Make-up air / heating and ventilating unit controller · BACnet points list

AbsolutAire UC-3 control system BACnet points list

Updated 6 November 2026

Short answer

The UC-3 is the unit controller on AbsolutAire heating and ventilating units. It joins a BACnet MS/TP network with a device instance built from its DIP-switch MAC address. The BMS writes network_ values for on/off, occupancy, setpoints, economizer and sensor overrides, and reads temperatures, commands, fan/burner status and alarm objects. The IC-3 user guide prints the identical points table.

This page lists 65 BACnet objects for the AbsolutAire UC-3 control system — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.

Manufacturer
AbsolutAire
Model
UC-3 control system
Equipment
Make-up air / heating and ventilating unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
65 (26 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3640 followed by the MAC address (e.g. MAC 25 = 364025)
Also known as
UC-3, IC-3, IC-3 control system, Smart-Vue
Source document
UC-3 User Guide - Network Integration / Network Points List · UC-3 User Guide 110921
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.

BMS integration notes: AbsolutAire UC-3 control system

Integration in brief

Write network_FanCommand (AV 103) to turn the unit on/off, network_Occupancy (AV 134) for occupancy, and the heat/cool setpoints (AV 102-106). Writing 255 to the network space temperature, building pressure or occupancy objects hands control back to the unit's own sensors or schedule. Read fan and burner status (BV 21/22) and the alarm multistates.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 103network_FanCommandOn/off command: 0=Off, 1=On, 2=AutoWrite
AV 134network_OccupancyOccupancy: 0=Occ, 1=Unocc, 255=scheduleWrite
AV 102network_OccHeatSetPointOccupied heat setpoint, 55-90 °FWrite
AV 105network_OccCoolSetPointOccupied cool setpoint, 55-90 °FWrite
BV 21Fan Running StatusSupply fan runningRead
BV 22Burner Operating StatusBurner onRead
AV 54DischargeTemperatureDischarge air temperatureRead
AV 51SpaceTemperatureSpace temperatureRead
MV 37BurnerLockoutAlarmBurner lockout alarmRead
MV 39MotorNotRespondingAlarmFan motor failed to startRead

Enable & remote start

AV 103 network_FanCommand is the point the guide says to use to command the unit on and off (0 = Off, 1 = On, 2 = Auto).

Sensors & values from the BMS

AV 132 network_SpaceTemperature and AV 133 network_BuildingPressure override the local sensors; write 255 to return to the local sensor. AV 134 network_Occupancy overrides the schedule (255 = schedule).

