Make-up air unit controls (discharge temperature and humidity) · BACnet points list

AbsolutAire PC-3 / LC-3 psychrometric control system BACnet points list

Updated 12 November 2026

Short answer

The PC-3 user guide covers AbsolutAire's psychrometric controls package (the preface calls it LC-3), which holds discharge temperature and humidity by cooling to a dew point and reheating, with optional humidification and VFD airflow control. The controller joins a BACnet MS/TP network, finds the baud rate itself and takes its MAC address from DIP switches. The BMS can switch the unit on and off and write discharge temperature, humidity and airflow setpoints.

This page lists 44 BACnet objects for the AbsolutAire PC-3 / LC-3 psychrometric control system — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AbsolutAire’s own free documentation, linked below.

Manufacturer
AbsolutAire
Model
PC-3 / LC-3 psychrometric control system
Equipment
Make-up air unit controls (discharge temperature and humidity)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
44 (16 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
3640 followed by the MAC address (MAC 25 = 364025)
Also known as
PC-3, LC-3, LC-3 Psychrometric Controls Package, Smart-Vue, PC-3 User Guide 010220
Source document
PC-3 User Guide - Network Integration · PC-3 User Guide 010220
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AbsolutAire’s current documentation and the live device before use. Not official AbsolutAire information. Terms of use.

BMS integration notes: AbsolutAire PC-3 / LC-3 psychrometric control system

Integration in brief

Set the MAC address on the DIP switches and connect to the BACnet MS/TP trunk; the controller detects the baud rate after a power cycle and its device instance becomes 3640 followed by the MAC. Command the unit with network_FanCommand and write the discharge temperature and humidity setpoints; read the discharge conditions, command outputs and the multistate alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 22network_FanCommandUnit on/off commandWrite
AV 52network_TempSetPointDischarge temperature setpoint, °FWrite
AV 53network_HumiditySetPointDischarge humidity setpoint, %RHWrite
AV 54network_CFM_SetPointDischarge airflow setpoint, CFM (airflow option)Write
AV 40DischargeTemperatureDischarge air temperatureRead
AV 41DischargeHumidityDischarge air humidityRead
AV 36OutsideTemperatureOutside air temperatureRead
MV 9MotorNotRespondingAlarmFan did not start within 2 min of a run commandRead
MV 7PreheatBurnerLockoutAlarmPreheat burner lockoutRead
MV 2LowTempAlarmLow temperature alarmRead

Enable & remote start

network_FanCommand (BV 22) turns the unit on and off from the BMS.

Network setup

Watch out for

AbsolutAire PC-3 / LC-3 psychrometric control system BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

