Make-up air unit controls (heating and ventilating unit) · BACnet points list

AbsolutAire UC-3 Lite control system (heating and ventilating) BACnet points list

Updated 12 November 2026

Short answer

The UC-3 Lite is AbsolutAire's simpler heat-and-vent unit controller, running the burner to a space or discharge temperature with optional VFD and mixed-air damper. It joins a BACnet MS/TP network with its MAC address set on DIP switches. The BMS turns the unit off, on or to auto with network_UnitEnableCommand, sets occupancy, mode and heat setpoints, and can send its own space temperature.

This page lists 50 BACnet objects for the AbsolutAire UC-3 Lite control system (heating and ventilating) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.

Manufacturer
AbsolutAire
Model
UC-3 Lite control system (heating and ventilating)
Equipment
Make-up air unit controls (heating and ventilating unit)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
50 (17 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3640 followed by the MAC address (MAC 25 = 364025)
Also known as
UC-3 Lite, UC-3 LITE, Smart-Vue, UC-3 Lite User Guide 091121
Source document
UC-3 Lite User Guide - Network Integration / Network Points List · UC-3 Lite User Guide 091121
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.

BMS integration notes: AbsolutAire UC-3 Lite control system (heating and ventilating)

Integration in brief

Use network_UnitEnableCommand (the guide marks it as the point to command the unit on and off) with OFF, ON or AUTO, then set occupancy, HVAC mode and the occupied/unoccupied heat setpoints. If the BMS supplies the space temperature, write network_SpaceTemperatureOverride (255 returns control to the local sensor). Watch fan and burner status and the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 11network_UnitEnableCommandUnit command: OFF / ON / AUTOWrite
BV 11network_OccupancyCommand0 occupied, 1 unoccupiedWrite
BV 12network_HVAC_Mode0 vent, 1 heatWrite
AV 26network_OccupiedHeatSetPointOccupied heat setpoint, 55-150 °FWrite
AV 33network_SpaceTemperatureOverrideSpace temp from the BMS; 255 = use local sensorWrite
BV 1FanStatusFan running statusRead
BV 23BurnerStatusBurner on/off statusRead
AV 3DischargeTemperatureDischarge air temperatureRead
BV 4BurnerLockoutAlarmBurner lockoutRead
BV 8MotorNotRespondingAlarmFan motor did not startRead

Enable & remote start

network_UnitEnableCommand (MV 11): OFF / ON / AUTO. The guide marks it as the point to command the unit on and off; AUTO cycles the unit per BV 14 and BV 15.

Sensors & values from the BMS

network_SpaceTemperatureOverride (AV 33) replaces the local space sensor with an averaged or network temperature; write 255 to go back to the local sensor. AV 6 shows the value in use.

Network setup

Watch out for

AbsolutAire UC-3 Lite control system (heating and ventilating) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

