 68 binary inputs, 2 binary outputs, 22 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet points are writable?
44 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521) BACnet documentation?
The source is Design Envelope Integrated Tower Controller Data points (BACnet Communication Interface Rev 17.111) (82.21), revision 2018-07-17, published free by Armstrong Fluid Technology at https://armstrongfluidtechnology.com/~/media/documents/installation_maintenance_parts/installation-and-operating-instructions/82-21_designenvelope_itc9521_datapoints.pdf.
What are the minimum BACnet points to integrate the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)?
Start with BO 1 Remote Start (Start/stop from the BMS (1 = start)); BO 2 Alarm Reset (Reset alarms (positive edge)); BI 1 Plant Status (Controller on/off status); AI 1 Leaving Tower Water Temp (Condenser water leaving the towers); AI 2 Entering Tower Water Temp (Condenser water entering the towers); AI 3 Condenser Flow (Condenser water flow); AI 4 Outside Air Temp (Dry Bulb) (Outdoor dry-bulb temperature); BI 128 Cooling Tower Water Low Level Alarm (Tower basin low water level).
How do I enable BMS control of the Armstrong Fluid Technology Design Envelope Integrated Tower Controller (ITC 9521)?
BO 1 Remote Start (0 = Stop, 1 = Start) starts and stops the controller from the BMS. The data-points sheet says nothing more about local/remote selection.
How do I check these points on the real Design Envelope Integrated Tower Controller (ITC 9521)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Armstrong Fluid Technology BACnet points lists
- Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W10 chiller plant controller (water-cooled)
Armstrong EE-W10 water-cooled chilled water plant controls; the object list covers up to 3 chillers, 3 chilled water pumps, 3 condenser water pumps and 3 towers.
Also known as: EE-W10, EE-W 10, Armstrong EE-W10, 90.7651 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology EE-W20 chiller plant controller (water-cooled)
Armstrong EE-W20 water-cooled chilled water plant controls; the object list covers up to 5 chillers, 10 chilled water pumps, 10 condenser water pumps, 5 towers and 5 control zones.
Also known as: EE-W20, EE-W 20, Armstrong EE-W20, 90.7661 - Chiller plant controller (water-cooled chillers, pumps and towers)
Armstrong Fluid Technology IPC 9521 chilled water plant controller
Armstrong IPC 9521 water-cooled chilled water plant controls (legacy product); the object list covers up to 5 chillers, 5 chilled and 5 condenser water pumps (A and B sides), 5 towers and 5 zones.
Also known as: IPC 9521, IPC9521, Armstrong IPC 9521, 90.874 - Pump system controller (variable primary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable primary
Armstrong IPS 4000 controllers set up for variable primary pumping: up to 8 pumps, 16 control zones and 8 chillers or boilers with flow and differential pressure limits.
Also known as: IPS 4000, IPS4000, IPS 4000 primary, Integrated Pumping System 4000, 90.9751 - Pump system controller (variable secondary)
Armstrong Fluid Technology IPS 4000 pumping system controller - variable secondary
Armstrong IPS 4000 controllers set up for variable secondary pumping: up to 8 pumps and 16 control zones.
Also known as: IPS 4000, IPS4000, IPS 4000 secondary, Integrated Pumping System 4000, 90.9761 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A10 chiller plant controller
Armstrong SE-A10 chilled water plant controls with no condenser water side; the object list covers up to 3 chillers and 3 chilled water pumps.
Also known as: SE-A10, SE-A 10, Armstrong SE-A10, 90.7671 - Chiller plant controller (chillers and chilled water pumps)
Armstrong Fluid Technology SE-A20 chiller plant controller
Armstrong SE-A20 chilled water plant controls with no condenser water side; the object list covers up to 5 chillers, 10 chilled water pumps and 5 control zones.
Also known as: SE-A20, SE-A 20, Armstrong SE-A20, 90.7681
Source: Design Envelope Integrated Tower Controller Data points (BACnet Communication Interface Rev 17.111) · 82.21 · rev. 2018-07-17. Object names, instances and units are reproduced as published; descriptions are our own.