44 of 44 shown
Type
AnalogBinaryMulti-state
Access
Show
AbsolutAire PC-3 / LC-3 psychrometric control system BACnet Points List
DescriptionStates
AVmin36OutsideTemperatureOutside Temperature°FRead
AV37OutsideHumidityOutside Air Humidity%RHRead
AV38CoilExitTemperatureCoil Exit Temperature°FRead
AV39PreheatExitTemperaturePreheat exit temperature°FRead
AVmin40DischargeTemperatureDischarge Air Temperature°FRead
AVmin41DischargeHumidityDischarge Humidity%RHRead
AV42DischargeAirflowCFMDischarge Airflow CFMCFMRead
AV43CoolingCommandCooling command, %%Read
AV44PreheatCommandPreheat Command Percent%Read
AV45HumiditficationCommandHumidification command, %%Read
AV46ReheatCommandReheat Command Percent%Read
AV47ControlHysteresisTemperature control hysteresis°FWrite
AV48BuildingPressureSetPointBuilding pressure set point for controlinWCWrite
AV49BuildingPressureSensorBuilding pressure sensorinWCRead
AV50network_MinimumEconomizer_VFDMinimum VFD speed or OA percent%Write
AV51network_MazimumEconomizer_VFDMaximum VFD speed or OA percent%Write
AVmin52network_TempSetPointDischarge Temperature Set Point°FWrite
AVmin53network_HumiditySetPointDischarge Humidity Set Point%RHWrite
AVmin54network_CFM_SetPointDischarge airflow setpointCFMWrite
AV55network_VFD_Econ_SetPointManual VFD speed setpoint (null = automatic)%Write
AV56network_PreHeatBurnerResetPreheat burner reset (toggle to reset)Write
AV57network_ReHeatBurnerResetReheat burner reset (toggle to reset)Write
AV58network_LowTempSetPointLow Temp Alarm Set Point°FWrite
AV59network_LowTempDelayTimeLow temperature alarm delayminWrite
AV60network_MinimumDischargeTempMinimum Discharge Temperature°FWrite
AV61network_MaximumDischargeTempMaximum Discharge Temperature°FWrite
AV62EFF_SpaceTemperatureCurrent Space Temperature°FRead
AV63EFF_SpaceHumidityCurrent Space Humidity%RHRead
BV21ControlTypeSpace or discharge controlWriteEnumeration (SPACE;DISCHARGE) - see notes
BVmin22network_FanCommandUnit on/off commandWrite0=Off, 1=On
MV1DirtyPreFitlerAlarmDirty pre-filter alarmReadEnumeration: Filters
MVmin2LowTempAlarmLow Temp AlarmReadEnumeration: Alarm / Normal
MV5OutsideTempSensorAlarmOutside Temp Sensor AlarmReadEnumeration: SensorReliability
MV6OutsideHumiditySensorAlarmOutside Humidity Sensor AlarmReadEnumeration: SensorReliability
MVmin7PreheatBurnerLockoutAlarmPreheat burner lockout alarmReadEnumeration: Alarm / Normal
MVmin9MotorNotRespondingAlarmFan motor not responding alarmReadEnumeration: Alarm / Normal
MV21DirtyFinalFilterAlarmDirty final filter alarmReadEnumeration: Filters
MV22CoilExitTempSensorAlarmCoil Exit Sensor AlarmReadEnumeration: SensorReliability
MV23PreheatTempSensorAlarmPreheat Sensor AlarmReadEnumeration: SensorReliability
MV24DischargeTempSensorAlarmDischarge Temp Sensor AlarmReadEnumeration: SensorReliability
MV25ReturnTempSensorAlarmReturn temperature sensor alarmReadEnumeration: SensorReliability
MV26DischargeHumiditySensorAlarmDischarge Humidity Sensor AlarmReadEnumeration: SensorReliability
MV27ReturnHumiditySensorAlarmReturn humidity sensor alarmReadEnumeration: SensorReliability
MV28ReheatBurnerLockoutAlarmReheat burner lockout alarmReadEnumeration: Lockout / Normal
Object ID lookup: AbsolutAire PC-3 / LC-3 psychrometric control system point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PC-3 / LC-3 psychrometric control system and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AbsolutAire PC-3 / LC-3 psychrometric control system

How many BACnet points does the AbsolutAire PC-3 / LC-3 psychrometric control system have?

This list has 44 BACnet objects: 28 analog values, 2 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AbsolutAire PC-3 / LC-3 psychrometric control system BACnet points are writable?

16 of the 44 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AbsolutAire PC-3 / LC-3 psychrometric control system BACnet documentation?

The source is PC-3 User Guide - Network Integration (PC-3 User Guide 010220), published free by AbsolutAire at https://www.absolutaire.com/wp-content/uploads/pc_3_users_guide.pdf.

What are the minimum BACnet points to integrate the AbsolutAire PC-3 / LC-3 psychrometric control system?

Start with BV 22 network_FanCommand (Unit on/off command); AV 52 network_TempSetPoint (Discharge temperature setpoint, °F); AV 53 network_HumiditySetPoint (Discharge humidity setpoint, %RH); AV 54 network_CFM_SetPoint (Discharge airflow setpoint, CFM (airflow option)); AV 40 DischargeTemperature (Discharge air temperature); AV 41 DischargeHumidity (Discharge air humidity); AV 36 OutsideTemperature (Outside air temperature); MV 9 MotorNotRespondingAlarm (Fan did not start within 2 min of a run command); MV 7 PreheatBurnerLockoutAlarm (Preheat burner lockout); MV 2 LowTempAlarm (Low temperature alarm).

How do I enable BMS control of the AbsolutAire PC-3 / LC-3 psychrometric control system?

network_FanCommand (BV 22) turns the unit on and off from the BMS.

How do I check these points on the real PC-3 / LC-3 psychrometric control system?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AbsolutAire BACnet points lists

Source: PC-3 User Guide - Network Integration · PC-3 User Guide 010220. Object names, instances and units are reproduced as published; descriptions are our own.