Make-up air / heating and ventilating unit controller · BACnet points list

AbsolutAire TC-3 control system BACnet points list

Updated 6 November 2026

Short answer

The TC-3 is a smaller unit controller for AbsolutAire heating and ventilating units with burner control, OA/RA dampers and optional 0-10 V setpoint input. It joins a BACnet MS/TP network with a device instance built from its DIP-switch MAC address. The BMS writes network unit and burner enables, occupancy, heat setpoints and an optional network space temperature, and reads temperatures, burner command and sensor alarms.

This page lists 26 BACnet objects for the AbsolutAire TC-3 control system — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.

Manufacturer
AbsolutAire
Model
TC-3 control system
Equipment
Make-up air / heating and ventilating unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
26 (9 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3640 followed by the MAC address (e.g. MAC 25 = 364025)
Also known as
TC-3, Smart-Vue
Source document
TC-3 User Guide - Network Integration / Network Points List · TC-3 User Guide 091621
Download CSV 26 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.

BMS integration notes: AbsolutAire TC-3 control system

Integration in brief

Write network_UnitEnable (BV 47) and network_BurnerEnable (BV 48) to run the unit, network_Occupancy (AV 84) for occupancy and the heat setpoints (AV 82/85). Writing 255 to AV 84 returns to the local schedule and 255 to AV 83 releases the network space temperature. Read discharge and space temperatures, the burner command and the sensor alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 47network_UnitEnableUnit enable from the BMSWrite
BV 48network_BurnerEnableBurner enable from the BMSWrite
AV 84network_OccupancyOccupancy: 0=Occ, 1=Unocc, 255=scheduleWrite
AV 82network_OccHeatSetPointOccupied heat setpoint, 55-150 °FWrite
AV 27DischargeTemperatureDischarge air temperatureRead
AV 24SpaceTemperatureSpace temperatureRead
AV 30BurnerOutputCommandBurner command, %Read
MV 3DischargeSensorAlarmDischarge sensor faultRead

Enable & remote start

BV 47 network_UnitEnable and BV 48 network_BurnerEnable start the unit and burner; they are only used when the factory settings BV 5 UseFanEnable and BV 6 UseBurnerEnable are YES.

Sensors & values from the BMS

AV 83 network_SpaceTemperature replaces the local space sensor; write 255 for null (use local). AV 84 network_Occupancy overrides the schedule (255 = local schedule).

Network setup

Watch out for

AbsolutAire TC-3 control system BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

26 of 26 shown
Type
AnalogBinaryMulti-state
Access
Show
AbsolutAire TC-3 control system BACnet Points List
DescriptionStates
AVmin24SpaceTemperatureCurrent space temperature°FRead
AV25OutsideTemperatureCurrent outside temperature°FRead
AV26ReturnTemperatureCurrent return air temperature°FRead
AVmin27DischargeTemperatureCurrent discharge air temperature°FRead
AVmin30BurnerOutputCommandCurrent burner command%Read
AVmin82network_OccHeatSetPointOccupied heat setpoint, 55-150 °F°FWrite
AV83network_SpaceTemperatureNetwork space temperature; 255 = null (use local)°FWrite
AVmin84network_OccupancyOccupancy: 0=Occupied, 1=Unoccupied, 255 = local schedule°FWrite
AV85network_UnoccHeatSetPointUnoccupied heat setpoint, 55-150 °F°FWrite
AV88network_MinimumDischargeMinimum discharge temperature (default 55 °F)°FWrite
AV89network_MaximumDischargeMaximum discharge temperature (default 90 °F)°FWrite
BV1SpaceSensorTypeFactory config, do not write: 0=HMI, 1=Remote wiredReadActive=Remote Wired, Inactive=HMI
BV2SetPointConfigFactory config, do not write: 0=HMI, 1=VDCReadActive=VDC, Inactive=HMI
BV3IsSchedAvailableFactory config, do not write: scheduling availableReadActive=YES, Inactive=NO
BV4UseCO2_DetectorFactory config, do not write: CO2 detector usedReadActive=YES, Inactive=NO
BV5UseFanEnableFactory config, do not write: use network fan enable pointReadActive=YES, Inactive=NO
BV6UseBurnerEnableFactory config, do not write: use network burner enable pointReadActive=YES, Inactive=NO
BV44network_ControlTypeControl type: 0=Discharge, 1=SpaceWriteActive=Space, Inactive=Discharge
BVmin47network_UnitEnableNetwork unit enableWriteActive=On, Inactive=Off
BVmin48network_BurnerEnableNetwork burner enableWriteActive=On, Inactive=Off
MV1OA_PercentFactory config, do not write: outside air 1=100 %, 2=20 %, 3=15 %Read1=100, 2=20, 3=15
MVmin3DischargeSensorAlarmDischarge temperature sensor alarm (enum SensorReliability)Read
MV4SpaceSensorAlarmSpace temperature sensor alarm (enum SensorReliability)Read
MV5OutsideSensorAlarmOutside temperature sensor alarm (enum SensorReliability)Read
MV6ReturnSensorAlarmReturn temperature sensor alarm (enum SensorReliability)Read
MV8DamperFeedbackAlarmDamper feedback alarm (enum SensorReliability)Read
Object ID lookup: AbsolutAire TC-3 control system point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TC-3 control system and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AbsolutAire TC-3 control system

How many BACnet points does the AbsolutAire TC-3 control system have?

This list has 26 BACnet objects: 11 analog values, 9 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AbsolutAire TC-3 control system BACnet points are writable?

9 of the 26 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AbsolutAire TC-3 control system BACnet documentation?

The source is TC-3 User Guide - Network Integration / Network Points List (TC-3 User Guide 091621), published free by AbsolutAire at https://absolutaire.com/sites/default/files/public/pdfs/tc-3_user_guide.pdf.

What are the minimum BACnet points to integrate the AbsolutAire TC-3 control system?

Start with BV 47 network_UnitEnable (Unit enable from the BMS); BV 48 network_BurnerEnable (Burner enable from the BMS); AV 84 network_Occupancy (Occupancy: 0=Occ, 1=Unocc, 255=schedule); AV 82 network_OccHeatSetPoint (Occupied heat setpoint, 55-150 °F); AV 27 DischargeTemperature (Discharge air temperature); AV 24 SpaceTemperature (Space temperature); AV 30 BurnerOutputCommand (Burner command, %); MV 3 DischargeSensorAlarm (Discharge sensor fault).

How do I enable BMS control of the AbsolutAire TC-3 control system?

BV 47 network_UnitEnable and BV 48 network_BurnerEnable start the unit and burner; they are only used when the factory settings BV 5 UseFanEnable and BV 6 UseBurnerEnable are YES.

Can the BMS supply sensor values to the AbsolutAire TC-3 control system?

AV 83 network_SpaceTemperature replaces the local space sensor; write 255 for null (use local). AV 84 network_Occupancy overrides the schedule (255 = local schedule).

How do I check these points on the real TC-3 control system?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AbsolutAire BACnet points lists

Source: TC-3 User Guide - Network Integration / Network Points List · TC-3 User Guide 091621. Object names, instances and units are reproduced as published; descriptions are our own.