Network setup

Watch out for

AbsolutAire UC-3 control system BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
AnalogBinaryMulti-state
Access
Show
AbsolutAire UC-3 control system BACnet Points List
DescriptionStates
AV4ActiveCoolingStagesNumber of active cooling stagesRead
AV5Cooling Coil Temperature SensorCooling coil leaving air temperature°FRead
AVmin51SpaceTemperatureCurrent space temperature°FRead
AV52OutsideTemperatureCurrent outside temperature°FRead
AV53ReturnTemperatureCurrent return air temperature°FRead
AVmin54DischargeTemperatureCurrent discharge air temperature°FRead
AV55BuildingPressureCurrent building pressureinH2ORead
AV56EconomizerCommandCurrent economizer command%Read
AV57HeatCommandCurrent heat (burner) command%Read
AV58Cooling CommandCurrent cooling command%Read
AVmin102network_OccHeatSetPointOccupied heat setpoint, 55-90 °F°FWrite
AVmin103network_FanCommandUnit on/off command: 0=Off, 1=On, 2=AutoWrite
AV104network_UnoccHeatSetPointUnoccupied heat setpoint, 55-90 °F°FWrite
AVmin105network_OccCoolSetPointOccupied cool setpoint, 55-90 °F°FWrite
AV106network_UnoccCoolSetPointUnoccupied cool setpoint, 55-90 °F°FWrite
AV107network_BuiildingPressSetPointBuilding pressure setpoint, -0.1 to 0.1 in. w.c.inH2OWrite
AV108network_EconomizerOverrideEconomizer override 0-100 %, 255 = auto%Write
AV109network_ManualEconPercentManual economizer 0-100 %; not with building pressure option%Write
AV110network_TwoSpeedEconTwo-speed economizer: 0=Low, 1=HighWrite
AV111network_HeatCoolModeMode: 0=Air, 1=Heat, 2=Cool (units with cooling)Write
AV112network_HeatVentModeMode: 0=Vent, 1=Heat (units without cooling)Write
AV113network_HeatLockoutHeat lockout setpoint (default 65 °F)°FWrite
AV114network_CoolLockoutCooling lockout setpoint (default 75 °F)°FWrite
AV115network_LowTempLimitLow temperature alarm setpoint (default 40 °F)°FWrite
AV116network_LowTempTimeLow temperature alarm delay (default 5 min)minWrite
AV118network_MinimumDischargeMinimum discharge temperature (default 55 °F)°FWrite
AV119network_MaximumDischargeMaximum discharge temperature (default 90 °F)°FWrite
AV122network_LowEconomizerEconomizer low limit (default 0 %)%Write
AV123network_HighEconomizerEconomizer high limit (default 100 %)%Write
AV131network_BurnerResetBurner reset command (toggle on)Write
AV132network_SpaceTemperatureNetwork space temperature; 255 = use local sensor°FWrite
AV133network_BuildingPressureNetwork building pressure; 255 = use local sensorinH2OWrite
AVmin134network_OccupancyOccupancy: 0=Occupied, 1=Unoccupied, 255 = scheduleWrite
BV16CoolingStage_1Cooling stage 1 statusReadActive=On, Inactive=Off
BV17CoolingStage_2Cooling stage 2 statusReadActive=On, Inactive=Off
BV18CoolingStage_3Cooling stage 3 statusReadActive=On, Inactive=Off
BV19CoolingStage_4Cooling stage 4 statusReadActive=On, Inactive=Off
BVmin21Fan Running StatusUnit fan statusReadActive=On, Inactive=Off
BVmin22Burner Operating StatusUnit burner statusReadActive=On, Inactive=Off
BV51network_ControlTypeControl type: 0=Discharge, 1=SpaceWriteActive=Space, Inactive=Discharge
BV52network_CycleOccupiedCycle on space temperature when occupiedWriteActive=YES, Inactive=NO
BV53network_CycleUnoccupiedCycle on space temperature when unoccupiedWriteActive=YES, Inactive=NO
BV54HardwareOutput_1_OverrideHardware output 1 overridden from the networkReadActive=Alarm, Inactive=Normal
BV55HardwareOutput_2_OverrideHardware output 2 overridden from the networkReadActive=Alarm, Inactive=Normal
BV56HardwareOutput_3_OverrideHardware output 3 overridden from the networkReadActive=Alarm, Inactive=Normal
BV57HardwareOutput_4_OverrideHardware output 4 overridden from the networkReadActive=Alarm, Inactive=Normal
BV58HardwareOutput_5_OverrideHardware output 5 overridden from the networkReadActive=Alarm, Inactive=Normal
BV59HardwareOutput_6_OverrideHardware output 6 overridden from the networkReadActive=Alarm, Inactive=Normal
BV60HardwareOutput_7_OverrideHardware output 7 overridden from the networkReadActive=Alarm, Inactive=Normal
BV61HardwareOutput_8_OverrideHardware output 8 overridden from the networkReadActive=Alarm, Inactive=Normal
BV62HardwareOutput_9_OverrideHardware output 9 overridden from the networkReadActive=Alarm, Inactive=Normal
BV63HardwareOutput_10_OverrideHardware output 10 overridden from the networkReadActive=Alarm, Inactive=Normal
BV64HardwareOutput_11_OverrideHardware output 11 overridden from the networkReadActive=Alarm, Inactive=Normal
BV65HardwareOutput_12_OverrideHardware output 12 overridden from the networkReadActive=Alarm, Inactive=Normal
MV31DirtyFilterAlarmDirty filter alarm (enum Filters)Read
MV32Low_TempAlarmLow temperature alarmReadAlarm / Normal
MV33DischargeSensorAlarmDischarge sensor alarm (enum SensorReliability)Read
MV34SpaceSensorAlarmSpace sensor alarm (enum SensorReliability)Read
MV35OutsideSensorAlarmOutside sensor alarm (enum SensorReliability)Read
MV36ReturnSensorAlarmReturn sensor alarm (enum SensorReliability)Read
MVmin37BurnerLockoutAlarmBurner lockout alarmReadAlarm / Normal
MV38DamperFeedbackAlarmDamper feedback alarm (enum SensorReliability)Read
MVmin39MotorNotRespondingAlarmSupply fan motor not responding alarmReadAlarm / Normal
MV40BurnerNotRespondingAlarmBurner not responding alarmReadAlarm / Normal
MV41CoolingCoilExitSensorAlarmCooling coil sensor alarm (enum SensorReliability)Read
Object ID lookup: AbsolutAire UC-3 control system point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UC-3 control system and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AbsolutAire UC-3 control system

How many BACnet points does the AbsolutAire UC-3 control system have?

This list has 65 BACnet objects: 33 analog values, 21 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AbsolutAire UC-3 control system BACnet points are writable?

26 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AbsolutAire UC-3 control system BACnet documentation?

The source is UC-3 User Guide - Network Integration / Network Points List (UC-3 User Guide 110921), published free by AbsolutAire at https://absolutaire.com/sites/default/files/public/pdfs/uc_3_user_guide.pdf.

What are the minimum BACnet points to integrate the AbsolutAire UC-3 control system?

Start with AV 103 network_FanCommand (On/off command: 0=Off, 1=On, 2=Auto); AV 134 network_Occupancy (Occupancy: 0=Occ, 1=Unocc, 255=schedule); AV 102 network_OccHeatSetPoint (Occupied heat setpoint, 55-90 °F); AV 105 network_OccCoolSetPoint (Occupied cool setpoint, 55-90 °F); BV 21 Fan Running Status (Supply fan running); BV 22 Burner Operating Status (Burner on); AV 54 DischargeTemperature (Discharge air temperature); AV 51 SpaceTemperature (Space temperature); MV 37 BurnerLockoutAlarm (Burner lockout alarm); MV 39 MotorNotRespondingAlarm (Fan motor failed to start).

How do I enable BMS control of the AbsolutAire UC-3 control system?

AV 103 network_FanCommand is the point the guide says to use to command the unit on and off (0 = Off, 1 = On, 2 = Auto).

Can the BMS supply sensor values to the AbsolutAire UC-3 control system?

AV 132 network_SpaceTemperature and AV 133 network_BuildingPressure override the local sensors; write 255 to return to the local sensor. AV 134 network_Occupancy overrides the schedule (255 = schedule).

How do I check these points on the real UC-3 control system?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AbsolutAire BACnet points lists

Source: UC-3 User Guide - Network Integration / Network Points List · UC-3 User Guide 110921. Object names, instances and units are reproduced as published; descriptions are our own.