50 of 50 shown
Type
AnalogBinaryMulti-state
Access
Show
AbsolutAire UC-3 Lite control system (heating and ventilating) BACnet Points List
DescriptionStates
AV1UnitDesignTempRiseUnit design temperature rise (factory configuration)°FRead
AV2SpaceTemperatureSensorSpace temperature (local sensor)°FRead
AVmin3DischargeTemperatureDischarge temperature°FRead
AV4OutsideTemperatureOutside temperature°FRead
AV5BurnerCommandBurner modulation command%Read
AV6ControlSpaceTemperatureSpace temperature in use (AV 2, or AV 33 when overridden)°FRead
AV7Custom RA PercentCustom return air percent (factory configuration)%Read
AV8Custom OA PercentCustom outside air percent (factory configuration)%Read
AVmin26network_OccupiedHeatSetPointOccupied heat setpoint (55-150 °F)°FWrite
AV27network_UnoccupiedHeatSetPointUnoccupied heat setpoint (55-150 °F)°FWrite
AV28network_MinimumDischargeTempMinimum discharge temperature (45-90 °F)°FWrite
AV29network_MaximumDischargeTempMaximum discharge temperature (up to 150 °F)°FWrite
AV30network_HeatLockoutSetPointHeat lockout: burner off above this OA temperature°FWrite
AV31network_LowTempAlarmSetPointLow temperature lockout alarm setpoint (35-70 °F)°FWrite
AV32network_LowTempAlarmDelayTimeLow temperature alarm delay (2-15 min)minWrite
AVmin33network_SpaceTemperatureOverrideSpace temperature from the network (255 = use local sensor)°FWrite
AV34network_VFD_SpeedCommandVFD speed command (VFD units only)%Write
AV35network_DamperCommandMixed air damper command (return air units only)%Write
BVmin1FanStatusUnit fan statusReadBoolean (ON;OFF)
BV2UseSpaceSensorHMIUse local space sensor (factory configuration)ReadBoolean (YES;NO)
BV3Use_LTLLow temperature lockout feature fitted (factory configuration)ReadBoolean (YES;NO)
BVmin4BurnerLockoutAlarmBurner lockout alarmReadBoolean (LOCKOUT;NORMAL)
BV5DirtyFilterAlarmDirty filter alarmReadBoolean (ALARM;NORMAL)
BV6UnitEnableStatusUnit enable statusReadBoolean (ENABLE;OFF)
BV7BurnerEnableStatusBurner enable statusReadBoolean (ENABLE;OFF)
BVmin8MotorNotRespondingAlarmFan motor not responding alarmReadBoolean (ALARM;NORMAL)
BV9BurnerNotRespondingAlarmBurner not responding alarmReadBoolean (ALARM;NORMAL)
BV10BurnerWatchdogAlarmBurner watchdog alarmReadBoolean (ALARM;NORMAL)
BVmin11network_OccupancyCommandOccupancy commandWrite0=Occupied, 1=Unoccupied
BVmin12network_HVAC_ModeHVAC mode commandWrite0=Vent (summer), 1=Heat (winter)
BV13network_ControlTypeControl typeWrite0=Space, 1=Discharge
BV14network_CycleWhenOccupiedCycle to space setpoint when occupiedWriteBoolean (YES;NO)
BV15network_CycleWhenUnoccupiedCycle to space setpoint when unoccupiedWriteBoolean (YES;NO)
BV16HardwareOutput_1_OverrideAlarmNetwork override alarm, hardware output 1ReadBoolean (ALARM;NORMAL)
BV17HardwareOutput_2_OverrideAlarmNetwork override alarm, hardware output 2ReadBoolean (ALARM;NORMAL)
BV18HardwareOutput_3_OverrideAlarmNetwork override alarm, hardware output 3ReadBoolean (ALARM;NORMAL)
BV19HardwareOutput_4_OverrideAlarmNetwork override alarm, hardware output 4ReadBoolean (ALARM;NORMAL)
BV20HardwareOutput_6_OverrideNetwork override alarm, hardware output 6ReadBoolean (ALARM;NORMAL)
BV21HardwareOutput_8_OverrideAlarmNetwork override alarm, hardware output 8ReadBoolean (ALARM;NORMAL)
BV22LowDischargeTempAlarmLow discharge temperature alarm (unit off then on to reset)ReadBoolean (ALARM;NORMAL)
BVmin23BurnerStatusBurner statusReadBoolean (ON;OFF)
BV24network_BurnerResetCommandBurner reset (toggle the state to reset)WriteBoolean (RESET;_RESET)
BV25Use_VFDUnit has a VFD (factory configuration)ReadBoolean (YES;NO)
BV26Use_CO2_DetectorUnit has a CO2 contact (factory configuration)ReadBoolean (YES;NO)
MV1SpaceSensorAlarmSpace temperature sensor alarmReadSENSOR RELIABILITY enumeration
MV2DischargeSensorAlarmDischarge temperature sensor alarmReadSENSOR RELIABILITY enumeration
MV3OutsideSensorAlarmOutside temperature sensor alarmReadSENSOR RELIABILITY enumeration
MV4Unit OA PercentUnit design OA (factory configuration)ReadConfig OA Percent enumeration
MV5ReturnSensorAlarmReturn temperature sensor alarmReadSENSOR RELIABILITY enumeration
MVmin11network_UnitEnableCommandUnit enable command (OFF / ON / AUTO)WriteUNIT ENABLE enumeration (OFF/ON/AUTO)
Object ID lookup: AbsolutAire UC-3 Lite control system point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UC-3 Lite control system (heating and ventilating) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AbsolutAire UC-3 Lite control system (heating and ventilating)

How many BACnet points does the AbsolutAire UC-3 Lite control system (heating and ventilating) have?

This list has 50 BACnet objects: 18 analog values, 26 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AbsolutAire UC-3 Lite control system (heating and ventilating) BACnet points are writable?

17 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AbsolutAire UC-3 Lite control system (heating and ventilating) BACnet documentation?

The source is UC-3 Lite User Guide - Network Integration / Network Points List (UC-3 Lite User Guide 091121), published free by AbsolutAire at https://www.absolutaire.com/wp-content/uploads/uc-3_lite_user_guide.pdf.

What are the minimum BACnet points to integrate the AbsolutAire UC-3 Lite control system (heating and ventilating)?

Start with MV 11 network_UnitEnableCommand (Unit command: OFF / ON / AUTO); BV 11 network_OccupancyCommand (0 occupied, 1 unoccupied); BV 12 network_HVAC_Mode (0 vent, 1 heat); AV 26 network_OccupiedHeatSetPoint (Occupied heat setpoint, 55-150 °F); AV 33 network_SpaceTemperatureOverride (Space temp from the BMS; 255 = use local sensor); BV 1 FanStatus (Fan running status); BV 23 BurnerStatus (Burner on/off status); AV 3 DischargeTemperature (Discharge air temperature); BV 4 BurnerLockoutAlarm (Burner lockout); BV 8 MotorNotRespondingAlarm (Fan motor did not start).

How do I enable BMS control of the AbsolutAire UC-3 Lite control system (heating and ventilating)?

network_UnitEnableCommand (MV 11): OFF / ON / AUTO. The guide marks it as the point to command the unit on and off; AUTO cycles the unit per BV 14 and BV 15.

Can the BMS supply sensor values to the AbsolutAire UC-3 Lite control system (heating and ventilating)?

network_SpaceTemperatureOverride (AV 33) replaces the local space sensor with an averaged or network temperature; write 255 to go back to the local sensor. AV 6 shows the value in use.

How do I check these points on the real UC-3 Lite control system (heating and ventilating)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AbsolutAire BACnet points lists

Source: UC-3 Lite User Guide - Network Integration / Network Points List · UC-3 Lite User Guide 091121. Object names, instances and units are reproduced as published; descriptions are our own.